Optical Smoke Detectors FL5100-600, FL6100-600 • Loop technology with Apollo protocol • M ounted almost flush with ceiling thanks to chamberless technology • A ctivation behaviour can be set by selecting one of five levels • Sealed electronics • V ersions with plastic or stainless steel faceplate Description The Optical Smoke Detector FL5100-600 from the model range SOTERIA® Dimension operates with a chamberless detection technology based on the principle of scattered light. Through a combination of 3 infrared LEDs and 2 photo diodes, smoke particles are detected directly below the detector and are evaluated as alarm. With the modern design that is almost flush with the ceiling, the smoke detector meets even the highest architectural requirements. The integrated microcontroller evaluates the measured data and ensures that smoke can be safely distinguished from noise variables. In addition, intelligent evaluation algorithms compensate for the impact of contamination of the light entrance window. In this way, the response sensitivity of the detector is kept constant for a long time - a further effective step to avoid false alarms. Furthermore, the activation behaviour of the detector can be set on the fire detection control panel by selecting one of five levels to adjust the detector optimally to the respective application. The smoke detector is installed by means of the plastic hollow wall box FL5000-200 which also contains the detector base. The detector is designed for use on the loop with Apollo protocol and is suitable for indoor mounting. The integrated dual-isolator disconnects the loop in the event of a short circuit on the loop. E 2531-CPR-CSP10950 2531-CPR-CSP10952 Building Safety. Building Security. © LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A COMPANY OF THE LABOR STRAUSS GROUP WWW.LABORSTRAUSS.COM • ALL RIGHTS AND CHANGES RESERVED A FL5100-600-FL6100-600_DBL_LST_EN_2117.PDF • PAGE 1 The Optical Smoke Detector FL6100-600 has the same range of functions as the smoke detector FL5100-600. However, it has a sturdy faceplate made of coated stainless steel and tamper-proof screws, which gives it higher resistance to unauthorized intervention or damage. Therefore the detector is ideal for use in prisons, youth centres and health care facilities. Specifications Operating voltage Supply through loop voltage Current consumption typ. 1mA (quiescent) Relative humidity 0 – 95% (no condensation) Protection class IP55 Optical Smoke Detector FL5100-600 Ambient temperature -20°C to +55°C (no icing) Dimensions Ø × H 140 × 38 (mm) Thickness of faceplate 5mm Colour of faceplate white Weight 148g Approvals VdS G218020 2531-CPR-CSP10950 Order number 241170 Order name Optical Smoke Detector/Core/ISM FL5100-600 Optical Smoke Detector FL6100-600 Ambient temperature -40°C to +55°C (no icing) Dimensions Ø × H 170 × 36.5 (mm) Colour of faceplate light grey Weight 321g Approvals VdS G218021 2531-CPR-CSP10952 Order number 241171 Order name Optical Smoke Detector/Core/ISM FL6100-600 Hollow wall box with detector base Dimensions Ø × H 132 × 71 (mm) Ceiling cut-out Ø min. 114mm Thickness of inserted ceiling 9 – 40 (mm) Weight 125g Order number 246170 Order name Detector Base/FLx100 FL5000-200 Building Safety. Building Security. © LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A COMPANY OF THE LABOR STRAUSS GROUP WWW.LABORSTRAUSS.COM • ALL RIGHTS AND CHANGES RESERVED A FL5100-600-FL6100-600_DBL_LST_EN_2117.PDF • PAGE 2