A project Report on Grid connected Photo-voltaic active power filter By Mote Mahesh (19891D5403) Under guidance of G. Srikanth Assistant professor Dr. D. Suresh Assistant professor Department of Electrical and Electronics Engineering Vignan institute of technology and science, Deshmukhi CONTENTS CHAPTER 1: CHAPTER 2: CHAPTER 3: Chapter 4: REFERENCES CHAPTER I INTRODUCTION 1. Introduction Normally the sources of harmonics are divided into four categories. [1-3] [4] as shown in the table I. Table I. Source of harmonics Power electronics converters Arcing equipment Saturable devices Adjustable speed drives Arc furnaces Transformers Uninterruptable power supplies Induction motors switch mode power supplies furnaces welders Generators etc. static converters thyristor Lighting etc. converter systems, diode bridges induction furnaces based power electronics etc. Control devices static VAR compensators, power factor correction capacitors The increased use of power semiconductor devices in wide variety of loads has given birth to numerous power quality problems in the electric power networks. These power quality problems (pq) such as voltage regulation, power factor deviation, harmonics and current unbalance etc. Threats posed by these power quality problems are being mitigated by installing filters in shunt with nonlinear loads [3]. Earlier, passive filters were in use, but owing to drawbacks pretense by them viz. large size, resonance and fixed compensation [9], the focus of power engineers has shifted towards APFS. APFS are capable enough to provide the solution related to harmonic compensation, reactive power compensation, balancing three-phase line currents, damping of oscillation in currents and voltage regulation. Since, shunt APFS are connected in parallel with the load, and thus, they do not burden the source on account of displacement power factor and loading. The accuracy and fast response of active power filter controller depend upon the proper estimation of reference current, both in quality and configuration. Various control algorithms are reported in literature [3, 4, 5-13]. Many of them were time relevant. Most of the algorithms reported in literature need two axis transformations, and hence, augment the complexities in their implementation. Some direct and indirect controls of APF are also reported in the literature [3, 5]. However, the rising uncertainties in ac electrical system and increasing dynamics and nonlinearity of loads have attracted more attention of engineers/researchers to evolve improved methods. This leads to evolution of universal control technique of compensation having substantially improved transient performance balanced/under unbalanced load conditions. In addition to above, in most of the industrial environment the distortion in utility voltage is escalating at a very fast rate. It is experienced that the performance of active power filter has deteriorated under distorted supply voltage conditions [1]. Under distorted supply voltage, the harmonics are generated in the load current despite the linear load. Among these the sum of all frequency components of utility harmonic current is defined as total conforming current, which have similar shape as that of the voltage due to same relative level of harmonics. It is the current that the customer should be allowed to draw from a non-sinusoidal supply voltage network. On the other hand, the sum of frequency components of customer generated harmonic current is the harmonic current, which is generated by the customer and should be compensated by active power filter [12]. As a consequence, firstly, there is a need to develop a method which attributes the responsibilities of the customer and utility at the point of common coupling. Secondly, there is a need to develop controller for active power filter that works properly and compensates generated harmonics from the nonlinear load. 1.1. Active power filter The active power filter is prime device, which will maintain the grid voltage and current in sinusoidal by supplying reactive power or drawing reactive power. The power electronics based converter used for transmission voltage termed as static compensator. Now days active power filter application has been extended to the distribution level and converter used at distribution voltage level termed as distributed static compensator. 1.1.1. Basic Compensation Principle of active power filter Active power filter consists of three parts 1. Measuring devices 2. Power inverter circuit 3. Active power filter controller The inverter circuit used to draw the compensating current from power supply. The compensating current is drawn from power supply in phase opposition with the load current. Therefore, inverter is responsible for compensating current. The active power filter controller is used for control scheme implementation and generation of gate pulses for switching devices of the inverter. These switching pulses continuously supplied to the gate driver of switching devices. The active power filter power circuit diagram is shown in Fig.9. A voltage source inverter with necessary passive components is used as an active power filter and is connected in parallel at the point-of-common coupling (PCC). VSa iSa iLa Lac VSb iSb iLb Lac VSc iSc iLc Lac Threephase, Three-wire Non-linear Load iCa iCb iCc Lc Cdc Figure 1. Topology Of active power filter The compensation characteristics of active power filter are shown in the Fig. 10. The current IL represents the load current, waveform IC represents the compensation current injected by the active power filter, waveforms VS represents the voltage waveform and IS represent the source current. The active power filter control scheme is implemented on the processor to generate the firing pulses and passed to the switching device. Fig. 2.Basic compensation principle of APF. The firing pulses are passed to active power filter to draw the compensating current IC from the ac power supply. The active power filter is inject the compensating current to cancels the reactive and harmonic current contained in the load current IL. After compensation with active power filter the source current (IS) is sinusoidal and in synchronous with its respective source voltage waveform (VS). 1.1.2. Solution methodologies Many harmonic mitigation devices, like passive filter, active filter and distribution static compensator, have been designed and installed in power networks to improve the quality of power. For appropriate design and optimal placement of these harmonic mitigation devices, analysis of harmonic is essential. Harmonics analysis is basically the process of calculating the magnitude and phases of the fundamental and higher order harmonics of a given periodic wave. The resulting series, known as Fourier series, establishes a relation between the time domain and frequency domain of a given function. The complete power system harmonic study can be described by the different techniques for harmonic analysis, identification of harmonic sources, monitoring of harmonics and their mitigation methods. From the literature review, it is apparent that a lot of work has been carried out in the area of harmonic power flow studies. Different algorithms for carrying out harmonic analysis have been proposed in the literature, with some of them even being commercialized. Due to continuous advancement in technology and invention of newer power electronic devices for a more efficient operation, nature of harmonics generated by the loads is also changing. In this changing behavioral environment of loads, it is necessary to update the power system planners and operators with recent harmonic trends, nature and patterns. Thus, there is still a need for regular harmonic measurements and analysis, so that one can identify the causes and effects, and take appropriate remedial action accordingly. In this work, instantaneous reactive power theory has been used for the active power filter to estimate reference current. The active power filter with IRPT method eliminates harmonics of nonlinear load. Chapter II Grid connected neutral point clamped inverter based Photo-voltaic active power filter Abstract: In this paper, the diode bridge rectifier based the grid integrated active neutral point clamped converter based APF presented for elimination of harmonics caused by the nonlinear load and injection of active power harvested from photo-voltaic arrays. It is well-known multilevel converters can possess great advantages such as low switching losses and reduced size of filter requirement. The instantaneous reactive power theory based reference current estimation is presented with maximum power point (MPPT) tracking. The MPPT algorithm based on perturb and observe is integrated with instantaneous reactive power theory. The simulated response of the NPC based APF is show effective for injecting active power from photo voltaic system. 2.1. INTRODUCTION The increased use of power semiconductor devices in wide variety of loads has given birth to numerous power quality problems in the electric power networks. These power quality problems, their causes and effects on the power system components are explicated in this chapter. Threats posed by these power quality problems are being mitigated by installing APF in shunt with nonlinear loads. Earlier, passive filters were in use, but owing to drawbacks pretense by them viz. large size, resonance and fixed compensation, the focus of power quality engineers has shifted towards APF. APFs are capable enough to provide the solution related to harmonic compensation, reactive power compensation, balancing three-phase line currents, damping of oscillation in currents and voltage regulation. Since, APFs are connected in parallel with the load and thus, they do not burden the source on account of displacement power factor and extra loading effect. The most of the APFs are based on shunt coupled active power filter, which is used for compensation of harmonics and volatile power of the nonlinear load. The family of APFs referred with single name that is custom power devices. The custom power devices are APF, dynamic voltage restorer and compensator of integrated power quality etc. The APF is multifunctional device which provide the harmonics elimination, reactive power compensation, voltage regulation, power factor correction, load balancing and termination of the line. The execution of the APF to a great extent relies upon the ongoing estimation of the remuneration current. The most usually utilized strategies in literature are instantaneous and synchronous theory-based detection of the compensation current. Because of its ease of calculation of harmonics currents and self-learning ability, adaptive control scheme gain attention in the estimation of reference currents [13]. In this chapter, IRPT algorithm is arrived for harmonics current estimation. Now a day, the grid integration of renewable energy based generation is increasing with improved power quality feature such as harmonics elimination, reactive power compensation and load balancing. In recent studies the two and three level inverters are compared based on semiconductor losses and filter consideration and evaluated that three level inverter possess lower semiconductor losses for higher switching frequencies than the two level counterparts because three level inverters have only one device commutate at each transition. In addition to that, ac output waveform of a multilevel inverter possess a lower harmonic and reduced sizes of the ac filter components are possible[1]-[4]. 2. 2. Diode bridge rectifier based battery charger 2.3. CONFIGURATION OF APF TOPOLOGY The APF configuration based on diode clamped multilevel inverter is shown in the Fig. 3.1. The DCMLI seems to be most suitable inverter topology for photo-voltaic application without separate inverter. The DCMLI inverter has common dc bus for easy integration of photovoltaic cell. The overall power circuit of APF consist of PV array on dc side, DCMLI inverter, interfacing inductor and dc link capacitor. The interfacing inductor used to suppress the switching high frequency harmonics. The APF connected at point of common coupling through interfacing inductor. Fig. 2. 1. Topology of PV cell integrated APF. 2.3. : Instantaneous reactive power theory IRPT theory (p-q or IRP theory) depends on the set of instant power defined in the time domain [2]. The IRPT can be used for four wire system with modification. Given system terminal voltages vSa d vm dcost 2 v v cos t Sbd md 3 4 v v cos t Scd md 3 (1) The IRPT theory starts with three phase voltages and currents transforming into the αβ0 stationary reference frame. Clark Transformation In the immediate voltages in three-phase instant voltages αβ0-axes vα, vβ and v0, in vSa, vSb, and vSc, 1 2 v0d v 2 1 dd 3 v 0 1 2 1 v vSad vSbd 2 Sc 3 d 2 1 2 1 2 3 2 (2) Similarly, instant three-phase currents in the abc-phases, ica, icb, and icc are converted into the instant two phase currents on the αβ0-axesiα, iβ, and i0 as, i 0 i i d d d 1 2 2 1 3 0 1 2 1 2 3 2 1 i 2 ca 1 icb 2 i 3 cc 2 d d (3) d Since the 3P3W systems do not have a zero-sequence part, the v0and i0 can is eliminated in the equations and leads to the v0 of equation from the equation v d v d 1 1 2 2 3 0 3 2 1 v 2 Sad v 3 Sbd v Sc 2 d (4) Similarly, the zero sequence components i0 also eliminated from the current quantities. 1 i 1 2 2 3 i 3 0 d 2 d 1 i 2 cad icb 3 i d 2 ccd (5) The instantaneous real power (p) and the instantaneous reactive power (q) are defined from instantaneous phase voltages and load currents on the αβ0 axes as, pd vd id v di d (6) qd v d i d v di d (7) pd v qd v d d (8) v i vd id d d Instant active and reactive forces P and Q can be classified as an average (DC) and a oscillating (AC) quantities. pd pd pd q q q d d d (9) The oscillation component of active power is eliminated with DSTATCOM. The oscillation part of active power computed with low pass filter pd pd pd . In addition, DSTATCOM replaces the reactive power q q q . It is computed from transformed signals. The DSTATCOM compensation current estimated with IRPT scheme in are computed αβ0-reference frames as follows i* v 1 C d 2 * v2 v v d i C d d d d v p d (q dq ) v d d d (10) Due to negative signals in non-compensating powers, the compensation for producing the exact opposite of the D-STATCOM or the undesirable powers drawn by reactive load is drawn. Let the compulsory power (ploss) necessary to perform the dc bus voltage to its reference value. As a result, the equation becomes i* d vd 1 , iC* 2 2 v v v d d d C d vd pC pLoss d d v q Cd d These quantities computed in o frame are transformed back to ABC quantities using inverse Clarke’s transformation as, (11) 1 * iCa 1 i* 2 Cb 3 2 i* Cc 1 2 0 i* 3 iC * 2 C 3 (12) 2 The reference current computed with IRPT scheme is depicted in Fig.2.2. Fig.2.1. Instantaneous reactive power theory. 2.4. Dynamics model of APF The diode based dynamic model of photo-voltaic cell is shown in Fig.3.4. To obtain the required level of power from photo voltaic cells, which are connected in series and parallel to form modules and the modules are connected array to obtain higher voltage and current level. Fig.2.2. Equivalent circuit of photovoltaic cell The PV modules can be represented as approximate constant current source. The equation, which is used to describing the I-V characteristic of a practical PV cell is I I I I I I e qVoc Vout RS I 1 L D Rsh CkT L d sh (1) Where I D the saturation is current, q is the electron charge 1.6 1019 C , C is the diode emission factor, k is the Boltzmann constant 1.381023 J/K and T is the temperature. The power produced will be maximum at the knee point of the I-V characteristics of the PV module and it is depicted in Fig.3. Voltage and current properties are consistent with the kneepoint of I-V. The maximum power can be obtained from PV modules with Maximum power point tracking (MPPT) algorithm. The maximum point algorithm is attached with the APF control scheme. The APF voltage is maintained with the MPPT algorithm at the correct value. In this project, the incremental conductance method is used for tracking the maximum power from PV modules [6]. This MPPT mechanism is the power line of the PV MPP point (where dv/dt=0), on the left is positively, the opposite is negative. In the following equations, dv/di are a sample delay values V (2) (3) (4) I (0, ISC) CURRENT SOURCE VOLTAGE SOURCE (VSC, 0) V Fig.1. V-I characteristics of PV cell. The DC voltage regulator with MPPT algorithm used for estimation of reference voltage is shown in Fig.3. The reference DC voltage is estimated with incremental conductance method and power generated from PV system also estimated for injecting active power from APF to grid. The active power injected is carry negative sign, which shows that the APF inject active power into the DG set feeding system. 3.4. DC link voltage regulation 3.5. Simulation results and discussion The complete system of APF consists of the power source, DCMLI APF and nonlinear load. Fig.2. Simulated waveform of APF. Fig.3. Simulated waveform with MPPT. When APF alone operating without photo voltaic modules connected on its dc side and it is used for elimination of harmonics caused by the nonlinear load. Before t=0.05 sec., the source current is consist of integer multiple triplen harmonics current. When APF is connected at t=0.05 sec. source current tend to sinusoidal and in synchronous with voltage waveform. The source current total harmonics distortion before compensation is 23.62% and its value after compensation is found to be 2.04%. Fig.4. Simulated waveform with power variation. The simulated response of the DCMLI based APF is shown in Fig.4. Before compensation with APF source current highly nonlinear and contains harmonics which is result in heating of armature of the synchronous generator. When PV-APF start injecting active power harvested from PV module, the source current tends to sinusoidal. The source current is in phase opposition to source voltage, which shows the active power flow from PV-APF to the load. As load demand increases on grid, PV-APF compensate the load current demand. This is in turn results in reduction of fuel consumption. And also, APF compensate harmonics and balance the current while feeding variety of the load. The power variation with solar insolation is shown in the Fig.6. The different waveform of spectrum identified as PV array voltage, PV array current and active power output of the PV array. With increase in solar insolation, the quantity of output active power also increases. The increase in power output from PV array the quantity of active power injected at point of common coupling also increases. This increase in active power can be observed from the Fig.5, the value of source current gradually increase with increase in compensating current of APF. The active power injected from PV-APF relieves the loading on the DG set and also compensate the harmonics and reactive power demand of the nonlinear load connected with DG set. Fig.5. Source current THD without APF Fig.6. Source current with APF compensation. 3.4. CONCLUSION In this project, DCML Inverter is connected to PV APF and is connected to the elimination of harmonics and reactive power compensation and active power injections. Instant reactive power theory is connected with the MPPT controller. The algorithm is implemented based on the incremental conductance method to obtain the maximum power from the PV array. The active power control calculated from the PV range is used to introduce active power during joint coups in combination. DCML Investor-based APF's simplest response shows the potential compensation of active power injection from harmonics, reactive power and PV array. Chapter III Active neutral point clamped inverter based grid connected active power filter In this chapter, diode rectifier based battery charger with active neutral point clamped inverter (ANPCLI) based active power filter (APF) is presented. The active power filter with instantaneous reactive power theory simultaneously eliminate harmonic current caused by load and feed the active power to the source from photo-voltaic modules. The ANPC based active offer various advantages such as equal distribution switching losses and reduced passive filter size than that of neutral point clamped converter. The APF reference current tracked with IRPT method. The IRPT method is combined with maximum power tracking algorithm to optimize the active power fed to the grid. The incremental conductance based scheme is used as maximum power point tracking algorithm. The reference estimated scheme is presented with maximum power point tracking is used for simultaneous compensation of harmonics and active power injection from the photo voltaic modules without requirement of the separate inverter power circuit. The computer simulation study is carried out to test the efficacy of the control method for simultaneous compensation of harmonics and active power injection from photovoltaic (PV) modules. The PV-APF is used to relieve the source from excessive power demand from the battery charger. The computer simulation study of system is carried to eliminate the harmonics current caused by line frequency diode rectifier based battery charger. 3.1. INTRODUCTION The power quality depends on the load characteristics and are varied with currents. As the load become complex and sophisticated, current distortion become very costly for the manufacturers in terms of loss of production, loss of raw materials and damage to the device. In addition to this, non-linear characteristics leads to many abnormalities such as voltage regulation, single phasing and torque pulsation. This overall chapter is dedicated to the detailed computer simulation study of the distributed static compensator as photo-voltaic grid connected APF with ANPC based voltage source inverter connected in shunt with the electrical network. The first part of the chapter describes the operating principle of a APF followed by control scheme used for the reference current estimation. The second part presents the configurations of distributed static compensator based on active neutral point clamped converter based three-level voltage inverter. The third section is used to describe the photo-voltaic APF based on the active neutral point clamped inverter. Finally, the last part is used to demonstrate the complete computer simulation studies of APF as active power injection device and harmonics elimination without any requirement of the separate inverter [1]-[4]. 3.2. CONFIGURATION OF APF TOPOLOGY The power circuit diagram is shown in the Figure1. The APF is connected in shunt with load and the point of common coupling to eliminates the harmonics current and inject active power of the photo-voltaic modules. The APF is connected at point of common coupling through interfacing inductor. However, the size of the inductor depends on the switching frequency. The dc link capacitor is connected on the dc side of the ANPC APF. The overall system of the APF power system composed of source block, control of APF, voltage source inverter and nonlinear load block. The control unit consists of the estimation of the harmonics current and control of the current inject at the point of common coupling of electrical power system of APF. The APF block consist of the interfacing inductor and dc link capacitor. The non-linear load block consists of the bridge rectifier, commutation inductor and resistiveinductive load on the dc side of the bridge. The power circuit VSa ISa VSb ISb VSc ISc iLa ICa iLb ICb iLc ICc Lc Three-phase, Three-wire Non-linear Load Lc Lc Photovoltaic modules S1a Vdc1 O S1b S2a S2ac S2bc S2b a Photovoltaic modules S2bc S2c b S2bc S2ac S1c S1a’ S1b’ S2a’ S2b’ c S2cc S1c’ Vdc2 S2c’ Fig. 7. Topology of PV cell integrated APF. 3.3. CONTROL SCHEME of APF The control scheme of PV-APF is given in section.2.2. 3.4. DC link voltage regulation The outer loop used for voltage control with maximum power point tracking algorithm is shown in Fig.4. The measured value of photo-voltaic voltage and current is used for the estimation of the reference voltage. The estimated voltage with incremental conductance method is used for voltage regulation across the dc link capacitors of the APF. The value of the reference estimated voltage with maximum power point tracking is depends on the solar irradiations. Then the estimated voltage is used to decide the active power injected into the grid. The active power injection is carried out with the ANPC APF. In addition to this, the active power estimated with maximum power point algorithm also substrated from the harmonics active power of control scheme. The complete process used for the subsequent computations of the reference currents of the APF. IP VP MAXIMUM POWER POINT TRACKING ALGORITHM PI controll er Fig. 8. DC voltage regulator 3.5. Simulation results and discussion The complete power system blocks of the grid connected APF is built with MATLAB/Simulink Simpower system block sets. The complete system of APF consists of the source block, APF, control unit, and nonlinear load. The three source blocks of the APF block sets are realized with MATLAB/Simulink Simpower system source block sets. The control unit of the APF is realized with commonly used Simulink library and control blocks of MATLAB/Simulink library. The APF and nonlinear load are realized with power electronics and elements of library of MATLAB/Simulink. Fig.9. Simulated waveform of APF. Fig.10. APF Simulated waveform with MPPT. The computer simulation with MATLAB/Simulink is shown in the Fig.5. The simulated results of the APF is obtained before connection of photo-voltaic modules. When APF acting alone without photo-voltaic modules then it eliminates the harmonics caused by the nonlinear load. Initially, before the t=0.05sec., the source current is in stepped waveform and distorted. The total harmonics distortion of source current is 23.7%. At the instant t=0.05 sec., when the firing pulses are given to the APF switches then corresponding to it, APF injecting harmonics current to eliminate the harmonics current caused by the non-linear load. The total harmonics distortion of the source current before harmonics elimination is shown in the Fig.8. After the harmonics current elimination with APF the total harmonics distortion is 2.7% and corresponding total harmonics distortion shown in the Fig.9. The value of total harmonics distortion is reduced from the 23.7% to 2.7%. The harmonic current caused by the nonlinear load is eliminated to great extent as depicted in Fig.9. From the waveforms of APF it can be observed from Fig.5. The source current waveform is tends to almost sinusoidal waveform. After harmonics elimination with APF, source current is in synchronous with source voltage. Fig.11. Simulated waveform with power variation. The simulation study of the photo-voltaic based APF is revealed in Fig.5. It can be observed from the Fig.3, the simulated response of the APF is same as that of the active power filter. Before APF operation, source phase current is same as that of load current. After APF switched-on, source current follows source voltage and leads to sinusoidal as it can be seen from the Fig.3. When PV-modules are connected on the dc bus of the APF, the MPPT algorithm estimates the active power from PV-panels. The estimated active power altered the dc bus voltage reference voltage to injected active power from PV panels to the grid. As this can be seen from Fig.4, the active power caused by PV modules flow from APF to source is in reverse to the source current. At the same time, variation in currents waveforms is also observed this variation is due to the variation in solar insolation. The APF characteristics with power variation are depicted in the Fig.6. The different waveform from the spectrum is recognized as photo-voltaic panel voltage, photo-voltaic panel current and active power generated from PV-panel. The photo-voltaic voltage is same as that of the dc link voltage of capacitor. The dc side voltage is used for regulating the active power injected into the grid. As the solar irradiation is constant then the active power generated from the PV-panel is constant. When the solar insolation increases corresponding increase in the generated active power is witnessed from the Fig.6. The increase in the active power generated on dc side of the APF inverter then the corresponding increase in the source current is witnessed from Fig.5. The peak value of the source phase current increases progressively with injected compensating current. As the solar irradiance increases then the corresponding sources current in opposite direction increases, this results in relieving the loading on the source. Fig.12. Source current THD without APF Fig.13. Source current with APF compensation. 3.4. CONCLUSION In this project, photovoltaic inverter based on ANPC is used as a APF. The photo-voltaic APF is used to eliminate harmonics and carryout active power injection from the photovoltaic system to the grid. The PV-APF does not require the separate inverter power circuit to for harmonics eliminations and reactive power compensation to meet the load demand. The reference current estimation PV-APF is carried out with IRPT method. The maximum power point tracking algorithm is implemented based on incremental conductance method. The MPPT algorithm is integrated with IRPT method to track the active power and compensates harmonics currents of the load. The active power computed from the PV-modules is used to regulate the dc side voltage of the APF. The reference dc link voltage changes corresponding change in active power injected to the grid are observed. The ANPC based APF shows the promising results for simultaneous compensation of harmonics and active power injection without requirement of separate ANPCAPF. Chapter 4 4.1. Conclusion This these dealt with diode bridge rectifier based battery charger integrated with photo-voltaic active power filter. The active power filter is used to eliminate the harmonics current and inject the active power to the grid and relieve the power demand from the source. The IRPT control scheme is used for the control of APF to eliminate the harmonics caused by load. IRPT algorithm. The IRPT algorithm is used to compute the active and reactive power and eliminates the load of harmonics and reactive power of the load. From simulation results, it can be confirmed that the active power filter with IRPT method can eliminates the harmonics caused by the diode rectifier based battery charger. And also feed active power to the source. Also, the DCMLI and ANPC is used as active power filter to eliminate harmonics current and fed active power to the source from PV modules. The Dc link control of the IRPT algorithm has been combined with the MPPT algorithm to track the maximum power from the photo-voltaic cell. Increasing conducting mechanism is implemented to obtain maximum power from photovoltaic cells. 4.2. Future scope The grid interconnection of renewable energy is emerging field of power electronics application. 1. Active power filter performance characteristic can be carried with all non-conventional energy sources such as biomass, solar thermal and photo-voltaic power generation 2. The single-stage conversion with active power filter performance characteristics can be carried out with integration the renewable energy source without requirement of the separate inverter circuit. 3. Sliding mode controller can be implemented with neural network is the potential area of research 4. Different maximum power point tracking algorithm performance can be investigated with different control scheme. Acknowledgement Thanks Science and research board of Department of Science and Technology providing fund under ECR scheme File No. ECR/2016/000813. References [1] B. Singh, K. Al-Haddad and A. Chandra, "A review of active filters for power quality improvement," in IEEE Transactions on Industrial Electronics, vol. 46, no. 5, pp. 960971, Oct. 1999. [2] shaque, K., Salam, Z., & Taheri, H. (2011). Accurate MATLAB Simulink PV system simulator based on a two-diode model. Journal of Power Electronics, vol. 11, issue 2, 179–187. [3] H. Akagi, Y. Kanazawa, A. Nabae, "Generalized theory of the instantaneous reactive power in three-phase circuits", Proc. IEEE JIEE IPEC, pp. 821-827, 1983. [4] D. Suresh, K. Venkateswarlu, S.P. Singh, “T2FLC based CHBMLI APF for power quality Improvement,” in IEEE conference, ICCCI-2018, January, 2018. [5] D. Suresh, K. Venkateswarlu, S.P. Singh, “Adaptive control of three level active power filter,” in IEEE conference, ICCCI-2018, January, 2018. [6] D. Suresh, K. Venkateswarlu, S.P. Singh, SIFLC based control implementation of APF, in IEEE conference, ICCCI-2018, January, 2018. [7] Kadri, R., Gaubert, J. P., & Champenois, G. (2011). An improved maximum power point tracking for photovoltaic grid-connected inverter based on voltage-oriented control. IEEE Transactions on Industrial Electronics, Vol.58, No.1, pp.66–75. [8] Mummadi Veerachary, “Improved Maximum Power Point Tracking Algorithm For Photovoltaic Sources, ‟IEEE International Conference on Sustainable Energy Technologies (ICSET)., Nov.2008, 301-305.