Uploaded by basman george

1769-um013 -en-p

advertisement
PowerFlex 1769-SM2
Compact I/O DSI/Modbus
Communications Module
Firmware Version 1.xxx
User Manual
Important User Information
Solid state equipment has operational characteristics differing from those of
electromechanical equipment. Safety Guidelines for the Application, Installation
and Maintenance of Solid State Controls (Publication SGI-1.1 available from your
local Rockwell Automation sales office or online at http://
www.rockwellautomation.com/literature) describes some important differences
between solid state equipment and hard-wired electromechanical devices. Because
of this difference, and also because of the wide variety of uses for solid state
equipment, all persons responsible for applying this equipment must satisfy
themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or
consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative
purposes. Because of the many variables and requirements associated with any
particular installation, Rockwell Automation, Inc. cannot assume responsibility or
liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of
information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written
permission of Rockwell Automation, Inc. is prohibited.
Throughout this manual, when necessary we use notes to make you aware of safety
considerations.
!!
WARNING: Identifies information about practices or circumstances
that can cause an explosion in a hazardous environment, which may
lead to personal injury or death, property damage, or economic loss.
Important: Identifies information that is critical for successful application and
understanding of the product.
!!
ATTENTION: Identifies information about practices or circumstances
that can lead to personal injury or death, property damage, or economic
loss. Attentions help you identify a hazard, avoid a hazard, and
recognize the consequences.
Shock Hazard labels may be located on or inside the equipment (e.g.,
drive or motor) to alert people that dangerous voltage may be present.
Burn Hazard labels may be located on or inside the equipment (e.g.,
drive or motor) to alert people that surfaces may be at dangerous
temperatures.
Allen-Bradley, PowerFlex, DriveExplorer, DriveExecutive, DriveTools SP, CompactLogix, MicroLogix, DSI, RSNetWorx for
DeviceNet, and ControlFLASH are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Summary of Changes
The information below summarizes the changes made to this manual
since version 1769-UM013B-EN-P (January 2006):
Description
Page(s)
Changed Figures 1.3 and 1.4 to correctly show the wiring of the RJ45
daisy-chained connectors.
1-4 and 1-5
In the “Compatible Products” section, added the PowerFlex 4M and
PowerFlex 40P drives.
1-6
Moved the Module Start-Up Status Indication table from Chapter 1 to
Chapter 2 after the “Applying Power” section.
2-15
Added the subsection “Special Case—Data Entry for 2 Stop Bits
Communication.”
3-8
Changed module Parameters 15 - [RTU Parity 1], 30 - [RTU Parity 2], and 3-17, B-3,
45 - [RTU Parity 3] per 1769-SM2 firmware v2.001 update. The parameter B-5, and B-7
numbers remain the same but the parameter names changed from [RTU
Parity x] to [RTU Format x]. Also, in addition to parity (None, Even or Odd),
the parameter function changed to include choice of stop bits (1 or 2).
In the “Using Reference/Feedback” section, revised table to include
PowerFlex 4M and PowerFlex 40P drives.
4-4
Added the new section “Using RSLinx Classic” to Chapter 8.
8-2
Updated the Logic Command word and Logic Status word information to
include data for all PowerFlex 4-Class drives.
D-1 and D-2
soc-ii
Table of Contents
Preface
About This Manual
Related Documentation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P-1
Rockwell Automation Support. . . . . . . . . . . . . . . . . . . . . . . . P-2
Conventions Used in this Manual . . . . . . . . . . . . . . . . . . . . . P-3
Chapter 1
Getting Started
Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
Single Mode vs. Multi-Drive Mode . . . . . . . . . . . . . . . . . . . . 1-3
Compatible Products . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-6
Required Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-6
Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-7
Quick Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-9
Status Indicators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-10
Chapter 2
Installing the Module
Preparing for an Installation. . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Removing Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
Setting the Configuration Mode Switch. . . . . . . . . . . . . . . . . 2-3
Setting the Operating Mode Switch (Single/Multi-Drive). . . 2-4
Assembling the Module to the Controller . . . . . . . . . . . . . . . 2-5
Mounting the Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6
Replacing the Module within a System . . . . . . . . . . . . . . . . . 2-9
Connecting Drive(s) to the Module . . . . . . . . . . . . . . . . . . . 2-10
Grounding the Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-12
Network Cable Strain Relief . . . . . . . . . . . . . . . . . . . . . . . . 2-14
Applying Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-14
Viewing Start-Up Status Indicators . . . . . . . . . . . . . . . . . . . 2-15
Chapter 3
Configuring the Module
Determining I/O Image Size . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Configuration Tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Configuration Methods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
Controller Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
Parameter Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-12
Using the Optional, External PowerFlex 4-Class HIM . . . . 3-13
Setting the I/O Configuration (Multi-Drive Mode Only). . . 3-14
Setting an Idle Action (Single and Multi-Drive Mode) . . . . 3-15
Setting Drive Node Addresses (Multi-Drive Mode Only) . . 3-16
Configuring the Modbus RTU Master Parameters. . . . . . . . 3-17
Resetting the Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-20
Viewing the Module Status Using Parameters. . . . . . . . . . . 3-21
Flash Updating the Module . . . . . . . . . . . . . . . . . . . . . . . . . 3-22
ii
Table of Contents
Chapter 4
Understanding the I/O Image
Module Control Word . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Module Status Word. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Using Logic Command/Status . . . . . . . . . . . . . . . . . . . . . . . .
Using Reference/Feedback . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 5
4-2
4-3
4-4
4-4
Understanding Explicit Messaging
Formatting Explicit Messages . . . . . . . . . . . . . . . . . . . . . . . . 5-2
Modbus RTU Master Operation Messages . . . . . . . . . . . . . . 5-9
Chapter 6
MicroLogix 1500 Example Ladder Programs
Single Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
Multi-Drive Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-8
Chapter 7
CompactLogix Example Ladder Programs
Single Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
Multi-Drive Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-10
Chapter 8
ControlLogix w/1769-ADN DeviceNet Example Ladder
Program
Single Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-1
Using RSLinx Classic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-2
Using RSNetWorx for DeviceNet . . . . . . . . . . . . . . . . . . . . . 8-3
Setting Up the 1769-ADN . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-4
Registering the 1769-SM2 EDS File . . . . . . . . . . . . . . . . . . . 8-8
PowerFlex 40 Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-12
1769-SM2 Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-12
ControlLogix w/1769-ADN Example Program. . . . . . . . . . 8-13
Example Program Data Table . . . . . . . . . . . . . . . . . . . . . . . 8-21
Chapter 9
Troubleshooting
Locating the Status Indicators . . . . . . . . . . . . . . . . . . . . . . . .
MODULE Status Indicator . . . . . . . . . . . . . . . . . . . . . . . . . .
CH1…CH3 Status Indicators. . . . . . . . . . . . . . . . . . . . . . . . .
Viewing Module Diagnostic Items. . . . . . . . . . . . . . . . . . . . .
Viewing and Clearing Events. . . . . . . . . . . . . . . . . . . . . . . . .
Appendix A
9-1
9-2
9-3
9-4
9-6
Specifications
Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Mechanical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Environmental . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Regulatory Compliance . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DSI Cable Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . .
A-1
A-1
A-1
A-2
A-2
A-2
Table of Contents
Appendix B
iii
Module Parameters
About Parameter Numbers. . . . . . . . . . . . . . . . . . . . . . . . . . . B-1
Parameter List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-1
Appendix C
CIP/DSI Objects
CIP Identity Object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-3
CIP Parameter Object. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-4
DSI Device Object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-7
DSI Parameter Object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-10
DSI Fault Object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-14
DSI Diagnostic Object . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-16
Appendix D
PowerFlex 4-Class Drives Logic Command/Status
Words
Logic Command Word. . . . . . . . . . . . . . . . . . . . . . . . . . . . . D-1
Logic Status Word . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D-2
Glossary
Index
iv
Table of Contents
Preface
About This Manual
Topic
Related Documentation
Conventions Used in this Manual
Rockwell Automation Support
Page
P-1
P-3
P-2
Related Documentation
For:
DriveExplorer™
Refer to:
http://www.ab.com/drives/driveexplorer, and
DriveExplorer online help (1)
DriveTools™ SP
http://www.ab.com/drives/drivetools, and
(includes DriveExecutive) DriveExecutive online help (1)
PowerFlex 4-Class HIM HIM Quick Reference
(22-HIM-A3 / -C2S)
PowerFlex 4 User Manual
PowerFlex® 4 Drive
PowerFlex 4 Quick Start
PowerFlex® 4M Drive
PowerFlex 4M User Manual
PowerFlex 4M Quick Start
PowerFlex® 40 Drive
PowerFlex 40 User Manual
PowerFlex 40 Quick Start
PowerFlex® 40P Drive PowerFlex 40P User Manual
PowerFlex 40P Quick Start
PowerFlex® 400 Drive
PowerFlex 400 User Manual
PowerFlex 400 Quick Start
RSLinx® Classic
Getting Results with RSLinx Guide, and online help (1)
RSLogix™ 500
RSLogix 500 Getting Results Guide, and online help (1)
RSLogix 5000 Getting Results Guide, and online help (1)
RSLogix™ 5000
RSNetWorx™ for
RSNetWorx for DeviceNet Getting Results Guide, and
DeviceNet
online help (1)
MicroLogix™ 1500
MicroLogix 1500 Programmable Controllers User Manual
MicroLogix 1200 and MicroLogix 1500 Programmable
Controllers Reference Manual
CompactLogix™
CompactLogix System User Manual
ControlLogix Gateway System User Manual
ControlLogix®
Modbus RTU
Modbus – ida.org
Specification
PowerFlex 7-Class Drive 20-COMM-H RS-485 HVAC Adapter User Manual
Connectivity
(1)
The online help is installed with the software.
Publication
—
—
22HIM-QR001
22A-UM001
22A-QS-001
22F-UM001
22F-QS-001
22B-UM001
22B-QS-001
22D-UM001
22D-QS-001
22C-UM001
22C-QS-001
LINX-GR001
LG500-GR002
9399-RLD300GR
DNET-GR001
1764-UM001
1762-RM001
1769-UM007
1756-6.5.13
—
20COMM-UM009
P-2
About This Manual
You can view or download publications at http://
literature.rockwellautomation.com. To order paper copies of technical
documentation, contact your local Rockwell Automation distributor or
sales representative.
To find your local Rockwell Automation distributor or sales
representative, visit www.rockwellautomation.com/locations.
For information such as firmware updates or answers to drive-related
questions, go to the Drives Service & Support web site at www.ab.com/
support/abdrives and click on the “Downloads” or “Knowledgebase” link.
Rockwell Automation Support
Rockwell Automation, Inc. offers support services worldwide, with over
75 sales/support offices, over 500 authorized distributors, and over 250
authorized systems integrators located through the United States alone.
In addition, Rockwell Automation, Inc. representatives are in every
major country in the world.
Local Support
Contact your local Rockwell Automation, Inc. representative for:
•
•
•
•
Sales and order support
Product technical training
Warranty support
Support service agreements
Technical Assistance
For technical assistance, please review the information in Chapter 9,
Troubleshooting, first. If you still have problems, then access the
Allen-Bradley Technical Support web site at www.ab.com/support/
abdrives or contact Rockwell Automation, Inc.
About This Manual
P-3
Conventions Used in this Manual
The following conventions are used throughout this manual:
•
Parameter names are shown in the format Parameter xx - [*]. The
xx represents the parameter number. The * represents the parameter
name. For example Parameter 01 - [Config Mode].
•
Menu commands are shown in bold type face and follow the format
Menu > Command. For example, if you read “Select File > Open,”
you should click the File menu and then click the Open command.
•
RSNetWorx for DeviceNet (version 4.01) and RSLinx (version 2.41)
were used for the screen shots in this manual. Different versions of
the software may differ in appearance and procedures.
•
The firmware release is displayed as FRN X.xxx. The “FRN”
signifies Firmware Release Number. The “X” is the major release
number. The “xxx” is the minor update number. This manual is for
Firmware release 1.xxx.
P-4
Notes:
About This Manual
Chapter 1
Getting Started
The 1769-SM2 Compact I/O to DSI module provides a Compact I/O
connection for PowerFlex 4-Class drives. It can be used with a
MicroLogix 1500, CompactLogix, or a remote 1769-based adapter such
as the 1769-ADN.
Topic
Components
Features
Single Mode vs. Multi-Drive Mode
Compatible Products
Page
1-1
1-2
1-3
1-6
Topic
Required Equipment
Safety Precautions
Quick Start
Status Indicators
Page
1-6
1-7
1-9
1-10
Components
Figure 1.1 Components of the Module
➋
➊
MODULE
CH1
CH2
➍
➏
CH3
MODU
LE
CH2
CH3
DSI
DSI
CH1
C
H
1
➐
C
H
1
C
H
2
➑
C
H
2
C
H
3
C
H
3
➒
➌
➓
➎
11
Item Part
Item Part
➊
➋
➌
➍
➎
Bus lever (with locking function)
Movable bus connector with female pins
Upper panel mounting tab
➐
➑
➒
➓
Lower panel mounting tab
11
Terminal block for network communication
shielding and earth ground wire.
➏
Module status indicators (see Chapter 9,
Troubleshooting for details).
Upper DIN rail latch
Lower DIN rail latch
Bus connector with male pins
Nameplate label
DSI connectors
1-2
Getting Started
Features
The 1769-SM2 Compact I/O to DSI module features include:
•
Three Compact I/O connection channels for PowerFlex 4-Class
drives. Up to 3 drives can be connected in Single mode (1 per
channel) and up to 15 drives can be connected in Multi-Drive mode
(5 per channel). Any channel in Multi-Drive mode can also be
configured to operate as a Modbus RTU Master, allowing
connectivity to a maximum of 31 other Modbus RTU Slave devices,
such as PowerFlex 7-Class drives with 20-COMM-H RS485 HVAC
adapters.
•
Use as expansion I/O on MicroLogix 1500 and CompactLogix
controllers or with a remote 1769-based adapter. It receives the
required power from the Compact I/O backplane.
•
Parameter-configurable I/O, including Logic Command/Reference
and Logic Status/Feedback for each connected drive.
•
Explicit messaging (parameter read/write, etc.) support for:
–
MicroLogix 1500 LRP Series C systems when used with
RSLogix 500 v6.30 (or higher)
–
Enhanced CompactLogix processors, such as the -L31, -L32E,
and -L35E
Explicit messaging is NOT available for CompactLogix -L20 and
-L30 processors, or 1769-ADN DeviceNet adapters.
•
User-defined fault actions to determine how the module and
connected drives respond to controllers in idle mode (Idle Action).
•
Bi-color (red/green) status indicators to report the status of the
module and channel communications.
•
Compatibility with various configuration tools to configure the
module and connected drive(s). The tools include an optional,
external PowerFlex 4-Class HIM (22-HIM-A3 or 22-HIM-C2S), and
drive-configuration software such as DriveExplorer v3.01 (or higher)
or DriveExecutive v4.01 (or higher).
Getting Started
1-3
Single Mode vs. Multi-Drive Mode
Single mode is a one-to-one connection, where a channel is connected to
a single PowerFlex 4-Class drive (Figure 1.2).
Figure 1.2 Single Mode Wiring Example
Powerflex 4-Class Drives
1769-SM2
Module
MODULE
CH1
CH1
CH2
CH3
CH2
CH3
C
H
1
AK-U0-RJ45-TB2P
Terminal Block
Connector
AK-U0-RJ45-TB2P
Terminal Block
Connector
AK-U0-RJ45-TB2P
Terminal Block
Connector
C
H
2
C
H
3
22-RJ45CBL-C20 Cable, or User-Supplied Wire
(recommend Belden No. 3105A or equivalent)
with AK-U0-RJ45-TB2P terminal block connectors
Earth Ground
Connection
Ground Wire Connection
(for network communication
shielding)
An additional DSI peripheral device, such as an external PowerFlex
4-Class HIM or Serial Converter module (22-SCM-232) with a software
tool, can be used with each drive. An AK-U0-RJ45-SC1 DSI Splitter
cable can be used to split the RJ45 connector on the drive into two RJ45
connectors.
1-4
Getting Started
Multi-Drive mode enables increased connectivity, where one to five
PowerFlex 4-Class drives can be connected per channel. All of the drives
are daisy-chained to the 1769-SM2 module over RS-485 as shown in
Figure 1.3.
Figure 1.3 Multi-Drive Mode Wiring Example
Up to 5 PowerFlex 4-Class drives
Wiring Tip:
The 1769-SM2 has an
integral terminating
resistor for each channel.
Thus, it is only necessary
to connect a terminating
resistor to the RJ45
terminal block at the last
drive on each channel.
AK-U0-RJ45-TB2P
Terminal Block
Connectors
User-Supplied Wire (recommend
Belden No. 3105A or equivalent)
120 ohm, ¼ Watt
Terminating Resistor
Up to 5 PowerFlex 4-Class drives
1769-SM2
Module
MODULE
CH1
CH1
CH2
CH3
CH2
CH3
C
H
1
AK-U0-RJ45-TB2P
Terminal Block
Connectors
C
H
2
C
H
3
User-Supplied Wire (recommend
Belden No. 3105A or equivalent)
120 ohm, ¼ Watt
Terminating Resistor
Up to 5 PowerFlex 4-Class drives
Earth Ground
Connection
Ground Wire Connection
(for network
communication
cable shielding)
AK-U0-RJ45-TB2P
Terminal Block
Connectors
User-Supplied Wire (recommend
Belden No. 3105A or equivalent)
120 ohm , ¼ Watt
Terminating Resistor
Getting Started
1-5
In Multi-Drive mode, any channel can be configured for “RTU Master”
operation (Figure 1.4). This enables connection of up to 31 RTU Slave
devices, such as PowerFlex 7-Class drives with 20-COMM-H RS485
HVAC adapters.
Figure 1.4 Multi-Drive Mode and Modbus RTU Master Mode Wiring Example
CH1 - Multi-Drive Mode (up to 5 PowerFlex 4-Class Drives)
Wiring Tip:
The 1769-SM2 has an
integral terminating
resistor for each channel.
Thus, it is only necessary
to connect a terminating
resistor to the RJ45
terminal block at the last
drive on each channel.
AK-U0-RJ45-TB2P
Terminal Block
Connectors
User-Supplied Wire (recommend
Belden No. 3105A or equivalent)
120 ohm, ¼ Watt
Terminating Resistor
CH2 - Multi-Drive Mode (up to 5 PowerFlex 4-Class Drives)
1769-SM2
Module
MODULE
CH1
CH1
CH2
CH3
CH2
CH3
C
H
1
AK-U0-RJ45-TB2P
Terminal Block
Connectors
C
H
2
C
H
3
Earth Ground
Connection
User-Supplied Wire (recommend
Belden No. 3105A or equivalent)
120 ohm, ¼ Watt
Terminating Resistor
CH3 - Modbus RTU Master Mode (up to 31 Devices)
PowerFlex 7-Class Drives
with 20-COMM-H RS485 HVAC
Communication Adapters
Generic
Modbus RTU
Device
Ground Wire Connection
(for network
communication
cable shielding)
User-Supplied Wire (recommend
Belden No. 3105A or equivalent)
...
120 ohm, ¼ Watt
Terminating Resistor
1-6
Getting Started
Benefits of Multi-Drive mode include:
•
Lower hardware costs. Only one 1769-SM2 is needed for up to five
PowerFlex 4-Class drives per channel (15 total).
•
Controller can independently control, monitor, and read/write
parameters for all five drives on each channel (same functionality as
Single mode).
The trade-offs of Multi-Drive mode include:
•
Since the RS-485 ports are used for daisy-chaining the drives,
additional DSI peripheral devices cannot be used with the drives.
This includes an optional, external PowerFlex 4-Class HIM
(22-HIM-A3 or 22-HIM-C2S) or a 22-SCM-232 Serial Converter
module with a software tool. The AK-U0-RJ45-SC1 DSI Splitter
cable cannot be used to add a second connection for a DSI peripheral
device.
Compatible Products
The 1769-SM2 module is compatible with Allen-Bradley PowerFlex
4-Class (Component class) drives and other products that support DSI.
At the time of publication, compatible products include:
•
•
•
•
•
PowerFlex 4 drives
PowerFlex 4M drives
PowerFlex 40 drives
PowerFlex 40P drives
PowerFlex 400 drives
When the 1769-SM2 is used in Multi-Drive as a Modbus RTU Master,
other Modbus RTU Slave devices, such as PowerFlex 7-Class drives
with 20-COMM-H RS485 HVAC adapters, can also be connected.
Required Equipment
Equipment Shipped with the Module
When you unpack the module, verify that the package includes:
❑ One 1769-SM2 module
❑ This manual
Getting Started
1-7
User-Supplied Equipment
To install and configure the 1769-SM2 module, you must supply:
❑ A small flathead screwdriver
❑ Communications cable 22-RJ45CBL-C20
- orAK-U0-RJ45-TB2P terminal block connectors (one for each
channel connection and one for each drive connection) and twisted
pair network wiring (Belden No. 3105A or equivalent)
❑ Configuration tool, such as:
– PowerFlex 4-Class HIM (22-HIM-A3 or 22-HIM-C2S)—
required to access module parameters if not using DriveExplorer
software or DriveExecutive software
– DriveExplorer (version 3.01 or higher)
– DriveExecutive stand-alone software (version 4.01 or higher) or
bundled with the DriveTools SP suite (version 4.01 or higher)
– RSNetWorx for DeviceNet
❑ Controller configuration software (such as RSLogix 500/5000)
Safety Precautions
Please read the following safety precautions carefully.
!
!
ATTENTION: Risk of injury or death exists. The PowerFlex drive
may contain high voltages that can cause injury or death. Remove all
power from the PowerFlex drive, and then verify power has been
removed before installing or removing the module.
ATTENTION: Risk of injury or equipment damage exists. Only
personnel familiar with drive and power products and the associated
machinery should plan or implement the installation, start-up,
configuration, and subsequent maintenance of the product using the
module. Failure to comply may result in injury and/or equipment
damage.
!
ATTENTION: Risk of injury or equipment damage exists. If the
module is transmitting control I/O to the drive, the drive may fault when
you reset the module. Determine how your drive will respond before
resetting the module.
!
ATTENTION: Risk of injury or equipment damage exists. When a
system is configured for the first time, there may be unintended or
incorrect machine motion. Disconnect the motor from the machine or
process during initial system testing.
1-8
Getting Started
!
!
!
ATTENTION: Risk of injury or equipment damage exists.
Parameters 04 - [Idle Action 1], 19 - [Idle Action 2], and 34 - [Idle
Action 3] let you determine the action of the module and connected
drives if communications are disrupted. By default, these parameters
fault the drive. You can set these parameters so that the drive continues
to run. Precautions should be taken to ensure that the settings of these
parameters do not create a risk of injury or equipment damage. When
commissioning the drive, verify that your system responds correctly to
various situations (for example, a disconnected cable or a faulted
controller).
ATTENTION: Risk of injury or equipment damage exists. The
examples in this publication are intended solely for purposes of
example. There are many variables and requirements with any
application. Rockwell Automation, Inc. does not assume responsibility
or liability (to include intellectual property liability) for actual use of
the examples shown in this publication.
ATTENTION: This equipment is intended for use in a Pollution
Degree 2 industrial environment, in overvoltage Category II
applications (as defined in IEC publication 60664-1), at altitudes up to
2000 meters without derating.
This equipment is considered Group 1, Class A industrial equipment
according to IEC/CISPR Publication 11. Without appropriate
precautions, there may be potential difficulties ensuring
electromagnetic compatibility in other environments due to conducted
as well as radiated disturbance.
This equipment is supplied as “open type” equipment. It must be
mounted within an enclosure that is suitably designed for those specific
environmental conditions that will be present and appropriately
designed to prevent personal injury resulting from accessibility to live
parts. The interior of the enclosure must be accessible only by the use
of a tool. Subsequent sections of this publication may contain
additional information regarding specific enclosure type ratings that are
required to comply with certain product safety certifications.
See NEMA Standards publication 250 and IEC publication 60529, as
applicable, for explanations of the degrees of protection provided by
different types of enclosure. Also, see the appropriate sections in this
publication, as well as the Allen-Bradley publication 1770-4.1
(“Industrial Automation Wiring and Grounding Guidelines”), for
additional installation requirements pertaining to this equipment.
Getting Started
1-9
Quick Start
This section is provided to help experienced users quickly start using the
1769-SM2 Compact I/O to DSI module. If you are unsure how to
complete a step, refer to the referenced chapter.
Step
1
2
3
Action
Review the safety precautions for the module.
Verify that the drive is properly installed.
Install the module.
4
Verify that the controller is not powered. Connect the
module to the controller backplane bus. Then connect
the module to the drive(s) using communications cable
22-RJ45CBL-C20 or AK-U0-RJ45-TB2P terminal block
connectors and communications network wiring.
Apply power to the module.
5
The module receives power from the controller. Apply
power to the controller. The MODULE indicator should
be green or flashing green. If it flashes red, there is a
problem. Refer to Chapter 9, Troubleshooting.
Configure the module for your application.
6
7
8
Refer to…
Throughout This Manual
Drive User Manual
Chapter 2,
Installing the Module
Chapter 3,
Set the following parameters for the module as required Configuring the Module
by your application:
• I/O configuration.
• Fault actions.
Apply power to the drive.
Configure the controller to communicate with the
module.
Create a ladder logic program.
Use a programming tool such as RSLogix to create a
ladder logic program that enables you to:
• Control the module and connected drive.
• Monitor or configure the drive using Explicit
Messages.
Drive User Manual
Depending on the type of
controller and 1769-SM2
operating mode:
• Chapter 6,
MicroLogix 1500
Example Ladder
Programs
• Chapter 7,
CompactLogix
Example Ladder
Programs
• Chapter 8,
ControlLogix w/
1769-ADN DeviceNet
Example Ladder
Program
Getting Started
Status Indicators
The module uses four status indicators to report its operating status.
They can be viewed on the front of the module (Figure 1.5).
Figure 1.5 Status Indicators
➊
MODULE
MODULE
CH1
CH2
CH1
CH3
CH2
CH3
DSI
1-10
C
H
1
➋
C
H
2
➍
➌
C
H
3
Item
Name
➊
➋
➌
➍
MODULE
CH1
CH2
CH3
After installing the module and applying power to the drive(s), refer to
Viewing Start-Up Status Indicators on page 2-15 for possible start-up
status indications and their descriptions.
Chapter 2
Installing the Module
This chapter provides instructions for installing the 1769-SM2 as an
expansion I/O module on MicroLogix 1500 and CompactLogix
controllers, or with a remote 1769-based adapter.
Topic
Preparing for an Installation
Removing Power
Setting the Configuration Mode Switch
Setting the Operating Mode Switch (Single/Multi-Drive)
Assembling the Module to the Controller
Mounting the Module
Replacing the Module within a System
Connecting Drive(s) to the Module
Grounding the Module
Network Cable Strain Relief
Applying Power
Viewing Start-Up Status Indicators
Page
2-1
2-2
2-3
2-4
2-5
2-6
2-9
2-10
2-12
2-14
2-14
2-15
Preparing for an Installation
Consider the following when installing the 1769-SM2 module:
•
Verify that you have all required equipment. Refer to Required
Equipment on page 1-6.
•
A MicroLogix 1500 Base Unit or Compact I/O power supply has
limits in the amount of +5V dc and +24V dc current it can supply to
modules in its I/O bank. These limits depend on the catalog number
(e.g. 1769-PA2) of the power supply. A bank of modules must not
exceed the current limits of the MicroLogix 1500 Base Unit or I/O
bank power supply.
Refer to the MicroLogix 1500 User Manual (publication
1764-UM001) or the Compact 1769 Expansion I/O Power Supplies
Installation Instructions (publication 1769-5.14).
•
The module has a distance rating of four. Therefore, the module must
be within four modules of the I/O bank’s power supply.
2-2
Installing the Module
!
ATTENTION: Risk of equipment damage exists. The 1769-SM2
module contains ESD (Electrostatic Discharge) sensitive parts that can
be damaged if you do not follow ESD control procedures. Static control
precautions are required when handling the module. If you are
unfamiliar with static control procedures, refer to Guarding Against
Electrostatic Damage (publication 8000-4.5.2).
Removing Power
!
ATTENTION: Risk of equipment damage exists. Remove power
before installing or removing the 1769-SM2 module. When you install
or remove the module with power applied, an electrical arc may occur.
An electrical arc can cause personal injury or equipment damage by:
•
Sending an erroneous signal to your system’s field devices, causing
unintended machine motion.
•
Causing an explosion in a hazardous environment.
Electrical arcing causes excessive wear to contacts on both the module
and its mating connector. Worn contacts may create electrical
resistance.
Installing the Module
2-3
Setting the Configuration Mode Switch
Before installing the module, make sure its Configuration Mode Switch
is correctly set. See Configuration Methods on page 3-3 for details on
the Controller and Parameter configuration modes. Then set the
Configuration Mode Switch (SW1 in Figure 2.1) for your application.
Figure 2.1 Configuration Mode and Single/Multi-Drive Operation Switch Locations
Configuration
Mode Switch
(SW1)
Operating
Mode Switch
(SW2)
SW1 Setting
CONT (Controller)
back position
(Controller
Position)
(Parameter
Position)
CONT
1X
PARAM
5X
(Single
Position)
(Multi-Drive
Position)
Description
Default setting—The 1769-SM2 module uses the configuration
data downloaded from the controller on power-up and when the
controller is placed in run mode.
PARAM (Parameter) The 1769-SM2 module uses its internal parameter settings to
front position
configure the module.
2-4
Installing the Module
Setting the Operating Mode Switch (Single/Multi-Drive)
Before installing the module, set its Operating Mode Switch (SW2 in
Figure 2.1) for Single or Multi-Drive operation. All channels (CH1,
CH2, and CH3) will operate in the selected mode.
SW2 Setting
1X (Single mode)
back position
Description
Default setting — sets the 1769-SM2 module for Single mode
using a single drive connection (one drive per channel).
Important: In Single mode, only one drive can be connected per
channel. Connections to multiple drives must be removed since
all powered and connected hosts will respond to any message
sent by the module.
5X (Multi-Drive mode) Sets the 1769-SM2 module for Multi-Drive mode using up to five
front position
PowerFlex 4-Class drives per channel.
In Multi-Drive mode, DSI peripherals such as the 22-HIM-A3 /
-C2S Human Interface Module, 22-SCM-232 serial converter, etc.
CANNOT be used. They will not operate with the 1769-SM2
module or drives.
The specific number of drives used in Multi-Drive mode for each
channel and a unique address for each drive must be configured
using 1769-SM2 module parameters. For instructions, see
Setting the I/O Configuration (Multi-Drive Mode Only) on
page 3-14 and Setting Drive Node Addresses (Multi-Drive Mode
Only) on page 3-16.
NOTE: In Multi-Drive mode, each channel can be independently
configured for Modbus RTU Master operation by setting the
respective channel’s [DSI I/O Cfg] parameter to “5” (RTU Master).
This enables up to 31 RTU slave devices, such as PowerFlex
7-Class drives with 20-COMM-H RS485 HVAC adapters to be
connected to that channel.
Important: A new switch setting is recognized only when power is
applied to the module, or the module is reset. If you change
a setting, cycle power or reset the module.
The Configuration Mode Switch (SW1) and Operating Mode Switch
(SW2) settings can be verified by respectively viewing module
Parameters 01 - [Config Mode] and 02 - [DSI Mode] using an
optional, external PowerFlex 4-Class HIM, DriveExplorer software or
DriveExecutive software.
Installing the Module
2-5
Assembling the Module to the Controller
The 1769-SM2 module can be attached to adjacent controller modules
before or after mounting. For mounting instructions, see Panel
Mounting on page 2-6 or DIN Rail Mounting on page 2-8. To work with
a system that is already mounted, see Replacing the Module within a
System on page 2-9.
Figure 2.2 and the following procedure describes how to assemble the
Compact I/O system.
Figure 2.2 Assembling 1769-SM2 Module to Compact I/O System
A
D
E
C
B
G
B
F
1. Disconnect power.
2. Check that the bus lever (A) of the 1769-SM2 module is in the
unlocked (fully right) position.
3. Use the upper and lower tongue-and-groove slots (B) to secure the
modules together.
4. Move the 1769-SM2 module back along the tongue-and-groove slots
until the bus connectors (C) line up with each other.
5. Use your fingers or a small screwdriver to push the bus lever back
slightly to clear the positioning tab (D).
6. Move the 1769-SM2 module’s bus lever fully to the left (E) until it
clicks. Ensure it is locked firmly in place.
!
ATTENTION: Risk of equipment damage exists. When attaching the
1769-SM2 module to a Compact I/O system, it is very important that
the bus connectors are securely locked together to ensure proper
electrical connection. Failure to do this may cause an electrical arc,
which can cause personal injury or equipment damage.
2-6
Installing the Module
7. Attach an end cap terminator (F) to the last module in the system by
using the tongue-and-groove slots as before.
8. Lock the end cap bus terminator (G).
Important: A 1769-ECR or 1769-ECL right or left end cap must be
used to terminate the end of the serial communication
bus.
Mounting the Module
Minimum Spacing
Maintain spacing from enclosure walls, wireways, adjacent equipment,
etc. Allow 50 mm (2 in.) of space on all sides for adequate ventilation as
shown:
Compact I/O
End Cap or Cable
Compact I/O
Compact I/O
Controller
Side
Compact I/O
Top
Compact I/O
!
ATTENTION: Risk of equipment damage exists. During panel or
DIN rail mounting of all devices, be sure that all debris (metal chips,
wire strands, etc.) is kept from falling into the 1769-SM2 module.
Debris that falls into the module could cause damage on power up.
Side
Bottom
Allow at least 140 mm (5.5 in.) of enclosure depth to accommodate the
1769-SM2 module.
Panel Mounting
Mount the 1769-SM2 module to a panel using two screws per module.
Use M4 or #8 panhead screws (not included). Mounting screws are
required on every module.
Installing the Module
2-7
Panel Mounting Using the Dimensional Drawing
NOTE: All dimensions are in mm (inches). Hole spacing tolerance is
±0.4 mm (0.016 in.).
Figure 2.3 1769-SM2 Module with MicroLogix 1500 Base Unit and Processor
168 mm
(6.62 in)
35 mm
(1.38 in)
35 mm
(1.38 in)
DPI / SCANport
118 mm (4.65 in)
59 mm
(2.32 in)
59 mm
(2.32 in)
122.6 mm (4.83 in)
132 mm (5.19 in)
147 mm
(5.79 in)
MODULE
CH1
CH2
CH3
C
H
1
C
H
2
C
H
3
13.5 mm
(0.53 in)
DIN Rail
Center Line
28.5 mm
(1.12 in)
147.4 mm (5.81 in)
Mounting Hole
Dimension
14.7 mm
(0.58 in)
Figure 2.4 1769-SM2 Module with CompactLogix Controller
35 mm
(1.38 in)
35 mm
(1.38 in)
MODULE
CH1
C
H
1
C
H
2
C
H
3
DIN Rail
Center Line
14.7 mm
(0.58 in)
28.5 mm
(1.12 in)
CH2
CH3
147.4 mm (5.81 in)
35 mm
(1.38 in)
70 mm
(2.76 in)
35 mm 35 mm
(1.38 in) (1.38 in)
118 mm (4.65 in)
59 mm
(2.32 in)
59 mm
(2.32 in)
122.6 mm (4.83 in)
132 mm (5.19 in)
40 mm
(1.58 in)
35 mm
(1.38 in)
DPI / SCANport
50 mm
(1.97 in)
Mounting Hole
Dimension
Installing the Module
Figure 2.5 1769-SM2 Module with Remote 1769-Based Adapter
NS
DIAG
70 mm
(2.76 in)
35 mm 35 mm
(1.38 in) (1.38 in)
35 mm
(1.38 in)
35 mm
(1.38 in)
28.5 mm
(1.12 in)
MODULE
CH1
CH2
CH3
C
H
1
C
H
2
C
H
3
DIN Rail
Center Line
147.4 mm (5.81 in)
59 mm
59 mm
(2.32 in)
(2.32 in)
118 mm (4.65 in)
122.6 mm (4.83 in)
MS
IO
35 mm
(1.38 in)
35 mm
(1.38 in)
DPI / SCANport
50 mm
(1.97 in)
40 mm
(1.58 in)
Mounting Hole
Dimension
132 mm (5.19 in)
2-8
14.7 mm
(0.58 in)
Panel Mounting Procedure Using Module as a Template
The following procedure enables you to use the assembled modules as a
template for drilling holes in the panel. Due to module mounting hole
tolerance, it is important to follow these steps:
1. On a clean work surface, assemble no more than three modules.
2. Using the assembled modules as a template, carefully mark the
center of all module-mounting holes on the panel.
3. Return the assembled modules to the clean work surface, including
any previously mounted modules.
4. Drill and tap the mounting holes for the recommended M4 or #8
screw (not included).
5. Place the modules back on the panel, and check for proper hole
alignment.
6. Attach the modules to the panel using the mounting screws.
DIN Rail Mounting
The 1769-SM2 module can be mounted using these DIN rails:
• 35 x 7.5 mm (EN 50 022 - 35 x 7.5)
• 35 x 15 mm (EN 50 022 - 35 x 15)
When mounting the module to a DIN rail, make sure that the latches are
closed and properly securing the module.
Installing the Module
2-9
Replacing the Module within a System
The 1769-SM2 module can be replaced while the system is mounted to a
panel (or DIN rail).
!
ATTENTION: Risk of equipment damage exists. Remove power
before installing or removing the 1769-SM2 module. When you install
or remove the module with power applied, an electrical arc may occur.
An electrical arc can cause personal injury or equipment damage by:
•
Sending an erroneous signal to your system’s field devices, causing
unintended machine motion.
• Causing an explosion in a hazardous environment.
Electrical arcing causes excessive wear to contacts on both the module
and its mating connector. Worn contacts may create electrical
resistance.
1. Remove power.
2. Unplug the communications cable from each port (CH1, CH2, CH3)
on the 1769-SM2 module. Note each drive and the port to which it is
connected.
3. Remove the upper and lower mounting screws from the module (or
open the DIN latches using a flat-blade screwdriver).
4. On the right-side adjacent module, move its bus lever to the right
(unlock) to disconnect it from the module being removed.
5. Gently slide the disconnected 1769-SM2 module forward.
If you feel excessive resistance, make sure that you disconnected the
module from the bus and that you removed both mounting screws (or
opened the DIN latches).
TIP: It may be necessary to rock the module slightly from front to
back to remove it or, in a panel-mounted system, to loosen the screws
of adjacent modules.
6. Before installing the replacement 1769-SM2 module, be sure that the
bus lever on the right-side adjacent module is in the unlocked (fully
right) position.
7. Slide the replacement 1769-SM2 module into the open slot.
2-10
Installing the Module
8. Connect the 1769-SM2 module and adjacent modules together by
locking (fully left) the bus levers on the 1769-SM2 module and the
right-side adjacent module.
9. Replace the mounting screws (or snap the module onto the DIN rail).
10. Plug the appropriate communications cable into its respective port on
the 1769-SM2 module.
11. Restore 1769-SM2 module configuration using an appropriate
configuration tool.
Connecting Drive(s) to the Module
NOTE: For Single or Multi-Drive mode, there is a maximum cable
distance limit per channel. See DSI Cable Requirements on page A-2 for
more information.
For network wiring diagram examples, see the following figures:
1769-SM2 Operating Mode
Single mode (Default)
Multi-Drive mode
Multi-Drive mode with Modbus RTU Master
Network Wiring
Diagram Example…
Figure 1.2
Figure 1.3
Figure 1.4
Single Mode
When the 1769-SM2 module is operated in Single drive mode, each
drive is directly connected to a channel port (CH1, CH2 or CH3) on the
module. Use either a 22-RJ45CBL-C20 communications cable for each
channel or AK-U0-RJ45-TB2P terminal block connectors and twisted
pair network wiring (Belden No. 3105A or equivalent).
Important: When connecting a drive to the channel port using
AK-U0-RJ45-TB2P terminal block connectors and twisted
pair network wiring, the following drive parameters MUST
be configured to the settings shown so that the 1769-SM2
module will communicate with the drive:
Drive Parameter
A103 - [Comm Data Rate]
A107 - [Comm Format]
Setting
“4” (19.2K)
“0” (RTU 8-N-1)
Changes to these drive parameters require the drive to be
reset for the new settings to take effect.
Installing the Module
2-11
When connecting a drive to the channel port using 22-RJ45CBL-C20
communications cable, the above drive parameters do not require
configuration because the drive senses that a DSI peripheral is connected
and it ignores these parameter settings.
Multi-Drive Mode
For Multi-Drive mode, each channel port MUST be connected to the
drives via daisy-chaining using AK-U0-RJ45-TB2P terminal block
connectors (one for the port connection and one for each drive
connection) and twisted pair network wiring (Belden No. 3105A or
equivalent). The 22-RJ45CBL-C20 communications cable and splitter
cables cannot be used.
Important: The following drive parameters MUST be configured to the
settings shown so that the 1769-SM2 module will
communicate with the drives:
Drive Parameter
A103 - [Comm Data Rate]
A104 - [Comm Node Addr]
A107 - [Comm Format]
Setting
“4” (19.2K)
Value of Drive Addr x parameter in the
1769-SM2
“0” (RTU 8-N-1)
Changes to these drive parameters require the drive to be
reset for the new settings to take effect.
Installing the Module
Grounding the Module
The 1769-SM2 module is intended to be mounted to a well-grounded
mounting surface such as a metal panel. Additional grounding
connections from the module’s mounting tabs or DIN rail (if used) are
not required unless the mounting surface cannot be grounded. Refer to
Industrial Automation Wiring and Grounding Guidelines, publication
1770-4.1, for additional information.
Shielded Connector Grounding Requirements
When using the 22-RJ45CBL-20 cable, which has shielded connectors,
the shields are all grounded to the chassis terminal block on the
1769-SM2 module (item 11 in Figure 1.1). However, the user must:
•
Install a wire from the chassis terminal block on the 1769-SM2
module to a grounded, conductive surface (i.e. metal panel). See
Figure 2.6.
•
Remove the shield connection to chassis ground at the drive I/O
block shield terminal.
Drive
PowerFlex 4
PowerFlex 4M
PowerFlex 40
PowerFlex 40P
PowerFlex 400
Drive I/O Block
Terminal 16
Terminal 16
Terminal 19
Terminal 19
Terminal 20
Figure 2.6 Shielded Connector Grounding Details
DSI / Modbus RTU
2-12
MODULE
CH1
CH2
CH3
C
H
1
To Drive 1
C
H
2
To Drive 2
C
H
3
To Drive 3
Installing the Module
2-13
Unshielded Connector Grounding Requirements
When using twisted pair network wiring with unshielded
AK-U0-RJ45-TB2P connectors, ground the RJ45 socket on the drive by
connecting the drive chassis ground power terminal to the I/O block
shield terminal.
Drive
PowerFlex 4
PowerFlex 4M
PowerFlex 40
PowerFlex 40P
PowerFlex 400
Drive I/O Block
Terminal 16
Terminal 16
Terminal 19
Terminal 19
Terminal 20
The 1769-SM2 module’s RJ45 connectors (CH1, CH2, and CH3), which
are electrically common, should be grounded by attaching a drain wire
from the 1769-SM2 terminal block (item 11 in Figure 1.1) to a grounded,
conductive surface (i.e. metal panel). If shielded cable (not required) is
used, the cable shield should also be connected to the chassis by
attaching the cable shield to the 1769-SM2 terminal block (Figure 2.7).
Good wiring practice dictates that the cable shield be terminated to the
chassis at only one point along the cable to prevent ground loops from
occurring. The chassis terminal block on the 1769-SM2 module is
provided as a convenient place for this termination.
Figure 2.7 Unshielded Connector Grounding Details
DSI / Modbus RTU
To Drive 1
To Drive 2
...
MODULE
CH1
CH2
CH3
To Drive 1
To Drive 2
C
H
1
...
C
H
2
C
H
3
To Drive 1
To Drive 2
...
2-14
Installing the Module
Network Cable Strain Relief
Some type of strain relief should be provided for the communication
cables within 12 inches (305 mm) of the 1769-SM2 module. This may
include wireways, cable ties, panel mounted strain reliefs, or some other
appropriate strain relief device.
Applying Power
!
ATTENTION: Risk of equipment damage, injury, or death exists.
Unpredictable operation may occur if you fail to verify that parameter
settings are compatible with your application. Verify that settings are
compatible with your application before applying power to the drive.
1. Apply power to the controller. The status indicators can be viewed on
the front of the 1769-SM2 module after power has been applied.
2. Apply power to the drive(s). When you apply power to the
1769-SM2 module, controller, and drives for the first time, the status
indicators should be green after an initialization. If the status
indicators go red, there is a problem. Refer to Chapter 9,
Troubleshooting.
Installing the Module
2-15
Viewing Start-Up Status Indicators
Status indicators for the communication module can be viewed on the
front of the module (Figure 2.8) after power has been applied. Possible
start-up status indications are shown in Table 2.A.
Figure 2.8 Module Status Indictors
➊
MODULE
MODULE
CH2
CH1
CH3
CH2
CH3
DSI
CH1
C
H
1
➋
C
H
2
➍
➌
C
H
3
Table 2.A Module Start-Up Status Indications
Item
➊
➋
➌
➍
(1)
Status
Status(1) Description
Indicator
MODULE Green
Normal Operation. The module has established
communications with the controller.
Flashing The module is establishing communications with the
Green
controller.
CH1
Green
Normal Operation. CH1 is operating and is transferring I/O
data between the controller and the drive(s).
Flashing Normal Operation. CH1 is operating but is not transferring
Green
I/O data between the controller and the drive(s).
CH2
Green
Normal Operation. CH2 is operating and is transferring I/O
data between the controller and the drive(s).
Flashing Normal Operation. CH2 is operating but is not transferring
Green
I/O data between the controller and the drive(s).
CH3
Green
Normal Operation. CH3 is operating and is transferring I/O
data between the controller and the drive(s).
Flashing Normal Operation. CH3 is operating but is not transferring
Green
I/O data between the controller and the drive(s).
If all status indicators are off, the module is not receiving power. Refer to Chapter 2, Installing the
Module, for instructions on installing the module.
For more details on status indicator operation, see page 9-2 and
page 9-3.
2-16
Notes:
Installing the Module
Chapter 3
Configuring the Module
This chapter provides instructions and information for setting the
parameters in the 1769-SM2 module.
Topic
Determining I/O Image Size
Configuration Tools
Configuration Methods
Controller Mode
Parameter Mode
Using the Optional, External PowerFlex 4-Class HIM
Setting the I/O Configuration (Multi-Drive Mode Only)
Setting an Idle Action (Single and Multi-Drive Mode)
Setting Drive Node Addresses (Multi-Drive Mode Only)
Configuring the Modbus RTU Master Parameters
Resetting the Module
Viewing the Module Status Using Parameters
Flash Updating the Module
Page
3-1
3-2
3-3
3-3
3-12
3-13
3-14
3-15
3-16
3-17
3-20
3-21
3-22
For a list of parameters, refer to Appendix B, Module Parameters. For
definitions of terms in this chapter, refer to the Glossary.
Determining I/O Image Size
Single Mode
When the module is in Single mode, the I/O image is comprised of a
maximum of 7 words (Table 3.A).
Table 3.A I/O Image Table for Single Mode
Output Image
Input Image
Module Control Word
Logic Command
Reference
Module Status Word
Logic Status
Feedback
CH1
1
2
Word
CH2
0
3
4
CH3
5
6
TIP: When using Single mode, it is recommended to set the I/O size to
7 Input words and 7 Output words. This accommodates one drive per
channel, even if a channel is left unused for future use.
3-2
Configuring the Module
Multi-Drive Mode
When the module is in Multi-Drive mode, the I/O image is comprised of
a maximum of 31 words (Table 3.B).
Table 3.B I/O Image Table for Multi-Drive Mode
Drive 0
Drive 1
Drive 2
Drive 3
Drive 4
Output Image
Input Image
Module Control Word
Logic Command
Reference
Logic Command
Reference
Logic Command
Reference
Logic Command
Reference
Logic Command
Reference
Module Status Word
Logic Status
Feedback
Logic Status
Feedback
Logic Status
Feedback
Logic Status
Feedback
Logic Status
Feedback
CH1
1
2
3
4
5
6
7
8
9
10
Word
CH2
0
11
12
13
14
15
16
17
18
19
20
CH3
21
22
23
24
25
26
27
28
29
30
TIP: When using Multi-Drive mode, it is recommended to set the I/O
size to 31 Input words and 31 Output words. This accommodates up to 5
drives per channel, even if a channel is left unused for future use.
Configure a smaller I/O size only if there is a limited amount of I/O
available on a controller.
For additional information on configuring the I/O image size, refer to
Chapter 4, Understanding the I/O Image.
Configuration Tools
The 1769-SM2 module stores parameters and other information in its
own non-volatile memory. You must, therefore, access the module to
view and edit its parameters. The following tools can be used to access
the module parameters:
Tool
PowerFlex 4-Class HIM
(22-HIM-A3 or 22-HIM-C2S)
DriveExplorer Software
(version 3.01 or higher)
DriveExecutive Software
(version 4.01 or higher)
RSLogix 500
RSLogix 5000
RSNetWorx for DeviceNet
Refer to…
Page 3-13
http://www.ab.com/drives/driveexplorer, or
DriveExplorer online help (installed with the software)
http://www.ab.com/drives/drivetools, or
DriveExecutive online help (installed with the software)
LG500-GR001
9399-RLD300GR
DNET-GR001
Configuring the Module
3-3
Configuration Methods
The 1769-SM2 module has two methods of configuration, which are
determined by the Configuration Mode Switch (SW1 in Figure 2.1):
• Controller mode—The 1769-SM2 uses the configuration data
downloaded from the controller on power-up and when the controller
is placed in run mode. The data is configured using RSLogix 500,
RSLogix 5000 or RSNetWorx for DeviceNet.
• Parameter mode—The 1769-SM2 uses its internal parameter settings
to configure the module. The data is configured using an optional,
external PowerFlex 4-Class HIM, DriveExplorer, or DriveExecutive.
Only one method can be selected, and it is used for all three channels.
Controller Mode
When the Configuration Mode Switch (SW1 in Figure 2.1) is in the
default CONT (Controller) position, the 1769-SM2 uses the configuration
data downloaded from the controller on power-up and when the controller
is placed in run mode. Depending on the controller, configuration data is
allocated and entered using RSLogix500 or RSLogix 5000.
Configuration Data
The 1769-SM2 module contains a set of 42 words of configuration data
that is used to configure the module's behavior (Table 3.C). A software
tool, such as RSLogix 500, RSLogix 5000 or RSNetWorx for DeviceNet
is used to read/write the configuration data.
Table 3.C 1769-SM2 Module Configuration Data
Parameter Name
Idle Action
Flt Cfg Logic
Flt Cfg Ref
DSI I/O Cfg
Drive 0 Addr
Drive 1 Addr
Drive 2 Addr
Drive 3 Addr
Drive 4 Addr
RTU Baud Rate
RTU Format
RTU Rx Delay
RTU Tx Delay
RTU Msg Timeout
CH1
Word 0
Word 1
Word 2
Word 3
Word 4
Word 5
Word 6
Word 7
Word 8
Word 9
Word 10
Word 11
Word 12
Word 13
CH2
Word 14
Word 15
Word 16
Word 17
Word 18
Word 19
Word 20
Word 21
Word 22
Word 23
Word 24
Word 25
Word 26
Word 27
CH3
Word 28
Word 29
Word 30
Word 31
Word 32
Word 33
Word 34
Word 35
Word 36
Word 37
Word 38
Word 39
Word 40
Word 41
3-4
Configuring the Module
The configuration data directly correlates to the module parameters.
Refer to Appendix B for more information.
Entering MicroLogix 1500 Configuration Data Using RSLogix 500
Before v6.30
Earlier versions of RSLogix 500 can be used, but the configuration data
must be entered in raw form in a Data Config table following the format
in Table 3.C. However, RSLogix 500 v6.30 (or higher) is highly
recommended for use with the 1769-SM2 because it contains a dedicated
I/O configuration window for the module to simplify the configuration
process. Version 6.30 is also required to perform explicit messaging,
such as parameter reads/writes.
Entering MicroLogix 1500 Configuration Data Using RSLogix 500
v6.30 (or higher)
Allocate and enter the configuration data by performing these steps:
1. In the RSLogix 500 treeview, double-click on I/O Configuration to
open the I/O Configuration window. Double-click the 1769-SM2 in
the Current Cards Available list to add the module to the controller
system. Select the “1769-SM2” row and click the Adv Config
command button. The 1769-SM2 I/O Configuration window
(Figure 3.1) appears.
Figure 3.1 I/O Configuration Window and Expansion General Configuration Screen
Configuring the Module
3-5
2. Enter the Series letter of the 1769-SM2, which can be determined by
checking the data nameplate label on the module (item 9 in
Figure 1.1).
The I/O image of the module can be up to 31 words of Input and 31
words of Output, depending on the mode selected (Single or
Multi-Drive) and the number of drives connected. A Single mode
system with one drive on each channel requires 7 Input words and 7
Output words. A Multi-Drive mode system with five drives on each
channel requires 31 Input words and 31 Output words. See Table 3.A
or Table 3.B to determine the number of Input Words and Output
Words to enter for your system.
The Extra Data Length field can only be set to a size of 0 or 42. If the
controller will contain the configuration data for download to the
1769-SM2 module (Configuration Mode Switch SW1 set to CONT
position), set this value to 42. If the configuration data will be
contained in the 1769-SM2 parameters (Configuration Mode Switch
SW1 set to PARAM position), this value should be set to 0. See
Table 3.C for descriptions of these configuration words.
Figure 3.2 Expansion General Configuration Tab Screen
3-6
Configuring the Module
3. Click on the Chan. 1 tab (Figure 3.3) and set the I/O Config data
area accordingly. In this example, the 1769-SM2 is configured to
fault if the controller is switched to Program mode, and one drive is
connected at node address 100.
Figure 3.3 Chan. 1 Tab Data Example Screen
Important: When using Multi-Drive mode, the node addresses
entered in the Drive Addr x fields must match the
corresponding drive Parameter 104 - [Comm Node
Addr] value in the PowerFlex 4-Class drives so that the
1769-SM2 module will communicate with the drives.
Note that the DSI Fault Config settings can only be accessed if the
Idle Action is set to “Send Flt Cfg” (Figure 3.4).
Configuring the Module
3-7
Figure 3.4 Chan. 1 Tab Data Screen with Idle Action - Send Flt Cfg Enabled
4. For each additional channel being used, select its respective tab, set
the desired I/O configuration, and enable the appropriate idle action.
TIP: Alternatively, data can be entered on the Generic Extra Data
Config tab (shown in Figure 3.5 for identification purposes only).
However, with the easy-to-use Chan.1, Chan. 2, and Chan. 3 tabs, there
is no need to enter data on the Generic Extra Data Config tab. But as a
useful reference, this tab does show how the controller stores the data in
the configuration words.
Figure 3.5 Generic Extra Data Config Tab Screen
3-8
Configuring the Module
See Table 3.C for descriptions of these configuration words.
5. Click OK when finished. The MicroLogix 1500 will download the
configuration data to the 1769-SM2 module when the controller is
placed in run mode.
Special Case— Data Entry for 2 Stop Bits Communication
The Chan.1, Chan. 2, and Chan 3 tabs do not allow settings that specify 2
stop bits communication in Modbus RTU operation. For this type of
configuration, you must use the Generic Extra Data Config tab to enter
the data by performing these steps:
1. To configure a specific 1769-SM2 module channel for 2 stop bits
communication, click on the Generic Extra Data Config tab.
2. On the Generic Extra Data Config tab screen, enter the appropriate
values from Table 3.D in the offset addresses highlighted in Figure 3.6.
Figure 3.6 Entering Data for 2 Stop Bits on Generic Extra Data Config Screen
Table 3.D Entry Data for 2 Stop Bits Communication
1769-SM2 CH
1
Offset Address
10
2
24
3
38
Value
3
4
5
3
4
5
3
4
5
Description
Sets CH1 for 8-N-2 format
Sets CH1 for 8-E-2 format
Sets CH1 for 8-O-2 format
Sets CH2 for 8-N-2 format
Sets CH2 for 8-E-2 format
Sets CH2 for 8-O-2 format
Sets CH3 for 8-N-2 format
Sets CH3 for 8-E-2 format
Sets CH3 for 8-O-2 format
Configuring the Module
3-9
3. Click OK to apply the changes and close the screen. However, if you
click Apply or leave this tab to go to another tab, you may see this
message dialog box. If so, click Yes to apply the changes.
Entering CompactLogix Configuration Data Using RSLogix 5000
v10 (or higher)
Allocate and enter the configuration data by performing these steps:
1. In the RSLogix 5000 treeview, right-click on CompactBus Local
and select New Module.
Figure 3.7 Treeview Window with New Module Inset Screen
2. After the Select Module Type screen (Figure 3.8) appears, select the
1769-MODULE and click OK.
3-10
Configuring the Module
Figure 3.8 Select Module Type Screen
3. After the Module Properties screen (Figure 3.9) appears, enter a
name for the module, such as “My_1769_SM2.” Change the Comm
Format to “Data - INT,” which will enable the entry of Output
Connection parameters (no longer grayed out). Enter the Slot
location of the 1769-SM2. Enter the desired Input and Output word
length (see Table 3.A or Table 3.B) and Configuration data size
(Table 3.C). Click Next >.
Figure 3.9 Module Properties Screen
4. On the Module Properties last screen (Figure 3.10), click Finish >>.
Configuring the Module
3-11
Figure 3.10 Module Properties Last Screen
5. The treeview (Figure 3.11) now shows the 1769-MODULE.
Figure 3.11 RSLogix 5000 Treeview with Listed 1769-MODULE
6. Double-clicking on the Controller Tags or Program Tags in the
treeview will display the various tags, including the tags for the
1769-SM2 module (Figure 3.12). Click on the Monitor Tags tab at
the bottom of the window to enter the configuration data.
Figure 3.12 Controller Tags Screen
NOTE: RSLogix 5000 may create a data array that is much larger than
the 42 words previously specified when the module was configured. Use
words 0…41 and ignore all other words (42+). Refer to Table 3.C for
configuration data words and parameter descriptions. Also note that the
data entry format in Figure 3.12 is hexadecimal (16#). To change the
format, click on the appropriate field in the “Style” column.
The CompactLogix will download the configuration data to the
1769-SM2 module on power-up.
3-12
Configuring the Module
Parameter Mode
When the Configuration Mode Switch (SW1 in Figure 2.1) is in the
PARAM (Parameter) position, the 1769-SM2 uses its internal parameter
settings to configure the module. If any configuration data is downloaded
by the controller, it will be ignored.
Important: When the Parameter mode is used, the configuration data
size in the controller should be set to “0.” See Controller
Mode on page 3-3 for more information.
Host PowerFlex 4-Class drives can use this feature since connected DSI
peripheral devices (optional, external PowerFlex 4-Class HIMs,
DriveExplorer with 22-SCM-232, etc.) can access the 1769-SM2 module
directly. However, the 1769-SM2 module must be set to Single mode for
these DSI peripherals to work with the module.
Figure 3.13 DriveExplorer Window with Mapped 1769-SM2 Compact I/O Module
Configuring the Module
3-13
Using the Optional, External PowerFlex 4-Class HIM
When using the 1769-SM2 module in Single mode, the optional,
external PowerFlex 4-Class HIM (Human Interface Module) can be used
to access its parameters. Basic steps to access module parameters using
the HIM are shown in Table 3.E. For additional HIM information, refer
to the PowerFlex 4-Class HIM Quick Reference (publication
22HIM-QR001).
Table 3.E Accessing Module Parameters Using the HIM (22-HIM-A3 or 22-HIM-C2S)
Step
Example Screens
1. Power up the drive. Then plug the
Parameters
external HIM into the bottom of the
Groups
drive. The Parameters menu for the
Linear List
drive will be displayed.
Changed Params
DIAG PARAM DSEL
2.
Press Sel key once to display the
Device Select menu.
MEM
SEL MEM
SEL MEM
SEL Device Select
DSI Devices
DIAG PARAM DSEL
3.
4.
Press
(Enter) key to display the
DSI Devices menu. Press
Arrow to scroll to 1769-SM2.
DSI Devices
Press
(Enter) key to select the
1769-SM2. The Parameters menu
for the module will be displayed.
Parameters
PowerFlex 40
1769-SM2
Linear List
Changed Params
DIAG PARAM DSEL
5.
Press
(Enter) key to access
the parameters. Edit the module
parameters using the same
techniques that you use to edit drive
parameters.
Mode
RO
Parameter:
#
001
0 = Controller
VALUE LIMITS
SEL Configuring the Module
Setting the I/O Configuration (Multi-Drive Mode Only)
The I/O configuration sets the number of drives that are connected to
each channel. When the 1769-SM2 module is used in Single mode
(Operating Mode Switch SW2 set to “1X”), only one PowerFlex 4-Class
drive can be connected to each channel and module Parameters 07 [DSI I/O Cfg 1], 22 - [DSI I/O Cfg 2], and 37 - [DSI I/O Cfg 3] have no
effect. When the module is used in Multi-Drive mode (Operating Mode
Switch set to “5X”), up to five PowerFlex 4-Class drives can be
connected to each channel. When a channel is selected for Modbus RTU
Master operation, up to 31 devices can be connected.
1. Set the value in Parameters 07 - [DSI I/O Cfg 1], 22 - [DSI I/O Cfg
2], and 37 - [DSI I/O Cfg 3] to respectively configure each module
channel for the number of drives being used in Multi-Drive mode.
Figure 3.14 Example I/O Cfg Screen for CH1 Drive(s) in Multi-Drive Mode
DSI I/O Cfg 1
Parameter:
Drives 0…4
VALUE
LIMITS
#
007
4
SEL Value
0
1
2
3
4
5
Mode Switch Position
Description
Single Multi-Drive
Drive 0 (Default) ✓
✓
✓
Drives 0…1
Drives 0…2
✓
Drives 0…3
✓
Drives 0…4
✓
RTU Master
✓
Not Applicable
3-14
Each drive (Drive 0, Drive 1, etc.) on the node must be assigned a
node address [see Setting Drive Node Addresses (Multi-Drive Mode
Only) on page 3-16]. For more information on Multi-Drive mode and
RTU Master mode, refer to the Multi-Drive Mode section in the
chapter corresponding to your controller type:
• Chapter 6, MicroLogix 1500 Example Ladder Programs
• Chapter 7, CompactLogix Example Ladder Programs
• Chapter 8, ControlLogix w/1769-ADN DeviceNet Example
Ladder Program
2. Configure the parameters in each enabled drive to accept the Logic
Command and Reference from the 1769-SM2 module. For example,
set PowerFlex 4/40/400 drive Parameters 36 - [Start Source] and 38 [Speed Reference] to “5” (Comm Port) so that the drive uses the
Reference from the 1769-SM2 module.
3. Reset the module (see Resetting the Module on page 3-20).
Configuring the Module
3-15
Setting an Idle Action (Single and Multi-Drive Mode)
By default, when the controller is idle, the drive responds by faulting
when using I/O from the 1769-SM2 module. You can respectively
configure a different response to an idle controller using Parameters 04
- [Idle Action 1], 19 - [Idle Action 2], and 34 - [Idle Action 3] for each
channel’s connected drives.
!
ATTENTION: Risk of injury or equipment damage exists.
Parameters 04 - [Idle Action 1], 19 - [Idle Action 2], and 34 - [Idle
Action 3] let you determine the action of each respective channel’s
connected PowerFlex 4-Class drives when the controller is idle. By
default, each parameter faults its respective channel’s drives. You can
set each parameter so that the respective channel’s drives continue to
run. Precautions should be taken to ensure that the settings of these
parameters do not create a hazard of injury or equipment damage.
Changing the Idle Action
Set the values of Parameters 04 - [Idle Action 1], 19 - [Idle Action 2],
and 34 - [Idle Action 3] to the desired responses:
Value
0
1
2
3
4
Action
Fault (default)
Stop
Zero Data
Description
The drive(s) is faulted and stopped. (Default)
The drive(s) is stopped, but not faulted.
The drive(s) is sent 0 for Logic Command and Reference after a
communications disruption. This does not command a stop.
Hold Last
The drive(s) continues in its present state after a communications
disruption.
Send Flt Cfg The drive(s) is sent the data that you set in the fault configuration
parameters. For:
CH1 drives, Parameters 05 - [Flt Cfg Logic 1] and 06 - [Flt Cfg Ref 1]
CH2 drives, Parameters 20 - [Flt Cfg Logic 2] and 21 - [Flt Cfg Ref 2]
CH3 drives, Parameters 35 - [Flt Cfg Logic 3] and 36 - [Flt Cfg Ref 3]
Figure 3.15 Example Idle Action HIM Screen for CH1 Drive(s)
Idle Action 1
Parameter:
#
Fault
VALUE
LIMITS
004
0
SEL Changes to these parameters take effect immediately. A reset is not
required.
Important: In Multi-Drive mode, the same fault action is used by all of
that channel’s connected drives (Drive 0…Drive 4).
3-16
Configuring the Module
ATTENTION: Idle Action is NOT available for RTU Master
operation in Multi-Drive mode. The connected RTU Slave devices will
take their respective internal fault actions in response to receiving no
communications from the 1769-SM2 module.
!
Setting the Fault Configuration Parameters
If you set Parameter 04 - [Idle Action 1], 19 - [Idle Action 2], or 34 [Idle Action 3] to “Send Flt Cfg,” the values in the following 1769-SM2
module parameters are sent to the drive after an idle action occurs. You
must set these parameters to values required by your application.
Parameter No.
CH1 CH2 CH3 Name
05 20 35 Flt Cfg Logic
06
21
36 Flt Cfg Ref
Description
A 16-bit value sent to the drive for Logic Command. Refer to
Appendix D for a description of the Logic Command bits.
A 16-bit value sent to the drive as a Reference. Format is:
xxx.x Hz. for PowerFlex 4/4M/40/40P drives
xxx.xx Hz. for PowerFlex 400 drives
Changes to these parameters take effect immediately. A reset is not required.
Setting Drive Node Addresses (Multi-Drive Mode Only)
When using the 1769-SM2 module in Multi-Drive mode, a unique node
address must be set for each drive. Use the following parameters to set
the drive node addresses:
For CH1 Drives
For CH2 Drives
For CH3 Drives
Parameters 09 - [Drv 0 Addr 1] through 13 - [Drv 4 Addr 1]
Parameters 24 - [Drv 0 Addr 2] through 28 - [Drv 4 Addr 2]
Parameters 39 - [Drv 0 Addr 3] through 43 - [Drv 4 Addr 3]
Important: The setting for each of these parameters must match the
drive Parameter 104 - [Comm Node Addr] value for each
respective drive. Each drive node address must be unique
(no duplicate node addresses).
Figure 3.16 Example Node Address HIM Screen for CH1 Drive 0
Drv 0 Addr 1
Parameter:
#
009
100
VALUE
LIMITS
SEL Default: 100
Minimum: 1
Maximum: 247
Configuring the Module
3-17
Configuring the Modbus RTU Master Parameters
In Multi-Drive mode, any module channel can be configured for RTU
Master operation by setting Parameter 07 - [DSI I/O Cfg 1], 22 - [DSI
I/O Cfg 2] or 37 - [DSI I/O Cfg 3] to “5” (RTU Master). When doing
this, additional Modbus RTU Master parameters must be set to complete
that channel’s configuration.
Setting the RTU Baud Rate
By default, each channel set for RTU Master operation uses a 38.4K
baud rate. The values of Parameters 14 - [RTU Baud Rate 1], 29 [RTU Baud Rate 2], and 44 - [RTU Baud Rate 3] set the specific baud
rate used by the respective channel to communicate.
1. Set the values of Parameters 14 - [RTU Baud Rate 1], 29 - [RTU
Baud Rate 2], and 44 - [RTU Baud Rate 3] to the specific baud rate
at which that channel communicates.
Figure 3.17 Example RTU Baud Rate HIM Screen for CH1 Drives
RTU Baud Rate 1
Parameter:
#
014
0
VALUE
LIMITS
SEL Value
0
1
2
3
4
5
6
7
Baud Rate
38.4K bits/sec (default)
19200 bits/sec
9600 bits/sec
4800 bits/sec
2400 bits/sec
1200 bits/sec
600 bits/sec
300 bits/sec
2. Reset the module (see Resetting the Module on page 3-20).
Selecting the RTU Format
By default, each channel set for RTU Master operation uses an RTU
format of 8-N-1. The RTU format consists of data bits (8 data bits only),
parity (None, Even or Odd), and stop bits (1 or 2).
1. Set the values of Parameters 15 - [RTU Format 1], 30- [RTU
Format 2], and 45 - [RTU Format 3] to match the communication
format required for the respective channel.
3-18
Configuring the Module
Figure 3.18 Example RTU Format HIM Screen for CH1 Drives
RTU Format 1
Parameter:
#
015
0
VALUE
SEL LIMITS
Value
0
1
2
3
4
5
Format
8-N-1 (default)
8-E-1
8-O-1
8-N-2
8-E-2
8-O-2
2. Reset the module (see Resetting the Module on page 3-20).
Setting the RTU Rx Delay Time
1. Set the values of Parameters 16 - [RTU Rx Delay 1], 31- [RTU Rx
Delay 2], and 46 - [RTU Rx Delay 3] to establish the inter-character
delay time that detects the end of a receive packet for the respective
channel.
Figure 3.19 Example RTU Rx Delay HIM Screen for CH1 Drives
RTU Rx Delay 1
Parameter:
#
016
0
VALUE
LIMITS
Default: 0 milliseconds
Minimum: 0 milliseconds
Maximum: 500 milliseconds
SEL TIP: If the Modbus RTU slave is a PowerFlex 4-Class drive, set the
value of [RTU Rx Delay x] to 2 milliseconds when the value of
[RTU Baud Rate x] is 19200.
2. Reset the module (see Resetting the Module on page 3-20).
Setting the RTU Tx Delay Time
1. Set the values of Parameters 17 - [RTU Tx Delay 1], 32- [RTU Tx
Delay 2], and 47 - [RTU Tx Delay 3] to establish the inter-frame
delay time that delays the sending of a transmit packet for the
respective channel.
Configuring the Module
3-19
Figure 3.20 Example RTU Tx Delay HIM Screen for CH1 Drives
RTU Tx Delay 1
Parameter:
#
017
0
VALUE
Default: 0 milliseconds
Minimum: 0 milliseconds
Maximum: 500 milliseconds
SEL LIMITS
TIP: If the Modbus RTU slave is a PowerFlex 4-Class drive, set the
value of [RTU Tx Delay x] to 8 milliseconds when the value of
[RTU Baud Rate x] is 19200.
2. Reset the module (see Resetting the Module on page 3-20).
Setting the RTU Message Timeout
1. Set the values of Parameters 18 - [RTU MsgTimeout 1], 33- [RTU
MsgTimeout 2], and 48 - [RTU MsgTimeout 3] to establish the
amount of time that the module will wait for a response from the
respective channel’s drives.
Figure 3.21 Example RTU MsgTimeout HIM Screen for CH1 Drives
RTU MsgTimeout 1
Parameter:
#
018
2
VALUE
LIMITS
Default: 2 seconds
Minimum: 0 seconds
Maximum: 60 seconds
SEL Important: The RTU Message Timeout value must be considered
when determining the timeout values in the slave nodes.
For example, if five RTU messages are being sent to a
slave node and the slave is powered down, the overall
network cycle time can increase by as much as 10
seconds (5 messages x 2 seconds timeout for each slave
node).
2. Reset the module (see Resetting the Module on page 3-20).
TIP: When configured for RTU Master operation, the RTU Slave
addresses do not get assigned with parameter values. The Slave
address is contained in the message data as described in Chapter 5.
3-20
Configuring the Module
Resetting the Module
Changes to switch settings and some module parameters require that you
reset the 1769-SM2 module before the new settings take effect. You can
reset the module by cycling power to the module or by using Parameter
03 - [Reset Module].
!
ATTENTION: Risk of injury or equipment damage exists. If the
module is transmitting control I/O to the drive, the drive may fault when
you reset the module. Determine how your drive will respond before
resetting a connected module.
Set Parameter 03 - [Reset Module] to “1” (Reset Module):
Figure 3.22 Example Reset Module HIM Screen
Reset Module
Parameter:
#
Ready
VALUE
LIMITS
003
0
Value
0
1
2
Description
Ready (Default)
Reset Module
Set Defaults
SEL When you enter “1” (Reset Module), the module will be immediately
reset. When you enter “2” (Set Defaults), the module will set all module
parameters to their factory-default settings. After performing a Set
Defaults, enter “1” (Reset Module) so that the new values take effect.
The value of this parameter will be restored to “0” (Ready) after the
module is reset.
Configuring the Module
3-21
Viewing the Module Status Using Parameters
The following parameters provide information about the status of the
1769-SM2 module. You can view these parameters at any time.
23 - [DSI I/O Act 2]
24 - [Drv 0 Addr 2]
25 - [Drv 1 Addr 2]
26 - [Drv 2 Addr 2]
27 - [Drv 3 Addr 2]
28 - [Drv 4 Addr 2]
38 [DSI I/O Act 3]
39 - [Drv 0 Addr 3]
40 - [Drv 1 Addr 3]
41 - [Drv 2 Addr 3]
42 - [Drv 3 Addr 3]
43 - [Drv 4 Addr 3]
Bit
Definition
Not Used
Not Used
Not Used
Drive 4
Drive 3
Drive 2
Drive 1
Drive 0
Default
Bit
x x x 0 0 0 0 1
7 6 5 4 3 2 1 0
0 = Drive Active
1 = Drive Inactive
The node addresses of the daisy-chained CH1 drives (only when
in Multi-Drive mode).
Important: The setting for each of these parameters must match
the drive Parameter 104 - [Comm Node Addr] value for each
respective drive. Each drive node address must be unique (no
duplicate node addresses).
The CH2 drives that are active in Multi-Drive mode.
Bit
Definition
Not Used
Not Used
Not Used
Drive 4
Drive 3
Drive 2
Drive 1
Drive 0
09 - [Drv 0 Addr 1]
10 - [Drv 1 Addr 1]
11 - [Drv 2 Addr 1]
12 - [Drv 3 Addr 1]
13 - [Drv 4 Addr 1]
Description
The module configuration mode (Controller or Parameters).
The module operating mode (Single or Multi-Drive).
The CH1 drives that are active in Multi-Drive mode.
Default
Bit
x x x 0 0 0 0 1
7 6 5 4 3 2 1 0
0 = Drive Active
1 = Drive Inactive
The node addresses of the daisy-chained CH2 drives (only when
module is operated in Multi-Drive mode).
Important: The setting for each of these parameters must match
the drive Parameter 104 - [Comm Node Addr] value for each
respective drive. Each drive node address must be unique (no
duplicate node addresses).
The CH3 drives that are active in Multi-Drive mode.
Bit
Definition
Not Used
Not Used
Not Used
Drive 4
Drive 3
Drive 2
Drive 1
Drive 0
Parameter
01 - [Config Mode]
02 - [DSI Mode]
08 - [DSI I/O Act 1]
Default
Bit
x x x 0 0 0 0 1
7 6 5 4 3 2 1 0
0 = Drive Active
1 = Drive Inactive
The node addresses of the daisy-chained CH3 drives (only when
module is operated in Multi-Drive mode).
Important: The setting for each of these parameters must match
the drive Parameter 104 - [Comm Node Addr] value for each
respective drive. Each drive node address must be unique (no
duplicate node addresses).
3-22
Configuring the Module
Flash Updating the Module
The adapter can be flash updated over the network (via EtherNet/IP
using DriveExplorer Full only) or serially through a direct connection
from a computer to the drive using a 1203-USB converter or
22-SCM-232 serial converter module (firmware v2.005 or higher).
Not all flash methods (DriveExplorer Lite/Full, ControlFLASH or
HyperTerminal) can be used successfully in all cases. Depending on the
controller and the operating mode of the 1769-SM2 module, these flash
methods can be used:
Controller
MicroLogix 1500
1769-SM2
Operating Mode
Single
Multi-Drive
CompactLogix
Single
Multi-Drive
Flash Methods to Use
DriveExplorer Lite/Full, ControlFLASH or
HyperTerminal via a 1203-USB or 22-SCM-232
converter
Must first change the 1769-SM2 operating mode
from Multi-Drive to Single before flashing. Then
flash using any of the methods listed in the row
above.
• DriveExplorer Lite/Full, ControlFLASH or
HyperTerminal via a 1203-USB or
22-SCM-232 converter
• ControlFLASH via the CompactLogix
controller backplane
ControlFLASH via the CompactLogix controller
backplane
Important: In ALL cases, the controller must be set to Program
mode—not the Run mode—to successfully flash the
1769-SM2 module.
To obtain a flash update for this adapter, go to http://www.ab.com/
support/abdrives/webupdate. This site contains all firmware update files
and associated Release Notes that describe firmware update
enhancements/anomalies, how to determine the existing firmware
version, and how to flash update using DriveExplorer Lite/Full,
ControlFLASH or HyperTerminal.
Chapter 4
Understanding the I/O Image
This chapter provides information and examples of the 1769-SM2
module I/O image, including Module Control/Status, Logic Command/
Status, and Reference/Feedback.
Topic
Module Control Word
Module Status Word
Using Logic Command/Status
Using Reference/Feedback
Page
4-2
4-3
4-4
4-4
The I/O image for the 1769-SM2 module varies based on its selected
operating mode (Single or Multi-Drive), and the settings for Parameters
07 - [DSI I/O Cfg 1], 22 - [DSI I/O Cfg 2], and 37 - [DSI I/O Cfg 3].
Table 4.A 1769-SM2 Module I/O Image Table for Single Mode
Output Image
Input Image
Module Control Word
Logic Command
Reference
Module Status Word
Logic Status
Feedback
CH1
1
2
Word
CH2
0
3
4
CH3
5
6
Table 4.B 1769-SM2 Module I/O Image Table for Multi-Drive Mode
Drive 0
Drive 1
Drive 2
Drive 3
Drive 4
Output Image
Input Image
Module Control Word
Logic Command
Reference
Logic Command
Reference
Logic Command
Reference
Logic Command
Reference
Logic Command
Reference
Module Status Word
Logic Status
Feedback
Logic Status
Feedback
Logic Status
Feedback
Logic Status
Feedback
Logic Status
Feedback
CH1
1
2
3
4
5
6
7
8
9
10
Word
CH2
0
11
12
13
14
15
16
17
18
19
20
CH3
21
22
23
24
25
26
27
28
29
30
Note that the I/O words for each channel are contiguous, keeping the
required I/O space to a minimum. For example, to connect one
PowerFlex 40 drive in Single mode and perform control (Logic
Command/Status and Reference/Feedback), only 3 words of I/O are
4-2
Understanding the I/O Image
needed. Likewise, five PowerFlex drives on CH1 in Multi-Drive mode
using control would require 11 words of I/O.
TIP: To minimize the number of I/O words needed, connect the drive(s)
starting with CH1, followed by CH2, and then CH3.
Table 4.C 1769-SM2 Module I/O Image Examples
CH1
Operating
Parameter 07 Mode
[DSI I/O Cfg 1]
Single
Multi-Drive
CH2
Parameter 22 [DSI I/O Cfg 2]
CH3
Parameter 37 [DSI I/O Cfg 3]
Maximum
I/O Words
Used
Maximum Drives
Connected
“0” (Drive 0)
“0” (Drive 0)
“0” (Drive 0)
7
3 (1/channel)
“0” (Drive 0)
“0” (Drive 0)
“0” (Drive 0)
23
3 (1/channel)
“4” (Drive 0…4)
“0” (Drive 0)
“0” (Drive 0)
23 (1)
7 (5/CH1, 1/CH2,
and 1/CH3)
“4” (Drive 0…4)
“4” (Drive 0…4)
“0” (Drive 0)
23 (2)
11 (5/CH1, 5/CH2,
and 1/CH3)
“4” (Drive 0…4)
“4” (Drive 0…4)
“4” (Drive 0…4)
31
15 (5/each CH)
(1)
If CH2 and CH3 would not be used (only 5 drives connected to CH1), the I/O size in the RSLogix 500/5000 module
configuration window could be set to “11” instead of “23” to save I/O space.
(2)
If CH3 would not be used (only CH1 and CH2 have 5 drives each), the I/O size in the RSLogix 500/5000 module
configuration window could be set to “21” instead of “23” to save I/O space.
Module Control Word
The Module Control Word (output word 0) is used for all channels, where:
Bit #
Name
Description
0
Channel 1 Enable
1
Channel 2 Enable
2
Channel 3 Enable
“0” = Disables sending output data (Logic Command/
Reference) to the respective channel’s drive(s). All
input (Logic Status/Feedback) data is zeroed (“0”) to
indicate that the data is no longer being updated.
“1” = Enables sending output data (Logic Command/
Reference) to the respective channel’s drive(s). All
respective input data will also be updated.
3…15 Not used
Reserved for future use.
The Module Control Word is a “master” enable/disable switch for
communications on each channel when using the module in Single or
Multi-Drive mode (only DSI operation). The actual output/input data
being sent/received is determined by Parameter 07 - [DSI I/O Cfg 1],
Parameter 22 - [DSI I/O Cfg 2], and Parameter 37 - [DSI I/O Cfg 3].
Important: If the Channel “x” Enable bit is transitioned from ON (1) to
OFF (0), the connected PowerFlex 4-Class drives will fault.
The Channel “x” Enable bits are not used when the module is configured
for Modbus RTU Master operation in Multi-Drive mode.
Understanding the I/O Image
4-3
Module Status Word
The Module Status Word (input word 0) is used for all channels, where:
Bit # Bit Name
Description
0
CH1 Logic Status 0 Valid
“0” = Logic Status/Feedback data for CH1 Drive 0 is not valid
“1” = Logic Status/Feedback data for CH1 Drive 0 is valid
1
CH1 Logic Status 1 Valid
“0” = Logic Status/Feedback data for CH1 Drive 1 is not valid
“1” = Logic Status/Feedback data for CH1 Drive 1 is valid
2
CH1 Logic Status 2 Valid
“0” = Logic Status/Feedback data for CH1 Drive 2 is not valid
“1” = Logic Status/Feedback data for CH1 Drive 2 is valid
3
CH1 Logic Status 3 Valid
“0” = Logic Status/Feedback data for CH1 Drive 3 is not valid
“1” = Logic Status/Feedback data for CH1 Drive 3 is valid
4
CH1 Logic Status 4 Valid
“0” = Logic Status/Feedback data for CH1 Drive 4 is not valid
“1” = Logic Status/Feedback data for CH1 Drive 4 is valid
5
CH2 Logic Status 0 Valid
“0” = Logic Status/Feedback data for CH2 Drive 0 is not valid
“1” = Logic Status/Feedback data for CH2 Drive 0 is valid
6
CH2 Logic Status 1 Valid
“0” = Logic Status/Feedback data for CH2 Drive 1 is not valid
“1” = Logic Status/Feedback data for CH2 Drive 1 is valid
7
CH2 Logic Status 2 Valid
“0” = Logic Status/Feedback data for CH2 Drive 2 is not valid
“1” = Logic Status/Feedback data for CH2 Drive 2 is valid
8
CH2 Logic Status 3 Valid
“0” = Logic Status/Feedback data for CH2 Drive 3 is not valid
“1” = Logic Status/Feedback data for CH2 Drive 3 is valid
9
CH2 Logic Status 4 Valid
“0” = Logic Status/Feedback data for CH2 Drive 4 is not valid
“1” = Logic Status/Feedback data for CH2 Drive 4 is valid
10
CH3 Logic Status 0 Valid
“0” = Logic Status/Feedback data for CH3 Drive 0 is not valid
“1” = Logic Status/Feedback data for CH3 Drive 0 is valid
11
CH3 Logic Status 1 Valid
“0” = Logic Status/Feedback data for CH3 Drive 1 is not valid
“1” = Logic Status/Feedback data for CH3 Drive 1 is valid
12
CH3 Logic Status 2 Valid
“0” = Logic Status/Feedback data for CH3 Drive 2 is not valid
“1” = Logic Status/Feedback data for CH3 Drive 2 is valid
13
CH3 Logic Status 3 Valid
“0” = Logic Status/Feedback data for CH3 Drive 3 is not valid
“1” = Logic Status/Feedback data for CH3 Drive 3 is valid
14
CH3 Logic Status 4 Valid
“0” = Logic Status/Feedback data for CH3 Drive 4 is not valid
“1” = Logic Status/Feedback data for CH3 Drive 4 is valid
15
Config Valid
“1” = The module has a valid configuration
The data valid bits (0…14) can be used in the ladder program to
determine if the received data is valid and can be used. Bit 15 provides
diagnostic feedback on the status of the 1769-SM2 module
configuration.
When the module is configured for RTU Master operation in
Multi-Drive mode, bits 0…14 are not used and will be “0.”
4-4
Understanding the I/O Image
Using Logic Command/Status
The Logic Command is a 16-bit word of control data produced by the
controller and consumed by the 1769-SM2 module. The Logic Status is a
16-bit word of status data produced by the 1769-SM2 module and
consumed by the controller.
This manual contains the bit definitions for compatible products
available at the time of publication in Appendix D. For other products,
refer to their documentation.
Using Reference/Feedback
The Reference (16 bits) is produced by the controller and consumed by
the 1769-SM2 module. The Feedback (16 bits) is produced by the
1769-SM2 module and consumed by the controller.
Valid Reference/Feedback values for PowerFlex 4-Class drives are:
Size
16-bit
(1)
Drive
PowerFlex 4
PowerFlex 4M
PowerFlex 40
PowerFlex 40P
PowerFlex 400
Valid Values (1)
-240.0…240.0 Hz
-400.0…400.0 Hz
-320.00…320.00 Hz
The Reference/Feedback for a PowerFlex 4-Class drive is set in Hz and
not in engineering units like PowerFlex 7-Class drives. For example,
“300” equates to 30.0 Hz (the decimal point is always implied) for all
PowerFlex 4-Class drives—except PowerFlex 400 for which “3000”
equates to 30.00 Hz. In all cases, a minus value equates to reverse
motor direction, and a plus value equates to forward motor direction.
Chapter 5
Understanding Explicit Messaging
This chapter provides information about explicit messaging.
Topic
Formatting Explicit Messages
Modbus RTU Master Operation Messages
Page
5-2
5-9
Explicit messaging is used to read/write data that is not part of the
module’s I/O Image (Chapter 4), such as:
•
Reading/writing drive parameters.
•
Operating as a Modbus RTU Master and initiating Request/Response
messages to Modbus RTU Slave devices, such as PowerFlex 7-Class
drives with 20-COMM-H adapters.
The following table shows various products that can be used with the
1769-SM2 module and whether they support explicit messaging:
Products
MicroLogix 1500 LRP Series A and B, and
LSP processors
MicroLogix 1500 LRP Series C (or newer) and
RSLogix 500 v6.30 (or higher)
Important: This LRP processor supports messaging
only for the first two I/O modules capable of messaging.
RSLogix 500 versions prior to v6.30
Enhanced CompactLogix processors such as the -L31,
-L32E, and -L35E
CompactLogix -L20 and -L30 processors
1769-ADN DeviceNet adapter (see documentation for
possible future explicit messaging support)
Supports Explicit Messaging
Yes
No
✔
✔
✔
✔
✔
✔
Contact your local Rockwell Automation, Inc. representative for
inquiries about the explicit message capabilities of products not
specified above.
!
ATTENTION: Hazard of equipment damage exists. If Explicit
Messages are programmed to write parameter data to Non-Volatile
Storage (NVS) frequently, the NVS will quickly exceed its life cycle
and cause the drive to malfunction. Do not create a program that
frequently uses Explicit Messages to write parameter data to NVS.
5-2
Understanding Explicit Messaging
Formatting Explicit Messages
For RSLogix 500, format each message as shown in Figure 5.1 and see
Table 5.A for a description of the data required in each field. For
RSLogix 5000, format each message as shown in Figure 5.2 and see
Table 5.B.
Figure 5.1 RSLogix 500 Explicit Message Setup Screen
Table 5.A RSLogix 500 Explicit Message Configuration Data
This Controller Section
Channel
Slot
Port
Communication Command
Data Table Address (Receive)
Size in Bytes (Receive)
Data Table Address (Send)
Size in Bytes (Send)
Target Device Section
Message Timeout
Target Type
Net Addr
Service (Text or hex)
Class (hex or dec)
Instance (hex or dec)
Attribute (hex or dec)
Description
Always use “Expansion Comms Port.”
The chassis slot occupied by the 1769-SM2 module.
Always set to “2.” Note: This field was not configurable in earlier
versions of RSLogix 500.
Always use “CIP Generic.”
The file and element where response service data (if any) is stored.
Number of bytes of response service data (if any).
The file and element where request service data (if any) is stored.
Number of bytes of request service data (if any).
Description
The timeout delay in seconds.
Always use “Network Device.”
The number of the channel (1…3) on the 1769-SM2 module where
the message will be sent. Note: This field was called “Channel” in
earlier versions of RSLogix 500.
Code for the requested service.
The Class ID.
Instance number is the same as the parameter number.
Attribute number.
Understanding Explicit Messaging
Figure 5.2 RSLogix 5000 Explicit Message Setup Screen
Table 5.B RSLogix 5000 Explicit Message Configuration Data
Configuration Tab
Message Type
Service Type
Service Code
Class
Instance
Attribute
Source Element
Source Length
Destination
Communication Tab
Path
Tag Tab
Name
Description
Always use “CIP Generic.”
The service is used to read/write a parameter value.
Code for the requested service.
Class ID for the DSI Parameter Object.
Instance number in the Class.
Attribute number of the Instance.
Source of the request service data.
Length of the request service data.
Location where the response service data (if any) is stored.
Description
Format is <Name of Module>,2,n — where “n” equals the
channel number (1…3) on the 1769-SM2.
Description
The name for the message instruction.
5-3
5-4
Understanding Explicit Messaging
Table 5.C shows the instance numbers to be used for message
configuration:
Table 5.C Instance Numbers for Message Configuration
Instances (Dec.)
0…16383
16384…17407
17408…18431
18432…19455
19456…20479
20480…21503
21504…22527
(1)
Single Mode
Instances 0…1023 in drive/module (1)
Instances 0…1023 in module
Instances 0…1023 in drive
Not supported
Not supported
Not supported
Not supported
Multi-Drive Mode
Instances 0…1023 in module
Instances 0…1023 in module
Instances 0…1023 in Drive 0
Instances 0…1023 in Drive 1
Instances 0…1023 in Drive 2
Instances 0…1023 in Drive 3
Instances 0…1023 in Drive 4
The module parameters are appended to the drive parameters for this range of instances.
Instance “1” typically equates to parameter 1. For example, when using
the 1769-SM2 module in Single mode, instance “17409” is for
parameter 1 in the drive.
NOTE: Instance Attribute 1 is used to access the parameter value. For
additional information, refer to the CIP Parameter Object on page C-4.
Understanding Explicit Messaging
5-5
RSLogix 500 Parameter Read/Write Examples
In this example, a read and a write of PowerFlex 40 drive Parameter 78
- [Jog Frequency] is being done.
The RSLogix 500 Message Configuration screen example to read a
parameter is shown in Figure 5.3. It is assumed that the 1769-SM2
module occupies slot 1 and is operated in Single mode, and that the drive
is connected to CH1.
See Table 5.A for descriptions of the message configuration data.
Figure 5.3 RSLogix 500 Example Message Setup Screen to Read a Parameter
The response data for the message is stored at Data Table Address N7:3.
The Size in Bytes of the response data is 2 bytes because the data size for
PowerFlex 40 drive Parameter 78 - [Jog Frequency] is 2 bytes (1
word). No Data Table Address is specified for the request data, since the
Read Parameter service has no request data.
5-6
Understanding Explicit Messaging
The RSLogix 500 Message Configuration example screen to write to a
parameter is shown in Figure 5.4. It is assumed that the 1769-SM2
module occupies slot 1 and is operated in Single mode, and that the drive
is connected to CH1.
See Table 5.A for descriptions of the message configuration data.
Figure 5.4 RSLogix 500 Example Message Setup Screen to Write to a Parameter
The request data for the message is stored at Data Table Address N7:2.
The Size in Bytes of the request data is 2 bytes because the data size for
PowerFlex 40 drive Parameter 78 - [Jog Frequency] is 2 bytes (1
word). No Data Table Address is specified for the response data, since
the Write Parameter service has no response data.
Understanding Explicit Messaging
5-7
RSLogix 5000 Parameter Read/Write Examples
In this example, a read and a write of PowerFlex 40 drive Parameter 78
- [Jog Frequency] is being done.
The RSLogix 5000 Message Configuration example screen to read a
parameter is shown in Figure 5.5. It is assumed that the 1769-SM2
module occupies slot 1 and is operated in Single mode, and that the drive
is connected to CH1.
See Table 5.B for descriptions of the message configuration data.
Figure 5.5 RSLogix 5000 Example Message Setup Screen to Read a Parameter
The response data for the message is stored in CH1_Read_Value. The
“Get Attribute Single” Service Type (Service Code “e”) is used to read a
single parameter. Class “f” refers to the CIP Parameter Object on
page C-4 and Instance “78” is drive Parameter 78 - [Jog Frequency].
Instance Attribute “1” is the parameter value.
5-8
Understanding Explicit Messaging
The RSLogix 5000 Message Configuration example screen to write to a
parameter is shown in Figure 5.6. It is assumed that the 1769-SM2
module occupies slot 1 and is operated in Single mode, and that the drive
is connected to CH1.
See Table 5.B for descriptions of the message configuration data.
Figure 5.6 RSLogix 5000 Example Message Setup Screen to Write to a Parameter
The request data for the message is stored in CH1_Write_Value. The
“Set Attribute Single” Service Type (Service Code “10”) is used to write
a single parameter. Class “f” refers to the CIP Parameter Object on
page C-4 and Instance “78” is drive Parameter 78 - [Jog Frequency].
Instance Attribute “1” is the parameter value.
Understanding Explicit Messaging
5-9
Modbus RTU Master Operation Messages
In Multi-Drive mode, any channel can be configured for Modbus RTU
Master operation to communicate with a variety of Rockwell
Automation or 3rd Party RTU Slave devices, such as PowerFlex 7-Class
drives with 20-COMM-H adapters. In the Multi-Drive ladder examples
provided in this manual, CH3 is used to communicate with a PowerFlex
70 drive.
The following Modbus Function Codes are supported:
Function Name
Code
Maximum
Bits/Word
Function Name
Code
Maximum
Bits/Word
01
Read Coils
512
05
Write Single Coil
n/a
02
Read Discrete Inputs
512
06
Write Single Register
n/a
03
Read Holding Registers 32
15
Write Multiple Coils
512
04
Read Input Registers
16
Write Multiple Registers 512
32
The format of the Modbus command message data is:
Word
Name
1
RTU Slave Address
Description
The node address of the Modbus RTU Slave.
2
Function Code
The Modbus Function Code to perform.
3
Starting Address
The starting coil/register address in the Slave device.
4
Number of bits/words
The number of coils/registers to read/write.
5+
Data Words
Only used for write messages and contains the data
to be written.
The format of the Modbus response message data is:
Word
Name
Description
1+
Data Words
Only used for read messages and contains the data
that was read.
The format of the message instruction is different for Modbus RTU
Master operation messaging. For RSLogix 500, format each message as
shown in Figure 5.7 and see Table 5.D for a description of the data
required in each field. For RSLogix 5000, format each message as shown
in Figure 5.8 and see Table 5.E.
5-10
Understanding Explicit Messaging
Figure 5.7 RSLogix 500 Modbus RTU Master Message Setup Screen
Table 5.D RSLogix 500 Modbus RTU Master Message Configuration Data
This Controller Section
Description
Channel
Always use “Expansion Comms Port.”
Slot
The chassis slot occupied by the 1769-SM2 module.
Port
Always set to “2.” Note: This field was not configurable in earlier
versions of RSLogix 500.
Communication Command
Always use “CIP Generic.”
Send (Data Table Address)
Starting data table address of the Modbus command data.
Size in Bytes (Receive)
Number of bytes of receive data. It is set to “0” for a Modbus write
message, and to the necessary length for a read message (greater
than “0”).
Send (Size in Bytes)
Number of bytes of command data.
Target Device Section
Description
Message Timeout
Timeout delay in seconds. This value must be greater than the
Message Timeout configured for the channel in the module’s I/O
configuration.
Target Type
Always use “Network Device.”
Net Addr
The number of the channel (1…3) on the 1769-SM2 module where
the message will be sent. Note: This field was called “Channel” in
earlier versions of RSLogix 500.
Service
Always use “Custom.”
Service Code (hex)
Always use “4b.” This is the Execute Modbus service.
Class (hex)
Always use “33F.” This is the Class number for the Modbus RTU
Master object.
Instance (hex or dec)
Not used. Leave at “0.”
Attribute (hex or dec)
Not used. Leave at “0.”
Understanding Explicit Messaging
Figure 5.8 RSLogix 5000 Modbus RTU Master Message Setup Screen
Table 5.E RSLogix 5000 Modbus RTU Master Message Configuration Data
Configuration Tab
Description
Message Type
Always use “CIP Generic.”
Service Type
Type of Service to execute.
Service Code
Code of the respective Service Type.
Class
Class ID for the DSI Parameter Object.
Instance
Instance number in the Class.
Attribute
Attribute number of the Instance.
Source Element
Source of the request service data.
Source Length
Length of the request service data.
Destination
Location where the response service data is stored.
Communication Tab
Description
Path
Format is <Name of Module>,2,n — where “n” equals the
channel number (1…3) on the 1769-SM2.
Tag Tab
Description
Name
The name for the message instruction.
5-11
5-12
Understanding Explicit Messaging
RSLogix 500 Modbus RTU Master Write Message Example
Figure 5.9 shows an example Modbus RTU Master write message setup
screen. See Table 5.D for descriptions of the message configuration data.
Figure 5.9 RSLogix 500 Example Modbus RTU Master Write Message Setup Screen
In this example, Logic Command and Reference are being written to a
PowerFlex 70 drive. N7:100 through N7:106 (note the send length is 14
bytes or 7 words) contain the command data where:
Data Word
N7:100
N7:101
N7:102
N7:103
N7:104
N7:105
N7:106
Example Value
15
16
0
3
18
0
8192
Description
PowerFlex 70 node address
Function Code – Write Multiple Registers
Starting Register Address (40001)
Number of registers to write
Value for 40001 – Logic Command word
Value for 40002 – not used
Value for 40003 – Reference word
Note the Size in Bytes (Receive) is set to “0” because no data is returned
for a write message.
For additional information about Modbus RTU write messages for
PowerFlex 7-Class drives, refer to the 20-COMM-H Adapter User
Manual, publication 20COMM-UM009.
Understanding Explicit Messaging
5-13
RSLogix 500 Modbus RTU Master Read Message Example
Figure 5.10 shows an example Modbus RTU Master read message setup
screen. See Table 5.D for descriptions of the message configuration data.
Figure 5.10 RSLogix 500 Example Modbus RTU Master Read Message Setup Screen
In this example, Logic Status and Feedback are being read from a
PowerFlex 70 drive. N7:110 through N7:113 (note the send length is 8
bytes or 4 words) contain the command data where:
Data Word
N7:110
N7:111
N7:112
N7:113
Example Value
15
4
0
3
Description
PowerFlex 70 node address
Function Code – Read Input Registers
Starting Register Address (30001)
Number of registers to read
N7:114 through N7:116 (note the Receive length is 6 bytes or 3 words)
contain the response data where:
Data Word
N7:114
N7:115
N7:116
Example Value
3855
0
8192
Description
Value for 30001 – Logic Status word
Value for 30002 – not used
Value for 30003 – Feedback word
For additional information about Modbus RTU read messages for
PowerFlex 7-Class drives, refer to the 20-COMM-H Adapter User
Manual, publication 20COMM-UM009.
5-14
Understanding Explicit Messaging
RSLogix 5000 Modbus RTU Master Write Message Example
Figure 5.11 shows an example Modbus RTU Master write message setup
screen. See Table 5.E for descriptions of the message configuration data.
Figure 5.11 RSLogix 5000 Example Modbus RTU Master Write Message Setup Screen
In this example, Logic Command and Reference are being written to a
PowerFlex 70 drive. The CH3_MSG1_REQ array (14 bytes = 7 words)
contains the command data where:
Data Word
CH3_MSG1_REQ [0]
CH3_MSG1_REQ [1]
CH3_MSG1_REQ [2]
CH3_MSG1_REQ [3]
CH3_MSG1_REQ [4]
CH3_MSG1_REQ [5]
CH3_MSG1_REQ [6]
Example Value
15
16
0
3
18
0
8192
Description
PowerFlex 70 node address
Function Code – Write Multiple Registers
Starting Register Address (40001)
Number of registers to write
Value for 40001 – Logic Command word
Value for 40002 – not used
Value for 40003 – Reference word
A Destination element is not needed for a write message because no data
is returned.
For additional information about Modbus RTU write messages for
PowerFlex 7-Class drives, refer to the 20-COMM-H Adapter User
Manual, publication 20COMM-UM009.
Understanding Explicit Messaging
5-15
RSLogix 5000 Modbus RTU Master Read Message Example
Figure 5.12 shows an example Modbus RTU Master read message setup
screen. See Table 5.E for descriptions of the message configuration data.
Figure 5.12 RSLogix 5000 Example Modbus RTU Master Read Message Setup Screen
In this example, Logic Status and Feedback are being read from a
PowerFlex 70 drive. The CH3_MSG2_REQ array (8 bytes = 4 words)
contains the command data where:
Data Word
CH3_MSG2_REQ [0]
CH3_MSG2_REQ [1]
CH3_MSG2_REQ [2]
CH3_MSG2_REQ [3]
Example Value
15
4
0
3
Description
PowerFlex 70 node address
Function Code – Read Input Registers
Starting Register Address (30001)
Number of registers to read
The CH3_MSG2_RESP array contains the response data where:
Data Word
CH3_MSG2_RESP [0]
CH3_MSG2_RESP [1]
CH3_MSG2_RESP [2]
Example Value
3855
0
8192
Description
Value for 30001 – Logic Status word
Value for 30002 – not used
Value for 30003 – Feedback word
For additional information about Modbus RTU read messages for
PowerFlex 7-Class drives, refer to the 20-COMM-H Adapter User
Manual, publication 20COMM-UM009.
5-16
Notes:
Understanding Explicit Messaging
Chapter 6
MicroLogix 1500 Example Ladder
Programs
This chapter provides ladder examples for a MicroLogix 1500 controller
used with a 1769-SM2 module in Single mode and Multi-Drive mode.
Topic
Single Mode
Multi-Drive Mode
Page
6-1
6-8
Single Mode
The ladder example provided in this section is based on a 1769-SM2
module in slot 1 with one PowerFlex 4/40 drive connected to each
channel (Figure 6.1). The ladder example demonstrates the following
functionality for each channel:
•
•
•
•
Send a Logic Command to control the drive (for example, start, stop).
Send a Reference to the drive and receive Feedback from the drive.
Receive Logic Status information from the drive.
Write and read parameters.
Explicit messaging (parameter read/write) capability varies between the
RSLogix software packages and controllers:
•
Versions of RSLogix 500 before v6.30 do NOT support creating a
Message instruction for the 1769-SM2 module. This limits the
MicroLogix 1500 to performing I/O messaging (Logic Command/
Reference, and Logic Status/Feedback) only.
•
RSLogix 500 v6.30 (or higher) must be used with a MicroLogix
1500 LRP Series C (or newer) controller to create Message
instructions to send explicit messages to the 1769-SM2 module.
MicroLogix 1500 Example Ladder Programs
Figure 6.1 Example MicroLogix 1500 Single Mode System Arrangement
MicroLogix 1500 Controller
PowerFlex 4/40 Drives
DSI
6-2
C
H
1
C
H
2
C
H
3
CH1
CH2
CH3
PowerFlex 40 Drive Settings
The PowerFlex 40 drives used in the example program have the
following parameter settings:
Parameter
P036 - [Start Source]
P038 - [Speed Reference]
A103 - [Comm Data Rate]
A104 - [Comm Node Addr]
A107 - [Comm Format]
Setting
5 (Comm Port)
5 (Comm Port)
4 (19.2K)
100
0 (RTU 8-N-1)
1769-SM2 Module Settings
The 1769-SM2 module used in the example program has the following
switch settings:
Switch
Configuration Mode Switch (SW1)
Operating Mode Switch (SW2)
Setting
CONT position
1X (Single) position
MicroLogix 1500 Example Ladder Programs
6-3
The I/O configuration in RSLogix 500 v6.30 (or higher) for the Single
mode example program is:
Refer to Table 3.C for configuration data words and parameter
descriptions. Also, see Chapter 4 for information about the I/O image,
Module Enable/Status, Logic Command/Status, and Reference/
Feedback.
6-4
MicroLogix 1500 Example Ladder Programs
MicroLogix 1500 Example Program
Figure 6.2 Example MicroLogix 1500 Single Mode Ladder Logic Main Routine
MicroLogix 1500 w/ 1769-SM2 in Single mode
In this Single mode example program, the channels are utilized as follows:
Channel 1 - Connected to 1 PowerFlex 4/40 drive (maximum allowed)
Channel 2 - Connected to 1 PowerFlex 4/40 drive (maximum allowed)
Channel 3 - Connected to 1 PowerFlex 4/40 drive (maximum allowed)
This rung enables the 1769-SM2 to send the Channel 1 Logic Command and Reference words to the drive.
Channel 1
Enable
O:1
0000
0
1769-SM2
Channel 1 Subroutine
JSR
Jump To Subroutine
SBR File Number
0001
U:3
This rung enables the 1769-SM2 to send the Channel 2 Logic Command and Reference words to the drive.
Channel 2
Enable
O:1
0002
1
1769-SM2
Channel 2 Subroutine
JSR
Jump To Subroutine
SBR File Number
0003
U:4
This rung enables the 1769-SM2 to send the Channel 3 Logic Command and Reference words to the drive.
Channel 3
Enable
O:1
0004
2
1769-SM2
Channel 3 Subroutine
JSR
Jump To Subroutine
SBR File Number
0005
0006
0007
0008
U:5
CH1
Drive 0
Logic Sts Valid
I:1
CH2
Drive 0
Logic Sts Valid
I:1
CH3
Drive 0
Logic Sts Valid
I:1
1769-SM2
Input Data
Valid
B3:0
0
1769-SM2
5
1769-SM2
10
1769-SM2
0
1769-SM2
Config Data
Valid
I:1
1769-SM2
Config Data
Error
B3:0
15
1769-SM2
1
END
MicroLogix 1500 Example Ladder Programs
6-5
Figure 6.3 Example MicroLogix 1500 Single Mode Ladder Logic CH1 Subroutine
1769-SM2 Channel 1 Subroutine
The following rungs display some of the Logic Status bits from the drive. Refer to Appendix D in the 1769-SM2 user manual for additional
information about the Logic Status word.
0000
0001
0002
0003
0004
CH1 Drv0
Logic Sts
Bit 00
I:1
CH1
Drive 0
Ready
B3:1
16
1769-SM2
0
CH1 Drv0
Logic Sts
Bit 01
I:1
CH1
Drive 0
Active
B3:1
17
1769-SM2
1
CH1 Drv0
Logic Sts
Bit 03
I:1
CH1
Drive 0
Running Fwd
B3:1
19
1769-SM2
3
CH1 Drv0
Logic Sts
Bit 07
I:1
CH1
Drive 0
Fault
B3:1
23
1769-SM2
7
CH1 Drv0
Logic Sts
Bit 08
I:1
CH1
Drive 0
At Speed
B3:1
24
1769-SM2
8
This rung displays the Feedback from the drive. An integer represents the xxx.x Hz format (decimal is implied) used by the drive, so a displayed
value of "300" equates to 30.0 Hz.
CH1
Drive 0
Feedback
MOV
Move
Source
0005
Dest
I:1.2
0<
N7:1
0<
The following rungs display some of the Logic Command bits sent to the drive. Refer to Appendix D in the 1769-SM2 user manual for additional
information about the Logic Command word.
0006
CH1
Drive 0
Stop
B3:2
CH1 Drv0
Logic Cmd
Bit 00
O:1
0
16
1769-SM2
6-6
MicroLogix 1500 Example Ladder Programs
Figure 6.3 Example MicroLogix 1500 Single Mode Ladder Logic CH1 Subroutine (Continued)
This rung unlatches the contact that turns on the Start command when the drive is not communicating with the 1769-SM2. This prevents the drive
from immediately starting when communications is restored. If an immediate start is desired for the application, this rung could be deleted.
CH1
CH1
Drive 0
Drive 0
Logic Sts Valid
Start
I:1
B3:2
U
0007
0
1
1769-SM2
0008
0009
0010
0011
0012
CH1
Drive 0
Start
B3:2
CH1 Drv0
Logic Cmd
Bit 01
O:1
1
17
1769-SM2
CH1
Drive 0
Jog
B3:2
CH1 Drv0
Logic Cmd
Bit 02
O:1
2
18
1769-SM2
CH1
Drive 0
Clear Faults
B3:2
CH1 Drv0
Logic Cmd
Bit 03
O:1
3
19
1769-SM2
CH1 Drv0
Logic Cmd
Bit 04
O:1
CH1
Drive 0
Forward
B3:2
4
20
1769-SM2
CH1
Drive 0
Forward
B3:2
CH1 Drv0
Logic Cmd
Bit 05
O:1
4
21
1769-SM2
This rung displays the Reference being sent to the drive. The data is used by the drive as xxx.x Hz format (decimal is implied), so entering a value
of "300" equates to 30.0 Hz.
CH1 Drv 0
Reference
Word
MOV
Move
Source
0013
Dest
N7:0
200<
O:1.2
200<
The following rungs are used to send explicit messages to the 1769-SM2 to read and write Parameter 78 [Jog Frequency] in PowerFlex 4/40 drives.
N7:2 = Write value
N7:3 = Read value
In Single mode, the desired parameter number is the value entered for the Target Device Instance number.
Read
Parameter
Request
B3:1
MSG
EN
0014
Read/Write Message
DN
14
MSG File
MG9:0
ER
Setup Screen
0015
0016
0017
Write
Parameter
Request
B3:1
15
MSG
Read/Write Message
MSG File
MG9:1
Setup Screen
EN
DN
ER
RET
Return
END
MicroLogix 1500 Example Ladder Programs
6-7
The read and write message instructions for PowerFlex 40 drive
Parameter 78 - [Jog Frequency] are configured as follows:
Single Mode Example Program Data Table
Integer File N7: is used to contain the input and output data to/from the
three channels of the module:
N7: Word
CH1
0
1
2
3
CH2
10
11
12
13
CH3
20
21
22
23
Description
Reference
Feedback
Parameter 78 Write Value
Parameter 78 Read Value
6-8
MicroLogix 1500 Example Ladder Programs
An example of data table values are shown below:
A value of “200” for the Reference equates to 20.0 Hz. A value of “100”
for drive Parameter 78 - [Jog Frequency] equates to 10.0 Hz.
Since CH2 and CH3 ladder routines are similar to the CH1 routine, they
are not provided.
Multi-Drive Mode
The ladder example provided in this section is based on a 1769-SM2
module in slot 1 with five PowerFlex 4/40 drives connected to CH1 and
to CH2, and one PowerFlex 70 connected to CH3 (Figure 6.4). The
ladder example demonstrates the following functionality for each
channel’s drives:
•
•
•
•
Send a Logic Command to control the drive (for example, start, stop).
Send a Reference to the drive and receive Feedback from the drive.
Receive Logic Status information from the drive.
Write and read parameters.
Explicit messaging (parameter read/write) capability varies between the
RSLogix software packages and controllers:
•
Versions of RSLogix 500 before v6.30 do NOT support creating a
Message instruction for the 1769-SM2 module. This limits the
MicroLogix 1500 to performing I/O messaging (Logic Command/
Reference, and Logic Status/Feedback) only.
•
RSLogix 500 v6.30 (or higher) must be used with a MicroLogix
1500 LRP Series C (or newer) controller to create Message
instructions to send explicit messages to the 1769-SM2 module.
MicroLogix 1500 Example Ladder Programs
6-9
Figure 6.4 Example MicroLogix 1500 Multi-Drive Mode System Arrangement
MicroLogix 1500 Controller
DSI
Up to 5 PowerFlex 4/40 Drives
C
H
1
C
H
2
C
H
3
CH1
Up to 5 PowerFlex 4/40 Drives
CH2
PowerFlex 70 Drive
with 20-COMM-H Adapter
CH3
PowerFlex 40 Settings
The PowerFlex 40 drives used in the example program have the
following parameter settings:
Parameter
P036 - [Start Source]
P038 - [Speed Reference]
A103 - [Comm Data Rate]
A104 - [Comm Node Addr]
A107 - [Comm Format]
Setting
5 (Comm Port)
5 (Comm Port)
4 (19.2K)
100…104
0 (RTU 8-N-1)
PowerFlex 70 Setting
The PowerFlex 70 drive used in the example program has the following
parameter setting:
Parameter
90 - [Speed Ref A Sel]
Setting
22 (DPI Port 5)
6-10
MicroLogix 1500 Example Ladder Programs
20-COMM-H Settings
The 20-COMM-H adapter used in the example program has the
following parameter and switch settings:
Parameter Settings
Parameter
5 - [Net Rate Cfg]
7 - [Net Parity Cfg]
16 - [DPI I/O Cfg]
30 - [Stop Bits Cfg]
Setting
2 (19200 Baud)
1 (Odd)
00001 = Logic Command/Reference
0 (1 bit)
Switch Settings
Switch
Node Address Switches
Network Protocol Switch
Setting
15
RTU position
1769-SM2 Settings
The 1769-SM2 module used in the example program has the following
switch settings:
Switch
Configuration Mode Switch (SW1)
Operating Mode Switch (SW2)
Setting
CONT position
5X (Multi-Drive) position
MicroLogix 1500 Example Ladder Programs
6-11
The I/O configuration in RSLogix 500 v6.30 (or higher) for the
Multi-Drive mode example program is:
Refer to Chapter 4 for information about the I/O image, Module Enable/
Status, Logic Command/Status, and Reference/Feedback.
6-12
MicroLogix 1500 Example Ladder Programs
MicroLogix 1500 Multi-Drive Mode Example Program
Figure 6.5 Example MicroLogix 1500 Multi-Drive Ladder Logic Main Routine
MicroLogix 1500 w/ 1769-SM2 in Multi-Drive mode
In this Multi-Drive example program, the channels are utilized as follows:
Channel 1 - Connected to 5 PowerFlex 4/40 drives (maximum allowed)
Channel 2 - Connected to 5 PowerFlex 4/40 drives (maximum allowed)
Channel 3 - Configured for Modbus RTU Master mode and connected to 1 PowerFlex 70 drive (with 20-COMM-H adapter)
This rung enables the 1769-SM2 to send the Channel 1 Logic Command and Reference words to the drives.
Channel 1
Enable
O:1
0000
0
1769-SM2
Channel 1 Drive 0 Subroutine
0001
Channel 1 Drive 1 Subroutine
0002
Channel 1 Drive 2 Subroutine
0003
Channel 1 Drive 3 Subroutine
0004
Channel 1 Drive 4 Subroutine
0005
JSR
Jump To Subroutine
SBR File Number
U:3
JSR
Jump To Subroutine
SBR File Number
U:4
JSR
Jump To Subroutine
SBR File Number
U:5
JSR
Jump To Subroutine
SBR File Number
U:6
JSR
Jump To Subroutine
SBR File Number
U:7
This rung enables the 1769-SM2 to send the Channel 2 Logic Command and Reference words to the drives.
Channel 2
Enable
O:1
0006
1
1769-SM2
Channel 2 Drive 0 Subroutine
0007
Channel 2 Drive 1 Subroutine
0008
JSR
Jump To Subroutine
SBR File Number
U:8
JSR
Jump To Subroutine
SBR File Number
U:9
MicroLogix 1500 Example Ladder Programs
6-13
Figure 6.5 Example MicroLogix 1500 Multi-Drive Ladder Logic Main Routine (Continued)
Channel 2 Drive 2 Subroutine
0009
Channel 2 Drive 3 Subroutine
0010
Channel 2 Drive 4 Subroutine
0011
Channel 3 Modbus RTU Master Subroutine
0012
0013
0014
0015
0016
0017
JSR
Jump To Subroutine
SBR File Number
U:10
JSR
Jump To Subroutine
SBR File Number
U:11
JSR
Jump To Subroutine
SBR File Number
U:12
JSR
Jump To Subroutine
SBR File Number
U:13
CH1
Drive 0
Logic Sts Valid
I:1
CH1
Drive 1
Logic Sts Valid
I:1
CH1
Drive 2
Logic Sts Valid
I:1
CH1
Drive 3
Logic Sts Valid
I:1
CH1
Drive 4
Logic Sts Valid
I:1
1769-SM2
CH1 Input Data
Valid
B3:0
0
1769-SM2
1
1769-SM2
2
1769-SM2
3
1769-SM2
4
1769-SM2
2
CH2
Drive 0
Logic Sts Valid
I:1
CH2
Drive 1
Logic Sts Valid
I:1
CH2
Drive 2
Logic Sts Valid
I:1
CH2
Drive 3
Logic Sts Valid
I:1
CH2
Drive 4
Logic Sts Valid
I:1
1769-SM2
CH2 Input Data
Valid
B3:0
5
1769-SM2
6
1769-SM2
7
1769-SM2
8
1769-SM2
9
1769-SM2
3
1769-SM2
CH1 Input Data
Valid
B3:0
1769-SM2
CH2 Input Data
Valid
B3:0
2
3
1769-SM2
All Input Data
Valid
B3:0
0
1769-SM2
Config Data
Valid
I:1
1769-SM2
Config Data
Error
B3:0
15
1769-SM2
1
END
6-14
MicroLogix 1500 Example Ladder Programs
Figure 6.6 Example MicroLogix 1500 Multi-Drive Ladder Logic CH1 Drive 0 Subroutine
1769-SM2 Channel 1 Drive 0 Subroutine
The following rungs display some of the Logic Status bits from the drive. Refer to Appendix D in the 1769-SM2 user manual for additional
information about the Logic Status word.
0000
0001
0002
0003
0004
CH1 Drv0
Logic Sts
Bit 00
I:1
CH1
Drive 0
Ready
B3:10
16
1769-SM2
0
CH1 Drv0
Logic Sts
Bit 01
I:1
CH1
Drive 0
Active
B3:10
17
1769-SM2
1
CH1 Drv0
Logic Sts
Bit 03
I:1
CH1
Drive 0
Running Fwd
B3:10
19
1769-SM2
3
CH1 Drv0
Logic Sts
Bit 07
I:1
CH1
Drive 0
Fault
B3:10
23
1769-SM2
7
CH1 Drv0
Logic Sts
Bit 08
I:1
CH1
Drive 0
At Speed
B3:10
24
1769-SM2
8
This rung displays the Feedback from the drive. An integer represents the xxx.x Hz format (decimal is implied) used by the drive, so a displayed
value of "300" equates to 30.0 Hz.
CH1
Drive 0
Feedback
MOV
Move
Source
0005
Dest
I:1.2
101<
N7:1
101<
The following rungs display some of the Logic Command bits from the drive. Refer to Appendix D in the 1769-SM2 user manual for additional
information about the Logic Command word.
0006
CH1
Drive 0
Stop
B3:11
CH1 Drv0
Logic Cmd
Bit 00
O:1
0
16
1769-SM2
MicroLogix 1500 Example Ladder Programs
6-15
Figure 6.6 Example MicroLogix 1500 Multi-Drive Ladder Logic CH1 Drive 0 Subroutine (Continued)
This rung unlatches the contact that turns on the Start command when the drive is not communicating with the 1769-SM2. This prevents the drive
from immediately starting when communications is restored. If an immediate start is desired for the application, this rung could be deleted.
CH1
CH1
Drive 0
Drive 0
Start
Logic Sts Valid
B3:11
I:1
U
0007
1
0
1769-SM2
0008
0009
0010
0011
0012
CH1
Drive 0
Start
B3:11
CH1 Drv0
Logic Cmd
Bit 01
O:1
1
17
1769-SM2
CH1
Drive 0
Jog
B3:11
CH1 Drv0
Logic Cmd
Bit 02
O:1
2
18
1769-SM2
CH1
Drive 0
Clear Faults
B3:11
CH1 Drv0
Logic Cmd
Bit 03
O:1
3
19
1769-SM2
CH1
Drive 0
Forward
B3:11
CH1 Drv0
Logic Cmd
Bit 04
O:1
4
20
1769-SM2
CH1
Drive 0
Forward
B3:11
CH1 Drv0
Logic Cmd
Bit 05
O:1
4
21
1769-SM2
This rung displays the Reference being sent to the drive. The data is used by the drive as xxx.x Hz format (decimal is implied), so entering a value
of "300" equates to 30.0 Hz.
CH1
Drive 0
Reference
MOV
Move
Source
0013
Dest
N7:0
101<
O:1.2
101<
The following rungs are used to send explicit messages to the 1769-SM2 to read and write Parameter 78 [Jog Frequency] in PowerFlex 4/40 drives.
N7:2 = Write value
N7:3 = Read value
In Single mode, the desired parameter number is the value entered for the Target Device Instance number.
Read
Parameter
Request
B3:11
MSG
EN
0014
Read/Write Message
DN
14
MSG File
MG9:0
ER
Setup Screen
0015
0016
0017
Write
Parameter
Request
B3:11
15
MSG
Read/Write Message
MSG File
MG9:1
Setup Screen
EN
DN
ER
RET
Return
END
6-16
MicroLogix 1500 Example Ladder Programs
The read and write message instructions for PowerFlex 40 drive
Parameter 78 - [Jog Frequency] are configured as follows:
For additional information about the message setup, refer to page 5-3.
Multi-Drive Example Program Data Tables
Integer File N7: is used to contain the input and output data to/from the
three channels:
N7: Words for CH1
Drive 0 Drive 1 Drive 2
0
10
20
1
11
21
2
12
22
3
13
23
Drive 3
30
31
32
33
Drive 4
40
41
42
43
Description
Reference
Feedback
Parameter 78 Write Value
Parameter 78 Read Value
MicroLogix 1500 Example Ladder Programs
N7: Words for CH2
Drive 0 Drive 1 Drive 2
50
60
70
51
61
71
52
62
72
53
63
73
Drive 3
80
81
82
83
Drive 4
90
91
92
93
6-17
Description
Reference
Feedback
Parameter 78 Write Value
Parameter 78 Read Value
An example of data table values are shown below:
A value of “101” for the Reference equates to 10.1 Hz. A value of “100”
for drive Parameter 78 - [Jog Frequency] equates to 10.0 Hz.
Since the Drive 1…4 and CH2 ladder routines are similar to the CH1
Drive 0 routine, they are not provided.
6-18
MicroLogix 1500 Example Ladder Programs
CH3 Modbus RTU Master Subroutine Example
In Multi-Drive mode, any channel can be configured for Modbus RTU
Master operation. In the MicroLogix 1500 Multi-Drive ladder logic
example, CH3 is used to communicate with a PowerFlex 70 drive via
Modbus RTU operation.
Figure 6.7 Example MicroLogix 1500 Modbus RTU Ladder Logic CH3 Subroutine
1769-SM2 Channel 3 Modbus RTU Master Subroutine
Channel 3 consists of a single PowerFlex 70 drive with a 20-COMM-H adapter.
0000
0001
Write Logic Command and Reference.
N7:100 = Slave Address ("15" is the 20-COMM-H address)
N7:101 = Function Code ("16" is Write Multiple Registers command)
N7:102 = Starting Address ("0" = 4x0001)
N7:103 = Length ("3")
N7:104 = Logic Command word
N7:105 = MSW of 32-bit Reference
N7:106 = 16-bit Reference or LSW of 32-bit Reference
CH3
Write
Control
B3:30
0
MSG
Read/Write Message
MSG File
MG9:20
Setup Screen
Execute the control message continuously if the CH3 Write Control bit (B3:30/0) is ON.
Message
Done
MG9:20
EN
DN
ER
Message
Enable
MG9:20
U
EN
DN
Message
Error
MG9:20
ER
Read Logic Status and Feedback.
N7:110 = Slave Address ("15" is the 20-COMM-H address)
N7:111 = Function Code ("4" is Read Input Registers command)
N7:112 = Starting Address ("0" = 3x0001)
N7:113 = Length ("3")
0002
0003
The response data is stored in:
N7:114 = Logic Status word
N7:115 = MSW of 32-bit Feedback
N7:116 = 16-bit Feedback or LSW of 32-bit Feedback
CH3
Read
Status
B3:30
1
Execute the status message continuously if the CH3 Read Status bit (B3:30/1) is ON.
Message
Done
MG9:21
DN
Message
Error
MG9:21
ER
MSG
Read/Write Message
MSG File
MG9:21
Setup Screen
EN
DN
ER
Message
Enable
MG9:21
U
EN
MicroLogix 1500 Example Ladder Programs
6-19
Figure 6.7 Example MicroLogix 1500 Modbus RTU Ladder Logic CH3 Subroutine (Continued)
0004
Write Parameter 100 [Jog Frequency] (written 1x per request).
N7:120 = Slave Address ("15" is the 20-COMM-H address)
N7:121 = Function Code ("6" is Write Single Register command)
N7:122 = Starting Address ("1099" = 4x1100)
N7:123 = Length ("1")
N7:124 = Pr. 100 [Jog Frequency] Write Value
CH3
Write
Pr.100
B3:30
2
MSG
Read/Write Message
MSG File
MG9:22
Setup Screen
EN
DN
ER
MSG
Read/Write Message
MSG File
MG9:23
Setup Screen
EN
DN
ER
Read Parameter 100 [Jog Frequency] (read 1x per request).
N7:130 = Slave Address ("15" is the 20-COMM-H address)
N7:131 = Function Code ("3" is Read Holding Register command)
N7:132 = Starting Address ("1099" = 4x1100)
N7:133 = Length ("1")
0005
0006
0007
The response data is stored in:
N7:134 = Pr. 100 [Jog Frequency] Read Value
CH3
Read
Pr.100
B3:30
3
RET
Return
END
The Logic Command/Reference write message instruction on rung 0000
is configured as follows:
6-20
MicroLogix 1500 Example Ladder Programs
The format of the command data is:
Data Word
N7:100
N7:101
N7:102
N7:103
N7:104
N7:105
N7:106
Example Value
15
16
0
3
18
0
8192
Description
PowerFlex 70 node address
Function Code – Write Multiple Registers
Starting Register Address (40001)
Number of registers to write
Value for 40001 – Logic Command word
Value for 40002 – not used
Value for 40003 – Reference word
The Logic Status/Feedback read message instruction on rung 0002 is
configured as follows:
The format of the command data is:
Data Word
N7:110
N7:111
N7:112
N7:113
Example Value
15
4
0
3
Description
PowerFlex 70 node address
Function Code – Read Input Registers
Starting Register Address (30001)
Number of registers to read
The format of the response data is:
Data Word
N7:114
N7:115
N7:116
Example Value
3855
0
8192
Description
Value for 30001 – Logic Status word
Value for 30002 – not used
Value for 30003 – Feedback word
MicroLogix 1500 Example Ladder Programs
The write message instruction on rung 0004 for PowerFlex 70 drive
Parameter 100 - [Jog Speed] is configured as follows:
The format of the command data is:
Data Word
N7:120
N7:121
N7:122
N7:123
N7:124
Example Value
15
6
1099
1
111
Description
PowerFlex 70 node address
Function Code – Write Single Registers
Starting Register Address (41100)
Number of registers to write
Parameter 100 write data
6-21
6-22
MicroLogix 1500 Example Ladder Programs
The read message instruction on rung 0005 for PowerFlex 70 drive
Parameter 100 - [Jog Speed] is configured as follows:
The format of the command data is:
Data Word
N7:130
N7:131
N7:132
N7:133
Example Value
15
3
1099
1
Description
PowerFlex 70 node address
Function Code – Read Holding Registers
Starting Register Address (41100)
Number of registers to read
The format of the response data is:
Data Word
N7:134
Example Value
111
Description
Parameter 100 read data
For additional information about Modbus RTU Master messages for
PowerFlex 7-Class drives, refer to the 20-COMM-H Adapter User
Manual, publication 20COMM-UM009.
Chapter 7
CompactLogix Example Ladder
Programs
This chapter provides ladder examples for a CompactLogix controller
used with a 1769-SM2 module in Single mode and Multi-Drive mode.
Topic
Single Mode
Multi-Drive Mode
Page
7-1
7-10
Single Mode
The ladder example provided in this section is based on a 1769-SM2
module in slot 1 with one PowerFlex 4/40 drive connected to each
channel (Figure 7.1). The ladder example demonstrates the following
functionality for each channel:
•
•
•
•
Send a Logic Command to control the drive (for example, start, stop).
Send a Reference to the drive and receive Feedback from the drive.
Receive Logic Status information from the drive.
Write and read parameters.
Explicit messaging (parameter read/write) capability varies between the
RSLogix software packages and controllers:
•
Explicit messaging can be used with enhanced CompactLogix
processors, such as the -L31, -L32E, and -L35E.
•
CompactLogix -L20 and -L30 processors do NOT have explicit
messaging capability.
CompactLogix Example Ladder Programs
Figure 7.1 Example CompactLogix Single Mode System Arrangement
CompactLogix Controller
PowerFlex 4/40 Drives
MODULE
CH1
CH2
CH3
DSI
7-2
C
H
1
C
H
2
C
H
3
CH1
CH2
CH3
PowerFlex 40 Settings
The PowerFlex 40 drives used in the example program have the
following parameter settings:
Parameter
P036 - [Start Source]
P038 - [Speed Reference]
A103 - [Comm Data Rate]
A104 - [Comm Node Addr]
A107 - [Comm Format]
Setting
5 (Comm Port)
5 (Comm Port)
4 (19.2K)
100
0 (RTU 8-N-1)
1769-SM2 Settings
The 1769-SM2 module used in the example program has the following
switch settings:
Switch
Configuration Mode Switch (SW1)
Operating Mode Switch (SW2)
Setting
CONT position
1X (Single) position
CompactLogix Example Ladder Programs
7-3
The I/O configuration in RSLogix 5000 for the Single mode example
program is:
Refer to Chapter 4 for information about the I/O image, Module Enable/
Status, Logic Command/Status, and Reference/Feedback.
7-4
CompactLogix Example Ladder Programs
CompactLogix Example Program
Figure 7.2 Example CompactLogix Ladder Logic Main Routine
CompactLogix -L35E w// 1769-SM2 in Single Mode
In this Single mode example program, the channels are utilized as follows:
s:
Channel 1 - Connected to 1 PowerFlex 4/40 drive (maximum allowed)
Channel 2 - Connected to 1 PowerFlex 4/40 drive (maximum allowed)
Channel 3 - Connected to 1 PowerFlex 4/40 drive (maximum allowed)
This rung enables the 1769-SM2 to send the Channel 1 Logix Command and Reference words to the drive.
CH1_Enable
<Local:1:O.Data[0].0>
0
Channel 1 Subroutine
CH1 control logic
JSR
Jump To Subroutine
Routine Name Channel_1
1
This rung enables the 1769-SM2 to send the Channel 2 Logix Command and Reference words to the drive.
CH2_Enable
<Local:1:O.Data[0].1>
2
Channel 2 Subroutine
CH2 control logic
JSR
Jump To Subroutine
Routine Name Channel_2
3
This rung enables the 1769-SM2 to send the Channel 3 Logix Command and Reference words to the drive.
CH3_Enable
<Local:1:O.Data[0].2>
4
Channel 3 Subroutine
CH3 control logic
JSR
Jump To Subroutine
Routine Name Channel_3
5
CH1_Valid_Data
CH2_Valid_Data
CH3_Valid_Data
<Local:1:I.Data[0].0> <Local:1:I.Data[0].5> <Local:1:I.Data[0].10>
SM2_Data_Valid
6
7
(End)
SM2_Cfg_Data_Valid
<Local:1:I.Data[0].15>
/
SM2_Cfg_Error
CompactLogix Example Ladder Programs
7-5
Figure 7.3 Example CompactLogix Single Mode Ladder Logic CH1 Subroutine
1769-SM2 Channel 1 Subroutine
The following
i rungs display some of the Logic Status bits from the drive. Refer to Appendix D in the 1769-SM2 user manual
for additional information about the Logic Status word.
Channel 1
Logic Status
Bit 00
Local:1:I.Data[1].0
CH1_Ready
Channel 1
Logic Status
Bit 01
Local:1:I.Data[1].1
CH1_Active
Channel 1
Logic Status
Bit 03
Local:1:I.Data[1].3
CH1_Forward
Channel 1
Logic Status
Bit 07
Local:1:I.Data[1].7
CH1_Fault
Channel 1
Logic Status
Bit 08
Local:1:I.Data[1].8
CH1_At_Speed
0
1
2
3
4
5
This rung displays the Feedback from the drive. An integer represents the xxx.x Hz format (decimal is implied) used by the
drive, so a displayed value of "300" equates to 30.0 Hz.
MOV
Move
Source Local:1:I.Data[2]
100
Dest
CH1_Feedback
100
The following
i rungs display some of the Logic Command bits sent to the drive. Refer to Appendix D in the 1769-SM2 user
manual for additional information about the Logic Command word.
CH1_Stop
6
Channel 1
Logic Command
Bit 00
Local:1:O.Data[1].0
7-6
CompactLogix Example Ladder Programs
Figure 7.3 Example CompactLogix Single Mode Ladder Logic CH1 Subroutine (Continued)
7
This rung unlatches the contact that turns on the Start command when the drive is not communicating with
i the 1769-SM2.
This prevents the drive from immediately starting when communications are restored. If an immediate start is desired for an
application, this rung could be deleted.
CH1_Valid_Data
<Local:1:I.Data[0].0>
CH1_Start
/
U
CH1_Start
Channel 1
Logic Command
Bit 01
Local:1:O.Data[1].1
CH1_Jog
Channel 1
Logic Command
Bit 02
Local:1:O.Data[1].2
CH1_Clear_Fault
Channel 1
Logic Command
Bit 03
Local:1:O.Data[1].3
CH1_Forward_Cmd
Channel 1
Logic Command
Bit 04
Local:1:O.Data[1].4
8
9
10
11
12
13
Channel 1
Logic Command
Bit 05
Local:1:O.Data[1].5
CH1_Forward_Cmd
/
This rung displays the Reference being sent to the drive. An integer represents the xxx.x Hz format (decimal is implied) used
by the drive, so a displayed value of "300" equates to 30.0 Hz.
Channel 1
Reference Word
MOV
Move
Source CH1_Reference
100
Dest Local:1:O.Data[2]
100
These rungs send an explicit message to the 1769-SM2 to read/write Parameter 78 [Jog Frequency]. In Single mode, the
desired parameter number is the value entered for the Instance number.
CH1_Read_Param
14
Type - CIP Generic
Message Control
MSG
CH1_Read_Msg ...
EN
DN
ER
CompactLogix Example Ladder Programs
7-7
Figure 7.3 Example CompactLogix Single Mode Ladder Logic CH1 Subroutine (Continued)
15
Move
Source
MOV
CH1_Read_Value
111
Dest CH1_Read_Jog_Frequency
111
MOV
Move
Source CH1_Write_Jog_Frequency
111
Dest
CH1_Write_Value
111
16
CH1_Write_Param
17
Type - CIP Generic
Message Control
18
MSG
CH1_Write_Msg ...
Return
RET
(End)
The read and write message instructions for PowerFlex 40 drive
Parameter 78 - [Jog Frequency] are configured as follows:
Read Message (Rung 14)
EN
DN
ER
7-8
CompactLogix Example Ladder Programs
Write Message (Rung 17)
Single Mode Example Program Tags
The following tags are used to contain the input and output data to/from
the three channels of the module:
CompactLogix Example Ladder Programs
7-9
7-10
CompactLogix Example Ladder Programs
Since CH2 and CH3 ladder routines are similar to the CH1 routine, they
are not provided.
Multi-Drive Mode
The ladder example provided in this section is based on a 1769-SM2
module in slot 1 with five PowerFlex 4/40 drives connected to CH1 and
to CH2, and one PowerFlex 70 connected to CH3 (Figure 7.4). The
ladder example demonstrates the following functionality for each
channel’s drives:
•
•
•
•
Send a Logic Command to control the drive (for example, start, stop).
Send a Reference to the drive and receive Feedback from the drive.
Receive Logic Status information from the drive.
Write and read parameters.
Explicit messaging (parameter read/write) capability varies between the
RSLogix software packages and controllers:
•
Explicit messaging can be used with enhanced CompactLogix
processors, such as the -L31, -L32E, and -L35E.
•
CompactLogix -L20 and -L30 processors do NOT have explicit
messaging capability.
CompactLogix Example Ladder Programs
7-11
Figure 7.4 Example CompactLogix Multi-Drive Mode System Arrangement
CompactLogix Controller
Up to 5 PowerFlex 4/40 Drives
MODULE
CH2
CH3
DSI
CH1
C
H
1
C
H
2
C
H
3
CH1
Up to 5 PowerFlex 4/40 Drives
CH2
PowerFlex 70 Drive
with 20-COMM-H Adapter
CH3
PowerFlex 40 Settings
The PowerFlex 40 drives used in the example program have the
following parameter settings:
Parameter
P036 - [Start Source]
P038 - [Speed Reference]
A103 - [Comm Data Rate]
A104 - [Comm Node Addr]
A107 - [Comm Format]
Setting
5 (Comm Port)
5 (Comm Port)
4 (19.2K)
100…104
0 (RTU 8-N-1)
PowerFlex 70 Setting
The PowerFlex 70 drive used in the example program has the following
parameter setting:
Parameter
90 - [Speed Ref A Sel]
Setting
22(DPI Port 5)
7-12
CompactLogix Example Ladder Programs
20-COMM-H Settings
The 20-COMM-H adapter used in the example program has the
following parameter and switch settings:
Parameter Settings
Parameter
5 - [Net Rate Cfg]
7 - [Net Parity Cfg]
16 - [DPI I/O Cfg]
30 - [Stop Bits Cfg]
Setting
2 (19200 Baud)
1 (Odd)
00001 = Logic Command/Reference
0 (1 bit)
Switch Settings
Switch
Node Address Switches
Network Protocol Switch
Setting
15
RTU position
1769-SM2 Settings
The 1769-SM2 module used in the example program has the following
switch settings:
Switch
Configuration Mode Switch (SW1)
Operating Mode Switch (SW2)
Setting
CONT position
5X (Multi-Drive) position
The I/O configuration in RSLogix 5000 for the Multi-Drive mode
example program is:
CompactLogix Example Ladder Programs
7-13
Refer to Chapter 4 for information about the I/O image, Module Enable/
Status, Logic Command/Status, and Reference/Feedback.
7-14
CompactLogix Example Ladder Programs
CompactLogix Multi-Drive Mode Example Program
Figure 7.5 Example CompactLogix Multi-Drive Ladder Logic Main Routine
CompactLogix -L35E w// 1769-SM2 in Multi-Drive Mode
In this Multi-Drive mode example program, the channels are utilized as follows:
s:
Channel 1 - Connected to 5 PowerFlex
e
4/40 drives (maximum allowed)
Channel 2 - Connected to 5 PowerFlex 4/40 drives (maximum allowed)
Channel 3 - Configured for Modbus RTU Master mode and connected to 1 PowerFlex 70 drive (with 20-COMM-H adapter)
This rung enables the 1769-SM2 to send the Channel 1 Logix Command and Reference words to the drives.
CH1_Enable
<Local:1:O.Data[0].0>
0
Channel 1 Drive 0 Subroutine
Channel 1 Drive 0
control logic
JSR
Jump To Subroutine
Routine Name CH1_Drive0
1
Channel 1 Drive 1 Subroutine
Channel 1 Drive 1
control logic
JSR
Jump To Subroutine
Routine Name CH1_Drive1
2
Channel 1 Drive 2 Subroutine
Channel 1 Drive 2
control logic
JSR
Jump To Subroutine
Routine Name CH1_Drive2
3
Channel 1 Drive 3 Subroutine
Channel 1 Drive 3
control logic
JSR
Jump To Subroutine
Routine Name CH1_Drive3
4
Channel 1 Drive 4 Subroutine
5
Channel 1 Drive 4
control logic
JSR
Jump To Subroutine
Routine Name CH1_Drive4
This rung enables the 1769-SM2 to send the Channel 2 Logix Command and Reference words to the drive.
CH2_Enable
<Local:1:O.Data[0].1>
6
CompactLogix Example Ladder Programs
7-15
Figure 7.5 Example CompactLogix Multi-Drive Ladder Logic Main Routine (Continued)
Channel 2 Drive 0 Subroutine
Channel 2 Drive 0
control logic
JSR
Jump To Subroutine
Routine Name CH2_Drive0
7
Channel 2 Drive 1 Subroutine
Channel 2 Drive 1
control logic
JSR
Jump To Subroutine
Routine Name CH2_Drive1
8
Channel 2 Drive 2 Subroutine
Channel 2 Drive 2
control logic
JSR
Jump To Subroutine
Routine Name CH2_Drive2
9
Channel 2 Drive 3 Subroutine
Channel 2 Drive 3
control logic
JSR
Jump To Subroutine
Routine Name CH2_Drive3
10
Channel 2 Drive 4 Subroutine
Channel 2 Drive 4
control logic
JSR
Jump To Subroutine
Routine Name CH2_Drive4
11
Channel 3 Modbus RTU Master Subroutine
Channel 3 Modbus
RTU Master
JSR
Jump To Subroutine
Routine Name CH3_Modbus
12
CH1_Drv0_Valid_Data
<Local:1:I.Data[0].0>
CH1_Drv1_Valid_Data
<Local:1:I.Data[0].1>
CH1_Drv2_Valid_Data
<Local:1:I.Data[0].2>
CH1_Drv3_Valid_Data
<Local:1:I.Data[0].3>
13
CH1_Drv4_Valid_Data
<Local:1:I.Data[0].4>
SM2_CH1_Data_Valid
7-16
CompactLogix Example Ladder Programs
Figure 7.5 Example CompactLogix Multi-Drive Ladder Logic Main Routine (Continued)
CH2_Drv0_Valid_Data
<Local:1:I.Data[0].5>
CH2_Drv1_Valid_Data
<Local:1:I.Data[0].6>
CH2_Drv2_Valid_Data
<Local:1:I.Data[0].7>
CH2_Drv3_Valid_Data
<Local:1:I.Data[0].8>
14
CH2_Drv4_Valid_Data
<Local:1:I.Data[0].9>
SM2_CH1_Data_Valid
SM2_CH2_Data_Valid
SM2_CH2_Data_Valid
SM2_Input_Data_Valid
15
16
(End)
SM2_Cfg_Data_Valid
<Local:1:I.Data[0].15>
/
SM2_Cfg_Error
CompactLogix Example Ladder Programs
7-17
Figure 7.6 Example CompactLogix Multi-Drive Ladder Logic CH1 Drive 0 Subroutine
1769-SM2 Channel 1 Drive 0 Subroutine
The following
i rungs display some of the Logic Status bits from the drive. Refer to Appendix D in the 1769-SM2 user manual
for additional information about the Logic Status word.
CH1 Drv0
Logic Status
Bit 00
Local:1:I.Data[1].0
CH1_Drv0_Ready
CH1 Drv0
Logic Status
Bit 01
Local:1:I.Data[1].1
CH1_Drv0_Active
CH1 Drv0
Logic Status
Bit 03
Local:1:I.Data[1].3
CH1_Drv0_Forward
CH1 Drv0
Logic Status
Bit 07
Local:1:I.Data[1].7
CH1_Drv0_Fault
CH1 Drv0
Logic Status
Bit 08
Local:1:I.Data[1].8
CH1_Drv0_At_Speed
0
1
2
3
4
5
This rung displays the Feedback from the drive. An integer represents the xxx.x Hz format (decimal is implied) used by the
drive, so a displayed value of "300" equates to 30.0 Hz.
MOV
Move
Source
Local:1:I.Data[2]
0
Dest CH1_Drv0_Feedback
0
The following rungs display some of the Logic Command bits sent to the drive. Refer to Appendix D in the 1769-SM2 user
manual for additional information about the Logic Command word.
CH1_Drv0_Stop
6
CH1 Drv0
Logic Command
Bit 00
Local:1:O.Data[1].0
7-18
CompactLogix Example Ladder Programs
Figure 7.6 Example CompactLogix Multi-Drive Ladder Logic CH1 Drive 0 Subroutine (Continued)
7
This rung unlatches the contact that turns on the Start command when the drive is not communicating with
i the 1769-SM2.
This prevents the drive from immediately starting when communications are restored. If an immediate start is desired for an
application, this rung could be deleted.
CH1_Drv0_Valid_Data
<Local:1:I.Data[0].0>
CH1_Drv0_Start
/
U
CH1_Drv0_Start
CH1 Drv0
Logic Command
Bit 01
Local:1:O.Data[1].1
CH1_Drv0_Jog
CH1 Drv0
Logic Command
Bit 02
Local:1:O.Data[1].2
CH1_Drv0_Clear_Fault
CH1 Drv0
Logic Command
Bit 03
Local:1:O.Data[1].3
CH1_Drv0_Forward_Cmd
CH1 Drv0
Logic Command
Bit 04
Local:1:O.Data[1].4
8
9
10
11
12
13
14
CH1_Drv0_Forward_Cmd
/
CH1 Drv0
Logic Command
Bit 05
Local:1:O.Data[1].5
This rung displays the Reference being sent to the drive. An integer represents the xxx.x Hz format (decimal is implied) used
by the drive, so a displayed value of "300" equates to 30.0 Hz.
CH1 Drv0
Reference Word
MOV
Move
Source CH1_Drv0_Reference
100
Dest
Local:1:O.Data[2]
100
These rungs send an explicit message to the 1769-SM2 to read/write Parameter 78 [Jog Frequency].
CH1_Drv0_Read_Param
MSG
Type - CIP Generic
Message Control
CH1_Drv0_Read_Msg ...
EN
DN
ER
CompactLogix Example Ladder Programs
7-19
Figure 7.6 Example CompactLogix Multi-Drive Ladder Logic CH1 Drive 0 Subroutine (Continued)
15
MOV
Move
Source
CH1_Drv0_Read_Value
111
Dest CH1_Drv0_Read_Jog_Frequency
111
MOV
Move
Source CH1_Drv0_Write_Jog_Frequency
111
Dest
CH1_Drv0_Write_Value
111
16
CH1_Drv0_Write_Param
17
Type - CIP Generic
Message Control
18
MSG
CH1_Drv0_Write_Msg ...
Return
RET
(End)
The read and write message instructions for PowerFlex 40 drive
Parameter 78 - [Jog Frequency] are configured as follows:
Read Message (Rung 14)
EN
DN
ER
7-20
CompactLogix Example Ladder Programs
A “17486” equates to Parameter 78 (17486 - 17408 = 78), since 17408 is
Instance 0 in the drive (17409 is Parameter 1). For additional information
about the message setup, refer to page 5-3.
Write Message (Rung 17)
A “17486” equates to Parameter 78 (17486 - 17408 = 78), since 17408 is
Instance 0 in the drive (17409 is Parameter 1). For additional information
about the message setup, refer to page 5-3.
CompactLogix Example Ladder Programs
7-21
Multi-Drive Example Program Tags
The following tags are used to contain the input and output data to/from
CH1 Drive 0:
Since the Drive 1…4 and CH2 ladder routines are similar to the CH1
Drive 0 routine, they are not provided.
7-22
CompactLogix Example Ladder Programs
CH3 Modbus RTU Master Subroutine Example
In Multi-Drive mode, any channel can be configured for Modbus RTU
Master operation. In the CompactLogix Multi-Drive ladder logic
example, CH3 is used to communicate with a PowerFlex 70 drive via
Modbus RTU operation.
Figure 7.7 Example CompactLogix Modbus RTU Ladder Logic CH3 Subroutine
1769-SM2 Channel 3 Modbus RTU Master Subroutine
Channel 3 consists of a single PowerFlex 70 drive with
i a 20-COMM-H adapter.
Channel 3
Write Control
CH3_WR_Control
Write Logic Command and Reference.
CH3_MSG1_REQ[0] = Slave Address ("15" is the 20-COMM-H address)
CH3_MSG1_REQ[1] = Function Code ("16" is Write Multiple Registers command)
CH3_MSG1_REQ[2] = Starting Address ("0" = 4x0001)
CH3_MSG1_REQ[3] = Length ("3")
CH3_MSG1_REQ[4] = Logic Command word
CH3_MSG1_REQ[5] = MSW of 32-bit Reference
CH3_MSG1_REQ[6] = 16-bit Reference or LSW of 32-bit Reference
0
MSG
Type - CIP Generic
Message Control
CH3_MSG1 ...
EN
DN
ER
Execute the control message continuously if the CH3_WR_Control bit is ON.
CH3_MSG1.EN
U
CH3_MSG1.DN
1
CH3_MSG1.ER
Read Logic Status and Feedback.
CH3_MSG2_REQ[0] = Slave Address ("15" is the 20-COMM-H address)
CH3_MSG2_REQ[1] = Function Code ("4" is Read Input Registers command)
CH3_MSG2_REQ[2] = Starting Address ("0" = 3x0001)
CH3_MSG2_REQ[3] = Length ("3")
Channel 3
Read Status
CH3_RD_Status
2
The response data is stored in:
CH3_MSG2_RESP[0] = Logic Status word
CH3_MSG2_RESP[1] = MSW of 32-bit Feedback
CH3_MSG2_RESP[2] = 16-bit Feedback or LSW of 32-bit Feedback
MSG
Type - CIP Generic
Message Control
CH3_MSG2 ...
EN
DN
ER
Execute the status message continuously if the CH3_RD_Status bit is ON.
CH3_MSG2.DN
3
CH3_MSG2.ER
CH3_MSG2.EN
U
CompactLogix Example Ladder Programs
7-23
Figure 7.7 Example CompactLogix Modbus RTU Ladder Logic CH3 Subroutine (Continued)
Write Parameter 100 [Jog Frequency] (written 1x per request)
CH3_MSG3_REQ[0] = Slave Address ("15" is the 20-COMM-H address)
CH3_MSG3_REQ[1] = Function Code ("6" is Write Single Register command)
CH3_MSG3_REQ[2] = Starting Address ("1099" = 4x1101)
CH3_MSG3_REQ[3] = Length ("1")
CH3_MSG3_REQ[4] = Pr.100 Write Value
Channel 3
Write Pr.100
CH3_WR_Pr100
4
MSG
Type - CIP Generic
Message Control
CH3_MSG3 ...
EN
DN
ER
Read Parameter 100 [Jog Frequency] (written 1x per request)
CH3_MSG4_REQ[0] = Slave Address ("15" is the 20-COMM-H address)
CH3_MSG4_REQ[1] = Function Code ("3" is Read Holding Register command)
CH3_MSG4_REQ[2] = Starting Address ("1099" = 4x1101)
CH3_MSG4_REQ[3] = Length ("1")
Channel 3
Read Pr.100
CH3_RD_Pr100
5
6
(End)
The response data is stored in:
CH3_MSG4_RESP[0] = Pr.100 Read Value
MSG
Type - CIP Generic
Message Control
CH3_MSG4 ...
Return
RET
EN
DN
ER
7-24
CompactLogix Example Ladder Programs
The Logic Command/Reference write message instruction on rung 0 is
configured as follows:
The format of the command data is:
CompactLogix Example Ladder Programs
The Logic Status/Feedback read message instruction on rung 2 is
configured as follows:
The format of the command and response data is:
7-25
7-26
CompactLogix Example Ladder Programs
The write message instruction on rung 4 for PowerFlex 70 drive
Parameter 100 - [Jog Speed] is configured as follows:
The format of the command data is:
The read message instruction on rung 5 for PowerFlex 70 drive
Parameter 100 - [Jog Speed] is configured as follows:
CompactLogix Example Ladder Programs
The format of the command and response data is:
For additional information about Modbus RTU Master messages for
PowerFlex 7-Class drives, refer to the 20-COMM-H Adapter User
Manual, publication 20COMM-UM009.
7-27
7-28
Notes:
CompactLogix Example Ladder Programs
Chapter 8
ControlLogix w/1769-ADN DeviceNet
Example Ladder Program
This chapter provides an example of a ControlLogix controller and
1769-ADN Remote DeviceNet adapter system used with a 1769-SM2
module in Single mode.
Important: When the 1769-SM2 module is used with the 1769-ADN,
the Configuration Mode switch (SW1) must be set to the
“Controller” position (default). See Chapter 2 for
information on Configuration Mode switch settings.
Topic
Single Mode
Using RSLinx Classic
Using RSNetWorx for DeviceNet
Setting Up the 1769-ADN
Registering the 1769-SM2 EDS File
PowerFlex 40 Settings
1769-SM2 Settings
ControlLogix w/1769-ADN Example Program
Example Program Data Table
Page
8-1
8-2
8-3
8-4
8-8
8-12
8-12
8-13
8-21
The 1769-SM2 module can be operated in Multi-Drive mode when used
in a 1769-ADN system (example not provided). However, explicit
messaging and Modbus RTU Master operation CANNOT be used in
Single or Multi-Drive mode because, at the time of publication, the ADN
does NOT support messaging.
Single Mode
The ladder example provided in this section is based on a 1769-SM2
module in slot 1 with one PowerFlex 4/40 drive connected to each
channel (Figure 8.1). The ladder example demonstrates the following
functionality for each channel:
•
•
•
Send a Logic Command to control the drive (for example, start, stop).
Send a Reference to the drive and receive Feedback from the drive.
Receive Logic Status information from the drive.
ControlLogix w/1769-ADN DeviceNet Example Ladder Program
Explicit messaging (parameter read/write) capability varies between the
RSLogix software packages and controllers:
•
At the time of publication, the 1769-ADN does NOT have explicit
messaging capability. Refer to ADN documentation for possible
future explicit messaging support.
Figure 8.1 Example ControlLogix/1769-ADN DeviceNet Adapter in a Single Mode
System Arrangement
DeviceNet
1769-ADN
MS
NS
IO
DIAG
PowerFlex 4/40 Drives
MODULE
CH1
CH2
CH3
DSI
8-2
C
H
1
C
H
2
C
H
3
CH1
CH2
CH3
Using RSLinx Classic
To use RSNetWorx for DeviceNet, you must first set up a driver in
RSLinx. RSLinx Classic, in all its variations (Lite, Gateway, OEM, etc.),
is used to provide a communication link between the computer, network,
and controller. RSLinx Classic requires its network-specific driver to be
configured before communications are established with network devices.
To configure the RSLinx driver:
1. Start RSLinx and select Communications > Configure Drivers to
display the Configure Drivers screen.
2. In the Available Drivers pull-down box, select “DeviceNet Drivers
(1784-PCD/PCIDS, …drivers” and then click Add New… to display
the DeviceNet Driver Selection screen.
3. Select the PC communication card (1770-KFD, 1771-SDNPT, etc.)
for connection of your computer to the network and then click
Select.
4. Configure the driver for your computer and network settings and
click OK.
ControlLogix w/1769-ADN DeviceNet Example Ladder Program
8-3
5. In the Add New RSLinx Driver screen, use the default name or type a
new name and click OK. The Configure Drivers screen reappears
with the new driver in the Configured Drivers list (Figure 8.2).
Figure 8.2 Configure Drivers Dialog Box with a Configured Driver
6. Click Close to close the Configure Drivers screen. Keep RSLinx
running.
7. Verify that your computer recognizes the drive. Select
Communications > RSWho and, in the treeview, click the “+”
symbol next to the DeviceNet driver.
Using RSNetWorx for DeviceNet
RSNetWorx for DeviceNet is a Rockwell Software application that can
be used to set up DeviceNet networks and configure connected devices.
You can view the devices on a DeviceNet network by going online. A
device may appear as an unrecognized device (node 63 in Figure 8.3) if
RSNetWorx for DeviceNet does not have an EDS file for it.
Step
1. After setting up a driver in RSLinx (see Using RSLinx Classic on
page 8-2), start RSNetWorx for DeviceNet.
2.
3.
Select Network > Online. If the Browse for Network dialog box
appears, RSLinx has multiple drivers configured. Select your
DeviceNet network, and click OK. A prompt appears.
Click OK to go online. The devices on the network appear in the
Configuration View. You can select Graph, Spreadsheet, or Master/
Slave views. Figure 8.3 shows an example network in a Graph view.
Icon
Shortcut to
RSNetWorx
8-4
ControlLogix w/1769-ADN DeviceNet Example Ladder Program
Figure 8.3 Example DeviceNet Network
Setting Up the 1769-ADN
To configure the 1769-ADN for use with the example program using
RSNetWorx for DeviceNet v3.21 (or higher), perform these steps:
1. Double-click on the 1769-ADN adapter image in the graphic display
window (Figure 8.4). In the ladder example system, the node address
setting on the adapter is “2.”
Figure 8.4 1769-ADN Adapter Image Screen
2. Select the Module Configuration tab and build the remote ADN
system by dragging and dropping components (Figure 8.5). In the
ladder example, the remote drop consists of an ADN, PA4 power
supply, 1769-SM2 module, and ECR end cap terminator.
ControlLogix w/1769-ADN DeviceNet Example Ladder Program
8-5
Figure 8.5 1769-ADN Adapter Module Configuration Tab Screen
The EDS file for the 1769-SM2 module is needed to configure the
remote 1769-ADN DeviceNet system. If the 1769-SM2 is not listed
as a selection (Figure 8.5), the EDS file will need to be downloaded
from the Internet. For more information, refer to Registering the
1769-SM2 EDS File on page 8-8.
3. Select the 1769-SM2 and click on the Properties command button. A
screen similar to Figure 8.6 will appear.
Figure 8.6 1769-SM2 Module Properties Screen
Enter a “1” in the Bank field, and click OK.
8-6
ControlLogix w/1769-ADN DeviceNet Example Ladder Program
4. Select the Advanced Parameters tab (Figure 8.7). Refer to Chapter 4,
Understanding the I/O Image regarding the Input and Output Data
Sizes. In the ladder example, the Input and Output Data Sizes are set
for 7 words each to allow for Logic Command/Reference and Logic
Status/Feedback for all 3 drives.
Figure 8.7 1769-SM2 Module Advanced Parameters Tab Screen
5. Select the Configuration Settings tab. The configuration data for each
channel is contained in a folder. Click on the Channel 1 folder
(Figure 8.8).
Figure 8.8 1769-SM2 Channel 1 Config Data Screen
ControlLogix w/1769-ADN DeviceNet Example Ladder Program
8-7
Parameters can be adjusted by double-clicking on the desired
parameter. Default settings are used for this ladder example. Click
OK to complete the 1769-SM2 configuration.
6. Select the I/O Summary tab (Figure 8.9). The 1769-ADN uses 4
Input bytes and the 1769-SM2 module has been configured for 14
bytes (7 words) of Input and Output data. The I/O Summary below is
required for the example ladder program.
Figure 8.9 1769-ADN Adapter I/O Summary Tab Screen
Click OK to complete the configuration.
8-8
ControlLogix w/1769-ADN DeviceNet Example Ladder Program
Registering the 1769-SM2 EDS File
The EDS file for the 1769-SM2 module is needed to configure the
remote 1769-ADN DeviceNet system. If the 1769-SM2 is not listed as a
selection in the Hardware list (Figure 8.10), the EDS file will need to be
downloaded from the Internet and registered using the EDS Wizard.
Figure 8.10 1769-ADN Adapter Module Configuration Tab Screen
1. Download the EDS file for the 1769-SM2 module from
www.ab.com/networks/eds.
2. Using RSNetWorx for DeviceNet, click on Tools > EDS Wizard to
launch the EDS Wizard (Figure 8.11).
Figure 8.11 EDS Wizard Welcome Screen
ControlLogix w/1769-ADN DeviceNet Example Ladder Program
8-9
3. Click Next > to display the EDS Wizard Task screen (Figure 8.12).
Select Register an EDS file(s) and click Next >.
Figure 8.12 EDS Wizard Task Screen
4. The EDS Wizard Registration screen (Figure 8.13) will appear.
Select Register a single file and use the Browse command button to
browse to the EDS file on your hard drive. Click Next >.
Figure 8.13 EDS Wizard Registration Screen
5. The EDS file is installed and tested (Figure 8.14). Click Next >.
8-10
ControlLogix w/1769-ADN DeviceNet Example Ladder Program
Figure 8.14 EDS Wizard Installation Test Screen
6. The EDS Wizard Change Graphic Image screen (Figure 8.15)
appears, enabling the icon associated with the EDS file for the
1769-SM2 module to be changed if desired. Click Next >.
Figure 8.15 EDS Wizard Change Graphic Image Screen
7. The EDS Wizard Final Task Summary screen (Figure 8.16) will
appear. Click Next > to register the 1769-SM2 module.
ControlLogix w/1769-ADN DeviceNet Example Ladder Program
8-11
Figure 8.16 EDS Wizard Final Task Summary Screen
8. The EDS Wizard is now completed (Figure 8.17). Click Finish.
Figure 8.17 EDS Wizard Finish Screen
Earlier versions of RSNetWorx for DeviceNet require you to close and
restart RSNetWorx for DeviceNet to enable the 1769-SM2 module to
appear in the 1769-ADN Module Configuration tab (Figure 8.10). If you
do not see the 1769-SM2 in the Hardware list, close and restart
RSNetWorx for DeviceNet.
8-12
ControlLogix w/1769-ADN DeviceNet Example Ladder Program
PowerFlex 40 Settings
The PowerFlex 40 drives used in the example program have the
following parameter settings:
Parameter
P036 - [Start Source]
P038 - [Speed Reference]
A103 - [Comm Data Rate]
A104 - [Comm Node Addr]
A107 - [Comm Format]
Setting
5 (Comm Port)
5 (Comm Port)
4 (19.2K)
100
0 (RTU 8-N-1)
1769-SM2 Settings
The 1769-SM2 module used in the example program has the following
switch settings:
Switch
Configuration Mode Switch (SW1)
Operating Mode Switch (SW2)
Setting
CONT position
1X (Single) position
ControlLogix w/1769-ADN DeviceNet Example Ladder Program
8-13
ControlLogix w/1769-ADN Example Program
Figure 8.18 Example ControlLogix Ladder Logic Main Routine
ControlLogix DeviceNet system w// 1769-ADN using 1769-SM2 in Single Mode
de
In this Single mode example program, the channels are utilized as follows:
s:
Channel 1 - Connected to 1 PowerFlex
erFle 4/40 drive (maximum allowed)
Channel 2 - Connected to 1 PowerFlex
erFle 4/40 drive (maximum allowed)
Channel 3 - Connected to 1 PowerFlex
e
4/40 drive (maximum allowed)
Note: No parameter read/write messages are shown because explicit messaging can NOT be used with
i the 1769-ADN.
This rung commands the 1756-SDN to run.
Local:6:O.CommandRegister.Run
0
1
Copy the DNB I/O (DINT format) over to an input data array in INT format for easier use by the program.
SM2_Input_Data[0] = 1769-ADN overhead
SM2_Input_Data[1] = 1769-ADN overhead
SM2_Input_Data[2] = SM2 Status word
SM2_Input_Data[3] = SM2 CH1 Logic Status
SM2_Input_Data[4] = SM2 CH1 Feedback
SM2_Input_Data[5] = SM2 CH2 Logic Status
SM2_Input_Data[6] = SM2 CH2 Feedback
SM2_Input_Data[7] = SM2 CH3 Logic Status
SM2_Input_Data[8] = SM2 CH3 Feedback
1769-ADN
Overhead
COP
Copy File
Source Local:6:I.Data[0]
Dest SM2_Input_Data[0]
Length
9
This rung enables the 1769-SM2 to send the Channel 1 Logix Command and Reference words
to the drive.
o
CH1_Enable
<SM2_Output_Data[0].0>
2
Channel 1 Subroutine
CH1 control logic
JSR
Jump To Subroutine
Routine Name Channel_1
3
This rung enables the 1769-SM2 to send the Channel 2 Logix Command and Reference words
o
to the drive.
CH2_Enable
<SM2_Output_Data[0].1>
4
Channel 2 Subroutine
5
CH2 control logic
JSR
Jump To Subroutine
Routine Name Channel_2
8-14
ControlLogix w/1769-ADN DeviceNet Example Ladder Program
Figure 8.18 Example ControlLogix Ladder Logic Main Routine (Continued)
This rung enables the 1769-SM2 to send the Channel 3 Logix Command and Reference words to the drive.
CH3_Enable
<SM2_Output_Data[0].2>
6
Channel 3 Subroutine
CH3 control logic
JSR
Jump To Subroutine
Routine Name Channel_3
7
CH1_Valid_Data
CH2_Valid_Data
CH3_Valid_Data
<SM2_Input_Data[2].0> <SM2_Input_Data[2].5> <SM2_Input_Data[2].10>
SM2_Data_Valid
8
SM2_Cfg_Data_Valid
<SM2_Input_Data[2].15>
9
SM2_Cfg_Error
/
Copy the SM2 input data array (INT format) to the DNB Outputs (DINT format).
SM2_Output_Data[0] = SM2 Status word
SM2_Output_Data[1] = SM2 CH1 Logic Command
SM2_Output_Data[2] = SM2 CH1 Reference
SM2_Output_Data[3] = SM2 CH2 Logic Command
SM2_Output_Data[4] = SM2 CH2 Reference
SM2_Output_Data[5] = SM2 CH3 Logic Command
SM2_Output_Data[6] = SM2 CH3 Reference
10
(End)
COP
Copy File
Source SM2_Output_Data[0]
Dest
Local:6:O.Data[0]
Length
4
ControlLogix w/1769-ADN DeviceNet Example Ladder Program
8-15
Figure 8.19 Example ControlLogix Ladder Logic CH1 Subroutine
1769-SM2 Channel 1 Subroutine
The following
i rungs display some of the Logic Status bits from the drive. Refer to Appendix D in the 1769-SM2 user manual
for additional information about the Logic Status word.
SM2_Input_Data[3].0
CH1_Ready
SM2_Input_Data[3].1
CH1_Active
SM2_Input_Data[3].3
CH1_Forward
SM2_Input_Data[3].7
CH1_Fault
SM2_Input_Data[3].8
CH1_At_Speed
0
1
2
3
4
5
This rung displays the Feedback from the drive. An integer represents the xxx.x Hz format (decimal is implied) used by the
drive, so a displayed value of "300" equates to 30.0 Hz.
MOV
Move
Source SM2_Input_Data[4]
100
Dest
CH1_Feedback
100
i rungs display some of the Logic Command bits sent to the drive. Refer to Appendix D in the 1769-SM2 user
The following
manual for additional information about the Logic Command word.
CH1_Stop
SM2_Output_Data[1].0
6
This rung unlatches the contact that turns on the Start command when the drive is not communicating with the 1769-SM2.
This prevents the drive from immediately starting when communications are restored. If an immediate start is desired for an
application, this rung could be deleted.
CH1_Valid_Data
<SM2_Input_Data[2].0>
CH1_Start
7
/
U
CH1_Start
SM2_Output_Data[1].1
CH1_Jog
SM2_Output_Data[1].2
CH1_Clear_Fault
SM2_Output_Data[1].3
8
9
10
8-16
ControlLogix w/1769-ADN DeviceNet Example Ladder Program
Figure 8.19 Example ControlLogix Ladder Logic CH1 Subroutine (Continued)
CH1_Forward_Cmd
SM2_Output_Data[1].4
CH1_Forward_Cmd
/
SM2_Output_Data[1].5
11
12
13
14
(End)
This rung displays the Reference being sent to the drive. An integer represents the xxx.x Hz format (decimal is implied) used
by the drive, so a displayed value of "300" equates to 30.0 Hz.
SM2 CH1
Reference
MOV
Move
Source
CH1_Reference
100
Dest SM2_Output_Data[2]
100
Return
RET
ControlLogix w/1769-ADN DeviceNet Example Ladder Program
8-17
Figure 8.20 Example ControlLogix Ladder Logic CH2 Subroutine
1769-SM2 Channel 2 Subroutine
The following rungs display some of the Logic Status bits from the drive. Refer to Appendix D in the 1769-SM2 user manual
for additional information about the Logic Status word.
SM2_Input_Data[5].0
CH2_Ready
SM2_Input_Data[5].1
CH2_Active
SM2_Input_Data[5].3
CH2_Forward
SM2_Input_Data[5].7
CH2_Fault
SM2_Input_Data[5].8
CH2_At_Speed
0
1
2
3
4
5
This rung displays the Feedback from the drive. An integer represents the xxx.x Hz format (decimal is implied) used by the
drive, so a displayed value of "300" equates to 30.0 Hz.
MOV
Move
Source SM2_Input_Data[6]
200
Dest
CH2_Feedback
200
The following
i rungs display some of the Logic Command bits sent to the drive. Refer to Appendix D in the 1769-SM2 user
manual for additional information about the Logic Command word.
CH2_Stop
SM2_Output_Data[3].0
6
i the 1769-SM2.
This rung unlatches the contact that turns on the Start command when the drive is not communicating with
This prevents the drive from immediately starting when communications are restored. If an immediate start is desired for an
application, this rung could be deleted.
CH2_Valid_Data
<SM2_Input_Data[2].5>
CH2_Start
/
7
U
CH2_Start
SM2_Output_Data[3].1
CH2_Jog
SM2_Output_Data[3].2
CH2_Clear_Fault
SM2_Output_Data[3].3
8
9
10
8-18
ControlLogix w/1769-ADN DeviceNet Example Ladder Program
Figure 8.20 Example ControlLogix Ladder Logic CH2 Subroutine (Continued)
CH2_Forward_Cmd
SM2_Output_Data[3].4
CH2_Forward_Cmd
SM2_Output_Data[3].5
11
12
13
14
(End)
/
This rung displays the Reference being sent to the drive. An integer represents the xxx.x Hz format (decimal is implied) used
by the drive, so a displayed value of "300" equates to 30.0 Hz.
SM2 CH2
Reference
MOV
Move
Source
CH2_Reference
200
Dest SM2_Output_Data[4]
2000
Return
RET
ControlLogix w/1769-ADN DeviceNet Example Ladder Program
8-19
Figure 8.21 Example ControlLogix Ladder Logic CH3 Subroutine
1769-SM2 Channel 3 Subroutine
The following
i rungs display some of the Logic Status bits from the drive. Refer to Appendix D in the 1769-SM2 user manual
for additional information about the Logic Status word.
SM2_Input_Data[7].0
CH3_Ready
SM2_Input_Data[7].1
CH3_Active
SM2_Input_Data[7].3
CH3_Forward
SM2_Input_Data[7].7
CH3_Fault
SM2_Input_Data[7].8
CH3_At_Speed
0
1
2
3
4
5
This rung displays the Feedback from the drive. An integer represents the xxx.x Hz format (decimal is implied) used by the
drive, so a displayed value of "300" equates to 30.0 Hz.
MOV
Move
Source SM2_Input_Data[8]
300
Dest
CH3_Feedback
300
i rungs display some of the Logic Command bits sent to the drive. Refer to Appendix D in the 1769-SM2 user
The following
manual for additional information about the Logic Command word.
CH3_Stop
SM2_Output_Data[5].0
6
This rung unlatches the contact that turns on the Start command when the drive is not communicating with
i the 1769-SM2.
This prevents the drive from immediately starting when communications are restored. If an immediate start is desired for an
application, this rung could be deleted.
CH3_Valid_Data
<SM2_Input_Data[2].10>
CH3_Start
7
/
U
CH3_Start
SM2_Output_Data[5].1
CH3_Jog
SM2_Output_Data[5].2
CH3_Clear_Fault
SM2_Output_Data[5].3
8
9
10
8-20
ControlLogix w/1769-ADN DeviceNet Example Ladder Program
Figure 8.21 Example ControlLogix Ladder Logic CH3 Subroutine (Continued)
CH3_Forward_Cmd
SM2_Output_Data[5].4
CH3_Forward_Cmd
/
SM2_Output_Data[5].5
11
12
13
14
(End)
This rung displays the Reference being sent to the drive. An integer represents the xxx.x Hz format (decimal is implied) used
by the drive, so a displayed value of "300" equates to 30.0 Hz.
SM2 CH3
Reference
MOV
Move
Source
CH3_Reference
300
Dest SM2_Output_Data[6]
3000
Return
RET
ControlLogix w/1769-ADN DeviceNet Example Ladder Program
Example Program Data Table
In this example program, the following controller tags are used:
Figure 8.22 Controller Tags
8-21
8-22
ControlLogix w/1769-ADN DeviceNet Example Ladder Program
An example of Input/Output values are shown below:
Figure 8.23 1769-SM2 Input Data
Figure 8.24 1769-SM2 Output Data
Chapter 9
Troubleshooting
This chapter provides information for troubleshooting potential
problems with 1769-SM2 module and network.
Topic
Locating the Status Indicators
MODULE Status Indicator
CH1…CH3 Status Indicators
Viewing Module Diagnostic Items
Viewing and Clearing Events
Page
9-1
9-2
9-3
9-4
9-6
Locating the Status Indicators
The 1769-SM2 module has four status indicators. They can be viewed on
the front of the module. See Figure 9.1.
Figure 9.1 Status Indicators
➊
MODULE
MODULE
CH2
CH1
CH3
CH2
CH3
DSI
CH1
C
H
1
➋
C
H
2
➍
➌
C
H
3
Item Status Indicator
Description
Page
➊
➋
➌
➍
MODULE
Module Status
9-2
CH1
Channel 1 Status
9-3
CH2
Channel 2 Status
9-3
CH3
Channel 3 Status
9-3
9-2
Troubleshooting
MODULE Status Indicator
The MODULE status indicator is a bicolor red and green LED.
Status
Cause
Corrective Action
Off
The module is not powered.
Apply power to the module.
Flashing
Red
The module’s configuration data • Change the controller configuration
is not valid.
data to valid settings.
• Reset the module parameters to
their default settings, and then reset
the module.
Steady Red The module is unable to
Cycle power to the controller.
establish communication with the
controller.
Flashing
Green
The module is establishing
communications with the
controller.
Normal behavior -- no action required.
Steady
Green
The module has established
communications with the
controller.
Normal behavior -- no action required.
Flashing
Red/Green
The module is in boot mode.
Flash download the application code to
the module.
Troubleshooting
9-3
CH1…CH3 Status Indicators
The CH1, CH2, and CH3 status indicators are bicolor red and green
LEDs.
Status
Cause
Corrective Action
Off
The module is not powered.
• Apply power to the module.
The channel is not connected to • Apply power to the PowerFlex 4-Class
a PowerFlex 4-Class DSI drive.
DSI drive.
• Connect the module channel to the
The channel is set for Modbus
RTU Master operation, but is not
drive using a communications cable.
transmitting.
• Verify that the 22-RJ45CBL-C*
communications cable is securely
connected and not damaged. Replace
cable if necessary.
In Multi-Drive mode, the channel
is not receiving communication • Verify the setting for the [DSI I/O Cfg x]
parameter.
from one or more configured
drives.
• Verify the settings for the [Drv x Addr x]
Flashing In Single mode, the channel is
Red
not receiving communication
from the drive.
parameters.
• Verify the settings for the node address
and data rate parameters in the drive.
• Cycle power to the drive.
Flashing The channel is properly
Green
connected to the drive and is
communicating, but is not
sending I/O to the drive.
No action required.
The channel is set for Modbus
RTU Master operation, and is
transmitting.
Steady
Green
The channel is properly
connected to the drive and is
sending I/O to the drive.
No action required.
9-4
Troubleshooting
Viewing Module Diagnostic Items
Diagnostic items are provided for each respective channel.
The following diagnostic items can be accessed using DriveExplorer
v3.01 (or higher).
Table 9.A Diagnostic Items for Module in Single Mode
No. Name
Description
1
Reserved
—
2
Logic Cmd
Current value of the product-specific Logic Command being
transmitted to the drive by this module.
3
Reference
Current value of the product-specific Reference being
transmitted to the drive by this module.
4
Reserved
—
5
Logic Sts
Current value of the product-specific Logic Status being
received from the drive by this module.
6
Feedback
Current value of the product-specific Feedback being
received from the drive by this module.
7-22 Reserved
—
23
Number of DSI receive overrun errors.
DSI Overrun Errs
24
DSI Framing Errs
Number of DSI receive framing errors.
25
DSI CRC Errs
Number of DSI receive CRC errors.
26
Boot Flash Count
Number of times the boot firmware in the module has been
flash updated.
27
App Flash Count
Number of times the application firmware in the module has
been flash updated.
Table 9.B Diagnostic Items for Module in Multi-Drive Mode
No. Name
Description
1
Reserved
—
2
Drv 0 Logic Cmd
Current value of the product-specific Logic Command being
transmitted to Drive 0 by this module.
3
Drv 0 Reference
Current value of the product-specific Reference being
transmitted to Drive 0 by this module.
4
Reserved
—
5
Drv 0 Logic Sts
Current value of the product-specific Logic Status being
received from Drive 0 by this module.
6
Drv 0 Feedback
Current value of the product-specific Feedback being
received from Drive 0 by this module.
7
Drv 1 Logic Cmd
Current value of the product-specific Logic Command being
transmitted to Drive 1 by this module.
8
Drv 1 Reference
Current value of the product-specific Reference being
transmitted to Drive 1 by this module.
Troubleshooting
9-5
Table 9.B Diagnostic Items for Module in Multi-Drive Mode (Continued)
No. Name
Description
9
Drv 1 Logic Sts
Current value of the product-specific Logic Status being
received from Drive 1 by this module.
10
Drv 1 Feedback
Current value of the product-specific Feedback being
received from Drive 1 by this module.
11
Drv 2 Logic Cmd
Current value of the product-specific Logic Command being
transmitted to Drive 2 by this module.
12
Drv 2 Reference
Current value of the product-specific Reference being
transmitted to Drive 2 by this module.
13
Drv 2 Logic Sts
Current value of the product-specific Logic Status being
received from Drive 2 by this module.
14
Drv 2 Feedback
Current value of the product-specific Feedback being
received from Drive 2 by this module.
15
Drv 3 Logic Cmd
Current value of the product-specific Logic Command being
transmitted to Drive 3 by this module.
16
Drv 3 Reference
Current value of the product-specific Reference being
transmitted to Drive 3 by this module.
17
Drv 3 Logic Sts
Current value of the product-specific Logic Status being
received from Drive 3 by this module.
18
Drv 3 Feedback
Current value of the product-specific Feedback being
received from Drive 3 by this module.
19
Drv 4 Logic Cmd
Current value of the product-specific Logic Command being
transmitted to Drive 4 by this module.
20
Drv 4 Reference
Current value of the product-specific Reference being
transmitted to Drive 4 by this module.
21
Drv 4 Logic Sts
Current value of the product-specific Logic Status being
received from Drive 4 by this module.
22
Drv 4 Feedback
Current value of the product-specific Feedback being
received from Drive 4 by this module.
23
DSI Overrun Errs
Number of DSI receive overrun errors.
24
DSI Framing Errs
Number of DSI receive framing errors.
25
DSI CRC Errs
Number of DSI receive CRC errors.
26
Boot Flash Count
Number of times the boot firmware in the module has been
flash updated.
27
App Flash Count
Number of times the application firmware in the module has
been flash updated.
9-6
Troubleshooting
Viewing and Clearing Events
The module has an event queue to record significant events that occur in
the operation of the module. When such an event occurs, an entry is put
into the event queue. You can view the event queue using DriveExplorer
v3.01 (or higher) software.
Figure 9.2 DriveExplorer Event View/Clear Screen
The event queue can contain up to 32 entries. Eventually the event queue
will become full, since its contents are retained through module resets.
At that point, a new entry replaces the oldest entry. Only an event queue
clear operation or module power cycle will clear the event queue
contents.
Resetting the module to defaults has no effect on the event queue.
Many events in the event queue occur under normal operation. If you
encounter unexpected communications problems, the events may help
you or Allen-Bradley personnel troubleshoot the problem. The following
events may appear in the event queue:
Table 9.C Module Events
Code Event
Description
Module Events
0
No Event
1
Normal Startup The module successfully started up.
Empty event queue entry.
2
Manual Reset
The module performed a self-reset.
3
Watchdog T/O
Flt
The software watchdog detected a failure and reset the module.
4
App Updated
The application firmware has been flash updated.
5
Boot Updated
The boot firmware has been flash updated.
6
EEPROM Sum The EEPROM checksum/CRC is incorrect. The functionality of
Flt
the module will be limited. Default parameters must be loaded
to clear this condition.
Troubleshooting
9-7
Table 9.C Module Events (Continued)
Code Event
Description
7-9
—
Reserved
DSI Events
10
Slave Detected The module detected that the slave has been connected.
11
Slave Removed The module detected that the slave has been disconnected.
12
Slave Logon
The module has established communications with the slave.
13
Slave Timeout
The module has lost communications with the slave.
14
Slave Brand Flt The slave brand is different than the module.
15
Host 0 Logon
The module has established communications with host 0.
16
Host 1 Logon
The module has established communications with host 1.
17
Host 2 Logon
The module has established communications with host 2.
18
Host 3 Logon
The module has established communications with host 3.
19
Host 4 Logon
The module has established communications with host 4.
20
Host 0 Timeout The module has lost communications with host 0.
21
Host 1 Timeout The module has lost communications with host 1.
22
Host 2 Timeout The module has lost communications with host 2.
23
Host 3 Timeout The module has lost communications with host 3.
24
Host 4 Timeout The module has lost communications with host 4.
25
Host 0 Brand Flt The host 0 brand is different than the module.
26
Host 1 Brand Flt The host 1 brand is different than the module.
27
Host 2 Brand Flt The host 2 brand is different than the module.
28
Host 3 Brand Flt The host 3 brand is different than the module.
29
Host 4 Brand Flt The host 4 brand is different than the module.
Network Events
40
Net Link Up
The network link is established.
41
Net Link Down
The network link is lost.
42
Dup Net Addr
The module has detected that another device is using its
network address. In this case, the module will not participate in
any network activity.
43
Net Open
An I/O connection from the network to the module was opened.
44
Net Close
An I/O connection from the network to the module was closed.
45
Net Timeout
An I/O connection from the network to the module has timed
out.
46
Net Comm Flt
The module has performed the “Comm Flt” action specified by
the user.
47
Net Idle Flt
The module has performed the “Idle Flt” action specified by the
user.
48
PCCC IO Open The module has begun receiving PCCC Control messages (the
PCCC Control Timeout was previously set to a non-zero value).
49
PCCC IO Close The device sending PCCC Control messages to the module
has set the PCCC Control Timeout to a value of zero.
50
PCCC IO Time The module has not received a PCCC Control message for
Flt
longer than the PCCC Control Timeout.
51
Net Sent Reset The module received a reset from the network.
9-8
Troubleshooting
Table 9.C Module Events (Continued)
Code Event
Description
52
Msg Ctrl Open
The module has begun receiving Client-Server Control
messages (the Client-Server Control Timeout was previously
set to a non-zero value).
53
Msg Ctrl Close
The device sending Client-Server Control messages to the
module has set the Client-Server Control Timeout to a value of
zero.
54
Msg Ctrl
Timeout
The module has not received a Client-Server Control message
for longer than the established timeout period.
Appendix A
Specifications
Appendix A presents the specifications for the module.
Topic
Communications
Electrical
Mechanical
Environmental
Regulatory Compliance
DSI Cable Requirements
Page
A-1
A-1
A-1
A-2
A-2
A-2
Communications
Drive
Protocols
Data Rates
DSI or Modbus RTU Master
DSI Operation: 19200 bps
Modbus RTU Master Operation: 300, 600, 1200, 2400,
4800, 9600, 19200, or 38400 bps
Electrical
Consumption
Module data only
(no Channel data)
Power Supply
Distance Rating
350 mA @ 5Vdc and 0 mA @ 24Vdc supplied by the
Compact I/O Power Supply
4 (the 1769-SM2 module cannot be more than 4 modules
away from the power supply)
Mechanical
Dimensions
Height
Depth
Width
Weight
118 mm (4.65 inches)
87 mm (3.43 inches)
35 mm (1.38 inches)
142g (5 oz.)
A-2
Specifications
Environmental
Temperature
Operating
Storage
Relative Humidity
Atmosphere
Shock
Operational
Non-Operational
Vibration
Operational
Non-Operational
-10…50 °C (14…122 °F)
-40…85 °C (-40…185 °F)
-5…95% non-condensing
Important: The module must not be installed in an area
where the ambient atmosphere contains volatile or corrosive
gas, vapors, or dust. If the module is not going to be installed
for a period of time, it must be stored in an area where it will
not be exposed to a corrosive atmosphere.
30g, 11 ms
50g, 11 ms
5g, 10 to 500 Hz
5g, 5 to 2000 Hz
Regulatory Compliance
UL
cUL
CE
CTick
UL508C
CAN/CSA C22.2 No. 14-M91
EN50081-2 and EN61000-6-2
AS/NZS 2064
NOTE: In a domestic environment this product may cause radio
interference in which case supplementary mitigation measures may be
required.
NOTE: To meet CE and CTick certification, a ferrite core (Fair-Rite p/n
2643102002) must be added to DSI communication cables longer than
10 m (33 ft.), and the core must be attached within 305 mm (12 in.) of
the 1769-SM2 module.
DSI Cable Requirements
The maximum cable distance between the 1769-SM2 module and
connected PowerFlex 4-Class drives is 10 m (32.8 ft.) when 8-conductor
cables are used in Single mode. The maximum cable distance when
2-conductor twisted-pair network wiring is used with RJ45 two-position
terminal blocks (AK-U0-RJ45-TB2P) in Single or Multi-Drive mode is
1219 m / 4000 ft. (standard RS-485 specifications).
The installer must follow common system wiring practices and route
cables away from sources of EMI.
Appendix B
Module Parameters
Appendix B provides information about the 1769-SM2 module parameters.
Topic
About Parameter Numbers
Parameter List
Page
B-1
B-1
About Parameter Numbers
The parameters in the module are numbered consecutively.
Configuration Tool
Numbering Scheme
• DriveExplorer
The module parameters begin with parameter 01. For
example, Parameter 01 - [Config Mode] is parameter 01
as indicated by this manual.
• DriveExecutive
• HIM
TIP: All module parameters—except Parameters 01 - [Config Mode],
02 - [DSI Mode], and 03 - [Reset Module]—are grouped by channel
number. The respective channel number is shown at the end of the
parameter name (for example, Parameter 04 - [Idle Action 1] for CH1).
Parameter List
Parameter
No. Name and Description
01 [Config Mode]
02
Displays the module’s configuration mode
(Controller or Parameter) set with the
Configuration Mode Switch (SW1 in Figure 2.1).
[DSI Mode]
Displays the module’s operating mode (Single or
Multi-Drive) set with the Operating Mode Switch
(SW2 in Figure 2.1).
Details
Default:
Values:
Type:
Default:
Values:
Type:
0 = Controller
0 = Controller
1 = Parameter
Read Only
0 = Single
0 = Single
1 = Multi-Drive
Read Only
B-2
Module Parameters
Parameter
No. Name and Description
03 [Reset Module]
Details
Default:
No action if set to “0” (Ready). Resets the module Values
if set to “1” (Reset Module). Restores the module
to its factory default settings if set to “2” (Set
Defaults). This parameter is a command. It will be Type:
reset to “0” (Ready) after the command has been Reset Required:
performed.
!
04
05
ATTENTION: Risk of injury or equipment damage exists. If the module is
transmitting I/O that controls the drive, the drive may fault when you reset the
module. Determine how your drive will respond before resetting the module.
[Idle Action 1]
Default:
Sets the action that the module and CH1 drive(s) Values:
take if the module detects that the controller is in
program mode or faulted. This setting is effective
only if I/O that controls the drive is transmitted
through the module.
Type:
Reset Required:
!
07
0 = Fault
0 = Fault
1 = Stop
2 = Zero Data
3 = Hold Last
4 = Send Flt Cfg
Read/Write
No
ATTENTION: Risk of injury or equipment damage exists. Parameter 04 - [Idle
Action 1] lets you determine the action of the module and CH1 connected
drive(s) when the controller is idle. By default, this parameter faults the drive. You
can set this parameter so that the drive continues to run. Precautions should be
taken to ensure that the setting of this parameter does not create a risk of injury or
equipment damage. When commissioning the drive, verify that your system
responds correctly to various situations (for example, a disconnected drive).
[Flt Cfg Logic 1]
Sets the Logic Command data that is sent to the
CH1 drive(s) if Parameter 04 - [Idle Action 1] is
set to “4” (Send Flt Cfg) and the controller is idle.
06
0 = Ready
0 = Ready
1 = Reset Module
2 = Set Defaults
Read/Write
No
Default:
Minimum:
Maximum:
Type:
Reset Required:
0000 0000 0000 0000
0000 0000 0000 0000
1111 1111 1111 1111
Read/Write
No
Type:
Reset Required:
0
0
65535
Read/Write
No
0 = Drive 0
0 = Drive 0
1 = Drives 0…1
2 = Drives 0…2
3 = Drives 0…3
4 = Drives 0…4
5 = RTU Master
Read/Write
Yes
The bit definitions will depend on the drive(s) to
which the module is connected. See Appendix D.
[Flt Cfg Ref 1]
Default:
Minimum:
Sets the Reference data that is sent to the CH1
drive(s) if Parameter 04 - [Idle Action 1] is set to Maximum:
Type:
“4” (Send Flt Cfg) and the controller is idle.
Reset Required:
[DSI I/O Cfg 1]
Default:
Values:
Sets the number of CH1 drives that are used in
Multi-Drive mode. Identifies the connections that
would be attempted on a reset or power cycle.
Module Parameters
[Drv 0 Addr 1]
[Drv 1 Addr 1]
[Drv 2 Addr 1]
[Drv 3 Addr 1]
[Drv 4 Addr 1]
Sets the corresponding node addresses of the
daisy-chained CH1 drives when the module is in
Multi-Drive mode.
14
Drive 4
Drive 3
Drive 2
Drive 1
Drive 0
Default
Bit
Not Used
Type:
Bit
Definition
09
10
11
12
13
xxx0 0000
0 = Drive Active
1 = Drive Inactive
Read Only
Not Used
Displays the CH1 drives that are active in
Multi-Drive mode.
Details
Default:
Bit Values:
Not Used
Parameter
No. Name and Description
08 [DSI I/O Act 1]
x
7
x
6
x
5
0
4
0
3
0
2
0
1
1
0
Default:
Default:
Default:
Default:
Default:
Minimum:
Maximum:
Type:
Reset Required:
Important: The setting for each of these
parameters must match the drive Parameter 104 [Comm Node Addr] value for each respective
drive. Each drive node address must be unique
(no duplicate node addresses).
[RTU Baud Rate 1]
Default:
Sets the baud rate used by the CH1 drives when Values:
the module is in Multi-Drive mode and Parameter
07 - [DSI I/O Cfg 1] is set to “5” (RTU Master).
15
[RTU Format 1]
Selects the RTU format used by the CH1 drives
when the module is in Multi-Drive mode and
Parameter 07 - [DSI I/O Cfg 1] is set to “5” (RTU
Master). The RTU format consists of three
components: data bits (8 data bits only), parity
(None, Even or Odd), and stop bits (1 or 2).
16
B-3
Type:
Reset Required:
Default:
Value:
Type:
Reset Required:
Default:
[RTU Rx Delay 1]
Sets the CH1 inter-character delay used to detect Minimum:
the end of a receive packet when the module is in Maximum:
Type:
Multi-Drive mode and Parameter 07 - [DSI I/O
Reset Required:
Cfg 1] is set to “5” (RTU Master). If this value is
set to 0 (zero), the ModBus default delay of 1.5
character times is used.
100
100
100
100
100
0
247
Read/Write
Yes
0 = 38.4K bps
0 = 38.4K bps
1 = 19200 bps
2 = 9600 bps
3 = 4800 bps
4 = 2400 bps
5 = 1200 bps
6 = 600 bps
7 = 300 bps
Read/Write
Yes
0 = 8-N-1
0 = 8-N-1
1 = 8-E-1
2 = 8-O-1
3 = 8-N-2
4 = 8-E-2
5 = 8-O-2
Read/Write
Yes
0 milliseconds
0 milliseconds
500 milliseconds
Read/Write
Yes
B-4
Module Parameters
Parameter
No. Name and Description
17 [RTU Tx Delay 1]
18
19
Details
Default:
Sets the CH1 inter-frame delay used to delay the Minimum:
sending of a transmit packet when the module is in Maximum:
Type:
Multi-Drive mode and Parameter 07 - [DSI I/O
Reset Required:
Cfg 1] is set to “5” (RTU Master). If this value is
set to 0 (zero), the ModBus default delay of 3.5
character times is used.
[RTU MsgTimeout 1]
Default:
Minimum:
Sets the amount of time in seconds that the
Maximum:
module will wait for a response from a ModBus
RTU CH1 slave when the module is in Multi-Drive Type:
mode and Parameter 07 - [DSI I/O Cfg 1] is set to Reset Required:
“5” (RTU Master).
[Idle Action 2]
Default:
Sets the action that the module and CH2 drive(s) Values:
take if the module detects that the controller is in
program mode or faulted. This setting is effective
only if I/O that controls the drive is transmitted
through the module.
Type:
Reset Required:
!
20
22
2 seconds
0 seconds
60 seconds
Read/Write
Yes
0 = Fault
0 = Fault
1 = Stop
2 = Zero Data
3 = Hold Last
4 = Send Flt Cfg
Read/Write
No
ATTENTION: Risk of injury or equipment damage exists. Parameter 19 - [Idle
Action 2] lets you determine the action of the module and CH2 connected
drive(s) when the controller is idle. By default, this parameter faults the drive. You
can set this parameter so that the drive continues to run. Precautions should be
taken to ensure that the setting of this parameter does not create a risk of injury or
equipment damage. When commissioning the drive, verify that your system
responds correctly to various situations (for example, a disconnected drive).
[Flt Cfg Logic 2]
Sets the Logic Command data that is sent to the
CH2 drive(s) if Parameter 19 - [Idle Action 2] is
set to “4” (Send Flt Cfg) and the controller is idle.
21
0 milliseconds
0 milliseconds
500 milliseconds
Read/Write
Yes
Default:
Minimum:
Maximum:
Type:
Reset Required:
0000 0000 0000 0000
0000 0000 0000 0000
1111 1111 1111 1111
Read/Write
No
Type:
Reset Required:
0
0
65535
Read/Write
No
0 = Drive 0
0 = Drive 0
1 = Drives 0…1
2 = Drives 0…2
3 = Drives 0…3
4 = Drives 0…4
5 = RTU Master
Read/Write
Yes
The bit definitions will depend on the drive(s) to
which the module is connected. See Appendix D.
[Flt Cfg Ref 2]
Default:
Minimum:
Sets the Reference data that is sent to the CH2
drive(s) if Parameter 19 - [Idle Action 2] is set to Maximum:
Type:
“4” (Send Flt Cfg) and the controller is idle.
Reset Required:
[DSI I/O Cfg 2]
Default:
Values:
Sets the number of CH1 drives that are used in
Multi-Drive mode. Identifies the connections that
would be attempted on a reset or power cycle.
Module Parameters
[Drv 0 Addr 2]
[Drv 1 Addr 2]
[Drv 2 Addr 2]
[Drv 3 Addr 2]
[Drv 4 Addr 2]
Sets the corresponding node addresses of the
daisy-chained CH2 drives when the module is in
Multi-Drive mode.
29
Drive 4
Drive 3
Drive 2
Drive 1
Drive 0
Default
Bit
Not Used
Type:
Bit
Definition
24
25
26
27
28
xxx0 0000
0 = Drive Active
1 = Drive Inactive
Read Only
Not Used
Displays the CH2 drives that are active in
Multi-Drive mode.
Details
Default:
Bit Values:
Not Used
Parameter
No. Name and Description
23 [DSI I/O Act 2]
x
7
x
6
x
5
0
4
0
3
0
2
0
1
1
0
Default:
Default:
Default:
Default:
Default:
Minimum:
Maximum:
Type:
Reset Required:
Important: The setting for each of these
parameters must match the drive Parameter 104 [Comm Node Addr] value for each respective
drive. Each drive node address must be unique
(no duplicate node addresses).
[RTU Baud Rate 2]
Default:
Sets the baud rate used by the CH2 drives when Values:
the module is in Multi-Drive mode and Parameter
22 - [DSI I/O Cfg 2] is set to “5” (RTU Master).
30
[RTU Format 2]
Selects the RTU format used by the CH2 drives
when the module is in Multi-Drive mode and
Parameter 22 - [DSI I/O Cfg 2] is set to “5” (RTU
Master). The RTU format consists of three
components: data bits (8 data bits only), parity
(None, Even or Odd), and stop bits (1 or 2).
31
B-5
Type:
Reset Required:
Default:
Value:
Type:
Reset Required:
Default:
[RTU Rx Delay 2]
Sets the CH2 inter-character delay used to detect Minimum:
the end of a receive packet when the module is in Maximum:
Type:
Multi-Drive mode and Parameter 22 - [DSI I/O
Reset Required:
Cfg 2] is set to “5” (RTU Master). If this value is
set to 0 (zero), the ModBus default delay of 1.5
character times is used.
100
100
100
100
100
0
247
Read/Write
Yes
0 = 38.4K bps
0 = 38.4K bps
1 = 19200 bps
2 = 9600 bps
3 = 4800 bps
4 = 2400 bps
5 = 1200 bps
6 = 600 bps
7 = 300 bps
Read/Write
Yes
0 = 8-N-1
0 = 8-N-1
1 = 8-E-1
2 = 8-O-1
3 = 8-N-2
4 = 8-E-2
5 = 8-O-2
Read/Write
Yes
0 milliseconds
0 milliseconds
500 milliseconds
Read/Write
Yes
B-6
Module Parameters
Parameter
No. Name and Description
32 [RTU Tx Delay 2]
33
34
Details
Default:
Sets the CH2 inter-frame delay used to delay the Minimum:
sending of a transmit packet when the module is in Maximum:
Type:
Multi-Drive mode and Parameter 22 - [DSI I/O
Reset Required:
Cfg 2] is set to “5” (RTU Master). If this value is
set to 0 (zero), the ModBus default delay of 3.5
character times is used.
[RTU MsgTimeout 2]
Default:
Minimum:
Sets the amount of time in seconds that the
Maximum:
module will wait for a response from a ModBus
RTU CH2 slave when the module is in Multi-Drive Type:
mode and Parameter 22 - [DSI I/O Cfg 2] is set to Reset Required:
“5” (RTU Master).
[Idle Action 3]
Default:
Sets the action that the module and CH3 drive(s) Values:
take if the module detects that the controller is in
program mode or faulted. This setting is effective
only if I/O that controls the drive is transmitted
through the module.
Type:
Reset Required:
!
35
37
2 seconds
0 seconds
60 seconds
Read/Write
Yes
0 = Fault
0 = Fault
1 = Stop
2 = Zero Data
3 = Hold Last
4 = Send Flt Cfg
Read/Write
No
ATTENTION: Risk of injury or equipment damage exists. Parameter 34 - [Idle
Action 3] lets you determine the action of the module and CH3 connected
drive(s) when the controller is idle. By default, this parameter faults the drive. You
can set this parameter so that the drive continues to run. Precautions should be
taken to ensure that the setting of this parameter does not create a risk of injury or
equipment damage. When commissioning the drive, verify that your system
responds correctly to various situations (for example, a disconnected drive).
[Flt Cfg Logic 3]
Sets the Logic Command data that is sent to the
CH3 drive(s) if Parameter 34 - [Idle Action 3] is
set to “4” (Send Flt Cfg) and the controller is idle.
36
0 milliseconds
0 milliseconds
500 milliseconds
Read/Write
Yes
Default:
Minimum:
Maximum:
Type:
Reset Required:
The bit definitions will depend on the drive(s) to
which the module is connected. See Appendix D.
[Flt Cfg Ref 3]
Default:
Minimum:
Sets the Reference data that is sent to the CH3
drive(s) if Parameter 34 - [Idle Action 3] is set to Maximum:
Type:
“4” (Send Flt Cfg) and the controller is idle.
Reset Required:
[DSI I/O Cfg 3]
Default:
Values:
Sets the number of CH1 drives that are used in
Multi-Drive mode. Identifies the connections that
would be attempted on a reset or power cycle.
Type:
Reset Required:
0000 0000 0000 0000
0000 0000 0000 0000
1111 1111 1111 1111
Read/Write
No
0
0
65535
Read/Write
No
0 = Drive 0
0 = Drive 0
1 = Drives 0…1
2 = Drives 0…2
3 = Drives 0…3
4 = Drives 0…4
5 = RTU Master
Read/Write
Yes
Module Parameters
[Drv 0 Addr 3]
[Drv 1 Addr 3]
[Drv 2 Addr 3]
[Drv 3 Addr 3]
[Drv 4 Addr 3]
Sets the corresponding node addresses of the
daisy-chained CH3 drives when the module is in
Multi-Drive mode.
44
Drive 4
Drive 3
Drive 2
Drive 1
Drive 0
Default
Bit
Not Used
Type:
Bit
Definition
39
40
41
42
43
xxx0 0000
0 = Drive Active
1 = Drive Inactive
Read Only
Not Used
Displays the CH3 drives that are active in
Multi-Drive mode.
Details
Default:
Bit Values:
Not Used
Parameter
No. Name and Description
38 [DSI I/O Act 3]
x
7
x
6
x
5
0
4
0
3
0
2
0
1
1
0
Default:
Default:
Default:
Default:
Default:
Minimum:
Maximum:
Type:
Reset Required:
Important: The setting for each of these
parameters must match the drive Parameter 104 [Comm Node Addr] value for each respective
drive. Each drive node address must be unique
(no duplicate node addresses).
[RTU Baud Rate 3]
Default:
Sets the baud rate used by the CH3 drives when Values:
the module is in Multi-Drive mode and Parameter
37 - [DSI I/O Cfg 3] is set to “5” (RTU Master).
45
[RTU Format 3]
Selects the RTU format used by the CH3 drives
when the module is in Multi-Drive mode and
Parameter 37 - [DSI I/O Cfg 3] is set to “5” (RTU
Master). The RTU format consists of three
components: data bits (8 data bits only), parity
(None, Even or Odd), and stop bits (1 or 2).
46
B-7
Type:
Reset Required:
Default:
Value:
Type:
Reset Required:
Default:
[RTU Rx Delay 3]
Sets the CH3 inter-character delay used to detect Minimum:
the end of a receive packet when the module is in Maximum:
Type:
Multi-Drive mode and Parameter 37 - [DSI I/O
Reset Required:
Cfg 3] is set to “5” (RTU Master). If this value is
set to 0 (zero), the ModBus default delay of 1.5
character times is used.
100
100
100
100
100
0
247
Read/Write
Yes
0 = 38.4K bps
0 = 38.4K bps
1 = 19200 bps
2 = 9600 bps
3 = 4800 bps
4 = 2400 bps
5 = 1200 bps
6 = 600 bps
7 = 300 bps
Read/Write
Yes
0 = 8-N-1
0 = 8-N-1
1 = 8-E-1
2 = 8-O-1
3 = 8-N-2
4 = 8-E-2
5 = 8-O-2
Read/Write
Yes
0 milliseconds
0 milliseconds
500 milliseconds
Read/Write
Yes
B-8
Module Parameters
Parameter
No. Name and Description
47 [RTU Tx Delay 3]
48
Details
Default:
Sets the CH3 inter-frame delay used to delay the Minimum:
sending of a transmit packet when the module is in Maximum:
Type:
Multi-Drive mode and Parameter 37 - [DSI I/O
Reset Required:
Cfg 3] is set to “5” (RTU Master). If this value is
set to 0 (zero), the ModBus default delay of 3.5
character times is used.
[RTU MsgTimeout 3]
Default:
Minimum:
Sets the amount of time in seconds that the
Maximum:
module will wait for a response from a ModBus
RTU CH3 slave when the module is in Multi-Drive Type:
mode and Parameter 37 - [DSI I/O Cfg 3] is set to Reset Required:
“5” (RTU Master).
0 milliseconds
0 milliseconds
500 milliseconds
Read/Write
Yes
2 seconds
0 seconds
60 seconds
Read/Write
Yes
Appendix C
CIP/DSI Objects
Appendix C presents information about the CIP and DSI objects that can
be accessed using Explicit Messages.
For information on formatting Explicit Messages and example ladder
logic programs, refer to the corresponding chapter:
•
Chapter 5, Understanding Explicit Messaging
•
Chapter 6, MicroLogix 1500 Example Ladder Programs
•
Chapter 7, CompactLogix Example Ladder Programs
•
Chapter 8, ControlLogix w/1769-ADN DeviceNet Example Ladder
Program
Object
Class Code
Hex.
Page
Dec.
CIP Identity Object
0x01
1
C-3
CIP Parameter Object
0x0F
15
C-4
DSI Device Object
0x92
146
C-7
DSI Parameter Object
0x93
147
C-10
DSI Fault Object
0x97
151
C-14
DSI Diagnostic Object
0x99
153
C-16
TIP: Refer to the CIP Common specification for more information
about CIP objects. Information about the CIP Common specification is
available on the ODVA web site (http://www.odva.org).
C-2
CIP/DSI Objects
Supported Data Types
Data Type
Description
BYTE
8-bit unsigned integer
WORD
16-bit unsigned integer
DWORD
32-bit unsigned integer
LWORD
64-bit unsigned integer
SINT
8-bit signed integer
USINT
8-bit unsigned integer
INT
16-bit signed integer
UINT
16-bit unsigned integer
DINT
32-bit signed integer
UDINT
32-bit unsigned integer
BOOL
8-bit value -- low bit is true or false
BOOL[n]
Array of n bits
STRING[n]
Array of n characters
SHORT_STRING
1-byte length indicator + that many characters
STRUCT
Structure name only - no size in addition to elements
CONTAINER
32-bit parameter value - sign extended if necessary
TCHAR
8 or 16-bit character
REAL
32-bit floating point
CIP/DSI Objects
C-3
CIP Identity Object
Class Code
Hexadecimal
0x01
Decimal
1
Services
Service Code
0x01
0x0E
Implemented for:
Class
Instance
Yes
Yes
Yes
Yes
Service Name
Get_Attributes_All
Get_Attribute_Single
Class Attributes
Attribute
ID
1
2
6
Access
Rule
Get
Get
Get
7
Get
Name
Data Type
Description
Revision
Max Instance
Max ID Number of
Class Attributes
Max ID Number of
Instance Attributes
UINT
UINT
UINT
1
1
7
UINT
7
Instance Attributes
Attribute
ID
1
2
3
Access
Rule
Get
Get
Get
4
Get
Name
Data Type
Description
Vendor ID
Device Type
Product Code
UINT
UINT
UINT
1 = Allen-Bradley
132
Number identifying product
name and rating
STRUCT of:
USINT
USINT
WORD
UDINT
SHORT_STRING
5
Get
Revision:
Major
Minor
Status
6
7
Get
Get
Serial Number
Product Name
Value varies
Value varies
Bit 0 = Owned
Bit 2 = Configured
Bit 10 = Recoverable fault
Bit 11 = Unrecoverable fault
Unique 32-bit number
Product name and rating
C-4
CIP/DSI Objects
CIP Parameter Object
Class Code
Hexadecimal
0x0F
Decimal
15
Instances
The parameters for the DSI devices can be accessed using the
instance-offset encoding shown in the table below:
Instances (Dec.)
0…16383
16384…17407
17408…18431
18432…19455
19456…20479
20480…21503
21504…22527
(1)
Single-Drive Mode
Instances 0…1023 in drive/module (1)
Instances 0…1023 in module
Instances 0…1023 in drive
Not supported
Not supported
Not supported
Not supported
Multi-Drive Mode
Instances 0…1023 in module
Instances 0…1023 in module
Instances 0…1023 in Drive 0
Instances 0…1023 in Drive 1
Instances 0…1023 in Drive 2
Instances 0…1023 in Drive 3
Instances 0…1023 in Drive 4
The module parameters are appended to the drive parameters for this range of instances.
Class Attributes
Attribute
ID
1
2
8
Access
Rule
Get
Get
Get
9
Get
10
Get
Name
Data Type Description
Revision
Max Instance
Parameter
Class
Descriptor
UINT
UINT
WORD
Configuration
Assembly
Instance
Native
Language
UINT
USINT
1
Number of parameters
0 = False, 1 = True
Bit 0 = Supports parameter instances
Bit 1 = Supports full attributes
Bit 2 = Must do NVS save command
Bit 3 = Parameters are stored in NVS
0
0 = English
1 = French
2 = Spanish
3 = Italian
4 = German
5 = Japanese
6 = Portuguese
7 = Mandarin Chinese
8 = Russian
9 = Dutch
CIP/DSI Objects
C-5
CIP Parameter Object (Continued)
Instance Attributes
Attribute Access Name
ID
Rule
(1)
Parameter Value
1
2
Get
Link Path Size
Data Type Description
(2)
(3)
USINT
0 = No link specified
n = The size of Attribute 3 in bytes
(4)
3
4
Get
Get
Link Path
Descriptor
WORD
5
Get
Data Type
USINT
6
7
Get
Get
Get
9
Get
Help String
USINT
SHORT_
STRING
SHORT_
STRING
SHORT_
STRING
(3)
8
Data Size
Parameter Name
String
Units String
10
11
12
13
14
15
16
17
18
19
20
21
Get
Get
Get
Get
Get
Get
Get
Get
Get
Get
Get
Get
Minimum Value
Maximum Value
Default Value
Scaling Multiplier
Scaling Divisor
Scaling Base
Scaling Offset
Multiplier Link
Divisor Link
Base Link
Offset Link
Decimal Precision
(1)
(3)
(1)
(3)
(1)
(3)
UINT
UINT
UINT
UINT
UINT
UINT
UINT
UINT
USINT
(3)
(1)
0 = False, 1 = True
Bit 1 = Supports ENUMs
Bit 2 = Supports scaling
Bit 3 = Supports scaling links
Bit 4 = Read only
Bit 5 = Monitor
Bit 6 = Extended precision scaling
0xC2 = SINT (8-bits)
0xC3 = INT (16-bits)
0xC4 = DINT (32-bits)
0xC6 = USINT (8-bits)
0xC7 = UINT (16-bits)
0xCA = REAL (32-bits)
0xD2 = WORD (16-bits)
(3)
(3)
Null string
(3)
(3)
(3)
(3)
(3)
(3)
(3)
(3)
Access rule is defined in bit 4 of instance attribute 4. 0 = Get/Set, 1 = Get.
Specified in descriptor, data type, and data size.
(3)
Value varies based on parameter instance.
(4) Refer to the CIP Common specification for a description of the link path.
(2)
C-6
CIP/DSI Objects
CIP Parameter Object (Continued)
Services
Service Code
0x01
0x05
0x0E
0x10
0x4B
Implemented for:
Class
Instance
Yes
Yes
Yes
No
Yes
Yes
No
Yes
No
Yes
Service Name
Get_Attributes_All
Reset
Get_Attribute_Single
Set_Attribute_Single
Get_Enum_String
CIP/DSI Objects
C-7
DSI Device Object
Class Code
Hexadecimal
0x92
Decimal
146
Services
Service Code
0x0E
0x10
Implemented for:
Class
Instance
Yes
Yes
Yes
Yes
Service Name
Get_Attribute_Single
Set_Attribute_Single
Instances
The number of instances depends on the number of components in the
device. The total number of components can be read in Instance 0, Class
Attribute 4.
Instances (Dec.)
0…16383
16384…17407
17408…18431
18432…19455
19456…20479
20480…21503
21504…22527
Single-Drive Mode
Instances 0…16383 in drive
Instances 0…1023 in module
Instances 0…1023 in module
Instances 0…1023 in slave
Not supported
Not supported
Not supported
Multi-Drive Mode
Instances 0…16383 in Drive 0
Instances 0…1023 in module
Instances 0…1023 in Drive 1
Instances 0…1023 in Drive 2
Instances 0…1023 in Drive 3
Instances 0…1023 in Drive 4
Instances 0…1023 in module
Class Attributes
Attribute
ID
0
1
2
Access
Rule
Get
Get
Set
Name
Data Type
Description
Family Code
Family Text
Language Code
BYTE
STRING[16]
BYTE
Code identifying the device.
Text identifying the device.
0 = English
1 = French
2 = Spanish
3 = Italian
4 = German
5 = Japanese
6 = Portuguese
7 = Mandarin Chinese
8 = Russian
9 = Dutch
C-8
CIP/DSI Objects
DSI Device Object (Continued)
Class Attributes (Continued)
Attribute Access Name
ID
Rule
3
Get
Product Series
Data Type
Description
BYTE
4
Get
Number of
Components
BYTE
5
Set
User Definable Text
STRING[16]
6
7
8
Get
Get
Get
Status Text
Configuration Code
Configuration Text
STRING[12]
BYTE
STRING[16]
9
11
Get
Get
Brand Code
NVS Checksum
WORD
WORD
12
13
Get
Get
Class Revision
WORD
Character Set Code BYTE
1=A
2 = B…
Number of components (for example,
main control board, I/O boards) in the
device.
Text identifying the device with a
user-supplied name
Text describing the status of the device.
Identification of variations.
Text identifying a variation of a family
device.
0x0001 = Allen-Bradley
Checksum of the Non-Volatile Storage in
a device.
2 = DSI
0 = SCANport HIM
1 = ISO 8859-1 (Latin 1)
2 = ISO 8859-2 (Latin 2)
3 = ISO 8859-3 (Latin 3)
4 = ISO 8859-4 (Latin 4)
5 = ISO 8859-5 (Cyrillic)
6 = ISO 8859-6 (Arabic)
7 = ISO 8859-7 (Greek)
8 = ISO 8859-8 (Hebrew)
9 = ISO 8859-9 (Turkish)
10 = ISO 8859-10 (Nordic)
255 = ISO 10646 (Unicode)
14
Get
15
Get
Product Option
Support Bits
Languages
Supported
16
17
18
Get
Get
Get
STRUCT of:
BYTE
BYTE[n]
Date of Manufacture STRUCT of:
WORD
BYTE
BYTE
Product Revision
STRUCT of:
BYTE
BYTE
Serial Number
DWORD
Number of Languages
Language Codes (See Class Attribute 2)
Year
Month
Day
Major Firmware Release
Minor Firmware Release
Value between 0x00 and 0xFFFFFFFF
CIP/DSI Objects
DSI Device Object (Continued)
Instance Attributes
Attribute
ID
3
4
Access Name
Rule
Get
Component Name
Get
Component
Firmware Revision
5
Get
6
Get
7
Get
8
Get
Component
Hardware Change
Number
First Flash Object
Instance
Number of Flash
Object Instances
Component Serial
Number
Data Type
Description
STRING[32]
STRUCT of:
BYTE
BYTE
BYTE
Name of the component
DWORD
Major Revision
Minor Revision
Value between 0x00 and
0xFFFFFFFF
C-9
C-10
CIP/DSI Objects
DSI Parameter Object
Class Code
Hexadecimal
0x93
Decimal
147
Instances
The number of instances depends on the number of parameters in the
device. The total number of parameters can be read in Instance 0,
Attribute 0.
Instances (Dec.)
0…16383
16384…17407
17408…18431
18432…19455
19456…20479
20480…21503
21504…22527
Single-Drive Mode
Instances 0…16383 in drive
Instances 0…1023 in module
Instances 0…1023 in module
Instances 0…1023 in slave
Not supported
Not supported
Not supported
Multi-Drive Mode
Instances 0…16383 in Drive 0
Instances 0…1023 in module
Instances 0…1023 in Drive 1
Instances 0…1023 in Drive 2
Instances 0…1023 in Drive 3
Instances 0…1023 in Drive 4
Instances 0…1023 in module
Class Attributes
Attribute Access Name
ID
Rule
0
Get
Number of
Instances
1
Set
Write Protect
Password
2
Set
NVS Command
Write
3
Get
4
Get
5
Get
7
8
9
Data Type
Description
WORD
Number of parameters in the device
WORD
0 = Password disabled
n = Password
0 = No Operation
1 = Store values in active memory to NVS
2 = Load values in NVS to active memory
3 = Load default values to active memory
Checksum of all parameter values in a user
set in NVS
Checksum of parameter links in a user set
in NVS
First parameter available if parameters are
protected by passwords. A “0” indicates all
parameters are protected.
2 = DSI
The first parameter that has been written
with a value outside of its range. A “0”
indicates no errors.
0 = No Operation
1 = Clear All Parameter Links (This does not
clear links to function blocks.)
BYTE
NVS Parameter
Value Checksum
NVS Link Value
Checksum
First Accessible
Parameter
WORD
Get
Get
Class Revision
First Parameter
Processing Error
WORD
WORD
Set
Link Command
BYTE
WORD
WORD
CIP/DSI Objects
C-11
DSI Parameter Object (Continued)
Instance Attributes
Attribute Access Name
ID
Rule
7
Get
DSI Online Read
Full
8
9
11
Get
DSI Descriptor
Get/Set DSI Parameter
Value
Get/Set DSI RAM
Parameter Value
Get/Set DSI Link
12
Get
13
Get
10
14
Get
15
Get
16
Get
(1)
Help Object
Instance
DSI Read Basic
DSI Parameter
Name
DSI Parameter
Alias
Parameter
Processing Error
Data Type
Description
STRUCT of:
BOOL[32]
CONTAINER(1)
CONTAINER
CONTAINER
CONTAINER
WORD
WORD
STRING[4]
UINT
UINT
UINT
INT
BYTE[3]
BYTE
STRING[16]
BOOL[32]
Various
Descriptor (see pages C-12 and C-13)
Parameter value
Minimum value
Maximum value
Default value
Next parameter
Previous parameter
Units (e.g., Amp, Hz)
Multiplier (2)
Divisor (2)
Base (2)
Offset (2)
Link (source of the value) (0 = no link)
Always zero (0)
Parameter name
Descriptor (see pages C-12 and C-13)
Parameter value in NVS. (3)
Various
Parameter value in temporary memory.
BYTE[3]
WORD
Link (parameter or function block that is
the source of the value) (0 = no link)
ID for help text for this parameter
STRUCT of:
BOOL[32]
CONTAINER
CONTAINER
CONTAINER
CONTAINER
STRING[16]
STRING[4]
STRING[16]
Descriptor (see pages C-12 and C-13)
Parameter value
Minimum value
Maximum value
Default value
Parameter name
Units (e.g., Amp, Hz)
Parameter name
STRING[16]
BYTE
Customer supplied parameter name.
Only supported by PowerFlex 700S at
time of publication.
0 = No error
1 = Value is less than the minimum
2 = Value is greater than the maximum
A CONTAINER is a 32-bit block of data that contains the data type used by a parameter value. If signed, the value
is sign extended. Padding is used in the CONTAINER to ensure that it is always 32-bits.
(2) This value is used in the formulas used to convert the parameter value between display units and internal units.
Refer to Formulas for Converting on page C-13.
(3)
Do NOT continually write parameter data to NVS. Refer to the attention on page 5-1.
C-12
CIP/DSI Objects
DSI Parameter Object (Continued)
Descriptor Attributes
Bit
0
1
2
Name
Data Type (Bit 1)
Data Type (Bit 2)
Data Type (Bit 3)
3
Sign Type
4
Hidden
5
Not a Link Sink
6
Not Recallable
7
ENUM
8
Writable
9
Not Writable When
Enabled
Instance
10
11
12
13
14
15
16
17
18
Reserved
Decimal Place (Bit 0)
Decimal Place (Bit 1)
Decimal Place (Bit 2)
Decimal Place (Bit 3)
Extended Data Type
(Bit 1)
Extended Data Type
(Bit 2)
Extended Data Type
(Bit 2)
Description
Right bit is least significant bit (0).
000 = BYTE used as an array of Boolean
001 = WORD used as an array of Boolean
010 = BYTE (8-bit integer)
011 = WORD (16-bit integer)
100 = DWORD (32-bit integer)
101 = TCHAR (8-bit (not unicode) or 16-bits (unicode))
110 = REAL (32-bit floating point value)
111 = Use bits 16, 17, 18
0 = unsigned
1 = signed
0 = visible
1 = hidden
0 = Parameter can sink a link
1 = Parameter cannot sink a link
0 = Recallable from NVS
1 = Not Recallable from NVS
0 = No ENUM text
1 = ENUM text
0 = Read only
1 = Read/write
0 = Writable when enabled (for example, drive running)
1 = Not writable when enabled
0 = Parameter value is not a Reference to another
parameter
1 = Parameter value refers to another parameter
Must be zero
Number of digits to the right of the decimal point.
0000 = 0
1111 = 15
Right bit is least significant bit (16).
000 = Reserved
001 = DWORD used as an array of Boolean
010 = Reserved
011 = Reserved
100 = Reserved
101 = Reserved
110 = Reserved
111 = Reserved
CIP/DSI Objects
C-13
DSI Parameter Object (Continued)
Descriptor Attributes (Continued)
Bit
19
20
21
22
23
24
25
26
Name
Parameter Exists
Not Used
Formula Links
Access Level (Bit 1)
Access Level (Bit 2)
Access Level (Bit 3)
Writable ENUM
Not a Link Source
27
28
29
30
31
Enhanced Bit ENUM
Enhanced ENUM
Not Used
Not Used
Not Used
Description
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
0 = Parameter can be a source for a link
1 = Parameter cannot be a source for a link
Reserved
Reserved
Reserved
Reserved
Reserved
Formulas for Converting
Display Value = ((Internal Value + Offset) x Multiplier x Base) / (Divisor x 10 Decimal Places)
Internal Value = ((Display Value x Divisor x 10 Decimal Places) / (Multiplier x Base)) - Offset
Common Services
Service Code
0x0E
0x10
Implemented for:
Class
Instance
Yes
Yes
Yes
Yes
Service Name
Get_Attribute_Single
Set_Attribute_Single
Object Specific Services
Service Code
0x32
0x34
(1)
Service Name
Get_Attributes_Scattered (1)
Set_Attributes_Scattered (1)
The instance and attribute are ignored for these services.
The table below lists the parameters for the Get_Attributes_Scattered
and Set_Attributes_Scattered object-specific service:
Name
Scattered Parameters
Parameter Number
Parameter Value
Data Type
STRUCT of
WORD
WORD
Description
—
Parameter to read or write
Parameter value to read or write (zero when reading)
Important: The STRUCT may repeat up to 55 times in a single message.
C-14
CIP/DSI Objects
DSI Fault Object
Class Code
Hexadecimal
0x97
Decimal
151
Products such as PowerFlex drives use this object for faults. Modules use
this object for events.
Services
Service Code
0x0E
0x10
Implemented for:
Class
Instance
Yes
Yes
Yes
Yes
Service Name
Get_Attribute_Single
Set_Attribute_Single
Instances
The number of instances depends on the maximum number of faults or
events supported in the queue. The maximum number of faults/events
can be read in Instance 0, Attribute 2.
Instances (Dec.)
0…16383
16384…17407
17408…18431
18432…19455
19456…20479
20480…21503
21504…22527
Single-Drive Mode
Instances 0…16383 in drive
Instances 0…1023 in module
Instances 0…1023 in module
Instances 0…1023 in slave
Not supported
Not supported
Not supported
Multi-Drive Mode
Instances 0…16383 in Drive 0
Instances 0…1023 in module
Instances 0…1023 in Drive 1
Instances 0…1023 in Drive 2
Instances 0…1023 in Drive 3
Instances 0…1023 in Drive 4
Instances 0…1023 in module
Class Attributes
Attribute
ID
1
2
3
4
Access Name
Rule
Get
Class Revision
Get
Number of
Instances
Set
Fault Command
Write
Get
Fault Trip
Instance Read
Data Type
Description
WORD
WORD
Revision of object
Maximum number of faults/events that the
device can record in its queue
0 = No Operation
1 = Clear Fault/Event
2 = Clear Fault/Event Queue
3 = Reset Device
Fault that tripped the device. For adapters,
this value is always 1 when faulted.
BYTE
WORD
CIP/DSI Objects
C-15
DSI Fault Object (Continued)
Class Attributes (Continued)
Attribute Access Name
ID
Rule
5
Get
Fault Data List
6
Get
7
Get
Number of
Recorded Faults
Fault Parameter
Reference
Data Type
Description
STRUCT of:
BYTE
BYTE
WORD[n]
WORD
Reserved
WORD
Number of faults/events in the queue. A
“0” indicates the fault queue is empty.
Reserved
Instance Attributes
Attribute Access Name
ID
Rule
0
Get
Full/All
Information
1
Get
Basic
Information
Data Type
STRUCT of:
WORD
STRUCT of:
BYTE
BYTE
STRING[16]
STRUCT of:
LWORD
BOOL[16]
WORD
CONTAINER[n]
STRUCT of:
WORD
STRUCT of:
BYTE
BYTE
STRUCT of:
LWORD
BOOL[16]
Description
Fault code
Fault source
DSI port
DSI Device Object
Fault text
Fault time stamp
Timer value (0 = Timer not supported)
BOOL[0]: (0 = invalid data, 1 = valid data)
BOOL[1]: (0 = elapsed time, 1 = real time)
BOOL[2…15]: Not used
Reserved
Reserved
Fault code
Fault source
DSI port
DSI Device Object
Fault time stamp
Timer value (0 = Timer not supported)
BOOL[0]: (0 = invalid data, 1 = valid data)
BOOL[1]: (0 = elapsed time, 1 = real time)
BOOL[2…15]: Not used
C-16
CIP/DSI Objects
DSI Diagnostic Object
Class Code
Hexadecimal
0x99
Decimal
153
Services
Service Code
Implemented for:
Class
Instance
Yes
Yes
Yes
Yes
0x0E
0x10
Service Name
Get_Attribute_Single
Set_Attribute_Single
Instances
The number of instances depends on the maximum number of diagnostic
items in the device. The total number of diagnostic items can be read in
Instance 0, Attribute 2.
Instances (Dec.)
0…16383
16384…17407
17408…18431
18432…19455
19456…20479
20480…21503
21504…22527
Single-Drive Mode
Instances 0…16383 in drive
Instances 0…1023 in module
Instances 0…1023 in module
Instances 0…1023 in slave
Not supported
Not supported
Not supported
Multi-Drive Mode
Instances 0…16383 in Drive 0
Instances 0…1023 in module
Instances 0…1023 in Drive 1
Instances 0…1023 in Drive 2
Instances 0…1023 in Drive 3
Instances 0…1023 in Drive 4
Instances 0…1023 in module
Class Attributes
Attribute
ID
1
2
3
Access Name
Rule
Get
Class Revision
Get
Number of
Instances
Get
ENUM Offset
Data Type
Description
WORD
WORD
1
Number of diagnostic items in the
device
DSI ENUM object instance offset
WORD
CIP/DSI Objects
C-17
DSI Diagnostic Object (Continued)
Instance Attributes
Attribute Access Name
ID
Rule
0
Get
Full/All Info
1
(1)
Get/Set Value
Data Type
STRUCT of:
BOOL[32]
CONTAINER (1)
CONTAINER
CONTAINER
CONTAINER
WORD
WORD
STRING[4]
UINT
UINT
UINT
INT
DWORD
STRING[16]
Various
Description
Descriptor (see pages C-12 and C-13)
Value
Minimum value
Maximum value
Default value
Pad Word
Pad Word
Units (e.g., Amp, Hz)
Multiplier (2)
Divisor (2)
Base (2)
Offset (2)
Link (source of the value) (0 = no link)
Always zero (0)
Parameter name
Diagnostic item value
A CONTAINER is a 32-bit block of data that contains the data type used by a value. If signed, the value is
sign extended. Padding is used in the CONTAINER to ensure that it is always 32-bits.
(2) This value is used in the formulas used to convert the value between display units and internal units. Refer
to Formulas for Converting on page C-13.
C-18
Notes:
CIP/DSI Objects
Appendix D
PowerFlex 4-Class Drives Logic
Command/Status Words
Appendix D provides the definitions of the Logic Command/Logic
Status words that are used for some drives that can be connected to the
1769-SM2 module. If the Logic Command/Logic Status for the drive
that you are using is not listed, refer to your drive’s documentation.
Logic Command Word
Logic Bits
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
x
x
x
x
x
x
x
x
x
x
(1)
(2)
(3)
x
x
x
x
x
0 Command
x Stop
Start (1)
Jog
Clear Faults
Direction
Description
0 = Not Stop
1 = Stop
0 = Not Start
1 = Start
0 = Not Jog
1 = Jog
0 = Not Clear Faults
1 = Clear Faults
00 = No Command
01 = Forward Command
10 = Reverse Command
11 = No Command
(2)
(2)
Accel Rate(3) 00 = No Command
01 = Accel Rate 1 Command
10 = Accel Rate 2 Command
11 = Hold Accel Rate
Decel Rate(3) 00 = No Command
01 = Decel Rate 1 Command
10 = Decel Rate 2 Command
11 = Hold Decel Rate
000 = No Command
Reference
(3)
001 = Freq Source (Spd Ref. par.)
Select
010 = Freq Source (Int. Freq par.)
011 = Freq Source (Comm)
100 = Preset Freq 0
101 = Preset Freq 1
110 = Preset Freq 2
111 = Preset Freq 3
(2)
A “0 = Not Stop” condition (logic 0) must first be present before a “1 = Start” condition will start the drive. The Start command acts as
a momentary Start command. A “1” will start the drive, but returning to “0” will not stop the drive.
Depending on the PowerFlex 4-Class drive, the functions for bits 6, 7, and 15 change. Refer to Appendix C in the PowerFlex 4,
PowerFlex 4M, PowerFlex 40 or PowerFlex 40P drive User Manual, or Appendix E for the PowerFlex 400 drive bit functions.
The functions for these bits are the same for all PowerFlex 4-Class drives—including the PowerFlex 40P when it is used in the
“Velocity” mode. When using the PowerFlex 40P in the “Position” mode, the bit functions are different. For details, refer to Appendix C
in the PowerFlex 40P User Manual.
D-2
PowerFlex 4-Class Drives Logic Command/Status Words
Logic Status Word
Logic Bits
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
(1)
(2)
0 Status
x Ready
Description
0 = Not Ready
1 = Ready
Active
0 = Not Active
1 = Active
Command
0 = Reverse
Direction
1 = Forward
Actual Direction 0 = Reverse
1 = Forward
Accel
0 = Not Accelerating
1 = Accelerating
Decel
0 = Not Decelerating
1 = Decelerating
Alarm
0 = No Alarm
1 = Alarm
Fault
0 = No Fault
1 = Fault
At Speed
0 = Not At Reference
1 = At Reference
(1)
0 = Not Controlled By Comm
Main Freq
1 = Controlled By Comm
Operation
0 = Not Controlled By Comm
(1)
Command
1 = Controlled By Comm
0 = Not Locked
Parameters(1)
1 = Locked
Digital Input 1
Status(1)
Digital Input 2
Status(1)
Digital Input 3
Status(1) (2)
Digital Input 4
Status(2) (2)
The functions for these bits are the same for all PowerFlex 4-Class drives—including the PowerFlex 40P when it is used in the
“Velocity” mode. When using the PowerFlex 40P in the “position” mode, the bit functions are different. For details, refer to Appendix C
in the PowerFlex 40P User Manual.
This status is available for only PowerFlex 40 drives with firmware version 2.xx (or higher). For PowerFlex 4 and PowerFlex 4M
drives, these bits are not used.
Glossary
C
CIP (Common Industrial Protocol)
CIP is the transport and application layer protocol used for messaging
over EtherNet/IP, ControlNet, and DeviceNet networks. The protocol is
used for implicit messaging (real time I/O) and explicit messaging
(configuration, data collection, and diagnostics).
Class
A class is defined by the DeviceNet specification as “a set of objects that
all represent the same kind of system component. A class is a
generalization of an object. All objects in a class are identical in form
and behavior, but may contain different attribute values.”
ControlFLASH
An Allen-Bradley software tool that lets users electronically update
firmware on printed circuit boards.
Controller
A controller, also called programmable logic controller, is a solid-state
control system that has a user-programmable memory for storage of
instructions to implement specific functions such as I/O control, logic,
timing, counting, report generation, communication, arithmetic, and data
file manipulation. A controller consists of a central processor, input/
output interface, and memory. See also Scanner.
D
DeviceNet Network
An open producer/consumer Controller Area Network (CAN) which
connects devices (for example, controllers, drives, and motor starters).
Both I/O and explicit messages can be transmitted over the network. A
DeviceNet network can support a maximum of 64 devices. Each device
is assigned a unique node address and transmits data on the network at
the same data rate.
A cable is used to connect devices on the network. It contains both the
signal and power wires. Devices can be connected to the network with
drop lines, in a daisy chain connection, or a combination of the two.
General information about DeviceNet and the DeviceNet specification
are maintained by the Open DeviceNet Vendor’s Association (ODVA).
ODVA is online at http://www.odva.org.
DSI (Drive Serial Interface)
DSI is based on the Modbus RTU serial communication protocol and is
used by various Allen-Bradley drives, such as PowerFlex 4-Class drives.
Glossary-2
DSI Peripheral
A device that provides an interface between DSI and a network or user.
Peripheral devices are also referred to as “adapters” or “modules.” The
1769-SM2 module, 1203-USB or 22-SMC-232 converter, and
PowerFlex 4-Class HIMs (22-HIM-A3 or 22-HIM-C2S) are examples of
DSI peripherals.
DSI Product
A device that uses the DSI communications interface to communicate
with one or more peripheral devices. For example, a motor drive such as
a PowerFlex 4-Class drive is a DSI product. In this manual, a DSI
product is also referred to as “drive” or “host.”
DriveExplorer Software
A tool for monitoring and configuring Allen-Bradley products and
modules. It can be run on computers running various Microsoft
Windows operating systems. DriveExplorer version 2.xx (or higher) can
be used to configure this module and connected PowerFlex drives.
Information about DriveExplorer software and a free lite version can be
accessed at http://www.ab.com/drives/driveexplorer.
DriveTools SP Software
A software suite designed for running on various Microsoft Windows
operating systems. This software suite provides a family of tools,
including DriveExecutive, that you can use to program, monitor, control,
troubleshoot, and maintain Allen Bradley products. DriveTools SP can
be used with Allen-Bradley drives. Information about DriveTools SP can
be accessed at http://www.ab.com/drives/drivetools.
E
EDS (Electronic Data Sheet) Files
Simple text files that are used by network configuration tools such as
RSNetWorx for DeviceNet to describe products so that you can easily
commission them on a network. EDS files describe a product device type
and revision. EDS files for many Allen-Bradley products can be found at
http://www.ab.com/networks/eds.
Explicit Messaging
Explicit Messages are used to transfer data that does not require
continuous updates. They are typically used to configure, monitor, and
diagnose devices over the network.
F
Flash Update
The process of updating firmware in a device. The module can be flash
updated using various Allen-Bradley software tools. Refer to Flash
Updating the Module on page 3-22 for more information.
Glossary-3
H
HIM (Human Interface Module)
A device that can be used to configure and control a drive. PowerFlex
4-Class HIMs (22-HIM-A3 or 22-HIM-C2S) can be used to configure
PowerFlex 4-Class drives and their connected peripherals.
Hold Last
When communication is disrupted (for example, the controller is idle),
the module and PowerFlex drive can respond by holding last. Hold last
results in the drive receiving the last data received via the network
connection before the disruption. If the drive was running and using the
Reference from the module, it will continue to run at the same
Reference.
I
Idle Action
An idle action determines how the module and connected drive act when
the controller is switched out of run mode.
I/O Data
I/O data, sometimes called “implicit messages” or “input/output,” is
time-critical data such as a Logic Command and Reference. The terms
“input” and “output” are defined from the controller’s point of view.
Output is produced by the controller and consumed by the module. Input
is produced by the module and consumed by the controller.
L
Logic Command/Logic Status
The Logic Command is used to control the PowerFlex 4-Class drive (for
example, start, stop, direction). It consists of one 16-bit word of output to
the module from the network. The definitions of the bits in this word
depend on the drive, and are shown in Appendix D.
The Logic Status is used to monitor the PowerFlex 4-Class drive (for
example, operating state, motor direction). It consists of one 16-bit word
of input from the module to the network. The definitions of the bits in
this word depend on the drive, and are shown in Appendix D.
N
NVS (Non-Volatile Storage)
NVS is the permanent memory of a device. Devices such as the module
and drive store parameters and other information in NVS so that they are
not lost when the device loses power. NVS is sometimes called
“EEPROM.”
O
Objects
The CIP common specification defines an object as “an abstract
representation of a particular component within a product.”
Glossary-4
P
PCCC (Programmable Controller Communications Command)
PCCC is the protocol used by some controllers to communicate with
devices on a network. Some software products (for example,
DriveExplorer and DriveExecutive) also use PCCC to communicate.
PowerFlex 4-Class (Component Class) Drives
The Allen-Bradley PowerFlex 4-Class family of drives supports DSI and
includes the PowerFlex 4, PowerFlex 4M, PowerFlex 40, PowerFlex
40P, and PowerFlex 400. These drives can be used for applications
ranging from 0.2…110 kW (0.25…150 HP).
R
Reference/Feedback
The Reference is used to send a setpoint (for example, speed, frequency,
torque) to the drive. It consists of one 16-bit word of output to the
module from the network.
Feedback is used to monitor the speed of the drive. It consists of one
16-bit word of input from the module to the network.
RSLogix 500/5000
RSLogix software is a tool for configuring and monitoring controllers to
communicate with connected devices. It is a 32-bit application that runs
on various Windows operating systems. Information about RSLogix
software can be found at http://www.software.rockwell.com/rslogix.
RSNetWorx for DeviceNet
A software tool for configuring and monitoring DeviceNet networks and
connected devices. It is a 32-bit application that runs on various
Windows operating systems. Information about RSNetWorx for
DeviceNet software can be found at http://www.software.rockwell.com/
rsnetworx.
RTU Baud Rate
The baud rate is the speed at which data is transferred when the
1769-SM2 module is operating in Multi-Drive mode and the DSI I/O
Cfg parameter for a channel is set to “5” (RTU Master). The available
baud rates are:
38.4K bps
19200 bps
9600 bps
4800 bps
2400 bps
1200 bps
600 bps
300 bps
Glossary-5
S
Scanner
A scanner is a separate module (of a multi-module controller) or a
built-in component (of a single-module controller) that provides
communication with modules connected to a network. See also
Controller.
Status Indicators
Status indicators are LEDs that are used to report the status of the
module, network, and drive. They are on the front of the module.
Z
Zero Data
When communication is disrupted (for example, the controller is idle),
the module and drive can respond with zero data. Zero data results in the
drive receiving zero as values for Logic Command and Reference data. If
the drive was running and using the Reference from the module, it will
stay running but at zero Reference.
Glossary-6
Notes:
Index
A
adapter, see module
applying power to the module, 2-14
assembling module to the controller,
2-5
attentions, 1-7
B
baud rate, see RTU baud rate
bit definitions for
Logic Command word, D-1
Logic Status word, D-2
C
CH1…CH3 status indicators
locating, 1-10
troubleshooting with, 9-3
CIP (Common Industrial Protocol),
G-1
CIP/DSI objects list, C-1
class, G-1
communications cables, 1-6, 2-10
CompactLogix example ladder
program
Multi-Drive mode
1769-SM2 settings, 7-12
20-COMM-H settings, 7-12
CH3 Modbus RTU Master
subroutine example, 7-22 to
7-27
main routine/subroutines, 7-14
to 7-19
PowerFlex 40 settings, 7-11
PowerFlex 70 settings, 7-11
programs tags, 7-21
system arrangement, 7-11
Single mode
1769-SM2 settings, 7-2
main routine/subroutines, 7-4
to 7-7
PowerFlex 40 settings, 7-2
programs tags, 7-8
system arrangement, 7-2
compatible products, 1-6
components of module, 1-1
Config Mode parameter, B-1
Configuration Mode switch, 2-3
configuration tools, 3-2
configuring the module, 3-1
ControlFLASH, G-1
controller
definition, G-1
mode, 3-3
Index-2
ControlLogix w/1769-ADN example
ladder program
1769-SM2
input/output data, 8-22
registering the EDS file, 8-8
settings, 8-12
controller tags, 8-21
main routine/subroutines, 8-13 to
8-20
Multi-Drive mode, 8-13
PowerFlex 40 settings, 8-12
setting up the 1769-ADN, 8-4
Single mode, 8-1
Single mode system arrangement,
8-2
D
DeviceNet
definition, G-1
specification, G-1
dimensions of module, A-1
DriveExecutive
accessing parameters with, 3-2
supported feature, 1-2
DriveExplorer
accessing parameters with, 3-2
definition, G-2
free lite version, G-2
supported feature, 1-2
drives, see DSI compatible products
or PowerFlex drives
DriveTools SP Software, G-2
Drv 0…4 Addr 1 parameters, B-3
Drv 0…4 Addr 2 parameters, B-5
Drv 0…4 Addr 3 parameters, B-7
DSI
cable requirements, A-2
compatible products, 1-6
definition, G-1
peripheral definition, G-2
product definition, G-2
DSI Device object, C-7
DSI Diagnostic object, C-16
DSI Fault object, C-14
DSI I/O Act 1 parameter, B-3
DSI I/O Act 2 parameter, B-5
DSI I/O Act 3 parameter, B-7
DSI I/O Cfg 1 parameter, B-2
DSI I/O Cfg 2 parameter, B-4
DSI I/O Cfg 3 parameter, B-6
DSI Mode parameter, B-1
DSI Parameter object, C-10
E
EDS (Electronic Data Sheet) files
definition, G-2
web site, G-2
EEPROM, see Non-Volatile Storage
(NVS)
equipment required, 1-6
events
list of, 9-6
viewing/clearing, 9-6
Explicit Messaging
definition, G-2
supported feature, 1-2
F
faults, see events
features, 1-2
firmware release, P-3
flash update
definition, G-2
guidelines, 3-22
Flt Cfg Logic 1 parameter, B-2
Flt Cfg Logic 2 parameter, B-4
Flt Cfg Logic 3 parameter, B-6
Flt Cfg Ref 1 parameter, B-2
Flt Cfg Ref 2 parameter, B-4
Flt Cfg Ref 3 parameter, B-6
G
grounding the module, 2-12
Index-3
H
HIM (Human Interface Module)
accessing parameters with, 3-13
definition, G-3
hold last
configuring the module for, 3-15
definition, G-3
I
I/O
configuring the module for, 3-14
definition, G-3
image examples, 3-2, 4-2
image table, 3-1, 4-1
module control word, 4-2
module status word, 4-3
understanding the I/O image, 4-1
using Reference/Feedback, 4-4
Identity object, C-3
idle action
configuring the module for, 3-15
definition, G-3
Idle Action 1 parameter, B-2
Idle Action 2 parameter, B-4
Idle Action 3 parameter, B-6
installation
applying power to module, 2-14
connecting drives to module, 2-10
preparing for, 2-1
removing power from module, 2-2
L
LEDs, see status indicators
Logic Command/Status word
bit definitions, D-1, D-2
definition, G-3
M
manual
conventions, P-3
related documentation, P-1
web site, P-1
messaging, see Explicit Messaging
MicroLogix 1500 example ladder
program
Multi-Drive mode
1769-SM2 settings, 6-10
20-COMM-H settings, 6-10
CH3 Modbus RTU Master
subroutine example, 6-18 to
6-22
main routine/subroutines, 6-12
to 6-15
PowerFlex 40 settings, 6-9
PowerFlex 70 setting, 6-9
program data tables, 6-16
system arrangement, 6-9
Single mode
1769-SM2 settings, 6-2
main routine/subroutines, 6-4
to 6-6
PowerFlex 40 settings, 6-2
program data table, 6-7
system arrangement, 6-2
Index-4
module
applying power, 2-14
assembling to the controller, 2-5
compatible products, 1-6
components, 1-1
connecting drives to, 2-10
control word, 4-2
controller mode, 3-3
dimensions, A-1
features, 1-2
flash updating, 3-22
grounding, 2-12
illustration, 1-1
installing, 2-1 to 2-15
mounting, 2-6
operating status, 2-15
parameter mode, 3-12
parameters, B-1 to B-8
removing power, 2-2
replacing within a system, 2-9
resetting, 3-20
selecting configuration mode, 2-3
setting
Configuration Mode Switch
(SW1), 2-3
drive node addresses, 3-16
I/O, 3-14
Operating Mode Switch
(SW2), 2-4
RTU Modbus Master
operation, 3-17
Single/Multi-Drive mode of
operation, 1-3
specifications, A-1
status word, 4-3
tools for configuring, 3-2
troubleshooting, 9-1
viewing status, 3-21
MODULE status indicator
locating, 1-10
troubleshooting with, 9-2
mounting the module, 2-6
Multi-Drive mode versus Single
mode, 1-3
O
objects
definition, G-3
DSI list, C-1
ODVA (Open DeviceNet Vendor’s
Association), G-1
Operating Mode switch (SW2), 2-4
operating status, 2-15
P
Parameter object, C-4
parameters
accessing, 3-13
convention, P-3
list of, B-1 to B-8
numbers, B-1 to B-8
viewing module status, 3-21
PCCC (Programmable Controller
Communications
Command), G-4
power consumption, A-1
PowerFlex drives
compatible with module, 1-6
definition, G-4
Logic Command/Status word, D-1
optional, external HIM, 3-13
preparing for an installation, 2-1
processor, see controller
products, see DSI compatible
products or PowerFlex
drives
programmable logic controller, see
controller
Q
quick start guide, 1-9
R
N
Non-Volatile Storage (NVS)
definition, G-3
in module, 3-2
Reference/Feedback
definition, G-4
using, 4-4
regulatory compliance, A-1
Index-5
related documentation, P-1
removing power from the module, 2-2
replacing module within a system, 2-9
Reset Module parameter, B-2
resetting the module, 3-20
RSLinx, P-3, 8-2
RSLogix 500/5000, G-4
RSNetWorx for DeviceNet
definition, G-4
setting up RSLinx for, 8-2
using, 8-3
web site, G-4
RTU Baud Rate 1 parameter, B-3
RTU Baud Rate 2 parameter, B-5
RTU Baud Rate 3 parameter, B-7
RTU baud rate definition, G-4
RTU Format 1 parameter, B-3
RTU Format 2 parameter, B-5
RTU Format 3 parameter, B-7
RTU Master operation
setting the baud rate, 3-17
setting the RTU format, 3-17
setting the Rx Delay Time, 3-18
setting the Tx Delay Time, 3-18
RTU MsgTimeout 1 parameter, B-4
RTU MsgTimeout 2 parameter, B-6
RTU MsgTimeout 3 parameter, B-8
RTU Rx Delay 1 parameter, B-3
RTU Rx Delay 2 parameter, B-5
RTU Rx Delay 3 parameter, B-7
RTU Tx Delay 1 parameter, B-4
RTU Tx Delay 2 parameter, B-6
RTU Tx Delay 3 parameter, B-8
S
safety precautions, 1-7
scanner, G-5
setting
1769-ADN, 8-4
Configuration Mode switch (SW1),
2-3
Operating Mode switch (SW2), 2-4
Single mode versus Multi-Drive
mode, 1-3
specifications
DeviceNet, G-1
module, A-1
status indicators
CH1…CH3, 1-10, 9-3
definition, G-5
locating, 1-10
MODULE, 1-10, 9-2
normal operation, 2-15
troubleshooting with, 9-2 to 9-3
understanding, 9-1
T
technical support, P-2
tools required, 1-6
troubleshooting, 9-1
U
understanding the I/O image, 4-1
updating module, see flash update
using RSNetWorx for DeviceNet, 8-3
W
web site
DeviceNet, G-1
DriveExecutive software, G-2
DriveExplorer software, G-2
DriveTools SP software, G-2
EDS files, G-2
ODVA (Open DeviceNet Vendor’s
Association), G-1
related documentation, P-1
RSLogix 500/5000, G-4
RSNetWorx for DeviceNet, G-4
Z
zero data
configuring the module for, 3-15
definition, G-5
Index-6
U.S. Allen-Bradley Drives Technical Support
Tel: (1) 262.512.8176, Fax: (1) 262.512.2222, Email: support@drives.ra.rockwell.com, Online: www.ab.com/support/abdrives
www.rockwellautomation.com
Power, Control and Information Solutions Headquarters
Americas: Rockwell Automation, 1201 South Second Street, Milwaukee, WI 53204-2496 USA, Tel: (1) 414.382.2000, Fax: (1) 414.382.4444
Europe/Middle East/Africa: Rockwell Automation, Pegasus Park, De Kleetlaan 12a, 1831 Diegem, Belgium, Tel: (32) 2 663 0600, Fax: (32) 2 663 0640
Asia Pacific: Rockwell Automation, Level 14, Core F, Cyberport 3, 100 Cyberport Road, Hong Kong, Tel: (852) 2887 4788, Fax: (852) 2508 1846
Publication 1769-UM013C-EN-P – June, 2010
Supersedes 1769-UM013B-EN-P – January, 2006
PN-77639
Copyright © 2010 Rockwell Automation, Inc. All rights reserved. Printed in USA.
Download