Analytical Analysis of Transformer Interaction Caused by Inrush Current P. Heretík, M. Kováč, A. Beláň, V. Volčko and M. Koníček Institute of Power and Applied Electrical Engineering Slovak University of Technology in Bratislava Bratislava, Slovakia Pavol.Heretik@stuba.sk, Matus.Kovac@stuba.sk, Anton.Belan@stuba.sk, Vladimir.Volcko@stuba.sk, Michal.Konicek@stuba.sk Abstract— This paper analyzes the phenomenon of sympathetic interaction between transformers which is very likely to occur when a transformer is energized on to a system where are other transformers already connected. This interaction significantly changes the duration and the magnitude of the transient magnetizing currents in the transformers involved and may lead to maloperation of some power protections. This article presents the formation process of sympathetic inrush current through the flux analytical expression and bias flux attenuation between two parallel operation transformers. After that, the reasons of sympathetic inrush current generation are illustrated. Presented analytical analysis is valuable for comprehensive understanding of sympathetic inrush current, estimating the reasons of generation and eliminating it. Keywords— Inrush Current, Power Transformer Saturation, Transient Phenomenon I. Protections, INTRODUCTION Magnetizing inrush current occurs during the energization of a single transformer connected to a power system network with no other transformers. However, the energization of a transformer connected to a network in the presence of other transformers, as shown in Fig. 1, which are already in operation, leads to the phenomenon of sympathetic inrush current. Although, severity of the inrush current is higher during single transformer energization, the sympathetic inrush current is special important due to its unusual characteristics. The inrush current in a transformer decays, usually, within a few cycles, but the sympathetic inrush current persists in the network for a relatively longer duration. In recent years, there are several reports of closing a transformer without load which led to the mal-operation of the adjacent transformer differential protection or generator differential protection. Many research addressed the transformer inrush transients caused by energizing transformers into a system assuming that there is no other transformers connected to the same system. In practice, however, energisation of transformers is normally conducted either in parallel or in series with other adjacent transformers that are already in operation. By recent observations [1,2,3] has been found out that such elements may significantly influence the magnitude and duration of the inrush current and therefore a comprehensive view of the switching This work was supported by the Slovak Research and Development Agency under the contract No. APVV-0280-10 Integrated Analysis of the Solar Power Plants. 978-1-4799-3807-0/14/$31.00 ©2014 IEEE transients from the perspective of a complete electricity network is necessary. Moreover, these already connected transformers may experience unexpected saturation during energization of the adjacent transformer. This sharing of the transient inrush current by already connected transformers is called sympathetic inrush [2,4,5]. The available literature includes numerous investigations on the inrush current phenomenon in power transformers and its impact on the design and operation of protection schemes [4,5,6]. Most of the approaches are based on the electrical equivalent circuit [6-8] or magnetic equivalent circuit [9–11] but they neglect certain surrounding devices in the electrical system which could have some influence on the transients. Some of them present analysis within the complete electrical system but they are not comprehensive. In this work, in order to solve the problems brought by the sympathetic inrush current, we deeply expound mathematical theory of sympathetic inrush current of two shunt wound transformer which understanding is very meaningful in an effort to avoid mal-operation of differential and generator protections. II. MEASUREMENTS OF SYMPATHETIC INRUSH IN REAL SYSTEMS Sympathetic inrush has been recently encountered in some practical systems and caused significant concerns. In [12], sympathetic interaction between transformers in a 20 kV converter test facility was reported. The configuration of the test facility is shown in Fig. 1. During converter testing, the active power is circulating between S1-T1-TO-T2-S2-S1 and only the losses are compensated from a 20 kV grid (with 160 MVA short-circuit level). The two transformers T1 and T2 need to be energised on a daily basis for carrying out tests. To reduce inrush current, a 100 Ohm short-circuit current limiting resistor was connected, which is large enough to limit the inrush current magnitude to values below 150 A and to damp out inrush current in less than 50 ms. However, subsequent to the inclusion of resistance sustaining sympathetic inrush currents were encountered. As shown in Fig. 2, T1 was energised at 52.2 s and then T2 was energised at 52.26 s; although inrush current caused by energising T1 was damped out in one cycle, long-duration sympathetic inrush currents were induced after energising T2. The damping resistor, which helped reduce inrush current in the case of energising T1, caused voltage asymmetry which resulted in sympathetic inrush when T2 was energised. Fig. 3. Simplified electrical system circuit diagram [13] Fig. 1. Diagram of 20 kV supply system of Converter Test Facility [12] Fig. 4. Measured voltage dips at 23 kV busbar according to Fig. 3 [13] III. Fig. 2. Inrush currents measured in the supply line during energization of T1 and T2 after inclusion of 100Ω resistor according to Fig. 1 [12] Voltage dips caused by sympathetic inrush between 100 MVA 220/23 kV transformers were reported in [13]. The configuration of the electrical system subjected to sympathetic inrush is shown in Fig. 3. The substation is fed by two 220 kV overhead lines with length of 178 km; it originally consisted of two 100 MVA, 220/23 kV transformers (T1 and T2) connected in parallel to supply power to mining facilities. A new transformer T3 was added to meet increasing demands. When energising T3, sympathetic inrush was induced in the two already connected transformers T1 and T2. The energisation also resulted in high distortion of voltages and caused tripping of those equipment connected to 23 kV busbar due to undervoltage protection relay. Field measurement of RMS voltage dip waveforms are shown in Fig. 4. It can be seen that in both cases, the maximum voltage dip magnitudes were no more than 8%, however, the duration to achieve a recovery were over 10 seconds. It shows that, despite of small voltage dip magnitude, voltage dips accompanied by sympathetic inrush lasts much longer and may still trip off sensitive equipment. PROCESS OF SYMPATHETIC INRUSH BETWEEN PARALLEL TRANSFORMERS To deeply illustrate the process of mutual interaction between transformers "Sympathetic Inrush" is used an example of parallel transformers according to Fig. 5. In this case T1 and T2 are two identical 500/230 kV, 150 MVA single-phase transformers. Fig. 5. Equivalent circuit used to analyze sympathetic inrush of transformers in parallel connection The simulated currents i1, i2 and is are displayed in following Fig. 6. As it can be seen, the inrush current i2 reached maximum peak right after the energisation of T2 and then decayed gradually, while the sympathetic inrush current i1 built up in T1 gradually reached its maximum peak and then gradually decayed; the supply current is is the sum of the currents i1 and i2, the peaks of sympathetic inrush current i1 and of the inrush current i2 occur in direction opposite to each other, on alternate half cycles. The reason of saturation transformer T1, despite the longterm operation and so generation of sympathetic inrush in electrical circuit according to Fig. 5 is that sudden connection of transformer T2 without load will produce excitation current which passes the system resistance. Subsequently, the system current causes asymmetrical fluctuation of the busbar voltage (Fig. 7), resulting in saturations and generating sympathetic inrush current in adjacent transformer T1. The system impedance is given by parameters Rs = 6.55Ω, Ls = 0.36H. The two transformers are exactly the same, having same parameters: the primary, the secondary and tertiary winding resistance are 0.002(pu), the leakage inductance are 0.08(pu), the excitation resistance are 500(pu), the basic magnetization curve using two broken line linearization processing, two broken line determined by the three points (0,0; 0.0024,1.2; 1.0,1.52). IV. ANALYTICAL ANALYSIS OF SYMPATHETIC INRUSH CURRENT For the comprehensive analysis of the various influencing factors of sympathetic inrush current, it is necessary to understand the generation mechanism of it. This section will present the formation process of sympathetic inrush current through the flux analytical expression and bias flux attenuation between two parallel operation transformers. Operating one transformer, and closing the other without loads, generally, has two connection modes: parallel or series. In this work we will focus on parallel connection which is shown in Fig. 5 whereas in an article [14] is derived that the size of inrush currents during switching series transformers are generally smaller than in the case of parallel. In the scheme in Fig. 5 Us(t) is the system source voltage; RS & Ls are respective resistance and inductance of electrical system, R11σ & L11σ, R12σ & L12σ, R1m & L1m, are respective resistance and leakage inductance of transformer T1’s primary and secondary winding and also the excitation resistance and excitation inductance; R21σ & L21σ, R22σ & L22σ, R2m & L2m, are respective resistance and inductance of transformer T2 similarly to the transformer T1. We will next consider i1(t) and i2(t) are respective inrush current of operation T1 and the closing transformer T2 and because of the fact that these transformers are operated at no load we can write R1 = R11σ + R1m, L1 = L11σ + L1m, R2 = R21σ + R2m, L2 = L21σ + L2m. The system voltage source is us(t) = Um sin(ωt+α) and α is represented the close angle. Fig. 6. Inrush current (i2), sympathetic inrush current (i1) and system current (iS) during energization parallel transformer T2 according to Fig. 5 In [14, 15] and [16], the interactions between parallel transformers were simply analyzed using the voltage drop across circuit resistances, with system and transformer winding inductances neglected. Before closing S, only the magnetizing current of the unloaded transformer T1 flows through the system; application of kirchhoff's law we could write: us (t ) = ( Rs + R1 ) i1 + dψ 1 dt (1) The integration of us over one cycle gives: t + Δt ∫ us (t )dt = t Fig. 7. Voltage drop across the system impedance according to Fig. 5 Note: In the simulation, we considered the voltage source whose rated voltage Us is 500kV and rated frequency is 60Hz. t +Δt ∫ ⎡⎣( R s + R1 ) i1 ⎤⎦ dt + Δψ 1 (2) t Where ∆t is of one cycle interval and ∆ψ1 represents the flux change per cycle in transformer T1. Considering the system source us(t) is symmetric periodical function, so: t +T ∫U t m sin (ωt + α ) dt = 0 (3) We could write the following relation for the flux change per cycle in transformer T1: Δψ 1 = − t +Δt ∫ ⎡⎣( R s + R1 ) i1 ⎤⎦ dt (4) t According to previous equation if current of transformer i1 is symmetrical and transformer T2 is not connected, ∆ψ1 will be zero. This situation corresponds to the state before switching transformer T2. After closing S, saturation of transformer T2 causes a transient inrush current i2 which flows through Rs. Due to the unidirectional characteristic of the inrush current, each cycle transformer T1 experiences an offset flux by an amount of: Δψ 1 = − t +Δt ∫ ⎡⎣( R s + R1 ) i1 + Rs i2 ⎤⎦ dt (5) be significantly prolonged in power systems with large transformers energised, as the winding resistances of these transformers are normally of relatively small value. Note: The fluxes ψ1, ψ2 attenuate respectively by the value of (10)(11) periodically and the damping role of the system resistance disappears, and it is attenuating, in accordance with the basic time constant τ1 and τ2 which results in longer attenuation. ∫ ⎡⎣( Rs + R2 ) i2 + Rs i1 ⎤⎦ dt t As the transformer T1 becomes more and more saturated, a sympathetic inrush current i1 gradually increases from the steady state magnetizing current to a considerable magnitude. Noted that as the transformer T1 saturates with the polarity opposite to that of transformer T2, the peaks of the sympathetic inrush current i1 are with polarity opposite to that of inrush current i2, on alternate half cycles. As a result, the voltage asymmetry on transformer terminals caused by the inrush current i2 during one half cycle is reduced by the voltage drop produced by the sympathetic inrush current i1 during the subsequent half cycle. This decreases both ∆ψ1 and ∆ψ2, and therefore reduces the changing rate of the magnitude of both the increasing sympathetic inrush current i1 and the decaying inrush current i2. After a certain time, the increase of i1 and decay of i2 can reach a point that: ( Rs + R1 ) i1 = − Rs i2 (10) Where ψ1 and ψ2 are respective fluxes of transformers T1 and T2. Obviously, the relation (10) is a nonlinear equation. In order to analyse the flux relation of the two transformers, we should get analytical formula because we need to do linear process with relation (10). Here, the non-linear excitation inductance L1m and L2m are replaced by the average inductance of the transformer magnetizing circuit and we will further consider the same transformers: L1 =L2 =L, R1m =R2m = R. Then using Laplace transform and Laplace inverse transform, we can get two transformers flux expression: ψ 1 (t ) = L 1 U m sin (ω t + α − ϕ ) − [ψ 1 ( 0 ) − Z 2 −ψ 2 ( 0 )]e ψ 2 (t ) = − R + 2 Rs t L + 2 Ls R − t 1 + ⎡⎣ψ 1 ( 0 ) −ψ 2 ( 0 ) ⎤⎦ e L 2 L 1 U m sin (ωt + α − ϕ ) − [ψ 1 ( 0 ) − Z 2 −ψ 2 ( 0 )]e − R + 2 Rs t L + 2 Ls R − t 1 − ⎡⎣ψ 1 ( 0 ) −ψ 2 ( 0 ) ⎤⎦ e L 2 (11) (12) Where: (7) At this point, the flux change per cycle ∆ψ1 is zero and hence current i1 stops increasing. Thereafter, the polarity of ∆ψ1 reverses and starts to reduce the offset flux in the transformer T1, as a result, the sympathetic inrush current i1 begins to decay (so does the inrush current i2). Since both decaying currents have the same amplitude but with polarities opposite to each other, no voltage asymmetry is produced on the transformer terminals and the flux change per cycle in each transformer only depends on the winding resistance of each transformer. This is one of the reasons for the inrush current to (9) dis dψ + R1i1 + 1 = U m sin (ω t + α ) dt dt dψ dψ 2 R1i1 + 1 = R2 i2 + dt dt is = i1 + i2 (6) At the initial stage, both ∆ψ1 and ∆ψ2 are of the same polarity and mainly depend on the voltage drop caused by the inrush current i2. The accumulation of ∆ψ1 drives transformer T1 into saturation, while the effect of ∆ψ2 is to reduce the initial offset flux in transformer T2 so as to produce the decay of inrush current i2. τ 2 = L2 R2 Rs is + Ls Meanwhile, an offset flux per cycle ∆ψ2 is produced in transformer T2 by: t +Δt (8) In order to express exact current waveforms of transformers during sympathetic interaction we need to solve the complete system of differential equations which define electrical grid in Fig. 5. The application of the circuit principle we can write: t Δψ 2 = − τ 1 = L1 R1 Z= ( R + 2 Rs ) + ( L + 2 Ls ) ϕ = arctan 2 ω ( L + 2 Ls ) R + 2 Rs 2 (13) (14) And ψ1(0) and ψ2(0) are the respective initial fluxes of transformers T1 and T2. From equations (11) and (12), it can be seen that both ψ1 and ψ2 consist of one sinusoidal component and two exponential DC components. The AC component and the first DC component are the same, but the second DC component in ψ1 is opposite to that in ψ2, therefore i1 and i2 are opposite to each other and appear alternately. Also, because the both DC components in ψ2 are negative, so the maximum peak of i2 would appear right after the energisation of T2, whilst the DC components in ψ1 are of opposite polarity and the time constant of the first DC component τ1 = (L+2Ls)/(R+2Rs) is smaller than that of the second DC component τ2 = L/R, so i1 will gradually reach the maximum peak, and gradually decay afterwards as we could see in Fig. 6 and Fig. 8. The simplified analytical analysis shows in a general way the variation of flux-linkages in T1 and T2 which depends on the time constants formed by the inductances and resistances of the circuit branches. In real situation, the core inductance is nonlinear and therefore the time constants cannot be so readily determined. is ( t ) = 2 1 U m sin (ω t + α − ϕ ) − [ψ 1 ( 0 ) Z L −ψ 2 ( 0 )]e − R + 2 Rs t L + 2 Ls (17) Now is apparent that, one of two transient component from (11,12) with time constant τ2 = L/R is circulating around the loop formed by the two transformer windings in series without flowing in the transmission line during the sympathetic phenomenon (Fig. 9), whilst the second one with time constant τ1 = (L+2Ls)/(R+2Rs) is created by system voltage source. Fig. 9. Transient magnetic component of magnetic flux which represents circulating current It is interesting to note that the circulating current, both with respect to magnitude and rate of decay, is entirely independent of the characteristics of the transmission line circuit, being determined solely by the inductance and resistance of the transformers themselves in conjunction with the initial bus voltage, the frequency, and the switching angle and it causes relatively longer duration of transient phenomenon of energization a parallel transformer in comparison to energization of a single transformer. V. Fig. 8. Waveforms of magnetic fluxes of transformers T1 and T2 For aperiodic components of magnetic fluxes ψ1 and ψ2 from equations (11) (12) in the previous Fig. 8, we could apply: 1 ψ a ( t ) = ⎣⎡ψ 1 ( 0 ) + ψ 2 ( 0 )⎦⎤ e 2 − R + 2 Rs t L + 2 Ls R − t 1 ψ b ( t ) = ⎣⎡ψ 1 ( 0 ) + ψ 2 ( 0 ) ⎦⎤ e L 2 (15) Summing the individual magnetic fluxes (ψ1, ψ2) we get relation for total magnetic flux: ψ (t ) = 2L U m sin (ω t + α − ϕ ) − [ψ 1 ( 0 ) Z −ψ 2 ( 0 )]e − R + 2 Rs t L + 2 Ls In this paper, we have presented a detailed formulation for the analysis of sympathetic inrush phenomenon for the configuration of parallel transformers. When the sympathetic interaction between transformers happens, the operating transformer coud be saturated and generate the sympathetic inrush, which could influence transformer protections and therefore the exact understanding of this phenomenon is very important. The analytical analysis helped us to explain its behaviour and confirmed some real cases of sympathetic interactions which are also shown. Furthermore, a practical example of the phenomenon was presented. The system was created and simulated in Matlab/Simulink which enabled us to present instantaneous current waveforms in detail. (16) Considering linear characteristic of transformers T1 and T2 (i1 = ψ1/L1, i2 = ψ2/L2) we could write equation represented line current (is) based on relation (16): CONCLUSION REFERENCES [1] [2] S. V. Kulkarni, “Influence of system operating conditions on magnetizing inrush phenomenon of transformer,” International Conference on transformers, TRAFOTECH-94, Bangalore, India, pp. VI 19–23, January 1994. R. Yacamini and A. A. Nasser, “Calculation of inrush current in singlephase transformers,” IEE Proceedings - Electric Power Applications, vol. 128, no. 6, pp. 327– 334, November 1981. [3] [4] [5] [6] [7] [8] [9] R. Yacamini and A. Abu-Nasser, “Numerical calculation of inrush current in single-phase transformers,” IEE Proceedings - Electric Power Applications, vol. 128, no. 6, pp. 327–334, 1981. J. Peng, “Assessment of Transformer Energisation Transients and Their Impacts on Power Systems”, Phd. Thesis, Manchester 2013. C. Paul, Y. Ling, and A. Basak, “Investigation of magnetizing inrush current in a single-phase transformer,” IEEE Transactions on Magnetics, vol. 24, no. 6, pp. 3217– 3222, November 1988. C. E. Lin, C. L. Cheng, C. L. Huang, and J. C. Yeh, “Investigation of magnetizing inrush current in transformers, Part I - numerical simulation,” IEEE Transactions on Power Delivery, vol. 8, no. 1, pp. 246–254, January 1993. G. Baoming, A. T. de Almeida, Z. Qionglin, and W. Xiangheng, “An equivalent instantaneous inductance-based technique for discrimination between inrush current and internal faults in power transformers,” IEEE Transactions on Power Delivery, vol. 20, no. 4, pp. 2473–2482, October 2005. A. A. Adly, H. H. Hanafy, and S. E. Abu-Shady, “Utilizing preisach models of hysteresis in the computation of three-phase transformer inrush currents,” Electric Power Systems Research, vol. 65, pp. 233– 238, 2003. R. Yacamini and H. S. Bronzeado, “Transformer inrush calculation using a coupled electromagnetic model,” IEE Procedings - Science, Measurement and Technology, vol. 141, no. 6, pp. 491–498, November 1994. [10] M. Elleuch and M. Poloujadoff, “A contribution to the modeling of three phase transformers using reluctances,” IEEE Transactions on Magnetics, vol. 32, no. 2, pp. 335– 343, March 1996. [11] K. S. Smith, L. Ran, and B. Leyman, “Analysis of transformer inrush transients in offshore electrical systems,” IEE Proceedings - Generation, Transmission and Distribution, vol. 146, pp. 89–95, January 1999. [12] S. Schramm, C. Sihler, and S. Rosado, "Limiting sympathetic interaction between transformers caused by inrush transients," in International Conference on Power Systems Transients (IPST), Delft, the Netherlands, 2011. [13] J. Pontt, J. Rodriguez, J. S. Martin, and R. Aguilera, "Mitigation of sympathetic interaction between power transformers fed by long over head lines caused by inrush transient currents," in IEEE Industry Applications Conference, pp. 1360-1363, New Orleans, USA, 2007. [14] Bi Daqiang, Wang Xiangheng, Li Dejia, et al. Theory Analysis of the Sympathetic Inrush in Operating Transformers. Automation of Electric Power Systems, 2005,29(6):1-8. [15] H. S. Bronzeado, P. B. Brogan, and R. Yacamini, "Harmonic analysis of transient currents during sympathetic interaction," IEEE Transactions on Power Systems, vol. 11, no. 4, pp. 2051-2056, 1996. [16] H. Bronzeado and R. Yacamini, "Phenomenon of sympathetic interaction between transformers caused by inrush transients," IEE Proceedings - Science, Measurement and Technology, vol. 142, no. 4, pp. 323-329, 1995.