SIGA-UM and SIGA-MAB
Universal Class A/B Modules
SPECIFICATION DATA
FEATURES
• 15 functions in one.
• Non-volatile memory.
• Integral microprocessor.
• High ambient temperature operation (up to 120°F
[49°C]).
• Electronic addressing and device mapping.
• One red and one green status LED.
• Designed and manufactured to ISO9001 standards.
GENERAL
• Models for electrical box or I/O motherboard
mounting.
The SIGA-UM and SIGA-MAB Class A/B modules are
intelligent, addressable devices used for the following
applications:
— One Class A or two Class B initiating device circuits
(IDC).
— One Class A or B indicating (signal) appliance circuit
(IAC).
— One Class A or B circuit for 2-wire smoke detectors.
— One Form “C” (NO/NC) dry output contact relay.
These modules provide the features of up to 15 function to
support multiple applications including Class A or B device
circuit wiring, Class A or B 2-wire smoke detector circuits, and
delayed latching (retard) for water flow alarm applications.
The personality code for either device is assigned during
system configuration using the system definition utility. The
code is downloaded from the controller.
Continuously running self-diagnostics update device statistics
and store them in a history log in non-volatile memory. The
history log contains information including hours of operation,
last maintenance date, number of alarms and troubles and
time and date of last alarm.
The electronically coded serial number and address allow
controllers on the same circuit to map automatically the
location of the module and use that information in “as built”
drawings.
® U.S. Registered Trademark
Copyright © 1999 Honeywell Inc. • All Rights Reserved
74-2068-1
SIGA-UM AND SIGA-MAB UNIVERSAL CLASS A/B MODULES
accommodate individual risers for each on-board module, or
shared risers in any combination with their UIO modules. All
wiring connections are made to terminal blocks on the
motherboard. UIO assemblies can be mounted in Honeywell
enclosures. The SIGA-MAB can be used to connect any one
of the following:
• Two Class B or one Class A initiating device circuits.
• One Class A or B circuit for 2-wire smoke detectors.
• One Class A or B indicating appliance circuit.
DESCRIPTION
The SIGA-UM and SIGA-MAB Universal Class A/B Modules
gather information from the devices and convert that
information into digital signals. An on-board microprocessor
measures and analyzes the signal and decides whether or
not to input an alarm.
The module constantly runs self-checks to provide important
maintenance information. The modules store the results of
the self-check in its permanent on-volatile memory. Some or
all of this information can be printed for review from the
control panel on the XLS1000 Loop Controller, a personal
computer (PC) laptop interface, or the Service Tool. History
log information includes:
• Module serial number, address, and type.
• Date of manufacture, hours of operation, and last
maintenance date.
• Number of recorded alarms and troubles.
• Time and date of last alarm.
• A maximum of 32 possible trouble codes that the module
can use to specify faults.
TYPICAL WIRING AND APPLICATIONS
The modules accept 18 AWG (0.75 mm2), 16 AWG
(1.0 mm2), and 14 AWG (1.5 mm2) wire sizes.
NOTE: Sizes 16 AWG (1.0 mm2) and 14 AWG (1.5 mm2)
are preferred for ease of installation.
Initiating Device Circuit Wire Specifications
Maximum Allowable Wire Resistance: 50 ohms (25 ohms per
wire) per circuit.
Maximum Allowable Wire Capacitance: 0.1µF per circuit.
On board intelligence permits the modules to operate in
stand-alone mode. If controller communication fails for more
than four seconds but remains powered, all devices on that
circuit go into stand-alone mode. The circuit acts like a
conventional alarm receiving circuit. Each module on the
circuit continues to collect and analyze information from its
surroundings. Modules configured as alarm devices alarm if
the connected alarm initiating device activates.
Table 1. Distances Allowable for each Wire Size.
On-board intelligence also means less information needs to
be sent between the module and the loop controller. Other
than regular supervisory polling response, the module only
needs to communicate with the loop controller when it has a
new condition to report. This feature provides very fast
response time and allows use of a lower baud rate for
communication on the loop. The lower baud rate offers
several advantages, including:
• Less sensitivity to loop wire characteristics.
• Less sensitivity to noise glitches on the cable.
• Less emitted noise from the wiring.
Maximum Distance to end of
line resister (EOLR)
18 AWG (0.75 mm2)
3,930 ft (1,198m)
16 AWG (1.0 mm2)
6,225 ft (1,897m)
14 AWG (1.5 mm2)
9,900 ft (3,018m)
CAUTION
Equipment Damage.
This module operates on electrical power. Fires often
cause power interruption. Discuss further safeguards
with your fire protection specialist.
Applications
The actual duty performed by the SIGA-UM and SIGA-MAB is
determined by its sub-type or “personality code.” The code is
selected for the desired application, It is assigned during
system definition and downloaded from the loop controller.
The SIGA-UM installs to a standard North American 2-gang
electrical box, making it ideal for locations where only one
module is required. Separate I/O and data loop connections
are made to each module. The SIGA-UM can be used to
connect any one of the following items:
• Two Class B or one Class A initiating device circuits.
• One Class A or B indicating appliance circuit.
• One Class A or B circuit for 2-wire smoke detectors.
• One Form C (no/nc) dry output contact relay.
Personality codes are assigned to each address. Only codes
0,1,2,3, and 4 can be mixed on any one module. For
example, personality code 1 can be assigned to the first
address (circuit A) and code 4 can be assigned to the second
address (circuit B). All other codes automatically use up both
addresses simultaneously, so they cannot be mixed.
The SIGA MAB is part of the Universal Input/Output (UIO)
family of plug-in Signature Series models. It takes advantage
of the modular flexibility and easy installation that
characterizes all UIO models. Two-module and six-module
UIO motherboards are available. These motherboards can
74-2068—1
Wire Size
NOTE: Personality Code 0: NOT CONFIGURED, the factory
default, can be applied to both circuits separately.
2
SIGA-UM AND SIGA-MAB UNIVERSAL CLASS A/B MODULES
Table 2. Circuits and Applications for Personality Codes.
Code
Class
Description
Suitable for
1
B
Normally
Open
Alarm
Latching
Assign to one or both circuits. Configures either circuit 1, 2,
or both for Class B normally-open dry contact initiating
devices. An ALARM signal is sent to the loop controller when
the input contact is closed. The condition alarm is latched at
the module.
Pull stations,
Heat
detectors
2
B
Normally
Open
Alarm
Delayed
Latching
Assign to one or both Circuits. Configures either circuit 1 or
circuit 2 or both for Class B normally-open dry contact. An
ALARM signal is sent to the loop controller when the input
contact is closed at least 16 seconds. The condition alarm is
latched at the module.
Waterflow
alarm switches
3
B
Normally
Open
Active
NonLatching
Assign to one or both circuits. Configures either circuit 1, 2
or both for Class B normally open dry contact monitoring
input. An ACTIVE signal is sent to the loop controller when
the input contact is closed. The active condition is not
latched at the module.
Fans,
dampers,
doors
4
B
Normally
Open
Active
Latching
Assign to one or both circuits. Configures either circuit 1, 2
or both for Class B normally open dry contact monitoring
input. An ACTIVE signal is sent to the loop controller when
the input contact is closed. The active condition is latched at
the module.
Supervisory
and tamper
switches
8
Control Relay
Applies to circuits 1 and 2 simultaneously. Configures
module to provide one Form C dry relay contact. Contact
rating is 2.0A at 24 Vdc; 0.5A aat 120 Vac (or 220 Vac nonUL). This personality code is only available with the SIGAUM.
Door closers,
fans, dampers
9
A
Normally
Open
Alarm
Latching
Applies to both circuits 1 and 2 simultaneously. Configures
module for Class A normally-open dry contact initiating
devices. An ALARM signal is sent to the loop controller when
the when the input contact is closed. The active condition is
latched at the module.
Pull stations,
Heat
detectors
10
A
Normally
Open
Alarm
Delayed
Latching
Applies to both circuits 1 and 2 simultaneously. Configures
module for Class A normally-open dry contact initiating
devices. An ALARM signal is sent to the loop controller when
the when the input contact is closed. The alarm condition is
latched at the module.
Waterflow
alarm switches
11
A
Normally
Open
Active
NonLatching
Applies to both circuits 1 and 2 simultaneously. Configures
module for Class A normally-open dry contact initiating
devices. An ACTIVE signal is sent to the loop controller
when the when the input contact is closed. The active
condition is active latched at the module.
Fans, Doors,
Dampers
12
A
Normally
Open
Active
Latching
Applies to both circuits 1 and 2 simultaneously. Configures
module for Class A normally-open dry contact initiating
devices. An ACTIVE signal is sent to the loop controller
when the when the input contact is closed. The active
condition is latched at the module.
Supervisory
switches,
Tamper
switches
13
B
2-Wire
Smoke
Alarm
Nonverified
2-wire smoke detectors that do not require alarm verification.
Normally-open dry contact initiating devices. Can be on the
same circuit only with personality code 13. An ALARM signal
is sent to the loop controller when the input contact is closed
or a smoke detector enters into alarm. The alarm condition is
latched at the module. The LED on only the first smoke
detector to alarm latches ON steady. Circuit B monitors
smoke power from the loop controller.
Smoke
detectors,
Pull stations,
Heat
detectors
(continued)
3
74-2068—1
SIGA-UM AND SIGA-MAB UNIVERSAL CLASS A/B MODULES
Table 2. Circuits and Applications for Personality Codes (Continued).
Code
Class
Description
14
B
2-Wire
Smoke
15
A
16
Suitable for
Applies to both circuits 1 and 2 simultaneously. Configures
module for connection of up to 1.0 mA or conventional 2-wire
smoke detectors that do require alarm verification. Normallyopen dry contact initiating devices can not be on the same
alarm circuit. An ALARM signal is sent to the loop controller
when a smoke detector enters into alarm. The alarm
condition is latched at the module. The LED only the first
smoke detector to alarm latches ON steady. Circuit B
monitors smoke power from the loop controller.
Smoke
detectors,
Pull stations,
Heat
detectors
Signal Output
Applies to both circuits 1 and 2 simultaneously. Configures
module for connection of Class A Indicating Appliance
Circuit (IAC). The maximum allowable signal power is 2A at
24 Vdc, 0.5A at 120 Vac (or 220 Vac non-UL). The maximum
allowable speaker power is 50W (25V audio) or 35W (70V
audio).
Horns,
Speakers
B
Signal Output
Applies to both circuits 1 and 2 simultaneously. Configures
module for connection of Class B Indicating Appliance
Circuit (IAC). The maximum allowable signal power is 2A at
24 Vdc, 0.5A at 120 Vac (or 220 Vac non-UL). The maximum
allowable speaker power is 50W (25V audio) or 35W (70V
audio).
Horns,
Speakers
20
A
2-Wire
Smoke
Alarm
NonVerified
Operates the same as personality code 13, except the wiring
is Class A.
Smoke
detectors,
Heat
detectors,
Pull stations
21
A
2-Wire
Smoke
Alarm
Verified
Operates the same as personality code 14, except the wiring
is Class A.
Smoke
detectors,
Heat
detectors,
Pull stations
Alarm
verified
Personality codes are assigned to each address. Only codes
1,2,3, and 4 can be mixed on any individual module. For
example, personality code 1 can be assigned to the first
address (circuit A) and code 4 can be assigned to the second
address (circuit B). All other codes automatically use up both
addresses at the same time, so they cannot be mixed.
—
The following notes refer to the wiring diagrams that follow.
Notes 1 through 6 are referenced in the diagrams with
callouts.
—
—
—
—
NOTES:
— For maximum wire resistance and distances, refer to the
System Installation Instructions.
— Maximum 14 AWG (1.5 sq mm) wire. Minimum 18 AWG
(0.75 sq mm).
— Refer to the System Installation Instructions for wiring
specifications.
— These modules do not support 2-wire smoke detectors
unless configured for personality 13, 14, 20, or 21.
74-2068—1
4
Maximum 12.5 ohms resistance per wire for Class A
configurations (for initiating devices and monitoring
circuits).
Compatible smoke detector. Refer to Personality Codes
13, 14, 20, or 21 for type and quantity.
For SIGA-CR, SIGA-UM and SIGA-MAB must be
installed in the same room as the device they control.
All wiring power limited and supervised (only for circuits
shown).
Polarity at terminals 11 and 12 shown in Supervisory
condition. Connect as shown in diagram. (Polarity
reverses on Alarm. Polarity reversal depends on the
polarity of the riser inside the alarm. Polarity does not
reverse if circuits are wired incorrectly.
SIGA-UM AND SIGA-MAB UNIVERSAL CLASS A/B MODULES
INPUT 1
INPUT 2
4
UL/ULC LISTED
47K OHMS EOL
UL/ULC LISTED
47K OHMS EOL
NOT USED
TYPICAL INITIATING DEVICE
STYLE B (CLASS B)
TB4
TB3
JP1
1
2
GREEN LED
(NORMAL)
RED LED
(ALARM/ACTIVE)
TB1
TB2
NOT USED
DATA IN (+)
DATA OUT (+)
DATA IN (–)
DATA OUT (–)
FROM SIGNATURE CONTROLLER
OR PREVIOUS DEVICE
TO NEXT DEVICE
3
C8255
Fig. 1. Class B Dual Input Module
Normally Open Alarm—Latching Class B
Normally Open Active—Non-Latching Class B
(Personality Code 1)
Assign to one or both circuits. Configures either 1, 2, or both
for Class B normally-open dry contact initiating devices such
as pull stations, heat detectors, and similar devices. An
ALARM signal is sent to the loop controller when the input
contact is closed. The alarm condition is latched at the
module.
(Personality Code 3)
Assign to one or both circuits. Configures either 1, 2, or both
for Class B normally-open dry contact initiating devices
monitoring input from fans, dampers, doors, and similar
devices. An ACTIVE signal is sent to the loop controller when
the input contact is closed. The alarm condition is not latched
at the module.
Normally Open Alarm—Delayed Latching Class B
Normally Open Active—Latching Class B
(Personality Code 2)
Assign to one or both circuits. Configures either 1, 2, or both
for Class B normally-open dry contact initiating devices such
as water flow alarm switches. An ALARM signal is sent to the
loop controller when the input contact is closed for at least 16
seconds. The alarm condition is latched at the module.
(Personality Code 4)
Assign to one or both circuits. Configures either 1, 2, or both
for Class B normally-open dry contact initiating devices
monitoring input from supervisory switches, tamper switches,
and similar devices. An ACTIVE signal is sent to the loop
controller when the input contact is closed. The alarm
condition is latched at the module.
5
74-2068—1
SIGA-UM AND SIGA-MAB UNIVERSAL CLASS A/B MODULES
4
JP1
321
NORMALLYCLOSED
NORMALLYOPEN
COMMON
NOT
NOT
USED
USED
NOT
USED
TB4
TB3
JP1
GREEN LED
(NORMAL)
RED LED
(ALARM/ACTIVE)
TB1
TB2
NOT USED
DATA IN (+)
DATA OUT (+)
DATA IN (–)
DATA OUT (–)
FROM SIGNATURE CONTROLLER
OR PREVIOUS DEVICE
TO NEXT DEVICE
3
C8256
Fig. 2. Control Relay Module.
Control Relay Dry Contact Output
(Personality Code 8)
Applies to both circuits 1 and 2 simultaneously. Configures module to provide one Form “C” dry relay contact to control door
closers, fans, dampers, and similar devices. Contact rating is 2.0A at 24 Vdc; 0.5A at 120 Vac (or 220 Vac non-UL).
4
UL/ULC LISTED
47K OHMS EOL
STYLE D (CLASS A)
5
2
TYPICAL INITIATING DEVICE
NOT USED
TB4
STYLE B (CLASS B)
TB3
JP1
1
2
GREEN LED
(NORMAL)
RED LED
(ALARM/ACTIVE)
TB1
TB2
NOT USED
DATA IN (+)
DATA OUT (+)
DATA IN (–)
DATA OUT (–)
FROM SIGNATURE CONTROLLER
OR PREVIOUS DEVICE
TO NEXT DEVICE
3
C8257
Fig. 3. Class A Single Output Module.
74-2068—1
6
SIGA-UM AND SIGA-MAB UNIVERSAL CLASS A/B MODULES
Normally Open Alarm—Latching Class A
Normally Open Active—Non-Latching Class A
(Personality Code 9)
One circuit (two addresses used). Configures module for
Class A normally-open dry contact initiating devices such as
pull stations, heat sensors, and similar devices. An ALARM
signal is sent to the loop controller when the input contact is
closed. The alarm condition is latched at the module.
(Personality Code 11)
Configures module for Class A normally-open dry contact
initiating devices such as fans, dampers, doors, and similar
devices. An ACTIVE signal is sent to the loop controller when
the input contact is closed. The active condition is not latched
at the module.
Normally Open Alarm—Latching Class A
Normally Open Active—Latching Class A
(Personality Code 10)
Configures module for Class A normally-open dry contact
initiating devices such as water flow alarm switches. An
ALARM signal is sent to the loop controller when the input
contact is closed for at least 16 seconds. The alarm condition
is latched at the module.
(Personality Code 12)
Configures module for Class A normally-open dry contact
initiating devices such as supervisory switches, tamper
switches, and similar devices. An ACTIVE signal is sent to the
loop controller when the input contact is closed. The active
condition is latched at the module.
1
5
2
2
STYLE B (CLASS B)
+
+
IN OUT
—
STYLE D (CLASS A)
TO LAST DEVICE
UL/ULC LISTED
47K OHMS EOL
6
NOT USED
UL/ULC 22K OHMS EOL
USED FOR CLASS A ONLY
(CODE 20, 21)
TB4
TB3
JP1
SMOKE DETECTOR
POWER (+24 Vdc)
FROM SIGNATURE
CONTROLLER
OR PREVIOUS DEVICE
BACK TO
TERMINALS 14, 13
CODE 20, 21 ONLY
TYPICAL INITIATING DEVICE
(NO INITIATING DEVICES
ALLOWED WITH PERSONALITY
CODE 14 AND 21)
GREEN LED
(NORMAL)
RED LED
(ALARM/ACTIVE)
TB1
TB2
NOT USED
DATA IN (+)
DATA OUT (+)
DATA IN (–)
DATA OUT (–)
FROM SIGNATURE CONTROLLER
OR PREVIOUS DEVICE
TO NEXT DEVICE
C8258A
3
Fig. 4. Two-wire smoke detectors—Class A or Class B.
7
74-2068—1
SIGA-UM AND SIGA-MAB UNIVERSAL CLASS A/B MODULES
2-Wire smoke (Class A)—Non-verified
2-Wire smoke (Class A)—Alarm Verified
(Personality Code 20)
(Personality Code 21)
2-Wire smoke (Class A)—Non-verified
2-Wire smoke (Class A)—Non-Verified
(Personality Code 13)
There is only one circuit in this configuration, but two
addresses are used. The first address is the IDC. The second
address is for monitoring smoke detector power. This
configures modules for connection of up to 1.0 mA of
conventional 2-wire smoke detectors that do not require
alarm verification. These include normally-open dry contact
initiating devices such as pull stations, heat detectors, and
similar devices. These devices can be on the same circuit
only with personality code 13. An ALARM signal is sent to the
loop controller when the input contact is closed or a smoke
detector enters alarm. The alarm condition is latched at the
module. The LED on the first smoke detector to alarm latches
ON steady. Compatible smoke sensors include up to twenty
6250/6264 series or up to fifteen 6266/6269/6270 series. This
setting is also compatible with up to 10 model 1451 or 2451
sensors.
(Personality Code 14)
There is only one circuit in this configuration, but two
addresses are used. The first address is the IDC. The second
address is for monitoring smoke detector power. This
configures modules for connection of up to 1.0 mA of
conventional 2-wire smoke detectors that do require alarm
verification. These include normally-open dry contact initiating
devices such as pull stations, heat detectors, and similar
devices. These devices can be on the same circuit only with
personality code 13. An ALARM signal is sent to the loop
controller when the input contact is closed or a smoke
detector enters alarm. The alarm condition is latched at the
module. The LED on the first smoke detector to alarm latches
ON steady. Compatible smoke sensors include up to twenty
6250/6264 series or up to fifteen 6266/6269/6270 series. This
setting is also compatible with up to 10 model 1451 or 2451
sensors.
+
–
4
1
2
STYLE Z
(CLASS A)
NOT USED
+
–
TB4
+
–
+
–
+
–
+
–
UL/ULC LISTED
47K OHMS EOL
TYPICAL
INDICATING
APPLIANCE
TB3
JP1
WIRED TO
TERMINALS
13 AND 14
FOR STYLE Z
(CLASS A )
OR
STYLE Y
WIRED TO (CLASS B)
TERMINALS
11, 12
STYLE Y
(CLASS B) 2
2
UL/ULC LISTED
47K EOL
TYPICAL
INDICATING
APPLIANCE
GREEN LED
(NORMAL)
RED LED
(ALARM/ACTIVE)
TB1
TB2
FROM XLS
CONTROL
PANEL
RISER (+)
TO NEXT DEVICE OR EOL
RESISTOR SUPPLIED WITH
UL/ULC LISTED CONTROL PANEL
DATA OUT (–)
TO NEXT DEVICE
DATA OUT (+)
RISER (–)
RISER IN (+)
RISER IN (–)
FROM SIGNATURE
CONTROLLER
OR PREVIOUS DEVICE
+
–
DATA IN (+)
DATA IN (–)
3
1 FOR MAXIMUM WIRE RESISTANCE AND MAXIMUM WIRE DISTANCES,
REFER TO INSTALLATION INSTRUCTIONS.
4
THIS MODULE WILL NOT SUPPORT 2-WIRE SMOKE DETECTORS
UNLESS CONFIGURED FOR PERSONALITY 13, 14, 20 OR 21.
2 MAXIMUM NO. 14 AWG (1.5mm2) WIRE. MINIMUM NO. 18 AWG (0.75mm2).
5
MAXIMUM 12.5 OHMS RESISTANCE PER WIRE FOR CLASS A
CONFIGURATIONS.
3 REFER TO SIGNATURE LOOP CONTROLLER INSTALLATION SHEET
FOR WIRING SPECIFICATIONS.
C8259A
Fig. 5. Single output module.
74-2068—1
8
SIGA-UM AND SIGA-MAB UNIVERSAL CLASS A/B MODULES
Signal Output Class A
Signal Output Class B
(Personality Code 15)
There is only one circuit in this configuration, but it uses two
addresses. The first address is the IDC. The second address
is for monitoring smoke detector power. This code configures
the module for connection of Class A Indicating Appliance
Circuits (IAC). This is normally used to control bells,
speakers, and similar devices. The maximum allowable signal
power is 2A at 24 Vdc, 0.5A at 120 Vac (or 220 Vac non-UL).
The maximum allowable speaker power is 50W (25V audio)
or 35W (70V audio).
(Personality Code 16)
There is only one circuit in this configuration, but it uses two
addresses. The first address is the IDC. The second address
is for monitoring smoke detector power. This code configures
the module for connection of Class B Indicating Appliance
Circuits (IAC). This is normally used to control bells,
speakers, and similar devices. The maximum allowable signal
power is 2A at 24 Vdc, 0.5A at 120 Vac (or 220 Vac non-UL).
The maximum allowable signal power is 2A at 24 Vdc, 0.5A at
120 Vac (or 220 Vac non-UL). The maximum allowable
speaker power is 50W (25V audio) or 35W (70V audio).
9
74-2068—1
SIGA-UM AND SIGA-MAB UNIVERSAL CLASS A/B MODULES
CLASS A OR B 2-WIRE SMOKE DETECTOR AND CONTACT INPUT MODULE
(PERSONALITY CODE 13, 14, 20, OR 21)
TYPICAL N.O. INSTALLING DEVICE
(PERSONALLITY CODES 13 AND 20 ONLY)
+
UL/ULC
LISTED
15K OHM
EQL
–
–
1
S+
S+
+
2
GREEN LED (NORMAL)
RED LED (ACTIVE)
CLASS B
CIRCUITS ONLY
7
CLASS A CIRCUITS ONLY
SIGA-MAB
1 2 3 4
INSTALL
JP1 AND JP2
SIGA-UIO (R) SERVICE MOTHERBOARD
RISER 1 OUT
+ 24 Vdc SMOKE DETECTOR POWER
4
3
2
5
1
+ 24 Vdc SMOKE DETECTOR POWER
RISER 1 IN FROM SIGNATURE LOOP CONTROLLER
OR PREVIOUS DEVICE
+
–
DATA IN
4
3
2
1
SIGNATURE
DATA
CIRCUIT
DATA OUT
+
–
TB14
TB7
NO CONNECTIONS REQUIRED FOR
SIGA-MAB USING PERSONALITY
CODES 13, 14, 20, OR 21.
4
3
2
1
TB15
3
24VDC SMOKE
DETECTOR POWER
6
+
1 2 3 4
+
INSTALL THE JUMPERS BETWEEN ADJACENT
SIGNA-MABS WITH PERSONALITY
CODES 13, 14, 20, OR 21.
24 Vdc SMOKE DETECTOR POWER FROM SIGNATURE
LOOP CONTROLLER OR PREVIOUS DEVICE
CLASS A OR B DRY CONTACT INPUT MODULE
(PERSONALITY CODE 1,2,3,4,9,10,11 OR 12)
PERSONALITY CODES: 1, 2, 3, OR 4
1
UL/ULC
LISTED
15K OHM
EQL
2
7
PERSONALITY CODES: 9, 10, 11, OR 12
1
2
GREEN LED (NORMAL)
RED LED (ACTIVE)
7
REMOVE
MODULE
JUMPERS
DATA IN
SIGA-UIO (R) SERVICE MOTHERBOARD
+
–
4
3
2
1
TB14
4
3
2
1
SIGNATURE
DATA
CIRCUIT
DATA OUT
SIGA-MAB
1 2 3 4
+
–
TB7
4
3
2
1
TB15
3
NO CONNECTIONS REQUIRED FOR
SIGA-MAB USING PERSONALITY
CODES 1, 2, 3, 4, 9, 10, 11, OR 12.
NO CONNECTIONS REQUIRED FOR
SIGA-MAB USING PERSONALITY
CODES 1, 2, 3, 4, 9, 10, 11, OR 12.
REMOVE MOTHERBOARD JUMPERS.
1 2 3 4
1 FOR MAXIMUM RESISTANCE, SEE THE APPROPRIATE TECHNICAL
REFERENCE MANUAL. MAXIMUM CIRCUIT CAPACITANCE IS 0.1 MF.
7 SUPERVISED AND POWER-LIMITED.
8 SUPERVISED AND POWER-LIMITED WHEN CONNECTED TO A
POWER-LIMITED SOURCE. IF THE SOURCE IS NONPOWER-LIMITED,
MAINTAIN A SPACE OF 1/4 INCH FROM POWER-LIMITED WIRING
OR USE FPL, FPLP, FPLR, OR AN EQUIVALENT IN ACCORDANCE
WITH THE NATIONAL ELECTRICAL CODE.
2 MAXIMUM NO. 12 AWG (2.5 mm2) WIRE; MINIMUM NO. 18 AWG (0.75mm2)
3 REFER TO SIGATURE CONTROLLER INSTALLATION SHEET FOR
WIRING SPECIFICATIONS.
4 MAXIMUM 10 Vdc @ 350mA
9 THE INPUT FOR THIS RISER IS COMMON TO ALL MODULES.
5 THE SIGA-UIO6R DOES NOT COME WITH TB14.
10 MAXIMUM ALARM CURRENT IS 17 mA. OPERATING VOLTAGE
RANGE IS 16.0 TO 24.0 Vdc.
M16287
6 THE SIGA-UIO6 DOES NOT COME WITH TB8 THROUGH TB13.
74-2068—1
5
10
SIGA-UM AND SIGA-MAB UNIVERSAL CLASS A/B MODULES
MOTIFICATION OUTPUT MODULE
(PERSONALITY CODE 15 OR 16)
PERSONALITY
CODE 15
TYPICAL SPEAKER CIRCUIT
TYPICAL NOTIFICATION APPLIANCE CIRCUIT
PERSONALITY
CODE 16
BI-POLAR TRANSIENT
PROTECTOR (P/N 235196P)
1
2
4
+
–
+
–
+
–
+
–
UL/ULC
LISTED
15K OHM
EQL
CLASS B
CIRCUITS ONLY
SIGA-MAB
1 2 3 4
RED LED (ACTIVE)
SIGA-UIO (R) SERVICE MOTHERBOARD
+
–
+
–
–
+
–
+
4
3
2
1
4
3
2
1
SIGNATURE
DATA
CIRCUIT
DATA OUT
+
–
7
GREEN LED
(NORMAL)
DATA IN
+
–
RISER 1 OUT
RISER 1 IN
TB14
8
9
TB7
9
4
3
2
1
TB15
3
REMOVE
MODULE
JUMPERS
NO CONNECTIONS REQUIRED FOR
SIGA-MAB USING PERSONALITY
CODES 15 AND 16.
1 2 3 4
6
RISER 1 IN
7
+
–
–
+
RISER 1 OUT
1
FOR MAXIMUM RESISTANCE, SEE THE APPROPRIATE TECHNICAL
REFERENCE MANUAL. MAXIMUM CIRCUIT CAPACITANCE IS 0.1 MF.
2
MAXIMUM NO. 12 AWG (2.5 mm2) WIRE; MINIMUM NO. 18 AWG (0.75mm2)
3
REFER TO SIGATURE CONTROLLER INSTALLATION SHEET FOR
WIRING SPECIFICATIONS.
4
MAXIMUM 10 Vdc @ 350mA
9 THE INPUT FOR THIS RISER IS COMMON TO ALL MODULES.
5
THE SIGA-UIO6R DOES NOT COME WITH TB14.
6
THE SIGA-UIO6 DOES NOT COME WITH TB8 THROUGH TB13.
10 MAXIMUM ALARM CURRENT IS 17 mA. OPERATING VOLTAGE
RANGE IS 16.0 TO 24.0 Vdc.
M16288
7 SUPERVISED AND POWER-LIMITED.
8 SUPERVISED AND POWER-LIMITED WHEN CONNECTED TO A
POWER-LIMITED SOURCE. IF THE SOURCE IS NONPOWER-LIMITED,
MAINTAIN A SPACE OF 1/4 INCH FROM POWER-LIMITED WIRING
OR USE FPL, FPLP, FPLR, OR AN EQUIVALENT IN ACCORDANCE
WITH THE NATIONAL ELECTRICAL CODE.
SPECIFICATIONS
Operating Voltage:
15.2 Vdc to 19.95 Vdc (19 Vdc nominal).
Type Code:
53 (Factory set).
15 sub-types (personality codes) available.
LED Operation:
On-board green LED flashes when polled.
On-board red LED flashes when in alarm state, active state,
or both.
Both LED glow steady when in alarm (stand alone).
The LED are visible only when the front plate is removed.
Personality codes are assigned to the SIGA-UM and SIGAMAB by the installer. Only codes 1,2,3, and 4 can be mixed
on any one module. For example, personality code 1 can be
assigned to the first address (circuit A) and personality code 4
can be assigned to the second address (circuit B). All other
personality codes use up both addresses simultaneously, so
they cannot be mixed.
Compatibility:
XLS1000 and XLS100 loop controllers.
Address Requirements:
Two module addresses.
Operating Environment:
Temperature: 32°F to 120°F (0°C to 60°C).
Humidity: 0% to 93% rh noncondensing.
Storage Temperature: –4°F to 140°F (-20°C to 60°C).
11
74-2068—1
SIGA-UM AND SIGA-MAB UNIVERSAL CLASS A/B MODULES
Table 3. Operating Current.
Mode of Operation
Personality Code
Standby Current
Alarm Current
EOL Resister Value
Class B IDC
1,2,3,4
396 µA
680 µA
47k ohms
Form C dry contact relay1
8
100 µA
100 µA
Not required.
Class A IDC
9, 10, 11, 12
223 µA
365 µA
47k ohms
2-wire smoke detectors and IDC
13, 14, 20, 21
2 mA
See below
22k ohms (Class B)
15k ohms (Class A)
First detector into alarm
—
—
17 mA
—
Subsequent detectors into alarm
—
—
100 µA
—
Class A or Class B IAC1
15, 16
223 µA
365 µA
47k ohms (Class B)
1Contacts rated at 2A at 24 Vdc, 0.5A at 120 Vac (or 220 Vac non-UL), 50W at 25V audio and 35W at 70V audio.
Mounting SIGA-MAB:
SIGA-UIO2R/6R/6.
Shipping Weight:
SIGA-UM: 0.5 lb (0.23 kg).
SIGA-MAB: .18 lb (.08 kg).
Carton Dimensions:
5-1/3 in. (135 mm) wide by 2-1/2 in (64 mm) high by 5-1/3 in.
(135 mm) deep.
Construction and Finish:
Front Plate: High-impact white engineering polymer 2-gang
front plate.
Label: FIRE ALARM MODULE.
NOTE: The module includes a self-adhesive label in French.
All electronics utilize surface mount technology (SMT) for
smaller size and greater immunity to RF noise. A conformal
coating resists humidity and corrosion.
Mounting SIGA-UM:
North America: 2-1/2 in. (64 mm) deep 2-gang boxes and
1-1/2 in (38 mm) deep 4 in. square boxes.
Europe: 100 mm square boxes (purchased locally).
Terminals: Suitable for 14 AWG to 18 AWG (1.5 sq mm to
0.75 sq mm) wire sizes.
SIGA-UM Accessories:
Option Surface Mount Box:
Red 2-gang box (part no. 27193-21).
White 2-gang box (part no. 27143-26).
Dimensions: 4-13/16 in. (122 mm) wide by 4-3/4 in. (121 mm)
high by 2-1/2 in. (64 mm) deep.
Weight: 2 lb (0.8 kg).
SIGA-MAB Accessories:
SIGA-UIO2R: Universal Input/Output Module board with riser
inputs. 2 module positions.
SIGA-UIO6R: Universal Input/Output Module board with riser
inputs. 6 module positions.
SIGA-UIO6: Universal Input/Output Module board. 6 module
positions.
Standards:
ISO 9001.
Approvals:
UL, ULC.
Home and Building Control
Honeywell Inc.
Honeywell Plaza
P.O. Box 524
Minneapolis MN 55408-0524
Home and Building Control
Honeywell Limited-Honeywell Limitée
155 Gordon Baker Road
North York, Ontario
M2H 3N7
Honeywell Latin American Region
480 Sawgrass Corporate Parkway
Suite 200
Sunrise FL 33325
Honeywell Europe S.A.
3 Avenue du Bourget
1140 Brussels
Belgium
74-2068—1 D.A. Rev. 3-99
Printed in U.S.A. on recycled
paper containing at least 10%
post-consumer paper12
fibers.
Honeywell Asia Pacific Inc.
Room 3213-3225
Sun Hung Kai Centre
No. 30 Harbour Road
Wanchai
Hong Kong
www.honeywell.com
Download