NOTE: Attached CRS is part of this document. R1 R0 REV 01.06.22 18.05.22 ISSUE FOR APPROVAL LKY IKT MSI ISSUE FOR APPROVAL LKY IKT MSI PREPARED CHECKED APPROVED DESCRIPTION DATE OWNER & CLIENT RISING SUN ENERGY (K) PRIVATE LIMITED EPC CONTRACTOR STERLING & WILSON RENEWABLE ENERGY LTD CONSULTANT ARCHER BUSINESS SOLUTION PRIVATE LIMITED PROJECT TITLE OF DOCUMENT DRG. No: 190 MW (AC)/ 285Mwp (DC) SOLAR POWER PROJECT AT NOKH SOLAR PARK, NOKH (JAISALMER), RAJASTHAN. Design Basis Report - Electrical SW-IND-RSP-DBR-E-DOC-001 EPC CONTRACTOR: STERLING AND WILSON RENEWABLE ENERGY LTD CUST. DWG. NO --- CUST. PROJ. NO --- SHEET SIZE A4 DOC SOURCE DOCX ©COPYRIGHT STERLING & WILSON RENEWABLE ENERGY LTD COMPANY. All rights reserved. SUBMITTED FOR APPROVAL SCALE: Rev Sheet no R1 01 NTS DATE PREPARED BY LKY 01.06.22 INFORMATION CHECKED BY IKT 01.06.22 CONSTRUCTION APPROVED BY MSI 01.06.22 INDEX 1 GENERAL: ................................................................................................................... 2 1.1 1.2 1.3 1.4 1.5 Introduction: ....................................................................................... 2 Project summary: ................................................................................. 2 Codes and Standards:.............................................................................. 2 Site Details: ......................................................................................... 3 Environmental Details: ............................................................................ 3 2 SYSTEM CONFIGURATION: ....................................................................................... 3 3 4 ELECTRICAL SYSTEM PARAMETERS:..................................................................... 5 MAJOR ELECTRICAL EQUIPMENTS SPECIFICATION: ........................................... 6 4.1 4.2 4.3 4.4 4.5 4.6 4.7 4.8 4.9 4.10 4.11 4.12 5 AUXILIARY SUPPLY SYSTEM: ................................................................................. 17 5.1 5.2 6 Solar PV Modules: .................................................................................. 6 Solar/String Cable : ................................................................................ 7 PV Cable Connector : .............................................................................. 8 PV Branch Connector : ............................................................................ 9 String Combiner Box: ............................................................................ 10 Inverter: ........................................................................................... 10 LV AC cables: ..................................................................................... 12 DC Main Cables: .................................................................................. 13 Inverter Transformer: ........................................................................... 13 MV cables: ......................................................................................... 15 Cable Sizing Philosophy with respect to Losses as per Contract: ........................ 15 MV Switchboards: ................................................................................ 16 Aux Transformers: ............................................................................... 18 UPS ................................................................................................. 18 EARTHING SYSTEM: ................................................................................................ 18 7 LIGHTNING PROTECTION SYSTEM: ....................................................................... 19 8 SCADA SYSTEMS: .................................................................................................... 19 Power Plant Controller .................................................................................................... 22 9 WEATHER STATION:................................................................................................. 22 10 11 12 13 33 kV METERING KIOSK .......................................................................................... 23 CCTV SYSTEM & FIRE ALARM SYSTEM: ............................................................... 23 ILLUMINATION SYSTEM: ......................................................................................... 23 FIRE FIGHTING SYSTEM:......................................................................................... 24 14 CABLE CONDUITS .................................................................................................... 25 15 LUGS & TERMINATION ............................................................................................. 25 16 REFERENCES –. ....................................................................................................... 25 DESIGN BASIS REPORT - ELECTRICAL 1 GENERAL: 1.1 Introduction: This document lays down the brief system overview, design basis, various sub-system details for 190 MW Solar PV power plant. 1.2 Project summary: Rising Sun Energy Pvt Ltd., established in 2014. The company is working in the field of renewable energy, particularly solar, captive, rooftop & off grid installations and into setting up of R&D facility in India in collaboration with global partners. The Rising Sun energy has developed more than 140MW of solar plants. Rising Sun Energy (K) Pvt Ltd. 190MW solar project is a photovoltaic power plant that will be located in Rajasthan state of India, village Nokh Distt-Jaisalmer. The PV plant will be interconnected through a MV 33KV Circuit to the RSDCL Switchyard. The 33 kV metering kiosk at PSS end is considered the Point of Interconnection. System configuration The DC system comprises of 1500 V Zshine 540Wp,545Wp Mono Perc Half-cell PV modules. For All Wp modules string size is 30. PV Modules will be installed on module mounting structure of 2Px60 & 2Px30 Configurations with Fixed Tilt angle of 160 and 8 Meter Pitch. Inverter block comprises 4 Nos. of 3125 kVA / 2500 kVA 3-phase, Central Inverter and 12.5 MVA / 10 MVA, 5 winding- Inverter duty Transformer (33/0.66/0.66/0.66/0.66kV or 33/0.63/0.63/0.63/0.63kV). The output of the transformer is fed to the 33kV ICOG panel & 33 kV 3 breaker panel (outdoor type). From ICOG / 3 breaker panel, power shall be fed to 33 kV metering kiosk located in PSS. Outgoing power from 33kV metering kiosk Panel shall be fed to 33kV outdoor switchyard (not in SWREL scope). 1.3 Codes and Standards: General Codes and standards which shall follow for Electrical Design of PV plant are listed below. Indian Standard (IS) Code IE rules/CEA regulations CBIP Recommendations IEEE standards IEC standards RRVPNL Latest guidelines Generally, below standards shall be followed for system design, installation and testing & commissioning for plant. IS 1255: Cable installations IS 3043/IEEE80/CBIP Guidelines: Earthing system design IS 2309/NFC 17-102: Lightning protection system Doc No. SW-IND-RSP-GEN-E-DBR-001 Page 2 DESIGN BASIS REPORT - ELECTRICAL UL-864/IS 2189/EN 54-7/EN 54-2/EN 54-4/NFPA 72: Fire Alarm System IEC 60945/61000-4-2, 61000-4-6, EN61326-1: Weather Monitoring System IS 3646: Illumination/Lighting system State Electricity Board Standards/CBIP Guideline: Substation. IS/BS (relevant): Structure design Equipment installations & Testing shall be done as per manufacturer’s recommendations and applicable relevant Indian/international standards. 1.4 Site Details: Village Nokh District Jaisalmer State Rajasthan Co-ordinate 27°34'50.0"N, 72°13'30.83"E Airport Jodhpur (200 Km), Bikaner (130 Km) Nearest City 65KM Phalodi & 200KM from Jodhpur GIS S/S RSDCL Switchyard 1.5 Environmental Details: 2 Altitude Approx. 176m above MSL Maximum ambient temperature 50º C Minimum Ambient Temperature 3º C Average Wind Speed(10m): 1.6 m/s Humidity 45.50 % (Avg.), 74 % (Max.) Seismic Zone II Corrosion Category. C-3 corrosion (Medium) SYSTEM CONFIGURATION: The 190 MW solar power plant system configuration overview and description are summarized as follows. DC Capacity 285 MWp AC Capacity 190 MWac Doc No. SW-IND-RSP-GEN-E-DBR-001 Page 3 DESIGN BASIS REPORT - ELECTRICAL DC to AC ratio 1.50 Tilt of Module Mounting structure (MMS) 16° Fixed Pitch 8.0 m Collector width 4.401 m Inter row spacing 3.59 m Modules per mounting structure 60 (2x30 Portrait), 120 (2x60 Portrait), No of Inverter Transformer Stations 16 Nos No of Inverter 3.125MW per Block 4 No. No of Inverter 2.5MW per Block 4 No. No. of Inverter Transformer 12.5MW per Block 1 No. No. of ICOG/ 3 breaker panel Per Block 1 No. Total 12.5 MW inverter room 12 Nos. Total 10 MW inverter room 4 Nos. Total ICOG qty 10 Nos. Total 3 breaker panel qty 6 Nos. ELECTRICAL SYSTEM PV Module Type Mono Perc Half-cell (Free issue) Module rating 540Wp, 545Wp Total Modules Zshine 540Wp- 263400 Nos. Zshine 545Wp- 261960 Nos. Total strings 17512 Nos. Module per string 30 modules in series- 540Wp, 545Wp Strings per Y connector 2 nos. Modules per MMS 120 (2x 60 Potrait) & 60 (2x30 Potrait) 2 x 30: 550 Nos., 2 x 60: 4103 Nos., Total MMS NOTE: Total MMS will be as per site layout requirement. Inverter Type Central Doc No. SW-IND-RSP-GEN-E-DBR-001 Page 4 DESIGN BASIS REPORT - ELECTRICAL ELECTRICAL SYSTEM Inverter Rating 3125 kW @50 Degree, 2500 kW @50 Degree, 3125 KW Inverter Qty 48 Nos 2500 KW Inverter Qty 16 Nos Inverter Transformer Type ONAN Inverter Transformer rating 12.5 MVA, 12 Nos., 10 MVA, 4 Nos., Inverter Room MV Panel 33kV Outdoor ICOG panel & 3 breaker panel Inverter Room MV Panel Qty ICOG panel- 10 Nos, 3 breaker panel- 6 Nos For Overall Plant Key Single Line Diagram (Key SLD) refer drawing no. : - SW-IND-RSP-GEN-E-SLD-101 For DC single line diagram refer drawing no. : - SW-IND-RSP-GEN-E-SLD-100 For PLC/SCADA architecture refer drawing no. : - SW-IND-RSP-GEN-I-DRG-901 3 ELECTRICAL SYSTEM PARAMETERS: The following parameters are adopted in design engineering of the electrical system and associated equipment: 1 Nominal voltage 33kV 660/630V 415V 2 Highest system voltage 36kV - - 3 Number of phases 3Ph, 3W 3Ph, 3W 3Ph, 4W 4 Permissible variation in voltage ±10% ±10% ±10% 5 Frequency 50Hz 50Hz 50Hz 6 Permissible frequency ±3% ±3% ±3% 7 Combined variations in voltage 10% and frequency (absolute) 10% 10% variation Doc No. SW-IND-RSP-GEN-E-DBR-001 in Page 5 DESIGN BASIS REPORT - ELECTRICAL 4 8 Maximum fault level 25 kA for 1 50 kA for 1 sec sec 10 kA for 1sec 9 System neutral earthing Solidly earthed Solidly earthed Floating MAJOR ELECTRICAL EQUIPMENTS SPECIFICATION: This design basis covers the major electrical systems/ equipment/ commodities and design philosophy for the proposed PV solar power plant. 1. Solar PV module- Zshine 540Wp, 545Wp Mono Perc Half-cell module 2. Solar cable (String cable) 3. PV branch connectors 4. String Combiner Box 5. LT cables 6. Inverter 7. Inverter Transformer 8. MV cables 9. MV switchgears 10. Aux. Power supply system 11. UPS & Battery 12. Battery & Battery charger 13. Earthing, Lightning, Illumination 14. Plant Communication & SLDC/NRLDC connectivity 4.1 Solar PV Modules: The PV module converts the sunlight into DC electricity and certified for use up to system voltage of 1500 VDC. The Salient features for the PV module are as follows: Doc No. SW-IND-RSP-GEN-E-DBR-001 Page 6 DESIGN BASIS REPORT - ELECTRICAL Description of parameter Unit Nominal Values Nominal Power (± 5%) PMPP (W) 540 Wp 545 Wp Voltage at Pmax VMPP (V) 41.40 V 41.60 V Current at Pmax IMPP (A) 13.05 A 13.11 A Open Circuit Voltage VOC (V) 49.70 V 49.90 V Short Circuit Current ISC (A) 13.78 A 13.84 A Maximum System Voltage VSYS (V) 1500 V 1500 V Maximum Series Fuse ICF (A) 25 A 25 A (°C) 44±2℃ 44±2℃ -0.35%/℃ -0.35%/℃ Nominal Operating Temperature Temperature PMAX Cell Coefficient of TK (PMAX) Temperature Coefficient of VOC TK (VOC) -0.29%/℃ -0.29%/℃ Temperature Coefficient of ISC TK (ISC) 0.05%/℃ 0.05%/℃ NOTE: Terminal cable length of 1200 mm to be provided with PV Modules. Supply of PV Module is not in scope of EPC contractor. 4.2 Solar/String Cable : Solar cable of size 6mm2 Copper is used for connecting strings to string combiner box. Cable size is chosen based on the acceptable/reasonable power loss and voltage drop. The typical solar cable specification is as below: Doc No. SW-IND-RSP-GEN-E-DBR-001 Page 7 DESIGN BASIS REPORT - ELECTRICAL Description Nominal values Cable size 1Cx6 mm2 Nominal Voltage 1500 V dc Conductor material & type Annealed Tinned Flexible Copper Conductor as per EN 60228 Temperature range -40°C to +90°C (max. conductor temperature is 120°C) Insulation/Outer sheath type Electron bean cross-linked polyolefin co-polymer (XLPO) Armouring Unarmoured Properties UV, Flame Resistant, Weather, Halogen Free Applicable standard IEC60811-404, EN50396, IEC60332-1-2, IEC60068-2-78, IEC60287, IEC61034-2, EN 50395, EN 50252-1 Approval EN 50618 4.3 PV Cable Connector : Connectors are integral part of string connection of solar power which is used for string interconnection and also interconnect the parallel connection solar output from the Y connector to another solar cable which is intended to further connect to the String Combiner Box. The typical connector specification is as below: Description Rated Voltage Rated Current Connector type/compatible Contact Material Ambient temperature range Over Voltage category/Pollution degree Max temperature Contact Resistance Type of termination Insulation Material Doc No. SW-IND-RSP-GEN-E-DBR-001 Nominal values 1500V DC 50 A (6 mm2 ; 10AWG) PV-JK03M/xy series Copper, tin plated. -40 to +85 ̊C CATIII/2 110 ̊C ≤ 0.3mΩ Crimping PPE/PA Page 8 DESIGN BASIS REPORT - ELECTRICAL Protection class Applicable standard Degree of Protection II TÜV IEC 62852:2014 ; UL6703;IEC61730 IP 68 4.4 PV Branch Connector : PV branch connector of 2 in and 1 out type is proposed for first level string paralleling at module mounting structure. Two strings are paralleled through branch connector & the output of branch connector will be connected to String combiner box. The salient features of branch connector specifications are provided as below: Description Nominal values System voltage 1500V DC Type/Configuration/No of ways Rated Current PV-JK03M/xy series ,2 in & 1 out 50 A (6 mm2 ; 10AWG) Ambient Temperature 500C Degree of Protection IP 68 Application Class Class A Overvoltage Category / Pollution Degree CAT III/2 Fuse rating Fuse connector of 25A rating considered where Doc No. SW-IND-RSP-GEN-E-DBR-001 Page 9 DESIGN BASIS REPORT - ELECTRICAL Contact Resistance two strings are paralleled. (only for positive side) ≤ 0.5mΩ Protection Class Class II Conduction Material Silver Plated copper alloy Fuse assembly type Removable type with male & female connector Connectors PV Cable Connectors Applicable standard TÜV IEC 62852:2014 ; UL6703;IEC61730 4.5 String Combiner Box: Power from strings is combined at string combiner box (SCB). String combiner box essentially comprises of positive and negative bus, fuses, type 1+2 rated surge arrestors and dis-connector switch. From SCB the power is further transferred to inverter through DC cable. Details of SCB are as follows: Description Nominal values Rating 12+1 spare Input String Combiner Box Number of Inputs 12+1 spare No of Fuse per Input 1 Nos / String on +Ve side Fuse Rating 50 Amps Rated System Voltage 1500Volts DC Disconnector Switch Rating 500A/1500V Enclosure Material FRP Degree of Protection Output SPD Type IP-65, IK-10, (UL94Vo Flammability rating, UV resistance Test upto 2500Hrs.) Type- I+II SPD at 1500V O/P 4.6 Inverter: The Sineng make EP-3125-H B-UD & EP-2500-HA-UD Inverters are proposed. The inverter converts the DC power to AC power to facilitate feeding into the grid. The Salient features for the grid connect inverter are as follows: Doc No. SW-IND-RSP-GEN-E-DBR-001 Page 10 DESIGN BASIS REPORT - ELECTRICAL Description Nominal values Nominal DC Input Power 3125 kW at 50˚C, 2500 kW at 50˚C Maximum DC Input Power MPP Voltage 150% of Nominal at 50˚C 945 Vdc to 1300 Vdc, 900 Vdc to 1300 Vdc Input Current 4036A, 3260A Rated AC Output Power 3125 kW @ Cosϕ 1 & 50⁰C, 2500 kW @ Cosϕ 1 & 50⁰C Maximum AC Power at Cos ф=1 3738kVA at 30⁰C , 2875kVA at 30⁰C AC Voltage 660V, 50Hz, 3 Phase, 630V, 50Hz, 3 Phase Maximum AC Current 3270 A, 2635 A Maximum Efficiency 99.00% Euro Efficiency 98.70% Internal Consumption <4.0kW Degree of protection IP65 Ambient Temperature -30˚C to 60˚C Derating Temperature >50˚C Inbuilt Protections DC Side Over Voltage Protection Over Current Protection Reverse Polarity Anti PID Negative Grounding Ground Fault Monitoring Insulation Monitoring Over Heat Protection Surge Protection (Type I+II, Y configuration as per IEC 61643) Short Circuit Protection Fan Protection Emergency Switch AC side Doc No. SW-IND-RSP-GEN-E-DBR-001 Page 11 DESIGN BASIS REPORT - ELECTRICAL Description Nominal values Over / Under Voltage Protection Over Current Protection Current Balance Over / Under Frequency Protection Short Circuit Protection Surge Protection (Type II, Y configuration as per IEC 61643) Earth Fault 4.7 LV AC cables: 1Cx400 mm2 1.9/3.3kV [E] XLPE armoured Aluminium conductor LV cables shall be laid on the cable tray for connecting Inverter to Inverter Transformer. The cables size is selected considering the service current carrying capacity, short circuit current, and voltage drop and power loss criteria. Description Nominal values Cable size 1Cx400 mm2 Nominal Voltage 1.9/3.3kV [E] Conductor material & type Aluminium Stranded Compacted sector & Class 2 Operating conductor range 0 °C to 90° C Insulation Extruded XLPE Insulation as per IS: 7098 (P2) -2011 Armouring Flat strip H4 Grade 8130/2013 & IS: 3975 Outer sheath type Extruded FR PVC ST2 as per IS 5831 - 1984 Applicable standard IS 7098 Part II Doc No. SW-IND-RSP-GEN-E-DBR-001 Aluminium to IS Page 12 DESIGN BASIS REPORT - ELECTRICAL 4.8 DC Main Cables: 1Cx300/400 mm2 1.9/3.3kV [E] XLPE armoured Aluminium conductor LV cables shall be laid in Ground from SCB to Inverter. The cables size is selected considering the service current carrying capacity, short circuit current, and voltage drop and power loss criteria. Description Nominal values Cable size 1Cx300 / 400 mm2 Nominal Voltage 1.9/3.3kV [E] Conductor material & type Aluminium Stranded Compacted sector & Class 2 Operating conductor range 0 °C to 90° C Insulation Extruded XLPE Insulation as per IS: 7098 (P2) -2011 Armouring Flat strip H4 Grade 8130/2013 & IS: 3975 Outer sheath type Extruded FR PVC ST2 as per IS 5831 - 1984 Applicable standard IS 7098 Part II Aluminium to IS 4.9 Inverter Transformer: 12.5 MVA & 10 MVA capacity of the five winding step-up inverter duty transformer shall be chosen to suit the rated MVA capacity of the inverter for an ambient temperature of 50°C. The Salient features for the step-up transformer are as follows; Doc No. SW-IND-RSP-GEN-E-DBR-001 Page 13 DESIGN BASIS REPORT - ELECTRICAL Description Nominal values Rating 12.5 MVA, 33/.660/.660/.660/.660 kV 10 MVA, 33/.630/.630/.630/.630 kV Service Outdoor Number of phases Three Voltage HV – 33kV, LV – 660 / 630 V Frequency 50Hz Rated Current 1. HV 218.69 A , 174.95 A 2. LV. 4x2733.74 , 2291.13 A Vector group Yd11d11d11d11 Type of cooling ONAN Impedance (%): 7% (+/- IS Tol) Insulation Level 1. LV 40kVp/10kVrms 2. HV 170kVp/70kVrms Temp. rise over reference ambient 1. In oil thermometer 1. 50 °C 2. In winding by resistance 2. 55 °C Losses at Full Load at Unity PF No Load Loss Load Loss Type of tap changer Tapping range Approximate maximum Flux density Web/m2 1. At 90% rated voltage 2. At 100% rated voltage 3. At 110% rated voltage The Oil filled transformer is equipped with protections. Doc No. SW-IND-RSP-GEN-E-DBR-001 0.1% 0.9% OCTC (off load tap changer) +10% to –10%% in step of 2.5% 1.55 T 1.7 T 1.87 T ‐ Bucholz trip (63T) - (transformer mounted via marshalling box) ‐ Oil Temperature trip (26T)- (transformer mounted via marshalling box) ‐ Winding Temperature trip (49) - (transformer Page 14 DESIGN BASIS REPORT - ELECTRICAL ‐ 4.10 mounted via marshalling box) Pressure Relief Device mounted via marshalling box) (transformer MV cables: 1Cx185 mm2 & 1Cx300 mm2 33kV (E) XLPE armoured aluminium conductor cable, direct buried shall be used as required. The cables sizes are selected considering the short circuit current, service current carrying capacity, voltage drop and power loss criteria, Armour & metallic shield shall be as per calculated fault level and relay coordination. Underground Laying of cables will be with cable tie arrangement and above ground will be with trefoil arrangement. Description Nominal values Cable size 1Cx185 mm2 & 1Cx300 mm2 * Nominal Voltage 19/33 kV(E) Conductor material & type H4 Grade as per latest amendment of IS 8130 Aluminium Stranded Compacted circular & Class 2 Max. conductor temperature 90°C – Normal continuous operation 250°C – Short circuit condition Conductor shielding Extruded layer of semi-conducting compound Insulation Extruded XLPE as per IS:7098(P-2)/2011 Insulation shielding Extruded layer of non-magnetic semi-conducting compound Inner sheath Not applicable Armouring Aluminium Round Wire suitable to meet the calculated fault level for duration as per relay coordination. Outer sheath FR Extruded PVC ST2 (UV Protected with Anti-termite & anti rodent properties) Applicable standard IS 7098 Part II 4.11 Cable Sizing Philosophy with respect to Losses as per Contract: DC POWER losses can be proposed less than @ 1.75% average at Inverter level in the cable design calculations at 50 degree. Doc No. SW-IND-RSP-GEN-E-DBR-001 Page 15 DESIGN BASIS REPORT - ELECTRICAL Note: All DC cable shall be laid below MMS. 4.12 Overall AC Cable & Conductor loss will be 0.5% (i.e. from Inverter AC output till 33kV outgoing line). cable design calculations at 50 degree. MV Switchboards: The 33kV MV switchboards shall have following features; It shall be VCB, enclosed in air insulated switchboard type. Breaker shall have 3 positions-open, closed and earthed. Position of the power & earthing contacts shall be clearly visible on the front of the switchboard. Appropriate natural interlocking arrangement shall be done within the breaker to avoid unauthorized operations. Breaker manual TRIP arrangement with integrated push button on panel shall be provided. An operating mechanism can be used to manually close the circuit breaker and charge the mechanism. For 33kV Outdoor Type 33kV ICOG & 3 breaker Panel Control Supply for Closing coil, Tripping coil, Spring Charging motor, Protection & Auxiliary Relays and Indicating lamps will be 240 V AC UPS Supply with operating voltage range 85% to 110%. IEC 61850 Modbus Protocol to be followed for communication of relays & RS 485 for MFM with PLC/SCADA. The brief configuration of various 33kV MV Panels are described as given below; (a) 33kV ICOG @ Inverter station –Outdoor (IP55, 25kA for 1 Sec) - 10 Nos. Type feeder of No of Application feeder Breaker 01 Transformer and feeder VCB Rating Earth switch 630 A, SC 1 no Rating: 25 kA for 3 sec @ STC Protection Power Measurement 50/51, Through 0.5 50N/51N, 86, Class MFM 95 71, 63X, 49X,87T, 94, 80AC,PT fuse failure GE P645 (a) 33kV 3 Breaker panel @ Inverter station –Outdoor (IP55, 25kA for 1 Sec)- 6 Nos. Type feeder Breaker of No of feeder Application 01 Outgoing Power Doc No. SW-IND-RSP-GEN-E-DBR-001 VCB Rating Protection to 630A, SC Rating --25kA for 3 sec. Power Measurement --- Page 16 DESIGN BASIS REPORT - ELECTRICAL Transformer Breaker Breaker 1 1 Incoming from Adjacent ICOG-Panel 630A, SC Rating 50/51, Through 0.5 25kA for 3 sec 50N/51N, Class MFM 86, 94, 95, 80AC, Relay ABB REF 615H 630A, SC Rating 50/51, Through 0.5 25kA for 3 sec 50N/51N, Class MFM 86, 95 71, Incoming 63X, from Inverter 49X,87T, 94, trafo 80AC,PT fuse failure GE P645 SWITCHGEAR OPERATIONAL INTERLOCK Circuit breaker & respective earth switch Mechanical Prevent the removal of respective cable covers if circuit Electrical / Mechanical breaker is ‘ON’ Prevent the closure of circuit breaker if respective cable cover Electrical / Mechanical is open Cable test plug for CB accessible only if Earth switch Mechanical connected to earth 5 AUXILIARY SUPPLY SYSTEM: For Auxiliary supply system refer drawing no: - SW-IND-RSP-GEN-E-SLD-102 The plant auxiliary power supply shall be arranged by de-centralized distribution system. Each Inverter blocks are fed from suitably sized auxiliary transformers located in the inverter station and further will be distributed to various loads. Redundant supply for each inverter room by looping power supply with another Doc No. SW-IND-RSP-GEN-E-DBR-001 Page 17 DESIGN BASIS REPORT - ELECTRICAL nearest inverter room. Auxiliary transformer is suitably sized for two inverter room loads in case of failure of one Auxiliary transformer. Auxiliary transformer No-Load Loss <= 0.5%, Load Loss Max <= 2.5% Efficiency 97.5% at unity PF and full load. Aux loss of total plant will be 0.4%. 5.1 Aux Transformers: Rating 20kVA, 660 or 630 / 415V 50kVA, 660 or 630 / 415V - 63kVA, 660 or 630 / 415V – 8Nos. 4Nos. - 4 Nos Type Dry type Oil type Oil type 5.2 UPS Rating 3 kVA- 8Nos. 10 kVA- 1No. Battery Backup & type 120mins back up for ICR station; 120 mins back up for MCR; 12 V VRLA 12 V VRLA Batteries Batteries Location Inverter station Main Control Room 6 EARTHING SYSTEM: The Codes and standards referred for the design of earthing systems are as given below; ‐ IS 3043: Code of practice for Earthing – Maintenance free Earth pits considered. ‐ IS 3043/ IEEE 80, whichever applicable. Earthing system shall be in strict accordance with IS 3043 and Indian electricity rules/ acts. 260-ohm mtr. resistivity considered for design. maintenance free earth pit (Carbon based) with resistivity value of less than or equal to 0.7 ohm-m, 150 mm dia and 17.2mm copper clad steel rod of depth 3 mtr. Resistance of individual pit subject to change with change in resistivity value. AC /DC earthing grid and individual earth pits shall be connected and equipotential bonding shall be maintained. Metallic frame of all electrical equipment shall be earthed by two separate and distinct connections to earthing system. Earth Strip shall be installed in DC and MV cable trench along the cables and where separate trench to provided for earthing 600mm depth shall be kept. Connections between earth leads and equipment shall normally be of bolted type. Contact surfaces shall be thoroughly cleaned before connections. Equipment bolted connections after being tested and checked shall be painted with anti-corrosive paint/compound. Connections between equipment earthing leads and between main earthing conductors shall be of welded/bolted type. For rust protection the welds should be treated with red lead compound and afterwards thickly coated with bitumen compound. The material of the earthing conductors shall be as follows: Conductors above ground level and in built up trenches and buried - Galvanized steel earth strips Doc No. SW-IND-RSP-GEN-E-DBR-001 Page 18 DESIGN BASIS REPORT - ELECTRICAL 7 Earth electrodes @ Inverter Station & PV Yard – Maintenance free earth electrodes shall be provided for Inverter Stations, main control room & PV yard. The suitably sized earthing conductors for various electrical equipment’s based on prospective short circuit current. The exact size of earthing conductors required for various equipment and number of earth pits required to be used are detailed in respective design calculations. Module earthing shall be done as per installation guidelines of module manufacturer. All AC, DC, LA, earthing will be interconnected as per IEC-61000-5-02 1997 and overall resistance shall be less than 1 ohm. SCADA earthing will be separated and resistance value for SCADA shall be less than 4 ohms. LIGHTNING PROTECTION SYSTEM: The Codes and standards referred for the design of lightning protection system is as given below; IS 2309: Code of Practice for the protection of building and allied structures against lightning ‐ French standard NFC: 17-102-2011 The Inverter Station and PV area will be protected from external lightning. The protection system will be based on ESE (early streamer emission) lightning conductor air terminals as per NFC. The air terminals shall provide an umbrella protection against direct lightning strike covering a radial distance of maximum 107m with Level-IV protection. The air terminal will be capable of handling multiple strikes of lightning current and should be maintenance free after installation. The earthing stations for the lightning discharges shall be provided with test links and located at 1500mm above ground level in an easily accessible position for testing. LA Shadow from 8:30 AM to 4:30 PM to be considered. Accordingly, required shadow free space to be left around it. Each ESE LA will be provided with provided with Electromechanical Lightning strike counter. We will be providing two earth pits for each LA and both earth pits will be connected to DC Main grid as per IEC-61000-5-02 1997. ‐ 8 SCADA SYSTEMS: The Monitoring & Control system will be a PLC based rugged solution for providing the data acquisition, analysis, reporting and real-time performance monitoring from site and from remote location (through Internet). Doc No. SW-IND-RSP-GEN-E-DBR-001 Page 19 DESIGN BASIS REPORT - ELECTRICAL The power plant shall be provided SCADA system to monitor the input & output of each Inverter, Transformers, MV switchgear panels and weather stations so that system faults can be detected and rectified before they have an impact on production. Internet portal solution will be provided to access all data acquisition and real time performance monitoring can be done from office or remote areas. The SCADA system shall be composed of an integrated human-machine interface (HMI), input/output (I/O), PLCs communication infrastructure and software. SCADA for PV plant signals (MCR &ICR) considered. Redundant PLC controller considered for MCR PLC Panel. Remote PLC’s and I/O’s shall be used to collect data from various devises to transfer data to server which will carry out key functions. Detailed SCADA Architecture is mentioned in SW-IND-RSP-GEN-I-DRG-901 document. Plant Parameters: Inverter: Each input current monitoring, DC/AC voltage, power, pf, Energy MV switchgear panels at various inverter blocks: Transformer faults, relays, breaker & MFM data MV switchgear panel at Evacuation/Interconnection point (within plant): Active & Reactive Energy (Import/Export), Power factor (Import/export), Power, Voltage, frequencies, Grid status, Breaker status, Relay status & etc. Plant to LDC- As per Applicable grid code/NRLDC requirements. Plant Performance ratio on daily/monthly/quarterly/annual basis. Plant Capacity Utilization Factor on daily/monthly/quarterly/annual basis. Ring topology over OFC network considered for maintaining redundancy. Detailed IO signals (soft and hard-wired signals) are mentioned in SW-IND-RSP-GEN-I-LIST-902 document. REMOTE MONITORING OF SCADA: Apart from being able to Monitor the plant activities locally at site, monitoring of the plant on the SCADA application remotely via internet is considered with 3 web client licenses. The data exchange must be done over dedicated synchronous bandwidth over static IP. Internet must be routed through Firewall to ensure security of the operational system. PLANT COMMUNICATION & SLDC/NRLDC CONNECTIVITY: Telemetry system for real time data communication from PV Plant to RSDCL grid sub-station via OFC considered. System Requirements: Collect required parameters (All inverters, incomer, outgoing, WMS all analog and digital status from PV solar plant SCADA via redundant MODBUS TCP master ports. Provide all the required parameters same to RSDCL via redundant IEC-104 slave links. Provide optical interface components at solar plant and RSDCL Grid substation. Exact I/O point will be decided during detailed engineering as per NRLDC requirement. Doc No. SW-IND-RSP-GEN-E-DBR-001 Page 20 DESIGN BASIS REPORT - ELECTRICAL Meteorological Parameter: Following parameters will be integrating with SCADA through WMS datalogger. Global Horizontal Irradiation. Global Irradiance on inclined plain. Ambient air temperature. Relative humidity. Module temperature. Wind speed and direction. A Combination of MODBUS RS485, TCP/IP / LAN and Optic Fibre cables shall be used in a distributed network for communication between Field device. Likewise, the communication network at all the Inverter Blocks shall be connected to the main control room via OFC. CCTV will be communicating to NVR at MCR through same network. The PV Plant SCADA architecture worked out shall be referred for further details and understandings. Brief of SCADA specification as below. The system shall be provided with Supervisory Station that will refer to the server and software responsible for communicating with the field equipment, and then to the HMI software running on workstations in the main control room. Combination of Modbus, Industrial grade Ethernet LAN and fibre optic network shall be distributed throughout the field for communication to field devices. FO Cable network shall be in ring topology for better redundancy. The 2 nos. of OMS and EMS server to be chosen with Raid Configuration, redundant power supply and dual Ethernet. 50 Inch HD quality 1 No Monitor additional for viewing at SCADA room The SCADA shall be PLC based and shall be provided with two processors (Main processing unit and memories) one for normal operation and one as hot standby. In case of failure of working processor, there shall be an appropriate alarm and processor shall be totally bump less and shall not cause any plant disturbance whatsoever. In the event of both processors failing, the system shall revert to fail safe mode. It shall be possible to keep any of the processors as master and other as standby. The standby processor shall be updated in line with the changes made in working processor. Doc No. SW-IND-RSP-GEN-E-DBR-001 Page 21 DESIGN BASIS REPORT - ELECTRICAL Communication protocol for shall be based Modbus and TCP/IP. Power Plant Controller The power plant controller shall be integrated with the SCADA and operation of Power Plant Controller will be through a dedicated system. Power Plant Controller (PPC) designed mainly to communicate and to regulate the reactive power of the PV plant, in such a way that the PV plant is watched like a single generator at the Point of Interconnection. Redundant Power plant controller (PPC) system with monitor considered. The control system can provide the following functionalities (in coordination and depending on the capability of the inverters). Active power curtailment This functionality limits the active power at the Point of interconnection to a defined value, dispatching suitable reference values to the available inverters ramp rate limiter is used on the set points. Ramp rate limiter is the feature of inverter to control the active power export from inverter. Voltage / Reactive power regulation The system operates alternately (in one of the three modes) by power factor control, voltage control or reactive power control at the point of interconnection, dispatching suitable reference values to the available inverters 9 WEATHER STATION: The power plant weather station (self-powered -solar panel with battery) comprises the below sensors/instruments which are used for different purposes are as follows: Primary WMS System: 3 Sets. Datalogger- 1 No. Ethernet Interface with Extended data Storage Module- 1 No. Pyranometer- SMP10- 2 Nos. Ambient Temperature & Relative humidity sensor- 1 No. Anemometer & Wind Wane- 1 No. Module Temperature Sensor- 4 Nos. Rain Gauge Sensor- 1 No. Barometric Pressure sensor- 1 No. Power Supply- 1 No. Mounting Hardware & Enclosure- 1 No. Soiling station- 1 No. SLDC Sensors Cloud Cover Sensor -1No Diffuse & Direct Irradiance Sensor with Tracker-1No Secondary WMS Components: 7 Sets Tilted Pyranometer - 1No Module Temperature Sensor -2 Nos Data logger - 1No Mounting Hardware & Enclosure - 1 No Power supply - 1 No Doc No. SW-IND-RSP-GEN-E-DBR-001 Page 22 DESIGN BASIS REPORT - ELECTRICAL Soiling station shall be provided to monitor and analyse the effect of soiling on the energy generation through PV Modules. This shall be a standalone system integrated with the plant monitoring system. The system shall essentially comprise of two modules, of which one can soil naturally while the other is cleaned as per the PV module cleaning regime. Power output of both the modules shall be monitored thus enabling the O&M team to determine the optimized cleaning schedules. Proposed WMS datalogger will communicate to SCADA through TCP/IP Modbus Protocol and soiling station will communicate with SCADA directly through TCP/IP Modbus protocol. 10 33 kV METERING KIOSK 33kV Metering Kiosk shall be placed in PSS area. The Metering boards shall have outdoor IP55 protection class having Double door front, single tier, fully compartmentalized, metal enclosed construction. It shall consist of TVM meter along with metering CT, PT and LA.Tri vector meter (TVM) shall be communicable with SCADA and have RS485 communication Port. It will be used for measurement of PR. It shall comply with RSDCL technical specification. 11 CCTV SYSTEM & FIRE ALARM SYSTEM: CCTV will be communicating to NVR at MCR through same OFC network considered for SCADA. CCTV monitoring at MCR considered. SL 1 2 3 4 5 Item Description PTZ Type CCTV Camera @ Main gate + Strategic locations Bullet Type CCTV Camera for ICR, entry and exit gate Dome Type CCTV Camera @each Security cabin and Inside MCR entrance and SCADA room NETWORK VIDEO RECORDER – 64 CHANNELS 53# LED MONITOR @ SCADA room Unit Qty 7 Nos 23 Nos 9 Nos 1 No 1 No Conventional type FAS shall be installed in MCR and each ICR. Conventional fire alarm systems and its components are all wired to the same cable that connects them to a fire alarm control panel. When a component is activated, a signal is displayed on the control panel. 12 ILLUMINATION SYSTEM: Lighting shall be designed with LED light fixture and lux level as follow: S. No Location Doc No. SW-IND-RSP-GEN-E-DBR-001 Light fixture Page 23 DESIGN BASIS REPORT - ELECTRICAL 1 2 Inverter area, ICOG panel, Transformer area Periphery road Average of 50lux for the inverter stations . 30 W LED mounted on 4 M High Lighting Pole installed at every 40 Meters along the peripheral road. Avg lux will be 5. LED fixtures aligned to achieve lux level as mentioned for below areas Main Control Room 3 Avg 300 lux for the main control room, admin / SCADA rooms, 200 lux in switchgear shall be maintained 20% Lights in MCR, Inverter Station & Switchyard will be fed through emergency supply. 13 FIRE FIGHTING SYSTEM: The solar PV plant shall be equipped with suitable fire protection and fighting systems for entire PV array area, all control rooms as per the fire safety standards and local fire authority requirements. Firefighting of transformers and other electrical equipment’s as required shall be in accordance to tariff advisory committee guidelines, CBIP, IS 10028, NFPA 190 and NFPA 15. Fire Extinguishers: Portable type fire extinguishers conforming IS10658 shall be provided as means of dealing effectively and immediately with fire caused from oils, solvents, gases, paints, varnishes, electrical wiring and all flammable liquids and gases. System shall comply with required insurance norms. Following type of portable fire extinguishers shall be provided in PV array area, modular block control rooms and main control room. DCP type fire extinguisher CO2 operated hand portable extinguisher Foam type hand portable extinguisher Fire buckets: Fire buckets shall be provided in all modular unit control rooms with fine sand and fixed on an angle iron frame as per requirement of local authorities. Fire buckets shall be painted red with additional handle at the bottom and a cover to avoid moistening of sand. NIFPS: Oil filled Inverter transformer shall be provided with a dedicated Nitrogen Injection system for prevention against the transformer explosion which shall use nitrogen as quenching medium. The system shall prevent Transformer oil tank explosion and possible fire in case of internal / external cause. NIFPS panel shall be made of CRCA sheet of 3mm (minimum) thick complete with the base frame, painted inside Doc No. SW-IND-RSP-GEN-E-DBR-001 Page 24 DESIGN BASIS REPORT - ELECTRICAL and outside with post office red colour. It consists of Nitrogen gas cylinder with regulator, drain pipes, pressure monitoring switch. It will have Control box for monitoring system operation, automatic control, and remote operation. NIFPS Panel shall be mounted inside inverter control room. 14 CABLE CONDUITS 40/32 MM Diameter DWC HDPE pipe consisting of two layers, i.e. the outer layer is corrugated and the inner layer is plain and smooth will be used for laying the UV rated string cables and unarmoured communication cables (if any). Similar potential cables in flexible conduit will be laid to avoid any risk of short circuits. Conduit filling will be as per cable sizing calculation taking all applicable derating factors into consideration. Conduits shall not be filled more than 40% of inside space. UV protected and helogen free material will be used for manufacturing of 40/32 MM Diameter DWC HDPE pipe. 15 LUGS & TERMINATION Type, material and dimension of lugs will be based on terminal busbar and equipment manufacturer recommendation for termination. Termination of 33kV cables heat shrinkable type termination kits as per IS: 13573- Part 2, 2011 will be used for for indoor/outdoor installation. Bimetallic lug intend to be installed on circular or pre-rounded sectorial shaped, stranded, compacted aluminum conductors of power cables as terminals connected to copper busbars. Copper as per IS -191 & Aluminum as per IS-5082. All power cable terminals lugs will be conforming to IS : 8309. The dimension and tolerances as per as per Table-2 of IS: 8309. 16 REFERENCES –. Master Drawing List (which is capturing all the major design documents). Doc No. SW-IND-RSP-GEN-E-DBR-001 Page 25 DESIGN BASIS REPORT - ELECTRICAL NOTE: IN SOME PART OF THIS DOCUMENTS THE PICTURES OR SNAPS SHOWN IS JUST FOR ILLUSTRATION PURPOSE ONLY. - END - Doc No. SW-IND-RSP-GEN-E-DBR-001 Page 26 Customer RISING SUN ENERGY (K) PRIVATE LIMITED Consultant ARCHER BUSINESS SOLUTION PVT LTD EPC STERLING & WILSON RENEWABLE ENERGY LTD. Project name 190 MW (AC)/ 285Mwp (DC) SOLAR POWER PROJECT AT NOKH SOLAR PARK, NOKH (JAISALMER), RAJASTHAN. Drawing/ Document No. Subject Revision No. SW-IND-RSP-DBR-E-DOC-001 COMMENTS ON DESIGN BASIS REPORT - ELECTRICAL Sr. No. R1 Rising Sun Energy/ Archer Business Solution Comments SWSL Response RSEKPL / ABSPL Response 1 Clause 1.2, Page-3, Line-1: Name of Client to be written as Rising Sun Energy Pvt Ltd. Revised Noted 2 Clause 1.2, Page-3, Para-2: Name of Client/SPV to be written as Rising Sun Energy (K) Pvt Ltd. Revised Noted 3 4 5 6 7 Plant Communication & SLDC Connectivity: Include NRLDC with Revised SLDC. Illumination System: Mention Lux level of Periphery Road Lighting Revised also. Kiosk details included. PPC detail is already mentioned.pls Details of 33kV Kiosk, PPC to be included. refer SCADA part. Fire fighting system revised and Fire alarm system is already Details of Fire Fighting to be included. mentioned in CCTV and FAS. Fault Current Consideration reference to be mentioned in the 33kV fault level 25kA as per RFQ, 660 V side as per inverter document trafo imp. 3125/1.732/.66/.07 = 39kA and DC side max feed 5kA. However we have considered 50 kA which is more. For 415 V side max Aux trafo 63KVA having imp 4% so fault current at 415V side =63/.04/1.732/415 = 2.2 kA however we have considered the equipment for 10kA. detail SC fault current calculation will be submitted seperately for approval. Noted Noted Noted Noted Noted