Ave Maria Care 27 Belvoir Street Leicester LE1 6SL Proposed Specification for the Installation of a Level 3 AFD Fire Alarm System. Surveyor – Craig Shaw on the 11th March 2022 The location of the proposed equipment is viewed from the front of the building looking in to define left, right, front and rear. Zone 1 (Ground Floor) 2 Apollo S65 Series Optical smoke detector, Ceiling Mounted to give a 7.5m radius of detection for smouldering, slow and fast burning fires 1 Apollo Resettable Surface Manual Call Point located adjacent Entrance Door. Zone 2 (1st Floor) 4 Apollo S65 Series Optical smoke detector, Ceiling Mounted to give a 7.5m radius of detection for smouldering, slow and fast burning fires 2 Apollo Resettable Surface Manual Call Point located adjacent Landings.. Zone 3 (2nd Floor) 2 Apollo S65 Series Optical smoke detector, Ceiling Mounted to give a 7.5m radius of detection for smouldering, slow and fast burning fires 2 Apollo Resettable Surface Manual Call Point located on Landings. Sounder Circuit 1 Fulleon Conventional sounder located in Ground Floor Office. Sounder Circuit 2 Fulleon Conventional sounder located in 1 st Floor Lobby. Sounder Circuit 3 Fulleon Conventional sounder located in Training Area. Control Equipment 4 Zone C-Tec Conventional Fire Alarm Panel to be located Front Right of Ground Floor Office. Signalling Equipment None Requested. Engineering Notes. ADI Parts Required. 1 x 4 Zone C-Tec Conventional Fire panel (CFP-704-4) 8 x Apollo S65 Optical smoke heads (55000-317) 8 x Apollo detector bases (45681-277) 5 x Apollo MCP (55100-031APO) 3 x Fulleon sounders (540503FULL-0403x) 1 x FP200 Red Fire cable (VFP-215ERH) 1 x Mains Red Isolator (VMIS-R) 3 Days Labour with 2 Men Emergency Lighting. 5 x Bulkheads (ED/LED/M3/E) 2 x 50m 1.0mm Twin&Earth Mains Cable (H62427Y1.0G50) Toolstation Parts Required. 3 x Emergency Light Test Switch. (81000) 3 x Single Pattress Back Box. (61555) 1 to 2 Days Labour 2 Men.