bulk storage of acetic acid contents 1. INTRODUCTION 2 2. COMMERCIAL ASPECTS OF BULK STORAGE 2 3. TECHNICAL ASPECTS OF BULK STORAGE 3 4. LOCATION OF STORAGE TANKS 3 5. TANKER DISCHARGE 3 6. DESIGN AND CONSTRUCTION OF TANKS 4 7. LEVEL MEASUREMENT 4 8. PIPEWORK 5 9. VALVES 6 10. PUMPS 6 11. HEATING FACILITIES 6 12. PRE-COMMISSIONING 7 13. ACID DILUTION 7 14. LABELLING AND SAFETY PRECAUTIONS 8 15. PRODUCT TRAINING 8 16. OPERATING PROCEDURES 9 17. FURTHER TECHNICAL LITERATURE 9 Appendix 1 Key Safety and Environmental Data of Acetic Acid 10 Appendix 2 Typical Weights and Dimensions of Fully Laden Road Tankers 10 Appendix 3 Diagram of Typical Above Ground Storage Installation 11 Appendix 4 Diagram of Typical Above Ground Fixed Roof Storage Installation 12 Appendix 5 Diagram of Typical Under Ground Storage Installation 13 Appendix 6 Suitable Fittings for Tank Inlet Connections 14 Appendix 7 Suitable Materials for Seals, Gaskets and Hoses 14 1 bulk storage of acetic acid 1. INTRODUCTION of the bulk installation will depend upon its size and the rate at which the acetic acid is used. 1.1 This technical booklet has been produced for the guidance of customers who are interested in installing bulk storage facilities for acetic acid. It describes in general terms the requirements for a suitable installation. 2.2 Acetic acid is available in bulk from BP in four grades as follows: Chemically Pure Acetic Acid, 99.5% Technical, 80% Pure, and 80% Technical. 2.3 When small quantities of aqueous acetic acid are required, it is usual to buy the appropriate dilute grade, which is more convenient for handling. However, where large quantities are used, consideration should be given to the purchase of full strength acid in bulk which can be diluted to the required strength following receipt. The initial capital outlay is higher, because of the additional requirement to provide mixing equipment, but this is offset by the saving resulting from the lower purchase cost of the acid. 1.2 Our experience has shown that the design and construction of each bulk storage installation requires individual consideration, because of the nature of the site, the users specific requirements and the impact on any existing facilities in the vicinity. BP offers a Technical Advisory Service, free of charge, to customers who wish to make use of it. We consider that our Technical Advisory Service is most useful to a customer when discussions are held at the earliest possible stage and certainly before the design of the unit has been finalised. Our local Sales Representative will be pleased to make the necessary arrangements. 2.4 Bulk deliveries of BP’s acetic acid are normally made by road tankers. Customers should carefully consider the optimum storage capacity for the installation, bearing in mind delivery load sizes as well as current and estimated future usage. Adequate capacity should be provided to allow a delivery to be taken well before the previous supply is exhausted and also to hold sufficient stock to meet contingencies. The storage and handling of corrosive and flammable liquids is subject to legislative controls in many countries. Customers are recommended to obtain and make themselves familiar with any relevant regulations and keep abreast of new regulations, as and when these apply. Information contained in this booklet is not intended to replace any legal requirements which may be applicable to the storage and handling of acetic acid in particular circumstances. It is recommended however, that the guidance outlined in this technical booklet is followed, provided that it does not conflict with any specific legal obligations. 1.3 3. TECHNICAL ASPECTS OF BULK STORAGE 3.1 Acetic acid is a corrosive and flammable and thus certain precautions are necessary if it is to be stored and handled safely. This can be achieved by ensuring that the storage and handling facilities are correctly designed and constructed and that safe operating procedures are followed. 1.4 A Material Safety Data Sheet has been issued describing the health, safety and environmental properties of acetic acid, identifying the potential hazards and giving advice on handling precautions and emergency procedures. This must be consulted and fully understood before handling, storage or use. Key safety and environmental data are listed in Appendix 1. 3.2 Information on the design, construction and location of storage installations for acetic acid contained in this booklet is applicable only if the temperature of the liquid remains below 30°C. At higher temperatures, different materials of construction may be required. 3.3 The following aspects need to be considered for the safe and efficient receipt and storage of acetic acid: 2. COMMERCIAL ASPECTS OF BULK STORAGE 2.1 Although acetic acid can be supplied in packages, for example nominal 210 litre drums, it is often more convenient for the customer to receive bulk supplies. Bulk storage is more compact than storage in drums and therefore releases space and handling equipment for other duties. Stock control is also made easier and deliveries can be received less frequently. There may be cost savings from reduced handling. The time taken to recover the capital cost 2 • Location of storage tanks • Tanker discharge • Design and construction of tanks • Level measurement • Pipework • Valves return to contents • Pumps • Heating facilities • Pre-commissioning • Acid dilution • Labelling and safety precautions • Product training • Operating procedures small spillages and to minimise the surface area of any spillage. 3.4 These aspects are considered in detail in the following sections. 4.8 The floor of the bund should be sloped to prevent minor spillages remaining below any tank. Provision should be made for the removal or drainage of surface water from the area within the bund. Surface water should preferably be pumped out of bunds. If bund drains are used they should be provided with valves outside the bund walls, with procedures in force to ensure these valves remain closed, and preferably locked, except when drainings are being removed. 4. LOCATION OF STORAGE TANKS 5. TANKER DISCHARGE 4.1 The arrangement and any grouping of tanks requires careful consideration. It is important to consider access not only for normal operations but also for emergency evacuation. 5.1 The provision of vehicle access needs to be taken into account when selecting the site for the storage installation. The following aspects need to be considered: 4.2 The design of the tank farm should take account of the likely consequences of any accidental spillage or fire. Products which react chemically with acetic acid should be kept in totally segregated storage. a) a clear, safe access for the vehicle with sufficient room to manoeuvre to and from the discharge point (this must allow the vehicle to be driven forward from the unloading point in an emergency rather than being reversed), 4.3 Storage at ground level and in the open air is preferable because in the unlikely event that a leak occurs, it is more likely to be detected. Examination, modifications and repairs are also easier and corrosion can be more readily identified and controlled. An exception to an outside installation is where a small tank for glacial acetic acid can be conveniently installed in a building which is already heated thus removing the need for heating and insulating the tank. b) the width, corners, type of surface and loadbearing capacities of the approach road, c) headroom under any overhead gantries, d) any bridge or other restrictions. 4.4 Storage tanks should not be located: a) on the roof of a building, b) in an elevated position, c) on top of each other, 5.2 Typical weights of fully laden vehicles with dimensions and turning circle are shown in Appendix 2. 5.3 A trial run with an empty tanker may be appropriate if the access is doubtful. The unloading point should be located facing the tanker’s outlet connection to avoid the need to run flexible hoses under or to the rear of the tanker when discharging. Ideally, only one short length of flexible hose should be used for the discharge operation. 4.5 Storage tanks should be discharged by pump. Horizontal tanks should be positioned just high enough above ground level to provide clearance for convenient operation and maintenance of valves. Vehicles must not stand on a road or path used by the public while being discharged and must be at least 6 metres from a right of way. It is preferable if the immediate area surrounding the discharge point is closed to all except those directly concerned with the operation while tanker discharge is being carried out. 5.4 4.6 All tanks should be surrounded by a bund wall. The required capacity of the bund may be subject to local regulations. It should be equivalent to at least 110% of the capacity of the largest tank within the bund. The walls and floor of the bund should be impervious to liquid and designed to withstand a full hydrostatic head. Bund walls should not be higher than 1.5 metres in order to ensure adequate natural ventilation of the bunded areas, ready access for fire fighting and a good means of escape. 5.5 It is good practice to provide an earthing point near the discharge point for connection to the earthing point on the road tanker. 5.6 The rate at which the discharge takes place is normally about 600 litres per minute whether by the vehicle’s pump or compressor. This depends to 4.7 Intermediate lower bund walls are recommended to divide tanks into groups to contain 3 return to contents some degree on the configuration of the pipework to the storage tank. When the customer’s own pump is to be used, a similar rate should be planned. 7. LEVEL MEASUREMENT 7.1 Every tank should be provided with a suitable means of determining the volume of the contents. A contents indicator is preferred to manual dipping. 5.7 Road tankers are fully insulated to prevent acetic acid freezing in cold weather. The following types of contents indicator may be used: During the road tanker discharge operation acid vapour will normally be displaced from the storage tank vent. If the presence of acid vapour in the discharge area is unacceptable, the installation of a system to return the vapour to the road tanker can be considered. Further details can be obtained from BP’s Technical Advisory Service. 5.8 a) Gauge glasses of the reflex type may be used with 80% acid. They should be suitably protected on all sides against shock damage and fitted with top and bottom isolating cocks. They are not suitable for glacial acid because of the difficulty of preventing freezing in the gauge glass. 6. DESIGN AND CONSTRUCTION OF TANKS 6.1 The storage tank must be of adequate strength and capacity for the proposed duty. b) The choice of construction material for storage tanks depends upon the grade of acid, and also on cost. c) Tanks constructed from the following materials are suitable for storing 80% acetic acid. 6.2 Stainless steel grades 304, 316 and 321 b) High density polyethylene (HDPE) c) Polypropylene (PP) d) Glass reinforced plastic (GRP) with either a HDPE or PP lining e) Hydrostatic gauge Hydrostatic gauges provide a level measurement system requiring no external power source or adjustment. They are simple but robust in construction and require little maintenance. All metal parts of these instruments should be fabricated in stainless steel of a suitable grade. The tank and its supports should be designed and constructed in accordance with an appropriate recognised standard of good engineering practice. a) Gauge glass Pneumacator This is a simple type of level indicator which is relatively cheap but effective. Care should be taken that all parts of the system are compatible with acetic acid. All metal parts of these instruments should be fabricated in stainless steel of a suitable grade. d) Ultrasonic and radar level indicators For higher accuracy in level measurement, ultrasonic and radar level indicators are available for use with acetic acid. Care should be taken to ensure that they are intrinsically safe to BASEEFA (British Approvals Service for Electrical Equipment in Flammable Atmospheres) standard SFA 3012 for Zone ‘O’ with certified ‘Ex’ head units and probes, or to an equivalent standard. Rubber lined carbon steel. Increase in temperature can affect the mechanical properties of some plastics and care should be taken to avoid overheating the tank contents. 6.3 Stainless steel of ASTM 316 or 321 grade or equivalent is suitable for the storage of all grades of acetic acid. Where manual dipping is necessary the following precautions should be applied: 7.2 6.4 Aluminium of minimum 99.5% purity is suitable for the storage of glacial acetic acid, but any dilution of the acid should not be allowed as this will accelerate corrosion of the tank. The temperature control of the acid must be more precise when aluminium is used rather than stainless steel, since above 30°C the corrosion rate increases sharply, with the formation of aluminium acetate. 6.5 The materials of construction described above are only suitable for acetic acid as delivered. Where any process material is recycled to the storage tank, trace quantities of impurities may cause or accelerate corrosion. Corrosion tests should be carried out using the recycle material. 4 a) the tank should be fitted with a dip tube extending down close to the bottom of the tank, with a wear pad welded to the tank bottom beneath the dip tube. b) the top of the dip tube should have a vapour tight cap which should always be in position except when gauging is actually taking place. c) dip roads should be substantially smaller in diameter than the dip tube to reduce any inaccuracy in measurement. Wooden or stainless steel dip rods can be used. d) dipping should never take place through open manholes. return to contents It is recommended that each tank should be fitted with a high level alarm, the measuring element of which should be independent from level indicator. An alarm operated from a float switch is suitable for this purpose. far removed as possible from the inlet line. To prevent possible damage to the tank, the vent line should not be smaller in diameter than either the inlet or the discharge lines. 7.3 It is good practice to connect the vent line to a scrubbing system. However, if no such system is available, it is recommended that the tank vent is extended down into the tank bund to within 200mm of the floor, to prevent injury to personnel from windborne droplets of acetic acid at the end of the discharge. Free circulation of air around this vent is essential to disperse vapours, particularly while that tank is being filled. A vacuum break should be provided on this vent line. This may be in the form of a tun dish, or be a small hole (6mm) drilled in the vent line above the level of the bund wall. 8. PIPEWORK 8.1 The general layout of pipelines directly connected to the tank is shown in Appendices 3, 4 and 5. These should normally be of the same material as the tank, except for plastic tanks, which should have the inlet pipeline fabricated from a suitable grade of stainless steel. 8.2 The tanker hose connecting point (inlet connection) should be provided with a suitable fitting to connect to the delivery hose. Suitable fittings are described in Appendix 6. The inlet connection should be positioned as near as possible to where the vehicle will stand during discharge, and should be protected from accidental damage. The inlet connection should be located at a convenient height, i.e., not more than 1 metre above ground level, facing outwards, for hose coupling. The inlet line should be fitted with an isolation valve as close as possible to the inlet connection. When a number of different products are stored, each inlet connection should be clearly marked with the name of the product to which it relates. An inlet line of 80mm nominal bore is a suitable size for transferring acetic acid from the road tanker to the tank. The line should enter the top of the tank. The inlet should be sloped towards the tank as shown in Appendix 3. A drain cock should be fitted at the lowest point in the inlet line so that the line can be drained at the completion of tanker discharge. Space for a small receptacle (20 litres capacity) should be left under this drain cock. 8.6 In order to reduce vapour emissions to the atmosphere it is possible that legislation will in future require that bulk deliveries of acetic acid are made using a vapour return system or a tank with a vent scrubber. A typical vapour return system is shown in outline in Appendices 3 and 4. Vapours displaced from the storage tank during delivery would be transferred to the vapour space of the delivering tanker. 8.7 Wherever possible, continuously welded pipework should be used. However, where pipework may have to be disconnected for maintenance or inspection, flanged joints should be fitted. Flanges conforming to the American National Standards Institute (ANSI) 150lb and PTFE envelope gaskets are recommended. Other suitable gasket materials are shown in Appendix 7. Graphitised jointing paste should not be used with stainless steel. 8.8 A vapour tight manhole should be provided on all tanks to allow for internal inspection and cleaning. 8.9 An earthing point should be fitted on tanks containing pure acetic acid, and this should be connected to a good earth. The resistance to earth at any point of the installation should be less than 10 ohms. This also applies to the tanker earthing point which preferably should be connected to the same earth, or if independent should have minimal resistance between this and the tank-pipework system. It is good practice to fit an earthing point on tanks containing 80% acetic acid. A tank discharge line should be provided which should be a minimum of 50mm nominal bore. The discharge line is usually taken through the bottom or the side of the tank to an isolating valve. 8.3 This isolating valve should be located as close as possible to the tank. In all cases, discharge should be by pump. The pump and controls should be sited outside the bund. 8.4 If the tank discharge line is not located at the lowest point of the tank, a facility should be provided for draining the tank. A 25mm nominal bore branch fitted at the lowest point of the tank is suggested. The branch should be fitted with a suitable isolating valve and blanked off when not in use. 8.10 The pipework system should be designed such that liquid cannot be trapped between closed valves without some form of pressure relieving device. This applies especially to heated pipework (see section 11). A vent line needs to be provided, leading from the vapour space at the top of the tank, for the dispersion of vapour. This vent line should be connected to the highest point of the tank and be as 8.11 Joints in pipework should not be located over doorways, windows or close to possible sources of ignition. 8.5 Pipework should be routed to minimise the possibility of accidental damage. 8.12 5 return to contents 9. VALVES Temperature control Stainless steel ball or gate valves with PTFE seats are recommended for use with acetic acid and are suitable for all applications. 11.3 If heating is provided, thermostatic temperature control is strongly recommended to ensure that the temperature of the acetic acid does not exceed 30°C. At higher temperatures the rate of corrosion of stainless steel by acetic acid increases and flammable mixtures of air and acetic acid are possible. The fitting of low and high temperature alarms is recommended. 9.1 9.2 Plug or diaphragm valves can also be used with acetic acid. However, diaphragm valves should not be used on the bottom outlets of tanks. 9.3 PVC or polypropylene ball valves can be used for 80% acetic acid. 11.4 Thermostatic control also ensures economy in the usage of the heating medium and minimises vent loses. The temperature sensing element for the tank should be installed in a 40 mm nominal bore pocket at the side of the tank and which extends towards the bottom of the tank at a point remote from the heating element. The thermometer pocket should be of stainless steel, filled with oil. If heating is by hot water or steam and instrument air is available, a simple pneumatic temperature indicating controller will be adequate. If instrument air is not available a direct-acting controller must be used, and a direct reading temperature indicator should be installed. 10. PUMPS 10.1 Pumps should be located outside tank bunds, on an impervious base, in an open space, and not in walled or confined spaces. 10.2 Pumps for 99.5% acetic acid should be fabricated from a suitable grade of stainless steel, i.e. ASTM 316. Polypropylene may be used for 80% acetic acid. Self-priming centrifugal pumps should be used wherever possible. Mechanical seals with PTFE wedges (Crane Type 109 or equivalent) are recommended for this duty but these seals must not be run dry. If packed glands are used, braided PTFE should be used. If metering or other reciprocating pumps are used, PTFE packing is preferred. Glandless centrifugal pumps with magnetic coupling may also be used. 10.3 With electric heating, a simple on/off thermostatic control switch will be adequate. 11.5 Heating of the storage tank For glacial grades, the storage installation should be designed to maintain the tank contents at a temperature of 25°C ± 5°C. If the tank is installed inside a building, provided the ambient temperature is not allowed to fall below 20°C, no additional means of heating is required. Precautions will still have to be taken to avoid freezing of the inlet and vent pipes if these pass outside the building. 11.6 Arrangements should be made to collect any leakage from glands. Connections at the pump should be flanged to ANSI 150lb. Threaded joints must not be used. 10.4 10.5 When glacial acetic acid is being handled, it is normal practice to drain a pump after use and to close the isolating valves until it is required again. If the tank is installed outside, an internal stainless steel (ASTM 316L) heating coil is recommended. This may be heated by either hot water or low pressure steam. Electric heating pads can be used but these should be designed so that overheating of the surface of the tank does not occur. 11.7 10.6 If pumps can be remotely controlled, a stop button should be provided both at the pump, and at the delivery point. 10.7 Suitable materials for use as seals and hoses are shown in Appendix 7. 11.8 In all cases where storage tanks are heated, they must also be effectively insulated. 11. HEATING FACILITIES Heating of pipework Introduction 11.9 The ratio of heating surface to liquid volume is much higher in pipework than in the storage tank. This means that acid in a pipe is much more susceptible to overheating, if heat is applied, or to freezing if the insulation is faulty. In view of this, some system of thermostatically controlled heating on the pipework is recommended. Care must be taken to avoid high surface temperatures, as these might cause an increased rate of corrosion and In most situations it is necessary to take precautions, such as the provision of heating and/or insulation, to prevent glacial grades of acetic acid from freezing in tanks and pipelines. These grades freeze at temperatures between 14°C and 16°C. 11.1 For 80% grades, the need for precautions to be taken to prevent freezing of the acid will depend upon the location of the tank and local ambient temperature conditions. 80% grades of acetic acid freeze at -7°C. Consequently, in many cases special precautions are unnecessary. 11.2 6 return to contents consequent contamination of the acid. 12. PRE-COMMISSIONING 11.10 Pipelines may be heated electrically or by hot water. Electric heating tapes wrapped around the pipe or electric heating elements running along the underside of the pipe may be used. When hot water is available, a 15mm nominal bore mild steel trace line can be run directly below the acid line. The tracing is supported by the acid line but small spacing pads prevent direct contact. Maintenance is simplified if the trace line is jointed adjacent to the acid line joints. For pipelines in continuous service automatic control must be used to avoid overheating. 12.1 When the bulk installation is completed it is normal practice flush the whole system through with water to remove any debris. When this is done it is advisable to: a) fit fine wire mesh strainers at the inlets of pumps and meters to prevent them being damaged by solids, b) use water with a low chloride content i.e. below 30ppm, to avoid any possibility of chloride corrosion of the stainless steel. Where a stainless steel tank is to be used, and the iron content of the product is important, it is advisable to condition the tank before use, to remove iron. BP will be pleased to advise on suitable conditioning procedures. 12.2 For occasional duties, such as the inlet line, steam heating may be used. The installation should be similar to hot water heating, with steam traps at all low points. The line should be drained after use and the heating properly shut off. To ensure complete drainage the slope of the line should be increased to 1 in 50. 13. ACID DILUTION Introduction It is most important that the vent line is fully trace heated and insulated to avoid blockage by crystallised acetic acid vapour during cold weather. 13.1 Reference to price schedules will show whether it is economic to buy glacial acid and dilute it with water down to the required strength. There are no major process difficulties and personnel soon become accustomed to the method of dilution and its control. Heating of pumps Steam/water-jacketed pumps can be obtained but are not usually necessary. It is normally sufficient protection if the pump is sited inside a warm building or if the heating element or tracing line is continued around the base of the pump. 11.11 Water quality 13.2 All town water contain soluble salts, although some waters are of a better, or softer, quality than others. Heating of valves Steam/water-jacketed valves are expensive and not readily available. It is normally adequate to continue the heating element or tracing line close to the valve body. 11.12 13.3 The quality of the diluted acid depends upon the quality of the water used. For this reason, it is recommended that for high grade 80% acetic acid demineralised water or distillate is used as diluent. Filtered steam condensate may be used only if it has not been in contact with mild steel equipment. However, not all customers require such a high grade product. In such cases, ordinary towns water may be used as diluent. However, it should be noted that contaminants, e.g. chloride, can cause increased corrosion in subsequent processing. Thermal insulation of tanks and lines 11.13 Heated tanks, pumps and pipelines should be insulated to prevent heat losses and reduce heating costs. In addition, if the installation is sited outdoors, the insulation must be weatherproofed. 11.14 Preformed types of insulation are recommended. Preformed slabs or mattresses may be used with tanks, and preformed sections of adequate bore for the pipelines plus heating devices. All flanges, valve bodies and pumps should be insulated. Dilution equipment 13.4 The dilution is normally carried out in the bulk storage tank. The tank should be sized, therefore, to contain the required delivery of acetic acid, plus the dilution water, plus any residue of diluted acid which had not been utilised. Acid and water are intimately mixed using either a top entry agitator or a jet mixer nozzle and pump. Jet mixing is normally the more convenient method. It is favoured by the basic geometry of a storage tank and the cost can be less, particularly as a pump is usually required for other purposes. 11.15 For tanks and pipework in stainless steel, chloride-free insulation must be used or corrosion will result. 7 return to contents where W is the amount of water to be added in litres and M is the amount of 99.5% acid in tonnes. 13.5 Jet mixing is simply the circulation of acid from the tank into a pump and back into the tank through an inclined nozzle at the tank base. The jet of liquid from the nozzle produces the stirring action in the tank. For different strengths the following equation may be used: W = M x (X - 80) x 125.24 10 The nozzle design is critical, depending on the geometry of the tank and the pump rating. Our Technical Advisory Service engineers will, on request, advise on a jet mixing system for the proposed duty. 13.6 where X is the initial concentration of acetic acid, mass per cent, W is the amount of water to be added in litres and M is the amount of acid in tonnes. Thus, for X = 99% m/m The nozzle should not be used until there is about 1.5 metres of liquid above it. Mixing time is so short that this is not at all a serious disadvantage. The tank should not be filled through the nozzle. W = 1 x (99 - 80) x 125.24 litres per tonne 10 = 19 x 125.24 10 = 238.0 litres per tonne The inlet delivery line should be heat traced and insulated. Demineralised water 14. LABELLING AND SAFETY PRECAUTIONS Where demineralised water is used for the dilution of acid, a tank should be installed for the storage of the treated water. The economics of water treatment are such that it is cheaper to install a small capacity demineralising unit feeding over a prolonged period of time into a water storage tank rather than a large capacity unit feeding into the acid tank over a short period. Alternatively, the acid tank can be filled slowly with water if not required continuously. 13.7 14.1 The words: ACETIC ACID – CORROSIVE TO SKIN should be painted on all acetic acid bulk tanks. Emergency instructions, in case of splashing, should be shown at the main places of work. An adequate number of eye baths or wash bottles containing water (for use until a source of running water can be used) should be kept in the working area. Buckets of sodium bicarbonate may also be kept in the working area for skin use only. 13.8 Demineralising equipment is supplied by manufacturers specialising in this field and their advice should be sought regarding the most suitable unit for a specific application. In addition, safety showers with a quick acting valve, adequately protected against frost, or a water bath should be installed on site. There should be an adequate supply of water for hosing down the area in the event of an acid spillage. 14.2 Demineralised water is corrosive to some materials. Equipment such as the treated water storage tank should be of corrosion resistant material. Stainless steel, ebonite-lined carbon steel, polyethylene or polypropylene may be used. 13.9 14.3 Buildings in which acetic acid is stored or handled should be well ventilated. Method of dilution 15. PRODUCT TRAINING It is recommended that initially up to 80% of the water required for dilution is added before the acid delivery. After the delivery, the tank can be jet mixed and the contents sampled. Measurement of the relative density of the liquid and its assay will give the quantity of acid in the tank. 13.10 All personnel associated with the handling of acetic acid should be fully trained to enable them to understand: It is a simple matter to calculate the additional water and to add the quantity required accurately. The tank is again jet mixed and the assay checked. As the operator becomes more skilful in the technique of dilution, the initial charge of water may be increased to say 90%. Calculation of dilution 13.11 For the dilution of 99.5% by mass acetic acid to 80% by mass: W = 244.1 M 8 a) the nature of the potential hazards associated with the handling of acetic acid, b) the appropriate storage and handling precautions including personal protection measures, c) the appropriate action to be taken in the event of an emergency. return to contents 16. OPERATING PROCEDURES closed. The drain cock adjacent to the inlet valve should then be opened carefully, to allow any product remaining in the inlet pipe to drain into a receptacle. Next, the hose should be drained through the inlet valve and drain cock into a receptacle (5 to 10 litres of drainings may be expected). It is the customer’s responsibility to provide adequate facilities for disposal of these hose drainings. Written operating instructions should be available for the receipt of acetic acid, and operating personnel should be fully trained in their implementation. The instructions should take account of the specific hazards, and ensure the correct operation of equipment in both normal and emergency situations. Key points of a typical discharge operation for bulk road tankers are: a) b) h) the customer's representative must ensure that there is sufficient ullage available in the receiving tank to accept the nominated delivery. the delivery hose should be thoroughly washed through with water. i) prior to discharge, all appropriate safety equipment must be checked and suitably positioned. all equipment must be properly stowed before the road tanker is given authorisation to depart from the discharge point. j) finally, the quantity in the tank should be checked against the amount expected. Dipping the tank or removal of a sample for testing should not take place until at least 30 seconds after completion of discharge. This is to allow for the relaxation of any electro-static charge which may have been generated in the transfer. c) only those personnel directly concerned with the discharge operation should be in the area, with appropriate protective clothing being worn. d) a customer’s representative must identify the discharging point to be used, and the earthing point, and must supervise all connections to the vehicle. e) f) g) 17. FURTHER TECHNICAL LITERATURE the road tanker should be connected to the earthing point before the delivery hose is connected. This earth must be maintained throughout the operation and not be broken until after the hose is disconnected, on completion of product transfer. Further technical literature on acetic acid is available from BP as follows: 17.1 during discharge, regular checks should be carried out to ensure that the load is being received into the appropriate storage tank. The customer's representative must remain in attendance throughout the discharge operation. a) BP Acetic Acid Product Specification and Physical Properties. b) Material Safety Data Sheet, giving health, safety and environmental data. Copies of Material Safety Data Sheets are normally supplied automatically by our Sales Offices. Further copies are available either by direct request to the Sales Office or by asking our local sales representative to arrange for copies from the Sales Office. on completion of discharge, the pump (if used) should be stopped and the valves in the pipeline 9 return to contents APPENDIX 1 KEY SAFETY AND ENVIRONMENTAL DATA OF ACETIC ACID Flash point (closed cup) Acetic acid chemically pure 39°C Acetic acid 80% pure 65°C Autoignition temperature Freezing points Flammable limits in air 463°C Acetic acid chemically pure 16.6°C Acetic acid 80% pure -7.0°C lower 4.0% volume upper 19.9% volume Acetic acid is readily biodegradable in both fresh and salt water. It is slightly toxic to aquatic species, i.e. TLm96 10-100 ppm, but is unlikely to bio-accumulate. APPENDIX 2 TYPICAL WEIGHTS AND DIMENSIONS OF FULLY LADEN ROAD TANKERS Nett weight 22 – 25 tonnes Gross weight 38 – 44 tonnes Overall length 13.5 – 15.5 metres Overall height 4 metres Overall width 2.5 metres Turning circle 14 – 17 metres return to contents Actual values will depend upon the vehicle design and construction regulations currently in force in the country concerned. 10 750 mm approx. protective cap and chain 65mm intake valve 11 Tanker earthing with bulldog clip Single short length of flexible hose 2½" BSP male inlet connection Intake point for road tanker delivery 50mm drain branch Tank earthing 1 m min Sump LI 38mm vapour return (where fitted) Tank contents to be clearly marked on tank Slope to tank Products to be clearly marked at delivery point Bund wall 80mm inlet line 2m long common copper earthing rod 25mm drain valve 1 Max bund height 1.5m 2 Tank heating will be required for glacial grades of acetic acid Slope Tank supports steel or concrete Slope TI Bund wall 50mm ball valve 1m min Vent scrubber (alternate design) Fixed access ladder Impervious base 80mm minimum vent pipe Tank insulation (glacial grades) LAH 600mm manhole with bolted cover Pressure/vacuum valve Town's water supply Shower located adjacent to storage installation incorporating quick acting valve and eye-bath 50 mm delivery line To pump Pipes to be sealed in bund wall Water Water hose for washing down APPENDIX 3 DIAGRAM OF TYPICAL ABOVE GROUND STORAGE INSTALLATION return to contents 750mm approx. protective cap and chain 12 \` 65mm intake valve Tanker earthing with bulldog clip Single short lengths of flexible hose 2½ inch BSP male Intake point for road tanker delivery 25mm drain valve 38mm vapour return (where fitted) Bund wall Product to be clearly marked at delivery point 1 Max bund height 1.5m 2 Min bund wall to tank 1m 3 Tank heating will be required for glacial grades of acetic acid Sump Slope 80mm inlet line Non-return valve Handrails 50mm drain Slope Wear plate Mixing nozzle Tank contents to be clearly marked on tank Tank earthing LI Common earth system Manhole Tank insulation (glacial grades) LAH 150mm min 600mm manhole fitted with hinged emergency relief hatch pressure/ vacuum valve Impervious base TI Bund wall To pump Pipes to be sealed in bund wall Water Vent scrubber Sample point Fixed access stairs Pump recycle 50mm dip pipe with screwed cap local to stairs APPENDIX 4 DIAGRAM OF TYPICAL ABOVE GROUND FIXED ROOF STORAGE INSTALLATION return to contents 13 Reinforced concrete Sealed to keep out water 2m long common copper earthing rod Tanker earthing lead with bulldog clip Note: Tank recirculation system not shown Tank earthing Inlet connection for road tanker delivery Single short lengths of flexible hose 80mm fill and dip pipe fitted with lockable cap Wear plate Product and vapour return, where fitted, to be clearly marked at delivery point 38mm vapour return (where fitted) To pump Tank supports steel or concrete Pit back filled with dry sand Tank and pipes below ground to be protected against external corrosion 50mm suction line LI 80mm minimum vent pipe to safe location (to be fitted with a pressure relief system if a vapour return system is used) Flame arrestor APPENDIX 5 DIAGRAM OF TYPICAL UNDER GROUND STORAGE INSTALLATION return to contents APPENDIX 6 SUITABLE FITTINGS FOR TANK INLET CONNECTIONS UK: 2.5 inch BSP parallel threaded male connection France: symmetric coupling NF-E 29.572, 80 mm nominal diameter (type ‘Guillemin’ or equivalent) Germany: quick coupling DIN 28450, 3 inch male connection APPENDIX 7 Seals SUITABLE MATERIALS FOR SEALS, GASKETS AND HOSES Ethylene propylene rubber (EPDM) ‘Kalrez’ Butyl rubber PTFE encapsulated Gaskets PTFE envelope EPDM return to contents Butyl rubber Hoses Polyethylene Polypropylene Stainless steel (316) EPDM Butyl rubber PTFE 14 For further information BP Logistics Technical & Safety Unit Building A Chertsey Road Sunbury-on-Thames Middlesex TW16 7LL UK www.bpchemicals.com EXCLUSION OF LIABILITY Information contained in this publication is accurate to the best of the knowledge of BP p.l.c. Any information or advice obtained from BP otherwise than by means of this publication and whether relating to BP materials or other materials, is also given in good faith. However, it remains at all times, the responsibility of the customer to ensure that BP materials are suitable for the particular purpose intended. Insofar as materials not manufactured or supplied by BP are used in conjunction with or instead of BP materials, the customer should ensure that he has received from the manufacturer or supplier all the technical data and other information relating to such materials. BP accepts no liability whatsoever (except as otherwise expressly provided by law) arising out of the use of information supplied, the application or processing of the products described herein, the use of other materials in lieu of BP materials in conjunction with such other materials. Published by BP p.l.c. © BP p.l.c. February 2002 bp, and the Helios mark are trade marks of BP p.l.c. Designed by LTD Design Consultants Printed by Clement & Foster 20–8b/2001/1000GB