SIGA-UM and SIGA-MAB Universal Class A/B Modules SPECIFICATION DATA FEATURES • 15 functions in one. • Non-volatile memory. • Integral microprocessor. • High ambient temperature operation (up to 120°F [49°C]). • Electronic addressing and device mapping. • One red and one green status LED. • Designed and manufactured to ISO9001 standards. GENERAL • Models for electrical box or I/O motherboard mounting. The SIGA-UM and SIGA-MAB Class A/B modules are intelligent, addressable devices used for the following applications: — One Class A or two Class B initiating device circuits (IDC). — One Class A or B indicating (signal) appliance circuit (IAC). — One Class A or B circuit for 2-wire smoke detectors. — One Form “C” (NO/NC) dry output contact relay. These modules provide the features of up to 15 function to support multiple applications including Class A or B device circuit wiring, Class A or B 2-wire smoke detector circuits, and delayed latching (retard) for water flow alarm applications. The personality code for either device is assigned during system configuration using the system definition utility. The code is downloaded from the controller. Continuously running self-diagnostics update device statistics and store them in a history log in non-volatile memory. The history log contains information including hours of operation, last maintenance date, number of alarms and troubles and time and date of last alarm. The electronically coded serial number and address allow controllers on the same circuit to map automatically the location of the module and use that information in “as built” drawings. ® U.S. Registered Trademark Copyright © 1999 Honeywell Inc. • All Rights Reserved 74-2068-1 SIGA-UM AND SIGA-MAB UNIVERSAL CLASS A/B MODULES accommodate individual risers for each on-board module, or shared risers in any combination with their UIO modules. All wiring connections are made to terminal blocks on the motherboard. UIO assemblies can be mounted in Honeywell enclosures. The SIGA-MAB can be used to connect any one of the following: • Two Class B or one Class A initiating device circuits. • One Class A or B circuit for 2-wire smoke detectors. • One Class A or B indicating appliance circuit. DESCRIPTION The SIGA-UM and SIGA-MAB Universal Class A/B Modules gather information from the devices and convert that information into digital signals. An on-board microprocessor measures and analyzes the signal and decides whether or not to input an alarm. The module constantly runs self-checks to provide important maintenance information. The modules store the results of the self-check in its permanent on-volatile memory. Some or all of this information can be printed for review from the control panel on the XLS1000 Loop Controller, a personal computer (PC) laptop interface, or the Service Tool. History log information includes: • Module serial number, address, and type. • Date of manufacture, hours of operation, and last maintenance date. • Number of recorded alarms and troubles. • Time and date of last alarm. • A maximum of 32 possible trouble codes that the module can use to specify faults. TYPICAL WIRING AND APPLICATIONS The modules accept 18 AWG (0.75 mm2), 16 AWG (1.0 mm2), and 14 AWG (1.5 mm2) wire sizes. NOTE: Sizes 16 AWG (1.0 mm2) and 14 AWG (1.5 mm2) are preferred for ease of installation. Initiating Device Circuit Wire Specifications Maximum Allowable Wire Resistance: 50 ohms (25 ohms per wire) per circuit. Maximum Allowable Wire Capacitance: 0.1µF per circuit. On board intelligence permits the modules to operate in stand-alone mode. If controller communication fails for more than four seconds but remains powered, all devices on that circuit go into stand-alone mode. The circuit acts like a conventional alarm receiving circuit. Each module on the circuit continues to collect and analyze information from its surroundings. Modules configured as alarm devices alarm if the connected alarm initiating device activates. Table 1. Distances Allowable for each Wire Size. On-board intelligence also means less information needs to be sent between the module and the loop controller. Other than regular supervisory polling response, the module only needs to communicate with the loop controller when it has a new condition to report. This feature provides very fast response time and allows use of a lower baud rate for communication on the loop. The lower baud rate offers several advantages, including: • Less sensitivity to loop wire characteristics. • Less sensitivity to noise glitches on the cable. • Less emitted noise from the wiring. Maximum Distance to end of line resister (EOLR) 18 AWG (0.75 mm2) 3,930 ft (1,198m) 16 AWG (1.0 mm2) 6,225 ft (1,897m) 14 AWG (1.5 mm2) 9,900 ft (3,018m) CAUTION Equipment Damage. This module operates on electrical power. Fires often cause power interruption. Discuss further safeguards with your fire protection specialist. Applications The actual duty performed by the SIGA-UM and SIGA-MAB is determined by its sub-type or “personality code.” The code is selected for the desired application, It is assigned during system definition and downloaded from the loop controller. The SIGA-UM installs to a standard North American 2-gang electrical box, making it ideal for locations where only one module is required. Separate I/O and data loop connections are made to each module. The SIGA-UM can be used to connect any one of the following items: • Two Class B or one Class A initiating device circuits. • One Class A or B indicating appliance circuit. • One Class A or B circuit for 2-wire smoke detectors. • One Form C (no/nc) dry output contact relay. Personality codes are assigned to each address. Only codes 0,1,2,3, and 4 can be mixed on any one module. For example, personality code 1 can be assigned to the first address (circuit A) and code 4 can be assigned to the second address (circuit B). All other codes automatically use up both addresses simultaneously, so they cannot be mixed. The SIGA MAB is part of the Universal Input/Output (UIO) family of plug-in Signature Series models. It takes advantage of the modular flexibility and easy installation that characterizes all UIO models. Two-module and six-module UIO motherboards are available. These motherboards can 74-2068—1 Wire Size NOTE: Personality Code 0: NOT CONFIGURED, the factory default, can be applied to both circuits separately. 2 SIGA-UM AND SIGA-MAB UNIVERSAL CLASS A/B MODULES Table 2. Circuits and Applications for Personality Codes. Code Class Description Suitable for 1 B Normally Open Alarm Latching Assign to one or both circuits. Configures either circuit 1, 2, or both for Class B normally-open dry contact initiating devices. An ALARM signal is sent to the loop controller when the input contact is closed. The condition alarm is latched at the module. Pull stations, Heat detectors 2 B Normally Open Alarm Delayed Latching Assign to one or both Circuits. Configures either circuit 1 or circuit 2 or both for Class B normally-open dry contact. An ALARM signal is sent to the loop controller when the input contact is closed at least 16 seconds. The condition alarm is latched at the module. Waterflow alarm switches 3 B Normally Open Active NonLatching Assign to one or both circuits. Configures either circuit 1, 2 or both for Class B normally open dry contact monitoring input. An ACTIVE signal is sent to the loop controller when the input contact is closed. The active condition is not latched at the module. Fans, dampers, doors 4 B Normally Open Active Latching Assign to one or both circuits. Configures either circuit 1, 2 or both for Class B normally open dry contact monitoring input. An ACTIVE signal is sent to the loop controller when the input contact is closed. The active condition is latched at the module. Supervisory and tamper switches 8 Control Relay Applies to circuits 1 and 2 simultaneously. Configures module to provide one Form C dry relay contact. Contact rating is 2.0A at 24 Vdc; 0.5A aat 120 Vac (or 220 Vac nonUL). This personality code is only available with the SIGAUM. Door closers, fans, dampers 9 A Normally Open Alarm Latching Applies to both circuits 1 and 2 simultaneously. Configures module for Class A normally-open dry contact initiating devices. An ALARM signal is sent to the loop controller when the when the input contact is closed. The active condition is latched at the module. Pull stations, Heat detectors 10 A Normally Open Alarm Delayed Latching Applies to both circuits 1 and 2 simultaneously. Configures module for Class A normally-open dry contact initiating devices. An ALARM signal is sent to the loop controller when the when the input contact is closed. The alarm condition is latched at the module. Waterflow alarm switches 11 A Normally Open Active NonLatching Applies to both circuits 1 and 2 simultaneously. Configures module for Class A normally-open dry contact initiating devices. An ACTIVE signal is sent to the loop controller when the when the input contact is closed. The active condition is active latched at the module. Fans, Doors, Dampers 12 A Normally Open Active Latching Applies to both circuits 1 and 2 simultaneously. Configures module for Class A normally-open dry contact initiating devices. An ACTIVE signal is sent to the loop controller when the when the input contact is closed. The active condition is latched at the module. Supervisory switches, Tamper switches 13 B 2-Wire Smoke Alarm Nonverified 2-wire smoke detectors that do not require alarm verification. Normally-open dry contact initiating devices. Can be on the same circuit only with personality code 13. An ALARM signal is sent to the loop controller when the input contact is closed or a smoke detector enters into alarm. The alarm condition is latched at the module. The LED on only the first smoke detector to alarm latches ON steady. Circuit B monitors smoke power from the loop controller. Smoke detectors, Pull stations, Heat detectors (continued) 3 74-2068—1 SIGA-UM AND SIGA-MAB UNIVERSAL CLASS A/B MODULES Table 2. Circuits and Applications for Personality Codes (Continued). Code Class Description 14 B 2-Wire Smoke 15 A 16 Suitable for Applies to both circuits 1 and 2 simultaneously. Configures module for connection of up to 1.0 mA or conventional 2-wire smoke detectors that do require alarm verification. Normallyopen dry contact initiating devices can not be on the same alarm circuit. An ALARM signal is sent to the loop controller when a smoke detector enters into alarm. The alarm condition is latched at the module. The LED only the first smoke detector to alarm latches ON steady. Circuit B monitors smoke power from the loop controller. Smoke detectors, Pull stations, Heat detectors Signal Output Applies to both circuits 1 and 2 simultaneously. Configures module for connection of Class A Indicating Appliance Circuit (IAC). The maximum allowable signal power is 2A at 24 Vdc, 0.5A at 120 Vac (or 220 Vac non-UL). The maximum allowable speaker power is 50W (25V audio) or 35W (70V audio). Horns, Speakers B Signal Output Applies to both circuits 1 and 2 simultaneously. Configures module for connection of Class B Indicating Appliance Circuit (IAC). The maximum allowable signal power is 2A at 24 Vdc, 0.5A at 120 Vac (or 220 Vac non-UL). The maximum allowable speaker power is 50W (25V audio) or 35W (70V audio). Horns, Speakers 20 A 2-Wire Smoke Alarm NonVerified Operates the same as personality code 13, except the wiring is Class A. Smoke detectors, Heat detectors, Pull stations 21 A 2-Wire Smoke Alarm Verified Operates the same as personality code 14, except the wiring is Class A. Smoke detectors, Heat detectors, Pull stations Alarm verified Personality codes are assigned to each address. Only codes 1,2,3, and 4 can be mixed on any individual module. For example, personality code 1 can be assigned to the first address (circuit A) and code 4 can be assigned to the second address (circuit B). All other codes automatically use up both addresses at the same time, so they cannot be mixed. — The following notes refer to the wiring diagrams that follow. Notes 1 through 6 are referenced in the diagrams with callouts. — — — — NOTES: — For maximum wire resistance and distances, refer to the System Installation Instructions. — Maximum 14 AWG (1.5 sq mm) wire. Minimum 18 AWG (0.75 sq mm). — Refer to the System Installation Instructions for wiring specifications. — These modules do not support 2-wire smoke detectors unless configured for personality 13, 14, 20, or 21. 74-2068—1 4 Maximum 12.5 ohms resistance per wire for Class A configurations (for initiating devices and monitoring circuits). Compatible smoke detector. Refer to Personality Codes 13, 14, 20, or 21 for type and quantity. For SIGA-CR, SIGA-UM and SIGA-MAB must be installed in the same room as the device they control. All wiring power limited and supervised (only for circuits shown). Polarity at terminals 11 and 12 shown in Supervisory condition. Connect as shown in diagram. (Polarity reverses on Alarm. Polarity reversal depends on the polarity of the riser inside the alarm. Polarity does not reverse if circuits are wired incorrectly. SIGA-UM AND SIGA-MAB UNIVERSAL CLASS A/B MODULES INPUT 1 INPUT 2 4 UL/ULC LISTED 47K OHMS EOL UL/ULC LISTED 47K OHMS EOL NOT USED TYPICAL INITIATING DEVICE STYLE B (CLASS B) TB4 TB3 JP1 1 2 GREEN LED (NORMAL) RED LED (ALARM/ACTIVE) TB1 TB2 NOT USED DATA IN (+) DATA OUT (+) DATA IN (–) DATA OUT (–) FROM SIGNATURE CONTROLLER OR PREVIOUS DEVICE TO NEXT DEVICE 3 C8255 Fig. 1. Class B Dual Input Module Normally Open Alarm—Latching Class B Normally Open Active—Non-Latching Class B (Personality Code 1) Assign to one or both circuits. Configures either 1, 2, or both for Class B normally-open dry contact initiating devices such as pull stations, heat detectors, and similar devices. An ALARM signal is sent to the loop controller when the input contact is closed. The alarm condition is latched at the module. (Personality Code 3) Assign to one or both circuits. Configures either 1, 2, or both for Class B normally-open dry contact initiating devices monitoring input from fans, dampers, doors, and similar devices. An ACTIVE signal is sent to the loop controller when the input contact is closed. The alarm condition is not latched at the module. Normally Open Alarm—Delayed Latching Class B Normally Open Active—Latching Class B (Personality Code 2) Assign to one or both circuits. Configures either 1, 2, or both for Class B normally-open dry contact initiating devices such as water flow alarm switches. An ALARM signal is sent to the loop controller when the input contact is closed for at least 16 seconds. The alarm condition is latched at the module. (Personality Code 4) Assign to one or both circuits. Configures either 1, 2, or both for Class B normally-open dry contact initiating devices monitoring input from supervisory switches, tamper switches, and similar devices. An ACTIVE signal is sent to the loop controller when the input contact is closed. The alarm condition is latched at the module. 5 74-2068—1 SIGA-UM AND SIGA-MAB UNIVERSAL CLASS A/B MODULES 4 JP1 321 NORMALLYCLOSED NORMALLYOPEN COMMON NOT NOT USED USED NOT USED TB4 TB3 JP1 GREEN LED (NORMAL) RED LED (ALARM/ACTIVE) TB1 TB2 NOT USED DATA IN (+) DATA OUT (+) DATA IN (–) DATA OUT (–) FROM SIGNATURE CONTROLLER OR PREVIOUS DEVICE TO NEXT DEVICE 3 C8256 Fig. 2. Control Relay Module. Control Relay Dry Contact Output (Personality Code 8) Applies to both circuits 1 and 2 simultaneously. Configures module to provide one Form “C” dry relay contact to control door closers, fans, dampers, and similar devices. Contact rating is 2.0A at 24 Vdc; 0.5A at 120 Vac (or 220 Vac non-UL). 4 UL/ULC LISTED 47K OHMS EOL STYLE D (CLASS A) 5 2 TYPICAL INITIATING DEVICE NOT USED TB4 STYLE B (CLASS B) TB3 JP1 1 2 GREEN LED (NORMAL) RED LED (ALARM/ACTIVE) TB1 TB2 NOT USED DATA IN (+) DATA OUT (+) DATA IN (–) DATA OUT (–) FROM SIGNATURE CONTROLLER OR PREVIOUS DEVICE TO NEXT DEVICE 3 C8257 Fig. 3. Class A Single Output Module. 74-2068—1 6 SIGA-UM AND SIGA-MAB UNIVERSAL CLASS A/B MODULES Normally Open Alarm—Latching Class A Normally Open Active—Non-Latching Class A (Personality Code 9) One circuit (two addresses used). Configures module for Class A normally-open dry contact initiating devices such as pull stations, heat sensors, and similar devices. An ALARM signal is sent to the loop controller when the input contact is closed. The alarm condition is latched at the module. (Personality Code 11) Configures module for Class A normally-open dry contact initiating devices such as fans, dampers, doors, and similar devices. An ACTIVE signal is sent to the loop controller when the input contact is closed. The active condition is not latched at the module. Normally Open Alarm—Latching Class A Normally Open Active—Latching Class A (Personality Code 10) Configures module for Class A normally-open dry contact initiating devices such as water flow alarm switches. An ALARM signal is sent to the loop controller when the input contact is closed for at least 16 seconds. The alarm condition is latched at the module. (Personality Code 12) Configures module for Class A normally-open dry contact initiating devices such as supervisory switches, tamper switches, and similar devices. An ACTIVE signal is sent to the loop controller when the input contact is closed. The active condition is latched at the module. 1 5 2 2 STYLE B (CLASS B) + + IN OUT — STYLE D (CLASS A) TO LAST DEVICE UL/ULC LISTED 47K OHMS EOL 6 NOT USED UL/ULC 22K OHMS EOL USED FOR CLASS A ONLY (CODE 20, 21) TB4 TB3 JP1 SMOKE DETECTOR POWER (+24 Vdc) FROM SIGNATURE CONTROLLER OR PREVIOUS DEVICE BACK TO TERMINALS 14, 13 CODE 20, 21 ONLY TYPICAL INITIATING DEVICE (NO INITIATING DEVICES ALLOWED WITH PERSONALITY CODE 14 AND 21) GREEN LED (NORMAL) RED LED (ALARM/ACTIVE) TB1 TB2 NOT USED DATA IN (+) DATA OUT (+) DATA IN (–) DATA OUT (–) FROM SIGNATURE CONTROLLER OR PREVIOUS DEVICE TO NEXT DEVICE C8258A 3 Fig. 4. Two-wire smoke detectors—Class A or Class B. 7 74-2068—1 SIGA-UM AND SIGA-MAB UNIVERSAL CLASS A/B MODULES 2-Wire smoke (Class A)—Non-verified 2-Wire smoke (Class A)—Alarm Verified (Personality Code 20) (Personality Code 21) 2-Wire smoke (Class A)—Non-verified 2-Wire smoke (Class A)—Non-Verified (Personality Code 13) There is only one circuit in this configuration, but two addresses are used. The first address is the IDC. The second address is for monitoring smoke detector power. This configures modules for connection of up to 1.0 mA of conventional 2-wire smoke detectors that do not require alarm verification. These include normally-open dry contact initiating devices such as pull stations, heat detectors, and similar devices. These devices can be on the same circuit only with personality code 13. An ALARM signal is sent to the loop controller when the input contact is closed or a smoke detector enters alarm. The alarm condition is latched at the module. The LED on the first smoke detector to alarm latches ON steady. Compatible smoke sensors include up to twenty 6250/6264 series or up to fifteen 6266/6269/6270 series. This setting is also compatible with up to 10 model 1451 or 2451 sensors. (Personality Code 14) There is only one circuit in this configuration, but two addresses are used. The first address is the IDC. The second address is for monitoring smoke detector power. This configures modules for connection of up to 1.0 mA of conventional 2-wire smoke detectors that do require alarm verification. These include normally-open dry contact initiating devices such as pull stations, heat detectors, and similar devices. These devices can be on the same circuit only with personality code 13. An ALARM signal is sent to the loop controller when the input contact is closed or a smoke detector enters alarm. The alarm condition is latched at the module. The LED on the first smoke detector to alarm latches ON steady. Compatible smoke sensors include up to twenty 6250/6264 series or up to fifteen 6266/6269/6270 series. This setting is also compatible with up to 10 model 1451 or 2451 sensors. + – 4 1 2 STYLE Z (CLASS A) NOT USED + – TB4 + – + – + – + – UL/ULC LISTED 47K OHMS EOL TYPICAL INDICATING APPLIANCE TB3 JP1 WIRED TO TERMINALS 13 AND 14 FOR STYLE Z (CLASS A ) OR STYLE Y WIRED TO (CLASS B) TERMINALS 11, 12 STYLE Y (CLASS B) 2 2 UL/ULC LISTED 47K EOL TYPICAL INDICATING APPLIANCE GREEN LED (NORMAL) RED LED (ALARM/ACTIVE) TB1 TB2 FROM XLS CONTROL PANEL RISER (+) TO NEXT DEVICE OR EOL RESISTOR SUPPLIED WITH UL/ULC LISTED CONTROL PANEL DATA OUT (–) TO NEXT DEVICE DATA OUT (+) RISER (–) RISER IN (+) RISER IN (–) FROM SIGNATURE CONTROLLER OR PREVIOUS DEVICE + – DATA IN (+) DATA IN (–) 3 1 FOR MAXIMUM WIRE RESISTANCE AND MAXIMUM WIRE DISTANCES, REFER TO INSTALLATION INSTRUCTIONS. 4 THIS MODULE WILL NOT SUPPORT 2-WIRE SMOKE DETECTORS UNLESS CONFIGURED FOR PERSONALITY 13, 14, 20 OR 21. 2 MAXIMUM NO. 14 AWG (1.5mm2) WIRE. MINIMUM NO. 18 AWG (0.75mm2). 5 MAXIMUM 12.5 OHMS RESISTANCE PER WIRE FOR CLASS A CONFIGURATIONS. 3 REFER TO SIGNATURE LOOP CONTROLLER INSTALLATION SHEET FOR WIRING SPECIFICATIONS. C8259A Fig. 5. Single output module. 74-2068—1 8 SIGA-UM AND SIGA-MAB UNIVERSAL CLASS A/B MODULES Signal Output Class A Signal Output Class B (Personality Code 15) There is only one circuit in this configuration, but it uses two addresses. The first address is the IDC. The second address is for monitoring smoke detector power. This code configures the module for connection of Class A Indicating Appliance Circuits (IAC). This is normally used to control bells, speakers, and similar devices. The maximum allowable signal power is 2A at 24 Vdc, 0.5A at 120 Vac (or 220 Vac non-UL). The maximum allowable speaker power is 50W (25V audio) or 35W (70V audio). (Personality Code 16) There is only one circuit in this configuration, but it uses two addresses. The first address is the IDC. The second address is for monitoring smoke detector power. This code configures the module for connection of Class B Indicating Appliance Circuits (IAC). This is normally used to control bells, speakers, and similar devices. The maximum allowable signal power is 2A at 24 Vdc, 0.5A at 120 Vac (or 220 Vac non-UL). The maximum allowable signal power is 2A at 24 Vdc, 0.5A at 120 Vac (or 220 Vac non-UL). The maximum allowable speaker power is 50W (25V audio) or 35W (70V audio). 9 74-2068—1 SIGA-UM AND SIGA-MAB UNIVERSAL CLASS A/B MODULES CLASS A OR B 2-WIRE SMOKE DETECTOR AND CONTACT INPUT MODULE (PERSONALITY CODE 13, 14, 20, OR 21) TYPICAL N.O. INSTALLING DEVICE (PERSONALLITY CODES 13 AND 20 ONLY) + UL/ULC LISTED 15K OHM EQL – – 1 S+ S+ + 2 GREEN LED (NORMAL) RED LED (ACTIVE) CLASS B CIRCUITS ONLY 7 CLASS A CIRCUITS ONLY SIGA-MAB 1 2 3 4 INSTALL JP1 AND JP2 SIGA-UIO (R) SERVICE MOTHERBOARD RISER 1 OUT + 24 Vdc SMOKE DETECTOR POWER 4 3 2 5 1 + 24 Vdc SMOKE DETECTOR POWER RISER 1 IN FROM SIGNATURE LOOP CONTROLLER OR PREVIOUS DEVICE + – DATA IN 4 3 2 1 SIGNATURE DATA CIRCUIT DATA OUT + – TB14 TB7 NO CONNECTIONS REQUIRED FOR SIGA-MAB USING PERSONALITY CODES 13, 14, 20, OR 21. 4 3 2 1 TB15 3 24VDC SMOKE DETECTOR POWER 6 + 1 2 3 4 + INSTALL THE JUMPERS BETWEEN ADJACENT SIGNA-MABS WITH PERSONALITY CODES 13, 14, 20, OR 21. 24 Vdc SMOKE DETECTOR POWER FROM SIGNATURE LOOP CONTROLLER OR PREVIOUS DEVICE CLASS A OR B DRY CONTACT INPUT MODULE (PERSONALITY CODE 1,2,3,4,9,10,11 OR 12) PERSONALITY CODES: 1, 2, 3, OR 4 1 UL/ULC LISTED 15K OHM EQL 2 7 PERSONALITY CODES: 9, 10, 11, OR 12 1 2 GREEN LED (NORMAL) RED LED (ACTIVE) 7 REMOVE MODULE JUMPERS DATA IN SIGA-UIO (R) SERVICE MOTHERBOARD + – 4 3 2 1 TB14 4 3 2 1 SIGNATURE DATA CIRCUIT DATA OUT SIGA-MAB 1 2 3 4 + – TB7 4 3 2 1 TB15 3 NO CONNECTIONS REQUIRED FOR SIGA-MAB USING PERSONALITY CODES 1, 2, 3, 4, 9, 10, 11, OR 12. NO CONNECTIONS REQUIRED FOR SIGA-MAB USING PERSONALITY CODES 1, 2, 3, 4, 9, 10, 11, OR 12. REMOVE MOTHERBOARD JUMPERS. 1 2 3 4 1 FOR MAXIMUM RESISTANCE, SEE THE APPROPRIATE TECHNICAL REFERENCE MANUAL. MAXIMUM CIRCUIT CAPACITANCE IS 0.1 MF. 7 SUPERVISED AND POWER-LIMITED. 8 SUPERVISED AND POWER-LIMITED WHEN CONNECTED TO A POWER-LIMITED SOURCE. IF THE SOURCE IS NONPOWER-LIMITED, MAINTAIN A SPACE OF 1/4 INCH FROM POWER-LIMITED WIRING OR USE FPL, FPLP, FPLR, OR AN EQUIVALENT IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE. 2 MAXIMUM NO. 12 AWG (2.5 mm2) WIRE; MINIMUM NO. 18 AWG (0.75mm2) 3 REFER TO SIGATURE CONTROLLER INSTALLATION SHEET FOR WIRING SPECIFICATIONS. 4 MAXIMUM 10 Vdc @ 350mA 9 THE INPUT FOR THIS RISER IS COMMON TO ALL MODULES. 5 THE SIGA-UIO6R DOES NOT COME WITH TB14. 10 MAXIMUM ALARM CURRENT IS 17 mA. OPERATING VOLTAGE RANGE IS 16.0 TO 24.0 Vdc. M16287 6 THE SIGA-UIO6 DOES NOT COME WITH TB8 THROUGH TB13. 74-2068—1 5 10 SIGA-UM AND SIGA-MAB UNIVERSAL CLASS A/B MODULES MOTIFICATION OUTPUT MODULE (PERSONALITY CODE 15 OR 16) PERSONALITY CODE 15 TYPICAL SPEAKER CIRCUIT TYPICAL NOTIFICATION APPLIANCE CIRCUIT PERSONALITY CODE 16 BI-POLAR TRANSIENT PROTECTOR (P/N 235196P) 1 2 4 + – + – + – + – UL/ULC LISTED 15K OHM EQL CLASS B CIRCUITS ONLY SIGA-MAB 1 2 3 4 RED LED (ACTIVE) SIGA-UIO (R) SERVICE MOTHERBOARD + – + – – + – + 4 3 2 1 4 3 2 1 SIGNATURE DATA CIRCUIT DATA OUT + – 7 GREEN LED (NORMAL) DATA IN + – RISER 1 OUT RISER 1 IN TB14 8 9 TB7 9 4 3 2 1 TB15 3 REMOVE MODULE JUMPERS NO CONNECTIONS REQUIRED FOR SIGA-MAB USING PERSONALITY CODES 15 AND 16. 1 2 3 4 6 RISER 1 IN 7 + – – + RISER 1 OUT 1 FOR MAXIMUM RESISTANCE, SEE THE APPROPRIATE TECHNICAL REFERENCE MANUAL. MAXIMUM CIRCUIT CAPACITANCE IS 0.1 MF. 2 MAXIMUM NO. 12 AWG (2.5 mm2) WIRE; MINIMUM NO. 18 AWG (0.75mm2) 3 REFER TO SIGATURE CONTROLLER INSTALLATION SHEET FOR WIRING SPECIFICATIONS. 4 MAXIMUM 10 Vdc @ 350mA 9 THE INPUT FOR THIS RISER IS COMMON TO ALL MODULES. 5 THE SIGA-UIO6R DOES NOT COME WITH TB14. 6 THE SIGA-UIO6 DOES NOT COME WITH TB8 THROUGH TB13. 10 MAXIMUM ALARM CURRENT IS 17 mA. OPERATING VOLTAGE RANGE IS 16.0 TO 24.0 Vdc. M16288 7 SUPERVISED AND POWER-LIMITED. 8 SUPERVISED AND POWER-LIMITED WHEN CONNECTED TO A POWER-LIMITED SOURCE. IF THE SOURCE IS NONPOWER-LIMITED, MAINTAIN A SPACE OF 1/4 INCH FROM POWER-LIMITED WIRING OR USE FPL, FPLP, FPLR, OR AN EQUIVALENT IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE. SPECIFICATIONS Operating Voltage: 15.2 Vdc to 19.95 Vdc (19 Vdc nominal). Type Code: 53 (Factory set). 15 sub-types (personality codes) available. LED Operation: On-board green LED flashes when polled. On-board red LED flashes when in alarm state, active state, or both. Both LED glow steady when in alarm (stand alone). The LED are visible only when the front plate is removed. Personality codes are assigned to the SIGA-UM and SIGAMAB by the installer. Only codes 1,2,3, and 4 can be mixed on any one module. For example, personality code 1 can be assigned to the first address (circuit A) and personality code 4 can be assigned to the second address (circuit B). All other personality codes use up both addresses simultaneously, so they cannot be mixed. Compatibility: XLS1000 and XLS100 loop controllers. Address Requirements: Two module addresses. Operating Environment: Temperature: 32°F to 120°F (0°C to 60°C). Humidity: 0% to 93% rh noncondensing. Storage Temperature: –4°F to 140°F (-20°C to 60°C). 11 74-2068—1 SIGA-UM AND SIGA-MAB UNIVERSAL CLASS A/B MODULES Table 3. Operating Current. Mode of Operation Personality Code Standby Current Alarm Current EOL Resister Value Class B IDC 1,2,3,4 396 µA 680 µA 47k ohms Form C dry contact relay1 8 100 µA 100 µA Not required. Class A IDC 9, 10, 11, 12 223 µA 365 µA 47k ohms 2-wire smoke detectors and IDC 13, 14, 20, 21 2 mA See below 22k ohms (Class B) 15k ohms (Class A) First detector into alarm — — 17 mA — Subsequent detectors into alarm — — 100 µA — Class A or Class B IAC1 15, 16 223 µA 365 µA 47k ohms (Class B) 1Contacts rated at 2A at 24 Vdc, 0.5A at 120 Vac (or 220 Vac non-UL), 50W at 25V audio and 35W at 70V audio. Mounting SIGA-MAB: SIGA-UIO2R/6R/6. Shipping Weight: SIGA-UM: 0.5 lb (0.23 kg). SIGA-MAB: .18 lb (.08 kg). Carton Dimensions: 5-1/3 in. (135 mm) wide by 2-1/2 in (64 mm) high by 5-1/3 in. (135 mm) deep. Construction and Finish: Front Plate: High-impact white engineering polymer 2-gang front plate. Label: FIRE ALARM MODULE. NOTE: The module includes a self-adhesive label in French. All electronics utilize surface mount technology (SMT) for smaller size and greater immunity to RF noise. A conformal coating resists humidity and corrosion. Mounting SIGA-UM: North America: 2-1/2 in. (64 mm) deep 2-gang boxes and 1-1/2 in (38 mm) deep 4 in. square boxes. Europe: 100 mm square boxes (purchased locally). Terminals: Suitable for 14 AWG to 18 AWG (1.5 sq mm to 0.75 sq mm) wire sizes. SIGA-UM Accessories: Option Surface Mount Box: Red 2-gang box (part no. 27193-21). White 2-gang box (part no. 27143-26). Dimensions: 4-13/16 in. (122 mm) wide by 4-3/4 in. (121 mm) high by 2-1/2 in. (64 mm) deep. Weight: 2 lb (0.8 kg). SIGA-MAB Accessories: SIGA-UIO2R: Universal Input/Output Module board with riser inputs. 2 module positions. SIGA-UIO6R: Universal Input/Output Module board with riser inputs. 6 module positions. SIGA-UIO6: Universal Input/Output Module board. 6 module positions. Standards: ISO 9001. Approvals: UL, ULC. Home and Building Control Honeywell Inc. Honeywell Plaza P.O. Box 524 Minneapolis MN 55408-0524 Home and Building Control Honeywell Limited-Honeywell Limitée 155 Gordon Baker Road North York, Ontario M2H 3N7 Honeywell Latin American Region 480 Sawgrass Corporate Parkway Suite 200 Sunrise FL 33325 Honeywell Europe S.A. 3 Avenue du Bourget 1140 Brussels Belgium 74-2068—1 D.A. Rev. 3-99 Printed in U.S.A. on recycled paper containing at least 10% post-consumer paper12 fibers. Honeywell Asia Pacific Inc. Room 3213-3225 Sun Hung Kai Centre No. 30 Harbour Road Wanchai Hong Kong www.honeywell.com