s IEC 62271 standards for medium-voltage switchgear and controlgear Precise classifications make planning easier Author Ansgar Müller Siemens AG PTD M SP Mozartstrasse 31c 91052 Erlangen Tel. Fax Mail +49 9131 7-33619 +49 9131 8835-33619 ansgar.mueller@siemens.com IEC 62271 standards for medium-voltage switchgear and controlgear IEC 62271 standards for medium-voltage switchgear and controlgear – Precise classifications make planning easier Contents 1 Group of standards for high-voltage switchgear and controlgear 2 Classification of switchgear and controlgear 2.1 2.2 2.3 2.4 Switches Circuit-breakers Disconnectors Grounding switches IEC 60265-1 IEC 62271-100 IEC 62271-102 IEC 62271-102 3 Metal-enclosed switchgear and controlgear IEC 62271-200 3.1 Reasons for and objectives of revising the old standard 3.2 Classifications 3.3 Compartments 3.3.1 Partition class 3.3.2 Insulating medium 3.3.3 Accessibility of compartments and access control 3.3.4 Loss of service continuity category LSC 3.3.5 Examples 3.4 3.4.1 3.4.2 3.4.3 3.4.4 3.4.5 Internal arc classification IAC Test conditions Ignition and energy flow direction Testing arrangement Assessment criteria IAC designations 3.5 3.5.1 3.5.2 3.5.3 Gaps in the standards LSC category Cable testing PD measurement 4 Outlook 2 IEC 62271 standards for medium-voltage switchgear and controlgear 1 Group of standards for high-voltage switchgear and controlgear A few years ago, IEC decided to combine the standards of committees 17A and 17C for high-voltage switchgear and controlgear with rated values in excess of 1kV in one group with standardized numbering. This makes it easier for readers to find a standard. The new numbers are not changed on a key date, but are only applied after revision of a standard, and so the changeover period will extend until approximately the year 2010. IEC 62271 HV Switchgear and controlgear standards responsible IEC committee Parts 1 – 99 Generic standards SC 17A / 17C Parts 100 – 199 Switching devices SC 17A Parts 200 – 299 Switchgear installations SC 17C Parts 300 – 399 Guidelines, specifications SC 17A / 17C Fig. 1: New numbering structure In relation to medium voltage, Table 1 shows a selection of the most important standards in the new IEC 62271 group. The old IEC numbers did not indicate whether there were any relationships between standards. By contrast, some national standardisation organisations have been combining switchgear and controlgear standards for more than two decades now; for example in the German VDE 0670 group. IEC 62271 Title (short form) Old number IEC Part 1 Common specifications 60694 2007 Part 100 Circuit-breakers 60056 2001 Part 102 Disconnectors and earthing switches 60129 2001 Part 103 Switches 60265-1 Part 105 Switch-fuse combinations 60420 Part 106 Contactors 60470 Part 200 Metal-enclosed switchgear 60298 2003 Part 201 Insulation-enclosed switchgear 60466 2006 Part 202 Compact HV/LV stations 31330 2006 Table 1: Transition 2002 Numbering of standards for switchgear and controlgear in the medium voltage range (> 1 kV up to and including 52 kV) 3 IEC 62271 standards for medium-voltage switchgear and controlgear 2 Classification of switchgear and controlgear Besides specification of the usual rated values for switchgear and controlgear, it has become commonplace to specify a class that refers to a unit's useful life. Circuit-breakers are an exception. In their case, an additional class designates their response to breaking of capacitive currents. Although the term “useful life” would be more appropriate to an object, the expression "lifetime" has firmly established itself in the standards and so this term is also used below. In 1998, the switches standard was the first to introduce the lifetime classification. The lifetime is understood to be a minimum number of switching cycles that is possible without noteworthy maintenance activities (e.g. greasing, topping up gas or cleaning exterior surfaces). Classification encompasses the class "M" for the number of mechanical switching cycles and the class "E" for the electrical switching cycles. In the meantime, other equipment standards have also started defining such classifications. Unfortunately, neither the ways in which the classes are enumerated nor the staggered numbers of switching cycles given in the individual standards for switches are uniform and careful attention has to be paid. 2.1 Switches to IEC 60265-1 The standard defines classes only for the so-called multi-purpose switches, although, besides these, there are also "special purpose switches" and "limited purpose switches"1. As the name suggests, multi-purpose switches must be capable of switching different kinds of operating currents, for example load currents, ring currents, currents of unloaded transformers, charging currents of unloaded cables and overhead lines, and also of making short-circuit currents. Multi-purpose switches intended for use in networks with an isolated star point or with earth fault compensation must also be capable of switching under earth fault conditions. Their diversity is reflected in the fairly exact designations for the E classes. Class M Description M1 1000 Mechanical endurance M2 5000 Increased mechanical endurance E1 10 x I1 10 x I2a 2 x Ima E2 30 x I1 20 x I2a 3 x Ima E E3 Table 2: 1 Switching cycles 100 x I1 20 x I2a 5 x Ima 20 x 0.05 ⋅ I1 10 x I4a 10 x 0.2 to 0.4 ⋅ I4a 10 x I4b I1 I2a I4a I4b I6a I6b active load-breaking current closed-loop breaking current cable-charging breaking current line-charging breaking current earth fault breaking current cable- and line-charging breaking current under earth fault conditions Ima Short-circuit making current 10 x I6a 10 x I6b Classes for multi-purpose switches Limited purpose switches need only master a selection of a multi-purpose switch's duties. Special purpose switches are intended for switching tasks such as those of single capacitor banks, parallel switching of capacitor banks, ring circuits formed by parallel-connected transformers or motors (in the normal or braked state). 4 IEC 62271 standards for medium-voltage switchgear and controlgear 2.2 Circuit-breakers to IEC 62271-100 While the numbers of mechanical switching cycles of the M classes are expressly mentioned, the circuit-breaker standard does not define the electrical endurance of the E classes with specific numbers of switching cycles, but unfortunately only vaguely with a verbal description. The type test switching sequences of the short-circuit type tests provide some orientation as to what is to be understood by "normal electrical endurance" and "extended electrical endurance". The numbers of making and breaking operations are specified in the grayhighlighted boxes in the table. It must also be said that modern vacuum circuit-breakers are generally capable of making and breaking the rated normal current with the number of mechanical switching cycles. Class M Description M1 2,000 switching cycles Normal mechanical endurance M2 10,000 switching cycles Extended mechanical endurance, low maintenance E1 2 x C and 3 x O with 10%, 30%, 60% and 100% Isc Normal electrical endurance (circuit-breaker not covered by E2) 2 x C and 3 x O with 10%, 30%, 60% and 100% Isc Without ARE 2 operation E E2 26 x C 130 x O 10% Isc 26 x C 130 x O 30% Isc 4xC 8 x O 60% Isc 4xC 6 x O 100% Isc With ARE 2 operation Extended electrical endurance without maintenance of the arcing chamber C = closing, O = opening; Isc = rated short-circuit breaking current Table 3: Circuit-breaker classes Above and beyond the lifetime data, the standard also describes capacitive switching behavior by means of a class C, which summarizes the characteristics of three switching tasks, namely the switching of • Overhead lines • Cables • Capacitors (single and connected in parallel) Class Description C1 Low restriking probability during breaking of capacitive currents C2 Very low restriking probability during breaking of capacitive currents C Table 4: 2 Circuit-breaker classes in relation to capacitive switching behavior ARE = automatic reclosing 5 IEC 62271 standards for medium-voltage switchgear and controlgear Only at first glance does the definition of restriking probability as "low" and "very low" appear imprecise. On the contrary, it is covered by an extremely complex type test. Two test switching sequences have to be passed for each of the three test circuits (overhead line, cable and capacitor), and the switching sequences and testing severity differ for the classes C1 and C2. In the best and simplest case, during three-phase tests this signifies C1: 144 breaking operations without restriking in accordance with conditions for class C1 C2: 200 breaking operations without restriking in accordance with conditions for class C2 However, this by no means reflects all definitions. The reason is that the occurrence of restriking depends on marginal conditions (for example the condition of the switching contacts, the load on the contacts due to previous switching operations, and the arcing time during breaking) and, like many things in high-voltage physics, restriking is also a statistical phenomenon. It would be unrealistic to expect a circuit-breaker that is completely and utterly devoid of restriking. This is why restriking is allowed during the test series if subsequent repetition of the test switching sequence concerned occurs without restriking. Repetition may then call for about one hundred additional switching operations. This applies to three-phase circuit-breaker tests; single-phase tests may call for more than five hundred switching operations (with repetition). If a circuit-breaker does not pass the test for the desired class C2, it can by reclassified in accordance with certain criteria as belonging to class C1. There is no doubt that capacitive switching capacity is one of the indispensable characteristics of a circuit-breaker in the network. In medium-voltage networks, according to operating experience up to now, circuit-breakers have fully conformed to the demands. This is why the question must be raised as to whether the intensified type testing procedure in the standard is not too complex. A few hundred switching operations, in different test circuits and with a large number of different parameter settings, take up a considerable amount of time and therefore cost considerable amounts of money. Is the cost-benefit ratio still right? Proponents of complex test procedures still get their money's worth, though. 6 IEC 62271 standards for medium-voltage switchgear and controlgear 2.3 Disconnectors to IEC 62271-102 Disconnectors do not have any switching capacity3, and so classes have only been defined for the number of mechanical switching cycles. Class M Switching cycles M0 1,000 M1 2,000 M2 10,000 Table 5: 2.4 Description For general requirements Extended mechanical endurance Disconnector classes Earthing switches to IEC 62271-102 In the case of earthing switches, the classes designate their short-circuit making capacity (earthing to an applied voltage). E0 corresponds to a normal earthing switch and switches belonging to classes E1 and E2 are also referred to as "make-proof earthing switches". Class E Switching cycles E0 0 x Ima E1 2 x Ima E2 5 x Ima Table 6: Description No short-circuit making capacity Short-circuit making capacity For general requirements Reduced need for maintenance Classes for earthing switches The standard does not define how often an earthing switch can be actuated mechanically. There are no M classes for these switches. 3 Disconnectors up to 52 kV are only allowed to switch negligible currents up to 500 mA (e.g. voltage transformers) or higher currents only if the voltage difference is insignificant (e.g. when changing busbars with the bus coupling activated). 7 IEC 62271 standards for medium-voltage switchgear and controlgear 3 Metal-enclosed switchgear and controlgear The new IEC 62271-200 standard superseded its predecessor IEC 60298 on November 1, 2003. CENELEC ratified the IEC standard as the European standard EN 62271-200 on February 1, 2004. This date crucially influences the three-year transition period. Accordingly, the "old" national standards corresponding to EN 60298 can still be used up to February 1, 2007. 3.1 Reasons for and objectives of revising the old standard Medium-voltage switchgear and controlgear belong to the long-term capital investment goods of the electricity supply company, and have useful lives extending over decades. This is reflected in the standards and their revision cycles, which are oriented to the long term. The predecessor standard IEC 60298 appeared in 1990 and an addition was made to its subject matter in 1994, followed by a formal corrigendum in 19954. By the time of publication of its now valid successor, the thirteen-year-old standard had reached an age when an update had become absolutely essential. Following such a long time, the needs of the market and the state of the art, both of which ought to be considered in a standard, had evolved considerably. So, there were enough reasons for revising it. • In terms of its definitions and requirements, the previous standard was recognizably oriented to the design conditions of "removable" systems with switching devices on a truck or a withdrawable part. Modern fixed mounting or gas-insulated systems (GIS) were under-represented. • Acording to their design, switchgear and controlgear were subdivided into three partition types (Fig. 2): metal-clad, compartmented and cubicle. This subdivision, which was not quite consistently defined, now only insufficiently described the attributes of current switchgear and controlgear types. Firstly, the boundary between metal-clad and compartmented was blurred because insulator shutters were allowed in the case of metal-clad switchgear and controlgear. Secondly, so many types of construction had now come into being that could be classified as "cubicle" that this designation could no longer be used to describe clearly defined attributes. And, thirdly, there is now a whole range of systems on the market that hardly fits consistently into the patterns any more. Moreover, classification according to the type of compartmentalisation could be misunderstood as an order of precedence in terms of safety and reliability that does not reflect actual conditions. • Not least, there were also formal and editorial reasons for the update, e.g. the need for adaptation to IEC 606945, the "generic standard" for all high-voltage switchgear and controlgear above 1 kV. 4 IEC 60298:1990 +A1:1994 + Corrigendum:1995 - A.C. metal-enclosed switchgear and controlgear for rated voltages above 1 kV and up to and including 52 kV VDE 0670-6, Mai 1998 + Ber.1 März 1999 + Ber.2 Sept. 2001, Metallgekapselte WechselstromSchaltanlagen für Bemessungsspannungen über 1 kV bis einschließlich 52 kV 5 IEC 60694 Common specifications for high-voltage switchgear and controlgear standards VDE 0670-1000 Gemeinsame Bestimmungen fuer Hochspannungs-Schaltgeräte-Normen 8 IEC 62271 standards for medium-voltage switchgear and controlgear Metal enclosure – Designs acc. to IEC 60298 Function Enclosure protects against • external influences • contact and shock • internal arc faults (option) Metal-clad • Metal partitions • Metal or insulating shutters • Compartments for busbar, „main switching device“, cable Compartmentalisation provides safe access to one or more open compartments while the adjacent compartments and functional units can remain live Compartmented („plastic-clad“) • as „metal-clad, but partitions of non-metal Cubicle • all other designs User‘s benefit Safety Service continuity Maintainability Fig. 2: Classification in the previous IEC 60298 standard according to design features Standards are primarily a contractual basis for manufacturers and operators and this is why they must reflect market needs. The market has undergone considerable transformation in the past decade. Due to the liberalization of electricity markets and cost pressure in all sectors of the economy, the requirements for switchgear and controlgear have also changed. • There was a wish for a type of classification that would be oriented to safety, availability and maintainability, and thus to the "functionality" that stands behind the type of construction. • Gas-insulated switchgear and controlgear and other types of construction with fixedmounted switching devices have accounted for a large proportion of new installations and, at least in some countries, have driven back the share of "removable" systems. • Internal arc testing has become an attribute that has almost established itself worldwide and which ought to be given more appreciation. A (still optional) genuine test with defined test conditions and a "passed" or "failed" statement should take the place of a mere "assessment of the effects". • The standard should be open to future developments. For example, nowadays many functions that were once mechanical are now performed electrically or by software. Specifications stipulating mechanical designs should be dispensed with. 3.2 Classifications in accordance with IEC 62271-200 To place the functionality of a switchgear and controlgear in the focus of classification, it was only necessary to fall back on the functional attributes (on the right in Fig. 2) that already existed in the previous structural subdivision of switchgear and controlgear, namely safety, operational availability and maintainability. The enclosure and compartmentalisation ensure protection against physical contact and foreign matter. In an extreme case, the enclosure additionally protects persons outside the system against the effects of an arcing fault. The compartmentalisation also contributes to safety by protecting persons working inside an open system against contact with live or other dangerous parts. Defined arcing fault protection inside the system is not provided, however. Breaking down switchgear and controlgear into compartments also makes it possible to work in a functional unit and to at least maintain operation of the neighbouring units. Parts of the open functional unit may even possibly remain live. This reduces the scope of switching over 9 IEC 62271 standards for medium-voltage switchgear and controlgear and work activities. Ultimately, the number and design of the compartments define how complex access to the parts of the switchgear and controlgear is without interrupting operation in total, this being a measure of its operational availability and maintenancefriendliness. Metal enclosure – Designs acc. to Part 200 Compartmentalisation features Partition class • PM (metal) • PI (insulating material) Insulation medium • Ambient air • Fluid (SF6, oil) Non-accessible compartment Accessible compartment Access control • interlock-controlled • procedure-based • tool-based Loss of service continuity • LSC 1 • LSC 2A • LSC 2B Internal Arc Classification Option Fig. 3: New classification structure in accordance with IEC 62271-200 3.3 Compartments 3.3.1 Partition class While work is being done in open switchgear and controlgear, the partitions and shutters to the next compartment or to the neighboring functional unit protect against high voltage. The partition class specifies whether partitioning from high high-voltage parts is purely metallic or whether it contains insulators. Although both of them achieve the same degree of protection against electric shock, metal partitioning also screens off the electric field of the primary part. The PM class stands for "Partition metallic" with earthed, continuously metallic partitions and metallic shutters between the main circuit and the open compartment. The PI class stands for "Partition of insulating material" whenever at least one part of the partitioning is non-metallic, i.e. one or more partition(s) or shutter(s) is or are made of insulating material. Note: partitioning made of insulating material is subjected to complex tests and inspections to verify dielectric strength. 10 IEC 62271 standards for medium-voltage switchgear and controlgear Partition classes Class PM Characteristics • Metallic partitions and shutters between opened compartment and live parts ( Partitions metallic ) • Dielectric conditions correspond to metal enclosure Class PI • Non-metallic partitions and shutters between ( Partitions non-metallic; i = insulating material ) opened compartment and live parts Fig. 4: Dielectric classification of partitioning The partition class clearly designates the actual dielectric conditions around the work location. Previously, this was not the case because IEC 60298 also allowed insulating material shutters for metal partitioning. 3.3.2 Insulating medium Every compartment that does not use ambient air for insulation is considered to be a fluidfilled compartment. Fluid is subdivided into • Gas • Liquid The term "fluid" describes liquids and gases neutrally. Apart from a few exceptions, in practice the word fluid stands for oil or SF6. The standard, however, understands "gas" to be any gas or gas mixture, but with the exception of ambient air. All definitions, terms and formulations in the standard have been adapted according to this generalization in terms of fluid. For example, the rating plate no longer speaks of the filling pressure (instead, in the case of oil it would be a level), but generally of the filling level. 3.3.3 Accessibility of compartments and access control There are four kinds of compartments, initially generally distinguished according to whether they are accessible or not. Accessible compartments are subdivided according to how access is controlled. • Interlock-controlled accessible compartment The interlocks enable access only if all high-voltage parts are deenergized and earthed. According to the manufacturer's specifications, opening has been conceived for normal operation or for maintenance, e.g. to replace a fuse. By contrast, assembly, expansion and repair are not deemed normal maintenance. • Procedure-based accessible compartment Access is controlled via "work procedures" in combination with locking devices (padlock). Organizational measures must ensure that access is possible only when highvoltage parts are deenergized and earthed. As before, opening was conceived for normal operation or maintenance and not for assembly, expansion or repairs. 11 IEC 62271 standards for medium-voltage switchgear and controlgear • Tool-based accessible compartment Such a compartment can only be opened using a tool, but not for normal operation and maintenance. Defined work procedures (work instructions) are necessary as a safety measure, but are not specified any further. • Non-accessible compartment A non-accessible compartment (typical of gas-insulated systems) may not be opened by the operator because opening can destroy the space or render it useless. An appropriate notice for the operator must be placed on or in the proximity of the compartment. Compartment Interlock-controlled accessible Procedure-based accessible Characteristic of access • Access enabled if HV • Access for normal parts are dead and earthed operation and maintenance • Access controlled by e.g. to replace fuses locking and work instructions • Not to be opened for Tool-based accessible • Tools for opening, normal operation / maintenance specific procedure for access (instructions) e.g. for cable testing • Access not possible / not intended for user; Non-accessible opening may destroy compartment ( indication ) e.g. gas-insulated compartment Fig. 5: Types of compartments and accessibility 3.3.4 Loss of service continuity category LSC The loss of service continuity category describes the arrangement and design of compartments. It depends on whether and which parts of the switchgear and controlgear have to be deactivated or can remain live when a compartment is opened. This concerns neighboring functional units and also other compartments of an opened functional unit. LSC categories apply to switchgear and controlgear with accessible compartments. We have to start with the highest category to understand the definitions. • Category LSC 2 This category applies to switchgear and controlgear that possess not only the compartment of a single busbar, but also other, accessible, compartments. When any one compartment of a functional unit is opened, all neighboring functional units of the opened unit may remain live and can be operated as normally. The compartment of a single busbar, which prevents system operation when it is opened, is an exception to this rule. LSC 2 consists of two subdivisions: • Category LSC 2B This category applies to switchgear and controlgear belonging to the category LSC 2 in which the cable terminal compartment can also remain live if any other compartment in the same functional unit is open. 12 IEC 62271 standards for medium-voltage switchgear and controlgear • Category LSC 2A This category applies to switchgear and controlgear belonging to the category LSC 2 that does not conform to LSC 2B. • Category LSC 1 This category applies to switchgear and controlgear that does not conform to LSC 2. Category of Loss of Service Continuity If one accessible compartment (e.g. circuit-breaker) in a functional unit is opened … LSC 1 z adjacent functional units must be switched off LSC 2A z all other functional units remain in service (energized) LSC 2B z all other functional units remain in service (energized) and the cable compartment of the opened functional unit LSC 2 Design No partitions between panels Partitions between panels + disconnection and partition to BB As LSC 2A + disconnection and partition to cable Fig. 6: Loss of service continuity categories LSC 1: The number "1" stands for the lowest service continuity and signifies that at least one further functional unit, besides the open one, must be deactivated6. Class 1 has no partitions between the functional units, for example. LSC 2: The number "2" means that no functional units apart from the one with the open compartment need to be deactivated, i.e. the system remains available. LSC 2A: "A" means that the functional unit with the open compartment must be taken out of operation completely. Class 2A requires: - Partitions to neighboring functional units - At least two compartments in a functional unit - An isolation distance from the busbar LSC 2B: "B" means that, even in the functional unit with an open compartment, the other compartments may remain live. 2B offers the highest availability. Class 2B requires: - Partitions to neighboring functional units - At least three compartments in a functional unit - Isolation distances from the busbar and the cable The LSC categories do not make any difference between fixed-mounted compartments with shutters and temporary partitions (e.g. protective plates). LSC categories only make sense for switchgear and controlgear in which other compartments, with the exception of the busbar compartment, are accessible. This 6 If it is the busbar compartment, all other functional units belonging to this busbar section must be deenergized. 13 IEC 62271 standards for medium-voltage switchgear and controlgear categorization can therefore not be applied to gas-insulated switchgear and controlgear. This may be irritating, but Section 6.1 of this paper discusses this issue in greater detail. 3.3.5 Examples The following examples elucidate the new classifications. a) Air-insulated switchgear and controlgear with three compartments and metallic shutters. Old IEC 60298 designation: metal-clad Accessibility of compartments • BB: tool-based • CB: interlock-controlled or procedure-based • Cable: tool-based Loss of service continuity • Category LSC 2B Partitions and shutters • Class PM (metallic) Internal arc classification • Classification IAC Fig. 7: Air-insulated system with "metal-clad" b) Air-insulated switchgear and controlgear, circuit-breaker/cable connection and disconnector/earthing switch in separate compartments Accessibility of compartments • BB: tool-based • Disconnector and earthing switch: non-accessible • CB: interlock-controlled • Kabel: interlock-controlled Loss of service continuity • Category LSC 2A Partitions and shutters • Class PM Internal arc classification • Classification IAC Fig. 8: Air-insulated system with "cubicle" 14 IEC 62271 standards for medium-voltage switchgear and controlgear c) Gas-insulated switchgear and controlgear, circuit-breaker or switch and disconnector/earthing switch and cable connection in separate compartments; old IEC 60298 designation: metal-clad Accessibility of compartments • BB: tool-based accessible • CB/switch: non-accessible • Cable: interlock-controlled Partitions and shutters • Class PM Internal arc classification • Classification IAC Fig. 9: "Metal-clad" gas-insulated switchgear and controlgear d) Gas-insulated switchgear and controlgear, circuit-breaker and disconnector/earthing switch in one compartment; old IEC 60298 designation: metal-clad Accessibility of compartments • BB: tool-based • CB: non-accessible • Cable: tool-based Partitions and shutters • Class PM (metallic) Internal arc classification • Classification IAC Fig. 10: "Metal-clad" gas-insulated switchgear and controlgear 15 IEC 62271 standards for medium-voltage switchgear and controlgear e) Gas-insulated switchgear and controlgear; old IEC 60298 designation: metal-clad Accessibility of compartments • BB: non-accessible • CB: non-accessible • Cable: tool-based / procedure-based Partitions and shutters • Class PM Internal arc classification • Classification IAC Fig. 11: "Metal-clad" gas-insulated switchgear and controlgear 3.4 Internal arc classification IAC IAC stands for "internal arc classification". Clearly greater importance has been attached to internal arcing fault protection in IEC 60298 although, formally, the internal arc classification remains an optional attribute that can be fulfilled voluntarily; in practice however, it would hardly be possible to sell such an untested system. According to the new standard, testing is now undertaken under specified conditions and in accordance with defined criteria. Therefore, testing and its assessment are no longer a matter for negotiation. Thus, the "IAC" classification applies only to switchgear and controlgear that fulfil all prescribed assessment attributes for the protection of persons in the event of an internal arc, verified by relevant tests and inspections. • The test conditions are defined, and so they are no longer subject to an agreement between the manufacturer and operator or test laboratory. • Testing is passed only if all defined criteria are met. It is no longer possible to select individual criteria. 3.4.1 Test conditions The following defined test conditions are particularly important and worthy of emphasis: • The test object must be fully equipped, but equivalents are possible if they conform to the original in terms of volume and material. • A test object consists of at least two functional units. • Tests must be performed in each compartment (of the main circuit) and in the end unit. • Only compartments that have not been previously burdened (with internal arcs) may be tested, unless they are in a state that will not influence the result of testing. 16 IEC 62271 standards for medium-voltage switchgear and controlgear • SF6 may be replaced with air, but all other fluids must not be replaced for testing. Ö This is intended to avoid SF6 decomposition products and unnecessary emissions and is also for industrial safety reasons. However, it must be mentioned that the reaction products of the materials resulting from an arc burning in air also pose problems. • Degree of accessibility A, B or C Degrees A (specialist personnel) and B (general public) remain unchanged. The degree of accessibility C for devices and systems mounted on a pole is new. 3.4.2 Arc initiation and energy flow direction • The manufacturer defines the testing duration, and 1.0 / 0.5 / 0.1 s are recommended preferred values. • Ignition is normally three-phase. Systems with single conductors partitioned from one another that cannot influence each other are the exception to this rule. In their case, the arc is ignited to earth. • Ignition takes place in the tested compartment at the place furthest away from the incoming supply. Ö This is intended to make sure that the arc burns as long as possible there without the duration of burning being shortened by the run time to this location. The tacit prerequisite is that the arc travels to this point lest, in reality, it originates further towards the front at the incoming supply point. For ignition, the current flow direction (from the incoming supply to the ignition location) is: • In the cable terminal compartment: through the busbar and the switching device • In the busbar compartment without partitioning from unit to unit: through the busbar • In the busbar compartment with partitioning from unit to unit: through the switching device • In the switching device compartment – the switch is closed: through the busbar • In a compartment with several switching devices – all switches are closed except for one earthing switch: through a set of bushings 3.4.3 Testing arrangement In future, defined distances will also apply to the test object setup in the room simulation (see Fig. 12). 17 IEC 62271 standards for medium-voltage switchgear and controlgear • Specimen fully equipped 60 cm (mock-ups permitted) • Two functional units • Test in each compartment, 10 cm at end of the switchgear • Accessibility A, B or C 80 cm or 10 cm • Arc initiation and direction of power flow Ö Other arrangements are permitted Fig. 12: Standardised arrangement for internal arc tests The distance between the system and the ceiling is 60 cm, unless the system itself is less than 1.50 m high. In this case, the ceiling is at least 2 m high (above the floor). A distinction is made between whether or not the rear side is accessible, i.e. whether or not the system is set up directly on the wall. Accessible rear sides must be tested with a distance of 80 cm from the wall and rear panels directly on a wall must be tested with a distance of 10 cm. Ö The 80 cm dimension is the result of the indicator rack's setup width. Additional rules and regulations apply if a system is to be placed closer than 10 cm to the wall than when tested. The distance from the wall must be greater than a lasting deformation of the functional unit's enclosure as a result of the arc. Hot gases must not escape directly towards the wall either. Ö The wall must not support a system and must not hinder gas expulsion. Otherwise, the wall could exert such an unfavorable influence on the pressure conditions in the system that the result of testing (without the wall's influence) would no longer be representative of the setup conditions. If it is intended to bolt a system directly to the wall, internal arc resistance for this kind of setup must be verified by a separate test. Other heights and distances may be examined in additional tests for each separate case. Installations mounted closer to the wall than tested (10 cm) require: • the permanent deformation must be less than the distance to the wall • exhausting gases are not directed to the wall Fig. 13: The deformation influences setting up against a wall 18 IEC 62271 standards for medium-voltage switchgear and controlgear 3.4.4 Assessment criteria The following list shows the assessment criteria, which have only been modified slightly, but to which a few additional requirements have been added. Criterion 1 • Doors and covers remain closed. • Deformations are acceptable if no part reaches the indicators or walls (depending on what is closer). • The IP degree of protection no longer needs to be assured. Additional conditions if the system is to be placed closer to the wall than during testing: • Lasting deformation is less than the intended distance from the wall. • Expelled gases are not pointed at the wall. Criterion 2 • The enclosure does not break during testing. • No parts up to a single weight of 60 g may fly off. Criterion 3 • Up to a height of 2 m, holes must not be burned into the freely accessible exterior parts of the enclosure Criterion 4 • Indicators must not be ignited by hot gases. Permitted exception: • ignition by burning paint coatings, adhesive labels or glowing particles is acceptable. Criterion 5 • Earth connections remain effective. • Verify by visual inspection or by measurement in cases of doubt. 3.4.5 IAC designations If internal arc testing has been passed, switchgear and controlgear is assigned the following designations on the rating plate: Qualification: IAC ("Internal Arc Classified") Accessibility: A, B or C with details of the tested, accessible sides F, L, R F = front, L = Side ("lateral"), R = rear Tested values: Current [kA] and duration [s] 19 IEC 62271 standards for medium-voltage switchgear and controlgear IAC A FLR 25 kA 1s Switchgear accessible to authorized personnel only IAC BFL-AR 16 kA 1s Switchgear e.g. in a workshop; front and lateral side publicly accesible, rear to authorized personnel only Fig. 14: Internal arc classification examples Degree of accessibility: The degrees A (authorized personnel) and B (general public), which had already been defined previously, remain unchanged. The degree of accessibility C for devices and systems mounted on a pole is new. Hybrid forms of accessibility can also be declared, for example some sides accessible to the public and others only to specialist personnel or not at all. For example, a system such as the one shown on the right in Fig. 14 could serve as a load-center substation in a factory hall. These designations are unusual and it remains to be seen whether they are absolutely necessary on the rating plate. It must be said that, in total, as far as internal arc protection is concerned, the test results have become more comparable due to the defined test conditions and so users are able to assess safety with greater ease. 3.5 Gaps in the standards Not all issues have been satisfactorily clarified in IEC 62271-200. A few of them are mentioned here without dealing with their causes in greater detail. 3.5.1 LSC category Essentially, accessibility to the compartment of the main switching device (circuit-breaker) during normal operation determines the LSC category. Thus, (almost) all air-insulated systems can be described with an LSC category because the circuit-breaker compartment in the systems is generally accessible. Things are different in the case of gas-insulated systems, where the main switching device (switch or circuit-breaker) is in a non-accessible compartment. It is not necessary to open the gas compartments during normal operation and it is precisely for this reason that this is not possible either. Nowadays, many systems are "sealed for life". This dispenses with the prerequisite for assignment to an LSC category. This can cause confusion. For example, how are users to compare air and gas-insulated systems if they do not obtain any LSC information for a type of construction? Are GIS systems less reliable, for example? Of course they are not. GIS systems do not need this categorization because they are inherently more reliable and so the focus is not on accessibility and maintainability. 20 IEC 62271 standards for medium-voltage switchgear and controlgear One shortcoming of the standard is that this circumstance is not recognizable in an additional LSC category. LSC incorporates the right concept, i.e. that the design of a system determines its loss of service continuity category. Service continuity is inseparably linked with reliability, though. However, the standard does not contain any stipulations and definitions relating to reliability due to a lack of a secured – and internationally recognized – database. 3.5.2 Cable testing If cable testing is performed during operation of switchgear and controlgear without isolating the cable from the system, the isolation distance from the busbar is subjected to the total of the test voltage on the cable and the operating voltage of the busbar. UN ∆U uTest Beispiel: Schaltfeld mit Lasttrennschalter In some cases, there is then no safety margin left over for the withstand capability of the isolation distance. It is also a problem that, in some cases, the voltage stress contains a DC component, although DC is not a rated quantity for switchgear and controlgear. Due to a lack of uniformity of cable test voltages, which are highly diverse on the international scale, and also due to the absence of international reference standards, it was not possible to define any provisions in this respect. What is left is the reference to the hazard. Operators have to know how to perform testing, what their systems are capable of withstanding and what precautions they have to take. Fig. 15: Cable testing with cables that are not disconnected 3.5.3 PD measurement Even the old standard included an informative attachment about measurement of partial discharges (PD) which described measurement methods, but did not specify any permissible PD limits. As the partial discharge rate says something about the dielectric state of the insulation, it would be desirable for the standard to define testing. At the moment, though, several prerequisites for this are missing. Up to now, there have been no internationally established, generally valid assessment criteria to determine which PD levels are still tolerable for functional units or entire systems. Limits would have to be coordinated with those of individual components such as instrument transformers. Moreover, it is difficult to include interfering influences on a PD measurement locally in standards definitions. This is why the definition of permissible PD levels is still a matter for negotiation between operators and manufacturers, who are best able to assess the characteristics of their products. 21 IEC 62271 standards for medium-voltage switchgear and controlgear 4 Outlook 4.1 Switch standards By classifying the endurances of switching devices, the standards have closed a gap in recent years. The classes for the possible mechanical and electrical switching cycles provide users with additional information about what tasks they can expediently use a switch for. Endurance classes exist for switches and circuit-breakers and for disconnectors and earthing switches. Thus, the most important maneuvering and safety switches are covered. The contactor is still unaccounted for. It can be assumed that IEC 60470 will also introduce such classes in the next revision, but a date has not yet been named. The circuit-breaker standard IEC 62271-100, which is unfortunately not yet stable, is giving cause for concern. Although it was not published until 2001, it has already been amended to because of errors and two corrections have been implemented. A further, third amendment is currently in the draft stage. There are fierce disputes in the IEC committee in relation to the test procedures. It remains to be hoped that stability will return to this core standard. 4.2 Metal-enclosed switchgear and controlgear IEC 62271-200 introduces new terms and definitions which might need getting used to at the beginning, but which do better justice to the present-day requirements and types of switchgear and controlgear construction. Especially the internal arc qualification conditions are now defined more clearly and are declared unequivocally. Many, long overdue clarifications and adjustments to the state of the art have been achieved. The fact that there are still gaps has to do with the consensus without which no international standard would come into being. Practice will have to show how the new definitions prove themselves. Does the new standard influence types of switchgear and controlgear construction? There was a need to adjust switchgear and controlgear technology to the market. Therefore, it will not lead directly to new "designs", but will rather more pave the way for new types of construction. Nevertheless, the standard may have an indirect influence on the mechanical design of switchgear and controlgear. For example, the intensifying of internal arc testing may compel manufacturers to adopt different approaches. No-one will want to bear the expense of unnecessary tests to achieve qualification. This is why the characteristics of a system must already be optimized before testing, to make the occurrence of an internal fault (even) less probable, to limit the propagation and effect of an internal arc, and to ensure the design stability of the functional units. CAD processes may help here. Does switchgear and controlgear conform to the new standard and are old tests still valid? The new standard does not demand any design changes nor new safety requirements and so switchgear and controlgear currently constructed in accordance with IEC 60298 may also conform to IEC 62271-200. Rated values have not been changed and no new rated quantities have been introduced. This is why test verifications conforming to the old standard are still valid. This fundamentally also applies to internal arc testing, which has undergone wideranging changes. Systems that met all criteria in accordance with the old standard still offer solid protection against the effects of an internal arc. Specification of the new standard on the rating plate depends on whether purely formal requirements are also met. This must always be reviewed and documented in each individual case. These changeovers need time. Therefore, many switchgear and controlgear assemblies will continue to be constructed in accordance with the previous IEC 60298 standard during the current transition period up to February 1, 2007. System operators will also be able to use this period to change over their specifications. 22