Flat Slab resting directly on columns 1. What is a flat slab? 31.1 General The term flat slab means a reinforced concrete slab with or without drops, supported generally without beams, by columns with or without flared column heads Flat slab with drop panel and column head A flat slab may be solid slab or may have recesses formed on the soffit so that the soffit comprises a series of ribs in two directions. The recesses may be formed by removable or permanent filler blocks. Flat Slab with drop panels Flat slab with column head What is mean by Flat Slab? • A reinforced concrete slab supported directly by concrete columns without the use of beams. • Flat slabs are highly versatile elements widely used in construction, providing minimum depth, fast construction and allowing flexible column grids. Construction: The benefits of choosing flat slabs include a minimum depth solution, speed of construction, flexibility in the plan layout (both in terms of the shape and column layout). HISTORICAL DEVELOPMENT • Flat slabs were originally invented in the U.S.A in year 1906. • This was the start of these type of construction. • Many slabs were load-tested between 1910-20 in U.S.A. • 1914 Nicholas proposed a method of analysis of these slab based on simple statics, this method is know as direct design method. BASIC DEFINITION OF FLAT SLAB The term flat slab means a reinforces concrete slab with or without drop, supported generally without beams, by column with or without flared column heads. APPLICATION OF FLAT SLAB In the case of high rise building thinner slabs are required so that additional floors can be added. The distance that be spanned by post-tensioned slabs exceeds that of reinforced constructions with the same thickness. For increasing span lengths so as to increases the usable unencumbered floor space in buildings. For diminishing the number of joints in the structure. For the speedy construction of the project. The amount of steel required is much less than in normal RCC structure. The moulds can be used No. of times as per the demand. Due to reduce beam section the load transferred to foundation is less compared to that of RCC structure. The structure is crack free as the whole structure is in compression. Large span of slab can obtain easily. ADVANTAGES OF FLAT SLAB Floor to floor height reduction Faster construction Early formwork stripping Water resistant properties Saving in materials. Reduced foundation load Greater column free areas Architectural freedom Reduced construction costs LIMITATION OF FLAT SLAB Careful handling of prefabricated components such as concrete panels or steel and glass panels is required. Attention has to be paid to the strength and corrosion-resistance of the joining of prefabricated sections to avoid failure of the joint. Similarly, leaks can form at joints in prefabricated components. Transportation costs may be higher for voluminous prefabricated sections than for the materials of which they are made, which can often be packed more compactly. Types: 1. Typical flat slab 2. Slab without drop and column with column head. 3. Slab with drop and column without column head 4. Slab with drop and column with column head. Uses of column head: •Increase shear strength of slab . •Reduce the moment in the slab by reducing the clear or effective span. Uses of drop panels : •Increase shear strength of slab •Increase negative moment capacity of slab. 1. Typical flat slab:• This may be called as beam-slab construction. Hence in warehouses, offices and public halls some times beams are avoided and slabs are directly supported by columns. • This types of construction is aesthetically appealing also. These slabs which are directly supported by columns are called Flat Slabs. 2.Slab without drop and column with column head: • The column head is some times widened so as to reduce the punching shear in the slab. • The widened portions are called column heads. The column heads may be provided with any angle from the consideration of architecture but for the design, concrete in the portion at 45º on either side of vertical only is considered as effective for the design. 3.Slab with drop and column without column head: • Moments in the slabs are more near the column. Hence the slab is thickened near the columns by providing the drops. • Sometimes the drops are called as capital of the column. 4.Slab with drop and column with column head: Flat slab system: • 1.One way system: • One way slab is supported on two opposite side only thus structural action is only at one direction. Total load is carried in the direction perpendicular to the supporting beam. • If a slab is supported on all the four sides but the ratio of longer span to shorten span is greater than, then the slab will be considered as one way slab. 2. Two way slab: • Two way slabs are the slabs that are supported on four sides and the ratio of longer span to shorter span is less than. • In two way slabs, load will be carried in both the directions. So, main reinforcement is provided in both direction for two way slabs. Advantages: • Simple formwork • No beams—simplifying under-floor services outside the drops • Minimum structural depth. Disadvantages: • Drop panels may interfere with larger mechanical ducting. • Vertical penetrations need to avoid area around columns. INTRODUCTION What is a flat slab? • a reinforced concrete slab supported directly concrete columns without the use of beams by INTRODUCTION Flat slab Flat slab with column head Flat slab with drop panels Flat slab with drop panel and column head INTRODUCTION Uses of column heads : • increase shear strength of slab • reduce the moment in the slab by reducing the clear or effective span Flat slab with column head INTRODUCTION Uses of drop panels : • increase shear strength of slab • increase negative moment capacity of slab • stiffen the slab and hence reduce deflection BENEFITS BENEFITS • • • • • • Flexibility in room layout Saving in building height Shorter construction time Ease of installation of M&E services Prefabricated welded mesh Buildable score Benefits . . . FLEXIBILITY IN ROOM LAYOUT • allows Architect to introduce partition walls anywhere required • allows owner to change the size of room layout • allows choice of omitting false ceiling and finish soffit of slab with skim coating Benefits . . . SAVING IN BUILDING HEIGHT • Lower storey height will reduce building weight due to lower partitions and cladding to façade • approx. saves 10% in vertical members • reduce foundation load Slab Slab Beam 3.4m 2.8 m Conventional 2.8 m 3.2 m Beam-Free Benefits . . . SHORTER CONSTRUCTION TIME flat plate design will facilitate the use of big table formwork to increase productivity Benefits . . . SINGLE SOFFIT LEVEL Kitchen 30 26 0 Living Room 30 Toilet Sho wer 75 155 Balcony 30 Yard 30 Single Level Ceiling FlatPlate Slab • Simplified the table formwork needed Benefits . . . EASE OF INSTALLATION OF M&E SERVICES • all M & E services can be mounted directly on the underside of the slab instead of bending them to avoid the beams • avoids hacking through beams Benefits . . . PRE-FABRICATED WELDED MESH • Prefabricated in standard sizes • Minimised installation time • Better quality control Benefits . . . BUILDABLE SCORE • allows standardized structural members and prefabricated sections to be integrated into the design for ease of construction • this process will make the structure more buildable, reduce the number of site workers and increase the productivity at site • more tendency to achieve a higher Buildable score DESIGN CONSIDERATIONS Design Considerations. . . . WALL AND COLUMN POSITION • Locate position of wall to maximise the structural stiffness for lateral loads • Facilitates the rigidity to be located to the centre of building Typical floor plan of Compass the Elizabeth Design Considerations. . . . OPTIMISATION OF STRUCTURAL LAYOUT PLAN • the sizes of vertical and structural structural members can be optimised to keep the volume of concrete for the entire superstructure inclusive of walls and lift cores to be in the region of 0.4 to 0.5 m3 per square metre • this figure is considered to be economical and comparable to an optimum design in conventional of beam and slab systems Design Considerations. . . . DEFLECTION CHECK • necessary to include checking of the slab deflection for all load cases both for short and long term basis • In general, under full service load, < L/250 or 40 mm whichever is smaller • Limit set to prevent unsightly occurrence of cracks on nonstructural walls and floor finishes Design Considerations. . . . CRACK CONTROL • advisable to perform crack width calculations based on spacing of reinforcement as detailed and the moment envelope obtained from structural analysis • good detailing of reinforcement will – restrict the crack width to within acceptable tolerances as specified in the codes and – reduce future maintenance cost of the building Design Considerations. . . . FLOOR OPENINGS • No opening should encroach upon a column head or drop • Sufficient reinforcement must be provided to take care of stress concentration Design Considerations. . . . PUNCHING SHEAR • always a critical consideration in flat plate design around the columns • instead of using thicker section, shear reinforcement in the form of shear heads, shear studs or stirrup cages may be embedded in the slab to enhance shear capacity at the edges of walls and columns Design Considerations. . . . PUNCHING SHEAR Shear Studs Design Considerations. . . . CONSTRUCTION LOADS • critical for fast track project where removal of forms at early strength is required • possible to achieve 70% of specified concrete cube strength within a day or two by using high strength concrete • alternatively use 2 sets of forms Design Considerations. . . . LATERAL STABILITY • buildings with flat plate design is generally less rigid • lateral stiffness depends largely on the configuration of lift core position, layout of walls and columns • frame action is normally insufficient to resist lateral loads in high rise buildings, it needs to act in tendam with walls and lift cores to achieve the required stiffness Design Considerations. . . . LATERAL STABILITY MULTIPLE FUNCTION PERIMETER BEAMS • adds lateral rigidity • reduce slab deflection DESIGN METHODOLOGY Design methodology .. . METHODS OF DESIGN • the finite element analysis • the simplified method • the equivalent frame method Design methodology .. . FINITE ELEMENT METHOD • Based upon the division of complicated structures into smaller simpler pieces (elements) whose behaviour can be formulated. • E.g of software includes SAFE, ADAPT, etc • results includes – moment and shear envelopes – contour of structural deformation and Design methodology .. . SIMPLIFIED METHOD Table 3.19 may be used provided • Live load > 1.25 Dead load • Live load (excluding partitions) > 5KN/m2 • there are at least 3 rows of panels of approximately equal span in direction considered • lateral stability is independent of slab column connections Design methodology .. .. SIMPLIFIED METHOD Table 3.19: BM and SF coefficients for flat slab or 3 or more equal spans Outer Support Near centre of 1st span Column Wall Moment -0.04Fl* 0.086Fl 0.083Fl* Shear 0.45F 0.4F - 0.04Fl - - Total column moments First interior span -0.063Fl 0.6F 0.022Fl Centre of interior span Interior span 0.071Fl -0.055Fl - 0.5F - 0.022Fl * the design moments in the edge panel may have to be adjusted according to 3.7.4.3 F is the total design ultimate load on the strip of slab between adjacent columns considered (1.4gk + 1.6 qk) l is the effective span Design methodology .. . EQUIVALENT FRAME METHOD • most commonly used method • the flat slab structure is divided longitudinally and transversely into frames consisting of columns and strips of slabs with : – stiffness of members based on concrete alone – for vertical loading, full width of the slab is used to evaluate stiffness – effect of drop panel may be neglected if dimension < lx/3 Design methodology .. . EQUIVALENT FRAME METHOD Plan of floor slab Step 1 : define line of support in X & Y directions Design methodology .. . EQUIVALENT FRAME METHOD 9 10 10 9.2 0.8 DESIGN STRIP IN PROTOTYPE 9 10 10.6 10.5 0.8 STRAIGHTENED DESIGN STRIP Step 2 : define design strips in X & Y directions DESIGN STRIP IN ELEVATION ANALYSIS OF FLAT SLAB Analysis of flat slab.. COLUMN HEAD Effective dimension of a head , lh (mm) =lesser of lho or lh max where lho = actual dimension, lh max = lc + 2(dh-40) (i) lh = lh, max lh max lho lc (ii) lh = lho dh lh max lho lc dh Analysis of flat slab.. COLUMN HEAD (iii) lh = lh, max dh lh max lho 40 (iv) lh = lho lh max lc For circular column or column head, effective diameter , hc = 4 x area/ < 0.25lx lho lc dh Analysis of flat slab.. DIVISION OF PANELS The panels are divided into ‘column strips’ and middle strips’ in both direction. (a) Slab Without Drops Column strip middle strip (ly-lx/2) Column strip lx/4 lx/4 middle strip lx/4 ly (longer span) lx (shorter span) lx/4 Analysis of flat slab.. Slab With Drops Drop middle strip (ly-drop size) lx/4 middle strip Column strip = drop size ly (longer span) note : ignore drop if dimension is less than lx/3 l x Dro p (b) Analysis of flat slab.. MOMENT DIVISION Apportionment between column and middle strip expressed as % of the total negative design moment Column strip Middle strip Negative 75% 25% Positive 55% 45% • Note : For slab with drops where the width of the middle strip exceeds L/2, the distribution of moment in the middle strip should be increased in proportion to its increased width and the moment resisted by the column strip should be adjusted accordingly. Analysis of flat slab.. MOMENT DIVISION - EXAMPLE 6000 6000 6000 6000 6000 5000 7000 Layout of building 5000 A floor slab in a building where stability is provided by shear walls in one direction (N-S). The slab is without drops and is supported internally and on the external long sides by square columns . The imposed loading on the floor is 5 KN/m2 and an allowance of 2.5KN/m2 for finishes, etc. fcu = 40 KN/m2, fy = 460KN/m2 Analysis of flat slab.. MOMENT DIVISION - EXAMPLE 6000 6000 6000 6000 1250 5000 2500 3500 2500 2750 7000 4000 3000 3000 1500 3500 2500 Division of panels into strips in x and y direction Analysis of flat slab.. MOMENT DIVISION - EXAMPLE 6000 6000 200 200 35 3500 35 2500 200 Column strip 3000 3000 exterior support centre of 1st span 200 369 = 0.75*35 on 2.5m strip = 10.5Knm = 0.55*200 on 2.5 strip = 44KNm = 0.75*200 on 3m strip = 50KNm 1st interior support centre of interior span = 0.55 *369 on 3m strip = 67.7KNm 3500 2500 Middle strip exterior support centre of 1st span = 0.25*35 on 2.5m strip = 3.5KNm = 0.45*200 on 2.5 strip = 36KNm 1st interior support = 0.25*200 on 3m strip = 16.7KNm centre of interior span = 0.45 *369 on 3m strip = 55.4KNm Analysis of flat slab.. DESIGN FOR BENDING INTERNAL PANELS • columns and middle strips should be designed to withstand design moments from analysis Analysis of flat slab.. DESIGN FOR BENDING EDGE PANELS • apportionment of moment exactly the same as internal columns • max. design moment transferable between slab and edge column by a column strip of breadth be is Mt, max = 0.15 be d2 fcu < 0.5 design moment (EFM) < 0.7 design moment (FEM) Otherwise structural arrangements shall be changed. Analysis of flat slab.. PUNCHING SHEAR 1. Calculate Veff =kVt at column perimeter (approx. equal span) Vt = SF transferred from slab k = 1.15columns for internal 1.25 where corner and column, edge columns M acts parallel to free edge and 1.4 for edge columns where M acts at right angle to free edge Column perimeter Perimeter A Perimeter B 3d 3d 4 2 Column perimeter Perimeter A Perimeter B Perimeter C 3d 3d 3d 4 4 2 lx/3 2. Determine vmax= Veff /uod where uo is the Checkof vma < 0.8 perimeter f cu or 5 N/mm2 length column 3. Determine v=(Veff -V/ud) where u is the length of perimeter A and V is the column load and check v < vc 4. Repeat step 3 for perimeter B and C Analysis of flat slab.. DEFLECTION Span/depth ratio Cantilever 7 Simply supported 20 Continuous 26 (i) use normal span/effective depth ratio if drop width >1/3 span each way; otherwise (ii) to apply 0.9 modification factor for flat slab, or where drop panel width < L/3 1.0 otherwise Analysis of flat slab.. OPENINGS Holes in areas bounded by the column strips may be formed providing : • greatest dimension < 0.4 span length and lx (shorter span) • total positive and negative moments are redistributed between the remaining structure to meet the changed conditions ly (longer span) Analysis of flat slab.. OPENINGS Holes in areas common to two column strips may be formed providing : that their aggregate their length or width does not exceed one-tenth of the width of the column strip; • that the reduced sections are capable of resisting with the moments; and • that the perimeter for calculating the design shear stress is reduced if appropriate lx (shorter span) • ly (longer span) Analysis of flat slab.. OPENINGS Holes in areas common to the column strip and the middle strip may be formed providing : that in aggregate their length or width does not exceed one-quarter of the width of the column strip and • that the reduced sections are capable of resisting the design moments lx (shorter span) • ly (longer span) Analysis of flat slab.. OPENINGS For all other cases of openings, it should be framed on all sides with beams to carry the loads to the columns. DETAILING OF FLAT SLAB Detailing of flat slab .. . TYPE OF REINFORCEMENT F-mesh - A mesh formed by main wire with cross wire at a fixed spacing of 800 mm Main wire - hard drawn ribbed wire with diameter and spacing as per design Cross wire - hard drawn smooth wire as holding wire H8-800mm c/c for main wire diameter > 10mm Detailing of flat slab .. . TYPE OF REINFORCEMENT F-Mesh 2 Main Wire Holding Wire Holding Wire (800mm c/c) Main Wire F-Mesh 1 Holding Wire TensionLap = 45 dia. Main Wire Holding Wire Main Wire Plan View of Mesh Layout Main Wire F - Mesh Main Wire Cross Wire F - Mesh Main Wire Cross Wire Detailing of flat slab .. . REINFORCEMENT FOR INTERNAL PANELS • Reinforcement are arranged in 2 directions parallel to each span; and • 2/3 of the reinforcement required to resist negative moment in the column strip must be placed in the centre half of the strip • for slab with drops, the top reinforcement should be placed evenly across the column strip STANDARD LAPPING OF MESH (FOR FLAT SLAB) TYPICAL DETAIL SHOWING RECESS AT SLAB SOFFIT FOR SERVICES TYPICAL SECTION AT STAIRCASE DETAILS OF INSPECTION CHAMBER AT APRON DETAILS OF INSPECTION CHAMBER AT APRON DETAILS OF INSPECTION CHAMBER AT APRON DETAILS OF INSPECTION CHAMBER AT APRON DETAILS OF INSPECTION CHAMBER AT PLAY AREA 1ST STOREY (DWELLING UNIT) SLAB DETAILS OF HOUSEHOLD SHELTER TYPICAL DETAILS OF 125X250 RC CHANNEL FOR GAS PIPE ENTRY INTRODUCTION CLASSIFICATION OF FLAT SLAB SYSTEM 1. Solid flat slab(or flat plate) 2. Solid flat slab with drop panels 3. Solid flat slab with column heads 4. Banded flat slab 1.Solid flat slab(or flat plate) 2.Solid flat slab with drop panels 3. Solid flat slab with column heads 3.Banded flat slab METHOD OF CONSTRUCTION SYSTEM The flat slabs can be cast-in-situ (cast-in-place). Else, the slabs can be precast at ground level and lifted to the final height. The later type of slabs is called lift slabs. 1. POST TENSIONING SYSTEM 2. PRE TENSIONING SYSTEM 1. POST TENSIONING SYSTEM 2. PRE TENSIONING SYSTEM 2. PURPOSE TENSIONING SYSTEM To reduce the deflection. To reduce the punching shear. Reduced structure depth To Greater column free areas. Reduces the required number of columns and foundations. To Increase load bearing capacity. To bear seismic forces. COMPONENT PARTS OF FLAT SLAB Column strip 2. Middle strip 3. Panel. 1. ANLYSIS OF FLAT SLAB The steps of analysis slab is 1. Determine the factored negative (Mu–) and positive moment (Mu+) demands at the critical sections in a slab-beam member from the analysis of an equivalent frame. The values of Mu– are calculated at the faces of the columns. The values of Mu+ are calculated at the spans. The following sketch shows a typical moment diagram in a level of an equivalent frame due to gravity loads. ANLYSIS OF FLAT SLAB 2. Distribute Mu– to the CS and the MS. These components are represented as Mu,–CS and Mu,– MS, respectively. Distribute Mu+ to the CS and the MS. These components are represented as Mu, +CS and Mu, +MS, respectively. ANLYSIS OF FLAT SLAB 3.If there is a beam in the column line in the spanning direction, distribute Mu, + CS between the beam and rest of the CS. 4) Add the moments Mu,–MS and Mu, +MS for the two portions of the MS frames). 5) Calculate the design moments per unit width of the CS and MS. each of Mu,–CS and (from adjacent equivalent Code provision for flat slab 1.Thickness of flat slab As per IS-456 : 2000 Code provision for flat slab 2. For drop 3. For column head DESIGN OF FLAT SLAB Direct design method Limitations Slab system designed by the direct design method shall fulfill the following condition. a. There shall be minimum of three continuous spans in each direction. b. The panels shall be rectangular, and the ratio of the longer span to the shorter span within a panel shall not be greater than 2.0. c. It shall be permissible to offset column to a maximum of 10 percent of span in the direction of offset not with standing the provision in (b). Direct design method d) The successive span length in each direction shall not differ by more than one-third of the longer span. The end spans may be shorter but not longer than the interior span , and e) The design lived load shall not exceed three times the design dead load. Design steps for flat slab 1. 2. 3. 4. 5. 6. 7. 8. Check preliminary dimension Check for applicability of DDm Divide the slab with frame in X and Y directions and obtain dimension of X and Y frames. Analysis the interior and exterior panel. a. Longitudinal distribution b. Transverse distribution Estimate the design moment in the external column Estimate the design moment in the internal column Design for shear Detailing should be done as per code requirement. Design for shear Punching shear Punching shear reinforcement CONCLUSIONS As per Indian code we are using cube strength but in international standards cylindered are used which gives higher strength than cube. Drops are important criteria in increasing the shear strength of the slab. Enhance resistance to punching failure at the junct ion of concrete slab & column. By incorporating heads in slab, we are increasing rigidity of slab. In the interior span, the total design moments (Mo). The negative moment’s section shall be designed to resist the larger of the two interior negative design moments for the span framing into common supports. CONCLUSIONS According to Indian standard (IS 456) for RCC code has recommended characteristic strength of concrete as 20, 25, and 30 and above 30 for high strength concrete. For design purpose strength of concrete is taken as 2/3 of actual strength this is to compensate the difference between cube strength and actual strength of concrete in structure. After that we apply factor of safety of 1.5. So in practice Indian standard actually us es 46% of total concrete characteristic strength. While in International practice is to take 85% of total strength achieved by test and then apply factor of safety which is same as Indian standard so in actual they use 57% of total strength. Pre fabricated sections to be integrated into the design for ease of construction. References Indian standards 456,875. S.P 16. Advanced Reinforced Concrete Design-P.C Varghese. A.K. Jain - Limit state design of Reinforced concrete. Reinforced concrete design - S.unnikrishna Pillai, Devdas Menon S.Ramamrutham & R. Narayan - Design of Reinforced concrete Structures. V.N, Vazirani & S.P Chandola – Hand book of civil Engineering. Introduction Common practice of design and construction is to support the slabs by beams and support the beams by columns. This may be called as beam-slab construction. The beams reduce the available net clear ceiling height. Hence in warehouses, offices and public halls some times beams are avoided and slabs are directly supported by columns. This types of construction is aesthetically appealing also. These slabs which are directly supported by columns are called Flat Slabs. Typical Flat slab (without drop & column head) The column head is some times widened so as to reduce the punching shear in the slab. The widened portions are called column heads. The column heads may be provided with any angle from the consideration of architecture but for the design, concrete in the portion at 45º on either side of vertical only is considered as effective for the design Slab without drop & column with column head Moments in the slabs are more near the column. Hence the slab is thickened near the columns by providing the drops Sometimes the drops are called as capital of the column. Slab with drop & column without column head Types of flat slabs Slabs without drop and column head Slabs without drop and column with column head Slabs with drop and column without column head Slabs with drop and column head Slab with drop & column with column head The portion of flat slab that is bound on each of its four sides by centre lines of adjacent columns is called a panel. A panel may be divided into column strips and middle strips. Column Strip means a design strip having a width of 0.25L1 or 0.25L2, whichever is less. The remaining middle portion which is bound by the column strips is called middle strip. Panels, column strip & middle strip in y-direction Proportioning of Flat slab Drops The drops when provided shall be rectangular in plan, and have a length in each direction not less than one third of the panel in that direction. For exterior panels, the width of drops at right angles to the non continuous edge and measured from the centreline of the columns shall be equal to one half of the width of drop for interior panels. Column Heads Where column heads are provided, that portion of the column head which lies within the largest right circular cone or pyramid entirely within the outlines of the column and the column head, shall be considered for design purpose Thickness of Flat Slab From the consideration of deflection control IS 456-2000 specifies minimum thickness in terms of span to effective depth ratio. For this purpose larger span is to be considered. If drop is provided, then the maximum value of ratio of larger span to thickness shall be 40, if mild steel is used 32, if Fe 415 or Fe 500 steel is used If drops are not provided or size of drops do not satisfy the specification, then the ratio shall not exceed 0.9 times the value specified above i.e., 40 X 0.9 = 36, if mild steel is used. 32 X 0.9 = 28.8, if HYSD bars are used It is also specified that in no case, the thickness of flat slab shall be less than 125 mm. Determination of BM & SF For this IS 456-2000 permits use of any one of the following two methods: The Direct Design Method The Equivalent Frame Method Direct Design Method This method has the limitation that it can be used only if the following conditions are fulfilled: There shall be minimum of three continuous spans in each directions. The panels shall be rectangular and the ratio of the longer span to the shorter span within a panel shall not be greater than 2. The successive span length in each direction shall not differ by more than one-third of longer span. The design live load shall not exceed three times the design dead load. The end span must be shorter but not greater than the interior span. It shall be permissible to offset columns a maximum of 10 percent of the span in the direction of the offset not withstanding the provision in (b). Total Design moment The absolute sum of the positive and negative moment in each direction is given by M0 = Total moment W = Design load on the area L2 X Ln Ln = Clear span extending from face to face of columns, capitals, brackets or walls but not less than 0.65 L1 L1 = Length of span in the direction of M0; and L2 = Length of span transverse to L1 In taking the values of Ln, L1 and L2, the following clauses are to be carefully noted: Circular supports shall be treated as square supports having the same area i.e., squares of size 0.886D. When the transverse span of the panel on either side of the centre line of support varies, L2 shall be taken as the average of the transverse spans. When the span adjacent and parallel to an edge is being considered, the distance from the edge to the centre-line of the panel shall be substituted for L2. Distribution of BM in to +ve & -ve moments The total design moment M0 in a panel is to be distributed into –ve moment and +ve moment as specified below: In an interior span: Negative Design Moment 0.65 M0 Positive Design Moment 0.35 M0 In an end span Interior negative design moment Positive design moment Exterior negative design moment where I is the ratio of flexural stiffness at the exterior columns to the flexural stiffness of the slab at a joint taken in the direction moments are being determined and is given by Kc = Sum of the flexural stiffness of the columns meeting at the joint; and Ks = Flexural stiffness of the slab, expressed as moment per unit rotation Distribution of Moments Across the Panel Width in a Column Strip Moments in Columns In this type of constructions column moments are to be modified as suggested in IS 456–2000 [Clause No. 31.4.5]. Shear Force The critical section for shear shall be at a distance d/2 from the periphery of the column/capital drop panel. Hence if drops are provided there are two critical sections near columns. The shape of the critical section in plan is similar to the support immediately below the slab as shown in Fig. For columns sections with re-entrant angles, the critical section shall be taken as indicated in Fig In case of columns near the free edge of a slab, the critical section shall be taken as shown in Fig. The nominal shear stress may be calculated as V – is shear force due to design bo – is the periphery of the critical section d – is the effective depth The permissible shear stress in concrete may be calculated as ksτc, where ks = 0.5 + but not greater than 1, where is the ratio of short side to long side of the column/capital; and If shear stress – no shear reinforcement are required. If , shear reinforcement shall be provided. If shear stress exceeds 1.5 flat slab shall be redesigned. 2. Types of flat slab • Flat Slab resting directly on columns • Flat slab with column head • Flat Slab with drop panels • Flat slab with drop panel and column head Drop is a local thickening of the slab in the region of column Structural Advantages • increase shear strength of slab • increase negative moment capacity of slab • stiffen the slab and hence reduce deflection Column head is a local enlargement of the column at the junction with the slab Structural Advantages • increase shear strength of slab (punching shear) • reduce the moment in the slab by reducing the clear or effective span A flat slab may have recesses formed on the soffit so that the soffit comprises a series of ribs in two directions ( waffle Slabs). Flat slabs with capitals, drop panels, or both. These slabs are very satisfactory for heavy loads and long spans. Although the formwork is more expensive than for flat plates, flat slabs will require less concrete and reinforcing than would be required for flat plates with the same loads and spans. They are particularly economical for warehouses, parking and industrial buildings, and similar structures, where exposed drop panels or capitals are acceptable. 3. Benefits of flat slab Flexibility in room layout • • • Introduce partition walls anywhere required Change the size of room layout Omit false ceiling Saving in building height • Lower storey height will reduce building weight • approx. saves 10% in vertical members • reduce foundation load Shorter construction time • flat plate design will facilitate the use of big table formwork to increase productivity Ease of installation of M&E services • all M & E services can be mounted directly on the underside of the slab instead of bending them to avoid the beams • avoids hacking through beams The main disadvantage is their lack of resistance to lateral loads due to wind and earthquakes. Lateral load resisting systems such as shear walls are oDen necessary When the loads or spans or both become quite large, the slab thickness and column sizes required for flat plates or flat slabs are of such magnitude that it is more economical to use two-‐way slabs with beams, despite the higher formwork costs. 4. Behaviour of Slab supported on Stiff , Flexible and no beams Case Study: • Panel Size = 4 m x 4m • Slab Thickness = 125 mm • Load = 5 kN/m2 • Stiff Supports ( Bearing wall) • Flexible Supports (Beam) : 300 x 300 , 300 x 450 , 300 x 600 , 300 x 1000 mm • Column supports at corners A. Two way Slab on Rigid Supports (bearing Walls) Mx = 3.616 kNm/m My = 3.616 kNm/m IS 456 Values (Table 27): 0.062 x 5 x 16 = 4.96 Slab Deflection = 1.4 mm B. Two way Slab on Flexible Supports (Beams on all sides) 1. Beam Size : 300 x300 mm Mx = 4.45 kNm/m My = 4.45 kNm/m IS 456 Values (Type 9): 0.056 x 5 x 16 = 4.48 Beam Moment = 12.2 kNm Beam Deflection = 1.33 mm Slab deflection= 2.9 mm Mxy = 0.37 kNm/m 2. Beam Size : 300 x450 mm Mx = 3 kNm/m My = 3 kNm/m IS 456 Values (Type 9): 0.056 x 5 x 16 = 4.48 Beam Moment = 15.6 kNm Beam Deflection = 0.5 mm Mxy = 0.73 kNm/m Slab deflection= 1.5 mm 3. Beam Size : 300 x 600 mm Mx = 2.43 kNm/m My = 2.43 kNm/m Mxy = 0.8 kNm/m IS 456 Values (Type 9): 0.056 x 5 x 16 = 4.48 Beam Moment = 17 kNm Beam Deflection = 0.24 mm Slab Deflection = 0.98 mm 4. Beam Size : 300 x 1000 mm Mx = 2 kNm/m My = 2 kNm/m IS 456 Values (Type 9): 0.056 x 5 x 16 = 4.48 Beam Moment = 18 kNm Mxy = 0.8 kNm/m 5. Beam Size : 300 x 125 mm (Concealed Beams) Mx = 9.8 kNm/m My = 9.8 kNm/m IS 456 Values (Type 9): 0.056 x 5 x 16 = 4.48 Beam Moment = 2.9 kNm Slab Deflection = 7.0 mm Mxy = 3 kNm/m B. Two way Slab on Point Supports at corners (Flat Slab) Mx = 9.075 kNm/m (Middle) =12.4 kNm/m (Edge Strip) My = 9.075 kNm/m (Middle) =12.4 kNm/m (Edge Strip) Slab Deflection = 8.67 mm Mxy = 7.76 kNm/m Results Summary Type of Support Rigid 300 x125 Mx My Mxy Beam Moment Deflection Slab Beam 3.616 3.616 2.6 -‐ 1.4 -‐ (Concealed Beams) 9.84 9.85 3.0 2.88 7.0 4.3 300 x300 4.45 4.45 0.37 12.2 2.9 1.33 300 x450 3 3 0.73 15.6 1.5 0.50 300 x600 2.43 2.43 0.8 17.0 0.98 0.24 300x1000 2 2 0.8 18.0 0.60 0.05 Flat Slab 9.0 9.0 7.76 -‐ 8.676 -‐ Observations • Two way Rectangular Slab supported on stiff beams, the shorter spans (stiffer portion of the slab) carry larger load and subjected to larger moments. The longer spans carry less load and subjected to less moment. • Results indicate that decrease in supporting beams stiffness leads to an increase in bending moments of slabs and decrease in bending moment of the beams (behavior that is not captured using code recommendations). • If the slab is supported on bearing walls, slab moments are distributed in similar way. • If the slab is supported only by the columns, the slab behaves like a two way slab with an essential difference that all the load is carried in both directions to accumulate it at the columns. • With Concealed beams it is reveled that the behaviour is close to Flat slabs rather than any useful beam action. 4. Structural Behaviour of Flat Slab Column Strip Column Strip Middle Strip Column Strip Middle Strip Deflected Shape 5. Distribution of Total Panel Moment in different zones -‐m8 A -‐m4 -‐m2 -‐m4 B m3 m7 C -‐m8 -‐m6 m1 -‐m8 Column Strip m3 -‐m4 Column Strip m7 m5 -‐m2 D A A -‐m6 Middle Strip Middle Strip C B A -‐m4 Column Strip -‐m8 Column Strip A Zone of –ve BM (Hogging) in both directions B Zone of +ve BM(Sagging) and –ve BM C Zone of -‐veBM and +ve BM D Zone of +ve BM in both directions m3 A -‐m8 Column Strip -‐m2 -‐m4 C B A -‐m6 Middle Strip -‐m8 Column Strip -‐m2 m1 C -‐m4 m3 A -‐m4 A m7 Middle Strip A D B A -‐m8 -‐m2 D C C -‐m2 -‐m4 B m7 m5 Column Strip -‐m8 m1 Column Strip m5 C -‐m4 B m7 A B -‐m6 -‐m4 m3 D A -‐m8 -‐m6 -‐m6 -‐m8 A Zone of –ve BM (Hogging) in both directions B Zone of +ve BM(Sagging) and –ve BM C Zone of -‐veBM and +ve BM D Zone of +ve BM in both directions Moment Direction 6. Definitions Moment Direction COLUMN STRIP 0.25L1 0.25L2 L2 SPAN Region MIDDLE STRIP SPAN Region: Bounded on all the four sides by middle strips COLUMN STRIP 0.25L1 0.25L2 COLUMN STRIP 0.25L2 0.25L1 MIDDLE STRIP L1 7. General Design Considerations CL 31.2 Proportioning 31.2.1 Thickness of Flat Slab • The thickness of the flat slab shall be generally controlled by considerations of span to effective depth ratios given in 23.2. • For slabs with drops conforming to 31.2.2, span to effective depth ratios given in 23.2 shall be applied directly; otherwise the span to effective depth ratios obtained in accordance with provisions in 23.2 shall be multiplied by 0.9. For this purpose, the longer span shall be considered. • The minimum thickness of slab shall be 125 mm. 31.2.2 Drop • The drops when provided shall be rectangular in plan, and have a length in each direction not less than onethird of the panel length in that direction. • For exterior panels, the width of drops at right angles to the non continuous edge and measured from the centreline of the columns shall be equal to one-half the width of drop for interior panels. • Minimum thickness of Drop > ¼ of Slab thickness and > 100 mm 31.2.3 Column Heads Where column heads are provided, that portion of a column head which lies within the largest right circular cone or pyramid that has a vertex angle of 900and can be included entirely within the outlines of the column and the column head, shall be considered for design purposes. 8. Determination of Bending Moment CL 31.3 31.3.1. Methods of Analysis and Design It shall be permissible to design the slab system by one of the following methods: a) The direct design method as specified in 31.4, and b) The equivalent frame method as specified in 31.5. In each case the applicable limitations given in 31.4 and 31.5 shall be met. 9. Direct Design Method CL 31.4 A. Limitations : 31.4.1 Slab system designed by the direct design method shall fulfil the following conditions: a) There shall be minimum of three continuous spans in each direction, b) The panels shall be rectangular, and the ratio of the longer span to the shorter span within a panel shall not be greater than 2.0 c) It shall be permissible to offset columns to a maximum of 10percent of the span in the direction of the offset notwithstanding the provision in (b) d) The successive span lengths in each direction shall not differ by more than one-third of the longer span. The end spans may be shorter but not longer than the interior spans, and e) The design live load shall not exceed three times the design dead load. Note: Applicable to gravity loading condition alone (and not to the lateral loading condition) Ly3 Ly2 3 For any Panel Longer Span/Shorter Span 2 0.1Lx1 Lx1 Lx2 Lx3 Lx2 Ly1 Ly2 Ly3 Ly2 2 0.1Ly2 Lx1 2Lx2/3 Lx3 2Lx2/3 Ly1 1 Lx1 2 Lx2 3 Lx3 Ly1 2Ly2/3 Ly3 2Ly2/3 wuL/wuD 3 B. Total Design Moment for a Span: CL31.4.2 31.4.2.1 In the direct design method, the total design moment for a span shall be determined for a strip bounded laterally by the centre-line of the panel on each side of the centre-line of the supports. 1 1 CL of Panel 1 DESIGN STRIP M0x M0y CL of Panel 2 2 31.4.2.2 The absolute sum of the positive and average negative bending moments in each direction shall be taken as: lnx 2 wu kN/m Ln Note: 1. It is the same as the total moment that occurs in a simply supported slab Ln L2 (L1) L1 (L2) 2. The moment that actually occurs in such a slab has been shown by experience and tests to be somewhat less than the value determined by the Mo expression. For this reason, l1 is replaced with ln 10. Distribution of Total Panel MomentM0 • It is next necessary to know what proportions of these total moments are positive and what proportions are negative. Interior Panel • If a slab was completely fixed at the end of each panel, the division would be as it is in a fixed-‐end beam, two-‐thirds negative and one-‐third positive, as shown in Figure. • This division is reasonably accurate for interior panels where the slab is continuous for several spans in each direction with equal span lengths and loads. Exterior Panel • The relative stiffnesses of the columns and slabs of exterior panels are of far greater significance in their effect on the moments than is the case for interior panels. • The magnitudes of the moments are very sensitive to the amount of torsional restraint supplied at the discontinuous edges. • This restraint is provided both by the flexural stiffness of the slab and by the flexural stiffness of the exterior column. Code Recommendations Distribution of Bending Moments across panel width Code Recommendations 11. Rebar Detailing - Code Recommendations Bent bars are also used. There seems to be a trend among designers to use straight bars more than bent bars. ELEVATION Rebar Detailing - Code Recommendations e b e e b b Ln greater of adjacent clear spans CL 31.7.3 (b) e e b b Section through Middle Strip 12. Two way Shear in Flat Slab • Flat plates present a possible problem in transferring the shear at the perimeter of the columns. • There is a danger that the columns may punch through the slabs. • As a result, it is frequently necessary to increase column sizes or slab thicknesses or to use shear heads. Shear heads consist of steel I or channel shapes placed in the slab over the columns Note: Flat Slab with drop panel and capital, shear is required to be checked at two sections 1. at a distance d/2 from the face of column capital 2. at a distance d/2 from the face of drop panel Design Example #1 Design by DDM flat plate supported on columns 450 mm square, for a Live Load = 3 kN/m2, Floor Finish = 1 kN/m2 use M20 and Fe415. Assume clear cover = 20 mm. Effective Column Height = 3.35m. Bay spacing in X and Y direction = 5m c/c • Interior Panel P5 • Corner Panel P7 3 bays @ 5 m c/c A. Interior Panel Design Zone A – Corner Strip Zone B – Middle Strip along X Zone C – Middle Strip along Y A 2.5 B m Zone D – Interior Region A Step 1: Panel Division into Strips C 2.5m A D B 5m 31.1.1(a) 5m C Moment direction Along L1 L2 X 5 5 1.25 and 1.25 m Adopt 1.25 m 2.5m Y 5 5 1.25 and 1.25 m Adopt 1.25 m 2.5m A Width of Column Strip on either side of Centre Line = 0.25L2 and 0.25 L1 Middle Strip Step 2: Trial Depth CL 31.2.1 • • • • • L/d = 26 Modification Factor = 1.33, Assuming pt = 0.4%, FIG 4 IS 456 d = 5000/(26 x 1.33) = 145 mm > 125 CL 31.2.1 DS= 145 + 20 + 18 = 183 mm ( assume #12 bars, and bars in two layers) Provide Ds= 200 mm d = 200-‐20-‐18= 162 mm Step 3 Design Loads / m width of Slab • wuD = 1.5(25x 0.2 + 1) = 9kN/m • wuL = 1.5 x 3 = 4.5kN/m • wu = 13.5 kN/m Step 4: Check for Applicability of DDM: CL 31.4.1 • • • • No. of Continuous Spans in each direction = 3 ; OK Long Span/Short Span = 5/5 = 1 <2 ; OK Successive spans in each direction = Equal; OK wuL/wuD = 4.5/9 = 0.5 < 3 ; OK 31.4.1(a) 31.4.1(b) 31.4.1(d) 31.4.1(e) Contributory Area Step 5: Check for punching shear around Column Assumed d = 162 mm Section 1: 5m • Critical Section at d/2 around the column • Perimeter of Critical Section = 4 x 0.612= 2.448 m • Design Shear at critical section Vu • Vu = 13.5 ( 52 – 0.6122) = 333kN • c = 0.25fck = 1.12 MPa • ks = 0.5 +1 = 1.5 <=1 ; ks=1 ; ks c = 1.12 • Shear Resistance of Concrete = 1.12 x 2448 x 162 = 444kN > 333 kN Critical Section 0.612m 0.612m 5m OK Step 6:Design Moments CL 31.4.2.2 wu = 13.5 kN /m Parameters L1 (Span in direction of Mo) 0.65L1 Ln (clear span extending from face to face of columns, capitals) Ln > 0.65L1 L2 (Span transverse to L1) W = wu L2Ln M0 = W Ln / 8 Along X Along Y 5 3.25 5 3.25 m m 4.55 4.55 m 4.55 5 307.2 174.72 4.55 5 307.2 174.72 (5-‐0.45) = m m kN kNm Step 7 : Distribution of Bending Moment across panel width ; CL: 31.4.3.2, 31.5.5 X Y 113.6 113.6 kNm 31.4.3.2 85.2 85.2 kNm 31.5.5.1 2x1.25 =2.5 2x1.25 =2.5 • -‐m1 = M1/ Csw (Zone A) 34.1 34.1 kNm/m • Middle Strip M2 = 0.25MN 28.4 28.4 kNm Moment Direction along Negative Design Moment MN = -‐0.65*M0 • Column Strip M1 = 0.75MN Width of Column Strip resisting M1 (Csw) m 31.5.5.4(a) Positive Design Moment MP = 0.35*M0 61.2 61.2 kNm 31.4.3.2 • Column Strip M1 = 0.6MP • +m1 = M1/ Csw 36.7 14.7 36.7 14.7 kNm 31.5.5.3 • Mid Span M2 = 0.4MP • +m2 = M2/Msw (Zone D) 24.5 9.8 24.5 9.8 kNm (Zone B &C) -‐34.1 -‐34.1 A 14.7 14.7 C 9.8 -‐11.4 -‐34.1 -‐34.1 A -‐11.4 A B -‐34.1 D C -‐11.4 -‐34.1 B 31.5.5.4(a) kNm/m -‐vesign : Hogging Moment (tension at top) +ve sign : Sagging Moment (tension at bottom) Step 8 : Check for adequacy of Depth 14.7 9.8 -‐11.4 14.7 -‐34.1 kNm/m A -‐34.1 • Max Design Bending moment = 34.1 kNm/m • Mu,lim = 72.41 kNm/m > 34.1, • Depth is adequate G-‐1.1(c) Step 9 :Rebar Details 26.5.2.1 • Ast,min = 0.12 x 200 x 1000 /100 = 240 mm2/m • Minimum Effective Depth of Slab = 162 mm G-‐1.1(b) • 7.5 Ast2 – 58490Ast + Mu =0 Location Moment Ast (kNm/m) (mm2/m) (-‐)34.1 14.7 (-‐)11.4 9.8 635 260 200 171 (-‐)34.1 (-‐)11.4 14.7 9.8 635 200 260 171 Bar dia Spacing 635 260 240 240 10 8 8 8 120 -‐T 190 -‐B 200 -‐T 200 -‐B 635 240 260 240 10 8 8 8 120 -‐T 200 -‐T 190 -‐B 200 -‐B Ast (prov) mm Along X Zone A Zone B Zone C Zone D Along Y Zone A Zone B Zone C Zone D #8@190 A A B 0.125Ln #8@190 #8@200 #8@190 #8@190 C #8@200 0.15Ln A Bottom Rebar Details in Interior Panel D 0.15Ln B C 0.125Ln A #10@120 A B #8@200 0.3Ln 0.2Ln #10@120 A D C C #8@200 0.2Ln 0.3Ln TOP Rebar Details in Interior Panel Note: Distances for curtailment of rebars are measured from column face #8@200 B. Corner Panel Design Step 5: Check for punching shear around Column Assumed d = 162 mm Section 1: • Critical Section at d/2 around the column • Perimeter of Critical Section = 2 x 0.531= 1.062 m • Design Shear at critical section Vu • Vu = 13.5 ( 2.52 – 0.5312) =81kN • c = 0.25fck = 1.12 MPa • ks = 0.5 +1 = 1.5 <=1 ; ks=1 ; ks c = 1.12 • Shear Resistance of Concrete = 1.12 x 1062 x 162 = 192kN > 81 kN OK 162/2 = 81 mm 450 Step 6:Design Moments CL 31.4.2.2 M0 = 174.72 kNm Step 7 : Distribution of Bending Moment across panel width ; CL 31.4.3.3 , 31.5.5 𝛼↓𝑐 =∑↑▒𝑘↓𝑐 /𝑘↓𝑠 A C 1.25m Assume Columns and Slab panels are with same modulus of elasticity A B 1.25m D B 5m A 5m C A Parameters Sum of c o l u m n stiffness above and below the slab Along X Along Y (2 x 4 x Ec x 450 x 4503/12) /3350 = 8.16 Ec x 106 2 (4EcIc)/Lc Slab stiffness ks = 4EsIs/Ls (4 Es x 5000 x 2003/12)/5000 = 2.67Es x 106 2.67Es x 106 c = kc /ks 3.06 3.06 = 1+ (1/c) 1.33 1.33 -‐m1 A. Exterior negative design moment: Exterior -‐m2 -‐m1 Y Exterior -‐m2 X • Column Strip M1 = MN Width of Column Strip Csw resisting M1 -‐m1= M1/Csw • Middle Strip M2=0 -‐m2 = 0 1.25 Interior -‐m1 1.25 Moment Direction along Negative Design Moment MN = -‐0.65*M0/ -‐m1 Interior X Y 85.4 85.4 kNm 31.4.3.3 85.4 85.4 kNm 31.55.2(a) 2x1.25 = 2.5 2.5 34.2 0 0 34.2 0 0 m kNm/m kNm kNm/m 31.5.5.4(a) Exterior B. Interior negative design moment: Y -‐m1 -‐m2 Interior Exterior X -‐m1 -‐m1 Moment Direction along Negative Design Moment MN = -‐(0.75 – 0.1/)Mo • Column Strip M1 = 0.75 MN Width of Column Strip Csw resisting M1 • -‐m1= M1/ Csw • Middle Strip M2 = 0.25 MN Width of Middle Strip Msw resisting M2 • -‐m2 = M2/Msw -‐m2 Interior -‐m1 X Y 118 118 kNm 31.4.3.3 88.5 2x1.25 =2.5 -‐35.4 22.12 2.5 -‐8.85 88.5 2.5 -‐35.4 22.12 2.5 -‐8.85 kNm 31.5.5.1 m kNm/m kNm m kNm/m 31.5.5.4(a) Exterior m1 C. Positive Moment in Mid Span: m Exteri 1 m2 Y m2 o m1 Interior X m1 r m1 Interior Moment Direction along Design Moment MP = (0.63 – 0.28/)Mo • Column Strip M1 = 0.6 MP Width of Column Strip Csw resisting M1 • m1 = M1/ Csw • Middle Strip M2 = 0.4 MP Width of Middle Strip Msw resisting M2 • m2 = M2/Msw X Y 73.29 73.29 kNm 31.4.3.3 43.98 2x1.25 =2.5 17.6 29.32 2.5 11.73 43.98 2.5 17.6 29.32 2.5 11.73 kNm 31.5.5.3 m kNm/m kNm m kNm/m 31.5.5.4(a) Exterior -‐34.2 -‐34.2 A -‐34.2 -‐0 17.6 A B -‐35.4 -‐vesign : Hogging Moment (tension at top) +ve sign : Sagging Moment (tension at bottom) Exterior 0 17.6 C 11.73 17.6 11.73 D C -‐8.85 Interior -‐35.4 -‐34.2 A -‐35.4 -‐8.85 17.6 B A -‐35.4 Interior Step 7 : Check for adequacy of Depth • Max Design Bending moment = 35.4 kNm/m • Mu,lim = 72.41 kNm/m > 35.4, Depth is adequate G-‐1.1(c) Step 8 :Rebar Details 26.5.2.1 • Ast,min = 0.12 x 200 x 1000 /100 = 240 mm2/m 7.5 Ast2 – 58490Ast + Mu =0 Strip Location Moment Ast (kNm/m) (mm2/m) (-‐)34.2 (-‐)35.4 17.6 (-‐)8.85 11.73 637 662 314 155 206 (-‐)34.2 (-‐)35.4 (-‐)8.85 17.6 11.73 637 662 155 314 206 Bar dia Spacing 637 662 314 240 240 10 120(T) 115(T) 160(B) 200(T) 200(B) 637 662 240 314 240 10 Ast (prov) mm Along X Zone A(Exterior) Zone A(Interior) Zone B Zone C(Interior) Zone D 10 8 8 8 Along Y Zone A (Exterior) Zone A(Interior) Zone B (Interior) Zone C Zone D 10 8 8 8 120(T) 115(T) 200(T) 160(B) 200(B) Exterior A 17.6 17.6 Exterior C A A B 11.73 11.73 D 17.6 C Interior 17.6 B Interior A Exterior -‐34.2 #8@200 #10@120 #10@115 #10@120 #8@200 #10@120 #8@200 -‐34.2 Exterior 0 A C -‐34.2 #10@115 #8@200 A B D -‐35.4 C -‐8.85 Interior -‐35.4 #10@115 -‐34.2 -‐0 A -‐35.4 -‐8.85 B A -‐35.4 Interior TOP Rebar details in Corner Panel Design Example #2 Design by DDM flat plate supported on columns 500 mm square, for a Live Load = 4 kN/m2, Floor Finish = 1 kN/m2 use M25 and Fe415. Floor slab is exposed to moderate environment. Column Height = 3.5m (c/c). Bay spacing in X and Y direction = 5.5m c/c. Assume that building is not restrained against sway • Interior Panel P5 • Corner Panel P7 3 bays @ 5.5 m c/c A. Interior Panel Design Zone A – Corner Strip Zone B – Middle Strip along X Zone C – Middle Strip along Y A 2.75 B m Zone D – Interior Region A Step 1: Panel Division into Strips C 2.75m A D B 5.5 m 5.5 m C 31.1.1(a) Moment direction Along L1 L2 X 5 5 1.375 and 1.375 m Adopt 1.375 m 2.75m Y 5 5 1.375 and 1.375 m Adopt 1.375 m 2.75m Width of Column Strip on either side of Centre Line = 0.25L2 and 0.25 L1 Middle Strip A Step 2: Trial Depth CL 31.2.1 • • • • • L/d = 26 Modification Factor = 1.33, Assuming pt = 0.4%, FIG 4 IS 456 d = 5500/(26 x 1.33) = 160 mm > 125 CL 31.2.1 DS= 160 + 30 + 18 = 208 mm ( assume #12 bars, and bars in two layers) Provide Ds= 225 mm d = 225-‐30-‐18= 177 mm Step 3 Design Loads / m width of Slab • wuD = 1.5(25x 0.225 + 1) = 9.94kN/m • wuL = 1.5 x 4 = 6kN/m • wu = 15.94 16 kN/m Step 4: Check for Applicability of DDM: CL 31.4.1 • • • • No. of Continuous Spans in each direction = 3 ; OK Long Span/Short Span = 5.5/5.5 = 1 <2 ; OK Successive spans in each direction = Equal; OK wuL/wuD = 6/9.94 = 0.6 < 3 ; OK 31.4.1(a) 31.4.1(b) 31.4.1(d) 31.4.1(e) Contributory Area Step 5: Check for punching shear around Column Assumed d = 177 mm Section 1: 5.5m • Critical Section at d/2 around the column • Perimeter of Critical Section = 4 x 0.677= 2.708 m • Vu = 16 ( 5.52 – 0.6772) =477kN • c = 0.25fck = 1.25 MPa • ks = 0.5 +1 = 1.5 <=1 ; ks=1 ; ks c = 1.25 • Shear Resistance of Concrete = 1.25 x 2708 x 177 = 599kN > 477 kN Critical Section 0.677m 0.677m 5.5m OK Step 6:Design Moments CL 31.4.2.2 wu = 16 kN /m Parameters L1 (Span in direction of Mo) 0.65L1 Ln (clear span extending from face to face of columns, capitals) Ln > 0.65L1 L2 (Span transverse to L1) W = wu L2Ln M0 = W Ln / 8 Along X 5.5 3.575 (5.5-‐0.5) = Along Y 5.5 m 3.575 m 5 5 5 5.5 440 275 5 5.5 440 275 m m m kN kNm Step 7 : Distribution of Bending Moment across panel width ; CL: 31.4.3.2, 31.5.5 X Y Moment Direction along Negative Design Moment 179 179 MN = -‐0.65*M0 134.3 134.3 • Column Strip M1 = 0.75MN kNm 31.4.3.2 kNm 31.5.5.1 2.75 2.75 m • -‐m1 = M1/ Csw (Zone A) 48.8 48.8 kNm/m • Middle Strip M2 = 0.25MN 44.8 44.8 kNm Width of Middle Strip resisting M2 (Msw) 2.75 2.75 m 16.3 16.3 kNm/m Width of Column Strip resisting M1 (Csw) • -‐m2 = M2/Msw (Zone B & C) 31.5.5.4(a) Positive Design Moment MP = 0.35*M0 96.3 96.3 kNm 31.4.3.2 • Column Strip M1 = 0.6MP • +m1 = M1/ Csw 57.8 57.8 kNm 31.5.5.3 21 21 • Mid Span M2 = 0.4MP 38.5 14 38.5 14 (Zone B &C) • +m2 = M2/Msw (Zone D) -‐48.8 -‐48.8 A 21 21 C 14 -‐16.3 -‐48.8 -‐48.8 A -‐16.3 -‐48.8 C B 31.5.5.4(a) kNm/m -‐vesign : Hogging Moment (tension at top) +ve sign : Sagging Moment (tension at bottom) Step 8 : Check for adequacy of Depth -‐16.3 -‐48.8 -‐16.3 21 A 21 D kNm -‐48.8 B 14 kNm/m A -‐48.8 • Max Design Bending moment = 48.8 kNm/m • Mu,lim = 108 kNm/m > 48.8 • Depth is adequate G-‐1.1(c) Step 9 :Rebar Details 26.5.2.1 • Ast,min = 0.12 x 225 x 1000 /100 = 270 mm2/m • Minimum Effective Depth of Slab = 177 mm G-‐1.1(b) • 6 Ast2 – 63906Ast + Mu = 0 Location Moment Ast (kNm/m) (mm2/m) (-‐)48.8 21 (-‐)16.3 14 828 340 262 224 (-‐)48.8 -‐16.3 21 14 828 262 340 224 Bar dia Spacing 828 340 270 270 10 8 8 8 90 -‐T 145 -‐B 180 -‐T 180 -‐B 828 270 340 270 10 8 8 8 90 -‐T 180 -‐T 145 -‐B 180 -‐B Ast (prov) mm Along X Zone A Zone B Zone C Zone D Along Y Zone A Zone B Zone C Zone D #8@145 A A B 0.125Ln #8@145 #8@180 #8@145 #8@145 C #8@180 0.15Ln A Bottom Rebar Details in Interior Panel D 0.15Ln B C 0.125Ln A #10@90 A B #8@180 0.3Ln 0.2Ln #10@90 A D C C #8@180 0.2Ln 0.3Ln TOP Rebar Details in Interior Panel Note: Distances for curtailment of rebars are measured from column face #8@200 B. Corner Panel Design Step 5: Check for punching shear around Column Assumed d = 177 mm Section 1: • Critical Section at d/2 around the column • Perimeter of Critical Section = 2 x 0.5885= 1.177 m • Vu = 16 ( 2.752 – 0.58852) =115.5kN • c = 0.25fck = 1.25 MPa • ks = 0.5 +1 = 1.5 <=1 ; ks=1 ; ks c = 1.25 • Shear Resistance of Concrete = 1.25 x 1177 x 177 = 260kN > 115.5 kN OK 177/2 = 88.5 mm 500 2.75m 2.75m Step 6:Design Moments CL 31.4.2.2 M0 = 275 kNm Step 7 : Distribution of Bending Moment across panel width ; CL 31.4.3.3 , 31.5.5 𝛼↓𝑐 =∑↑▒𝑘↓𝑐 /𝑘↓𝑠 A C 1.25m Assume Columns and Slab panels are with same modulus of elasticity A B 1.25m D B 5m A 5m C A Parameters Sum of c o l u m n stiffness above and below the slab Along X Along Y Leff = 1.2 Lc (CL E1) Lc = 3.5-‐0.225 = 3.275 (2 x 4 x Ec x 500 x 5003/12) /1.2*3275 = 10.6 Ec x 106 2 (4EcIc)/Lc Slab stiffness (4 Es x 5500 x 2253/12)/5500 ks = 4EsIs/Ls = 2.67Es x 106 c = kc /ks c min (Table 17) = 1+ (1/c) 2.8 3.8Es x 106 2.8 (0.7/0.5)*0.1 =0.14 < c. Adopt c = 2.8 1.36 1.36 -‐m1 A. Exterior negative design moment: Exterior -‐m2 -‐m1 Y X Interior -‐m1 Interior 1.25 • Column Strip M1 = MN Width of Column Strip Csw resisting M1 -‐m1= M1/Csw • Middle Strip M2=0 -‐m2 = 0 1.25 Exterior -‐m2 M0 = 275 kNm Moment Direction along Negative Design Moment MN = -‐0.65*M0/ -‐m1 X Y 131.4 131.4 kNm 31.4.3.3 131.4 131.4 kNm 31.55.2(a) 2.75 2.75 m 47.8 0 0 47.8 0 0 kNm/m kNm kNm/m 31.5.5.4(a) Exterior B. Interior negative design moment: Y -‐m1 -‐m2 Interior Exterior X -‐m1 -‐m1 Moment Direction along Negative Design Moment MN = -‐(0.75 – 0.1/)Mo • Column Strip M1 = 0.75 MN Width of Column Strip Csw resisting M1 • -‐m1= M1/ Csw • Middle Strip M2 = 0.25 MN Width of Middle Strip Msw resisting M2 • -‐m2 = M2/Msw -‐m2 Interior -‐m1 X Y 186 186 kNm 31.4.3.3 139.5 139.5 kNm 31.5.5.1 2.75 50.73 46.5 2.75 50.73 46.5 m 2.75 17 2.75 17 m kNm/m kNm kNm/m 31.5.5.4(a) Exterior m1 C. Positive Moment in Mid Span: m Exteri m2 1 Y m2 m1 Interior o X m1 r m1 Interior Moment Direction along Design Moment MP = (0.63 – 0.28/)Mo • Column Strip M1 = 0.6 MP Width of Column Strip Csw resisting M1 • m1 = M1/ Csw • Middle Strip M2 = 0.4 MP Width of Middle Strip Msw resisting M2 • m2 = M2/Msw X Y 116.6 116.6 kNm 31.4.3.3 70 2.75 25.5 46.7 2.75 17 70 2.75 25.5 46.7 2.75 17 kNm 31.5.5.3 m kNm/m kNm m kNm/m 31.5.5.4(a) Exterior -‐47.8 -‐47.8 A -‐47.8 -‐0 25.5 A B -‐50.73 -‐vesign : Hogging Moment (tension at top) +ve sign : Sagging Moment (tension at bottom) Exterior 0 25.5 C 17 25.5 17 D C -‐17 Interior -‐50.73 -‐47.8 A -‐50.73 -‐17 25.5 B A -‐50.73 Interior Step 7 : Check for adequacy of Depth • Max Design Bending moment = 50.73 kNm/m • Mu,lim = 108 kNm/m > 50.73, Depth is adequate G-‐1.1(c) Step 8 :Rebar Details 26.5.2.1 • Ast,min = 0.12 x 225 x 1000 /100 = 270 mm2/m 6 Ast2 – 63906Ast + Mu = 0 Strip Location Moment Ast (kNm/m) (mm2/m) (-‐)47.8 (-‐)50.73 25.5 (-‐)17 17 810 864 415 273 273 (-‐)47.8 (-‐)50.73 (-‐)17 25.5 17 810 864 273 415 273 Bar dia Spacing 810 864 415 273 273 10 10 10 8 8 90(T) 90(T) 180(B) 180(T) 180(B) 810 864 273 415 273 10 10 8 10 8 90(T) 90(T) 180(T) 180(B) 180(B) Ast (prov) mm Along X Zone A(Exterior) Zone A(Interior) Zone B Zone C(Interior) Zone D Along Y Zone A (Exterior) Zone A(Interior) Zone B (Interior) Zone C Zone D Design Example #3 Design by DDM flat plate supported on columns of dia = 450 mm, Column head = 1.5 m dia, Drop panel size = 3.2 x 3.2 m, for a Live Load = 4 kN/m2, Floor Finish = 1 kN/m2 use M20 and Fe415. Assume clear cover = 20 mm. Column Height = 3.35m 6.4m 6.4m • Interior Panel P5 • Exterior Panel P2/P4 • Corner Panel P1 6.4m 7.2m 7.2m 7.2m 1.6 A. Interior Panel Design 1.6 Step 1: Panel Division into Strips 31.1.1(a) MSy 1.6 1.6 CSy Moment direction Along L1 L2 Width of Column Strip on either side of Centre Line = 0.25L2 and 0.25 L1 CSx Middle Strip MSx CSx Lx = 7.2 Zone A – Corner Strip Zone B – Middle Strip along X Zone C – Middle Strip along Y X 7.2 6.4 1.6 < 1.8 m; 1.6 m 4m Y 6.4 7.2 1.8 > 1.6 m; 1.6 m 3.2m Zone D – Interior Region Ly = 6.4 CSy Step 2: Trial Depth CL 31.2.1 • • • • • L/d = 26 Modification Factor = 1.4, Assuming pt 0.4%, FIG 4 IS 456 d = 7200/(26 x 1.4) = 198 mm > 125 DS= 198+20+18= 236 mm ( assume #12 bars) Provide Ds= 240 mm , d = 198mm CL 31.2.1 Step 3: Design Loads / m width of Slab • wuD = 1.5(25 x 0.24 + 1) = 10.5kN • wuL = 1.5 x 4 = 6.0kN • wu = 16.5 kN Step 4: Check for Applicability of DDM: CL 31.4.1 • • • • No. of Continuous Spans in each direction = 3 ; OK Long Span/Short Span = 7.2/6.4 = 1.125 <2 ; OK Successive spans in each direction = Equal; OK wuL/wuD = 6/10.5 = 0.571 < 3 ; OK 31.4.1(a) 31.4.1(b) 31.4.1(d) 31.4.1(e) Step 5: Drop Panel Size : CL 31.2.2 • • • • • Length along X ≥ Lx/3 = 2.4 m Length along Y ≥ Ly/3 = 2.13 m Generally Drop Panel Size is set equal to Width of Column Strip Proposed size 3.2 x 3.2 meets all the requirements. Minimum thickness = ¼ DS = 60 mm or 100 mm; Adopt 100 mm Step 6:Column Head • 1/4 to 1/5 of average span = 7.2/5 = 1.44 m • Provided = 1.5 m ; Ok • Equivalent Square Capital =0.89D = 1.335 m • Minimum Effective Depth of Slab = 198 mm • Effective Depth at Drop location = 298 mm Section 1: • Critical Section at d/2 around the column capital • Perimeter of Critical Section = ( 1.5 + 0.298) = 5.65 m • Weight of Drop Projection below slab = 0.1x 25 x 1.5 = 3.75 kN/m2 • Design Shear at critical section around capital Vu • Vu = 16.5 ( 7.2 x 6.4 -‐ x 1.7982/4) + 3.75(3.2 x 3.2 -‐ x 1.7982/4) • = 747 kN • c = 0.25fck = 1.12 MPa • ks = 0.5 +1 = 1.5 <=1 ; ks=1 ; ks c = 1.12 • Shear Resistance of Concrete = 1.12 x 5650 x 298 = 1885kN > 747 kN Capital 1.5 3.2 m Step 7 : Check for Shear around Column Capital 1.798 Critical Section DROP 3.2 m OK Section 2 : Check for Shear around drop Critical Section at d/2 around the drop d = 198mm Perimeter of Critical Section = 4 x 3.4 = 13.6m Design Shear at critical section Vu = 16.5 ( 7.2 x 6.4 – 3.42) = 569 kN Shear Resistance of Concrete = 1.12 x 13600 x 198 = 3015kN > 569 kN 3.2 m • • • • • • Capital 1.5 DROP 3.2 m 3.2 + 0.198 = 3.4 Critical Section Step 8:Design Moments CL 31.4.2.2 wu = 16.5 kN /m Parameters L1 (Span in direction of Mo) 0.65L1 Ln (clear span extending from face to face of columns, capitals) Ln > 0.65L1 L2 (Span transverse to L1) W = wu L2Ln M0 = W Ln / 8 Along X 7.2 4.68 Along Y 6.4 m 4.16 m (7.2-‐1.335) = (6.4-‐1.335) = m 5.865 5.065 5.865 6.4 619.34 454 5.065 7.2 601.72 381 m m kN kNm Step 9 : Distribution of Bending Moment across panel width ; CL: 31.4.3.2, 31.5.5 X Y 295.1 247.65 kNm 31.4.3.2 221.33 185.74 kNm 31.5.5.1 2x1.6 =3.2 69.17 2x1.6 =3.2 58.04 73.78 61.91 Width of Middle Strip Msw 3.2 4 • -‐m2 = M2/Msw 23.06 15.48 Moment Direction along Negative Design Moment MN = -‐0.65*M0 • Column Strip M1 = 0.75MN Width of Column Strip Csw • -‐m1= M1/ Csw • Middle Strip M2 = 0.25MN m kNm/m kNm kNm/m 31.5.5.4(a) Positive Design Moment MP = 0.35*M0 • Column Strip M1 = 0.6MP • +m1 = M1/ Csw • Middle Strip M2 = 0.4MP • +m2 = M2/Msw -‐58.04 -‐69.17 A 29.79 -‐15.48 158.9 133.35 kNm 31.4.3.2 95.34 29.79 63.56 19.86 80.01 25 53.34 13.34 kNm 31.5.5.3 -‐58.04 A B -‐69.17 kNm/m kNm 31.5.5.4(a) kNm/m -‐vesign : Hogging Moment (tension at top) +ve sign : Sagging Moment (tension at bottom) Step 10 : Check for adequacy of Depth 25 C 19.86 -‐23.06 -‐58.04 -‐69.17 A 25 13.34 D -‐23.06 -‐58.04 -‐15.48 29.79 C B A -‐69.17 • Max Design Bending moment = 69.17 kNm/m • Mu,lim = 126.36 kNm/m > 69.17, G-‐1.1(c) • Depth is adequate Moment Direction FE Results from ETAB MS CS Moment Directio n CS Step 11 :Rebar Details 26.5.2.1 • Ast,min = 0.12 x 240 x 1000 /100 = 288 mm2/m • Minimum Effective Depth of Slab = 198 mm G-‐1.1(b) • 7.5 Ast2 – 71488Ast + Mu =0 Strip Location Moment Ast (kNm/m) (mm2/m) (-‐)69.17 29.79 (-‐)23.06 19.86 1093 437 334 286 (-‐)58.04 (-‐)15.48 25 13.34 896 222 364 190 Bar dia Spacing 1093 437 334 288 10 8 8 8 70 -‐T 110 -‐B 150 -‐T 170 -‐B 896 288 364 288 10 8 8 8 85 -‐T 170-‐T 135 -‐B 170 -‐B Ast (prov) mm Along X Zone A Zone B Zone C Zone D Along Y Zone A Zone B Zone C Zone D #8@110 A A B 0.125Ln #8@170 #8@110 C 0.15Ln #8@170 #8@135 A #8@135 LAP ZONE D C 0.15Ln B 7.2 m 0.125Ln A Bottom Rebar Details in Interior Panel 6.4 m #10@ 70 0.2Ln 0.2Ln #10@85 0.22Ln 0.22Ln #8@150 0.33Ln 0.33Ln A 0.33Ln 0.2Ln 0.33Ln 0.2Ln 0.22Ln 0.22Ln B A #8@170 Top Rebar Details in Interior Panel Note: Distances for curtailment of rebars are measured from column face #8@150 #8@135 #8@340 Section Through Middle Strip -‐CDC #8@170 7.2 m #10@140 #10@85 #10@70 Section Through Column Strip -‐ABA #8@340 #8@170 #8@170 2. Corner Panel Design Step 7 : Check for Shear around Column Capital • Minimum Effective Depth of Slab = 198 mm • Effective Depth at Drop location = 298 mm Section 1: • Critical Section at d/2 around the column capital • Perimeter of Critical Section = ( 1.5 + 0.298)/4 = 1.412 m • Weight of Drop Projection below slab = 0.1x 25 x 1.5 = 3.75 kN/m2 • Design Shear at critical section around capital Vu • Vu = 16.5 ( 3.6x 3.2 – ( x 1.7982/4)/4) + 3.75(1.6 x 1.6 – ( x1.7982/4)/4)) • = 187 kN • c = 0.25fck = 1.12 MPa • ks = 0.5 +1 = 1.5 <=1 ; ks=1 ; ks c = 1.12 • Shear Resistance of Concrete = 1.12 x 1412 x 298 = 471kN > 187 kN OK Section 2 : Check for Shear around drop free edge • • • • • • Critical Section at d/2 around the drop free edge d = 198mm Perimeter of Critical Section = 2 (1.7)=3.4m Design Shear at critical section =1.6 + 0.198/2 = 1.7 m Vu = 16.5 ( 3.6 x 3.2 – 1.72) = 143 kN Shear Resistance of Concrete = 1.12 x 3400 x 198 = 754kN > 143 kN Step 8:Design Moments CL 31.4.2.2 M0 = W Ln / 8 Along X 454 Along Y 381 kNm CRITICAL SECTION drop Step 9 : Distribution of Bending Moment across panel width ; CL 31.4.3.3 , 31.5.5 𝛼↓𝑐 =∑↑▒𝑘↓𝑐 /𝑘↓𝑠 Equivalent side of circular column = 0.89D = 0.89x 450 = 400 mm Assume Ec = Es Parameters Sum of c o l u m n stiffness above and below the slab Along X Along Y (2 x 4 x Ec x 400 x 4003/12) /3350 = 5.09 Ec x 106 2 (4EcIc)/Lc Slab stiffness (4 Es x 6400 x 2403/12)/7200 ks = 4EsIs/Ls = 4.1Es x 106 c = kc /ks c min (Table 17) = 1+ (1/c) (4 Es x 7200 x 2403/12)/6400 = 5.184Es x 106 1.24 0.98 l2/l1 = 6.4/7.2 = 0.89, WuL/WuD = 0.571 (0.7/0.5)*0.071 = 0.1 <c 7.2/6.4 = 1.125, WuL/WuD = 0.571 Adopt c (0.8/0.5)*0.071 = 0.113 <c Adopt c 1.8 2.02 -‐m1 A. Exterior negative design moment: Exterior -‐m2 -‐m1 Y -‐m1 Exterior -‐m2 X Interior -‐m1 Interior 1.6 Moment Direction along Negative Design Moment MN = -‐0.65*M0/ • Column Strip M1 = MN Width of Column Strip Csw resisting M1 -‐m1= M1/ 3.2 • Middle Strip M2=0 Width of Middle Strip Msw resisting M2 -‐m2 = 0 1.6 X Y 164 122.6 kNm 31.4.3.3 164 122.6 kNm 31.55.2(a) 2x1.6 =3.2 2x1.6 =3.2 m -‐51.3 0 -‐38.3 0 3.2 4 0 0 kNm/m kNm kNm/m 31.5.5.4(a) Exterior B. Interior negative design moment: Y -‐m1 -‐m2 Interior Exterior -‐m1 -‐m1 Moment Direction along Negative Design Moment MN = -‐(0.75 – 0.1/)Mo • Column Strip M1 = 0.75 MN Width of Column Strip Csw resisting M1 • -‐m1= M1/ Csw • Middle Strip M2 = 0.25 MN Width of Middle Strip Msw resisting M2 • -‐m2 = M2/Msw -‐m2 Interior -‐m1 X Y 315.3 266.9 kNm 31.4.3.3 236.5 2x1.6 =3.2 -‐73.9 78.83 3.2 -‐24.7 200.2 2x1.6 =3.2 -‐62.6 66.7 4 -‐16.7 kNm 31.5.5.1 m kNm/m kNm m kNm/m 31.5.5.4(a) X Exterior m1 C. Positive Moment in Mid Span: m Exteri m2 1 Y m2 m1 Interior o m1 r m1 Interior Moment Direction along Design Moment MP = (0.63 – 0.28/)Mo • Column Strip M1 = 0.6 MP Width of Column Strip Csw resisting M1 • m1 = M1/ Csw • Middle Strip M2 = 0.4 MP Width of Middle Strip Msw resisting M2 • m2 = M2/Msw X Y 215.4 187.2 kNm 31.4.3.3 129.3 2x1.6 =3.2 40.4 86.2 3.2 26.94 112.3 2x1.6 =3.2 35.1 74.9 4 18.7 kNm 31.5.5.3 m kNm/m kNm m kNm/m 31.5.5.4(a) X Exterior -‐38.3 -‐51.3 A -‐38.3 -‐0 40.4 A B -‐73.9 -‐vesign : Hogging Moment (tension at top) +ve sign : Sagging Moment (tension at bottom) Exterior 0 35.1 C 35.1 18.7 26.94 D C -‐24.7 Interior -‐62.6 -‐51.3 A -‐62.6 -‐16.7 40.4 B A -‐73.9 Interior Step 10 : Check for adequacy of Depth • Max Design Bending moment = 73.9 kNm/m • Mu,lim = 126.36 kNm/m > 73.9, Depth is adequate G-‐1.1(c) Step 11 :Rebar Details 26.5.2.1 • Ast,min = 0.12 x 240 x 1000 /100 = 288 mm2/m • Minimum Effective Depth of Slab = 198 mm • 7.5 Ast2 – 71488Ast + Mu =0 Strip Location Moment Ast (kNm/m) (mm2/m) (-‐)51.3 (-‐)73.9 40.4 (-‐)24.7 26.94 782 1180 604 359 393 (-‐)38.3 (-‐)62.6 (-‐)16.7 35.1 18.7 570 976 240 520 270 G-‐1.1(b) Bar dia Spacing 782 1180 604 359 393 10 10 8 8 8 100 -‐T 65 -‐T 80 -‐B 140 -‐T 125-‐B 570 976 288 520 288 10 10 8 8 8 135 80 170 95 170 Ast (prov) mm Along X Zone A(Exterior) Zone A(Interior) Zone B Zone C(Interior) Zone D Along Y Zone A (Exterior) Zone A(Interior) Zone B (Interior) Zone C Zone D #8@80 #8@125 #8@170 #8@80 #8@95 Spacing (kNm/m) Bar dia 40.4 26.94 8 8 80 -‐B 125-‐B 35.1 18.7 8 8 95 170 Strip Location Moment #8@95 mm Along X Zone B Zone D Along Y Zone C Zone D #10@65 #10@100 #8@170(Min)* -‐38.3 -‐51.3 #10@80 Exterior 0 A 35.1 C 40.4 -‐38.3 A-‐73.9 B 35.1 18.7 26.94 D C -‐24.7 Interior #8@140 #8@170(Min)* #10@135 Exterior -‐0 -‐62.6 -‐51.3 A -‐16.7 40.4 -‐62.6 A -‐73.9 B Interior #10@80 #10@135 #8@170 Spacing (kNm/m) Bar dia (-‐)51.3 (-‐)73.9 (-‐)24.7 10 10 8 100 -‐T 65 -‐T 140 -‐T (-‐)38.3 (-‐)62.6 (-‐)16.7 10 10 8 135 80 170 Moment mm Along X #10@65 #10@100 * Optional Top Rebars Strip Location Zone A(Exterior) Zone A(Interior) Zone C(Interior) Along Y Zone A (Exterior) Zone A(Interior) Zone B (Interior) Transfer of Moments and Shears between Slabs and Columns • The maximum load that a flat slab can support is dependent upon the strength of the joint between the column and the slab. • Load is transferred by shear from the slab to the column along an area around the column • In addition moments are also transferred. • The moment situation is usually most critical at the exterior columns. • Shear forces resulting from moment transfer must be considered in the design of the lateral column reinforcement (i.e., ties and spirals). EXAMPLE Compute moment transferred to Interior and corner Column in example 2 Interior Column • As spans are same in both directions • M = 0.08 (0.5 w L L2 Ln 2 /(1+1/c ) = 0.08 x 0.5 x 6 x 5.5 x 52 / 1.36 = 24.3 kNm • this moment is distributed to top and bottom column at junction in proportion to their stiffness. • M = 24.3/2 = 12.2 kNm Corner Column M = 131.4 kNm Equivalent Frame Method (EFM) CL 31.5 • • • Edge Frame Transverse Frame More Comprehensive and Logical method Used when limitations of DDM are not complied with Applicable when subjected to horizontal loads 31.5.1 (a) Idealizing the 3D slab –column system to 2D frames along column Centre lines in both longitudinal and transverse directions. Longitudinal Frame 31.5.1(b) For vertical loads, each floor, together with the columns above and below, is analyzed separately. For such an analysis, the far ends of the columns are considered fixed. If there are large number of panels, the moment at a particular joint in a slab beam can be satisfactorily obtained by assuming that the member is fixed two panels away. This simplification is permissible because vertical loads in one panel only appreciably affect the forces in that panel and in the one adjacent to it on each side. For lateral loads, it is necessary to consider an equivalent frame that extends for the entire height of the building, because the forces in a particular member are affected by the lateral forces on all the stories above the floor being considered. Entire Frame Analysis Gravity + Lateral Loads 31.5.1(C and d) variation of the flexural moment of inertia I2 = moment of inertia at the face of the column / column capital c2 = dimension of column capital in the transverse direction l2 = width of equivalent frame. • Variations of moment of inertia along the axis 0f the slab on account of provision of drops shall be taken into account • The stiffening effect of flared column heads may be ignored 31.5.2 Loading Paiern wu LL > ¾ wu,DL Critical Section Interior Column Centre Line Column /Capital face < = C/2 Results in Significant reduction of design moments Design Positive Moment (Span region) M3 = M0 – (M1+M2)/2 C Distribution of Moment Similar to DDM Example 3 : Compute moments in exterior/interior Panel along Longitudinal Span Longitudinal Span = 7.2m, Transverse Span = 6.4 m, Interior Column = 450mm dia, Column Capital = 1500mm dia, Exterior Column = 400x400mm, Column Capital = 870mm(square), Floor to Floor = 3.35 m, Slab Thickness = 240 mm, number of Panels = 4 in each direction 6.4m 6.4m 6.4m 7.2 m 7.2 m 7.2 m 7.2 m Step 1: Stiffness Computations Exterior Column (Kce) = 4E x (4004 /12) /3350 = 2.55E106 = 1 Interior Column (KcI) = 4E x (4504 /64) /3350 = 2.4E106 = 0.957 Slab(Ks) =4E x (6400 x 2403/12) /7200 = 4.1E106 = 1.608 Step 2: Simplified frame for analysis 31.5.1 (b) Joint A 3350 Relative Stiffness 1-‐A 1 1-‐2 1.608 1-‐C 1 0.277 2-‐B 0.957 0.187 2-‐1 1.608 0.314 2-‐3 1.608 2-‐D 0.957 Sum Distribution Factors B 1 2 3 1 3350 C Member 7200 D 7200 2 Fixed End Moments = (16.5 x 6.4) x 7.22/12 = 456.2 kNm 0.277 3.608 5.13 0.446 0.314 0.187 Joint Members 1 FIXED 1A+1C 2 1-‐2 2-‐1 FIXED 2B+2D 3 2-‐3 FIXED 3-‐2 Counter Clockwise end moments are positive DF FEM Bal CO Bal CO Bal CO Bal Final end Moments 0.554 0.446 0.314 -‐252.74 -‐ -‐ -‐ -‐8.85 -‐ 456.2 -‐203.46 -‐ -‐ 15.97 -‐7.12 -‐ -‐456.2 -‐ -‐101.73 31.94 -‐ -‐ -‐3.56 1.12 261.6 -‐528.43528.4339.37 489.26 489.26 -‐261.6 261.6 1 0.374 0.314 -‐ -‐ 38.04 -‐ -‐ -‐ 1.33 456.2 -‐ -‐ 31.94 -‐ -‐ -‐ 1.12 2 -‐ -‐456.2 -‐ -‐ -‐ 15.97 -‐ -‐ -‐440.23440.23 3 Step 3: Design Moments in Exterior Panel A. Design Negative Moments at Critical Section At Exterior Support : CL 31.5.3.2 Critical Section from Column Centre line = 435 mm 235 400 470 870 261.6 16.5 x 6.4 = 105.6 kN/m 528.43 0.435 105.6 x 7.2/2 -‐(528.43-‐261.6)/7.2 = 343 kN Design Moment = 343 x 0.435 -‐261.6 -‐105.6x0.4352/2 = -‐122.4 kNm (Hogging) At Interior Support : CL 31.5.3.1 Critical Section location is at capital face 261.6 Width of equivalent square = 0.89D = 1335 mm 16.5 x 6.4 = 105.6 kN/m 343 kN 528.43 0.6675 417.32 667.5 mm 0.175x7200 = 1260mm Design Moment = 417.32 x 0.6675 -‐528.3 -‐105.6x0.66752/2 = -‐273.26 kNm (Hogging) B. Design Positive Moment M(+) = (16.5 x 6.4x7.2)7.2/8 – ( 528.43 + 261.6)/2 = 289.3 kNm Moments DDM 215.4 EFM 289.3 Negative Moment(Exterior Support) 164 122.4 Negative Moment (Interior Support) 315.3 273.3 Positive Moment (Span) Step 4: Design Moments in Interior Panel A. Design Negative Moments at Critical Section At Interior Support : CL 31.5.3.1 489.26 440.23 A 16.5 x 6.4 = 105.6 kN/m 0.6675 387 kN B 0.6675 373.32 Design Moment at A= 387 x 0.6675 -‐489.26 -‐105.6x0.66752/2 = -‐254.5 kNm (Hogging) Design Moment at B = 373.32 x 0.6675 -‐440.23 -‐105.6x0.66752/2 = -‐214.6 kNm (Hogging) B. Design Positive Moment M(+) = (16.5 x 6.4x7.2)7.2/8 – ( 489.26 + 440.23)/2 = 219.5 kNm Moments Positive Moment (Span) DDM 158.9 EFM 219.5 Negative Moment (Interior Support) 295.1 254.5/214.6 Need for Computer Analysis The equivalent frame method is not satisfactory for hand calculations. It is possible, however, to use computers and plane frame analysis programs if the structure is modeled such that various nodal points in the structure can account for the changing moments of inertia along the member axis. Column SLAB Drop Panel Column Head Column