EcoStruxure Building TM Powered by EcoStruxure™ Building Operation End-to-end IP Architecture Options Apps, Analytics and Services EcoStruxure Building Advisor Edge Control EcoStruxure Building Operation IP EcoStruxure Building Operation Switch Edge Server AS-P IP Cisco IE Switch IP IP EcoStruxure Building Operation Edge Server AS-P Cisco IE Switch IP Edge Server AS-P EcoStruxure Workplace Advisor Connected Products SmartX IP Controller RP-C or MP-X SmartX IP Controller RP-C or MP-X Daisy Chain Topology - Private Network Hosted directly under Edge/Automation Server (AS-P) 50 RP/MP in a daisy chain Daisy Chain Topology Corporate Network hosted under Enterprise Server 50 RP/MP in a daisy chain Star Topoology - Hosted under Enterprise Server or Edge/ Automation Server (AS-P) Private network if hosted under an Automation Server Building Management Schneider Electric and Cisco® together have developed, tested and validated this building system design to provide customers with confidence in knowing that their systems will securely connect to an end-to-end IP network with a resilient architecture that is easy to manage. SmartX IP Controller RP-C or MP-X RSTP Topology (Self healing) - Private Network Hosted under Edge/ Automation Server (AS-P). 39 RP/MP is supported in an RSTP loop max 200 RP/MP under 1 AS-P. Max 50 RP/MP under 1 AS-B