PD Instruments
Portable Switchgear PD Solutions
IPEC Ltd is a specialist engineering company based in the industrial heart
of the United Kingdom, who are well renowned technological innovators
within the of electrical engineering industry. Formed in 1995, the
company has made great advancement in its field and IPEC are now
leading specialists in Online Partial Discharge (PD) detection and
location, for MV, HV and EHV cables, switchgear and accessories.
Partial discharge is generally accepted as the predominant cause of long
term degradation and eventual failure of electrical insulation. As a result,
its measurement is standard procedure in the factory testing of many
types of high voltage equipment. In addition, partial discharge activity
can be tested for or monitored on in-service equipment to warn against
pending insulation failure.
IPEC currently have a live network of over 150 Permanent PD monitoring
Systems - monitoring over 5,000 electricity assets worldwide.
IPEC’s mission is to bring innovation, expertise, and outstanding
products and services to the electricity supply industry. A goal
IPEC continually reaches for through cutting-edge Research and
Development, Knowledge Consolidation, and Listening to and
Understanding customer needs and demands
Par�al Discharge Instruments
A significant propor�on of disrup�ve failure in substa�on
assets can be prevented through PD tes�ng. Periodic
tes�ng of electrical assets means that a poten�al fault can
be detected and repaired before it becomes a risk to
engineers or the surrounding environment.
All IPEC products are designed and manufactured in
accordance with ISO 9001 standards. IPEC have a
dedicated team of highly skilled engineers, who are able to
bring innova�ve ideas from concept to final product. IPEC
only work with carefully selected partners, ensuring the
highest quality in Bri�sh product manufacturing.
PD-SGS
PD Detector
PD-SG1
TEV PD Detec�on
Par�al discharge ac�vity inside metal clad high voltage
plant induces small voltage impulses called Transient Earth
Voltages on the surface of the metal panels. TEVs travel
around the surface to the outside of the switchgear, where
they can be picked up externally using a PD detector.
Ultrasonic PD Detec�on
Defects on the surface of high voltage insulators are prone
to a phenomenon known as surface tracking. Tracking
causes carbon deposits that build up over �me, ul�mately
leading to flashover and insula�on failure. IPEC’s PD
instruments are highly sensi�ve to the ultrasonic
emissions produced by tracking and enable the on-set to
be detected before insula�on failure.
Our Range
Detec�on
Verifica�on
Loca�on
Level Mode is used to detect
presence of both TEV and
Ultrasonic ac�vity
PRPD enables the user to verify
PD ac�vity is genuine and not
from electrical noise
Dual sensor precedence mode
allows users to pin point the
source of the PD ac�vity
online, to a resolu�on of 8 cm
With the PD Detector, you can
also save PD Data
PD-SGS
PD Detector
PD-SG1
PD-SGS
PD-SGS is a dual transducer PD detector for switchgear. The instrument detects TEV
signals generated by internal discharge, as well as acous�c discharge generated by
surface tracking or corona. The device can measure TEV signals generated by
internal PD and it uses ultrasonic detec�on of surface PD ac�vity. The PD-SGS has
an integrated noise detec�on algorithm to avoid false posi�ves. Level mode and
trend mode can be heard through audible output, through headphones or built in
speaker.
What’s in the Box?
PD-SGS
Headphones
Func�on Tester
Mains Charger
USB Charger
Hard wearing PELI™ case
Handheld Switchgear PD Spot Tester
The Benefits
• Rapid survey whole substa�on - detects MV and HV
problems before they occur
• Personnel safety device - ensure the substa�on is clear of
PD before conduc�ng work
• Hear the PD - only instrument available that allows the
user to hear both ultrasonic and TEV PD ac�vity occur
• Ergonomic and compact design - fits in the user’s pocket
and is easy to use occur
• Long las�ng ba�ery - allowing a whole day of tes�ng
without requiring a recharge
Rapid Substa�on Survey
Personnel Safety
Audible PD
Ergonomic & Compact
Long Las�ng Ba�ery
Key Features
• Measurement of TEV signals generated by internal PD
• Ultrasonic detec�on of surface PD ac�vity
• Integrated Noise Detec�on Algorithm helps avoid ‘False
Posi�ves’
• Level Mode and Trend Mode
• Audible output through headphones or built in speaker
Detec�on
Verifica�on
Loca�on
Level Mode is used to detect
presence of both TEV and
Ultrasonic ac�vity
PRPD enables the user to verify
PD ac�vity is genuine and not
from electrical noise
Dual sensor precedence mode
allows users to pin point the
source of the PD ac�vity online,
to a resolu�on of 8 cm
With the PD Detector, you can
also save PD Data
PD Detector
PD Detector is a dual transducer test instrument, with data synchroniza�on, for
switchgear. The instrument detects TEV signals generated by internal par�al
discharge as well as acous�c discharge generated by surface tracking or corona. A
mobile device receives data directly from the instrument for display and
synchroniza�on with a central server. The user can log trend PD ac�vity against
par�cular assets and it can generate automa�c ‘high PD’ alerts to a management
team live from site.
What’s in the Box?
PD Detector
Android™ Mobile Phone
Headphones
Func�on Tester
Mains Charger
USB Charger
Hard wearing PELI™ case
Switchgear PD Detector with Data Synchronisa�on
The Benefits
• Rapid survey whole substa�on - detects MV and HV
problems before they occur
• Remote Data Storage - ensure all data is recorded from
each site test
• Trend - log the PD against individual assets and view data
from each test ever conducted
• Advanced Noise Rejec�on - system detects PD in higher
noise environments, no more false posi�ves
• Ac�ve Noise Separa�on - system will ac�vely show the
result of noise and PD separately on the screen
• PRPD - PRPD display allows user to dis�nguish between
PD and Noise
Rapid Substa�on Survey
Remote Data Storage
PD Trend
Ac�ve Noise Separa�on
PRPD
Key Features
• Measurement of TEV signals generated by internal PD
• Data synchronisa�on to central server
• Log and trend PD ac�vity against par�cular assets
• Automa�c data integra�on with SAP
• Automa�c high PD alerts to asset management team
live from site
• Integrated Noise Detec�on Algorithm helps avoid ‘False
Posi�ves
• Separate readings for noise and PD when detec�ng
PD Level
Noise
Level
Detec�on
Verifica�on
Loca�on
Level Mode is used to detect
presence of both TEV and
Ultrasonic ac�vity
PRPD enables the user to verify
PD ac�vity is genuine and not
from electrical noise
Dual sensor precedence mode
allows users to pin point the
source of the PD ac�vity online,
to a resolu�on of 8 cm
With the PD Detector, you can
also save PD Data
PD-SG1
PD-SG1 is a dual transducer switchgear PD detec�on instrument. The unit detect TEV signals
generated by internal discharge, as well as acous�c discharge generated by surface tracking or
corona. The system uses two channels to acquire TEV signals, enabling accurate loca�on of PD in
switchgear.
The PD-SG1 has three modes: Level Mode, used to detect presence of both TEV and ultrasonic
ac�vity; Cycle Mode, Phase Resolved Par�al Discharge Display (PRPD) enables the user to verify PD
ac�vity is genuine and not from electrical noise interference before taking further remedial ac�on;
Precedence Mode, dual sensor precedence allows users to pin-point the source of PD ac�vity.
What’s in the Box?
PD-SG1
Headphones
Sync Transmi�er
2x CC-TEV PD Sensor
1x AA Ultrasonic Sensor
1x HFCT 48 PD Sensor
Func�on Tester
Mains Charger
Hard wearing PELI™ case
Portable Switchgear PD Locator
The Benefits
• Detect MV and HV problems - before they develop into
tangible failure risks
• Personnel Safety Device - ensure the substa�on is clear of
PD before conduc�ng work
• Locate PD Source - precedence with pico second �ming
accurately locates PD within Switchgear
• PRPD - PRPD display allows user to dis�nguish between
PD and Noise
• Hear the PD - only instrument available that allows the
user to hear both ultrasonic and TEV PD ac�vity
Detect MV & HV Problems
Personnel Safety
Locate PD Source
Audible PD
PRPD
Key Features
• Integrated Noise Detec�on Algorithm helps avoid ‘False
Posi�ves’ Ultrasonic detec�on of surface PD ac�vity
• Displayed on the LCD screen as dB reading, as well as
audible signals through headphones
• Measurement of TEV signals generated by internal PD
• PRPD Mode for viewing PD pa�ern in power cycle,
allowing for the recogni�on of noise
• Precedence Mode for loca�on of PD within the assets
under test
Detec�on
Verifica�on
Loca�on
Level Mode is used to detect
presence of both TEV and
Ultrasonic ac�vity
PRPD enables the user to verify
PD ac�vity is genuine and not
from electrical noise
Dual sensor precedence mode
allows users to pin point the
source of the PD ac�vity online,
to a resolu�on of 8 cm
Technical Specifications
TEV Measurements
Sensor
Measurement Range
Resolution
Accuracy
Noise Rejection
Ultrasonic Measurements
Measurement Range
Resolution
Accuracy
Transducer Sensitivity
Transducer Centre Frequency
Hardware
Enclosure
Control
Connectors
PD-SGS
PD Detector
Capacitive
0 to 80 dBmV
1 dB
±1 dB
Yes
Capacitive
0 to 80 dBmV
1 dB
±1 dB
Yes, with PRPD
-6dBµV to + 70dBµV
1 dB
±1 dB
-65dB (0dB = 1volt/µbar RMS SPL)
40 kHz
-6dBµV to + 70dBµV
1 dB
±1 dB
-65dB (0dB = 1volt/µbar RMS SPL)
40 kHz
Injection moulded plastic case
Membrane keypad
Power, Headphones and External
Acoustic Sensor
OLED with level LEDs
Injection moulded plastic case
Membrane keypad
Power, Headphones and External
Acoustic Sensor
OLED with level LEDs
Display
Operating Environment
Operating Temperature
-20°C to 60°C
-20°C to 60°C
Humidity
60 ±25% RH non-condensing
60 ±25% RH non-condensing
IP Rating
54
54
Application
Communication
Bluetooth
Data Storage
Customer Server
Data Access
Web front end, SAP, Oracle, etc.
Capability
Android
Reporting
Yes
Results
dB, PRPD, Noise
Dimensions
Unit Size
190 x 90 x 55 mm
190 x 90 x 55 cm
Unit Weight
300 g
300 g
Kit Size
295 x 340 x 145 mm
295 x 340 x 145 cm
Kit Weight
2.8 kg
2.8 kg
Power
Internal Battery
Lithium Ion, 3.75V, 2.2Ah, 8.25Wh
Lithium Ion, 3.75V, 2.2Ah, 8.25Wh
Operating Time Approx.
12 hours
8 hours
Charging Temperature
0°C to 45°C
0°C to 45°C
Battery Charger
Rated Voltage
100 to 250 VAC, 5V, 3A
100 to 250 VAC, 5V, 3A
Frequency
47 to 63Hz
47 to 63Hz
Country Adapters
UK, EU, Australia, USA
UK, EU, Australia, USA
Charge time
2 hours
2 hours
CE-compliant in accordance with Low Voltage Directive (2014/35/EU) and EMC Directive (2014/30/EU)
PD-SG1
TEV Measurements
Sensor
Capacitive
Measurement Range
0 to 80 dBmV
Resolution
1 dB
Accuracy
±1 dB
Noise Rejection
Yes, with PRPD
Ultrasonic Measurements
Measurement Range
-6dBµV to + 70dBµV
Resolution
1 dB
Accuracy
±1 dB
Transducer Sensitivity
-65dB (0dB = 1volt/µbar RMS SPL)
Transducer Centre Frequency
40 kHz
High Frequency CT (HFCT)
Measurement Range
0 to 2,000,000pC
Transfer Function
4.8V/A
Frequency
100kHz to 13 MHz
Precedence
Time Resolution
240 pico-seconds
Distance Resolution
85mm
Power Cycle Mode
Frequency
50/60Hz
Display Modes
Live & Infinite Persistence
Linear Range
Min 0 to 20mV, Max 0 to 20V
dB Range
0 to 60dBmV
Hardware
Enclosure
Tough Aluminium case, with rubber protective side panels
Control
Membrane keypad
Connectors
Power, Headphones and External TEV and Acoustic Sensor
Display
Back-lit LCD with precedence LEDs
Operating Environment
Operating Temperature
-10°C to 60°C
Humidity
60 ±25% R.H non-condensing
IP Rating
54
Dimensions
Unit Size
210 x 90 x 65 mm
Unit Weight
1.8 kg
Kit Size
565 x 340 x 230 mm
Kit Weight
10.25 kg
Power
Internal Battery
Lithium Ion, 12V, 4Ah, 48Wh
Operating Time Approx.
8 hours
Charging Temperature
0°C to 45°C
Battery Charger
Rated Voltage
100 to 250 VAC, 12.6V, 1.65A
Frequency
50 to 60Hz
Country Adapters
UK, EU, Australia, USA
Charge time
4 hours
CE-compliant in accordance with Low Voltage Directive (2014/35/EU) and EMC Directive (2014/30/EU)