Determining the Valnes of Components in the Transformer Model The values of the resistances and inductances in the transformer equivalent circuis can be found by the open-circuit test and the short-circuit test. The open-circuit test: in this test, one of the transformer winding is open-circuited, and the other winding is connected to full rated supply voltage, see the circuit below. As seen from the transformer equivalent circuit, the input current flows through the excitation branch of the transformer. The series elements, R P and X P are too small in comparison to RC and X M , so essentially all the input voltage is dropped across the excitation branch. The open-circuit test connections are shown in the following figure. Usually, full line voltage is applied to one side of the transformer, and the input voltage, input current, and input power to the transformer are measured. From the figure, we conclude that,: - the magnitude of conductance of the excitation branch is: I YM OC VOC - The power factor angle of magnetization branch is: P OC cos 1 OC VOC .I OC Notice that the power factor is always lagging for a real transformer, so the angle of the current always lags the angle of the voltage by degrees. We know that the conductance of the excitation branch is: 1 1 YM j GC jBM RC XM From this, we find: I 1 GC Re{YM } YM . cos OC OC cos OC RC VOC And: Yasin A. Al Shiboul, Al Balqa Applied University, Faculty of Engineering Technology, EE Department I 1 BM Im{YM } YM . sin OC OC sin OC XM VOC The short-circuit test: In the short-circuit test, the low-voltage terminals of the transformer are short-circuited, and the high-voltage tenninals are connected to a variable voltage source, as shown below. The input voltage is adjusted until the current in the short-circuited windings is equal to its rated value. The input voltage, current and power are again measured. Since the input voltage is so low during the short-circuit test, negligible current flows through the excitation branch. If the excitation current is ignored, then all the voltage drop in the transfonner can be attributed to the series elements in the circuit. The magnitude of the series impedances referred to the primary side of the transformer is: V Z CS SC I SC - The power factor angle of circuit in the short-circuit test is: P SC cos 1 SC VSC .I SC Notice that the power factor is always lagging for a real transformer, so the angle of the current always lags the angle of the voltage by degrees. We know that, in the short-circuit test: Z CS Z P a 2 Z S RP a 2 RS j X P a 2 X S Thus: V (1) RP a 2 RS Re{Z SC } Z SC . cos SC SC cos SC I SC And: V (2) X P a 2 X S Im{ Z SC } Z SC . sin SC SC sin SC I SC For some simplification, the resistance of the primary winding , R P , can be estimated by measuring it by an ohmmeter while the seconary winding is open-circuited. After finding R P , the resistance of the secondary winding refered to primary, RS' a 2 RS can be found from (1), as the transformation ratio a is usually knowown, or easily can be found, the resistance RS is found. Yasin A. Al Shiboul, Al Balqa Applied University, Faculty of Engineering Technology, EE Department As regard to the reactances of the primary and secondary windings, and for practical transformers, X P and X S' a 2 X S are realively equal, as each of them can easily be found using (2). Example: Build the equivalent circuit of a 20kVA , 8000 / 240V , 60Hz transformer, knowing that the open-circuit test was performed on the secondary side of the transformer (to reduce the maximum voltage to be measured) and the short-circuit test were performed on the primary side of the transformer (to reduce the maximum current to be measured). The following data were taken: Open-circuit test (on secondary) VOC 240V I OC 7.133 A POC 400W Short-circuit test (on primary) VSC 489V I SC 2.5 A PSC 240W Solution: The transformation ratio of the transformer is: V 8000 a P 33.33 VS 240 From the open-circuit test: The power factor angle of magnetization branch is: P 400 0 OC cos 1 OC cos 1 76.5 240 x7.133 VOC .I OC The magnitude of conductance of the excitation branch is: I 7.133 YM OC 0.0297 VOC 240 YM YM OC 0.0297 76.5 0 0.0297 cos 76.5 0 j 0.0297 sin 76.5 0 0.00693 j 0.02888 But: YM 1 1 j RC XM Thus: 1 1 144 0.00693 and RC 0.00693 RC 1 1 34.63 0.02888 and X M 0.02888 XM From the short-circuit test: - The power factor angle is: 240 0 SC cos 1 78.7 489 x 2.5 The magnitude of the series impedances is: Yasin A. Al Shiboul, Al Balqa Applied University, Faculty of Engineering Technology, EE Department Z CS VSC 489 195.6 I SC 2.5 Z CS Z CS SC 195.678.7 0 195.6 cos 78.7 0 j195.6 sin 78.7 0 38.4 j192 But: Z CS Z P a 2 Z S RP a 2 RS j X P a 2 X S Req jX eq Thus: Req 38.4 and X eq 192 Therefore, the equivalent resistance and reactance referred to the high-voltage (primary) side are: Req 38.4 and X eq 192 The resulting simplified equivalent circuit referred to the high-voltage (primary) side can be found by converting the excitation branch values to the high-voltage side. Or: 2 RC , P a 2 RC ,S 33.33 144 159k X M , P a 2 X M ,S 33.33 34.63 38.4k The resulting equivalent circuit is shown in the figure below. 2 THE PER-UNIT SYSTEM OF MEASUREMENTS Circuits containing transformers can be solved easily using the per-unit (pu) system of measurements. This method provides the following advantages: 1- per unit data provides relative magnitude information. 2- simplifies the analysis of circuits containing transformers. The per unit impedance of a transformer in three-phase system is the same, regardless of the type of the winding connections (star-delta, delta-star, stat-star, or deltadelta). The per unit impedance of a transformer is the same when referred to either the primary or the secondary side, 3- circuit parameter are in narrow ranges (around 1 p.u) and this makes error checking easier. 4- Manufacturers usually specify the impedance of an equipment in per unit on the base of its nameplate rating. 5- The per unit impedance values of various ratings of equipment lie in a narrow range, (whereas the actual ohmic values may vary widely). Therefore when Yasin A. Al Shiboul, Al Balqa Applied University, Faculty of Engineering Technology, EE Department actual values are unknown, a good approximate (typical) value of similar equipment can be used. This method is suitable for systems with different voltage levels (sections connected with transformers). In this method base values are selected, and all the actual values are referred to their respective base values, as: actual value value in p.u base value normally two base values, base VA, VAB and the base voltage, VB are chosen. then for each section VB is found from the transformers ratios. then the base current I B and the base impedance Z B are calculated for each section. the p.u values then are found. For the case of single phase systems: - select the base VA, S base - select Vbase and calculate it for each section. - the base current for each section is calculated as: S I B base Vbase - the base impedance for each section is calculated as: V 2 V - Z B base base I base S base Example: A simple power system shown below contains a 480V generator connected to an ideal 1 : 10 step-up transformer, a transmission line, an ideal 20 : 1 step-down transformer, and a load. The impedance of the transmission line is 20 j 60 and the impedance of the load is 1030 0 . The base values for this system are chosen to be 480V and 10kVA at the generator. a) Find the base voltage, current, impedance, and apparent power at every point in the power system. b) Convert this system to its per-unit equivalent circuit. c) Find the power supplied to the load in this system. d) Find the power lost in the transmission line. Solution: a) In the generator region: S base 10kVA , Vbase1 480V , thus: Yasin A. Al Shiboul, Al Balqa Applied University, Faculty of Engineering Technology, EE Department I base1 S base 10000 20.83 A Vbase1 480 Vbase1 480 23.04 I base1 20.83 In the transmission line region: S base 10kVA , Vbase2 4800V , thus: S 10000 I base2 base 2.083 A Vbase2 4800 Z base1 Vbase2 4800 2304 I base2 2.083 In the load region: S base 10kVA , Vbase3 240V , thus: S 10000 I base3 base 41.67 A Vbase3 240 Z base2 Vbase3 240 5.76 I base3 41.67 b) the per-unit values of the circuit parameters are: the generator voltage in p.u: VG ,actual 480 VG. pu 1.0 p.u Vbase1 480 the impedance of the transmission line in p.u: Z Line,actual 20 j 60 Z Line. pu 0.0087 j 0.026 p.u Z base2 2304 the impedance of the load in p.u: Z Load ,actual 1030 0 Z Load . pu 1.73630 0 p.u 1.503 j 0.868 p.u Z base3 5.76 The per-unit equivalent circuit of the power system is shown below. Z base3 c) From this circuit: I G. pu I Line. pu I Load . pu VG , pu 10 0 0.569 30.6 0 p.u 0 0.0087 j 0.026 1.73630 Z line. pu Z load. pu The per-unit power of the load is: 2 2 PLoad . pu I Load . pu .RLoad , p.u 0.569 1.503 0.487 p.u 0.487 x10000 4870W Yasin A. Al Shiboul, Al Balqa Applied University, Faculty of Engineering Technology, EE Department d) The per-unit power loss in the transmission line is: 2 2 PLine. pu I Line. pu .RLine, p.u 0.569 0.0087 0.00282 p.u 0.00282 x10000 28.2W Yasin A. Al Shiboul, Al Balqa Applied University, Faculty of Engineering Technology, EE Department