9. In an office, a copy machine is found to produce 65 dB. If a computer printer is added to the room and it produces a sound intensity of 69 dB, what will be the resulting sound level? 10. What is the single number often used to evaluate A B C D @ 000 A B C D O@OO partitions? A. SOUND ABSORPTION COEFFICIENT C. SOUND INTENSITY B. SOUND TRANSMISSION CLASS D. TRANSMISSION LOSS 11. What method is used to specify the maximum allowable intensity of background sounds? A. NOISE CRITERIA C. NOISE REDUCTION B. NOISE INSULATION CLASS D. INVERSE SQUARE LAW 12. What is one variable affecting reverberation time? A. SOUND INTENSITY C. NOISE REDUCTION A B C D BOO0 A B C D 0@09 COEFFICIENT B. ROOM VOLUME D. PHON 13. Which of the following is not true about noise reduction between two rooms? A. Noise reduction increases with an increase in the transmission loss of the wall separating the two rooms. B. The stiffness of the wall has little effect on noise reduction. C. To improve noise reduction, you should place absorptive materials on both sides of the wall. D. An increase in wall area separating the two rooms is detrimental. A B C D OO@O 14. A room 4.50 M wide by 6.00 M long by 2.55 M high is finished with the following materials of listed absorptions. There is a window on one wall 1.05 M high by 2.40 M long. What is the total absorption of the room? NRC 125 250 A B C D 000@ 500 1000 2000 4000 floor wood 0.10 0.15 0.11 0.10 0.07 0.06 0.07 walls,gypsumboard 0.05 0.10 0.08 0.05 0.03 0.03 0.03 ceiling acoustical tile 0.60 0.29 0.29 0.55 0.75 0.73 0.57 window, glass 0.15 0.35 0.25 0.18 0.12 0.07 0.04 A. 228 Sabins C. 266 Sabins B. 244 Sabins D. 242 Sabins 15. If a material supplier told you that adding his product to a wall assembly in a critical acoustical situation would increase the noise reduction (STC rating) between two spaces by more than 3 dB, what should your reaction be? A B C D 0@ 00 A. Determine what the additional cost would be and then decide whether or not to use the product. B. Thank him for stopping by but explain that you probably will not be using his product because that amount of noise reduction does not make it worth the effort of cost. C. Specify the product as long as it does not affect the design or construction cost by more than 5%. D. Inquire whether some modification can be made to the product to increase its rating to 6 dB and say that then you might consider it. 16. During your design development presentation to the building committee of a middle school, one of the teachers on the committee mentions that there might be a noise problem between the classrooms shown in the partial plan because the larger classroom will be used for open discussions, movies, lab. work, and other loud activities. Both classrooms are scheduled to have gypsum board partitions, vinyl tile floors; and suspended acoustical ceilings. A B C D 00@ 0 classroom B classroom A corridor If cost is a consideration, what changes in the design should you suggest, in order of priority from most important to least important? I. Substitute carpeting for tile in both rooms. II. Move the operable windows near the separating wall so they are not so close together, and change the direction of the swing. Ill. Reroute the ductwork and conduit penetrations through the separating wall above the suspended ceiling and write specifications to direct that any remaining penetrations be tightly sealed. IV. Replan the layout so there is a small audiovisual storage room between the classrooms. V. Add an extra layer of gypsum board to each side of the separating partition and specify that the cavity be filled with sound - attenuating insulation. *ATTENUATION is the reduction of sound. VI. Hire an acoustical consultant to determine the special frequency problems associated with the activities planned for the larger classroom, and design custom sound - absorbing surfaces and partitions accordingly. B. IV, 11, Ill, V, Vl, I D. V, Ill, 11, I, IV, Vl C. SOLID STRUCTURE AND AIR-BORNE NOlSE REDUCTION 1. One way of reducing the noise is the selection of the . The existence and location or persistence of quiet locations is dependent on zoning ordinances and their enforcement.Architects in every community should cooperate with the civic authorities in the segregation of noxious activities including noisy industries, power stations, airports, traffic arteries. Inter urban automobile and truck traffic should be routed around, not through, area that have been zoned for schools, residences and hospitals, expressway that must pass through zones requiring quiet surroundings should be isolated by means of embankments or parapets along the outer edges of the highways. Trains should enter large metropolitan centers by underground routes; parks and landscaping should be planned to impede the propagation of noise into quiet zones; and approaches to airports, which are increasing noise nuisance in all large cities, should be from the outskirts of the city, not over it. 2. A. ORIENTING C. SITING B. LAYOUTING D. GROUPING is an effective way of NOISE CONTROL. An embankment placed betweenthe listener and the train that passes by, is effective. An earth embankment or a masonry garden wall often can be used to reduce the noise that impinges on a building and aid in the establishment of quite conditions within the building without resorting to costly measures of sound insulation. It may reduce the level by as much as 5 dB. Use Hedges or trees with dense foliage, dense vines, grassy turf to face the sources of NOISE as sound barriers and reflectors. A. PLANTING AND FENCING C. FILLING AND EXCAVATION B. GRADINGAND LANDSCAPING D. WALLING A B C A B D 0 0@ 0 0@ 3. The location of a building on its site, the arrangement of rooms, corridors and vestibules, and the location of doors and windows, all have a bearing on the control of noise. This is called the For example, the noise level at the end of a room adjacent to a busy street maybe at least 5 db higher than it is at the opposite end. In such a situation it is advantageous to place the speaker's platform at the end of the room. The side of a buildingfacing streets, playgrounds, or other sources of noise should house those activities that can tolerate the greatest amount of noise, and the sides of the building that face the quieter environment should be reserved for those rooms that require the quietest conditions windows should not open on noisy street or yards. A B C D @ 000 A B A. BI,IILDING LAYOUT C. GROUPING B. PLANNING D. FUNCTIONAL DIAGRAM 4. Compound-wall constructions or is one way of reducing air-borne noise. provide two adjoining walls with an open space in between without any materials like wood connectors, or chunks of plaster thrown in between that touches both walls. Another technique is to fill in the void with porous sound absorbent material. A. DOUBLE WALL C. BEARING WALL B. THICK WALL D. CAVITY WALL 5. Another way to reduce Air-borne noise is to use windows. 114"thickwith at least 112" (.0125) air space. One sheet is tilted at 1 inch in 12 inches to suppress high transmission of certain resonant requencies. In radio stations sometimes three sheets are required with at least 0.15 M separation between the sheets of glass. In such rooms, the periphery of the space between sheets should be lined with sound absorptive material. A. DOUBLE GLASS PANE C. LAMINATED GLASS B. TEMPERED GLASS D. WIREGLASS C D 000@ A B @ 000 C D 6. Just as sound will pass through the acoustically weakest part of a composite wall, so it will also find parallel or paths. 'That is, an acoustic short circuit. Proper design of window locations to avoid this path should be the following: In a corner design where corner windows are closely spaced such that noise from open window apt. A goes to open window apt 6 , solution, put hinge of window such that it buffers the sound when opened and put planting in between. Put a wide separation of straight wall windows. In a noisy walkway outside put windows away from this path. Also put sound barrier between the second floor and ceiling of the first floor. A. ALIGNING C. SINGLE B. FLANKING D. FILING 7. The isolation provided by a floor system against mechanical impact can be greatly improved by the use of a floor which rests on the structural floor but is separated from it by a resilient support of quilt (on top of the sub-floor is a 112" fiberboard or a resilient blanket then a l"X2" wood sleeper then finish floor. Below the floor would be a false ceiling. Meaning a ceiling with a horizontal 2 " X 6 ceiling foist never touching the floor (do not use 2"X2" or 2 "X3" hangers) A. CARPETED C. HOLLOWED B. DOUBLE STACK D. FLOATING MECHANICAL NOISE sources, those coming from the components of the air conditioning and AHU, or air handling units such as fans, compressor, cooling towers, condensers, ductwork, dampers, mixing boxes, induction units, and diffusers can be controlled. Pumps are another source of mechanical noise, which is frequently transmitted along pipes to remote points. Elevators, escalators and freight elevators also introduce mechanical noise into the building. The motors and switchgear are located on or above the prime upper floors of a building, and must be properly controlled to prevent annoyance to buildingtenants located near the shaftways or mechanical penthouses. A B 0@ A B C D 000@ 8. Machines cause noise by vibration. This noise is imparted directly to the surrounding air and by vibrational contact to the surrounding structure. Therefore there are three ways to reduce this noise: A B C D 00@ 0 I. Reduce the vibration itself II. Suspend the structure itself Ill. Wrap the enclosure with acoustical materials IV. Reduce the Air-borne noise by decoupling the vibration from efficient radiating sources V. Decouple the vibrating source from the structure VI. Locate the mechanical machine 20 meters away. A. I, ll and lV C. I, IV and V B. Il, Ill and lV D. II, IV and VI D. PHYSICS OF LIGHT AND SOURCES 1. The of a meterial such as a fixture or diffuser is a measure of its capability to transmit incident light. (it goes through) It's factor or coefficient is the ratio of the total emitted light to the total incident light (source). An example is a clear glass which displays this measure between 80% and 90% frosted glass between 70 and 85% and solid opal glass between 15 and 40%. A @ B C D 000 A. LUMINOUS C. RESISTANCE TRANSMITTANCE B. ILLUMINATION D. SPREADING FACTOR 2. The is the unit of luminous intensity. It is analogous to pressure in a hydraulic system and voltage in an electric system and representsthe force that generates the light that we use. A. LAMP POWER C. GLOWING POWER B. BRIGHTNESS D. CANDLE POWER A €3 C D 00 0@ 3. is a term used to describe all the factors in a lighting installation not directly concerned with quantity of illumination. Certainly it is obvious that if a given room is alternatively lighted with a bare bulb and with a luminous ceiling, both giving the same average quantitative illumination, there is a vast, difference in the two lighting systems. This is also a term which describes the luminance ratios, diffusion uniformity and chromaticity of the lighting. This is also a description of the visual comfort and visual adequacy of the system. A. CHARACTER OF LIGHTING C. QUALITY OF LIGHTING B. USAGE OF LIGHTING D. TYPE OF LIGHTING 4. Ucomfortable brightness ratios, where background luminance exceeds object luminance is called a A. FLICKER C. SPARKLE B. GLARE D. BUBBLE A B C 0 00 A B D C D 0@ 00 5. When the discomfort glare is caused by light sources in the field of vision it is known as (looking at the light at 45' angle). A. STRAIGHT GLARE @ DIRECT GLARE B. EYE TO SOURCE GLARE D. ECHO GLARE 6. When the glare is caused by reflectionof light source in a viewed surface (say a table) it is known as or "VEILING reflection". The object mirrors the source of light in the room. A B C D 0@ 00 A. TANGENT GLARE C. TRANSMITTED GLARE B. REFLECTED GLARE D. DIFFUSED GLARE 7. EFFICACY increases with wattage. Therefore it is energy - economical to use a small number of higherwattage lamps than big or many number of lowerwattage lamps. It is usually more economical with A B C D 000@ respect to fixtures since electric lighting in nonresidential buildings consumes 25 to 60°h of the electric energy utilized, any attempt to reduce this must necessarily include integration of the cheapest (in sofar as energy is concerned). Most abundant and , in many ways, most desirable form of lighting available, the A. SUNLIGHT C. TASK LIGHT B. NATURAL LIGHT D. DAYLIGHT A B C D 0000 Daylighting is an amenity rather than a necessity.As such its provision has been the province of architecture rather than lighting design. Windows provide visual contact with the outside and the resultant daylight provides a bright, pleasant, airy ambience. When DAYLIGHT enters through windows (side lighting) its horizontal directivity provides good modeling shadows, minimal veiling reflections, and excellent vertical surface illumination, aside from continual variation of daylight, it provides a constantly changing pattern of space illumination; one that is NOT or is unattainable with artificial light. 8. An consists of a tungsten filament placed within a sealed bulb containing an inert gas. When electricity is passed through the lamp the filament glows, producing light. These lamps are produced in a wide variety of shapes, sizes and wattages for different applications. The ADVANTAGES of these lamps are inexpensive, compact, easy to dim can be repeatedly started without a decrease in lamp life, and have a warm color rendition. In addition, their light output can be easily controlled with reflectors and lenses. Their DISADVANTAGES include low efficacy and heat production makes these lamps undesirable for large, energy - efficient installations. For example, a 150-watt lamp produces less than 20 lumens per watt while a 40watt cool white fluorescent lamp has an efficacy of about 80 lumens per watt with much less heat output. TYPES of this kind of lamp are the Arbitrary (standard), Globular, Pear-shaped, Flame-shape: cone shape, Par, parabolic aluminized reflector; R, Reflector, T, Tubular. A. INCANDESCENT LAMP C. TOUCH LAMP B. FLUORESCENT D. METAL HALIDE LAMP LAMP A @ 000 9 Anotfn~Jype@=i!!candescent lamp is the Lrght is produced by the incandescence of the f~lament,but there is a small amount of a halogen, such as iodine or bromine, in the bulb with the inert gas. Through a recurring cycle, part of the tungsten filament is burned off as the lamp operates, but it mixes with the halogen and is redeposited on the filament instead of on the wall of the bulb as in standard incandescent lamps. This results in longer bulb life, low lumen depreciation over the life of the bulb, and more uniform light color. Because the filament burns under higher pressure and temperature, the bulb is made from quartz and is much smaller than standard incandescent lamps. A. MERCURY VAPOR C. TUNGSTENHALOGEN B. METAL HALIDE 10. D. HIGH PRESSURE SODIUM are lamps that contain a mixture of an inert gas and low-pressure mercury vapor. When the larnp is energized, a mercury arc is formed that creates ultra violet light. This invisible light, in turn, strikes the phosphor-coated bulb causing it to fluoresce and produce visible light. The three types of this type of lamp are the PREHEAT, RAPID START, and INSTANT START, according to their circuitry. A. SODIUM LAMP C. VAPOR LAMP B. ULTRAVIOLET D. FLUORESCENT There are several general types of LIGHTING SYSTEMS. The terms used to describe them can refer to inaividual liminaires or to the entire lighting installation. They are broadly described as: I DIRECT II SEMI-DIRECT Ill DIRECT-INDIRECT IV SEMI-DIRECT V INDIRECT A B C D OO@O 11. This type provides approximately equal distribution of light upward and downward, resulting in a bright ceiling and upper wall background for the luminaire. For this reason, brightness ratios in the upper-vision zone are usually not a problem. Since the ceiling is a major, though secondary source of room illumination, diffuseness will be good, with resultant satisfactory vertical-plane illumination. A B C D @OOO One example of this type is a GENERAL DIFFUSE or an Opal Diffusing Globe fixture hanging from the ceiling which give light in all directions. The other type is an open top luminous side and bottom luminaire, which have little horizontal component. Stems from the ceiling should not be less than 0.30 M. 12. Ninety to one hundred percent of the light output of the luminaires is directed to the ceiling and upper walls of the room. This lighting system is called because practically all of the light reaches the horizontal working plane indirectly, That is, via reflection from the ceiling and upper walls. Therefore, the ceiling and upper walls in effect become the light source and, if these surfaces have a high-reflectancefinish, the room illumination is quite diffuse (shadowless). This luminaire is suspended at least 0.45M. METAL REFLECTORS is under this type. Also Architectural COVES near the ceiling wherein the light is not seen. Since essentially all the light is directed downward, ceiling illumination is entirely due to light reflected from the floor and room furnishings. This system requires a light, high-reflectance,diffuse floor unless a dark ceiling is desired from an architectural viewpoint. This system is called the lighting since it provide all light output on the task. A recessed fluorescent luminaire is an example of this type. Another type is a metal-enclosed fluorescent light, (no light goes to the ceiling and sides). A B C D O@OO A B C D O@OO 4. What method is the first defense from external noise by site selection and site planningfor a quiet internal acoustic environment? A B C D @boo0 A. Use of noise insulating building envelope B. Using non-sensitive parts of the building as barriers C. Positioning of openings away from the noise source D. Avoiding zone of directional sound 5. Compute for the velocity of sound if its wavelength is 1.50 M at a frequency of 1,500 Hz. A. .00328fps C. 304.87 fps B. 3048.7 fps D. 7,380 fps 6. Which of the following statements does NOTdescribe velocity of sound correctly? A B C D OOO@ A B C D O@OO A. If the temperature in a room increase, the speed of sound also increases B. Changes in pressure at controlled density have virtually no effect on the speed of sound C. Sound travels slightly slower in moist air than in dry air because moist air contains a greater number of lighter molecules D. The product of the wavelength and the frequency is equal to the speed of propagation of the sound wave 7. A perceptual characteristic of sound which is the average rate of follow of energy per unit area perpendicular to the direction of propagation. A. INTENSITY C. PITCH 6. HARMONIC CONSTITUTION D. LOUDNESS 8. Reflection of sound from a curved surface A. CREEP C. REFLECTOR 6. FREQUENCY D. REVERBERATION A B C D 0 0@ 0 A B C D 0000 AREA "C" PART II ARCHITECTURAL DESIGN AREA "C" ARCHITECTURAL DESIGN portion of the Board examination is the most difficult parts of the entire examination. The candidate must synthesize a large amount of information into a comprehensive design solution and do it under severe time contraints say, in 10 hours, in what becomes, at best, an arduous test of endurance. Many candidates fail, not because they cannot solve the problem but because they let it get the best of them. They begin to make the wrong decisions and choices at the wrong time, spend too much time on one part of the problem. Then panic and run short on time, and end up either not solving the problem or forgetting to include critical elements. The key elements of success are to budget your time, stick with your scheduled procedure of solution. The examinat~ondemands that the building aspects: Function, lifekafety code compliance, structure, mechanical systems, lighting, and so forth. Although it does ask that the building be appropriate for human occupancy in terms of scale, proportion, relationship to its surroundings, use of materials, and other design parameters, it does not demand an award winner. Your EMPHASIS, therefore, should be on solving the stated problem in ten (10) or twelve (12) hours, as required, COMPLETELY (plans, all floors, sections, elevators, lot and site plan, and an impressive perspective) with reasonable design decisions. 1. HOW TO SOLVE THE 10 OR 12-HOUR DESIGN PROBLEM A. Strategies for Time Management (8:OO - 835) First task should be to quickly read the problem statement and set up your own timetable. Do NOT read the program in detail the first time through; simply get a feeling for the problem, where major difficulties might be, and how much time you should allow for the final drafting of the solution. As a starting point, the following TIMETABLE might prove useful. Step I: Make a quick overview of the ................ 15 minutes (8:OO - 8:15) problem statement and a determination of your own timetable Step 2: Read the examination information......... 45 minutes (835 - 9:OO) booklet and translate the written data into a programming base sheet Step 3: Translate the programmed spaces ........30 minutes (9:OO - 9:30) into graphic or and calculate the maximum allowable gross area Step 4: Check areas and functions ....................15 minutes (930 - 9:45) for each floor Step 5: Begin adjacency/ .................................90 minutes (9:45 - 11:15) circulation diagrams Step 6: Study the structural system ...............30 minutes (11:I5 - 11 :45) Step 7: Study the mechanical/ .......................15 minutes (11:45 - 12:OO) plumbing systems Step 8: Design the development including .... 120 minutes (12:OO- 2:OO) plan, section and elevations 30 minutes (2:OO - 2:30) LUNCH BREAK .................................................... Step 9: Make the FINAL drawings .........................300 minutes (5 hours) Y a. perspective first 3 hrs. b final drawings 2 hrs. ........................................... (2:30- 7:30) Step 10: Make a final check ................................... 30 minutes (7:30-8:OO) TOTAL TIME: ................................................................................. 12 hours Note: If the total time required is only ten (10) hours, then readjust the allotted minutes. Tip #I : a) If the project is a multi-storey building, make your final footprint or the first floor plan, then just trace it for the upper floors. b) to make the elevations or sections, use your triangle and just slide it and make vertical lines through the walls, windows so as to save time instead of using again your scale. c) Remember you should proceed from "within" to "without" meaning from the circulation or plan to the exterior looks. d) Then proceed from "General" to "Particular" meaning, when making a perspective, first form the general outline before you even make any detail. e) If the perspective comes out alright, from there, you can now translate it to the elevations, the windows, doors, balconies, porte-cochere,entrance, roofing shape, and others. f\ You may want lo put in as a good design some details you have researched previously to enhance your design. I Draw overhangs with dashed lines. Indicateall built-in items as well as plumbingfixtures. It is especiall) important to show the detailed layout of the toilet rooms. Show stairwayswith individualsteps drawn in and an arrolk, indicat. ing direction up or down. Draw all required furniture and furniture necessary to explain you1 design or show a workable plan, using a single line. Label all rooms and spaces with the names exactly as given in the program. lndicate the locationof your sectioncut with a line through the building and an arrow pointing in the direction of the cut. lndicate drainage away from the building with arrows and a note. Use a simple paving pattern to indicate circulation both inside and outside the building. Use quick, simple indicationsfor tress, shrubs, and groundcover. When drawing the second-floor plan and open volumes of high spaces below, label them "open to below". 6. ELEVATIONS Show a design that incorporates aesthetic appeal, simple use of materials,and massing of formsthat indicateyou know how to integrate the internalfunctions of a buildingwiththe structure, fenestrationpattern, and human scale. Keep the elevations simple; try not to use more than two exterior materials in addition to glazing. Use simple material indications that are easy an<dquick to draw. Brick can be shown with closely spaced horizontal lines, stucco, stone, and precast concrete with stipple marks. Draw a heavy profile line around the perimeter of the elevation, and use v a r y m e w e i i g h t s to indicatethose portions of the elevation that are closest to the viewer --heaviestlinesclose and thinner lines farther away. The base line should be the heaviest and must correspondto the contour lines on the first-floorplan. Show the foundations and floor and ceiling levels with dashed lines. L --- --.-- Use a few scale figures and indicate landscapingif appropriate and if it corresponds to your site plan. However, the indications and other landscaping must not obscure the other elements of your design. Use shade shadowing iftime allows this a good way to provide contrast to the elevations and to indicateoverhangs and the form of the building more distinctly. C. SECTION Take the section cut through your buildingwhere most three-dimensional informationwill be shown. This includes two-storey spaces, changes in topography or levels of the building, areas for mechanical equipment, structure, and typical wall sections. Poche the cut sections of walls and foundations with solid black. Indicate ceiling heights and finish elevations of both first and second floors. Show the existing grade with a dashed line and the new grade at perimeter walls. Include a few scale figures. Clearly note the mechanical system, structural system, fire ratingof walls, roof system and roof drainage, ceiling finish, representative wall finishes, and footing depth. - D. DRAFTING TECHNIQUES AND FINAL CHECKS (7:30 8:00) Before you take the test you should decide on the type of drafting techniquesyou will use. You can completethe sketches with eitherfreehandor hard-line methods; use the one you feel most comfortablewith and the one that is fastest for you. Use simple block letteringon all the drawings and do not overdraft. Provide just enough to clearly present all the required information. In the half hour so you should leave at the end of the test for final checking make sure you have included everything specifically required by the problem statement. If you discover something is missing for your drawings and you do not have time to make changes, at least a note on the drawing to show the examiners you did not forget it. AREA "C" PART Ill SITE PLANNING AREA "C" PART III 1 A. DESIGN REQUIREMENTS RELATED TO TOPOGRAPHY A thorough knowledge of topography, its representationwith contour lines, and how contours are modified to suit the program requirements is mandatory for a 1 successful solution of the site design problem. As you work through the problem, keep the following points in mind. Although it is unlikely that you will have to locate a building on a site in this I portion of the exam, remember that it is better to ORIENT buildings with ' their length parallelto the contour lines. This makes modifying the contours easier and makes excavating and foundation work less expensive than an orientation perpendicularto the contour lines. Driveways and roads are best run parallelto if little or no change in elevation : is required. If a grade change is necessary, run the road at a slight angle to the existing contours and modify the road contour to provide for drainage. Roads should be laid out perpendicular to contour lines only if the resulting grade does not exceed recommended limits - usually 8 percent but a more gentle slope is preferred. Calculatethe slope after grade have been changed to verify that you are within recommended limits. Modify contours to BALANCE cut and fill. During the site exam you do not have to do detailed calculations, but it should appear that you are accomplishing this. One simple method is to draw as many new contour lines on the "FILL side of existing contour lines as you do on the "CUT" side at approximately the same distance from the existing lines. CONTOUR MODIFICATIONS FOR ROADS [area of fill f!area of cut a!,e ra (a) cut and fill balanced ' of fill area of Cut (b) fillexceeds cut BALANCE CUT AND FILL Minimize the amount of contour changes, since earth moving costs money and can create other problems such as steep grades; increasedexcavation costs, and a need for retaining walls. Make sure you have positive drainage away from buildings on all sides. This can be particularlytroublesome when the building is locatedparallel to the contours and therefore perpendicular to the natural drainage pattern. There should be a minimum of a 2 percent slope in landscaped areas away from the building, although 4 percent is preferred. These slopes correspondto 6.3 mmto 31 cm. (1 /4inch per foot) and .0126 M to 0.31 M (112" per foot) respectively. A comparison of percent slopes, slopes in inches per foot (mm to cm) and the visual qualities of various slopes is given in the table below. percent slope , inchesfloot rnmlcrn appearance 0.5% about I/, appears flat; use only for smoothest type of pavement 1.O% about I/, slope hardly noticeable 1.5% about Y1, good minimum for rough paving 2.0% about I/, noticeable in relation to level construction 2.5% about 5 / , , quite noticeable in relation to level construction 3.0% about 3/, very noticeable in relation to level construction - - (a) drainage directly into building (b) drainage diverted around building DRAINAGEAROUND BUILDINGS Drain approach walks away from buildings as well as landscaped areas. A minimum of 1 percent (118) inch per foot) (10 mm per meter) is required. Try to avoid elaborate drainage patterns or systems of drainage ditches and channels. In most cases, the drainage for the site design problemscan be accomplisheddirectly. If roads or paths must traverse ditches or drainage swales, make sure you maintain drainage with culverts and call them out on the plan. Check parking areas for proper drainage. Ideally, parking lot slopes should be between 1 '1, percent and 5 percent. Avoid very steep slopes that might be susceptible to erosion or make landscaping difficult. A 1 to 3 slope (0.10 M to 0.30 M) (4 inches per 12 inches) is considered the maximumfor a mowed grass slope while a 1 to 2 slope (6 inches per foot or 12 inches) (0.15 M to 0.30 M) is consideredthe maximum for unmowed landscape slopes. Steeper slopes require the use of retaining walls. B. PLANNING FOR CIRCULATION Separate pedestrian circulation from vehicular circulation. There should be walks next to parking lots that provide a path to the building. Provide ramps accessible by the physically disabled for all changes in elevation. Changes in elevation that cannot be made with a 1 in 20 sloped sidewalk are most efficientlyaccomplishedwith a rampthat returns on itself. Be aware of featuresadjacent to the site that generate pedestrianmovement, such as sidewalks, entrancesto nearby buildings, and public transportation stops. When the problem mentionsthese, it is important to providefor them. Locate vehicular entries to the site away from intersections. Cars waiting for a stop sign or stop light interfere with cars trying to pull into the site. In most cases, access from a one-way street is preferable to access from a two-way street.