Equipotential Earth Bonding 1 OVERVIEW In certain situations, DSE modules may be susceptible to damage caused by a potential difference (pd) across earth connections. This leads to the creation of an unforeseen fault current path through the module. A typical example of such a scenario would be: o o o o o o A DSE module connected to a 3 phase, 4 wire genset system. Star point and battery negative connected to the same earth point, both being well terminated with adequate sized cable. 4 current transformers (CT’s) in use, measuring L1,L2,L3 and N. S2 of each is connected to CT common on the DSE module and a common earth point. The termination to the earth point is sufficient, however a relatively high impedance is present between this earth point and the star point earth connection. In normal operation the pd between all earth points is close to 0 V, and the system operates correctly. An earth fault causes current to flow through the earth circuitry. The star point and battery negative earth terminals remain at a near-equal potential, even as the fault current rises. Conversely, impedance between the CT common earth and star point earth causes a pd across the circuit, which rises with increasing current flow. The pd is seen across the CT common and battery negative terminals of the DSE module. This gives rise to a fault current path through the module, causing erroneous sensor readings and damage, the extent of which is solely limited by the duration in which the current is allowed to flow. 2 INSTALLATION CONSIDERATIONS o o o o Each component of the earthing circuit must be adequately specified to handle the demands of the system it is designed to protect, including calculated fault currents. The layout of the system must be considered. Cables, terminals etc. must be in locations suitable for the function and serviceability of the system. There must be no pd across all earth terminals and the S2 connection of each CT must be connected to earth. The impedance of the earthing circuit must be low enough to negate the possibility of fault currents causing significant pd’s, such as the condition described above. Continued overleaf Author: J.Z. Page 1 of 2 056-091 ISSUE: 1 3 EXAMPLE SYSTEM NOTE: The diagram shows a generic earthing configuration. For further information on earthing conventions, such as floating or positive earth, refer to the relevant DSE operator’s manual. NOTE: For further details of earth fault protection, refer to DSE Publication: 056-019 Earth Fault Protection The diagram below shows a typical 3 phase, 4 wire, star (wye) generator system connected to a generic DSE module S2 of each CT must be connected to earth. If not connected dangerous voltage levels could be induced across the CT windings, leading to incorrect current readings, damage to the CT and, possibly the DSE module. Examples of earth faults include: Breakdown of conductor insulation creating a leakage path to earth, a fault on the load or a lightning strike to the system. A high potential at the CT common terminal with respect to the star point earth may cause damage to the DSE module. Voltage difference across the earth circuit may also lead to incorrect sensor readings and possibly sensor damage. 056-091 ISSUE: 1 Page 2 of 2 Author: J.Z.