Uploaded by zzuzw2112

13.Coupled Simulation of Eddy-Current Thermal Field

advertisement
2015 3rd International Conference on Electric Power Equipment - Switching Technology (ICEPE-ST) Oct. 25-28, 2015 Busan, Korea
Coupled Simulation of Eddy-Current Thermal Field
in Medium Voltage Switchgear
Hong Lü, Liuhuo Wang / Electric Power Research Inst.
of Guangdong Power Grid Corp.,
Guangzhou, Guangdong, China
Wensong Zheng, Lijun Wang, Jing Lin / State Key
Laboratory of Electrical Insulation and Power
Equipment, Xi’an Jiaotong University, Xi’an, China
Email: lijunwang@mail.xjtu.edu.cn
Abstract—The temperature rise is very critical for the normal
operation of switchgear, in which eddy current and contact
resistance are the two important influence factors. In this paper,
firstly, the main conductive circuit model of one kind of 12kV
medium voltage switchgear is established using commercial
software Solidworks. Secondly, the effect of the eddy current and
contact resistance on the temperature rise of switchgear is
simulated with consideration of heat conduction, convection and
radiation, and also reasonable boundary conditions. Simulation
results show that the loss of eddy current accounts for 20% of the
total loss, which indicates the eddy current is so significant that it
can’t be neglected. Then, the effect of the different position of the
contact resistance on temperature rise is also studied. Simulation
results show that when the contact resistance is close to the edge,
the heat loss of the contact increases significantly due to the
longer conductive path. The temperature of the contact near the
edge grows significantly due to the skewed-slots coil structure of
the axial magnetic field contact, which is unfavorable for the
energy transfer through heat conduction. And because of the
higher temperature at the edge, the temperature of other
positions can also be increased.
Keywords— Medium-voltage switchgear; eddy loss; contact
resistance; temperature rise; simulation
I.
INTRODUCTION
As important electrical equipment, switchgears are widely
used in power system and play a great role in opening and
closing, control and protection of electrical equipment. Based
on the voltage rank, they can be divided into high voltage,
middle voltage and low voltage switchgears. During the
switchgears’ normal operation, the components inside them
will generate ohmic loss due to the current flow, including
Joule heat and eddy loss because of induced current. When the
Sine current level is higher, the eddy loss will not be ignored.
After a long time of normal operation, due to the increase of
contact resistance and relatively closed structure, the heat
dissipation characteristic gets worse. The temperature on some
positions of the conductive path gets very high, and some even
close to or bigger than permitted temperature. This can not only
affect the characteristic and lifetime of the insulation facility
but also influence the steady and safely operation of power grid.
A lot of works on temperature rise of switch facilities have
been done by many researchers. J.K. Kim and S.C. Hahn
analyzed the single phase bus-bar of the GIS using the coupling
method between electromagnetic and thermal fields in which
eddy current was taking into account, but it was just a simple
two-dimensional model [1]. J. Paulke et al built the threedimensional model of low voltage switch facility and carried
out thermal analysis of different operating state with
consideration of influence of contact resistances [2]. N.
Benjemaa and R. Abdi proposed the way to calculate contact
resistance under the force region of copper bus-bar and also
carried out simulation and experiment on fixed and slide
contact [3]. F. Song studied eddy current and related loss
problem of GIS facility and showed the eddy loss and
temperature distribution of the disconnect switch room and
bus-bar room [4]. Literatures [5-8] also carried out simulation
calculation of thermal field on solid insulation and air-insulated
switchgear. In the paper [6], the concept of heat network was
introduced to make the results more accurate combining with
CFD, and a special analysis was carried out on instantaneous
temperature of switchgear during short-circuit fault.
In summary, simulation and analysis on electromagnetic
thermal coupling of medium-voltage switchgear main circuit
are less. And many related study didn’t consider the combined
effect of contact resistance, eddy current, convection and
radiation, and the impact of contact structure on the results was
not considered either. In this paper, a model of a kind of 12kV
switchgear is established and a simulation of temperature rise
of its normal operation based on Ansys Workbench combining
eddy current field and steady state thermal field considering the
several influence factors above is carried out.
II.
COUPLED METHOD OF EDDY-CURRENT THERMAL
FIELD
Eddy current field
Thermal field
Model import
Share model
Solver selection
Material
reassigned,mesh
Excitation, material,
boundary condition
Import loss
Adaptive meshing
Thermal field
Boundary condition
Solve after
cheking
Thermal field
Fig. 1 Simulation overall framework chart
Fig. 1 shows the framework of the simulation. Firstly, eddy
current field is calculated, then the loss value is imported into
978-1-4673-7414-9/15/$31.00 ©2015 IEEE
Authorized licensed use limited to: Xian Jiaotong University. Downloaded on January 07,2021 at 08:57:24 UTC from IEEE Xplore. Restrictions apply.
63
steady state thermal field, finally the temperature distribution is
obtained.
III.
SWITCHGEAR CALCULATION MODEL
The switchgear entity is shown in Fig. 2, whose rated
current is 3150A. The main circuit is composed of bus-bars,
isolating circuit breaker and current transformers. The current
is introduced from bus-bar and the conductive path is up and
down through.
Instrument
room
(b) Model details
Fig. 3 Simplified switchgear calculation model
Busbar
IV.
Isolated
breaker
Current
transformer
Fig. 2 Switchgear entity
In this paper, the 3D model is established by Solidworks.
As there are insulating materials between the conductive circuit
and the switchgear shell, only the model of the conductive path
is established and the shell is not taking account. In the model,
the electrical contact between the contact fingers and the
contacts is fully considered. The vacuum interrupter is wrapped
in solid epoxy seal pole. In the model, since the relative
permeability of the insulting material is close to 1, which
would not affect the calculation of electromagnetic field and its
thermal conductivity is so low to affect the thermal field, at the
same time, in order to save the computing time, the interrupter
shell and the epoxy parts are ignored. But for the current
transformer, as the epoxy is close to the metal parts, it is also
modeled. The model of other parts is exactly in agreement with
the entity, but the contact fingers are simplified when modeling.
The model is shown in Fig. 3.
Busbar
Contact
Soft
connection
Current
transformer
Feeder
busbar
(a) Calculation model of main circuit
THEORETICAL BASIS OF EDDY CURRENT LOSS AND
THERMAL FIELD CALCULATION
A. Eddy Current Calculations
Equations of the electromagnetic field are described by a
set of Maxwell equations [9], including four laws: Ampere's
law, Faraday's law of electromagnetic induction, Gauss's
electric flux law and Gauss magnetic flux law. For quasi-static
electromagnetic field, the electric flux density can be ignored
compared with the conduction current density, which means
the changes in the magnetic field generated by an electrical
field are not considered. The quasi static field that contains
conductive material is also called as eddy current field. The
differential equations can be expressed as:
&
’u+
&
’u(
&
’ ˜ %
&
&
(1)
w%
wW
(2)
(3)
& In which:
+& ——The strength of the magnetic field vector, A/m;
- ——The total current density vector, A/m2;
&
(& ——The electric field intensity vector, V/m;
% ——The magnetic induction vectorヤWb/m2 (T);
t ——Time, s.
Auxiliary equation:
&
&
V(
&
&
(4)
(5)
%
P+
In which:
P ——Permeability, H/m;
V ——Electrical conductivity, 1/Ωm.
In this paper, the electromagnetic field solving part is
completed by Maxwell eddy current solver. The Maxwell 3D
eddy current solver is used to analyze the time-varying
magnetic field caused by time-varying current in the
conductor or external alternating magnetic source. After the
definition of the current source and necessary boundary
conditions, the 3D eddy current field adopts the following two
kinds of combined methods to calculate magnetic field [10]. In
the case there exists eddy current inside the conductor, the
direct method is used to solve the magnetic field strength.
64
Authorized licensed use limited to: Xian Jiaotong University. Downloaded on January 07,2021 at 08:57:24 UTC from IEEE Xplore. Restrictions apply.
’u
1
’u H = jZP H (6)
V + jZH
Magnetic scalar potential method is adopted to calculate
magnetic field strength.
’ ˜ (P’I )=
(7)
For the object that eddy current is not specified, the solver
will adopt magnetic scalar potential method to calculate
magnetic field. And if eddy current calculation is needed, the
solver will adopt direct method to calculate eddy current. At
the boundary side, the solver forces H continuous, then
continuous magnetic field calculation is generated in the
model. Because the Maxwell software adopts adaptive
meshing technology, computing error can be reduced to any
specified value. And energy calculation error is less than 1%.
By calculating electromagnetic field, the ohmic loss can
be obtained by using the following law:
P
1
J · J *dV (8)
³
2V V
And the relationship between ohmic losses and resistance
is as follows:
P
I 2 RRMS (9)
In engineering practice, a variety of electrical contact has a
direct impact on the resistance value. Any refined and
processed flat is actually rough. When the surfaces are
contacted, even if a large contact force is applied on the
contact face, actual contact still occurs in few points. These
actual contacted surfaces bear all of the contact force. And
because of the oxide film effect of metal surface, only the
surfaces where oxide film is crushed have actual contact.
These contact points are called conductive points. When
current flows through the contact spots, the current line
shrinks to produce contact resistance. In the switchgears, the
contact resistance between separable static and dynamic
contact is particularly evident. For engineering applications,
the general assumption is that there is only one contact spot
between contact surfaces. This article assumes that there is a
cylinder (conductive bridge model) which is equivalent to
contact resistance between static and dynamic contacts.
The material property of conductive bridge is the same
as contact material, and the radius is determined by Holm
equation [11]. r
F
(10)
¯±
˜ ˜H
In the formula, F means contact pressure, ξ stands for
surface contact coefficient which is generally between 0.3 and
0.6, and H stands for material hardness. In this study, the
contact pressure of the isolation breaker at its operation
position is 4800N, and the contact coefficient is set as 0.3. The
material of the contact blade is CuCr50, the hardness of which
is 128. The cylindrical radius can be calculated to be 4mm.
And since the main circuit resistance of the isolation breaker is
under 50μΩ, the height of the cylinder can be identified as
4mm.
Fig. 4 Contact resistance model
In the eddy current calculation, 3150A current is loaded as
excitation, and the phase difference of three phases is 120o, the
frequency is power frequency 50Hz. The meshing method is
based on the depth of the surface, which fully takes the impact
of skin effect into account, and the displacement current is
ignored.
B. Steady-State Thermal Field Calculation
In thermal analysis, three kinds of main heat transfer
ways are included: thermal conduction, thermal convection
and thermal radiation. As the conductive components in the
switchgear are in a closed environment, thermal conduction is
the main cooling mode. And there is still small amount of
thermal convection and thermal radiation. The threedimensional steady-state thermal conduction is described by
the following formula [12]:
¬
w 7
w 7
w 7
w] w[ w\ q
(11)
In whichヲ
TĘĘTemperature (K);
ƉĘĘThermal conductivity (W/m·K);
q——Energy produced per unit volume (W/m3).
In steady-state thermal field calculation, the conduction
equations are calculated by the methods in which thermal
conductivity is given to the materials. But for thermal
convection and radiation, surface convection coefficient and
thermal emission coefficient are given to the surface to be
equivalent to convection and radiation process. In practice, the
two coefficients have important influence on the temperature
rise in the calculation.
For the boundary conditions of this paper, the conductor
pole and contact parts in the interrupter are only given the
radiation emission coefficient of 0.4
as their vacuum
environment. And the convection coefficient is set as 6W/m·K
for the bus-bar and contact base. The mechanical connection
part is given the coefficient of 3 W/m·K as its relative closed
environment. What’s more, the epoxy part surround the
current transformer is given the coefficient of 6W/m·K. The
ambient temperature is set as 22Ȕ.
The material of conductor pole, contact base, bus-bar
and mechanical part is copper. The contact support is made of
steel stainless. And the material of contact plate is made from
65
Authorized licensed use limited to: Xian Jiaotong University. Downloaded on January 07,2021 at 08:57:24 UTC from IEEE Xplore. Restrictions apply.
TAB 1 MATERIAL PROPERTY OF THE MAIN PARTS
Name
thermal conductivity
(W/m·K)
Bus-bar
Cu
401
Conductive clip
Cu
401
Contact base
Cu
401
Conductive pole
Cu
401
Contact blade
CuCr50
330
Contact support steel stainless
15.1
Insulation
epoxy
0.29
V.
material
SIMULATION RESULTS AND DISCUSSION
A. Influence of Eddy current on total loss
To illustrate the effect of eddy current on the total loss,
the electromagnetic field is calculated in two kinds of
conditions: with and without eddy current. Maxwell field
solver can calculate the total loss of each part, and the loss of
the main parts of the model under the two conditions is shown
in Table 2.
TAB 2 OHMIC LOSSES OF VARIOUS PARTS
Parts name
Without eddy
With eddy
Bus-bar
22.31W
28.80W
Conductive clip
0.75W
1.40W
Contact Base
5.70W
7.77W
Soft Connection
4.01W
4.50W
Contact plate
108.25W
113.73W
Conductive bridge
11.90W
12.03W
As can be seen, the losses of various parts increase
significantly after the eddy current is taken into account. The
total loss is 1400W when eddy current is ignored, but when it
is considered, the total loss increase to 1847W. That is to say
eddy current loss is about 24% of total ohmic loss, and is a
very important factor leading to conductor heating.
Meanwhile, the contact resistance and contact plate are two
sources that contribute to the losses of the conductive circuit,
which take account for 6% of the total loss. Therefore,
improving the material property of the contact plate or
reducing the contact resistance is important way to reduce the
losses.
B. Influence of convection coefficient and radiation
emissivity on temperature rise
In the setting of the thermal field boundary conditions,
the convection coefficient and emissivity of the model surface
are given according to the empirical values. So the different
coefficients will have some impacts on the results. To verify
these impacts, extreme cases are considered in which several
groups of different simulation conditions are conducted. In
some cases, only radiation emissivity is given to the model
surface and in others convection coefficient is added. Thus,
the impacts on the thermal field are compared under different
coefficients. The simulation results are shown in Fig. 5.
Without radiation
With radiation
Temperature
CuCr50. Table 1 shows the material property of the main parts
of the model.
Convection coefficient
Fig. 5 Impacts of convection heat transfer coefficients and radiation
emissivity
Since the convection coefficient on the metal surfaces is
generally between 2 and 10 [12], the results are only compared
in this range. The radiation efficient on copper surface is fixed
at 0.4. As can be seen from the comparison results, the
radiation begins to play a significant role when the
temperature is higher than 100oC. There is almost no
difference with or without radiation coefficient when the
temperature is lower than 100oC. When the convection
coefficient is set from 2 to 10, the temperature gradually
decreases, but the rate of decline slows down which shows
that changes of the convection coefficient begin to affect more
significantly as the temperature goes higher. And the
minimum temperature rise difference between them (with and
without radiation) is about 5K. When the convection
coefficient is selected as different values, the maximum
difference between them is 30K. The effect of radiation is
significant.
C. Steady-state Thermal Field Results
Based on the comparison of above simulation results, in the
steady-state thermal field calculation of this paper, radiation
emissivity is only set on the arc chamber surfaces since it is
the main high temperature area. And as the vacuum
environment, no convection heat exchange is nearly zero. The
convection coefficients of other parts are set according to
actual situation. The final steady-state thermal simulation
results are shown in Fig. 6.
ć
Temperature/ć
166.82
152.46
138.10
123.74
109.38
95.02
80.66
66.30
51.94
37.58
23.22
Fig. 6 Steady-state thermal field
As can be seen from the results, the highest temperature
of the main circuit is located near the contact, and the value is
66
Authorized licensed use limited to: Xian Jiaotong University. Downloaded on January 07,2021 at 08:57:24 UTC from IEEE Xplore. Restrictions apply.
D. Influence of contact resistance location on thermal field
In the above model, the contact resistance is assumed to
be located in the electrode center. But in practice, duo to the
uneven force on the end of the conductive poles and slightly
ablation on the contact plates, the actual contact points is
likely to deviate from the electrode center. To explore the
impact of this case on the circuit temperature rise, another two
cases are specially considered: contact resistance off the center
and contact resistance located in the edge. Three kinds of
positions of contact resistance are shown in Fig.7. In order to
compare the result with above, the diameter and height of the
contact resistance value is fixed.
Contact
resistance
(a)
(b)
(c)
Fig. 7 Contact resistance position (a) center; (b) off the center; (c) edge
The set of electromagnetic and thermal boundary
conditions is the same as when the contact resistance is
located in the center. The simulation results of the contact
section faces are shown in Fig. 8.
Temperature/ć
ć
233.93
221.03
208.12
195.22
182.31
169.41
156.50
143.59
130.69
117.78
104.88
(c) Contact resistance at the edge
Fig. 8 Contact thermal field of different contact resistance positions
When the contact resistance is located at the center, the
heat that generated by the contact resistance is conducted from
the contact plates to the stainless steel support and side copper
body below. Although the thermal conductivity of copper is
far greater than the stainless steel, duo to the chute structure of
axial magnetic field contact, the conductive path is so long to
make the thermal field evenly. When the contact resistance is
off the center, the current conduction path and heat conduction
path get changed. The temperature increases slightly but
doesn’t change significantly. And when the contact resistance
is located at the edge, the current is conducted along the chute
of the side. The conduction path gets much longer, so the heat
generated by the contact resistance can’t be conducted well,
resulting in the temperature of contact resistance much higher
than the previous. The highest temperature reaches to
233.93oC.
Similar to the foregoing, the temperature changes of busbar, contact base and conductive clip of three cases are
compared. The results are shown in Fig. 9.
Temperature/ć
166.82oC. The lowest temperature is 23.22oC which is located
at the epoxy parts surrounding the current transformer.
Thermal fields of three phases are basically the same. In
steady-state thermal simulation, temperatures rise of bus-bar,
contact base or other parts that are easy to be observed are
more concerned. In this example, the bus-bar temperature rise
is 59K, the contact base 63K, the conductive clip 74K.
According to the national standards, the temperature rise of
exposed parts in switchgear in steady state should not exceed
65K [13]. Simulation results show that it meets the standard
requirements.
250
233
183
166
150
100
Temperature/ć
ć
166.76
159.49
152.21
144.93
137.65
130.38
123.10
115.82
108,54
101.26
93.98
Highest
Busbar
Contact base
Soft connection
Lowest
200
122
111
106
82 88
83
90
90
97
50
23
23
23
0
At the center
Off the center
At the edge
Fig. 9 Influence of contact resistance positions on temperature of different
parts
(a) Contact resistance at the center
Temperature/ć
ć
183.74
175.04
166.33
157.63
148.92
140.22
131.51
122.81
114.10
105.40
96.69
(b) Contact resistance off the center
As can be seen from Fig. 9, when the contact resistance is
off the center, the effects of temperature on other parts are
limited. The temperature change of bus-bar and contact base
doesn’t exceed 5K. But when the contact resistance is at the
edge, significant temperature changes of each part can be seen.
And the temperature rise of contact resistance is about 210K,
which has direct effects on steady-state thermal field. Under
the operation of switchgear, to maintain the mechanical
moving parts work properly and to minimize the contact plate
surface erosion will help to keep the contact resistance located
at the central area to prevent the additional temperature rise
duo to the contact resistance deviation.
67
Authorized licensed use limited to: Xian Jiaotong University. Downloaded on January 07,2021 at 08:57:24 UTC from IEEE Xplore. Restrictions apply.
VI. CONCLUSIONS
Based on the modeling and simulation of medium
switchgear, the following conclusions can be drawn,
1) Eddy current loss is one important aspect of switchgear
main circuit ohmic loss, which accounts for 20% of the total
loss. Its impact on steady-state thermal during switchgear
operation can’t be neglected. Effective reduction of eddy
current loss can help to reduce the temperature rise.
2) The convection and radiation coefficients in the set of
steady-state thermal field boundary conditions will have a
significant impact on simulation results. In the actual
calculation, based on the specific circumstances, different
thermal boundary conditions should be set on different
positions.
3) During the actual operation of switchgear, duo to the
uneven force on the end of the conductive poles and slightly
ablation on the contact plates, the actual contact points are
likely to deviate off the center. When the contact resistance is
close to the electrode edge, the maximum temperature will
increase significantly. And the temperature of the bus-bars,
contact base and conductive clip will also rise.
[3]
[4]
[5]
[6]
[7]
[8]
[9]
[10]
REFERENCES
[1]
[2]
J.K. Kim, S.C. Hahn, K.Y. Park, H.K. Kim, Y. H. Oh. Temperature Rise
Prediction of EHV GIS Bus Bar by Coupled Magnetothermal Finite
Element Method, IEEE Trans. on Magnetics, 2005, 41(5)1636-1639.
J. Paulke, H. Weichert, P. Steinhaeuser, Thermal Simulation of
Switchgear, IEEE Trans. on Components and Packaging Technologies,
2002, 25(3): 434-439.
[11]
[12]
[13]
N. Benjemaa and R.E. Abdi, Numerical and experimental study of the
contact resistance for high copper alloys in force domain 1-100 N, Eur.
Phys. J. Appl. Phys. 49, 22906 (2010) p1-p8.
F. Song, J. Xu, X. Lin, W. Li, Three-Dimensional Magneto-Thermal
Fields Analysis of 1100kV GIS Dis-connector, The 1st International
Conference on High Voltage Engineering and Application. Chong Qing,
2007: 224-227.
S. Singh, R. Summer, U. Kalterborn, A Novel Approach For The
Thermal Analysis Of Air Insulated Switchgear, 21st International
Conference on Electricity Distribution, Frankfurt, Germany, 6-9 June
2011, 0492 (1-4).
T. Shimizu, S. Kinoshita, S. Makishima, J. Sato, O. Sakaguchi, Material
and simulation technology for solid insulated switchgear, Properties and
Applications of Dielectric Materials, Proceedings of the 7th International
Conference on. IEEE, 2003, 1-5 June, Vol 3, 1194-1197.
L. Koller and B. Novák, Transient heating of gas insulated switchgears,
Transmission and Distribution Conference and Exposition, 2010 IEEE
PES, 1-7.
H. Li, N Shu, X. Wu, H. Peng, Z. Li, Scale Modeling on the Overheat
Failure of Bus Contacts in Gas-Insulated Switchgears, IEEE
Transactions on Magnetics, 2014, 50(2): 305-308.
Ansys Maxwell 16.0 Online Help.
D. Robert and Pillsbury, A Three dimension eddy current formation
using two Potentials: the Magnetic Vector potential and total magnetic
scalar Potentials, IEEE Transactions on Magnetics, 1983, 6(19): 22842287.
R. Holm, Electrical Contacts. New York: Springer, 1979.
P. Kitak, J. POPOVI?, A. GLOTI?, I. TI?AR, Calculation of thermal
coefficients of a metal partition wall by FEM analysis, Przegl?d
Elektrotechniczny, 2011, 87: 96-98.
IEC 62272-200, first edition, 2003-11, AC metal en-closed switchgear
and control gear for rated voltages above 1 kV and up to and including
52 kV.
68
Authorized licensed use limited to: Xian Jiaotong University. Downloaded on January 07,2021 at 08:57:24 UTC from IEEE Xplore. Restrictions apply.
Download