DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS Page 1 of 124 DISTRIBUTED CONTROL SYSTEM (DCS)/ PROCESS CONTROL SYSTEM (PCS) SPECIFICATION For DAROU-1 SULHURIC ACID PLANT AND ITS UTILITY ICS INDORAMA SENEGAL – WEST AFRICA All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS Page 2 of 124 INDEX SR. NO. TOPIC 1.0 Scope 2.0 ABBREVIATIONS Used in this document 3.0 Control and Safeguarding Systems Objectives 4.0 Control and Operation philosophy 5.0 EQUIPMENT LOCATIONS 6.0 SYSTEMS INTEGRATION /FORIGEN INTERFACE 7.0 FIELD INTERFACE 8.0 POWER SUPPLY 9.0 ALARM MANAGEMENT 10.0 CONTROL AND SAFEGUARDING DESIGN CRITERIA 11.0 DCS DESIGN CRITERIA 12.0 SYSTEM OVERVIEW 13.0 FUNCTIONAL SPECIFICATIONS 14.0 BOUGHT OUT ITEMS INCLUDED IN VENDOR’S SCOPE OF SUPPLY 15.0 INSPECTION 16.0 TEST SET-UP REQUIREMENTS 17.0 INSTALLATION PRE-COMMISSIONING AND COMMISSIONING 18.0 FINAL ACCEPTANCE AND WARRANTY 19.0 TRAINING 20.0 SPARES PHILOSOPHY AND CONSUMABLES 21.0 INFORMATION REQUIRED WITH THE BID 22.0 DOCUMENTATION REQUIREMENTS ANNEXURE-I IO LIST ANNEXURE-II I/O LIST AND BOM QUOTED BY DIFFERENT VENDORS ANNEXURE-III APPLICABLE HARDWARE UNIT RATES FOR ADDITION / DELETION ANNEXURE-IV BIDDER to fill in the complete form for technical comparison purpose ANNEXURE-V ARCHITECTURE All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS Page 3 of 124 1. Scope This specification outlines the instrument control philosophy of the complete Project. Covered by this specification are the DCS system and their interfaces to other systems. This philosophy is not intended as a technical specification and is restricted to the description of the overall philosophy; detailed technical requirements are not specified. For detailed specifications, refer other sections of these documents. DAROU-1 SULPHURIC ACID PLNAT AND ITS UTILIITY Regulation Upgradation project involves: 1.1. Replacement of standalone electronic controllers/Recorders/Indicators with DCS System. 1.2. Replacement of Relay based trip interlock with DCS system. 1.3. Integration of DCS, field instrumentation and sub-systems shall be done at site by DCS vendors. 1.4. DCS system shall be installed in existing control room of Darou-1 1.5. Following specific sub-systems shall be integrated with DCS 1.5.1. Sulphuric acid plant (SAP-1) 1.5.1.1. Voith Speed Governing system for Tubro Blower. The system includes one Voith TurCon DTc Steam Turbine Controller along with its local Operating Control panel. Local panel is installed in Darou-1 Controller Room. The governor shall be integrated with DCS using Modbus TCP connectivity which is provided in Voith TurCon DTc controller. The DCS will have face faceplate of the governor to issue remote commands to Voith TurCon DTc controller for speed control. Trip contacts of Voith TurCon DTc controller shall be hard wired with DCS system. 1.5.1.2. Vibration monitoring system of Turbo Blower – Sarayu Condition Monitoring System VMS-3000. The VMS is installed in governor controller Panel. 4~20mA signals for individual channels will be hard wired to DCS. Trip contacts from VMS shall be hard wired with DCS system. The system will be integrated with DCS through RS-485 link (MODBUS RTU protocol) also, provided in the VMS, for display of all parameter on DCS. All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS Page 4 of 124 1.5.1.3. Acid Coolers Anodic Protection –Anodic protection System Consist of a controller module. The system will be integrated with DCS through 485 link (MODBUS RTU protocol) also, provided in the Anodic protection Controller, for display of all parameter on DCS. 1.5.2. UTILITY-1 1.5.2.1. Woodward Speed Governing system For TAP (Tubro Alternator Primary). The system includes one 505E Controller along with its local Operating Control panel. Local panel is installed in DAROU-1 Control Room. The governor shall be integrated with DCS using RS-485 connectivity which is provided in Woodward 505E controller. The DCS will have face faceplate of the governor to issue remote commands to Woodward 505 E controller for speed control and extraction pressure control. Trip contacts from 505E controller shall be hard wired with DCS system. 1.5.2.2. Vibration monitoring system For TAP – Bently Nevada make. The VMS is installed in governor controller Panel. 4~20mA signals for individual channels will be hard wired to DCS. Trip contacts from VMS shall be hard wired with DCS system. The system will be integrated with DCS through RS-485 link (MODBUS RTU protocol) also, provided in the VMS, for display of all parameter on DCS. 1.5.2.3. Governing Secondary). system For TAS (Tubro Alternator All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS Page 5 of 124 Presently there is no electronic Governing system for TAS. But In future this going to be migrated to electronic system. So following this need to considered. The governor shall be integrated with DCS using RS-485 connectivity (Modbus RTU) OR ModBus TCP. Both provisions need to be considered. The DCS will have face faceplate of the governor to issue remote commands to governor for speed control and extraction pressure control. Trip contacts from governor shall be hard wired with DCS system. 1.5.2.4. Vibration monitoring system For TAS – Presently there is no VMS. 4~20mA signals for individual channels will be hard wired to DCS. Trip contacts from VMS shall be hard wired with DCS system. The system will be integrated with DCS through RS-485 link (MODBUS RTU protocol) also, provided in the VMS, for display of all parameter on DCS. Modbus TCP need to be considered. 1.5.2.5. Instrument Air Compressor Controller- 4 nos The system will be integrated with DCS through RS-485 link (MODBUS RTU protocol) also, provided in the VMS, for display of all parameter on DCS. Modbus TCP need to be considered. 1.5.2.6. Electrical System: For Numerical Relay, Generator Controller etc. 10 nos. of RS-485 (Modbus RTU) and 15 Nos of Modbus TCP connection need to be considered. All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS Page 6 of 124 NOTE: 2 Nos of Profibus DP cards needs to be consider for Each FCS/DCS Controller. For every RS-485 Modbus RTU , Modbus TCP need to considered while design the system. All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS Page 7 of 124 1.6. SCOPE OF WORK 1.6.1. DCS Vendor: Design, Engineering (including making logics and control schemes as per owner’s drawings and incorporating the same in DCS), Supply, Installation and commissioning of : 1.6.1.1. DCS System including operator consoles, remote consoles, engineering workstation, printers, PDB for Field Instruments and Control panels, Current Transducer Penal, Isolators as per details specifications as per annexure. 1.6.1.2. Design, engineering, and incorporation of control schemes in DCS, Coordination with vendors for seamless integration of DCS and various sub-systems as specified elsewhere in the document. 1.6.1.3. Establishing communication with third party systems and demonstrating the same during FAT. 1.6.1.4. Generation of logging reports and other management information reports 1.6.1.5. Preparation of loop drawings as per formats finalized 1.6.1.6. Preparation of all drawings / documents required for engineering, review / approval 1.6.1.7. Preparation of all as-built drawings 1.6.1.8. Isolator panel cabinet complete with isolators, prewired and marked terminal strips, redundant power supply, cooling fans 1.6.1.9. Electrical interface cabinets along with associated hardware/modules/relays 1.6.1.10. Auxiliary console complete with annunciator, Push buttons, led lamps, Reset switches. 1.6.1.11. Supply of SS conduits for communication cables All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS Page 8 of 124 1.6.1.12. Supply of other erection hardware and consumables like cable glands, ferrules, lugs, etc. as required for cables supplied by vendor 1.6.1.13. Supply of furniture like consoles, chairs, furniture for peripherals etc. 1.6.1.14. Packing and forwarding of all items included in scope of supply 1.6.1.15. Pyrotech workspace/rittal make furniture for work stations/PCs including chairs for operators for control room and engineering room. 1.6.1.16. Master GPS clock need to consider for Time Synchronization. DCS, all sub systems, electrical systems need to be synchronized with Master GPS Clock. Accuracy must be within 1 ms. 1.6.1.17. Commissioning of DCS system in association with Sub System vendor for seamless integration of both the systems. 1.6.1.18. Pre-Factory Acceptance Test (Pre-FAT) 1.6.1.19. Integrated Factory Acceptance Test (IFAT) 1.6.1.20. Packing and forwarding of all items included in scope of supply 1.6.1.21. Transport to site of all items included in scope of supply. 1.6.1.22. Supply of commissioning spares, two years spares, consumables 1.6.1.23. Laying, termination, jointing of FO cables, incl. OTDR testing. 1.6.1.24. System power up, loading of configuration, application software 1.6.1.25. Internal loop / logic and interlock checking from marshalling racks up to operator stations. All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS 1.6.1.26. Integrated Site Acceptance Test (SAT) 1.6.1.27. Providing commissioning assistance 1.6.1.28. Documentation 1.6.1.29. Training for operation and maintenance staff. Page 9 of 124 1.6.1.30. Comprehensive AMC (without resident engineer) for five years after expiry of the warranty period with minimum five visits (including emergency & periodic visits) of the service engineer per year. The AMC shall include supply, replacement / repairs of all the system modules / cards etc. All the software problems / up gradations shall have to be taken care of by the vendor NOTE: Installation and Commissioning job will be carried out tentatively in Annual Shutdown. Approximately 30 days shutdown will be available to carry out the total job. However, installation work may be carried out beforehand in running plant wherever possible. 2. ABBREVIATIONS Used in this document: CPU DCS ESD HMI MCC CCR MOS POS MS OPC OLE PLC SER TÜV VDU = Central Processing Unit = Distributed Control System = Emergency Shutdown System = Human Machine Interface = Motor Control Centre = Central Control Room = Maintenance Override Switch = Position/operation override switch = Microsoft = (Object Linking and Embedding) for Process Control = Programmable Logic Controller = Sequence of Events Recorder = Technische Überwachsungs Verein = Video Display Unit ( Always 21” square model or 24” wide screen TFT /LCD type colour monitor) 3. Control and Safeguarding Systems Objectives: All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS Page 10 of 124 The main objective of the plant and its control system is to, safely and reliably, continuously produce on-specification product. Without compromising these objectives, the control systems shall also be designed to maximize plant availability, minimize plant energy consumption, adverse environmental impact and requirements for operator interventions. The principal objective of the safeguarding systems is the protection of personnel, environment, plant and equipment and the maintenance of safe operating conditions compatible with production requirements. This shall result in control and safeguarding system design that is: - Safe - Simple to maintain - Simple to operate - Flexible to accommodate changes in technology and operating requirements - Flexible to provide for expansion during 20 years design life – Reliable 4. Control and Operation philosophy: 4.1. This project comprises of following unit for which there shall be Common DCS system for all controls & interlocks with Redundant Fault Tolerance Controller/FCS for individual units: 4.1.1. 4.1.2. 4.1.3. 4.1.4. 4.1.5. SAP-1 (Sulphuric acid plant-1). TAP (Turbo Alternator Primary) TAS (Turbo Alternator Secondary) DM Plant Common Section (Air Compressor, Air Dryer etc.) 4.2. All existing plant facilities (as mentioned above in Sr no 4.1) are currently using pneumatic control system & single/Dual loop electronic controller located in Existing control room. All these instrumentation controls & interlocks will now be implemented in New DCS system as elaborated further in this document. 4.3. All process and utility units and related facilities for the entire plant shall be monitored and controlled from the Central DCS located at Central Control Room. Every major and minor unit of the plant shall be operated independently from dedicated console, consisting of DCS operator interfaces. All of these VDU’s shall be 24” wide screen LED type monitor only. All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS Page 11 of 124 4.4. The DCS operator interface (VDU based) shall be the primary integrated window for operation of the control and safeguarding systems and shall provide access to: 4.4.1. 4.4.2. 4.4.3. 4.4.4. 4.4.5. 4.4.6. 4.4.7. 4.4.8. 4.5. Process control Sequence control status Equipment status Alarm overview Trip status overview Historical data trending Generation of dynamic graphics as per process requirement Machine Monitoring All control and interlocks shall be monitored, controlled, and engineered through work stations as given below 4.5.1. Five operator stations. (5 in CCR and 1 in shift in-charge room) Consoles to be placed in the CCR will be Double tier type. 4.5.2. ONE Engineering stations. 4.5.3. One 72” wall mountable type console for process overview in CCR 4.5.4. 4.6. One dedicated PC for reports generated by DCS. All consoles for DCS shall be supplied with 24” wide screen LED type colour monitors. 4.7. All controls and interlocks of the complete plant, shall be performed / realized in the central DCS only. 4.8. Comprehensive facilities are to be provided to ensure that the operators at all times have complete overview of the plant status from the HMI. Information will be presented in the form of ‘live’ graphic displays and simulated instrument faceplates. The system shall be configured to permit the operator to determine the cause of an alarm with a minimum of keystrokes at the console, without having to memorise tag numbers, so that a rapid reaction to an abnormal situation can be achieved. 5. EQUIPMENT LOCATIONS 5.1. All DCS operator stations, auxiliary hardwired console shall be located in central control room of DAROU-1. All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS Page 12 of 124 5.2. All DCS marshalling cabinets, System hardware cabinets, etc. shall be located in central cabinet room of DAROU-1. 5.3. Existing subsystems such as Bently Nevada Vibration Monitoring system, Woodward Governor system, Anti-surge control system for the turbo machinery etc. system’s secondary hardware shall also be located in central cabinet room. 5.4. DCS engineering stations, all other programming PC/Engineering station of other type control systems, etc. shall be located in central engineering room which will be in the close vicinity of central cabinet room and central control room. 5.5. All IRC (Interposing Relay Cabinets or Digital Interface cabinet) and IFC (Interface cabinet or simply Analog Interface Cabinet) between Electrical and Instruments shall be located in central cabinet room only. However Current transducer panel and isolator for analog signals from electrical motor currents will be placed in electrical sub-station. 5.6. All DCS and other control systems’ Panel shall be openable from front and back side. The relevant DCS hardware shall be installed in dedicated panels. The panel make/model/size is specified in detail specification of DCS. There shall be panel segregation for various I/Os meant for DCS. Also, there shall be panel segregation for diff. type of I/Os for DCS, other control systems. This means that analog input and analog output shall be accommodated in a separate marshalling panel/DCS panel. Digital input and interposing shall be accommodated in a separate marshalling/DCS panel. Digital output and all interposing relays shall be accommodated in separate panels. 6. SYSTEMS INTEGRATION /FORIGEN INTERFACE 6.1. The vendors of DCS and Sub systems shall engineer the systems as one integrated control and safeguarding system with respect to operator presentation. The systems shall be brought ready for integration at site. DCS and sub system vendors will list out and share various requirements such as I/O’s communication ports etc for seamless integration of DCS and sub systems at site. The DCS HMI shall be the single operating window for integrated control and safeguarding system. Communications of the sub systems with the DCS shall be accomplished via dedicated redundant, single fault tolerant links. 6.2. An Open Control Systems Network shall allow the integrated control and safeguarding system to communicate with third party control systems, auxiliary information systems and higher-level automation systems utilizing All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS Page 13 of 124 OPC connectivity standards. Although APC is not envisaged immediately, The DCS shall have the capability to be seamlessly integrated with an APC whenever required. Special attention shall be given to network security of the Open Control Systems Network. Firewall shall prevent unauthorized access from the office network to the Open Control Systems Network. 6.3. Communication with Plant Network System: The operators shall be able to access entire Plant Information network through the operator consoles. A gateway from the DCS data highway and the Ethernet LAN shall be provided, to allow the Plant Information System to exchange data. Layer 3 switch with firewall to be provided. This Plant network information system shall collect data from DCS for data validation, history management, advanced process control, material balances. 6.4. It shall be possible to connect with the integrated control and safeguarding system with redundant OPC servers. 6.5. DCS vendor will supply All IRC (Interposing Relay Cabinets or Digital Interface cabinet) and IFC (Interface cabinet or simply Analog Interface Cabinet) between Electrical and Instruments. These shall be located in central cabinet room only. 6.6. All the necessary hardware required shall be considered. Hardware firewall between PLANT INFORMATION/HISTORIAN server and DCS OPC server must be provided. 6.7. Hardware and Software/Licence Required to communication with other DCS System need be consider. Both Read & write accessibility required. 6.8. However, isolator panel for analog signals from electrical motor currents will be placed in electrical sub-station. Electrical analog signals are available in electrical sub-station. DCS vendor will supply Electrical interface cabinets along with associated hardware/ modules/relays etc to be placed in substation. 7. FIELD INTERFACE All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS Page 14 of 124 7.1. Multi- core cables connected to junction boxes in the field, transmitting conventional 4-20 mA signals from all type of field transmitters, individually, will be connected to marshalling racks. In the marshalling racks the signals will be connected to the I/O cards of the DCS systems through pre-fab system cables. Separate RTD AI Cards need to be provided for RTDs. Thermocouple AI card need to be considered for thermocouple connection. 8. POWER SUPPLY 8.1. Power Supply Levels 8.1.1. The different power supply levels used shall be as follows: 8.1.1.1. Uninterruptible Power Supply (UPS, by others): 230 V ± 2%; 50 Hz, ± 2%, 1Ф 8.1.1.2. Standard (non-UPS) mains power supply : 240 V + 10%; 50 Hz, + 4 %, 1Ф 8.1.1.3. DC Power Supply : 24V DC, ± 0.5 % 8.1.2. The DC supply in 8.1.1.3 above shall be derived by the vendor from the UPS by providing two or more regulated SMPS in parallel redundant configuration. 8.1.3. Any other power supply required by the vendor shall be derived and distributed by him from the UPS / DC power supply. All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS Page 15 of 124 8.2. Power Supply Distribution Philosophy 8.2.1. The distribution of power to different plant loads at various voltage levels shall be as per the following table: Sr. Type Of Load Supply Type No. 1. DCS, printers, separately powered instruments, 230V AC, UPS solenoid valves 2. Panel lighting /socket outlets 240V AC, NonUPS 3. 2 Wire transmitters, interrogation of digital inputs, 24V DC interposing relay / contactor coils, trip amplifiers, active barriers, isolators, etc. 4. Solenoid valves 24V DC, 230VAC, 110 VAC 8.2.2. In the event of UPS failure the connected loads shall be automatically transferred to the mains supply where the voltage and frequency regulation shall be as per 8.1 above. (The voltage level shall be same as UPS) The DCS hardware therefore, shall be designed for continuous operation at these conditions. Vendor shall indicate the maximum voltage and frequency variation that the different components of the system can tolerate. 8.3. Bulk Power Supplies 24 V DC 8.3.1. The number and quantity shall be sized by the vendor as per requirement. These shall be in parallel redundant configuration with diode ‘OR’ing unit. In case of a failure of one unit, the redundant shall be capable of handling the entire load without any voltage dip. Output of the diode unit shall form a 24 V DC power supply bus, from which the downstream distribution shall be done. 8.3.2. Each bulk power supply shall be provided with incoming and outgoing MCBs for ease of maintenance. The MCBs on DC side shall be suitably derated for DC duty. 8.3.3. Individual power supply failure alarm shall be available on the operator station. The priority of this alarm shall be same as a system hardware alarm. All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS Page 16 of 124 8.3.4. Output voltage adjustment facility is required. Output shall be clamped to 28 V DC maximum. Regulation shall be as per 8.1 above. Digital voltmeter to read output voltage is required. 8.3.5. Earth fault detection with alarm on operator station is required. 9. ALARM MANAGEMENT 9.1. The purpose of an alarm is to bring the operator's attention to an abnormal event, such that he can take action to rectify the situation. During normal operation the Alarm Philosophy shall be that there are no active alarms present. To enable the operator to respond appropriately, alarms shall be categorized according to the following three priorities reflecting the severity of the abnormal situation, as a minimum. 9.1.1. A "First Failure" indication shall discriminate between related alarms to identify the first initiator of a trip with 1 mili second time resolution in the operator console. 9.1.2. A shutdown level alarm indicates that immediate operator action is required to prevent a trip condition (in this case it is also referred to as a pre-alarm), or is used for essential parameters for proper operation of the plant (e.g. quality alarms) in DCS operator console with diff. hooter/sound. 9.1.3. Secondary alarms draw only attention to an abnormal situation that could result in a severe operational upset if not acted upon. This shall also be reported at DCS operator station with diff. hooter /sound 9.1.4. 9.2. Alarm acknowledgement and first failure resetting shall be from the DCS keyboard, locally from equipment panels 9.3. On measurements that can lead to a trip, pre-alarms shall be implemented. 9.4. The alarm management of the DCS shall be developed with the following objectives: 9.4.1. Minimize the number of active alarms; 9.4.2. Optimize the information contained in the alarms; 9.4.3. Obtain effective alarm presentation by using Human Factor design principles and practice. All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS Page 17 of 124 9.5. Further techniques shall be employed to optimise the operator interface to the alarm system. 9.6. The DCS shall be compliant with Alarm Management standards EEMUA 191 and ISA-18.02. 9.7. Methods to be used are suppression techniques (static or dynamic), first failure indication and alarm overview displays in addition to the alarm list. The overview displays provide a layered structure of related alarms in annunciation screens. 9.8. Sequence of Events Recording system shall log all safety related alarms, commands and status changes for post-trip analysis on a dedicated PC station. 10. CONTROL AND SAFEGUARDING DESIGN CRITERIA 10.1. EXPANDABILITY 10.1.1. In I/O Count for, 20% spare capacity has been considered. This minimum 20% spare capacity shall be provided in each of the I/O cards in the form of spare channels. This spare capacity should be completely pre-wired with all the intermediate accessories like prefab cable, cable connector, barrier / isolator/relay up to marshalling terminal. 10.1.2. No I/O module in DCS shall be loaded more than 80%, 10.1.3. In addition, minimum 20% spare space in cabinets for installation of spare I/O cards shall be available throughout the system for allowing undefined future expansion. 10.1.4. To allow for future expansion 20% spare capacity shall be allowed & terminated in multi core cables, junction boxes, etc, marshalling racks, patch panels and power supply units. 10.1.5. Communication networks and cables shall have a spare load capacity of 50% as a minimum. 10.1.6. Plant wide networks shall have a node connection spare allowance of 50 % as a minimum. All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS Page 18 of 124 10.1.7. Local networks, if any, shall have a node connection spare allowance of 30 % as a minimum. 11. DCS DESIGN CRITERIA 11.1. Minimum Hardware Requirements 11.1.1. The DCS and all the subsystems shall be able to withstand the storage conditions at Senegal, West Africa for long periods stretching to as much as 5~6 months 11.1.2. The system shall have a proven track record of continuous successful operation in a chemical plant for a minimum period of two years after successful SAT. Vendor shall submit letters from end users to prove the above criterion. No prototype hardware / software of any nature shall be supplied 11.1.3. Offered system hardware shall be supported for at least ten years from date of PO. Vendor shall give a specific declaration to that effect. 11.1.4. The system shall be designed “fault tolerant” by selecting components of proven quality and by proper design. Redundancy shall be provided as a minimum as per requirements given later in this document to improve reliability and availability. 11.1.5. All electronic components / modules for controllers, I/O subsystem including the termination assemblies, communication interfaces, shall meet corrosion protection class G3 as per ANSI / ISA S71.04. Type test certificates from an independent agency to that effect shall be submitted. Vendor shall clearly identify hardware which does not meet this requirement. 11.1.6. On-line replacement (hot swapping) of any module shall be possible (i.e. removal and addition of a module without deenergizing the system). There shall be no interruption in the system functioning while replacing a faulty module on-line. 11.1.7. For HART analog signals from field devices, all components in the loop like barriers/isolators, trip amplifiers, Field Termination All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS Page 19 of 124 Assembly (FTA), input / module, etc., shall be HART pass through. Patch cards with multiplexers are not preferred. 11.1.8. Barriers/isolators, FTAs, shall faithfully repeat analog signal from 0 mA to 24.0 mA without clamping the same. 11.1.9. Analog input modules shall have the capability to read inputs below 4mA and beyond 20mA as per NAMUR standard NE 43. It shall be possible to set “bad PV” alarm for signals < 3.6 mA or > 21 mA and use the same in interlock logic. 11.1.10. Barriers, FTAs / input modules used for powering two wire transmitters, shall have short circuit protection against accidental earth fault. The same shall preferably through current limiting without violating requirements in i above. 11.1.11. The system shall be protected from static electric / magnetic fields as well as against commonly occurring EMI and RFI due to walkie-talkie sets, mobile phones, pagers, nearby wi-fi networks, operation of relays / contactors carrying heavy currents, etc. EMI / RFI protection shall be as per latest IEEE / SAMA standards. 11.1.12. Volatile memory shall be protected with battery back-up. Alarm annunciation shall be provided for low voltage of the battery. 11.1.13. A common physical layer diagnostic module shall be supplied for a group of eight power conditioner modules. This shall sit on the same motherboard. Necessary IIIrd party diagnostic software required for the purpose is included in scope of supply. The faults detected by the diagnostic module shall be annunciated on the operator station. Vendor shall indicate the diagnostics available on the physical layer. 11.2. Minimum Software Requirements: 11.2.1. Offered software shall be supported for at least ten years from date of PO. The support includes removal of bugs, installation of software patches for updates / upgrades and making the same compatible with any operating system changes. Vendor shall give specific declaration to that effect. In any case whatever updates / upgrades / improvements released for the software version supplied, up to warranty period, are to be supplied and installed without any price implication. Patches for removal All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS Page 20 of 124 software bugs shall be provided and installed free of cost for ten years from date of PO. 11.2.2. The operator and engineering stations shall be “MS WINDOWS”® based of latest approved version. Licensed antivirus software shall be installed to guard the operating system against external virus attacks. Regular updates on antivirus software up to warranty period, are included in scope of supply. 11.2.3. The DCS shall have the capability to exchange information with other software platforms and shall be OPC compliant. The necessary hardware and software necessary to meet this requirement shall be considered by the vendor. 11.2.4. System shall have extensive self-diagnostic software routines capable of locating and identifying faults at least up to module level and display of the same in detailed diagnostic displays. 11.2.5. The system shall have in built ready-made software to detect open sensors and bad process values with an alarm. 11.2.6. Self-tuning feature shall be available as a standard. It shall be possible to download on-line, parameters computed by the software either manually or automatically. The process shall not get disturbed when a loop is being tuned. 11.2.7. Database shall be global. It shall reside preferably at one point in the system and available to any node on the network. Data addressing shall be by using tag name and not physical or logical address. 11.2.8. Dynamic data shall be updated in all the operator stations simultaneously. Any configuration changes made in the system shall be downloaded to all the concerned stations simultaneously and without any manual intervention, transparent to the user. 11.2.9. The system shall support a powerful and easy to use graphic builder package. This shall include commonly used tools like cut and paste, object embedding etc. Drawing tools commonly found in CAD like midpoint of line, centre of circle, draw tangent, fill / unfill an object, duplicate an object, zoom object, shall be supported. All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS Page 21 of 124 Package shall have extensive library of symbols for equipment, piping components and instruments. 11.2.10. Control builder package shall support all the languages recommended by IEC 61131 standard. Configuration of loops shall be achieved using standard pre-configured program blocks and linking the same. Commonly available tools in “MS WINDOWS”® like drag and drop, copy / paste, hyperlink, shall be available to make the tasks simpler and faster. On line help shall be available, just a mouse clicks away, in the form of tips, explanations, examples, etc. Facility to enter users comments (non-intelligent data) shall be available for ease of understanding. The package shall support all the necessary software for sequence and batch execution as per ISA SP-88 recommendations 11.2.11. Alarm management features supported by the system shall include alarm prioritising (at least 5 levels); alarm sorting / filtering on priority, time span, plant unit, frequency of occurance, etc. It shall be possible to deactivate nuisance / secondary alarms. It shall be possible to organise alarm data in a browser view to analyse the same as per user’s requirements. Dead band shall be configurable individually for each alarm (not loopwise). 11.2.12. The system shall be capable of accepting signals from the following existing Fieldbus standards: 11.2.12.1. Foundation Fieldbus (FF) 11.2.12.2. Profibus 11.2.12.3. DeviceNet 11.2.12.4. ASI-bus 11.2.13. The system bulk memory shall be sized assuming all analog and digital inputs/outputs to be trended at a sampling rate of 1 second for a duration of 30 days. Data archival shall be supported. It shall be possible to archive old data automatically after a certain defined time period on to a storage media (CD, floppy, etc.) from which it can be viewed on-line for analysis. 11.2.14. System shall have extensive self documentation tools. It shall be possible to import in to the system / export from the system, tag database, in a easy to use format like “MS EXCEL”® or “MS ACCESS”® . E.g. it should be possible to extract from system / import in to system; tag database, tag no, service description, IO All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS Page 22 of 124 assignment, ranges, alarm value, trip values, controller action, alarm priority, etc.; in Excel format. Similarly it shall be possible to take print-outs of generated logic, loops and sequences in any of the languages specified by IEC 61131. In case this is not a standard feature of the system, necessary additional software shall be offered to comply with these requirements. 11.2.15. Dynamic display of generated loops, logic, sequences, shall be possible. It shall be possible to read raw data, results of intermediate computations in a dynamic form. 11.2.16. Offline simulation package shall be supported. This shall include simulation and testing of control strategies, logics, sequences; providing alerts and messages for configuration errors; on any offline PC without the actual system hardware in place. It shall be possible to enter data through keyboard to test functioning of a loop for correctness in off-line mode before downloading the same in to the system. 11.2.17. Configuration tool shall have both on-line and off-line capabilities. 11.2.18. On line changes in configuration of loop / logic /sequence shall be possible. Whenever a part of configuration is changed the outputs (analog or digital) pertaining only to that part of existing configuration shall be in ‘hold’ mode (held to last state). The rest of the configuration and outputs shall remain unaffected. When the downloading of configuration changes is complete, the controller shall take over the execution of the loop / logic as per the new configuration. This shall also apply to those cases when tag numbers are added / deleted from a data base. 11.2.19. The system shall boot ifself automatically on restoration of power after total power failure. This shall be a procedureless operation without any intervention by the operator or engineer whatsoever. During power failure, all the digital outputs / controller outputs shall go to zero state, and all controllers shall fall back to manual mode. On restoration of supply, the system shall be ready to receive instructions from the operator without the requirement of any system software files to be loaded , the controllers shall remain in manual mode with outputs at zero, and digital outputs shall assume their states as dictated by the logic / sequence. All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS Page 23 of 124 11.2.20. Forcing of digital outputs shall be possible even though this may not be shown in the logic. This shall be password protected. Whenever a output is bypassed, an alarm shall be generated. A separate dedicated alarm summary shall highlight all the outputs under bypassed state. 11.2.21. Time synchronisation shall be from Master GPS Clock which shall act as a master clock. All connected sub-systems shall be synchronised with the master for uniform time stamping of alarms and events. Time synchronisation within system nodes and with other systems shall be done at least once every hour. Alternatively, 11.3. Optional Software 11.3.1. Long Term Trend Archival Package: It shall run in all Operator station. The package shall enable storing of analog as well as digital data points (Selective) for 1 year duration at 1 Min rate. Vendor shall clearly specify any limitation on the number of tags v/s sampling rate. It should be possible to change the sampling rate to lesser than 1 min up to 1 Sec if required. 11.4. DCS, by employing distributed intelligence and database techniques, shall provide highly secure, safe, reliable, maintainable, effective process / safety monitoring and control of the production/ancillary facilities, from a permanently manned Central Control Room (CCR). DCS shall not be a PLC/SCADA based system. PLC Hardware like CPU, I/O modules etc. in any form are not acceptable in DCS. 11.5. The system shall enable process monitoring, control, safety detection & protection to be achieved, at several equipment nodes, with serial highspeed communications to the operator's console employing VDU's, keyboards, print server & printer, data storage devices, etc. 24” wide screen LED type colour monitor. 11.6. The DCS shall employ Dual redundant (fault tolerant) communications links. The system supplier shall prove that the system hardware redundancy, will achieve an availability figure better than 99.99% per control loop using his chosen hardware configuration. 11.7. Controllers should not be loaded more than 60%. If more number of controllers are required to meet 60% controller loading criteria, the same should be included. 11.8. The system shall be fully configurable without specialized programming knowledge, using proven, fully de-bugged and tested Supplier's standard All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS Page 24 of 124 software packages. Sufficient online storage shall be included to accommodate the database and alarm, event and historic data logs. To achieve the reliability/availability targets required, redundancy requirements shall be calculated and employed. Operational control of the plant will normally be from the CCR. Facilities shall be provided such that in the event of failure of operator workstations, the controllers shall continue to provide control operation at the last known set point. 11.9. The system shall be built on the latest state-of- the-art hardware and software platform and hardware/software/firmware revisions of complete system will be latest at the time of supply. The system architecture shall have Microsoft Windows (latest version) operating systems and compatible hardware. Number of consoles envisaged is indicated elsewhere in this document. There shall be a facility to operate these loops from the adjacent Operator station in case of any failure. Client Server Architecture is not acceptable. All Workstations should be directly sitting on Plant Communication Loop as INDEPENDENT NODES. No operating Station should be connected to Plant communication loop through a server. All workstation should be directly connected to main Plant communication loop as independent nodes with full functionality. However, “remote monitoring stations" which are meant for remote operation/ monitoring can be connected to plant communication l loop through server in case distance is a limitation for Server-Server configuration 11.10. The system shall be 100% fault tolerant and dual redundant for control processor, system bus, data highway, I/O for closed loops, power supply and communication. This means, all central control processors, all communication processors and all other central rack and individual node’s common cards, all the communication cards, networks and cables, etc. shall be 100% fault tolerant.. All the hardware including control/communication processors, networks, cables, all type of system cards, all type of I/O cards shall be hot replaceable. 11.11. All the I/O cards shall have individual channel to channel as well channel to field isolation. Analog input/output cards shall be galvanically isolated and digital input/output cards shall be optically isolated. Group isolated type or bulk I/O cards shall NOT be accepted in the whole system architecture. All I/O cards shall be intelligent type with All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS Page 25 of 124 microprocessor/microcontroller based hardware and capable of all type of signal conditioning, self diagnostic, fail safe value configurable (programmable) and time stamping at I/O card level. 11.12. I/O cards’ Channel density shall not exceed the following limits 11.12.1. Analog Input – 8 Channels 11.12.2. Analog Output – 8 Channels 11.12.3. RTD card - 8 Channels 11.12.4. TC card - 8 channels 11.12.5. Digital Input -32 Channels 11.12.6. Digital Output -32 Channels 11.13. All I/O cards in individual category shall be of same type/model/revision only. No different bulk I/O cards or I/O cards with degraded features shall be accepted in any of the category in a mix mode supply. 11.14. Input - output considerations 11.14.1. All cards will be provided with diagnostic features with High diagnostic coverage per channel at component level, able to detect any failure and giving a diagnostic alarm. Replacement of I/O cards shall be possible while the DCS is powered. 11.14.2. Removal and insertion of a DCS I/O card shall not affect the supply of field power to other loops connected to the DCS. 11.14.3. Shut down switches will work as follows: when the contact coming from the switch is OPEN, the shutdown sequence will start. This solution guarantees that plant shut down is initiated only if requested by operator and not as a consequence of a single hardware failure. 11.14.4. Bypass switch will deactivate a cause (or a group of causes, according to interlock process requirements) only when the contact coming from the switch is CLOSED. This way if there is a hardware fault interlock deactivation will not occur. 11.14.5. The following type of I/O modules shall be provided for as a minimum in the DCS but not limited to: 11.14.5.1. Digital input 11.14.5.1.1. All digital input must have interposing relays in DCS Marshalling. 11.14.5.1.2. Wiring Between IO Card and Interposing Relay Must be prefab. Cable. All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS Page 26 of 124 11.14.5.1.3. Interposing Relay board have redundant power supply. 11.14.5.1.4. Coil side power and contact side power must be from different redundant power supply system. 11.14.5.1.5. Coil side power must Non-UPS supply. While contact side is UPS supply . 11.14.5.1.6. Interposing Relay Rating: 24V dc to 230 V DC/AC coil supply. Contact Rating: As per DCS IO card. 11.14.5.2. Analogue Inputs/outputs 11.14.5.2.1. 4-20 mA dc , 1-5 V dc two wire type 11.14.5.2.2. All I/O circuits must be provided with galvanic isolation using isolating barriers. 11.14.5.2.3. Field Terminal Assembly (FTA) or Marshalling Terminal Assembly Must have redundant Power supply. 11.14.5.3. Digital Outputs 11.14.5.3.1. All digital outputs shall be equipped with protection against voltage surges caused by inductive loads. 11.14.5.3.2. Digital outputs shall be static type, free voltage contacts. The outputs shall be galvanic ally or optically isolated. 11.14.5.3.3. Outputs shall be without any common wiring and no looping in the terminal end is allowed. 11.14.5.3.4. The interposing relays shall be provided in the DCS Marshalling to match the required Contact ratings. 11.14.5.3.4.1. for Solenoid valves and MOV’s 24 V TO 230 V DC/AC - 3 Amps. 11.14.5.3.4.2. for MCC 24 V TO 230 V DC/AC - 5 Amps. 11.14.5.3.5. Interposing Relay Coil voltage: 24 V DC 11.14.5.3.6. Interposing relay board must have redundant power supply. All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS Page 27 of 124 11.15. All digital input terminal blocks and all digital output terminal blocks shall be fused Push Through type. (Phoneix Contact make) 11.16. The scan time of all type of analog/digital inputs cards & DCS algorithm (Scan time means the sum of total time required for reading an input, running control algorithm and writing the output values) shall be better than 250 milli-seconds for any type of channel. 11.17. There shall be minimum 1 nos. of engineering station software/personalities in overall DCS architecture, from where the complete DCS project can be developed and deployed on any other operator/control station, independently. Non-availability of both of these engineering stations simultaneously shall not affect the plant normal operation and shall neither cause any historical/trend data loss. All operator station shall be independent of engineering stations, self bootable and do not require engineering station for putting them into normal operation or restoring them after rebooting, once the developed project is deployed. System should allow on-line modification, addition / deletion or change in any control loop or part thereof. 11.18. All operator stations and engineering stations shall be OPC compliant without any upper limit on number of tags. However, if there is any specific limit applicable on the proposed system, it is to be specified. Two Operating station must have OPC Server facility with Required licence. There must not OPC tag upper limit. 11.19. Complete system hardware/software and communication load shall not exceed 50% system load even after the complete implementation of project and running at peak load. This includes redundant control processor load also. 11.20. System shall have 50% spare margin in software memory/load for future spare addition without replacing/upgrading any existing system hardware/software at all the levels. System shall be capable of loading up to 100% without any overrun/degradation of performance, etc. System shall report all type of load limit alarms, diagnostic alarms upto channel level, communication alarms, system hardware failure alarm and other global information with alarm facility on engineering/operator station in real time with 1 second resolution 11.21. System shall have 50% spare margin in software memory/load for future spare addition without replacing/upgrading any existing system hardware/software at all the levels. System shall be capable All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS Page 28 of 124 of loading up to 100% without any overrun/degradation of performance, etc. System shall report all type of load limit alarms, diagnostic alarms upto channel level, communication alarms, system hardware failure alarm and other global information with alarm facility on engineering/operator station in real time with 1 second resolution. 11.22. The system shall support all various type of control/interlock/sequence algorithm and shall also support various high level programming language like VB, C/C++ in real time control application, in addition to standard control algorithms available in the DCS. 11.23. System shall support various Hourly/Shift/Daily/Monthly Reports/Logs, Totalizers reports, SNAP shot reports, etc. in Microsoft excel format only. The layout and type of reports/data, nos. of tags per report, etc. shall be as per owner’s requirement. All the operator station, engineering stations shall be equipped with MS Office licensed copy. System shall support history for min. 5000 tags, out of which 2000 points shall be configurable for 1 second resolution, 1000 points shall be configurable for 2 seconds interval and remaining shall be configurable from 5 to 10 seconds. There shall be no limit on history data retention time, except the hard disk size. All the stations, wherever engineering database of complete project and historical/run time data is stored, shall be equipped with redundant hard disk with RAID1 configuration, to prevent any data loss. This will include not only the engineering station but all the operator station also, wherever applicable 11.24. System shall support 1 second time resolution real time trend for all the system tag/parameters, without any time limit. The minimum x – axis time span for real time trend with 1 second sample rate shall be 30 minutes. Also, all PID loop face plate display shall have real time/historical trend window by default for min. three parameters, i.e. measured or process variable, operator entered or remote/calculated set-point and output value or manipulated value for that particular loop. 11.25. DCS system shall have latest; windows based alarm manager with 1 second or better time resolution. In addition to various process alarms, the system shall also store operator action journal, system error messages, any other event, etc. Alarm manager shall also have historian facilities and there shall not be any storage limit except hard disk size for retention period of various alarms/events. 11.26. Complete system hardware shall be certified for ISA G3 class corrosion level protection and shall be compatible with various RFI/EMI immunity as per IEC. All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS Page 29 of 124 The complete system shall be supplied with 800 mm (W) x 800 mm (D) x 2100 mm (H) standard RITTAL make panels with RAL7032 colour shade. Marshalling philosophy and panel segregation for various type of I/O shall be as per Owner’s requirement, which is already described above. 11.27. DCS system shall have fast MODBUS I/O cards/Communication gateways for interconnecting with other various types of control systems like Speed/Vibration monitoring system, etc. via RS485 interface and MODBUS protocol AND via ethernet MODBUS TCP. The communication module and links shall be 100% fault tolerant. The signal exchange between various other system and DCS shall be hardwired if they are to be used for control/decision making purpose in DCS. All serial links shall be connected to dedicated gateways/cards. These gateways shall be independent and not combined with process controllers. Serial cards shall be redundant. 11.28. Vendor shall provide 230 V AC +/- 10% at 50 Hz 3/+1 Hz, UPS grade, floating power supply for complete DCS system at one location in cabinet room up to PDB panels. All digital input shall have 24 V DC interrogation voltage level. All Analog cards shall be capable of accepting 2 wire and 4 wire analog inputs and shall supply 24 V DC to field transmitters. All Digital output cards shall drive 24 V DC, 4 NO/NC, socket mounted, interposing relays with 24V to 230 VAC/DC/5 Amp contact ratings. All field loads from Digital Output cards, including Solenoid valves, MCC switch gear signals, etc. shall be interfaced via these interposing relays only. The output cards driving the MCC related output relays ( which are to be wired to MCC/Sub station) shall be accommodated in Digital Interface panel as specified above, separately to avoid any Interference problems in low voltage instrument signal cables. There shall be intrinsically safe active barriers of MTL / P&F make for analog inputs & outputs, and all NAMUR sensors (proximity switches) for Sulphur Zone and Boiler Zone. Isolators need to be considerd for AI signals between DCS and MCC/Electrical systems. 11.29. For various categories of I/O cards, 20% (minimum one set where 20% works out to be less than one) of each type of spare I/O All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS Page 30 of 124 modules as ware house spares shall be considered. These spare modules shall also include related termination assembly, isolating barriers and all system pre-fab cables. For modules, (controllers, communication modules, power supplies etc.) which are specified as redundant, 20% ware house spares shall be considered or 1 pair of each type if 20% works out to be less than one. 11.30. The offered system shall be supported by the DCS vendor for min. 15 years for all type of hardware and software spares and service supports 11.31. While preparing DCS database, all configuration like graphic symbols, colour codes, control/logic schematics, etc. shall be based on ISA standards. 11.32. The following Tagging and Identification philosophy for Equipment, wiring and terminals shall be followed 11.32.1. Each Cabinet, Workstation, operator station, card file, equipment, shall have identification label/Nameplate on the front and rear. The identification label shall be of laminated plastic or approved equal with white dull surface finish and information engraved in Black. These labels shall be permanently affixed with fasteners or Bonding to the Cabinets / equipment. Vendor to provide the Nameplate and labelling schedules for approval by ICS. 11.32.2. All the instruments, pushbuttons, switches, lamps etc. mounted in the Cabinets/ Consoles shall be identified by two identical nameplates, one on the front and one on inside the cabinet/ Console. The nameplates shall be made of plastic or stainless steel inscribed with tag no. and service. The nameplates shall be attached with non-corrosive fasteners. 11.32.3. All wires connected to Terminal blocks, including I/O module termination panels shall be tagged with 2 identification tags. The first Tag shall (closest to the end of the wire) identify the terminal number to which the wire is physically connected. The second tag shall identify the terminal or device number to which the opposite end of the wire is connected. Wires markers shall be slip-on, heat shrink, permanently embossed, sleeve type. All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS Page 31 of 124 11.32.4. Each terminal block shall be labelled with a sequential terminal identification number. Each row or column of terminal blocks shall be labelled with a unique Identification name or number. 11.32.5. Multicore cables with connector plugs shall be labelled with 2 identification tags. The first tag (closest to the plug) shall identify the cabinet identifier, device and socket to which the plug is to be connected. The second tag shall identify the cabinet identifier, socket or device to which the opposite end of the cable is connected. 11.33. SYSTEM TERMINATIONS 11.33.1. The termination in DCS panels have to be segregated per voltage level and voltage category. 11.33.1.1. Analog (Intrinsically safe) 11.33.1.2. Analog (Non- intrinsically safe) 11.33.1.3. Discrete (Explosion proof) 11.33.1.4. Power supply cables. 11.33.1.5. Control signal cables between MCC and control room. 11.33.2. Terminals shall be phoenix contact (push through type) type and shall be adequate for wiring of flexible wires of 0.5 - 2.5 mm2 section. No double terminal blocks may be used. 11.33.3. Terminal panels with electronic devices and/or relays mounted shall have a dedicated mechanical protection. 11.33.4. Each terminal panel shall have the individual identification tag and each channel shall be identified by the instrument connected with tag name. 11.33.5. The terminal panel connection to the I/O cards shall be through prefabricated cable with plug-in connector. All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS Page 32 of 124 11.33.6. The Terminals provided in the Marshalling cabinets shall be single tier and of suitable size depending upon the current rating and the size of the cable being terminated. 11.33.7. The terminals shall be of phoenix contact push through for the signal from / to field. Individual fuses and indicating LED/Lamps for indicating signal status shall be provided for each Digital O/P channel. 11.33.8. The digital outputs shall have LED/Lamps for indicating Fuse blown status. 11.34. Unauthorized access to the system shall be protected by means of suitable Hardware Key locks and Software passwords. Different levels of access shall be provided for the Operators and Engineers by means of passwords and key locks. 11.35. COMMUNICATION SUB SYSTEM 11.35.1. The Communication sub system cable shall be secured in conduit inside the control room. In such installations where communication subsystem extends outdoor and subjected to intermittent exposure to water or condensed moisture, it must be enclosed in rigid conduit. The communication subsystem, in such case must perform to the offered specifications for error rate, signal attenuation, noise immunity etc. 11.35.2. DCS Bus shall be fully deterministic based on IEEE802.4. 11.35.3. Communication speed on the system bus shall be minimum 100Mpbs and overall system performance shall not be degraded whether communication subsystem is 10% loaded or 100% loaded. 11.35.4. Vendor must furnish BUS LOADING calculations for each system. I.e. controller & Data Acquisition subsystem, console subsystem and communication subsystem. The Loading figures All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS Page 33 of 124 shall be demonstrated by vendor at FAT and finally during SAT. Vendor quoted Hardware and software shall meet these loading requirements. In case actual loading is found to be higher than the specified figure, vendor shall supply additional hardware / software to meet the requirements of this requisition without any commercial implications. 11.35.5. System bus, subsystem bus and I/O Bus redundancy shall be true redundant with 2 sets of Bus and redundant Cards. 11.35.6. DCS communication sub system shall be OPC compliant. 11.36. SELF TUNNING 11.36.1. It shall be possible to tune control loops automatically on selective basis. The operator shall either load tuning parameters computed by the system automatically or manually. 11.36.2. The software for the loop tuning may reside / run on any system hardware including controller and Data acquisition subsystem, Operator console subsystem, supervisory computer etc. The tuning package shall ensure that the system not disturbed whenever a loop is being tuned. Tuning package shall not slow or load the system performance. 11.37. POWER SUPPLY 11.37.1. Vendor to ensure the DCS component shall not get affected or failed due to blackouts. Fail Safe Operation of the system to be ensured under the following conditions. 11.37.1.1. Total Power failure 11.37.1.2. Voltage Variation more than ± 10% 11.37.1.3. Frequency variation More than ± 3% 11.37.1.4. Air conditioning failure resulting in temperature exceeding 40 deg C. 11.37.2. 230V AC, 50HZ UPS redundant feeder shall be made available to the vendor at one point in All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS Page 34 of 124 UPS room which is around 100 meters from control room.. Any other voltage requirement shall be derived from the above source by the vendor. 11.37.3. Bulk power supply provided by vendor for transmitter power or for any other application shall have the following specifications: 11.37.4. Bulk power supplies shall be redundant floating with +, - 0.5V tolerance. 11.37.5. Separate power supplies shall be provided for controller /subsystem. 11.37.6. Status indication for each power supply at operator console 11.37.7. Switch / Fuse/MCB for each loop. 11.37.8. Each power supply shall be sized for 150% of load. 11.37.9. The system shall restart without manual intervention after resuming the power sully with in CPU battery life. 11.37.10. Separate Diode O ring/ Isolator unit shall be provided for each bulk power supply. 11.38. EARTHING REQUIREMENT 11.38.1. Vendor to specify the earthling requirements and provide the required drawing as per their standards. 11.38.2. Vendor to provide the connectivity of existing or new earth pit and any additional requirement of earth pit and other details 11.39. CABINETS, RACKS AND PANELS 11.39.1. All cabinets, panels and racks shall be designed without congestion for ease of maintenance. Racks / cabinets shall be designed to take care of the following: 11.39.2. No marshalling rack / cabinet have more than 600 terminals in any case. 11.39.3. All the spare cores shall be terminated on the marshalling rack. No cable / core shall be left unterminated in the rack / cabinet. All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS Page 35 of 124 11.39.4. All spare cores shall be terminated in TB’s at top of the each marshalling cabinets with proper ferrule details. 11.39.5. No terminal or terminal strip, MCB shall be located on the side panel of the rack / cabinet. 11.39.6. Quality of all the panels and consoles shall be of highest quality as per good engineering practice and to the satisfaction of ICS engineer in charge. 11.39.7. Manufacturer of the panel shall be Rittal or equivalent, this shall be finalized during detailed engineering. 11.40. SPARES PHILOSOPHY 11.40.1. Installed engineering spares of 10% shall be provided in each subsystem for each type of module to enhance the system functional requirements including DCS and hardwired instruments. 11.40.2. In addition, the system shall have the following minimum spare capacity. 11.40.2.1. The controller and Data acquisition racks, Analog and digital marshalling racks shall have 20% usable spare space for installing additional I/O modules for future use. 11.40.2.2. Each operator console shall contain 20% usable spare group and related display capability. 11.40.2.3. The system shall have capability to extend its historical trending, logging and user’s memory by 20% to meet future expansion with / without adding additional memory modules. 11.40.2.4. I/O racks of DCS shall have 20% usable spare space for installing additional All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS Page 36 of 124 I/O cards of each type in future. However, internal wiring for the same shall be connected up to the I/O terminals. 11.40.2.5. Processor system of DCS shall have capability to execute additional 20% logic. Further it shall be possible to extend the memory by 20% at a later stage. 11.40.2.6. Usable spare space in cabinets and marshalling racks to install 20% spare hardwire items like barriers, trip amplifiers, and relays etc. including terminals in future. 11.40.3. Mandatory spares shall be 10% of each type of module with minimum of one module for each type or whichever is higher shall be supplied. 11.40.4. System spare capacity shall be provided as follows: 11.40.4.1. Bus capacity : 40% 11.40.4.2. No. of nodes : 50% 11.40.4.3. Vendor shall provide Min. 50% expandability on node connectivity on redundant communication subsystem for each kind of devices connected to the network. 11.41. System loading 11.41.1. DCS shall be sized in such a way to guarantee further expansion to End-User. 11.41.2. Details about software loading of DCS are referred in the different sections of this specification. They will apply to: 11.41.2.1. Communication loading : 60 % 11.41.2.2. Mass memory loading : 60 % 11.41.2.3. Process computations : 60 % 11.41.2.4. Operator console : 60 % 11.41.3. The above software loading figures shall apply to the fully configured system, comprehensive of spare. All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS Page 37 of 124 11.42. Vendor to confirm offered controller card and IO card shall be protected as per ISA GX CLASS 71.04 corrosive environment protection or better and relevant certificate shall be enclosed along with the offer In case of any conflict between above general requirement/guide lines, the more stringent DCS specifications will be followed. All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA 12. SPECIFICATIONS FOR DCS Page 38 of 124 SYSTEM OVERVIEW 12.1. The DCS shall have the following main components: 12.1.1. Operator / engineering stations consisting of PCs, Video Display Units (VDU), keyboards / mouse, auxiliary consoles, etc. 12.1.2. Peripheral devices like printers. 12.1.3. Multi-loop controllers and data acquisition system. 12.1.4. Communication networks and associated hardware. 12.1.5. Gateways for communication with other devices. 12.1.6. Marshalling cabinets. 12.1.7. System hardware cabinets. 12.1.8. Power distribution cabinets. 12.1.9. Control room furniture 12.1.10. Interconnecting cables. 12.1.11. Any other device needed to implement the requirements of this specification but not covered above. 12.1.12. Any other specific device needed to implement requirements of this specification. 12.1.13. Brief functional requirements of each of the above are given in the specification. 12.1.14. The system shall be dual redundant and 100% fault tolerant. This means, all central control processors, all communication processors and all other central rack and individual node’s INTERFACE cards, all the communication cards, networks and cables, etc. shall be 100% fault tolerant and dual redundant. All the system hardware of DCS shall have ISA G3 level corrosion protection. All the hardware including control/communication processors, networks, cables, all type of system cards, all type of I/O cards shall be hot replaceable. 12.1.15. The system shall be built on the latest state-of- the-art hardware and software platform and hardware/software/firmware revisions of complete system will be latest at the time of supply. The system architecture shall have latest version of operating systems and compatible hardware. All the operator station and engineering station shall equipped with 24” wide screen LED type colour monitor. DCS: FIVE No’s operator stations. (4 in CCR and 1 in shift incharge room), two No’s Engineering stations, two No’s remote operator stations for monitoring, are envisaged. These stations shall be placed in DAROU-1 situated approximately 500 meters from the CCR. 12.1.16. There shall be a facility to operate these loops from the adjacent Operator station in case of any failure. In addition to total nos. of operator stations, there shall be 1 operator station for shift All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS Page 39 of 124 engineers inside control room. This will be same as other operator station, except it will not be accommodated in operator console but will be provided with table top furniture. 12.1.17. Client Server Architecture is not acceptable. All Workstations should be directly sitting on Plant Communication Loop as INDEPENDENT NODES. No operating Station should be connected to Plant communication loop through a server. All workstation should be directly connected to main Plant communication loop as independent nodes. However, “remote monitoring stations" can be connected to plant communication loop through server. 12.1.18. Complete system hardware/software and communication load shall not exceed 50% system load even after the complete implementation of project and running at peak load. This includes redundant control processor load also. 12.2. Operator station consisting of: 12.2.1. 24” wide screen LED type colour monitor video display units (VDUS) with related system hardware like full fledge server grade machine with 32 GB RAM and 1TB RAID-I SSD, DVD writer, as a minimum. The hardware configuration of all operator station shall be same as that of engineering stations and license copy of operating system. 12.2.2. Operator’s/engineer’s touchscreen. keyboards with mouse 12.2.3. Dummy consoles to mount push buttons, hardwired/assignable instruments, annunciators etc. 12.2.4. Printers with furniture. 12.2.5. Hard copy units with furniture. and lamps, 12.3. Multi-loop controllers & Data acquisition system 12.3.1. It shall be fully redundant and fault tolerant with hotswappable redundant modules. The scan time of all type of analog/digital inputs cards & DCS algorithm (Scan time means the sum of total time required for reading an input, running control algorithm and writing the output values) shall be better than the required scan time of the fastest running control/closed loop like anti surge algorithm in the plant for various turbo machinery etc. All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS Page 40 of 124 However, in any case, this shall not be more than 250 milliseconds for any type of channel. The system shall support all various type of control/interlock/sequence algorithm and shall also support various high level programming language like VB, C/C++ in real time control application, in addition to standard control algorithms available in the DCS 12.4. I/O processing units: 12.4.1. All the I/O cards shall have individual channel to channel as well channel to field isolation. Analog input/output cards shall be galvanically isolated and digital input/output cards shall be optically isolated. Group isolated type or bulk I/O cards shall NOT be accepted in the whole system architecture. All I/O cards shall be intelligent type with microprocessor/microcontroller based hardware and capable of all type of signal conditioning, self diagnostic, fail safe value configurable (programmable) and time stamping at I/O card level. 12.4.2. All I/O cards in individual category shall be of same type/model/revision only. No diff bulk I/O cards or I/O cards with degraded features shall be accepted in any of the category in a mix mode supply 12.5. Data storage devices like SSD, portable USB hard disks, DVDs etc. 12.6. Communication network and associated hardware. 12.7. There shall be minimum 1 nos. of engineering station software/personalities in overall DCS architecture, from where the complete DCS project can be developed and deployed on any other operator/control station, independently. These engineering stations shall be used as operator station also. However non-availability of both of these engineering stations simultaneously shall not affect the plant normal operation and shall neither cause any historical/trend data loss. All operator station shall be independent of engineering stations, self bootable and do not require engineering station for putting them into normal operation or restoring them after rebooting, once the developed project is deployed. System should allow on-line modification, addition / deletion or change in any control loop or part thereof. 12.8. Gateways for communication with other devices. This includes Bently Nevada 3500 series vibration monitoring systems, WOODWARD make Digital Governors, Anti-surge system for turbo machinery etc All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA 13. SPECIFICATIONS FOR DCS Page 41 of 124 FUNCTIONAL SPECIFICATIONS 13.1. FUNCTIONAL REQUIREMENTS 13.1.1. The system, as a minimum, shall meet the following requirements without the supervisory computer: 13.1.1.1. Control 13.1.1.2. Data acquisition and monitoring 13.1.1.3. Alarming 13.1.1.4. Logging and report generation 13.1.1.5. Historical data storage 13.1.1.6. Trending 13.1.2. System shall have some free memory space available for the user and CPU shall have the additional capability to perform advance control functions, process optimization programs or generate management reports as specified in job specification in addition to space requirements. The availability of process control language shall be preferred. 13.1.3. Whenever information network is specified, the system shall meet any or all the following requirements:13.1.3.1. Centralized information system 13.1.3.2. Statistical process control/statistical quality control 13.1.4. Computer integrated manufacturing with information transfer to achieve functions like production and preventive maintenance scheduling and plant wide coordination etc. 13.1.5. Self-documentation 13.2. Operator Station (OS) 13.2.1. Each OS shall be a PC based workstation. It shall be used by the operators to control and monitor the plant. 13.2.2. Each OS shall have access to complete or part database of the plant as per requirements. Refer detailed system architecture diagram attached for details. 13.2.3. Software masking facility shall be available with which it shall be possible to inhibit selectively, operation of certain plant units, from an OS or a group of OS. From any OS within a group, dedicated to a plant unit / unit, it shall be possible to operate / control all the tags assigned to the unit / units; whereas tags from units not assigned to the OS can only be viewed. All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS Page 42 of 124 13.2.4. Each OS shall be PC based, standalone type, with its own power supply, display screen, CPU and memory, communication interface, keyboard, and mouse. 13.2.5. Each OS shall have the following specifications: 13.2.5.1. PC type : INDUSTRIAL GRADE vendor’s approved make 13.2.5.2. CPU : Pentium core duo i7 4GHz,(min) or equivalent. 13.2.5.3. Display : Colour, 24” , LED 13.2.5.4. Display arrangement : Double tier 13.2.5.5. Port to drive large screen display : Required 13.2.5.6. SSD : 1TB min RAID-5. 13.2.5.7. RAM : 32 GB 13.2.5.8. GRAPHIC CARD: 4 GB 13.2.5.9. CD/DVD, read / write drive : required 13.2.5.10. USB ports : USB 3.0 ( 8 nos) 13.2.5.11. Type C ports: 3 Nos 13.2.5.12. HDMI PORTS: 2 NOS 13.2.5.13. DP PORT : 2 NOS 13.2.5.14. Interface with data highway : Redundant 13.2.5.15. Mouse : Optical 13.2.5.16. Keyboard : Membrane type dust / spill proof, Additionally QUERTY key board shall also be supplied. 13.2.5.17. Dedicated assignable keys on keyboard : Required 13.2.5.18. A group of OS shall be arranged to form an operator console 13.2.5.19. The consoles shall be suitably provided with cooling fans & filters. The CPUs shall be placed on the sliding type pull out plates for ease of maintenance. 13.2.5.20. FAN FAILURE ALARM MUST CONSIDER 13.2.5.21. Each operator station shall be accommodated in its own independent console/furniture with the best befitting furniture with good system ergonomics and aesthetic. All the consoles of operator stations shall have cooling fans and filter louvers 13.2.5.22. Failure of any one workstation should not affect more than one operator station VDU 13.3. Engineering Station (ES) 13.3.1. This shall contain the necessary software required for engineering and configuration. It shall be used to perform the following functions: 13.3.1.1. To add / delete a system node through the system builder package. All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS Page 43 of 124 13.3.1.2. To configure a node and assign hardware to it. 13.3.1.3. To build graphics and other displays using the display builder package. 13.3.1.4. To configure control / monitoring loops, build logic / sequences. 13.3.1.5. To write / edit user written programs in higher level languages supported by the system. 13.3.1.6. To download the generated application software to different system nodes. 13.3.1.7. To generate self-documentation. 13.3.2. Each ES shall have the following specifications 13.3.2.1. PC type : Commercial grade vendor’s approved make 13.3.2.2. CPU : Intel® Xeon® processor (E5-1620 v3, QuadCore,3.5 GHz ). Or equivalent 13.3.2.3. Display : Colour, 24”, LED 13.3.2.4. SSD: 1 TB with RAID 5 13.3.2.5. CD / DVD read / write drive : required 13.3.2.6. Graphics Card : NVIDIA 4GB Graphics Card 13.3.2.7. USB ports : 8 13.3.2.8. Interface with data highway: Redundant 13.3.2.9. Mouse : USB Optical Scroll mouse 13.3.2.10. Keyboard : QUERTY, USB Type 13.3.2.11. EXPANSION SLOTS: 2 X PCI e Gen3 x16 slot 1 X PCI e Gen3 x16 slot /x8 connector 1 x PCI e Gen2 x4 slot/x4 connector 1 X PCI e Gen2 x1 slot 1 x PCI slot 13.3.2.12. COMMUNICATION PORTS: USB 3.0 - 1 (Front), 3 (Rear) USB 2.0 - 3 (Front), 3 (Rear) 13.3.2.13. Type C ports: 3 Nos 13.3.2.14. HDMI PORTS: 2 NOS 13.3.2.15. DP PORT : 2 NOS 13.3.3. One number of CD / DVD (combination) read / write drive shall be supplied loose. The combo drive shall be latest state of art with software for labelling of a CD/DVD. It shall be supplied with its power adapter, USB cable and the necessary R/W licensed software. This can be plugged in ES to load the licensed software or its updates in the system. The necessary drivers required for this shall be loaded in the ES. All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS Page 44 of 124 13.3.4. Whereas one engineering station should be sufficient to configure entire system, multiple engineering stations on a single highway should be supported. This will help in system engineering for different plant units simultaneously / from different locations. 13.3.5. If the vendors architecture is based on client /server concept where the server is the repository of the complete database and operator stations / controllers are the clients, the servers shall be fully redundant. Each server shall have RAID 1 architecture as a minimum. The necessary software for operation and engineering shall follow concurrent users’ philosophy. Vendor to confirm where will the optional software listed u/s 6.4 reside. 13.3.6. ES can be used as OS if required but not vice-versa. 13.4. Standard Displays The DCS shall have the following standard displays as a minimum: 13.4.1. Overview Display 13.4.1.1. This shall give an idea of the overall plant status with less emphasis on details. This can either be in the form of a deviation overview, overview of various plant units, alarm status of all tags etc. This display shall not be used for plant control. Similarly, no alarm shall be acknowledged from this display. It should be possible to approach any other operating display from overview with minimum of operations. All these features shall be user configurable. 13.4.2. Group Display 13.4.2.1. This shall enable an operator to view a group of tags (analog or digital in any combination) in the form of faceplates similar to instruments on a conventional control panel. Operator can do all the usual control actions and operate the plant through this display. Alarm status of a loop shall be available in this display. 13.4.2.2. Loop parameters like alarm status, PV, SV, MV values, mode status (Auto/Manual/Cascade) etc. shall be displayed prominently for each loop. This display should be conveniently linked to the plant overview display, detailed loop status display and also to the relevant graphic pages of the plant, for ease of operation. All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA 13.4.3. SPECIFICATIONS FOR DCS Page 45 of 124 Detailed Loop Status Display 13.4.3.1. This shall be used by engineers to analyse the behaviour of a loop. All loop constants can be changed only through this display. Tuning of a loop shall be done using this display. For this purpose, real-time trends of PV, SV, MV shall be available for the latest 30 minutes. Password protection shall be provided for access to tuning parameters. 13.4.3.2. This shall give in analog / digital form all the parameters of a particular loop like alarm set points, P, I, D values bias, loop status, PV, SV, MV values, limits on output or set point, algorithm description, controller action, other configuration details etc. This display shall be used mainly by engineers for changing constants, tuning a loop etc. Real time trends of PV, MV, SV for tuning purposes shall be available in this display. The sampling frequency for trends in this display shall be minimum 1s with configurable dead band for each parameter and the display time minimum 1030 minutes. 13.4.4. Displays for Alarm Handling 13.4.4.1. These shall chronologically list all the alarms in a plant. Operators can acknowledge and reset alarms through this display. Acknowledging an alarm shall be possible either through a dedicated key on the keyboard or through mouse click. Information such as tag number, alarm description, time of occurrence / return to normal, value, priority, shall be available as a minimum. 13.4.4.2. Five levels of priority shall be available. Each will have different audible and visible means of annunciation. System alarms shall be clearly distinguished from other alarms. It shall be possible to assign alarms on absolute values/rate of change of a variable. Variable can be anything from a PV, SV, MV, deviation, ratio, or any intermediate computed values in an algorithm. Latest process alarm shall be always available in any display. 13.4.4.3. This shall be one of the most important displays of the system. This shall have following features as a minimum. All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS Page 46 of 124 13.4.4.3.1. DCS system shall have latest; Alarm manager with 1 second or better time resolution. In addition to various process alarms, the system shall also store operator action journal, system error messages, any other event, etc. Alarm manager shall also have historian facilities and there shall not be any storage limit except hard disk size for retention period of various alarms/events. 13.4.4.3.2. A list of alarms based on occurrence with most recent alarm on top. 13.4.4.3.3. A common list of latest 100 alarms for the whole plant in chronological order. 13.4.4.3.4. Ack/scrolling ALM history and most recent alarms shall be possible through software targets on the same display. 13.4.4.3.5. The alarm list in each case shall give the tag no., the service description, type of alarm and the time of occurrence, status, acknowledgement information. BIDDER to specify total number of alarms per page. 13.4.4.3.6. It shall be possible to assign alarms on PV, SV, MV, rate of change (PV, SV), deviation, ratio, as well as on any intermediate computed value in case of a complicated algorithm. 13.4.4.3.7. The system should have minimum 5 levels of alarm priority with different colour and tone. 13.4.4.4. Emergency Alarms 13.4.4.4.1. These shall be grouped for the plant separately from other alarms. Acknowledgment of these shall be through a separate key with LED, dedicated for the purpose and a separate hooter shall be provided for the same. These shall be logged automatically on the printer. The security level should be such that these cannot be disabled by operator or supervisor but only by engineer through a key switch and password. 13.4.4.5. High Priority Alarms 13.4.4.5.1. These shall be similar to emergency alarms except that all high priority alarms shall be acknowledged through a separate key with LED assigned for the purpose. Those shall be logged automatically on the printer and can be disabled only by supervisor/engineer through a key switch and password. All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA 13.4.4.6. SPECIFICATIONS FOR DCS Page 47 of 124 Low Priority Alarms 13.4.4.6.1. These should be acknowledged through a separate dedicated key with LED. It should be possible for operator to disable the alarms. However, logging of the same should not be disabled. 13.4.4.7. It should be possible to disable alarms one by one (i.e. tag-wise) or globally in a unit of the plant through a single command. 13.4.4.8. It should be possible to assign different priorities to more than one alarm for the same tag. (e.g. it should be possible to assign different priorities to “high” & “low” alarms of the same loop). 13.4.4.9. The system software should automatically histories all alarms earlier than the latest 100 alarms.. 13.4.4.10. All system alarms (hardware & software) shall be available in a separate alarm summary with its own acknowledgment key and a dedicated hooter. 13.4.4.11. In alarm system, a common list of all defeated alarms shall appear disregarding their alarm types, priorities, grouping, unit etc. 13.4.5. Trend Displays These shall display one or more variables in a graphical form as in a chart recorder. It shall have the following minimum features. 13.4.5.1. Select / delete a tag for trending. This shall preferably an operator function. 13.4.5.2. Facility to trend any variable; analog / digital, intermediate computed value, etc. 13.4.5.3. Facility to view a minimum of four variables on a common time axis. 13.4.5.4. Assign different sampling frequency and time interval for viewing each variable. 13.4.5.5. Zooming of Y axis and scrolling of time axis. All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS Page 48 of 124 13.4.5.6. Reading instantaneous value of a variable at a given time by positioning the curser at that point on time axis. 13.4.5.7. Trending of one variable against some other (X-Y plots). 13.4.5.8. It shall be possible to view all trended variables from any OS. 13.4.5.9. Facility to group/delete a variable from a group. This should be an operator function. 13.4.5.10. Scrolling of time axis on X- axis and scrolling of range on Y axis. Tag no., alarm status and the dynamic value of the variable in digital form on the trend page. 13.4.5.11. It shall be possible to trend any variable, analog or digital and any parameter of any particular tag. 13.4.5.12. For an analog tag it shall be possible to trend PV, SV, MV deviation, ratio or any intermediate calculated value in a algorithm and any standard block parameter. 13.4.5.13. Maximum Sampling Time For Any Trend Shall Be 1s or less. It shall be possible to assign different sampling times tag wise independently without any limitation with user configurable DB. 13.4.5.14. It shall be possible to store all trends for long time historian without any time limit on retention period, except the hard disk size. If diff. operator stations are storing trend data of diff. trend group, all these stations shall be equipped with min. 2TB RAID-5 SSD. It shall be possible to dump data older than 120 hours automatically to a data storage device like RAID-5 SSD folders and from which it can be retrieved for viewing at later date. 13.4.5.15. BIDDER to give more details regarding data storage and retrieval. 13.4.5.16. On-line archiving of trends shall be possible. Real time trends of 2 hours time base shall be generated perfectly from the control stations. This should not need any history. In case of power failure, no loss of real time, historical and trend data shall occur. All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA 13.4.6. SPECIFICATIONS FOR DCS Page 49 of 124 Graphic Displays These shall be used most frequently by the operators for plant control and monitoring and shall have the following features: 13.4.6.1. Graphics shall be fully dynamic and interactive. Animation facility shall be available. BIDDER to inform the maximum number of dynamic targets any display can accommodate. 13.4.6.2. Library of frequently used pictures / symbols. Facility to build user defined symbols and store the same in the library. 13.4.6.3. Windowing of any graphic in to any other display and vice versa. Zooming of an object. 13.4.6.4. Overlays feature shall be provided to superimpose windows of various types and sizes on a graphic. The overlay can be a face plate of a loop, a part of any graphic, a trend, a message etc. It should be possible to have more than one overlay of different type on any graphic and they all are should be freely movable within main graphic window. 13.4.6.5. BIDDER have to specify the maximum numbers of overlays of different sizes, opened on a standard base graphics and any other limitations. 13.4.6.6. Font size shall be freely configurable. 13.4.6.7. Background colour of graphic shall be freely selectable. . 13.4.6.8. Graphics builder shall have all ISA symbols in library form, so that standard, uniform graphics can be generated in a less time. 13.4.6.9. It shall be possible to assign at least 4 modifier conditions to a graphic character/object. By modifier conditions it is meant change of colour, size, filling & visibility of a pattern etc. 13.4.6.10. Graphic builder package shall be easy to operate without any detailed knowledge of hardware/software. In particular following features are desirable: 13.4.6.11. It shall be possible to build graphic through “touch screen” and mouse. All features of interactive menu driven graphic builder like drag and drop , edit , copy , paste with on line program sensitive help shall be available. 13.4.6.12. Software shall have facilities to change/modify either at a global level or discrete level and the same can be updated in all places with minimum key strokes. . All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS Page 50 of 124 13.4.6.13. Graphic builder package shall have command / script support for complex graphic which can manipulate control strategy. 13.4.6.14. Facility to “zoom” a picture for better visibility shall be available. 13.4.6.15. Security features like masking / access lock shall be available for graphics or parts thereof. 13.4.6.16. It shall be possible to save pictures or parts thereof in the symbol library (to be used again) directly from the picture being drawn & the same need not be drawn once again for the purpose. 13.4.6.17. 60% of total nos. of analog I/O at 500msec scan time. 13.4.6.18. 40% of total nos. of closed loop at 250 msec. time. 13.4.6.19. 40% of total nos. of digital I/O at 10 msec. time. 13.4.6.20. 10% of total nos. of digital I/O at 1 msec. time. 13.4.7. System Configuration Displays: 13.4.7.1. These shall be generated automatically by the system software parallelly as the application software is developed. These shall be live displays and show different process parameters of a loop, intermediate computed values in complex loops, logic execution, sequence execution, etc. in a dynamic form. 13.4.7.2. These shall be used for configuring a loop and shall be mainly used by engineer. These should also be dynamic and should show the various loop intermediate parameters in the loop in digital form. (e.g. a temperature indicating loop should display the mV signal being received, the value after conversion to temperature units and so on). 13.4.7.3. It shall be possible to effect “on line” configuration changes using these displays. 13.4.7.4. Online changes made in the controller sub system, shall not affect the output of a closed loop or process. BIDDER to categorically clarify the limitations if any. 13.4.7.5. Changing of units, ranges, alarm values, dead bands, alarm priority, linearization etc. Of one I/O shall not affect the others. The last good values hold feature shall be implemented in the system with alarms. 13.4.7.6. The access to these displays shall be protected by key lock switch and/ or a password. 13.4.7.7. It shall be possible to log any tag, calculated results or any block standard parameter in the freely formatted manner and log scheduling shall be t user defined interval All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS Page 51 of 124 or on demand. BIDDER to specify the total nos. of log/reports and total point per log limit. Elementary calculations like min., max., averaging, addition, subtraction, rounding off, division, etc. shall be possible in the free format logs with time and date functions. It shall be possible to transfer all these type of reports/logs in a simple ASCII format in a storage media automatically. 13.4.7.8. High level programming language support The system shall provide proper and secure facilities for developing, modifying, compiling and running of user written programs in any high-level language like C, C++, VB or any other 3rd party optimization package etc. It shall be possible to modify, compile and download the program without affecting the normal controller operation. BIDDER to specify the residency and run time platform of these programs. If it requires any extra hardware, then BIDDER to quote for the same with full technical details and limitations. 13.4.8. System Diagnostic Displays 13.4.8.1. These shall be used to detect system faults and quickly determine a malfunctioning node of the system. These shall be dynamic and interactive and arranged in a hierarchical fashion to trace a fault up to module level. 13.4.8.2. These shall be arranged in a hierarchical fashion such that a fault in any of the units of the system can be traced upto module level by suitable annunciation. Modules and individual channel level fault diagnostics with immediate alarms on all operator stations are a must. The following information shall be available through these displays as a minimum. 13.4.8.3. BIDDER to explain the various diagnostic features/facilities/to stays available in the system including maintenance procedures and following information. 13.4.8.3.1. 13.4.8.3.2. Type and location of malfunctioning unit. Nature of fault. 13.4.9. All readouts and graphic displays shall be in S.I. units and all symbols as per ISA respectively and in English. Proper colour codes, graphic density etc. shall be as per OWNER’s requirement. All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS Page 52 of 124 13.4.10. The graphical user interface (GUI) shall follow advanced industrial software & hardware standards as far as possible. In case of using Workstation - based operator and engg. stations the GUI shall follow industrial standards. System shall be able to handle instrument tag numbers consisting of minimum 12 characters. 13.4.11. Display call up time for various displays shall be a maximum of 1 second irrespective of displays’ total dynamic I/O points, density. BIDDER to specify the display updates times. 13.5. Peripheral Devices Peripheral devices are printers, copiers etc. which are used to take print-outs of alarms, logs, display screens. The quantity of these shall be as per the system architecture attached with the specification. 13.5.1. Colour Printer with Scanner & Copy / Xerox: This shall be used for purpose of taking print-out of graphic pages / any other screen print-outs, logging reports, etc. Following specifications shall govern: 13.5.1.1. Type: Ink-jet type LAN printer 13.5.1.2. Paper size: A3 / A4 combined printer 13.5.1.3. Double sided printing : Required 13.5.1.4. Memory : 2GB min 13.5.1.5. Interface with OS / ES : Accessible to any OS / ES through printer LAN 13.5.1.6. COPY / XEROX : Required 13.5.1.7. Colour Scanning : Required 13.5.2. Black & White Printer This shall be used for printing of alarms / operator logs and will have the following specifications: 13.5.2.1. Type : Laser type LAN printer 13.5.2.2. Paper size : A3 / A4 combined printer 13.5.2.3. Print out : Page-wise 13.5.2.4. Double sided printing : Required 13.5.2.5. Memory : 1GB min 13.5.2.6. Interface with OS / ES : Accessible to any OS / ES through printer LAN All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS Page 53 of 124 13.6. Multi-loop Controllers and Data Acquisition System These shall be used for closed loop control / data acquisition. This shall also have capabilities to execute process sequences and interlock logic. It shall have full peer to peer communication with all other system nodes. ➢ Control, logic and sequence functions shall be executed through standard function blocks linked together using drag / drop techniques and assigning tag numbers. No special higher language programming be required for the purpose. The necessary builder package shall support all the languages recommended by IEC 61131. ➢ The system shall have the capability to build user defined control / monitoring blocks, logic / sequence blocks, or a combination of these; and store the same under a given name, for repeated use in future. ➢ All analog inputs shall be isolated with current limiting circuit to guard against short circuit / accidental grounding of field wires. ➢ wire transmitters shall be powered from active barriers and if no barriers are used, through the analog input card / signal conditioning hardware. ➢ Digital inputs and outputs shall be isolated. Isolation shall be galvanic / optical. ➢ The number of inputs / outputs per module shall be restricted to the following maximum: ❖ Analog inputs : 8 ❖ Analog outputs : 8 ❖ Digital inputs : 32 ❖ Digital outputs : 32 ❖ Pulse inputs :8 ❖ RTD inputs :8 ❖ Thermocouple inputs : 32 ➢ A / D conversion shall have a resolution of 16 bits minimum. D / A conversion shall have a resolution of 12 bits minimum. 13.6.1. Functions Supported Following functions shall be supported by the system as a standard. At start of engineering phase vendor shall furnish library of standard blocks available in the system elaborating their features. 13.6.1.1. Control & Monitoring Functions 13.6.1.1.1. PID, PID with external bias, PID on-off, PID gap, PID with cascade and ratio, PID with adaptive gain and reset. 13.6.1.1.2. Self-tuning 13.6.1.1.3. Lead / lag compensation 13.6.1.1.4. Dead time compensation All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS Page 54 of 124 13.6.1.1.5. Pressure and temperature compensation for flow 13.6.1.1.6. Pulse input scaling 13.6.1.1.7. Integration / totalising (resettable and non-resettable counters of 6 digits minimum) 13.6.1.1.8. Velocity limiter 13.6.1.1.9. Ramp generation 13.6.1.1.10. Cold junction compensation for all types of thermocouples 13.6.1.2. Mathematical & Computing Functions 13.6.1.2.1. Addition, subtraction, multiplication, division, square, square root 13.6.1.2.2. Piecewise linearisation 13.6.1.2.3. Moving average 13.6.1.2.4. Elapsed time computing 13.6.1.2.5. Absolute value 13.6.1.2.6. High / low / median / average value selection 13.6.1.2.7. Comparator (> , <, =, etc.) 13.6.1.2.8. Exponential, logarithmic functions 13.6.1.3. Logic Functions 13.6.1.3.1. AND, OR, EX-OR, Inverter 13.6.1.3.2. Flip-flops of all types 13.6.1.3.3. Timers (on-delay / off-delay, settable up to 24 hours) 13.6.1.3.4. Rising edge / falling edge trigger 13.6.1.4. Sequence Functions 13.6.1.4.1. System shall support Sequential Function Chart (SFC) function as per IEC 61131 / ISA SP-88 recommendations. 13.6.1.5. Database Support 13.6.1.5.1. Commonly required data like steam tables, T/C characteristic tables, etc. shall be available as a standard. 13.6.2. Inputs / Outputs System shall support the following inputs / outputs as a minimum: 13.6.2.1. Analog Inputs 13.6.2.1.1. 4~20 mA DC HART, active and passive. Input resistance 250 Ω maximum. 13.6.2.1.2. 1~5 V / 0~10 V DC. Input resistance of 10 MΩ minimum. 13.6.2.1.3. Pt 100, 2 / 3 / 4 wire RTD input as per IEC 751. 13.6.2.1.4. Thermocouples of all types as per IEC 584-2 All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS Page 55 of 124 13.6.2.2. Analog Outputs 13.6.2.2.1. 4~20 mA DC with permissible load resistance of 750 Ω minimum. 13.6.2.2.2. 1~5 / 0~10 V DC, into load resistance of 10 kΩ minimum. 13.6.2.3. Digital Inputs 13.6.2.3.1. Potential free contacts, momentary (10 ms pulse) and latched type. 13.6.2.3.2. Transistor open collector, PNP and NPN type. 13.6.2.3.3. All proximity sensors as per NAMUR standards. 13.6.2.3.4. Pulse train, frequency 0~10 kHz minimum, powered and nonpowered. 13.6.2.3.5. Digital inputs from MCC/ Switchgear shall be wired through PCB mounted interposing relays for isolation. 13.6.2.4. Digital Outputs 13.6.2.4.1. Digital outputs to all loads shall be through PCB mounted interposing relays. 13.6.2.4.2. The system shall support both latched and pulsed outputs. In case of pulsed outputs, it shall be possible to have both positive and negative pulse. Pulse width shall be adjustable individually from 1~60 seconds. 13.6.3. Scan Rates It shall be possible to assign scan rates to all loops and logic individually. By definition scan rate means the time taken to read the input, linearisation and A/D conversion of the same, performing control algorithms and outputting the result including D/A conversion. Following requirements shall be applicable: 13.6.3.1. Closed control loops flow, pressure : 500 ms 13.6.3.2. Closed control loops level / temperature and monitoring loops flow /pressure: 1 s 13.6.3.3. Monitoring loops for level, analysis, temperature :2s 13.6.3.4. Interlock logic : 500 ms 13.6.3.5. Vibration : 100-500 ms** 13.6.3.6. **: This shall be finalized in consultation with vendor’s specific guideline if Vibration Transmitters are used & tripping interlock is implemented in DCS. All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS Page 56 of 124 13.6.4. Redundancy Requirements Redundancy requirements at various levels are as follows: 13.6.4.1. Analog inputs / output modules for closed control loops: 1:1 13.6.4.2. Analog input modules for monitoring loops: Not required 13.6.4.3. Digital input modules : Not required 13.6.4.4. Digital output modules : Not required 13.6.4.5. Pulse input modules : Not required 13.6.4.6. Serial Input modules : Ref. Annexure 13.6.4.7. I/O communication modules with CPU : 1:1 13.6.4.8. I/O power supply modules : 1:1 13.6.4.9. CPU for control, I/O communication, network communication: 1:1 13.6.4.10. Power supply for all CPUs : 1:1 13.6.4.11. I/O bus between CPU and I/O with all necessary hardware : 1:1 13.7. COMMUNICATION NETWORKS 13.7.1. This shall mean all the hardware and software needed for communication between different system nodes as well as devices within a node. In general, this can be classified broadly in to following categories: 13.7.1.1. Central data highway on which the different system nodes shall communicate. 13.7.1.2. Internal communication bus on which different intelligent devices within a node shall communicate. 13.7.1.3. Communication between a node and a third-party device, printer, etc. 13.7.2. Central Data Highway This is the central network used by all system nodes to communicate with each other and hence is the most important communication network. It shall have the following requirements: a. This shall be a 100 % redundant network (both hardware and software) for operational security. The system diagnostic display shall indicate the status of active and standby highway at any given time. b. In case of failure of active high way the redundant one shall take over communication functions automatically, instantaneously and smoothly without any loss of communication. All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS Page 57 of 124 c. The health of both the highways shall be checked continuously and faults annunciate through a system alarm. d. It shall be possible to add or remove a node from the highway without interrupting the ongoing communication with other nodes. e. In case of failure of one or more connected nodes, the same shall be automatically bypassed. The communication with other nodes carries on uninterrupted. f. The communication shall be fast enough so that even during plant upsets, shutdowns or start-ups, the highway is not jammed. g. Each of the highways shall be routed differently to prevent damage to both in case of an accident. h. If the entire length of the data highway cable is routed within a room, the physical medium can be an armoured co-axial cable. For lengths running outside room (in between different rooms) the same shall be an armoured fibre-optic cable. Unarmoured data highway cables shall not be used anywhere in the network. Refer details of the architecture diagram enclosed for more details. 13.7.2.1. Fibre Optic (FO) Cable FO cable shall be laid in single runs between different control rooms in a plant without any joints or splices. The cable shall be designed to withstand plant temperatures up to 700 C minimum. FO cable shall be provided with water barrier, strain bearing glass yarn elements, PVC inner sheath, steel wire armour and with overall sheath of UV resistant PVC. Minimum two fibres shall be available as spares. In addition, following minimum requirements shall be met: 13.7.2.1.1. Fibre / cladding: High purity silica glass; make Corning / J Fibre 13.7.2.1.2. Construction : Graded index of refraction profile, 62.5/125 microns 13.7.2.1.3. Fill Gell / Protection tube: Poly α Olefin / PBT 13.7.2.1.4. Transmission: Multimode 13.7.2.1.5. Light wavelength: 1300 nm or higher 13.7.2.1.6. Attenuation: < 1 dB/km. Available bandwidth ~ 1.0 GB/km. All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA 13.7.2.2. SPECIFICATIONS FOR DCS Page 58 of 124 Ethernet Switches Ethernet switches if used shall be redundant, industrial type, of rugged construction, capable of withstanding atmospheric conditions as per clause 4 of the specification. Ethernet switches shall fulfil the following minimum requirements: Switches shall be managed type. Diagnostics of the same up to port level shall be available on 13.7.2.2.1. 13.7.2.2.2. OS. 13.7.2.2.3. Capability to program a port to control traffic on the same to prevent devices from being overwhelmed with unwanted data. 13.7.2.2.4. Capability to control bandwidth of each port to prevent one device from consuming too much bandwidth. 13.7.2.2.5. Assign data priority so that important data is given priority over other data. 13.7.2.2.6. Provide port security to select which devices can communicate through the switch. Each port shall be programmable through ES, with facility to lock (through software), unused ports to prevent its unauthorized use. 13.7.3. Internal Communication Bus This shall be the communication medium between the various I / O modules and the CPU executing control, data acquisition, logic execution and other tasks. The requirements of this are in general the same as given for Central Data Highway. In addition following requirements shall be met: 13.7.3.1. In case remote I / O modules are connected to this network the data transfer rate shall be fast enough to ensure that there is no compromise in scan times specified. 13.7.3.2. If the entire length of the cable is routed within a single cabinet, the physical medium can bean unarmoured coaxial cable. In case the cable extends beyond one cabinet in to another in the same room, armoured co-axial cable shall be used. 13.7.3.3. In case the remote I / O station is located in another room, armoured fibre optic cable shallbe used for runs in between the rooms. The fibre optic cable shall have at least two spare optical fibres. Refer specifications in above and system architecture diagram enclosed for more details. All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS Page 59 of 124 13.7.4. Communication with Third Party Devices, Printers, etc. This shall be serial communication type RS-232 / 422 / 485 or Ethernet TCPIP and shall be used for communicating with peripherals like printers or reading data from third party devices like PLCs VFDs etc. Specifications of cables used are same as above. Following additional requirement shall be met: 13.7.4.1. TCP/IP network for printers shall be separate from DCS communication networks for control. This is to prevent overloading of these networks with non-control related data. This network shall not be redundant. However minimum two Ethernet Switches shall be used in a distributed manner to connect DCS OS and ES with printers. This is to ensure that a single switch failure does not bring the total printing operation to a halt. 13.7.4.2. Communication requirements with third party devices along with redundancy requirements are spelt out in Annexure II of this specification 13.8. MARSHALLING CABINETS These shall be used to terminate all field cables and mount other hardware like signal conditioning cards, I/O termination assemblies, safety barriers, signal converters, relays and any other equipment as required. These shall have the following specifications: a. Marshalling cabinets shall be self standing type with hinged front/rear doors and lifting eyebolts. Hinges shall be concealed type. Door handles shall be flush type. Cabinets shall be provided with magnetic latches and door locks. b. It shall be possible to open all the cabinets with a single key. c. A 100 mm channel base shall be provided at the bottom. d. Dimensions (especially height and depth) and colour of all cabinets shall be identical from point of view of good aesthetics. Dimensions shall be standardised as follows: I. Height : 2100 mm including 100 mm channel frame II. Depth : 800 mm iii Width : 800 /1200 mm. Cabinets of width 600 mm to be avoided. e. Colour of cabinets shall be as per vendor’s standard. Preferred choice is RAL 7035 f. Cable entry shall be from bottom through removable gland plates. Sufficient space shall be left near the cable entry area for proper glanding of field cables. g. All wires shall be routed through covered PVC ducts. PVC ducts shall be sized liberally to ensure that future wiring can be easily accommodated without the duct overflowing. Separate ducts shall be All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA h. i. j. k. l. m. n. o. p. SPECIFICATIONS FOR DCS Page 60 of 124 used for intrinsically safe (IS) and no intrinsically safe (NIS) circuits. Whereas standard duct colour is grey, colour of IS ducts shall be blue. Pre-fabricated system cables between I/O termination assemblies and I/O modules shall be terminated through multiway cable transit blocks. Bunching of these cables and routing them through a single big cut-out is not permitted. Internal layout of marshalling cabinets shall ensure that there is no overcrowding of components and maintenance accesses are properly provided. Terminal strips shall be easily accessible and ferrules readable. All components shall be mounted on front and rear surfaces of the mounting plate. No component shall be mounted on the sides/doors/gland plates or in the bolting space provided between the adjacent cabinets. A safety earth bus bar shall be provided in each cabinet for earthing. For shields of cables and system earth, separate bus-bars shall be provided insulated from the cabinet structure. Material of all bus-bars shall be copper with nickel/chromium plating. Cabinets and all the components mounted inside them shall be numbered with rear engraved acrylic / printed labels. Ventilation fans and louvered openings with dust filters shall be provided in all cabinets on front/back doors. In case fans are mounted on top, they shall have canopies to prevent accidental condensation from AC ducts entering the cabinet. Every cabinet shall have a monitoring unit which shall monitor stop / stalled or open circuit condition of ventilation fans as well as cabinet temperature. Red LEDs shall indicate individual fan failure. An LED digital display shall indicate the cabinet temperature. A common potential free contact output shall be available for annunciating any of the fan faults and high cabinet temperature, on OS. Fluorescent light fittings (240 VAC) with isolation and door switches shall be provided (one each in front and rear) for proper illumination. A common fuse shall be provided to protect against any short circuit. Incoming two pole MCB shall be provided for each power supply. Outlet of MCB shall be terminated on busbars from which power to individual components shall be tapped through two pole MCBs. For loads with very low power consumption (viz. trip amplifiers, isolators) fused terminals shall be provided for isolation. MCBs shall be used only for rated currents 1A and above. Looping of wires for distribution of power is not acceptable. Quantity of marshalling racks shall be frozen only after final approval of layout drawings during detail engineering. All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS Page 61 of 124 13.8.1. Wiring 13.8.1.1. Wiring shall be done using PVC insulated wires 660 V grade. 13.8.1.2. All wires shall be provided with hot stamped ferrules with black letters on white background. The ferruling philosophy shall be self + cross. 13.8.1.3. The size and colour coding for wires to be used within the cabinets is as follows: Sr. No. Type Of Signal Conductor Cross Section Colour Code Wiring colour code to be finalised during detail engineering. 1. 4~20 mA, input / output 0.75 mm2 2. Digital Inputs 0.75 mm2 3. Digital Outputs 4. RTD Inputs 0.75 mm2 5. T/C Inputs 16 AWG / 20 AWG 6. 230 VAC Power Supply As per load requirements 7. 24 VDC Power Supply As per load requirements As per driven load 13.8.2. Terminals 13.8.2.1. Terminals shall be single tier type. Multi-tier terminals shall not be used. Following specifications shall govern: ➢ Make : Phoenix / Weidmuller ➢ Material : Polyamide ➢ Size :2.5 mm2. For power supply wiring, the size shall be as per requirements. ➢ The different types of terminals to be selected is as per the following philosophy: • Analog inputs, active and passive : push through type • Analog outputs : push through type • DI: Fused in both legs with LED indication push through type • DO: Fused in both legs with LED indication push through type 13.8.3. Relay Boards for Digital Inputs and Outputs These shall be used for digital inputs from electrical switchgear and all digital outputs. The wiring of relay boards with DI/DO modules shall be preferably through prefabricated cables. Relay boards shall be mounted on DIN rails. The brief specifications are: All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS Page 62 of 124 13.8.3.1. Relay type: Plug in, coil voltage 24 V DC ± 10%; coil to be provided with freewheeling diode. 13.8.3.2. Service life : At least 2 million cycles at rated conditions. 13.8.3.3. Contacts : Sealed, 2 NO/NC changeover type; both contacts to be wired up to terminals. 13.8.3.4. Contact rating: 240V AC, 10A @ worst PF 0.3 lagging; 24V DC TO 110 V DC, 10A 13.8.3.5. LED indication: Required. LED lights up when relay is energised. 13.8.4. Other Miscellaneous Requirements 13.8.4.1. The internal layout of the marshalling cabinets shall be such that at site, after erection, only pre-fabricated cables need to be laid from marshalling cabinets to system hardware cabinets; thus, saving valuable time. To achieve this, the signal conditioning hardware, relays, barriers, etc. shall be mounted in marshalling racks. 13.8.4.2. All field terminations shall be done on a terminal strip only and not directly on any other hardware. 13.8.4.3. Terminal strip blocks shall be arranged as per JB termination (including spare cores / pairs) to achieve 1:1 correspondence with JB termination. JB number shall be affixed along with the terminal block number 13.9. SYSTEM HARDWARE CABINETS These shall be used to mount the system hardware like the CPU and communication hardware, I/O modules etc. The colour and dimensions shall be same as those of marshalling cabinets. All other specifications remain identical to those of marshalling cabinets given as per 8.8. The quantity of system cabinets shall be frozen only after final approval of internal layout during detail engineering. 13.10. POWER DISTRIBUTION CABINETS These shall be used to mount the hardware required to distribute power at various voltage levels to DCS consumers as well as to field mounted instruments. These shall have the following minimum requirements: 13.10.1. Dimensions and colour shall be identical to those of marshalling cabinets / system cabinets. 13.10.2. Different cabinets shall be used for different voltage levels. In case the number of feeders for a voltage level are less to justify a separate cabinet, more than one distribution can be combined in All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS Page 63 of 124 to one cabinet. In such a case geographical separation shall be maintained by separating the distribution to front and back side of a cabinet, providing isolating barriers between the distributions, etc. 13.10.3. Incoming isolation shall be through a double pole MCB for rating ≤ 60 A, else a MCCB shall be used. Alternatively, a double pole switch with HRC fuses can be used. Further distributions shall be through busbars and double pole MCBs as in marshalling racks. No looping shall be done. MCCBs / MCBs used for DC service shall be suitably derated as per manufacturer’s recommendations. 13.10.4. Following indications are required. 13.10.4.1. Incoming “AC Power On’ lamp. Three separate lamps (one for each phase) in case of 3Φsupply. 13.10.4.2. Digital voltmeter for incoming AC supply (with a threeposition selector switch to read individual phase voltage in case of 3Φ supply). 13.10.4.3. Digital ammeter for incoming AC supply (with a threeposition selector switch to read individual phase current in case of 3Φ supply). 13.10.5. The rating of MCBs shall be as finalised during detail engineering. The ratings of individual MCBs, and incomer shall be co-ordinated with the overall power distribution scheme to avoid spurious trips. Vendor shall submit a consolidated document giving the characteristic curves of MCCBs, MCBs and fuses used by him; calculation of co-ordination with overall power distribution scheme, etc. for ICS approval. 13.10.6. The terminals for field wiring shall be chosen as per the size of cable to be terminated and shall be finalised during detail engineering. Sufficient space shall be reserved for this to accommodate bigger size aluminium cables. 13.10.7. All other specifications are identical to those for marshalling cabinets given in section 13.8. 13.10.8. Quantity of power distribution cabinets shall be frozen only after internal layouts are approved during detail engineering. 13.11. CONTROL ROOM FURNITURE 13.11.1. Operator Console I. Operator consoles shall be used to mount operator station PCs, screens, keyboards, mouse, paging system, telephone handsets, etc. Auxiliary consoles shall be used to mount other hardware like push buttons, lamps, annunciators, etc. Operator consoles and auxiliary consoles shall be similar in appearance All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA II. III. IV. V. VI. SPECIFICATIONS FOR DCS Page 64 of 124 and dimensions so as to form a single, smooth, continuous, unit. Corner consoles shall be considered as required. Consoles shall be ergonomically designed keeping in mind comfort level of operator, minimum eye strain and good aesthetics. PCs for operator stations shall be kept in closed lockable compartments below the table top. Compartments shall be provided with ventilation fans and louvers with dust filters. A common fan failure/high temperature alarm shall be available on OS per compartment similar to marshalling rack. Console framework shall be extruded aluminium or MS members. Table top shall befabricated from compacted medium density fibre board. Finishing shall be of high quality laminate / scratch resistant acrylic. Each console shall have its dedicated power supply distribution arrangement. All power andsignal wiring shall be done in closed metal / PVC ducts. OS screen and keyboard mounting shall provide for adjustment of elevation and inclination. Console shall be designed to meet following requirement: ➢ No. of OS with dual tier screens : 4 nos. ➢ No. of OS with single tier screens :1 nos. ➢ Printers / copiers : 2 nos. 13.11.2. Engineering Console I. Engineering Console shall be used to mount engineering station PC, screens, keyboard, mouse, etc. II. The general constructional features shall be similar to those of operator console ii – v above. III. Engineering station printer and the portable CD/DVD Combo drive shall be kept on the same console and the table top shall be big enough to accommodate the same. Lockable storage compartments shall be provided to store system CDs. 13.11.3. Printer Tables 13.11.3.1. Printer tables shall be used to mount printers. 13.11.3.2. These shall be self-standing type with power supply distribution arrangement and provided with shelves to store printer stationary. 13.11.3.3. Vendor’s standard design is acceptable. 13.11.4. Operator Chairs 13.11.4.1. Operator chairs shall be designed for maximum operator comfort and reducing fatigue considering long All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS Page 65 of 124 hours of work. They shall be provided with soft cushions, adjustable armrests, back inclination and seat height. Castors shall be provided to enable rolling of the same on floor with ease. 13.12. INTERCONNECTING CABLES These shall be used for interconnection between different cabinets when the same are located apart (not bolted together). Following specifications shall hold: Sr. No. Cable Type Cable Specification 1. Signal cables for analog I/O, 0.75 mm2 multi-stranded tinned copper conductor, PVC insulated, twisted pair/triad, overall screened, PVC inner digital inputs, RTD inputs sheath, armoured, PVC outer sheath; 6/12 pair, 8 triad. 660 V grade. 2. T/C extension cables 3. Cables for digital outputs 4. Power supply cables 5. Modbus cables 6. Central data Ethernet cables 7. Internal data highway cables Vendor’s standard specifications shall govern. 8. Pre-fabricated system cables Vendor’s standard specifications shall govern. 9. Fibre Optic cables for detailed specification REFER ABOVE Conductor material same as thermocouple, size 16 AWG, PVC insulated, twisted pair, overall screened, PVC inner sheath, armoured, PVC outer sheath; 6/12 pair. 660 V grade. 1.5 / 2.5 mm2, multi-stranded tinned copper conductor, PVC insulated, PVC inner sheath, armoured, PVC outer sheath; 12/24 core. 660 V grade. 3 core solid tinned copper conductor, (size of conductor as per requirements of load), PVC insulated, PVC inner sheath, armoured, PVC outer sheath. 660 V grade. Armoured, as per applicable std. highway Armoured, co-axial type as per vendor’s standard specifications. All interconnection cables shall be glanced at both ends with double compression type SS304 cable glands with PVC hoods. All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS Page 66 of 124 14. BOUGHT OUT ITEMS INCLUDED IN VENDOR’S SCOPE OF SUPPLY Following items are included in scope of supply of the vendor. The makes of these items shall be strictly adhered to and concurrence of INDORAMA ICS shall be taken before purchasing these from alternative sources. INDORAMA ICS reserve the right to reject / accept any vendor suggested by the vendor. Model numbers of each item shall be frozen during detail engineering. Sr. Description Acceptable Makes Qty. incl. Remarks No. spares 1. Safety barriers analog MTL, P & Active, HART pass input F through 2. Safety barriers analog MTL, P & Active, HART pass output F through 3. Safety barriers/Isolator MTL, P & digital inputs ( NAMUR) F 4. Safety barriers digital MTL, P & outputs F 5. Safety barriers FF MTL, P & signals F 6. RTD to Current MTL, P & 136 Active type Converter for RTD F Inputs 7. Safety barriers T/C MTL, P & Active type inputs F 8. Analog Input Signal MTL, P & 63 HART pass through isolators F 9. Analog Output Signal MTL, P & 20 HART pass through isolators F 10. Isolator digital MTL, P & 4 inputs ( NAMUR) F 11. Trip amplifiers MTL, P & F, HART pass through Yokogawa, 12. Signal converters Yokogawa HART pass through 13. Earth Fault Detector 14. µP based recorders Chino, Yokogawa - 15. µP based One Loop Controllers Sequence of event recorder Chino, Yokogawa - Hathaway - 16. Vendor to suggest Mounted console Mounted console Mounted console on auxiliary on auxiliary on auxiliary All rights reserved SPECIFICATIONS FOR DCS DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA 17. Alarm annunciators Minilec 18. Page 67 of 124 Mounted console on auxiliary Bulk power supplies 24 Phoenix, Cosel, V DC TRC Electronics (Mean Well) 19. 230 VAC to 110 ABB/ Siemense or VAC equivalent transformer 20. Diode ORing unit Phoenix, TRC Electronics (Mean Well) 21. Portable CD/DVD read Sony, Samsung / write drive 22. FF junction boxes with MTL, P&F barriers or segment protectors Sr. Description Acceptable No. Makes 23. Network Switches Cisco, Siemens As required 24. Printers, Copiers HP, Canon 25. Push buttons Paramount, Siemens, Technic, 26. Key switches Paramount, Siemens, Technic, Paramount, Siemens, Technic, Paramount, Siemens, Technic, J yoti, Omron, Paramount 1 Colour + 1 Black & white on 15 (Hold) Mounted auxiliary console Mushroom type 5 Nos + latch type 10 Nos Mounted on auxiliary console 27. Selector switches 28. Indicating lamps 29. PCB mounted relays ( mounted on on relay board, relay board DIN rain mounted) with 2 changeover contacts As 110 VAC required for required existing solenoid valves. As required Material SS/Polycarbonate Qty. incl. spares As required 2 Remarks 5 (Hold) Mounted on auxiliary console 15 (Hold) Mounted on auxiliary console 600 Coil Voltage 24VDC. Contact rating 230 VAC,5A & 24VDC, 3A. 262 (DI) +338(DO), Qty Hold to be All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS Page 68 of 124 finalised during detail engineering. 30. Relay boards with relays UL 31. Contactors Schneider, Siemens, L&T MDS, Siemens, Standard Kupp 32. MCBs double pole of different ratings 33. MCCBs 34. Voltmeters, Ammeters, CTs 35. Cabinets of all kind 36. OS/ES consoles 37. Printer / copier tables 38. Operator chairs 39. Multi-way cable transit blocks Sr. Description No. 40. FO cable Alsthom, Siemens AE L&T, Hoffman, Rittal Cosmos Knurr, Pyrotech Vendor’s standard Godrej, Pyrotech Bradburg / Roxtec Acceptable Makes Finolex, Birla Ericsson 10 6 Approved makes of relays: Omron, Paramount, Honeywell For HT Motors These are for powering field instruments. Other’s required within DCS panels shall be decided by vendor. Exact rating of each shall be given during detail engineering. As reqd As reqd As reqd to meet specificati ons Separate cabinets for AI/AO , DI & DO. Panelwise segregation for 230/110 VAC & 24 VDC to be kept 2 3 As reqd Qty. incl. spares As reqd Remarks Operator Stations will be located approx. 100 mtrs from Rack room, in separate building All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA 41. 15. Modbus, Profibus, Fieldbus Cable Belden, Kerpen As Required SPECIFICATIONS FOR DCS Page 69 of 124 Refer DCS Serial Link requirements for length calculations. Cable supply by vendor INSPECTION Inspection of the system shall be carried out in two stages: Pre-Factory Acceptance Test (Pre-FAT) Final FAT 15.1. Pre-FAT Pre-FAT shall be carried out to assess the overall preparedness of the vendor for final FAT. Following shall be checked: I. Availability of all hardware and assess shortfall if any. II. Completeness of all panels and consoles as regards mounting of components & hardware, labelling, wiring, ferruling, etc. (random sampling). III. Completeness of software generation as regards tag data base, graphics (static and dynamic), loop configuration, interlock generation, sequence generation, etc. This activity shall be done on random sampling basis. IV. General adherence with philosophy and approved documents to ensure that no common mode mistakes, omissions, are noticed later during FAT. This shall be checked on random sampling basis. The final date for final FAT shall be mutually decided after pre-FAT is complete; INDORAMA ICS is reasonably satisfied about progress of work; and FAT can be carried out without loss of time of clients and INDORAMAIndia. Cost of pre-FAT shall be borne by the vendor. 15.2. Final IFAT I. II. III. IV. Vendor shall give a minimum notice of 3 weeks to INDORAMA ICS for final FAT of the system at vendor’s works. Cost of inspection / testing shall be borne by the vendor. It is expected that vendor has completed all the in-house QC checks on the system. This includes not only standard checks on hardware but also checks on bought out components, complete application software, internal wiring, and so on. Vendor shall confirm in writing that all the inhouse checks are complete and the system is ready for final FAT. The entire system shall be staged by the vendor in his works. The consoles and cabinets shall be assembled in All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS Page 70 of 124 exactly the same way as they will be at site. All the interconnections between cabinets shall be complete, system hardware shall be in place, all software loaded and bought-out hardware included in vendor’s scope of supply duly mounted. Wiring within each cabinet and between cabinets shall be complete. V. Clients / tkIS-India reserve the right to carry out inspection of any bought out items at the sub-vendor’s works. VI. It shall be the responsibility of vendor to arrange all the test and measuring instruments required during inspection. The instruments shall have a valid calibration certificate from a recognised test house and the calibration shall be traceable to any of the national test houses. VII. 3rd party package vendors shall participate during FAT for checking completeness of 3rd party process packages e.g. Ammonia compressor. The inspection shall briefly envisage the following: 15.2.1. Hardware Inspection This shall consist of: I. Checks on general workmanship like fabrication quality, paint quality, paint shade, etc. II. Dimensional inspection for base frame, height, depth, width, etc. III. Provision of busbars for safety earth, system earth, IS earth. IV. Checks on correctness of all labels. V. Power supply wiring and operation checks for fans, tube lights, utility sockets, etc. VI. Power supply and signal wiring checks including colour code of wires, size of wires, correctness of ferrules, correctness of wiring termination, wiring segregation, etc. VII. Provision of terminals of correct size and type. VIII. Operation of lamps, push buttons / switches, MCCBs / MCBs, annunciators, relays /contactors, ammeters / voltmeters and other instruments mounted on the consoles or cabinets. IX. Megger test for power distribution cabinets. X. Checks on correct installation of I/O racks as per approved drawings and I/O modules within racks as per nest loading. XI. Redundancy checks as per specifications on power supply, CPU, communication, and I/O modules. All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA XII. XIII. 15.2.2. SPECIFICATIONS FOR DCS Page 71 of 124 Checks on battery back-up on all volatile memory by switching off power for the duration given in vendor’s specifications. Loop checking shall be conducted from graphics level till marshalling terminals. Detail procedure for the Loop checking shall be provided by INDORAMA ICS during detail engineering. Software Inspection This shall consist of 100% checks on following: I. Checks on generated data base. This includes checks on correctness of tag number, service description, measuring range, engineering units, input signal conditioning, control algorithms associated with the tag, output signal conditioning, etc. II. Graphics shall be checked for static and dynamic information. This includes checks on correctness of graphics as per process, line thickness and colour, correctness of equipment tags and instrument tags, units of measurement, modifier conditions, linking between pages, operation of dynamic and interactive targets, etc. III. Operation of all keys on the keyboard for their proper operation. IV. Printing operations like alarms, operator actions, log reports, etc. V. Correctness of tag grouping in group displays and trend displays, sampling interval for trends. VI. Alarm priorities. VII. Special (non-standard) loops shall be checked 100% from input to output for correctness of engineering. VIII. 100% checks on all logics and sequences. IX. Checks on any higher language programs. X. Communication between any third-party device and DCS. XI. After hardware and software inspection is complete, an exhaustive punch list of all pending, incomplete jobs, mistakes, etc. shall be prepared jointly by INDORAMA ICS and vendor. Vendor shall attend to all the punch list points and certify in writing to that effect. Dispatch clearance shall be given only after such a written confirmation is received. All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS Page 72 of 124 16. TEST SET-UP REQUIREMENTS Vendor shall make available the following testing apparatus / hardware during inspection. No inspection shall be carried out unless the test set up is ready. 16.1. Switch-bank of 64 switches, push buttons, duly wired; minimum 1 number. 16.2. Lamp-bank of 64 lamps; minimum 1 number. 16.3. 4~20 mA signal generators to simulate two wire and four wire transmitters, minimum 2 numbers. 16.4. mV generators, decade resistance box; minimum one number of each. 16.5. Pulse generator for testing pulse inputs. 17. INSTALLATION PRE-COMMISSIONING AND COMMISSIONING INDORAMA ICS shall intimate to the vendor in writing regarding the mobilisation schedule of his site staff at site. It shall be ensured by INDORAMA ICS that control room/s are reasonably completed, free of any debris / dust, doors and windows are fitted and major civil work is complete before such a request is sent to the vendor. On receipt of such a request the vendor shall send a team of experienced engineers, technicians and other erection staff for purpose of installation, pre commissioning and commissioning of the system at site. The engineer involved in application software generation shall be made available for deputation on a continuous basis. Additionally, it is expected that the engineers deputed to site for the purpose of pre-commissioning / commissioning activities, have an experience of at least five years with the vendor. Engineers less than this experience are not acceptable and any delay in site activities on this account shall be solely attributed to the vendor. Bio-data of proposed site deputees shall be submitted for INDORAMA ICS approval. vendor is responsible for the following activities: Assessment of any damages during transportation and providing necessary help to the clients for any follow-up action. Co-ordinate with INDORAMA ICS/site contractor during complete loop / interlock checking of the plant. Consolidate all loop checking reports with INDORAMA ICS. Correction of all drawings to make them ‘as built’. Provide commissioning assistance for tuning of loops, implement minor changes in interlocks, graphics, establish third party communication if it couldn’t be done earlier, etc. The system erection shall be deemed to be mechanically complete when all the internal loop / logic and interlock checking activity is complete. INDORAMA ICS site management shall indicate in writing to the vendor as soon as this activity is completed. The system is now ready for accepting inputs from plant when the instrument erection is complete and the pre commissioning and commissioning activities of the plant are started. The schedule of pre-commissioning and commissioning activities depends on a number of extraneous factors such as readiness of control room, availability of All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS Page 73 of 124 air conditioning, availability of power, progress of instrument erection, mechanical readiness of plant to start loop checking activity and so on. All of these may not be available in exactly the way it is desired. It is therefore expected that vendor is accommodative and willing to show the flexibility to fit-in his site activities within the constraints. 17.1. Mobilisation Schedule Mobilisation of vendor’s manpower for carrying out erection and commissioning activities shall be as per the following table. Sr. No. 1 18. Activity All activities up to internal loop checking, Pre commissioning and commissioning assistance Number Of Visits Expected Total Duration (Days) 3 100 Remarks FINAL ACCEPTANCE AND WARRANTY 18.1. INDORAMA ICS shall take over the system from vendor after final Site Acceptance Test (SAT) as given below. 18.2. The integrated system shall run uninterruptedly for two weeks from the date of commissioning of the whole plant. Any loss of time due to reasons like power failures, forced shutdowns of the plant, etc.; which are due to no fault of the vendor shall also be counted as run time. However if any major software / hardware failure of the system occurs due to which the system or a part thereof has to be shut down the test shall be carried out afresh on the system. As soon as four weeks of uninterrupted run of the system is completed successfully, the SAT is deemed to be complete. For the purpose of warranty, the above definition of SAT shall prevail. 19. TRAINING The vendor shall train INDORAMA ICS engineers in his works. The training imparted shall be by qualified and experienced staff. It shall be exhaustive and aimed at making the participants self-reliant for commonly encountered problems and day to day operations. For training the vendor shall make available as close a model of the system as the actual system to be installed. Necessary printed literature, instruction and maintenance manuals, in requisite copies in English, shall be arranged by the vendor. It is envisaged that the following activities are covered: 19.1. Maintenance Training This shall cover the following topics minimum: I. System architecture All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA II. III. IV. V. VI. VII. VIII. IX. SPECIFICATIONS FOR DCS Page 74 of 124 Functions of each subsystem Hardware in each subsystem Procedures for loading different software. Complete application software. This shall cover everything from basics like generation of the different system nodes, building of displays, loop and logic building, advanced language programming, debugging of developed application, etc. Commonly occurring hardware / software problems and the way to fix the same. Diagnostic routines available; their use and interpretations. Routine preventive maintenance procedures. Maintenance of peripheral devices like printers. 19.2. Operations Staff Training This shall be restricted to operation of the system and cover the following topics minimum: I. System architecture II. Functions of each subsystem III. Function of each key in the keyboard, various shortcuts. IV. Generation of various displays. V. Display hierarchy, access methods for various displays, switching between different displays. VI. Control of plant from various displays. VII. Alarm handling VIII. Logging software 19.3. Training Requirements Training requirements to Client shall be as per following table. Number of days required for each training shall be decided by the vendor as per the respective course contents given above. Sr. Description No. Of Persons Location Of Training No. Batches Per Batch 1. Maintenance Training 1 3 Vendor’s works 2. Operations Staff Training 1 3 Vendor’s works 3. Client’s Engineers Training 2 Vendor’s works 1 All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA 20. SPECIFICATIONS FOR DCS Page 75 of 124 SPARES PHILOSOPHY AND CONSUMABLES 20.1. Installed Spares and Spare Capacity Installed spares are those which shall be supplied with the system duly installed and wired up. Following philosophy shall govern. 20.1.1. 20% IO’s shall be offered as spares IO count indicated in Annexure-I is inclusive of this spare. These shall be supplied with all the hardware required like signal conditioning and termination assemblies, pre-fabricated cables, etc. The quantity of I/O nests shall be decided after considering these spare I/O modules for the IO’s. In addition, 1 spare I/O nest shall be supplied with power supply modules, communication modules etc. This shall be connected to one of the controllers (to be decided during detail engineering). 20.1.2. The I/O allocation in controllers shall be such that in each controller minimum one I/O nest can be added in future. I.e., the controller should not be loaded to its I/O capacity. 20.1.3. The controller CPU loading shall not exceed 60% with the installed I/O modules (including 20% installed spares in ‘a’ above). The CPU loading with all the I/Os connected to its capacity, shall not exceed 70%. The CPU loading shall be checked during SAT. 20.1.4. All bulk power supplies shall be sized such that 30% spare capacity shall be available for future after powering of installed hardware including spares. 20.1.5. Ethernet switches shall have at least 20% spare ports for future use. 20.1.6. The quantity of system cabinets shall be decided considering the requirements of 22.1.1 and 22.1.2 above. 20.1.7. The quantity of marshalling cabinets required shall be considering requirements of 22.1.1 and 22.1.2 above and after due consideration to mount other hardware like barriers, relays, etc. as per philosophy. 20.1.8. DCS licensed tag software shall have 20% additional tag capacity for future use. All optional software indicated above shall have 20% spare tag capacity for future use. 20% spare capacity after including IO’s after special requirements. 20.1.9. The racks shall have FOLLOWING space left as spare so that cards can be inserted in future. Empty slot shall be covered with blank plates. For AI/AO = 55% , DI = 25% , DO = 35% 20.1.10. The panels shall have FOLLOWING spare space so that components like barriers, relays, FTAs, terminals can be mounted as per future requirement. For AI/AO = 55% , DI = 25% , DO = 35% 20.1.11. Necessary spare quantities are already considered in bought out items. Hence no spares shall be considered for these items. All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS Page 76 of 124 20.2. Commissioning Spares These are spares required for replacement during erection / commissioning and till the time of final handing over of the system. Vendor is fully responsible to ensure that adequate spares are arranged by him at site as and when required, in shortest possible time, so that the site work is not affected. These spares shall be supplied free of cost. It is left to the vendor’s judgement to decide which spares have to be stocked at site and those which can be arranged from the works / subvendors at short notice. Unutilised spares shall be returned to the vendor. 20.3. Two Years Maintenance Spares Vendor to offer spares as per following guidelines: 20.3.1. For hardware modules which are redundant no spare is to be considered. 20.3.2. For all non-redundant modules one module of each type to be considered as spare. 20.3.3. If volatile memory is protected with a battery back-up, 5% of batteries or one min. to be considered as spare. 20.3.4. 5% of fuses of all types and rating. 20.4. Consumables Following consumables are required 20.4.1. A4 size paper for laser and ink-jet printer :1000 sheets 20.4.2. A3 size paper for laser and ink-jet printer :1000 sheets 20.4.3. Fan-fold printer for dot-matrix printer :1 carton 20.4.4. Toner cartridge for laser printer :1 no. 20.4.5. Toner cartridge (one of each colour) for colour ink-jet printer :1 set. 20.4.6. Ribbon cartridge for dot-matrix printer :1 no. 20.4.7. Fuses of all types and rating: 50 nos each 21. INFORMATION REQUIRED WITH THE BID Following information is required to be submitted with the bid: 21.1. Technical Details 21.1.1. Point-wise compliance with specifications. Separate deviation list if any. No deviation taken shall be interpreted as compliance to specification. 21.1.2. Proven Track Record (PTR). Vendor shall indicate installations of similar systems and the period for which they are in continuous operation for more than 2 years. 21.1.3. One-line architecture diagram of the offered system. d Preliminary drawing of operator console. 21.1.4. Complete bill of material of the system offered including all spares. This shall be properly segregated sub-system wise. All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS Page 77 of 124 21.1.5. List of all licensed software proprietary and bought out along with the quantity. 21.1.6. Catalogues, technical specifications for all hardware; in particular for the following: 21.1.6.1. OS/ES 21.1.6.2. Controller CPU/S 21.1.6.3. All types of I/O modules 21.1.6.4. All termination assemblies 21.1.6.5. Communication networks 21.1.6.6. All bought outs 21.1.7. CPU sizing details. 21.1.8. Power supply sizing details. 21.1.9. Expected total power supply consumption and heat dissipation. 21.1.10. Earthing requirements 21.2. Commercial Details 21.2.1. Cost of hardware and software segregated sub-system wise. 21.2.2. All taxes duties as applicable. 21.2.3. Lumpsum cost for erection up to mechanical completion of the system 21.2.4. Lumpsum cost for pre-commissioning and commissioning assistance. 21.2.5. Man-day rates applicable after end of the period stipulated for pre-commissioning and commissioning. 21.2.6. Rates quoted for activities above shall consider 6 day working per week with an average of 10 working hours per day. 21.3. Unit Rates for Addition / Deletion 21.3.1. Annexure III gives the rates to be quoted for addition / deletion. These shall be filled in by the vendor at the time of final submission of commercial offer. Unit rates shall be filled for all the items by the vendor. For yellow highlighted items, some notional quantity against each, is indicated. These items shall not be ordered but the total value computed for these items (based on notional quantity and unit rate quoted) shall be loaded in the main offer to arrive at the final price comparison. For items where no quantities are indicated, the costs shall not be added for cost comparison. 21.3.2. Vendor shall indicate the applicable taxes, packing forwarding and shipment costs to site, separately, for each item. The unit rates quoted shall be valid till SAT and final acceptance of the system. 21.3.3. The offer shall not be considered unless the table in Annexure III is filled by vendor and submitted along with final offer. All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS Page 78 of 124 21.4. SPECIAL REQUIREMENTS FOR THE PROJECT 21.4.1. Bidder shall include in cost all engineering changes till IFAT. No change order shall be raised for any changes in software engineering till FAT. Hardware changes shall be as per unit rates quoted as per Annexure III. 21.4.2. No extra claim for any software changes shall be accepted. Number of graphics & logics shall be provided to fulfil all the INDORAMA ICS requirements for the operation of plant. DCS vendor to consider the same. 21.4.3. There are 3 Nos existing ammonia refrigeration compressors in the plant. This compressor IO count is included in Annexure-I. Client shall replace these compressors in future. However, the new compressor IO types will be different than the current IO. Hence in future client may add related hardware for accommodating these new compressors IO’s in the same DCS. 21.4.4. There shall be additional space to be provided in the panels in addition, for mounting hardware components e.g., IO modules, TB’s, relay boards, Isolators, IO nests, Bulk power supply, NW switches etc. 21.4.5. However, software & CPU requirements to be considered now itself for above mentioned IO count. 21.4.6. AI/AO IO cards shall be HART Passthrough. 22. SR. NO. 1. 2. 3. 4. 5. DOCUMENTATION REQUIREMENTS DOCUMENT FOR INFORMATION AFTER PO/LOI FOR APPROVAL AFTER PO/LOI TIME COPIES (PRINTS ) SCH. WEEK INDORAMA ICS TIME COPIES (PRINTS) SCH. WEEK INDORAMA ICS FINAL COPIES S (1) P (1) Architecture (one line diagram of the offered system Detailed bill of material up to module level 1 1S 1 6 2 1S 1 6 Bill of material with catalogues for bought out items Proposed organization chart for project execution Detailed project schedule 2 1S 1 6 1S 1 6 1S 1 6 2 All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA 6. 7. 8. Standard dimensional and layout drawings for: ❖ Operator consoles ❖ Auxiliary consoles ❖ All cabinets Calculation of total power requirements at different voltage levels Calculation of heat Dissipation SPECIFICATIONS FOR DCS Page 79 of 124 3 1S 1 6 3 1S 1 6 3 1S 1 6 9. Earthing scheme 3 1S 1 6 10. Nest 4 1S 1 6 11. Logic drawings 6 1S 1 6 12. System tag data base 6 1S 1 6 13. Print outs of graphics 6 1S 1 6 14. Typical loop schematics 6 1S 1 6 15. Final loop drawings 10 1S 1 6 16. Loading calculations for: ❖ Controller CPU’s ❖ Communication Networks 6 1S 1 6 loading and i/o assignment FOR INFORMATION AFTER PO/LOI SR. NO. DOCUMENT 17. FAT procedure 18. Standard system Documentation available like: ❖ Installation and instruction manual ❖ Software ref. manual ❖ Algorithm library ❖ Any other TIME SCH. WEEK COPIES (PRINTS ) INDORAMA ICS FOR APPROVAL AFTER PO/LOI TIME COPIES (PRINTS) SCH. WEEK INDORAMA ICS 12 FINAL COPIES S (1) P (1) 1S 1 6 1S 1 6 All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA 22.1.1. SPECIFICATIONS FOR DCS Page 80 of 124 Abbreviations: S : Soft copies (.pdf files) P : Prints 22.1.2. Notes: 22.1.2.1. For Vendor documentation, wherever review/approval is specified, soft copy shall be sent to INDORAMA ICS Once the document is reviewed / approved, final sets of documents shall be sent to INDORAMA ICS office for further compilation as per address mentioned in Purchase order. These shall not be dispatched to site directly. 22.1.2.2. Drawings to be submitted for approval shall be submitted as per timeline indicated above and in line with order specifications. Any deviations with respect to order specifications shall be listed separately. In absence of same, order specification will be governing document. It is vendor responsibility to get drawings approved and if required vendor to visit Client office to get drawings approved. Delivery period shall be as per terms and conditions of Purchase order and any delay in drawing approval will not be considered as reason for delay in delivery. . 22.1.3. As-built drawings Vendor’s site representative shall mark-up all the engineering modifications done at site on one master copy at site. The mark-ups shall be transferred to Client’s copy periodically. THREE master copies to be maintained by him at site. The changes made at site in the master copy shall be incorporated in “As-built” documentation to be submitted by the vendor as per requirements given above. All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS Page 81 of 124 COMPLIANCE DECLARATION & PTR Please note that vendor shall indicate his replies to the following points without which the offer shall be liable for rejection. Deviations, if any, from INDORAMA ICS specifications, shall be listed in the enclosed format (List of Deviations) indicating the applicable specification clause. The vendor will be made liable for full compliance with the specification requirements, if deviations are not listed in ‘List of Deviations’, as it will be deemed as ‘No deviation’. SR. NO. DESCRIPTION EXPECTED REPLY 1. Confirm that all deviations against INDORAMA ICS specifications are consolidated under “List of Deviations”. Deviations mentioned elsewhere will not be taken into consideration. 2. Confirm that a soft copy of the technical bid, as per the attached format, is submitted with the technical offer. 3. Confirm that there is no discrepancy in the technical details outlined in the hard and soft copy of the offer. 4. Relevant Catalogues / literature giving specifications for all models offered including sizing data is enclosed with the offer. 5. Relevant Catalogues/specifications of all bought out items is enclosed with the offer. No Deviation 6. Quoted for Spare parts recommended for 2 years continuous trouble-free operation along with listing. 7. Quoted and offered recommended Commissioning spares along with listing. Quoted 8. Quoted for ‘Mandatory spares’ if specified in INDORAMA ICS specifications along with listing. Quoted CONFIRMATION BY VENDOR REMARKS Yes No Discrepancy Yes Yes Quoted All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA 9. Confirm that PTR form, as per attached format, is submitted with the technical offer in any of the following cases: a) Vendor has not supplied the item to INDORAMA ICS. b) Items/ part items not supplied to INDORAMA ICS. c) INDORAMA ICS Enquiry specifically asks for PTR. (Signature of Vendor) Name: Designation: Date: SPECIFICATIONS FOR DCS Page 82 of 124 Yes (Company Seal) LIST OF DEVIATIONS Doc. No: Sr. Clause No. Subject / Description Deviation Page No. No. All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA (Signature of Vendor) Name: Designation : Date : SPECIFICATIONS FOR DCS Page 83 of 124 (Company Seal) PROVEN TRACK RECORD I) Vendor to submit the filled PTR form as part of the initial offer itself in the following cases: (a) Vendor has not supplied the item to INDORAMA ICS (b) The vendor offer contains items / part items not supplied by vendor to ICS INDORAMA. e.g. accessory like Solenoid valve, limit switch, I/O card, control valve body etc. (c) PTR form is specifically required as per the INDORAMA ICS enquiry specification. II) PTR form, when required to be filled in, shall be submitted by vendor as part of the initial offer failing which their offer shall not be processed further. III) Vendor to fill the respective clause in the 'Compliance Declaration' form correctly. IV) Vendor to submit the PTR details in the format given below. All entries shall be for items which have been commissioned for more than a year. Vendors are required to fill out the contact details of the person (from End customer) from whom feedback regarding operation of item can be taken. All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS Page 84 of 124 PTR FORM Sr. No. Product / Accessory End Customer Country Plant / Project name Date of Supply Date of Comm. End customer contact details Name Tel. No. Mobile No. E-mail id 1 2 3 4 5 All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS Page 85 of 124 ANNEXURE-I INPUT / OUTPUT REQUIREMENTS REDUNDANT INPUTS OUTPUTS 86 30 10 8 30 16 10 45 66 6 25 10 20 30 10 8 30 16 10 45 75 6 25 10 30 30 20 70 40 20 10 330 480 16 220 190 144 150 192 246 122 102 768 1056 48 TAS COMMON 54 0 108 0 0 0 0 610 WB 238 20 0 WOB DO-MCC (THROUGH RELAY 22 TAP WOB AO 4-20 mA HART WI DI-MCC (THROUGH RELAY) WOB DI-SWITCH (THROUGH RELAY) 280 WB 220 20 WI WOB DI -SWITCH/PROXI. THERMOCOUPLE RTD AI (4-20 mA HART) WOB AI (4-20 mA) MCC WI 55 WI 50 35 WOB DO AO(4-20 mA HART) DI 105 50 0 THERMOCOUPLE 74 SAP-1 TOTAL INCLUDING (20% spare) CONTACT 50 WI WOB WB UNIT RTD AI 4-20 mA HART CONTACT SOV/OTHERS (THROUGH WETTED RELAY OUTPUTS WOB INPUTS NON REDUNDANT 355 ABBREVIATIONS: WB: WITH SAFETY BARRIERS WOB: WITHOUT SAFETY BARRIERS WI: WITH ISOLATOR The I/O count given above does not include the digital / analog inputs used to generate hardware alarms like fan failure, high cabinet temperature, bulk power supply failure, etc. For such alarms vendor should estimate separate dedicated hardware for implementation. These shall not be consumed from the available spares. All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS Page 86 of 124 SERIAL LINK/ SUB SYSTEM REQUIREMENTS Sr. No. Unit System Location Description Type of serial link Single/ RS485 , Modbus RTU/ Mod bus TCP Single/ RS485 , Modbus RTU/Modbus TCP 1 Serial links Maximum no. dedicate of tag d (D)/ or information through flow controller (C) 50 Meter Dedicated 50 1 50 Meter Dedicated 50 Single/ RS485 , Modbus RTU/Modbus TCP Single/ RS485 , Modbus RTU/Modbus TCP Single/ RS485 , Modbus RTU/Modbus TCP Single/ RS485 , Modbus RTU/Modbus TCP 1 50 Meter Dedicated 50 1 50 Meter Dedicated 50 1 50 Meter Dedicated 50 2 50 Meter Dedicated 50 1 SAP-1 TURBO BLOWER VOITH GOVERNER SAP-1 CABINET ROOM 2 SAP-1 TURBO BLOWER VIBRATION MONITRING SYSTEM SAP-1 CABINET ROOM 3 ACID COOLER ANODIC PROTECTION SAP-1 CABINET ROOM 4 TAP WOODWARD TAP GOVERNER CABINET ROOM 5 TAP VIBRATION MONITORING SYSTEM TAP CABINET ROOM 6 TAP ELECTRICAL TAP PROTECTION RELAY/EXICTATION CONTROLLER CABINET ROOM Distance No. of from Rack serial Room links ( Note 2) per system All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA 7 5 6 6 7 TAS WOODWARD TAS GOVERNER CABINET ROOM Single/ RS485 , Modbus RTU/Modbus TCP TAS VIBRATION TAS CABINET Single/ ROOM MONITORING RS485 , SYSTEM Modbus RTU/Modbus TCP TAS ELECTRICAL TAS CABINET Single/ ROOM PROTECTION RS485 , RELAY/EXICTATION Modbus CONTROLLER RTU/Modbus TCP AIR COMPRESSORS COMMON FIELD Single/ RS485 , Modbus RTU/Modbus TCP ELECTRICAL COMMON MCC/CABINET Single/ ROOM PROTECTION RS485 , RELAY, Modbus NUMERICAL RTU/Modbus RELAYS TCP SPECIFICATIONS FOR DCS 1 50 Meter Dedicated 50 1 50 Meter Dedicated 50 2 50 Meter Dedicated 50 4 300 Meter Dedicated 50 6 150 Meter Dedicated 50 Page 87 of 124 NOTES: 1) The I/O count given above does not include the digital / analog inputs used to generate hardware alarms like fan failure, high cabinet temperature, bulk power supply failure, FF physical layer diagnostic alarms, etc. For such alarms vendor should estimate separate dedicated hardware for implementation. These shall not be consumed from the available spares. 2) Modbus Cable shall be 2 Pair Twisted Individual & Overall Screen Armoured Cable, 18AWG copper conductor, armoured, with overall screen, PVC insulation, PVC sheath to be included by vendor. The exact cable length shall be decided during detail engineering. 3) Applicable standard for MODBUS cable : EN50288, IEC60331, IEC60332 All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS Page 88 of 124 ANNEXURE-III SR. NO. I/O LIST AND BOM QUOTED BY DIFFERENT VENDORS A I/O SUMMARY CR-1 Description 1 2 3 4 5 6 7 8 Quantity Model No. Quantity Reqd. Comments Model No. Quantity Reqd. Comments Model No. Quantity Reqd. Comments Quantity Model No. Quantity Comments Model No. Quantity Reqd. Comments Model No. Quantity Comments Quantity Model No. Quantity Comments Model No. Quantity Reqd. Comments Model No. Quantity Comments 4~20mA anlaog inputs (nonredundant) with and without barriers Pulse inputs (non-redundant) with and without barriers Digital inputs (redundant) proximity + contact Digital inputs (nonredundant) proximity + contact Digital outputs (redundant) for SOV & Others Digital outputs (non-redundant) for SOV & Others 10 FF inputs + outputs B I/O SUMMARY CR-2 Description 4~20 mA analog inputs (redundant) with and without barriers 4~20 mA outputs (redundant) with and without barriers 3 4~20mA anlaog inputs (nonredundant) for open loops with and without barriers Digital inputs (redundant) proximity + contact 4 Digital inputs (nonredundant) proximity + contact 5 Digital outputs (redundant) 6 Digital outputs (non-redundant) C I/O SUMMARY CR-3 Description 1 VENDOR 3 Pulse inputs (non-redundant) RS-485 Modbus Inputs 2 VENDOR 2 4~20 mA analog inputs (redundant) with and without barriers 4~20 mA analog outputs (redundant) with and without barriers 9 1 VENDOR 1 4~20 mA analog inputs (redundant) for closed loops with and without barriers All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA 2 3 Others 5 FF inputs + outputs OTHER HARDWARE REQUIRED 1 FTA/Terminal Board for 4~20mA analog inputs (redundant) 2 FTA/Terminal Board for 4~20mA analog inputs(non-redundant) 3 FTA/Terminal Board for 4~20mA analog outputs (redundant) 4 FTA/Terminal Board for digital inputs (redundant) 5 FTA/Terminal Board for digital inputs (non-redundant) 6 FTA/Terminal Board for digital outputs (redundant) 7 FTA/Terminal Board for digital outputs (non-redundant) 8 Special high capacity relays to drive DC loads of HT switchgear 9 HART Multiplexer Slaves 16 points 10 Hart Multiplexer Masters 16 points HART Patch Cards 16 points 11 Redundant Power Supplies for I/O modules including installed spares 12 13 14 15 Page 89 of 124 4~20 mA analog outputs (redundant) for closed loops with and without barriers 4~20mA anlaog inputs (nonredundant) for open loops with and without barriers Digital inputs (nonredundant) proximity + contact Digital outputs (nonredundant) for SOV & 4 D SPECIFICATIONS FOR DCS Model No. Quantity CR1/CR2/CR3 Comments Model No. Quantity CR1/CR2/CR3 Comments Model No. Quantity CR1/CR2/CR3 Comments Model No. Quantity CR1/CR2/CR3 Comments Model No. Quantity CR1/CR2/CR3 Comments Model No. Quantity CR1/CR2/CR3 Comments Redundant FF Power Supplies 500 mA with advanced diagnostic modules Segment protectors 12 way, mounted in FRP/Polycarbonate junction boxes with surge arresters, terminators, and terminals for trunk and spur cables Surge arresters in control room, one per segment. OS consisting of dual 22" TFT screen, Membrane Keyboard,Optical Mouse, PC,etc. Engineering station / server consisting of single 24” led screen, Qwerty Keyboard, 16 Optical Mouse, Server 17 Network Laser Printer A3/A4 size B/W 18 Colour Laser Network Printer A3/A4 19 Serial Gateway * port for third party devices 20 Ethernet Switch 21 Redundant Controller with redundant I/O communication and redundant Ethernet communication 22 Firewall 23 HART maintenance PC workstation with 22" TFT screen, Qwerty Keyboard, Optical 24 Mouse, 25 I/O racks 26 FO Cable with patch cards, LIU and other hardware for redundant RIO link and data highway extension to CEU control room. 27 External Firewall to interface to client's LAN. 28 E BOUGHT OUT ITEMS All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA 1 Barriers + isolators for analog inputs single channel 2 Barriers + isolators for analog outputs single channel 3 Barriers for digital/proximity inputs 4 Trip amplifiers (HART pass through) 5 Off-delay timers ǔP Digital indicators ǔP One Loop Controllers 6 Panel to house the above indicators/controllers ǔP Alarm Annunciator 16 windows along with hooter and test/reset/acknowledge Push buttons 7 Illuminated push buttons 8 Two position selectord switches Key switches 9 Indicating lamps 10 Console to mount the above push buttons/lamps /switches 11 MCBs double pole of different ratings (for TKIS-India use only) 12 MCCBs to isolate incoming power supply from UPS 13 Voltmeter/ammeter/CTs for ammeter etc.for incoming power supply. Signal distributor (1 input, 2 outputs) for analog inputs 14 Single channel isolation amplifier 1 input 2 outputs for proximity inputs DIN rail mounted relays 2NO+2NC SPECIFICATIONS FOR DCS Page 90 of 124 15 16 17 18 19 20 21 F CONTROL ROOM FURNITURE 1 Operator console 2 Engineering stn/server + printer table 3 Chairs 4 Printers tables 5 Corner consoles G LICENSED SOFTWARE 1 MS WINDOWS FOR OS,ES/Servers, HMS 2 Portable CD/DVD read / write driver software OS run time software 2 MS office software 3 ES software consisting of tag database generation, graphics, loop and logics, sequences, trends, self tuning, alarms & events, diagnostics, etc. 4 Server software if required; including redundancy software, and other special software if any. 5 HMS software for unlimited tags 6 OPC server DA software for unlimited tags 7 Controller software including redundancy 8 Controller firewall software 9 Special documentation software to enable printouts of logics, loops, tag database, etc. from ES / exporting the same to MS Office. 10 Log reports software for OS Modbus driver software Quantity CR1/CR2/CR3 Comments Quantity CR1/CR2/CR3 Comments Quantity CR1/CR2/CR3 Comments Quantity CR1/CR2/CR3 Comments Quantity CR1/CR2/CR3 Comments Quantity CR1/CR2/CR3 Comments All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA 11 Extetnal Firewall software 12 Third party diagnostic software for FF physical layer diagnostics SPECIFICATIONS FOR DCS Page 91 of 124 13 14 H CONSUMABLES 1 Colour printer cartridge for printer 2 B&W printer cartridge for B&W printers 3 A4 size sheets for printer 4 A3 size paper for A3/A4 printer 5 Fuses Quantity CR1/CR2/CR3 Comments Quantity CR1/CR2/CR3 Comments Quantity CR1/CR2/CR3 Comments All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS Page 92 of 124 ANNEXURE-III APPLICABLE HARDWARE UNIT RATES FOR ADDITION / DELETION Sr. No. Description UOM Qty. 1 Analog input module (redundant) with all accessories like terminal board, pre-fab cable etc. for closed & open loops nos. 1 2 Analog output module (redundant) with all accessories like terminal board, pre-fab cable etc. for closed & open loops loops nos. 1 3 Analog input module (nonredundant) with all accessories like terminal board, pre-fab cable etc. for open loops nos. 1 4 Analog output module (nonredundant) with all accessories like terminal board, pre-fab cable etc. for open loops nos. 1 5 Digital input module (redundant) with all accessories like terminal board, pre-fab cable etc nos. 1 6 Digital input module (nonredundant) with all accessories like terminal board, pre-fab cable etc. nos. 1 7 Digital output module (redundant) with all accessories like terminal board, pre-fab cable etc. nos. 1 8 Digital output module (nonredundant) with all accessories like terminal board, pre-fab cable etc. nos. 1 9 Digital input module for SOE 10 Pulse input module with all accessories like terminal board, pre-fab cable etc. Unit rate (USD) Total Price (USD) Taxes P&F Transport Cost 1 nos. 1 All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA 11 Serial interface input module with all accessories 12 RTD input module 1 13 T/C input module 1 14 Set of redundant controller CPU module with redundant power supply modules and redundant communication interface with data highway and I/O bus along with all accessories. nos. 1 15 Relay boards for DI with 16 relays nos. 1 16 Relay boards for DI with 32 relays nos. 1 17 Relay Boards for DO with 16 relays nos. 1 18 Relay boards for DO with 32 relays nos. 1 19 AI Barriers nos. 1 20 AO Barriers nos. 1 21 DI barriers (for proximity switches) single channel nos. 1 22 DI barriers (for proximity switches) double channel nos. 1 23 DI barriers (for proximity switches) single channel 1 input X 2 outputs nos. 1 24 DO barriers nos. 1 25 RTD barriers nos. 1 26 T/C barriers nos. 1 27 Trip Amplifiers with two independently adjustable alarm settings nos. 1 28 Distributors 1 no. 4~20 mA input X 2 nos 4~20 mA outputs nos. 1 29 Digital timers on/off delay delay setting between 1~500s nos. 1 30 DIN Rail mounted relays 2NO/NC nos. 1 31 SIL approved relay 2 NO/NC nos. 1 32 Push Buttons nos. 1 33 Illuminated Push Buttons nos. 1 nos. SPECIFICATIONS FOR DCS Page 93 of 124 1 All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA 34 Two Position Selector Switches nos. 1 35 Key Switches nos. 1 36 Indicating Lamps nos. 1 37 MCBs nos 1 38 Redundant FF power supply module 500 mA nos. --- 39 Redundant FF H1 card nos. --- 40 Advanced diagnostic module for FF physical layer nos. 1 41 FF Terminators nos. --- 42 FF segment surge arresters nos. --- 43 Segment protector 12 way for FF spurs mounted in FRP/polycarbonate JB complete with surge protector, terminator, terminals, and other necessary hardware nos. 1 44 HART patch card 16 pt nos. 1 45 HART multiplexer slave 16 pt nos. 1 46 HART Multiplexer master 16 pt nos. 1 47 Armoured Modbus Communication cable nos. 1 0 48 Armoured FO cable 4 fibre with necessary hardware as below m 1 0 (a) Patch Card nos. 1 (b) Patch Panel nos. 1 (c )FO converter nos. 1 (d) Terminators nos. 1 m 1 (a) Patch Card nos. 1 (b) Patch Panel nos. 1 (c )FO converter nos. 1 (d) Terminators nos. 1 50 Man-day rates beyond stipulated minimum period nos 1 0 51 Marshalling Cabinet nos 1 0 49 Armoured FO cable 6 fibre with necessary hardware as below SPECIFICATIONS FOR DCS Page 94 of 124 0 All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA 52 System cabinet nos 1 0 53 Power distribution board nos 1 0 54 Power module nos 1 0 (a)Power supply unit 10A nos 1 0 (b)Power supply unit 20A nos 1 0 (c)Power supply unit 40A nos 1 0 55 Ethernet switch *****port nos 1 0 56 I/O Point addition/deletion services beyond 5% of wired I/Os nos 1 0 TOTAL SPECIFICATIONS FOR DCS Page 95 of 124 0 Final cost including taxes, packing forwarding and transport All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS Page 96 of 124 ANNEXURE-IV BIDDER to fill in the complete form for technical comparison purpose. All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS SOFTWARE WISE OSI, PLATFORM INDEPENDENT BOUGHT OUT ITEM AVAILABLE IN OPEN MARKET, LIKE SERVER , MEMORY, PRINTERS, ETC.. AVAILABLE IN OPEN MARKET YES REAL TIME SYSTEM TRANSPARENT TO OUT SIDE NETWORK Page 97 of 124 DATA YES, THRU TCP/IP OVER ETHERNET HARDWARE FOR PLANT MIS (LAN) USER WRITTEN "C++" OR ANY OTHER YES, SUPPORT HIGH LEVEL LANGUAGE REQUIRED FOR C, C++ PROGRAM FOR ANY APPLICATION OR VB APPLICATION APART FROM CONTROL PROCESSOR’S STANDARD ALGORITHEMS SUPPORT FOR ANY 3RD PARTY YES SOFTWARE RUNNING IN THE SYSTEM MAIN FILE SERVER OR WORK STATION COMM. WITH ANY OTHER 3RD PARTY YES (DDE/OPC/ODBC, PACKAGES LIKE MICROSOFT OR ETC.) ORACLE TAG DATA AVAILABILITY OPERATING SYSTEM PROMPT AT YES APPLICATION PROGRAM INTERFACE YES, THROUGH USER SOFTWARE FOR REAL TIME DATA WRITTEN PROGRAM MANIPULATION 12 MAIN SYSTEM HARDWARE 13 MAIN SYSTEM SOFTWARE (O.S.) LATEST 14 RDBMS ORACLE/SQL SERVER WITH LATEST SOFTWARE VERSION AT THE TIME OF All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS Page 98 of 124 SUPPLY 15 IF OPERATING SYSTEM IS WINDOWS YES, BIDDER TO GIVE NT, VIRUS PROTECTION FOR THE ALL DETAILS ENITRE SYSTEM 16 SOFTWARE / FIRM WARE UPGRADE YES FOR THE NEXT FIVE YEARS AT FREE OF COST 17 SYSTEM HARDWARE , SOFTWARE AND ALL BOUGHT OUT ITEMS , INCLUDING ANY FIRMWARES ARE HAVING PROVEN TRACK RECORD FOR INDIAN OR ABROAD MARKET 18 SYSTEM CONFIGURATION CAN BE DONE ON LINE OR OFF LINE YES, VENDOR TO PROVIDE PTR DETAILS WITH RUNNING INSTALLATION YES, BOTH SYSTEM CONFIGURATION BOTH, THERE SHALL DEVELOPMENT TOOL IN SYSTEM / BE MIN. TWO P.C. ENGINEERING STATION, INDEPENDENT OF EACH OTHER, FROM WHERE COMPLETE PLANT DATABASE/ SYSTEM CONFIGURATION/GRAP HIC GENERATION ETC. CAN BE DEVELOPED/ DEPLOYED MAX. TAGS SUPPORTED BY THE SYSTEM MIN. 10,000 ON LINE CONTEXT SENSITIVE HELP YES, AT EACH LEVEL ADDITION OR DELETION OF ANY I/O YES MODULE IN RUN TIME ADDITION OR DELETION OF ANY BONUS CONTROL STATION IN RUN TIME ADDITION /DELETION OF ANY SINGLE YES OPEN AND CLOSE LOOP IN RUN TIME All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA BUILDING A NEW GRAPHIC MODIFICATION IN RUN TIME MODIFICATION OF STRATEGY IN RUN TIME SPECIFICATIONS FOR DCS Page 99 of 124 OR YES CONTROL YES CHANGE OF ANY TAG NAME IN RUN TIME YES CHANGE OF ANY SOFTWARE YES CONNECTION IN CONTROLLER IN RUN TIME 19 SECURITY WITH DIFF. LEVEL OF PASSWORD FOR DIFF. CATEGORY OF OPERATION MAIN FILE SERVER ( ENGINEERING TOTAL QTY.-2 STATION) PROCESSOR LATEST GRADE PROCESSOR SERVER RAM 32 GB MIN. SSD 1TB GB MIN. , RAID-I, HOTSWAPPABLE FOR ALL THE STATIONS, WHERE PROJECT, SYSTEM CONFIGURAITON DATABASE AS WELL AS HISTORICAL TREND, LOGS, ETC. RESIDES. THIS MAY INCLUDE OPERATOR STATIONS ALSO, DEPENDING SYSTEM ARCHITECTURE PORTABLE USB SSD YES DVD WRITER YES All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS DISPLAY 24” wide screen LED type colour monitor only, 1 NO. WITH EACH ENGINEERING STATION. MIN. DISPLAY RESOLUTION 1024X768 REDUNDANCY OFFERED FOR SSD 1 TB MIN. , RAID-I, HOTSWAPPABLE FOR ALL THE STATIONS, WHERE PROJECT, SYSTEM CONFIGURAITON DATABASE AS WELL AS HISTORICAL TREND, LOGS, ETC. RESIDES. THIS MAY INCLUDE OPERATOR STATIONS ALSO, DEPENDING SYSTEM ARCHITECTURE SERIAL / PARALLEL PORTS MIN. 2 EACH TYPE DOT MATRIX PRINTERS NOT REQUIRED INKJET PRINTERS MIN. 1 A3 SIZE WITH EACH ENGINEERING STATION, LOCALLY ACCESSIBLE FROM THAT PARTICULAR ENGGINEERING STATION. (TOTAL =2 FOR 2 NOS. OF ENGINEERING STATION) DISK USAGE LIMIT YES , FEATURE Page 100 of 124 SYSTEM All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA 20 SPECIFICATIONS FOR DCS SECURITY WITH DIFF. LEVEL OF PASSWORD FOR DIFF. CATEGORY OF OPERATION FILE , DIRECTORY LEVEL SECURITY YES ETHERNET PORT FOR MIS / XWINDOWS YES , 1 MIN ON EACH MACHINE IN THE COMPLETE SYSTEM Page 101 of 124 WORKSTATION PROCESSOR MAKE / MODEL / SPEED LATEST GRADE PROCESSOR SEREVR AVAILABLE RAM 32 GB MIN. HDD 1 TB MIN. , RAID-I, HOTSWAPPABLE FOR ALL THE STATIONS, WHERE PROJECT, SYSTEM CONFIGURAITON DATABASE AS WELL AS HISTORICAL TREND, LOGS, ETC. RESIDES. THIS MAY INCLUDE OPERATOR STATIONS ALSO, DEPENDING SYSTEM ARCHITECTURE DVD WRITER YES SERIAL / PARALLEL PORTS MIN. 2 PORTS OF EACH TYPE DOT MATRIX PRINTERS 132 COLUMN, MIN. 2 , ONE FOR LOG AND ONE FOR ALARM , BOTH SHOULD HAVE GLOBAL ACCESSIBILITY VIA ETHERNET NETWORK PRINTER PORT. All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS INKJET PRINTERS MINIMUM 1 NO. OF A3 IZE INKJET PRINTER WITH ETHERNET INTERFACE, WHICH IS GLOBALLY ACCESSIBLE FROM ALL OPERATOR STATIONS ON NETWORK FOR COLOUR GRAPHIC/TREND PRINTING. (GRAND TOTAL= 3 NOS. OF PRINTERS) DISK USAGE LIMIT YES , FEATURE ETHERNET PORT FOR MIS / XWINDOWS YES, MIN. ONE NO. DISPLAY SIZE 24” WIDE SCREEN LED TYPE COLOUR MONITOR DISPLAY RESOLUTION MIN. 1024x768 MOUSE AND KEY CONCURRENT OPERATION Page 102 of 124 SYSTEM BOARD YES QWERTY TYPE ENGINEERING KEY BOARD YES , 1 NO. MEMBRANE TYPE OPERATION KEY BOARD YES, 1 NO. TOUCH SCREEN YES MIN. DISPLAY CALL UP TIME FOR MAX. MAX. 2 SEC. LOADED GRAPHIC DISPLAY REFRESH RATE MAX. 2 SEC. LIMIT ON NOS. OF DYNAMIC POINT IN NO LIMIT A SINGLE GRAPHIC GLOBAL CONTROLS OF ANY PLANT YES AREA FROM ANY WORKSTATION GRAPHICS All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS Page 103 of 124 MASKING, ACCESS LIMIT OF ANY YES GRAPHICS OR PART THEREOF BY PASSWORD COMMON STATION FOR OPERATION YES AND ENGINEERING ANY OTHER FEATURES * LIMITATIONS NO LIMITATIONS 21 TYPE OF PRINTER SUPPORTED RS232C/USB SERIAL AND CENTRONICS PARALLEL / ETHERNET NETWORK PRINTERS 22 INK JET PRINTERS A3 SIZE INKJET , SERIAL INTERFACERS323C/US B PRINTER , MIN. 300 DPI RESOLUTION, AVAILABLE IN OPEN MARKET MIN. 1 NO. WITH EACH ENGINEERING STATION (TOTAL 2 ENGG. STATION) AND MIN. 1 NO. OF A3 SIZE INKJET PRINTER WITH ETHERNT NETWORK PORT FOR ALL OPERATOR STATIONS, GLOBALLY ACCESSIBLE All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA 23 NOS. OF PRINTERS SUPPORTED SPECIFICATIONS FOR DCS Page 104 of 124 MIN. 3 NOS. 1 NO OF ALARM PRINTER( 132 COLUMN DOT MATRIX, ETHERNET PORT), 1 NOS. OF LOG PRINTER (132 COLUMN, ETHERNET PORT) AND 1 NO. OF VIDEO COPIER(A3 INKEJT WITH ETHERNET PORT) ADDITIONALLY THERE SHALL BE A3 SIZE INKJET PRINTER ALONG WITH EACH ENGINEERING STATION AS SPECIFIED ABOVE. 24 VIDEO COPIER GLOBAL ACCESS 25 CONTROL STATION AND PRINTER YES, MUST VIA ETHERNET PORT AS A NETWORK PRITNER TYPE OF PROCESSOR / SPEED 64 BIT MINIMUM PROCESSOR USER RAM MIN. 32 MB MIN. CYCLE SCANNING TIME FOR INPUT 50 M SEC MIN. CYCLE TIME FOR ALGORITHM EXECUTION 250 MSEC OR BETTER MIN. CYCLE TIME FOR OUTPUT WRITING 50 MSEC NORMAL SOFTWARE LOADING 30% SOFTWARE LOADING IN WORST CONDITION 40% FUTURE MARGIN SOFTWARE LOAD AVAILABLE IN 50% All rights reserved SPECIFICATIONS FOR DCS DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA REDUNDANCY OFFERED 26 Page 105 of 124 YES , FULL, FAULT TOLERANT, HOT SWAPPABLE DIGITAL INPUT CARD NO. OF CHANNEL MAX. 16 CARD NOS. PER INTERROGATION VOLTAGE 24 V DC CHANNEL STATUS LED YES , PER CHANNEL CHANNEL ISOLATION ( CHANNEL TO YES, >1000V DC CHANNEL AND CHANNEL TO FIELD, OPTICALLY ISOLATED ALL CHANNEL SHALL HAVE AS PER IEC:XXX INDIVIDUAL ISOLATION, NO GROUP ISOLATED CARDS ARE ACCEPTED) 27 EARTH FAULT DETECTION CKT. YES, WITH ALARMS OVER CURRENT PROTECTION BY YES , WITH ALARMS LOOP CURRENT MAX. 2 AMP. SURGE WITH STAND CAPACITY YES , AS PER IEC:XXX SCAN RATE 50 MILLI SECOND OR BETTER REDUNDANCY NO Testable YES DIGITAL OUTPUT CARD NO. OF CHANNEL MA.X 16 PER CARD DRIVING VOLTAGE 24 V D.C. CHANNEL STATUS LED YES, PER CHANNEL CHANNEL ISOLATION ( CHANNEL TO OPTICALLY ISOLATED CHANNEL AND CHANNEL TO FIELD, ALL CHANNEL SHALL HAVE INDIVIDUAL ISOLATION, NO GROUP ISOLATED CARDS ARE ACCEPTED) EARTH FAULT DETECTION CKT. YES, WITH ALARMS OVER CURRENT PROTECTION BY YES, WITH ALARMS MAX LOOP CURRENT 2 AMP. SURGE WITH STAND CAPACITY YES, AS PER IEC:XXX SCAN RATE 50 MILLI BETTER SEC OR All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA 28 SHORT CIRCUIT PROTECTION YES, WITH ALARMS PROTECTION AGAINST BACK EMF. YES, AS PER IEC:XXX REDUNDANCY NO Testable YES SPECIFICATIONS FOR DCS Page 106 of 124 ANALOG INPUT CARD NO. OF CHANNEL MAX. 16 PER CARD TYPE OF INPUT SHALL BE CAPABLE OF ACCEPTING 4-20 MA INPUT FROM 2 WIRE AND 4 WIRE TRANSMITTERS, ALSO POWER UP 24 V DC TWO WIRE TRANSMITTER. SHALL HAVE MIN. 250 OHM RESISTOR, SO THAT HART COMMUNICATOR CAN BE PLACED IN PARALLEL WITHOUT DISCONNECTING THE TRANSMITTER LOOP AT ANY TIME DRIVING VOLTAGE 24 V D.C. CHANNEL STATUS LED YES CHANNEL ISOLATION ( CHANNEL TO YES, GALVANICALLY CHANNEL AND CHANNEL TO FIELD, ISOLATED ALL CHANNEL SHALL HAVE INDIVIDUAL ISOLATION, NO GROUP ISOLATED CARDS ARE ACCEPTED) EARTH FAULT DETECTION CKT. YES,WITH ALARMS OVER CURRENT PROTECTION BY YES,WITH ALARMS MAX LOOP CURRENT 100 mAMP SURGE WITH STAND CAPACITY YES, AS PER IEC:XXX SHORT CIRCUIT PROTECTION YES, WITH ALARMS TYPE OF ADC /RESOLUTION MIN. 13 BIT ACCURACY +/- 0.075% SCAN RATE 250 M SEC OR BETTER REDUNDANCY AS PER REQUIRMENT All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA Testable SPECIFICATIONS FOR DCS Page 107 of 124 YES 28.1 ANALOG OUTPUT CARD NO. OF CHANNEL MAX. 8 PER CARD OUTPUT 4-20 MA DC OUTPUT, ISOLATED IN MAX. 750 OHM CHANNEL STATUS LED YES CHANNEL ISOLATION ( CHANNEL TO YES, GALVANICALLY CHANNEL AND CHANNEL TO FIELD, ISOLATED ALL CHANNEL SHALL HAVE INDIVIDUAL ISOLATION, NO GROUP ISOLATED CARDS ARE ACCEPTED) 29 EARTH FAULT DETECTION CKT. YES,WITH ALARMS OVER CURRENT PROTECTION BY YES,WITH ALARMS MAX LOOP CURRENT 30 mAMP SURGE WITH STAND CAPACITY YES, AS PER IEC:XXX SHORT CIRCUIT PROTECTION YES, WITH ALARMS TYPE OF ADC /RESOLUTION MIN. 10 BIT ACCURACY +/- 0.1% SCAN RATE 1 SEC OR BETTER REDUNDANCY NO Testable YES THERMOCOUPLE INPUT CARDS MAX. NO. OF CHANNEL PER CARD 16 NOS. TYPE OF INPUT THERMOCOUPLES E,J,K,R,S,B,T, ETC.. CALIBRATION OF CARD AS PER AS PER ANSI:MC96.1 CALIB. FREQ.. REQUIRED MIN. CHANNEL ISOLATION ( CHANNEL TO YES, MIN 1000 VAC, CHANNEL AND CHANNEL TO FIELD, GALVANICALY ALL CHANNEL SHALL HAVE ISOLATED INDIVIDUAL ISOLATION, NO GROUP ISOLATED CARDS ARE ACCEPTED) ACCURACY +/- 0.1’C ADC RESOLUTION MIN. 13 BIT MIX. TYPE CONFIGURATION (i.e. DIFF. YES TYPES OF T/C FOR DIFF. CHANNEL OF SINGLE CARD) All rights reserved SPECIFICATIONS FOR DCS DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA 30 Page 108 of 124 INPUT ISOLATION GALAVANICALLY ISOLATED GROUNDED/UNGROUNDED INPUTS YES BURN OUT FEATURE YES , PER CHANNEL STATUS LED FOR IND. CHANNEL YES SCAN RATE 1 SECOND OR BETTER REDUNDANCY NO RTD INPUT CARDS MAX. NO. OF CHANNEL PER CARD 16 NOS. TYPE OF INPUT RTD SENSORS PT100 , 3 WIRE AND 4 WIRE AND OTHERS CALIBRATION OF CARD AS PER AS DIN:43760/IEC529 CALIB. FREQ.. REQUIRED MIN. PER CHANNEL ISOLATION ( CHANNEL TO YES, MIN. 1000 V AC CHANNEL AND CHANNEL TO FIELD, ALL CHANNEL SHALL HAVE INDIVIDUAL ISOLATION, NO GROUP ISOLATED CARDS ARE ACCEPTED) ACCURACY +/- 0.1 ‘C ADC RESOLUTION MIN. 13 BIT MIX. TYPE CONFIGURATION (i.e. DIFF. YES TYPES OF RTD FOR DIFF. CHANNEL OF SINGLE CARD) 31 INPUT ISOLATION GALVANICALLY ISOLATED 3 WIRE AND 4 WIRE RTD INPUTS YES SHORT CIRCUIT PROTECTION YES , WITH ALARMS OPEN CIRCUIT PROTECTION YES, WITH ALARMS STATUS LED FOR IND. CHANNEL YES, WITH ALARMS EARTH FAULT DETECTION CKT. YES, WITH ALARMS OVER CURRENT PROTECTION YES, WITH ALARMS SCAN RATE 1 SECOND OR BETTER REDUNDANCY NO CONTROLLER SYSTEM All rights reserved SPECIFICATIONS FOR DCS DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA CONTROLLER CAPACITY (An array of small controllers clubbed together to meet this specification will not be acceptable) Page 109 of 124 MIN. 100 CLOSED LOOPS AT 250 MILLI SECONDS, TOTAL I/O COUNTS SUPPORTED BY SINGLE CONTROL PROCESSOR SHALL BE MIN. 1000 NOS.CONTROLLER SHOULD BE CAPABLE OF MINIMUM EXECUTION TIME OF 50 MILLI SECONDS. CONTROL ALGORITHMS RUNNING IN MAIN CONTROL PROCESSOR AUTO TUNE AS STANDARD FEATURE YES , FOR ALL LOOPS BY DEFAULT MAX. ALGORITHM EXECUTION TIME 250 MSEC MIN. INPUT AND OUTPUT POLL TIME 50 SECOND BETTER MAX. LOAD APPLICATION FUTURE LOAD MARGIN FOR PRESENT 30% IN SOFTWARE 50% OR CONTROL PROCESSOR IS CAPABLE YES , FOR ALL LOOPS OF RUNNING THIRD PARTY PACKAGE SUPPORT FOR ALGORITHMS ALL STD. YES , FOR ALL STD. TYPES AS SPECIFIED IN ENQ. SPECS , INCLUDING SEQUENTILA,BATCH AND CONTINUOS CONTROL AND MATHS, LOGIC FUNCITON ON LINE MODIFICATION /ADDITION AND DELETION OF ANY LOOP OR LOOP TAG YES PEER TO PEER COMMUNICATION / LIMITATIONS YES WITHOUT TAG LIMIT ANY All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA PEER TO PEER COMMUNICATION LOAD SPECIFICATIONS FOR DCS Page 110 of 124 MIN. SOFTWARE PARAMETER NO INTERCONNECTION LIMIT DATA RETENTION TIME IN RAM MIN. 1000 HRS. SELF BOOTABLE YES CHECKPOINT FACILITY WITH AUTO SCHEDULING YES , AT REGULAR USER CONFIGURED INTERVAL CONTROL FACILITIES CONFIGURATION GUI BASED , SUPPORTED BY MOUSE AND KEY BOARD WITH ALL TYPES OF EDITING FEATURES AND ON LINE CONTEXT SENSITIVE HELP AUTOMATIC UPLOAD OF ANY RUN TIME CHANGES MADE IN CONTROL YES DATABASE 32 DOWNLOAD / BOOT TIME MIN. SECURITY WITH DIFF. LEVEL OF PASSWORD FOR DIFF. CATEGORY OF OPERATION REDUNDANCY YES, 100% REDUNDANT WITH FAULT TOLERANT FEATURES, HOTSWAPPABLE REDUNDANCY OFFERED AT I/O NO CPU YES (100% REDUNDANT WITH FAULT TOLERANT FEATURE WITH HOT SWAPPABLE CONFIGURATION) All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS INTERNAL BUSES YES (100% REDUNDANT WITH FAULT TOLERANT FEATURE WITH HOT SWAPPABLE CONFIGURATION) COMM. MODULE YES (100% REDUNDANT WITH FAULT TOLERANT FEATURE WITH HOT SWAPPABLE CONFIGURATION) MAIN NODE BUS YES (100% REDUNDANT WITH FAULT TOLERANT FEATURE WITH HOT SWAPPABLE CONFIGURATION) Page 111 of 124 POWER SUPPLY MODULES OF ALL YES (100% SYSTEM CARDS/MODULES/NODES REDUNDANT WITH FAULT TOLERANT FEATURE WITH HOT SWAPPABLE CONFIGURATION) CONTROLLERS YES REDUNDANT (100% WITH FAULT TOLERANT FEATURE WITH HOT SWAPPABLE CONFIGURATION) GATEWAYS YES (100% REDUNDANT WITH FAULT TOLERANT FEATURE WITH HOT SWAPPABLE CONFIGURATION) WORK STATIONS YES All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA 33 SPECIFICATIONS FOR DCS HDD YES (100% REDUNDANT WITH FAULT TOLERANT FEATURE WITH HOT SWAPPABLE CONFIGURATION) PRINTER BACK UP PORTS YES, INCASE OF FAILURE OF LOG OR ALARM PRINTER, THE OTHER WORKING PRINTER SHOULD AUTOMATICALLY RESUME THE ROLE OF THE FAILED PRINTER Page 112 of 124 COMMUNICATION TO PLC PROTOCOL MODBUS-RTU INTERFACE 2 WIRE RS485 MAX. LENGTH OF INTERFACE CABLE MIN. 1200 MTR. PERMITTED NO. OF PORTS ON SINGLE MODULE MULTIPLE MAX. BAUD RATES REQUIRED. MIN. 19200 MODULE REDUNDANCY YES BUS REDUNDANCY YES PARAMETER/SEC MAX. 1 SECOND WITH ANY TYPE OF MIX. CONFIGURATION TOTAL CAPACITY COMMUNICATION WITH ESTABLISHED GIVE THE NAMES OF ESD SYSTEMS FOR WHICH DCS VENDOR HAS ESTABLISHED COMMUNICAITONS SO FAR TOTAL LOADING FOR CONFIGURED <30% TAGS FUTURE MARGIN >50% LIMITATIONS NO All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS Page 113 of 124 OTHER FEATURES 34 COMMUNICATION AND PLC 35 WRITE BACK TO PLC FROM DCS 36 DCS CLOCK 37 BETWEEN DCS DCS BIDDER TO COORDINATE WITH PLC BIDDER FOR ESTABLISHING COMMUNICATION BETWEEN DCS AND PLC AND CONFIGURE REQUIRED INTERFACE / TAGS / DISPLAYS /DATABASE ETC. YES , WITH SECURITY FEATURES. HOWEVER THIS FEATURE SHALL NOT BE USED. TIME SYNCHRONIZATION METHOD WITH PLC YES STABILITY OF CLOCK +/- 1 SEC OND PER DAY TEMPERATURE EFFECT MIN. ALARMS SEQUENCE MAX. NOS. OF PROCESS ALARMS MIN. 10,000 MAX. NOS. OF SYSTEM ALARMS MIN. 5,000 SEGREGATION OF PROCESS AND YES WITH DIFF. SYSTEM ALARMS COLOUR/PRIORITY/HO OTER SOUNDS APPEARANCE OF ALARMS SEQUENTIAL MANNER IN YES WITH 1 SECOND TIME STAMP TIME AND DATE STAMPING WITH 1 YES SEC. RESOLUTION PRINT OUT OF CURRENT HSITORIZED ALARMS AND YES FULLY CONFIGURABLE ALARM DISPLAYS STD. YES, WITH WINDOWS TYPE FEATURE WITH ALL GUI FACILITIES OR TOTAL NOS. OF ALARM PAGES MIN. 25 MAX. NOS. OF ALRMS PER PAGE MIN. 20 All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA TOTAL NOS. OF SYSTEM ALARM PAGES MIN. 25 MAX. NOS. OF ALARMS PER PAGE MIN. 10 SPECIFICATIONS FOR DCS Page 114 of 124 TOTAL NOS. OF PROCESS ALARMS IN MIN. LAST 500 NOS. OF RECENT ALARM LIST ALARMS TOTAL NOS. OF SYSTEM ALARMS IN MIN. LAST 250 NOS. OF RECENT ALARM LIST ALARMS LAST IN FIRST OUT PATTERN IN YES PROCESS AND SYSTEM ALARM STORAGE IN REAL TIME AND HISTORY. SORTING OF ALARMS BASED ON TAG , PRIORITY, OCCURANCE, ETC. YES MULTIPLE ACKNOLEDGEMENT OF YES ALARMS WITH SINGLE KEY STROKE GLOBAL ACKNOWLEDGEMENT OF ALARMS YES , FROM ANY WORK STATION DIFF. PRIORITY AND TONES YES , MIN. 4 PRIORITY LEVELS WITH DIFF. TONE FOR PROCESS AND SYSTEM ALARM COLOUR STATE CHANGE IN ALALARM YES , MIN. 2 STATE OCCURANCE AND COLOUR CHANGES ACKNOWLEDGEMENT ALARM ENABLING AND DISABLING IN YES A LOOP RUN TIME ALARM VALUE CHANGES IN RUN TIME 38 YES PASSWORD PROTECTION ABOVE CHANGES FOR YES LATCHED TYPE ALRMS PROCESS AND SYSTEM FOR YES, WITHOUT OPERATOR INTRVENTION, IT SHOULD NOT DISAPPEAR FROM ALARM DATABASE OPERATOR ACTION JOURNAL WITH YES, SEQUENTIAL TIME DATE STAMP RECORING All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA 39 MAX. NOS. RECORDABLE OF 40 GRAPHICAL USER INTERFACE SPECIFICATIONS FOR DCS Page 115 of 124 CHANGES MIN. 10,000 GRAPHIC BUILDING WITH MOUSE AND YES KEY BOARD STANDARD GUI BASED WINDOWING GRAPHICS TOTAL NOS. SUPPORTED OF YES , LIKE XWINDOWS, OPEN LOOK, MOTIF OR WINDOWS NT GUI COLOURS MIN. 16 MILLION TOTAL NOS. OF DIFF. SIZE OF FONTS MIN. 16 SUPPORTED TOTAL NOS. OF DIFF. SIZE OF LINE MIN. 4 THICKENS SUPPORTED DRAG AND DROP WITH EDIT, COPY YES CUT, PASTE FEATURE LIBRARY FACILITIES FOR SYMBOLS YES, AS PER S5.X/IEC1131 ISA IMPORT / EXPORT OF GRAPHICS IN YES OTHER GRAPHICS STANDARD SYMBOL LIBRARY AS PER ISA FREELY FEATURE SIZABLE YES WINDOWING YES MAX. NO. OF WINDOWS ON A SIGNLE MIN. 4 OPERATOR STATION OVERLAYING FEATURE YES MAX. NO. OF OVERLAYS ON A SINGLE GRAPHIC NO LIMIT MAX.. NO. OF ALL TYPES DYNAMIC POINTS PER DISPLAY MAX. NOS. GRAPHICS OF USER OF NO LIMIT CREATED NO LIMIT MAX. FILE SIZE LIMIT OF A GRAPHIC NO LIMIT All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS Page 116 of 124 STANDARD GRAPHICS LIKE SYSTEM YES DIAGNOSTICS ETC. ON LINE CONTEXT SENSITIVE HELP YES FOR GRAPHIC BUILDING ANY PROGRAMMING LANGUAGE YES SUPPORT BY GRAPHICS STARTING OF USER PROGRAM FROM YES GRAPHIC PANLE / SOFT TARGETS CUSTOMIZED , COMPLEX GRAPHICS YES FOR MANIPULATING CONTROL STRATEGIES BY OPERATOR GLOBAL CHANGES FOR A GRAPHICS YES, WITHOUT ANY AT SINGLE LOCATION WITH SINGLE MANUAL COPY/PASTE COMMAND COMMANDS TO OTHER OPERATOR STATIONS MEMORY RESIDENT GRAPHICS AT WORKSTATION 41 MAX TRENDS REAL TIME TRENDS YES HISTORIAN TRENDS YES, MIN. 2000 TAGS AT 1 SECOND, MIN. 1000 TAGS AT 2 SECOND AND MIN. 2000 TAGS AT 5 TO 10 SECONDS. THERE SHALL NOT BE ANY DATA RETENTION LIMIT EXCEPT HDD SIZE FOR ALL HISTORICAL TREND DATA ZOOMING OF TIME AND VALUE AXIS YES OF TREND MIN. TREND TIME RESOLUTION WITH 1 SEC. MIN. 1 HOUR IN MIN. SPAN IN REAL TIME REAL TIME ANY PARAMETER / SYSTEM TAG CAN YES BE TRENDED FOR REAL TIME AS WELL AS HISTORIAN All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS Page 117 of 124 TUNING OF A LOOP IS SUPPORTED BY YES INPUT , SET POINT AND OUTPUT TRENDING SIZE OF A TREND PAGE GRAPHICS QUARTER/HALF AND FULL SCREEN, USER CONFIGURABLE MAX. NO. OF PARAMETERS MIN. 6 SUPPORTED IN ONE TREND PAGE DIGITAL VALUE OF PARAMETER WITH YES GRID SELECTED TIME BASE FOR ANY PARTICULAR TIME TREND REFRESH RATE 1 SEC. EFFECT OF NOS. OF TREND NO EFFECT PARAMETER ON A SINGLE TREND PAGE , ON TREND REFRESH RATE TREND DISPLAY CALL UP TIME 1 SEC. RUN TIME TREND PEN ASSIGNMENT YES OF ANY TAG. USER CONFIGURABLE TREND FOR YES ANY RANGE THROUGH OUT THE SPAN 42 MAX. REAL TIME TREND DEPTH OF ANY PARAMETER WHICH IS NOT CONFIGURED IN HISTORY MIN. 1 HOUR WITH 1 SECOND SAMPLING RATE TREND UPDATE VALUE dB IS USER CONFIGURABLE YES HISTORIAN TOTAL NO. OF HISTORIAN POINTS SYSTEM TAG SUPPORTED BY THE SYSTEM MIN. SCAN TIME PER POINT 1 SEC. FOR MIN. 200O TAGS, 2 SECONDS FOR MIN. 1000 TAGS, 5 TO 10 SECONDS FOR MIN. 1000 TAGS . TOTAL HISTORIAN SIZE SHALL BE MIN. 5000 AVERAGING , MIN. MAX. AND OTHER YES MATH FUNCTIONALITY AVAILABILITY All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA PRESENT HISTORIAN LOAD 40% FUTURE MARGIN IN HISTORY 60% SPECIFICATIONS FOR DCS Page 118 of 124 ANY ATTRIBUTE OF ANY PARAMETER YES (TAG) CAN BE HISTORIZED, LIKE PV ,MV,SV,ALARM FLAG, DIGITAL INPUT,OUTPUT,BAD VALUE FLAG,ETC.. RETENTION TIME FOR ALL THE POINTS AT 1 SEC. NO TIME LIMIT, EXCEPT THE HDD SIZE RUN TIME ADDITION OR DELETION OF YES ANY TAG IN HISTOYR EFFECT OF SYSTEM TIME NO LOSS OF DATA ADJUSTMENT , BACK AND FORHT ON HSITORIAN DATA 43 2ND HDD REQUIREMENT ON ALL THE STATIONS, WHERE HISTORIAN TREND, LONG TERM LOG/REPORT, ETC. ARE STORED, WILL BE QUIPPED WITH 500 GB RAID-I HDD WITH HOT SWAPPABLE FEATURE ANY OTHER LIMITATION NO LIMIT REPORTS / LOGS MAX. POINTS/TAGS PER REPORTS NO LIMIT MAX. NO. OF USER CONFIGURED REPORTS NO LIMIT TYPE OF REPORTS SNAP SHOT, HOURLY,SHIFT,DAILY, WEEKLY, MONTHLY, AND USER SCHEDULED INTERVAL ,ETC. ON DEMAND REPORTS YES GENERATION AND PRINTOUT AT ANY TIME FOR ANY TYPE OF REPORTS REPORT DEVELOPING TOOLS MENU DRIVEN , GUI BASED All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA HISTORY/ SUPPORT REAL TIME REPORT MATH. CAPACITY WRITER IN SPECIFICATIONS FOR DCS Page 119 of 124 YES REPORT YES REPORT RETENTION TIME NO LIMIT EXCEPT HDD SIZE REPORT ARCHIVE ON DAT YES , NO AUTOMATIC REPORT ARCHIVE ON 3.5" FLOPPY YES , AUTOMATIC REPORT FILE FORMAT MICROSOFT EXCEL LATEST VERSION. ALL OPERATOR AND ENGINEERING STATIONS SHALL BE EQUIPPED WITH MS OFFICE LICENSE COPY. CUSTOMIZED REPORT YES LIMIT, CUSTOMIZED REPORT SCHEDULE , YES RUNNING AT MIN. OF 1 MIN. INTERVAL 44 SYSTEM DIAGNOSTICS I/O MODULE YES , UPTO IND. CHANNEL STATUS CONTROLLER YES , INCLUDES ALL MODULE, COMPRISING OF CONTROLLER SUB SYSTEM MAIN FILE SERVER YES, INCLUDING ALL LOCAL PERIPHERALS ALL PERIPHERALS YES, ALL GLOBAL PERIPHERALS ANY TYPE OF MINOR SOFTWARE AND YES HARDWARE ERROR ROUTINE SYSTEM DIAGNOSTICS YES ANY INTERNAL OR EXTERNAL COMM. YES ERROR, INCLDING BUS FAILURES MAJOR HARDWARE FAILURE YES All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA MAJOR SOFTWARE FAILURE YES SYSTEM REDUNDANT COMPONENT CHANGEOVER YES ON LINE HELP FOR ALL TYPES OF FAILURES YES SYSTEM MODULE DYNAMIC LOAD INDICATIONS YES SPECIFICATIONS FOR DCS Page 120 of 124 ANY OTHER TYPE OF DIAGNOSTIC OFFERED 45 SYSTEM SECURITY LEVEL LEVEL-1 OPERATOR LEVEL-2 SUPERVISOR LEVEL-3 ENGINEER LEVEL4 SYS. ADMINISTRATOR 46 SYSTEM BATTERY BACK UP TIME FOR MIN. 72 HRS. DATA HOLD 47 COMPLETE SYSTEM COLD START UP MIN. TIME 48 SYSTEM SELF BOOTABLE YES , WITHOUT ANY USER INTERVENTION WITH ALL DEFAULT PERSONALITIES, IMAGES AND LAST CHECKPOINTED DATABASE 49 INTELLIGENT I/O YES 50 UNIVERSAL I/O BONUS 51 I/O SIGNAL SEGREGATION I/O TYPE YES REQUIRED FROM MARSHALLING PANEL LEVEL AND DCS SYSTEM HARDWARE PANEL LEVEL All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA PLANT UNIT AREA SPECIFICATIONS FOR DCS Page 121 of 124 YES REQUIRED FROM MARSHALLING PANEL LEVEL AND DCS SYSTEM HARDWARE PANEL LEVEL 52 OPTIONAL SOFTWARE QUOTED AS NOT ALLOWED AGAINST OUR STD. SOULUTION REQUIREMENT 53 OPTIONAL SOFTWARE QUOTED AS BIDDER TO HIGHLIGHT EXTRA FEATURE /SYSTEM ALL SUCH FEATURES ENHENCEMENT, WHICH ARE NOT INCLUDED IN ENQ. SPECS. 54 SPARES QUOTED FOR TWO YEARS YES, WTH UNIT PRICE TROUBLE FREE OPERATION OF THE COMPLETE SYSTEM 55 NOS. OF CABINETS SUFFICIENT TO ACCOMMODATE ALL H/W , AS SPECIFIED. MARSHALLING/PDB/SY STEM CABINET SHALL BE AS PER SPECIFICATIONS AND QTY SHALL BE AS PER OWNERS GUIDELINES/REQUIRE MENT SPECIFIED IN THIS COMPLETE ENQ. DOCUMENT 56 MAKE / MODEL OF CABINET RITTAL / MODEL: 4108 WITH ALL OTHER ACCESSORIES AS MENTIONED IN ENQ. SPECS 1200MM(W) X 800MM(D)X 2100MM(H), RAL 7032 COLOUR SHED, ALL IDENTICAL 57 INTERNAL WIRING OF PANELS All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA DIGITAL /COLOUR 58 59 INPUTS SPECIFICATIONS FOR DCS Page 122 of 124 WIRING SIZE 1.0 SQ. MM MULTI STRAND , SILVER COATED , TEFLON INSULATED/STD DIGITAL OUTPUTS SIZE /COLOUR WIRING 1.0 SQ. MM MULTI STRAND , SILVER COATED , TEFLON INSULATED/STD ANALOG INPUT SIZE / COLOUR WIRING 0.75 SQ. MM MULTI STRAND , SILVER COATED , TEFLON INSULATED/STD 110 V AC SUPPLY WIRING SIZE / COLOUR MIN. SIZE SHALL BE 2.5 SQ. MM , MULTISTREND, COPPER WIRE/STD 24 V DC SUPPLY WIRING SIZE / COLOUR MIN. SIZE SHALL BE 2.5 SQ. MM , MULTISTRAND, COPPER WIRE/STD INTERPOSING RELAYS MAKE AND MODEL OMRON MAKE, 24 V DC, SOCKET MOUNT, 4 NO/NC WITH LED INDICATION FOR COIL SUPPLY VOLTAGE 24 V D.C. CONTACT RATING 24V-240 V DC/ A.C. / 5 AMP INBUILT DIODE/LED YES NOS. OF CONTACTS 4 NO/NC BY-PASSING ARRANGEMENT NO MOUNTING ARRANGEMENT PLUG-IN TYPE / SOCKET DIN RAIL MOUNTED OTHER LIMITATIONS NO LIMITATIONS TYPE OF TERMINATIONS All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA ANALOG INPUT SPECIFICATIONS FOR DCS Page 123 of 124 0.5 TO 4.0 SQ. M.M. WIRE SUITABLE, MELAMINE MATERIAL OF WAGO MAKE, SCREW LESS, SIDE/SIDE ENTRY TYPE All rights reserved DCS SYSTEM FOR DAROU-1 SULPHURIC ACID PLANT AND ITS UTILITY AT ICS INDORAMA, SENEGAL, WEST AFRICA SPECIFICATIONS FOR DCS Page 124 of 124 ANNEXURE-V ARCHITECTURE All rights reserved