. RIFT VALLEY INSTITUTE OF SCIENCE AND TECHNOLOGY DEPARTMENT OF ELECTRICAL AND ELECTRONIC ENGINEERING (CEE) INDUSTRIAL MACHINE CONTROL (IMC) Lecture Notes By Dr. Cliff Orori Mosiori ©2015 i . Contents INTRODUCTION................................................................................................................................... 1 ELECTRIC MACHINES ........................................................................................................................ 1 Electric Motor ..................................................................................................................................... 1 Principle and Working of Electric Motor .................................................................................................. 2 TOPIC ONE ........................................................................................................................................ 2 D.C MACHINES................................................................................................................................. 2 Principles of D.C machines .................................................................................................................. 2 Construction of D.C machines ............................................................................................................. 2 Frame .................................................................................................................................................. 3 Main poles ........................................................................................................................................... 2 Armature ............................................................................................................................................. 2 Field windings ..................................................................................................................................... 2 Commutator ........................................................................................................................................ 3 Brush and brush holders ...................................................................................................................... 4 Generator E.M.F Equation ................................................................................................................... 1 Methods of Excitation.......................................................................................................................... 1 Torque and power ................................................................................................................................ 2 Voltage and current ............................................................................................................................. 2 Generator Characteristics ..................................................................................................................... 2 Characteristics Series of DC generator ................................................................................................. 6 Characteristics Shunt DC generator...................................................................................................... 7 Characteristics compound generator..................................................................................................... 8 The Efficiency of the DC Motor Increases by: ................................................................................... 10 Motor Characteristics......................................................................................................................... 10 Torque Speed Curves ......................................................................................................................... 10 Direct on line starter ............................................................................................................................ 1 TOPIC TWO: AC MACHINES ............................................................................................................... 2 Induction Motor................................................................................................................................... 2 Principle of operation and comparison to synchronous motors ............................................................. 2 Construction ........................................................................................................................................ 2 Types of rotors .................................................................................................................................... 2 ii . Slip ring rotor ...................................................................................................................................... 2 Solid core rotor .................................................................................................................................... 3 Starting of induction motors................................................................................................................. 3 Direct-on-line starting .......................................................................................................................... 3 Wye-Delta starters ............................................................................................................................... 4 Variable-frequency drives .................................................................................................................... 4 Resistance starters ............................................................................................................................... 4 Series Reactor starters.......................................................................................................................... 5 Single Phase induction motor ............................................................................................................... 5 Rotating magnetic field........................................................................................................................ 6 Description of magnetic field ............................................................................................................... 6 Permanent-split capacitor motor........................................................................................................... 1 Capacitor-start induction motor............................................................................................................ 2 Capacitor-run induction motor ............................................................................................................. 2 Resistance split-phase induction motor ................................................................................................ 3 THREE PHASE INDUCTION MOTOR ................................................................................................. 1 Working Principle of Three Phase Induction Motor ................................................................................. 1 Production of Rotating Magnetic Field ............................................................................................. 1 What is the operating principle of a 3ph induction motor? .................................................................... 2 Production of a rotating magnetic field ................................................................................................ 3 Production of magnetic flux ................................................................................................................. 3 SPEED CONTROL OF THREE PHASE INDUCTION MOTOR ............................................................ 5 The Speed of Induction Motor is changed from Both Stator and Rotor Side .............................. 2 Speed Control from Stator Side .................................................................................................... 2 Speed Control from Rotor Side ..................................................................................................... 4 Electric Motor Controls ....................................................................................................................... 2 Motor Starting ..................................................................................................................................... 2 Motor Protection.................................................................................................................................. 5 Other Motor Protection Devices ........................................................................................................... 6 TOPIC THREE: CONTACTORS ............................................................................................................ 2 CONTACTORS .................................................................................................................................. 2 Applications of Contactors................................................................................................................... 2 iii . 1. Lighting control ....................................................................................................................... 2 2. Magnetic starter ....................................................................................................................... 3 3. Vacuum contactor .................................................................................................................... 3 How Contactor Controls an Electric Motor .......................................................................................... 3 Topic four ............................................................................................................................................... 1 Preventive Maintenance........................................................................................................................... 1 Controlling Maintenance Hazards ........................................................................................................ 3 Instrumentation systems ......................................................................... Error! Bookmark not defined. Assemble a simple instrumentation ......................................................... Error! Bookmark not defined. Signal processing methods ...................................................................... Error! Bookmark not defined. Data processing elements ........................................................................ Error! Bookmark not defined. iv . INTRODUCTION ELECTRIC MACHINES Electric Motor An electric motor is an electric machine that converts electrical energy into mechanical energy. In normal motoring mode, most electric motors operate through the interaction between an electric motor's magnetic field and winding currents to generate force within the motor. In certain applications, such as in the from the power grid, inverters or generators. transportation industry with traction motors, Small motors may be found in electric electric motors can operate in both motoring watches. The largest of electric motors are and generating or braking modes to also used produce electrical energy from mechanical compression energy. applications with ratings reaching 100 for megawatts. ship propulsion, and pipeline pumped-storage Electric motors may be classified by electric power source type, internal construction, application, type of motion output, and so on Application of electric motors revolutionized industry. Industrial processes were no transmission compressed Found in applications as diverse as industrial longer using air or limited line by power shafts, hydraulic belts, pressure. Instead every machine could be equipped fans, blowers and pumps, machine tools, with its own electric motor, providing easy household appliances, power tools, and disk control at the point of use, and improving drives, electric motors can be powered by power direct current (DC) sources, such as from transmission efficiency. Electric motors applied in agriculture eliminated batteries, motor vehicles or rectifiers, or by human and animal muscle power from such alternating current (AC) sources, such as tasks as handling grain or pumping water. 1 . Household uses of electric motors reduced common motor works on direct current. So, heavy labor in the home and made higher it is also called DC motor. When a standards of convenience, comfort and rectangular coil carrying current is placed in safety possible. a magnetic field, a torque acts on the coil which rotates it continuously. When the coil rotates, the shaft attached to it also rotates Working Principle of Electric Motor and thus it is able to do mechanical work. An electric motor is a device which converts electrical energy into mechanical energy. A 2 . TOPIC ONE D.C MACHINES Principles of D.C machines D.C machines are the electro mechanical energy converters which work from a D.C source and generate mechanical power or convert mechanical power into a D.C power. In any electric motor, operation is based on simple electromagnetism. A current-carrying conductor generates a magnetic field; when this is then placed in an external magnetic field, it will experience a force proportional to the current in the conductor, and to the strength of the external magnetic field. Magnetic field in motor As you are well aware of from playing with magnets as a kid, opposite (North and South) polarities attract, while like polarities (North and North, South and South) repel. The internal 2 . configuration of a DC motor is designed to harness the magnetic interaction between a currentcarrying conductor and an external magnetic field to generate rotational motion. Direction of rotation Let's start by looking at a simple 2-pole DC magnets. The stator is the stationary part of electric motor (here red represents a magnet the motor -- this includes the motor casing, or winding with a "North" polarization, as well as two or more permanent magnet while green represents a magnet or winding pole pieces. The rotor (together with the with a "South" polarization). Every DC axle, and attached commutator) rotate with motor has six basic parts -- axle, rotor respect to the stator. The rotor consists of (armature), windings (generally on a core), the windings stator, commutator, field magnet(s), and brushes. In most common being DC motors, the external magnetic field is commutator. produced by high-strength permanent 3 electrically connected to the . Torque in motor The geometry of the brushes, commutator Given our example two-pole motor, the contacts, and rotor windings are such that rotation reverses the direction of current when power is applied, the polarities of the through the rotor winding, leading to a "flip" energized winding and the stator magnet(s) of the rotor's magnetic field, driving it to are misaligned, and the rotor will rotate until continue rotating.DC motors will always it is almost aligned with the stator's field have more than two poles. This avoids "dead magnets. As the rotor reaches alignment, the spots" in the commutator. With a two-pole brushes move to the next commutator motor, there is a moment where the contacts, and energize the next winding. commutator shorts out the power supply. 1 . This would be bad for the power supply, disadvantage of such a simple motor is that waste it would exhibit a high amount of torque energy, components as and well. damage Yet motor "ripple". another Current in Motor Force in Motor 2 . You'll notice that one pole is fully energized at a time (but two others are "partially" energized). As each brush transitions from one commutator contact to the next, one coil's field will rapidly collapse, as the next coil's field will rapidly charge up. You can see that this is a direct result of the coil But iron core construction also has several windings' series wiring. There's probably no disadvantages. The iron armature has a better way to see how an average DC motor relatively high inertia which limits motor is put together, than by just opening one up. acceleration. This construction also results This is a basic 3-pole DC motor, with 2 in high winding inductances which limit brushes and three commutator contacts. The brush and commutator life. use of an iron core armature is quite common, and has a number of advantages. In small motors, an alternative design is First off, the iron core provides a strong, often used which features a 'coreless' rigid support a armature winding. This design depends upon consideration for the coil wire itself for structural integrity. As high-torque motors. The core also conducts a result, the armature is hollow, and the heat away from the rotor windings, allowing permanent magnet can be mounted inside the motor to be driven harder than might the rotor coil. Coreless DC motors have otherwise be the case. Iron core construction much lower armature inductance than iron- is also relatively inexpensive compared with core motors of comparable size, extending other construction types. brush and commutator life. DC motors have for the windings particularly important -- been used in industrial applications for years. Coupled with a DC drive, DC motors provide very precise control DC motors can be used with conveyors, elevators, extruders, marine applications, material handling, paper, plastics, rubber, steel, and textile applications to name a few. 2 . Torque in a DC motor is produced by the product of the magnetic field created by the field winding or magnets and the current flowing in the armature winding. The action of a mechanical commutator switches the armature current from one winding to another to maintain the relative position of the current to the field, thereby producing Figure 1 - DC motor in schematic form torque independent of rotor position. Standard DC motors are readily available in one of two main forms: Wound-field - where the magnetic flux in the motor is controlled by the current flowing in a field or excitation winding, usually located on the stator. Permanent magnet - where the magnetic flux in the motor is created by permanent magnets which have a curved face to create a constant air-gap to the conventional armature, located on the rotor. These are commonly used at powers up to approximately 3 kW. 1 . VaIa = EaIa + Ia2Ra The circuit of a shunt-wound DC motor (3) (Fig. 2 below) shows the armature M, the armature resistance Ra and the (or total power supplied = power output + field armature losses). The interaction of the field winding. The armature supply voltage Va is flux and armature flux produces an armature supplied typically from a controlled thyristor torque as given in below equation 4. system and the field voltage Vf from a separate bridge rectifier. Torque M = k2IfIa (4) where k2 is a motor constant and If is the field current. This confirms the straightforward and linear characteristic of the DC motor and consideration of these simple equations will show its controllability and Figure 2 -Shunt wound DC motor inherent stability. The characteristic of a motor is represented by curves of speed As the armature rotates, an electromotive against input current or torque and its shape force (emf ) Ea is induced in the armature can be derived from eqns 1 and 2: circuit and is called the back-emf since it opposes the applied voltage Va (according to k1nφ = Va – (IaRa) (5) Lenz’s Law). The Ea is related to armature speed and main field flux, φ by: If the flux is held constant by holding the field Ea = k1nφ (1) current constant in a properly compensated motor then: where n is the speed of rotation, φ is the n = k2[Va – (IaRa)] (6) field flux and k1 is a motor constant. From Figure 1 it is seen that the terminal armature From eqns 4 and 6, it follows that full voltage Va is given by: control of the DC motor can be achieved through control of the field current and the Va = Ea + IaRa (2) armature current. In the DC shunt wound motor shown in Figure 2 these currents can Multiplying each side of eqn 2 by Ia gives: be controlled independently. Most industrial 2 . DC motor controllers or drives are voltage 5 per cent of Va, giving a torque - speed fed and the current is controlled by curve shown as a in Figure 6, where speed measuring the current and adjusting the remains constant over a wide range of load voltage to give the desired current. This torque. basic arrangement is shown in Figure 3. The compound-wound DC motor shown in The series DC motor shown in Figure 4 has Figure 5 combines both shunt and series the field and armature windings connected characteristics. The shape of the torque– in series. In this case the field current and speed characteristic is determined by the armature current are equal and show resistance values of the shunt and series characteristically performance fields. The slightly drooping characteristic results, though still defined by eqns. 4 and 6. (curve b in Figure 6) has the advantage in In the shunt motor the field flux φ is only many slightly affected by armature current, and mechanical effects of shock loading. different applications the value of IaRa at full load rarely exceeds Figure 3 - Control structure for a shunt wound DC motor 3 of reducing the . The series DC motor curve (in Figure 6) shows that the initial flux increases in proportion to current, falling away due to magnetic saturation. In addition the armature circuit includes the resistance of the field winding and the speed becomes roughly inversely proportional to the current. If the load falls to a low value the speed increases dramatically, which may be hazardous, so, the series motor should not normally be used where there is a possibility of load loss. Figure 4 - Schematic of series DC motor But because it produces high values of torque at low speed and its characteristic is falling speed with load increase, it is useful in applications such as traction and hoisting, and some mixing duties where initial stiction is dominant. Under semiconductor converter control with speed feedback from a tachogenerator, the shape of the speed–load curve is determined within the controller. It has become standard to use a shunt DC motor with converter control even though the speed-load curve, when under open-loop control is often slightly drooping. The power-speed limit for the DC motor is approximately 3 × 106 kW rev/min, due to restrictions imposed by the commutator. Construction of D.C machines A D.C machine consists mainly of two part the stationary part called stator and the rotating part called rotor. The stator consists of main poles used to produce magnetic flux ,commutating poles or interpoles in between the main poles to avoid sparking at the commutator but in the case of small machines sometimes the interpoles are avoided and finally the frame or yoke which forms the supporting structure of the machine. The rotor consist of an armature a cylindrical metallic body or core with slots in it to place armature windings or bars, a commutator and brush gears 2 . The magnetic flux path in a motor or generator is show below and it is called the magnetic structure of generator or motor. The major parts can be identified as, 1. Frame 5. Commutator and brush gear 2. Yoke 6. Commutating poles 3. Poles Institute of Technology Madras 7. Compensating winding 4. Armature 8. Other mechanical parts magnetic fluxes from the main poles and interpoles is called Yoke. Why we use cast steel instead of cast iron for the construction of Yoke? In early days Yoke was made up of cast iron but now it is replaced by cast steel. This is because cast iron is saturated by a flux density of 0.8 Wb/sq.m whereas saturation with cast iron steel is about 1.5 Wb/sq.m. So for the same magnetic flux density the cross section area needed for cast steel is less than cast iron hence the weight of the machine too. If we use cast iron there may be chances of blow holes in it while casting.so now rolled steels are developed and these have consistent magnetic Frame Frame is the stationary part of a machine on and mechanical properties. which the main poles and commutator poles are bolted and it forms the supporting structure by connecting the frame to the bed plate. The ring shaped body portion of the frame which makes the magnetic path for the 3 . End Shields or Bearings If the armature diameter does not exceed 35 Armature The armature to 45 cm then in addition to poles end shields conductors are located. The armature is or frame head with bearing are attached to constructed by stacking laminated sheets of the frame. If the armature diameter is greater silicon steel. Thickness of these lamination is than 1m pedestals type bearings are mounted kept low to reduce eddy current losses. As on the machine bed plate outside the frame. the laminations carry alternating flux the These bearings could be ball or roller type choice of suitable material, insulation coating but generally plain pedestals bearings are on the laminations, stacking it etc are to be employed. If the diameter of the armature is done more carefully. The core is divided into large a brush holder yoke is generally fixed packets to facilitate ventilation. The winding to the frame. cannot be placed on the surface of the rotor is where the moving due to the mechanical forces coming on the same. Open parallel sided equally spaced Main poles Solid poles of fabricated steel slots are normally punched in the rotor with laminations. These slots house the armature separate/integral pole shoes are fastened to winding. Large sized machines employ a the frame by means of bolts. Pole shoes are spider on which the laminations are stacked generally laminated. Sometimes pole body in segments. End plates are suitably shaped and pole shoe are formed from the same so as to serve as ’Winding supporters’. laminations. The pole shoes are shaped so as Armature construction process must ensure to have a slightly increased air gap at the tips. provision of sufficient axial and radial ducts Inter-poles are small additional poles located to facilitate easy removal of heat from the in between the main poles. These can be armature winding. solid, or laminated just as the main poles. These are also fastened to the yoke by bolts. Sometimes the yoke may be slotted to receive these poles. The inter poles could be of Field windings In the case of wound field machines (as tapered section or of uniform cross section. against permanent magnet excited machines) These are also called as commutating poles the field winding takes the form of a or com poles. The width of the tip of the com concentric coil wound around the main poles. pole can be about a rotor slot pitch. These carry the excitation current and 2 . produce the main field in the machine. Thus taped and lowered into the open slots on the the poles are created electromagnetically. armature. In the case of small machines, they Two types of windings are generally can be hand wound. The coils are prevented employed. In shunt winding large number of from flying out due to the centrifugal forces turns of small section copper conductor isof by means of bands of steel wire on the Technology Madras used. The resistance of surface of the rotor in small groves cut into it. such winding would be an order of In the case of large machines slot wedges are magnitude larger than the armature winding additionally used to restrain the coils from resistance. In the case of series winding a few flying away. The end portion of the windings turns of heavy cross section conductor is are taped at the free end and bound to the used. The resistance of such windings is low winding carrier ring of the armature at the and is comparable to armature resistance. commutator end. The armature must be Some machines may have both the windings dynamically on the poles. The total ampere turns required centrifugal forces at the operating speeds. to establish the necessary flux under the poles Compensating winding One may find a bar is calculated from the magnetic circuit winding housed in the slots on the pole shoes. calculations. The total mmf required is This is mostly found in D.C machines of very divided equally between north and south large poles as the poles are produced in pairs. The compensating winding. In smaller machines, mmf required to be shared between shunt and they may be absent. rating. balanced Such to reduce winding is the called series windings are apportioned as per the design requirements. As these work on the concentric coils. Mmf ’per pole’ is normally Commutator Commutator is the key element which made used in these calculations. Armature winding the D.C machine of the present day possible. As mentioned earlier, if the armature coils It consists of copper segments tightly are wound on the surface ofthe armature, fastened such construction becomes mechanically insulating separators on an insulated base. weak. The conductors may fly away when The whole commutator forms a rigid and the armature starts rotating. Hence the solid assembly of insulated copper strips and armature windings are in general pre-formed, can rotate at high speeds. Each com mutator same magnetic system they are in the form of 3 together with mica/micanite . segment is provided with a ’riser’ where the is taken out by means of flexible pigtail. The ends of the armature coils get connected. The brushes are kept pressed on the commutator surface of the commutator is machined and with the help of springs. This is to ensure surface is made concentric with the shaft and proper contact between the brushes and the the current collecting brushes rest on the commutator even under high speeds of same. Under-cutting the mica insulators that operation. Jumping of brushes must be are between these commutator segments has avoided to ensure arc free current collection to be done periodi- cally to avoid fouling of and to keep the brush contact drop low. Other the surface of the commutator by mica when mechanical parts End covers, fan and shaft the commutator gets worn out. bearings form other important me- chanical parts. End covers are completely solid or have opening for ventilation. They support Brush and brush holders Brushes rest on the surface the bearings which are on the shaft. Proper the machining is to be ensured for easy commutator. Normally electro-graphite is assembly. Fans can be external or internal. In used actual most machines the fan is on the non- composition of the brush depends on the commutator end sucking the air from the peripheral speed of the commutator and the commutator end and throwing the same out. working voltage. The hardness of the Adequate quantity of hot air removal has to graphite brush is selected to be lower than be ensured. as brush material. The of that of the commutator. When the brush wears out the graphite works as a solid Bearings lubricant coefficient. bearings at both ends. For larger machines More number of relatively smaller width roller bearings are used especially at the brushes is preferred in place of large broad driving end. The bearings are mounted press- brushes. The brush holders provide slots for fit on the shaft. They are housed inside the the brushes to be placed. The connection end shield in such a manner that it is not Brush holder with a Brush and Positioning of necessary to remove the bearings from the the brush on the commutator from the brush shaft for dismantling. reducing frictional 4 Small machines employ ball . series) Generator E.M.F Equation Let Φ = flux/pole in weber Z = total number in one path = Z/2 E.M.F. generated/path is of armture conductors = No.of slots x No.of conductors/slot P = No.of generator poles A = No.of parallel paths in armature N = For a simplex lap-wound generator armature rotation in revolutions per minute No.of parallel paths = P No.of conductors (in (r.p.m) E = e.m.f induced in any parallel path series) in armature Generated e.m.f Eg = e.m.f in one path = Z/P E.M.F.generated/path generated in any one of the parallel paths i.e E. Average e.m.f geneated /conductor = dΦ/dt volt (n=1) Now, flux cut/conductor in one revolution dΦ = ΦP Wb No. of In general generated e.m.f revolutions/second = N/60 Time for one revolution, dt according to Electromagnetic = 60/N second Hence, Faraday's Induction, Laws of E.M.F generated/conductor is where A = 2 - for simplex wave-winding A = P - for simplex lap-winding For a simplex wave-wound generator No. of parallel paths = 2 No. of conductors (in Methods of Excitation Various methods of excitation of the field windings are shown in Fig. 1 . Figure shows Field-circuit connections of dc machines: (a) separate excitation, (b) series, (c) shunt, (d) compound. Consider first dc generators. Separately-excited generators and Self- excited generators: series generators, shunt generators, compound generators. With self-excited generators, residual magnetism must be present in the machine iron to get the self-excitation process started. o N.B.: long- and short-shunt, cumulatively Figure Volt-ampere characteristics of dc and differentially compound. Typical characteristics steady-state volt-ampere are in shown generators. Any of the methods of excitation used for generators can also be used for Fig.7.5, motors. constant-speed operation being assumed. Typical steady-state dc-motor speed- The relation between the steady-state torque characteristics are shown in Fig.7.6, generated emf Ea and the armature terminal in which it is assumed that the motor voltage Va is Va =Ea −IaRa (7.10) terminals are supplied from a constantvoltage source. 2 . In a motor the relation between the emf Torque and power The electromagnetic torque Tmech, Ea generated in the armature and and the Tmech =KaΦdIa armature terminal voltage Va is The generated voltage, Ea Ea =KaΦdωm Va=Ea+IaRa (7.11) The application advantages of dc machines lie in the variety of performance characteristics offered by the possibilities of Voltage and current Va: the terminal voltage of the armature shunt, series, and compound excitation. winding Vt: the terminal voltage of the dc machine, including the voltage drop across the series connected field winding, Va = Vt if there is no series field winding Ra: the resistance of armature, Rs: the resistance of the series field, Va =Ea ± IaRa Vt=Ea ± Ia( Ra+Rs) IL =Ia±If Figure Speed-torque characteristics of dc motors. Generator Characteristics The three most important characteristics or curves of a d.c generator are; 1. Open Circuit Characteristic (O.C.C.) same for all generators whether separately or This curve shows the relation between the self-excited. The data for O.C.C. curve are generated e.m.f. at no-load (E0) and the field obtained experimentally by operating the current (If) at constant speed. It is also generator at no load and constant speed and known as magnetic characteristic or no-load recording the change in terminal voltage as saturation curve. Its shape is practically the the field current is varied. 2 . 2. Internal or Total characteristic (E/Ia) 1. No-load saturation characteristic This curve shows the relation between the (E0/If) generated e.m.f. on load (E) and the It armature current (Ia). The e.m.f. E is less characteristic than E0 due to the demagnetizing effect of Characteristic (O.C.C). It shows the armature reaction. Therefore, this curve will relation lie below the open circuit characteristic generated e.m.f in armature, E0 and (O.C.C.). The internal characteristic is of the field or exciting current If at a interest chiefly to the designer. It cannot be given fixed speed. It is just the obtained directly by experiment. It is magnetisation curve for the material because a voltmeter cannot read the e.m.f. of the electromagnets. Its shape is generated on load due to the voltage drop in practically the armature generators whether resistance. The internal is also know as or Open between the same Magnetic circuit no-load for all separately- excited or self-excited. characteristic can be obtained from external characteristic if winding resistances are known because armature reaction effect is included in both characteristics. 3. External characteristic (V/IL) This curve shows the relation between the terminal voltage (V) and load current (IL). The terminal voltage V will be less than E due to voltage drop in the armature circuit. Therefore, this curve will lie below the internal characteristic. This characteristic is A typical no load saturation curve is shown very important in determining the suitability in Figure. It has generator output voltage of a generator for a given purpose. It can be plotted against field current. The lower obtained by making simultaneous; straight line portion of the curve represents the air gap because the magnetic parts are not saturated. When the magnetic parts start to saturate, the curve bends over until 2 . complete saturation is reached. Then the in the poles, some e.m.f (= OA) is generated curve becomes a straight line again. even when If =0.Hence, the curve starts a little way up. The slight curvature at the lower end is due to magnetic inertia. It is 2. Separately-excited Generator seen that the first part of the curve is The No-load saturation curve of a separately practically straight. This is due to fact that at excited generator will be as shown in the low flux densities reluctance of iron path above figure. It is obvous that when If is being negligible, total reluctance is given by increased from its initial small value, the the air gap reluctance which is constant. flux and hence generated e.m.f Eg increase Hence, the flux and consequently, the directly as current so long as the poles are generated e.m.f is directly proportional to unsaturated. This is represented by straight the exciting current. However, at high flux portion in figure. But as the flux density densities, where μ is small, iron path increases, the poles become saturated, so a reluctance becomes appreciable and straight greater increase If is required to produce a relation between E and If no longer holds given increase in voltage than on the lower good. In other words, after point B, part of the curve. That is why the upper saturation of pole starts. However, the initial portion of the curve bends. slope of the curve is determined by air-gap width. O.C.C for higher speed would lie above this curve and for lower speed, would lie below it. Separately-excited consider a Generator separately-excited Let us generator giving its rated no-load voltage of E0 for a certain constant field current. If there were no armature reaction and armature voltage drop, then this voltage would have remained constant as shown in figure by the horizontal The O.C.C curve for self-excited generators line 1. But when the generator is loaded, the whether shunt or series wound is shown in voltage falls due to these two causes, above figure. Due to the residual magnetism 3 . thereby giving slightly dropping and hence generated e.m.f. is also increased characteristics. If we subtract from E0 the as shown by the curve. Curve Oa is the values of voltage drops due to armature O.C.C. The extra exciting current necessary reaction for different loads, then we get the to neutralize the weakening effect of value of E-the e.m.f actually induced in the armature reaction at full load is given by the armature under load conditions. Curve 2 is horizontal distance ab. Hence, point b is on plotted in this way and is known as the the internal characteristic. characteristic (V/I) It is also referred to as internal characteristic. 3. External performance characteristic or sometimes voltage-regulating curve. It gives relation between the terminal voltage V and the load current I. This curve lies below the internal characteristic because it takes in to account the voltage drop over the armature circuit resistance. The values of V are obtained by subtracting IaRa from corresponding values of E. This Series Generator characteristic is of great importance in judging the suitability of a generator for a particular purpose. It may be obtained in two ways (i) by making simultaneous measurements with a suitable voltmeter and an ammeter on a loaded generator or (ii) graphically from the O.C.C provided the armature and field resistances are known and also if the demagnetizing effect or the armature reaction is known. In this generator, because field windings are in series with the armature, they carry full armature current Ia. As Ia is increased, flux 4 . separate excitation. This is due to the fact that, since the output voltage is reduced because of the armature reaction effect and armature IR drop, the field voltage is also reduced which further reduces the flux. It can also be seen that beyond a certain critical value, the shunt generator shows a reversal in trend of current values with decreasing voltages. This point of maximum current output is known as the breakdown point. At the short circuit condition, the only Figure above shows the external flux available to produce current is the characteristic curves for generators with residual magnetism of the armature. various types of excitation. If a generator, which is separately excited, is driven at To build up the voltage on a series constant speed and has a fixed field current, generator, the external circuit must be the output voltage will decrease with connected and its resistance reduced to a increased load current as shown. This comparatively low value. Since the armature decrease is due to the armature resistance is in series with the field, load current must and armature reaction effects. If the field be flowing to obtain flux in the field. As the flux remained constant, the generated voltage and current rise the load resistance voltage would tend to remain constant and may be increased to its normal value. As the the output voltage would be equal to the external characteristic curve shows, the generated voltage minus the IR drop of the voltage output starts at zero, reaches a peak, armature circuit. and then falls back to zero. However, the demagnetizing component of The combination of a shunt field and a series armature reactions tends to decrease the field gives the best external characteristic as flux, thus adding an additional factor, which illustrated in Figure. The voltage drop, decreases the output voltage. In a shunt which occurs in the shunt machine, is excited generator, it can be seen that the compensated for by the voltage rise, which output voltage decreases faster than with 5 . occurs in the series machine. The addition of a sufficient number of series turns offsets the armature IR drop and armature reaction effect, resulting in a flat-compound generator, which has a nearly constant voltage. If more series turns are added, the (i) O.C.C. Curve 1 shows the open circuit voltage may rise with load and the machine characteristic (O.C.C.) of a series generator. is known as an over-compound generator. It can be obtained experimentally by The speed of a D.C machine operated as a disconnecting the field winding from the generator is fixed by the prime mover. machine and exciting it from a separate D.C For general-purpose operation, the prime source as discussed in Sec. (3.2). mover is equipped with a speed governor so that the speed of the generator is practically constant. Under such the (ii) Internal characteristic Curve 2 shows generator performance deals primarily with the total or internal characteristic of a series the relation between excitation, terminal generator. It gives the relation between the voltage and load. These relations can be best generated e.m.f. E. on load and armature exhibited graphically by means of curves current. Due to armature reaction, the flux in known as generator characteristics. These the machine will be less than the flux at no characteristics the load. Hence, e.m.f. E generated under load behaviour of the generator under different conditions will be less than the e.m.f. EO load conditions. generated show at condition, a glance under no load conditions. Consequently, internal characteristic curve generated Characteristics Series of DC generator Fig. shows the connections of a series under no load conditions. Consequently, internal characteristic curve lies below the O.C.C. curve; the difference wound generator. Since there is only one between them representing the effect of current (that which flows through the whole armature reaction [See Fig. 3.7 (ii)]. machine), the load current is the same as the exciting current. 6 . (iii)External characteristic Curve 3 shows Now raise a perpendicular from point B and the external characteristic of a series mark a point b on this line such that ab = generator. It gives the relation between AB. Then point b will lie on the external terminal voltage and load current IL. characteristic of the generator. Following similar procedure, other points of external V= E-Ia(Ra+Rse) characteristic can be located. It is easy to see that we can also plot internal characteristic from the external characteristic. Characteristics Shunt DC generator Fig (3.9) (i) shows the connections of a shunt wound generator. The armature current Ia splits up into two parts; a small fraction Ish flowing through shunt field winding while the major part IL goes to the external load. Therefore, external characteristic curve will lie below internal characteristic curve by an amount equal to ohmic drop [i.e., Ia(Ra+Rse)] in the machine as shown in Fig. (3.7) (ii). The internal and external characteristics of a D.C series generator can be plotted from one another as shown in Fig. (3.8). Suppose we are given the internal I. O.C.C. The O.C.C. of a shunt characteristic of the generator. Let the line generator is similar in shape to that of a OC represent the resistance of the whole series generator as shown in Fig. (3.9) machine i.e. Ra+Rse.If the load current is (ii). The line OA represents the shunt OB, drop in the machine is AB i.e. field circuit resistance. When the generator is run at normal speed, it will AB = Ohmic drop in the machine = build up a voltage OM. At no-load, the OB(Ra+Rse) terminal voltage of the generator will be 7 . constant (= OM) represented by the the increase in load current with the horizontal dotted line MC. decrease of load resistance. Any decrease of II) Internal characteristic load resistance beyond this point, instead of When the increasing the current, ultimately results in generator is loaded, flux per pole is reduced reduced current. Consequently, the external due to armature reaction. Therefore, e.m.f. E characteristic turns back (dotted curve) as generated on load is less than the e.m.f. shown in Fig. (3.10). The tangent OA to the generated at no load.As a result, the internal curve represents the minimum external characteristic (E/Ia) drops down slightly as resistance required to excite the shunt shown in Fig.(3.9) (ii). generator on load and is called critical (iii)External characteristic Curve 2 shows external resistance. If the resistance of the the external characteristic of a shunt external circuit is less than the critical generator. It gives the relation between external resistance (represented by tangent terminal voltage V and load current IL. V = OA in Fig. 3.10), the machine will refuse to E – IaRa = E -(IL +Ish)Ra Therefore, excite or will de-excite if already running external characteristic curve will lie below This means that external resistance is so low the internal characteristic curve by an as virtually to short circuit the machine and amount equal to drop in the armature circuit so doing away with its excitation. [i.e., (IL +Ish)Ra ] as shown in Fig. (3.9) Note. There are two critical resistances for a (ii). Note. It may be seen from the external shunt generator viz., (i) critical field characteristic that change in terminal voltage resistance (ii) critical external resistance. For from no-load to full load is small. The the shunt generator to build up voltage, the terminal voltage can always be maintained former should not be exceeded and the latter constant by adjusting the field rheostat R must not be gone below automatically External Resistance for Shunt Generator Characteristics compound generator In a compound generator, both series and f the load resistance across the terminals of a shunt excitation are combined as shown in shunt generator is decreased, then load Fig. (3.13). The shunt winding can be current increase? However, there is a limit to connected either across the armature only 8 . (short-shunt across flux and hence the generated voltage. The (long-shunt increase in generated voltage is greater than connection G). The compound generator can the IaRa drop so that instead of decreasing, be the terminal voltage increases as shown by armature connection plus series S) field cumulatively or compounded or curve A in Fig. (3.14). differentially compounded generator. The latter is rarely used in practice. Therefore, (ii) If series winding turns are so we shall discuss the characteristics of adjusted that with the increase in load cumulatively compounded generator. It may current, be noted that external characteristics of long series winding of such a machine has External characteristic lesser number of turns than the one in over-compounded Fig. (3.14) shows the external characteristics excitation aids the much shunt the increase in and, for a given load current. Consequently, the full-load voltage is excitation. The degree of compounding upon machine therefore, does not increase the flux as of a cumulatively compounded generator. depends voltage called flat-compounded generator. The almost identical. series terminal substantially remains constant, it is and short shunt compound generators are The the nearly equal to the no-load voltage as series indicated by curve B in Fig (3.14). excitation with the increase in load current. (iii) If series field winding has lesser number of turns than compounded machine, for the a flat terminal voltage falls with increase in load current as indicated by curve C m Fig. (3.14). Such a machine is called undercompounded generator. (i).If series winding turns are so adjusted that with the increase in load current the terminal voltage increases, it is called overcompounded generator. In such a case, as the load current increases, the series field m.m.f. increases and tends to increase the 9 . Voltage Regulation The change in terminal voltage of a generator between full and no load (at constant speed) is called the voltage regulation, usually expressed as a percentage of the voltage at full-load. % Voltage regulation= [(VNL-VFL)/VFL] × 100 where VNL = Terminal voltage of generator at no load VFL = Terminal voltage of generator at full load Note that voltage regulation of a generator is determined with field circuit and speed held constant. If the voltage The graph above shows a torque/speed curve regulation of a generator is 10%, it means of a typical D.C motor. Note that torque is that terminal voltage increases 10% as the inversely proportional to the speed of the load is changed from full load to no load. output shaft. In other words, there is a tradeoff between how much torque a motor The Efficiency of the DC Motor Increases delivers, and how fast the output shaft spins. by: Motor characteristics are frequently given as Increasing number of turns in the coil Increasing the strength of the current Increasing X-section area of of the coil the graph at which the torque is a maximum, Increasing the strength of the radial but the shaft is not rotating. two points on this graph: The stall torque,, represents the point on magnetic field The no load speed,, is the maximum output speed of the motor (when no torque is Motor Characteristics applied to the output shaft). Torque Speed Curves In order to effectively design with D.C The motors, it is necessary to understand their characteristic curves. For every motor, there linear model of a D.C motor torque/speed curve is a very good approximation. The torque/speed curves is a specific Torque/Speed curve and Power shown below are actual curves for the green curve. maxon motor (pictured at right) used by 10 . students in 2.007. One is a plot of empirical Recall that earlier we defined power as the data, and the other was plotted mechanically product of torque and angular velocity. This using a device developed at MIT. Note that corresponds to the area of a rectangle under the characteristic torque/speed curve for this the torque/speed curve with one corner at motor is quite linear. the origin and another corner at a point on the curve. Due to the linear inverse relationship between torque and speed, the maximum power occurs at the point where τ = ½ , and = ½ . This is generally true as long as the curve represents the direct output of the motor, or a simple gear reduced output. If the specifications are given as two points, it is safe to assume a linear curve. 11 . By substituting equations 3. and 4. into equation 2 above, we see that the power curves for a D.C motor with respect to both speed and torque are quadratics, as shown in equations 5. and 6. From these equations, we again find that maximum output power occurs at = ½, and = ½ respectively. 12 . Direct on line starter In electrical engineering, a direct on line circuit. The maximum size of a motor (DOL) or across the line starter starts limited by the supply utility for this reason. electric motors by applying the full line For example, a utility may require rural voltage to the motor terminals. This is the customers to use reduced-voltage starters for simplest type of motor starter. A DOL motor motors larger than 10 kW. allowed on a direct on line starter may be starter also contain protection devices, and in some cases, condition monitoring. DOL starting is sometimes used to start Smaller sizes of direct on-line starters are small water pumps, compressors, fans and manually operated; larger sizes use an conveyor electromechanical to asynchronous motor, such as the 3-phase switch the motor circuit. Solid-state direct squirrel-cage motor, the motor will draw a on line starters also exist. high starting current until it has run up to contactor (relay) belts. In the case of an full speed. This starting current is commonly A direct on line starter can be used if the around six times the full load current, but high inrush current of the motor does not may as high as 12 times the full load current. cause excessive voltage drop in the supply 1 . TOPIC TWO AC MACHINES Induction Motor An induction motor or asynchronous motor is a type of alternating current motor where power is supplied to the rotor by means of electromagnetic induction. An electric motor converts electrical power polyphase induction motors, which are to mechanical power in its rotor (rotating frequently used in industrial drives. part). There are several ways to supply power to the rotor. In a DC motor this power Induction motors are now the preferred is supplied to the armature directly from a choice for industrial motors due to their DC source, while in an induction motor this rugged construction, absence of brushes power is induced in the rotating device. An (which are required in most DC motors) induction motor is sometimes called a and—thanks to modern power electronics— rotating transformer because the stator the ability to control the speed of the motor. (stationary part) is essentially the primary side of the transformer and the rotor Principle of operation and comparison to synchronous motors 3-phase power supply provides a rotating (rotating part) is the secondary side. Unlike the normal transformer which magnetic field in an induction motor. The changes the current by using time varying basic difference between an induction motor flux, induction motors use rotating magnetic and a synchronous AC motor is that in the fields to transform the voltage. The primary latter a current is supplied into the rotor side's current creates an electromagnetic which in turn creates a magnetic field field which interacts with the secondary around the rotor. The rotating magnetic field side's electromagnetic field to produce a of the stator will impose an electromagnetic resultant torque, thereby transforming the torque on the still magnetic field of the rotor electrical energy into mechanical energy. causing it to move (about a shaft) and Induction motors are widely used, especially rotation of the rotor is produced. It is called synchronous because at steady state the 2 . speed of the rotor is the same as the speed of the rotating magnetic field in the stator. By way of contrast, the induction motor currents will be induced. If by some chance does not have any direct supply onto the this happens, the rotor typically slows rotor; instead, a secondary current is induced slightly until a current is re-induced and then in the rotor. To achieve this, stator windings the rotor continues as before. This difference are arranged around the rotor so that when between the speed of the rotor and speed of energized with a polyphase supply they the rotating magnetic field in the stator is create a rotating magnetic field pattern called slip. It is unitless and is the ratio which sweeps past the rotor. This changing between the relative speed of the magnetic magnetic field pattern induces current in the field as seen by the rotor (the slip speed) to rotor conductors. These currents interact the speed of the rotating stator field. Due to with the rotating magnetic field created by this an induction motor is sometimes the stator and in effect cause a rotational referred to as an asynchronous machine. motion on the rotor. However, for these currents to be induced, the speed of the physical rotor must be less than the speed of Construction The stator consists of wound 'poles' that the rotating magnetic field in the stator, or carry the supply current to induce a else the magnetic field will not be moving magnetic field that penetrates the rotor. In a relative to the rotor conductors and no very simple motor, there would be a single 2 . projecting piece of the stator (a salient pole) motors have three salient poles per pole for each pole, with windings around it; in number, so a four-pole motor would have fact, to optimize the distribution of the twelve salient poles. This allows the motor magnetic field, the windings are distributed to produce a rotating field, allowing the in many slots located around the stator, but motor to start with no extra equipment and the magnetic field still has the same number run more efficiently than a similar single- of north-south alternations. The number of phase motor. 'poles' can vary between motor types but the poles are always in pairs (i.e. 2, 4, 6, etc.). Types of rotors There are three types of rotor: Induction motors are most commonly built Squirrel-cage rotor to run on single-phase or three-phase power, The most common rotor is a squirrel-cage but two-phase motors also exist. In theory, rotor. It is made up of bars of either solid two-phase and more than three phase copper (most common) or aluminum that induction motors are possible; many single- span the length of the rotor, and those solid phase motors having two windings and copper or aluminum strips can be shorted or requiring a capacitor can actually be viewed connected by a ring or sometimes not, i.e. as two-phase motors, since the capacitor the rotor can be closed or semi closed type. generates a second power phase 90 degrees The rotor bars in squirrel-cage induction from the single-phase supply and feeds it to motors are not straight, but have some skew a separate motor winding. Single-phase to reduce noise and harmonics. power is more widely available in residential buildings, but cannot produce a rotating Slip ring rotor field in the motor (the field merely oscillates A slip ring rotor replaces the bars of the back and forth), so single-phase induction squirrel-cage rotor with windings that are motors must incorporate some kind of connected to slip rings. When these slip starting mechanism to produce a rotating rings are shorted, the rotor behaves similarly field. They would, using the simplified to a squirrel-cage rotor; they can also be analogy of salient poles, have one salient connected to resistors to produce a high- pole per pole number; a four-pole motor resistance rotor circuit, which can be would have four salient poles. Three-phase beneficial in starting. 2 . Solid core rotor A rotor can be made from solid mild steel. Starting of induction motors Direct-on-line starting The simplest way to start a three-phase The induced current causes the rotation. induction motor is to connect its terminals to Speed control the line. This method is often called "direct The synchronous rotational speed of the on line" and abbreviated DOL. rotor (i.e. the theoretical unloaded speed induction motor, the magnitude of the with no slip) is controlled by the number of induced pole pairs (number of windings in the stator) proportional to the stator field and the slip and by the frequency of the supply voltage. speed of the motor, and the rotor current Under load, the induction motor's speed depends on this emf. When the motor is varies according to size of the load. As the started, the rotor speed is zero. The load is increased the speed of the motor synchronous speed is constant, based on the decreases increasing the slip which increases frequency of the supplied AC voltage. emf in the rotor In an circuit is the rotor's field strength to bear the extra load. So the slip speed is equal to the synchronous speed, the slip ratio is 1, and the induced Before the development of economical emf in the rotor is large. As a result, a very semiconductor power electronics, it was high current flows through the rotor. This is difficult to vary the frequency to the motor similar to a transformer with the secondary and induction motors were mainly used in coil short circuited, which causes the fixed speed applications. As an induction primary coil to draw a high current from the motor has no brushes and is easy to control, mains. When an induction motor starts many older DC motors are now being DOL, a very high current is drawn by the replaced and stator, in the order of 5 to 9 times the full industrial load current. This high current can, in some with accompanying induction inverters motors in applications. motors, damage the windings; in addition, because it causes heavy line voltage drop, other appliances connected to the same line may be affected by the voltage fluctuation. 3 . To avoid such effects, several other ii. strategies are employed for starting motors. Increased complexity, as more contactors and some sort of speed switch or timers are needed Wye-Delta starters An induction motor's windings can be iii. Two shocks to the motor (one for connected to a 3-phase AC line in two the initial start and another when different ways: the motor switches from wye to i. delta) wye in U.S, star in Europe, where the windings are connected from phases of the Variable-frequency drives Variable-frequency drives (VFD) can be of supply to the neutral; ii. delta (sometimes mesh in considerable use in starting as well as Europe), where the windings are running motors. A VFD can easily start a connected between phases of the motor at a lower frequency than the AC line, supply. as well as a lower voltage, so that the motor starts with full rated torque and with no A delta connection of the machine winding inrush of current. The rotor circuit's results in a higher voltage at each winding impedance increases with slip frequency, compared to a wye connection. A wye-delta which is equal to supply frequency for a starter initially connects the motor in wye, stationary rotor, so running at a lower which produces a lower starting current than frequency actually increases torque. delta, then switches to delta when the motor has reached a set speed. Disadvantages of this method over DOL Resistance starters This method is used with slip ring motors starting are: where the rotor poles can be accessed by i. Lower starting torque, which way of the slip rings. Using brushes, may be a serious issue with variable power resistors are connected in pumps or any devices with series with the poles. During start-up the significant breakaway torque resistance is large and then reduced to zero at full speed. At start-up the resistance 4 . directly reduces the rotor current and so rotation may be commenced by manually rotor heating is reduced. Another important giving a slight turn to the rotor. The single advantage is the start-up torque can be phase induction motor may rotate in either controlled. As well, the resistors generate a direction and it is only the starting circuit phase shift in the field resulting in the which determines rotational direction. magnetic force acting on the rotor having a favorable angle. For small motors of a few watts the start rotation is done by means of a single turn of heavy copper wire around one corner of the Series Reactor starters In series reactor starter technology, an pole. The current induced in the single turn impedance in the form of a reactor is is out of phase with the supply current and introduced motor so causes an out-of-phase component in the terminals, which as a result reduces the magnetic field, which imparts to the field motor terminal voltage resulting in a sufficient rotational character to start the reduction of the starting current; the motor. Starting torque is very low and impedance of the reactor, a function of the efficiency is also reduced. current passing through it, gradually reduces Such shaded-pole motors are typically used as the motor accelerates, and at 95 % speed in low-power applications with low or zero the reactors are bypassed by a suitable starting torque requirements, such as desk bypass method which enables the motor to fans and record players. Larger motors are run at full voltage and full speed. Air core provided with a second stator winding which series reactor starters or a series reactor soft is fed with an out-of-phase current to create starter and a rotating magnetic field. The out-of-phase recommended method for fixed speed motor current may be derived by feeding the starting. The applicable standards are [IEC winding through a capacitor, or it may 289] AND [IS 5553 (PART 3)]. derive from the winding having different is in the series most with the common values of inductance and resistance from the main winding. Single Phase induction motor In a single phase induction motor, it is In some designs the second winding is necessary to provide a starting circuit to start disconnected once the motor is up to speed, rotation of the rotor. If this is not done, 5 . usually either by means of a switch operated by centrifugal force acting on weights on the motor shaft, or by a positive temperature coefficient thermistor which after a few seconds of operation heats up and increases its resistance to a high value, reducing the current through the second winding to an Sine wave current in each of the coils insignificant level. Other designs keep the produces sine varying magnetic field on the second winding continuously energized rotation axis. Magnetic fields add as vectors. during running, which improves torque. Control of speed in induction motor can be obtained in 3 ways: 1. Scalar control 2. Vector control 3. Direct torque control Rotating magnetic field Vector sum of the magnetic field vectors of Description of magnetic field A symmetric rotating magnetic field can be the stator coils produces a single rotating produced with as few as three coils. The The result of adding three 120-degrees three coils will have to be driven by a phased sine waves on the axis of the motor symmetric 3-phase AC sine current system, is a single rotating vector. The rotor has a thus each phase will be shifted 120 degrees constant magnetic field. The N pole of the in phase from the others. For the purpose of rotor will move toward the S pole of the this example, the magnetic field is taken to magnetic field of the stator, and vice versa. be the linear function of the coil's current This magneto-mechanical attraction creates vector of resulting rotating magnetic field. a force which will drive rotor to follow the rotating magnetic field in a synchronous manner. 6 . A permanent magnet in such a field will phase system to create the rotating field rotate so as to maintain its alignment with utilized in electric motors is one of the main the external field. This effect was utilized in reasons why three phase systems dominate early alternating current electric motors. A in the world electric power supply systems. rotating magnetic field can be constructed Rotating magnetic fields are also used in using two orthogonal coils with a 90 degree induction motors. Because magnets degrade phase difference in their AC currents. with time, induction motors use short- However, in practice such a system would circuited rotors (instead of a magnet) which be follow the rotating magnetic field of a multi- supplied through a three-wire coiled stator. arrangement with unequal currents. This inequality would cause serious problems in In these motors, the short circuited turns of the standardization of the conductor size. the rotor develop eddy currents in the rotating field of stator which in turn move In order to overcome this, three-phase the rotor by Lorentz force. These types of systems are used where the three currents motors are not usually synchronous, but are equal in magnitude and have a 120 instead necessarily involve a degree of 'slip' degree phase difference. Three similar coils in order that the current may be produced having mutual geometrical angles of 120 due to the relative movement of the field and degrees will create the rotating magnetic the rotor. field in this case. The ability of the three 3-φmotor runs from 1-φ power, but does not start 7 . The single coil of a single phase induction reverse direction, it will develop a similar motor does not produce a rotating magnetic large torque as it nears the speed of the field, backward rotating phasor. Single phase but maximum a pulsating intensity at field 0o reaching and 180o induction motors have a copper or aluminum electrical. Another view is that the single squirrel cage embedded in a cylinder of steel coil excited by a single phase current laminations, typical of poly-phase induction produces two counter rotating magnetic field motors. phasors, coinciding twice per revolution at 0o and 180o. When the phasors rotate to 90o and -90o they cancel in figure b. At 45o and Permanent-split capacitor motor One way to solve the single phase problem -45o (figure c) they are partially additive is to build a 2-phase motor, deriving 2-phase along the +x axis and cancel along the y power from single phase. This requires a axis. An analogous situation exists in figure motor with two windings spaced apart 90o d. The sum of these two phasors is a phasor electrical, fed with two phases of current stationary in space, but alternating polarity displaced 90o in time. This is called a in time. Thus, no starting torque is permanent-split capacitor motor in Figure developed. below, However, if the rotor is rotated forward at a bit less than the synchronous speed, it will develop maximum torque at 10% slip with respect to the forward rotating phasor. Less torque will be developed above or below 10% slip. The rotor will see 200% - 10% Permanent-split capacitor induction motor. slip with respect to the counter rotating magnetic field phasor. Little torque (see This type of motor suffers increased current torque vs slip curve) other than a double magnitude and backward time shift as the freqency ripple is developed from the motor comes up to speed, with torque counter rotating phasor. Thus, the single pulsations at full speed. The solution is to phase coil will develop torque, once the keep the capacitor (impedance) small to rotor is started. If the rotor is started in the minimize losses. The losses are less than for 1 . a shaded pole 1/4 Capacitor-run induction motor A variation of the capacitor-start motor usually (Figure below) is to start the motor with a applied to smaller motors. The direction of relatively large capacitor for high starting the motor is easily reversed by switching the torque, but leave a smaller value capacitor in capacitor in series with the other winding. place after starting to improve running configuration horsepower motor. works (200watt), well This up motor to though, characteristics while not drawing excessive current. The additional complexity of the Capacitor-start induction motor In Figure below a larger capacitor may be capacitor-run motor is justified for larger size motors. used to start a single phase induction motor via the auxiliary winding if it is switched out by a centrifugal switch once the motor is up to speed. Moreover, the auxiliary winding may be many more turns of heavier wire than used in a resistance split-phase motor to mitigate excessive temperature rise. The result is that more starting torque is available for conditioning heavy loads compressors. like This air motor Capacitor-run motor induction motor configuration works so well that it is available in multi-horsepower A motor starting capacitor may be a double- (multi- anode non-polar electrolytic capacitor which kilowatt) sizes. could be two + to + (or - to -) series connected polarized electrolytic capacitors. Such AC rated electrolytic capacitors have such high losses that they can only be used for intermittent duty (1 second on, 60 seconds off) like motor starting. A capacitor for motor running must not be of electrolytic Capacitor-start induction motor. construction, but a lower loss polymer type. 2 . Resistance split-phase induction motor If an auxiliary winding of much fewer turns capacitor) arrangement serves well for of smaller wire is placed at 90o electrical to driving easily started loads. motors up to 1/3 horsepower (250 watts) the main winding, it can start a single phase induction motor. (Figure below) With lower This motor has more starting torque than a inductance and higher resistance, the current shaded pole motor (next section), but not as will experience less phase shift than the much as a two phase motor built from the main phase same parts. The current density in the difference may be obtained. This coil auxiliary winding is so high during starting produces a moderate starting torque, which that the consequent rapid temperature rise is disconnected by a centrifugal switch at precludes frequent restarting or slow starting winding. About 30o of loads. 3/4 of synchronous speed. This simple (no Resistance split-phase motor induction motor 3 . TOPIC FOUR THREE PHASE INDUCTION MOTOR Working Principle of Three Phase Induction Motor An electrical motor is such an electromechanical device which converts electrical energy into a mechanical energy. In case of three phase AC operation, most bars which fits in each slots & they are short widely used motor is Three phase induction circuited by the end rings. The slots are not motor as this type of motor does not require exactly made parallel to the axis of the shaft any starting device or we can say they are but are slotted a little skewed because this self starting induction motor. arrangement reduces magnetic humming For better understanding the principle of three phase noise & can avoid stalling of motor. induction motor, the basic constructional Production of Rotating Magnetic Field feature of this motor must be known to us. The stator of the motor consists of This Motor consists of two major parts: overlapping winding offset by an electrical Stator: Stator of three phase induction angle of 120°. When the primary winding or motor is made up of numbers of slots to the stator is connected to a 3 phase AC construct a 3 phase winding circuit which is source, it establishes a rotating magnetic connected to 3 phase AC source. The three field which rotates at the synchronous speed. phase winding are arranged in such a manner in the slots that they produce a Secrets behind the rotation: rotating magnetic field after AC is given to According to Faraday’s law an e.m.f them. induced in any circuit is due to the rate of change of magnetic flux linkage through the Rotor: Rotor of three phase induction circuit. As the rotor winding in an induction motor consists of cylindrical laminated core motor are either closed through an external with parallel slots that can carry conductors. resistance or directly shorted by end ring, Conductors are heavy copper or aluminum 1 . and cut the stator rotating magnetic field, an • Less armature reaction and brush sparking e.m.f is induced in the rotor copper bar and because of the absence of commutators and due to this e.m.f a current flows through the brushes that may cause sparks. rotor conductor. • Robust in construction. • Economical. Here the relative velocity between the • Easier to maintain. rotating flux and static rotor conductor is the cause of electric current generation; hence as What is the operating principle of a 3ph per Lenz's law the rotor will rotate in the induction motor? same direction to reduce the cause i.e. the An electric motor converts electrical energy relative velocity. into a mechanical energy which is then supplied to different types of loads. A.C. Thus from the working principle of three motors operate on an A.C. supply, and they phase induction motor it may observed that are classified into synchronous, single phase the rotor speed should not reach the and 3 phase induction, and special purpose synchronous speed produced by the stator. If motors. Out of all types, 3 phase induction the speeds equals, there would be no such motors are most widely used for industrial relative velocity, so no emf induction in the applications mainly because they do not rotor, & no current would be flowing, and require a starting device. therefore no torque would be generated. Consequently the rotor cannot reach at the A 3 phase induction motor derives its synchronous speed. The difference between name from the fact that the rotor current is the stator (synchronous speed) and rotor induced by the magnetic field, instead of speeds is called the slip. The rotation of the electrical magnetic field in an induction motor has the connections. The operating principle of a 3 phase induction motor is advantage that no electrical connections based on the production of rmf. need to be made to the rotor. Thus the three phase induction motor is: • Self-starting. 2 . speed, a term given to the speed at which the field produced by primary currents will rotate, is determined by the following expression. Synchronous speed of rotation = (120* supply frequency)/Number of poles on the stator. Production of magnetic flux A rotating magnetic field in the stator is the first part of operation. To produce a torque Production of a rotating magnetic field and thus rotate, the rotors must be carrying The stator of an induction motor consists of some current. In induction motors, this a number of overlapping windings offset by current comes from the rotor conductors. an electrical angle of 120°. When the The revolving magnetic field produced in primary winding or stator is connected to a the stator cuts across the conductive bars of three phase alternating current supply, it the rotor and induces an emf. The rotor establishes a rotating magnetic field which rotates at a synchronous speed. windings in an induction motor are either The closed through an external resistance or direction of rotation of the motor depends on directly shorted. Therefore, the emf induced the phase sequence of supply lines, and the in the rotor causes current to flow in a order in which these lines are connected to the stator. Thus interchanging direction opposite to that of the revolving the magnetic field in the stator, and leads to a connection of any two primary terminals to twisting motion or torque in the rotor. the supply will reverse the direction of rotation. As a consequence, the rotor speed will not reach the synchronous speed of the rmf in The number of poles and the frequency of the applied voltage determine the stator. If the speeds match, there would the be no emf induced in the rotor, no current synchronous speed of rotation in the motor’s would be flowing, and therefore no torque stator. Motors are commonly configured to would be generated. The difference between have 2, 4, 6 or 8 poles. The synchronous the stator (synchronous speed) and rotor 3 . speeds is called the slip. The rotation of the delayed in time by one third and two thirds magnetic field in an induction motor has the of one cycle of the electric current. This advantage that no electrical connections delay between phases causes an effect of need to be made to the rotor. giving constant power transfer over each cycle of the current and also makes it What results is a motor that is: Self-starting Explosion proofed (because of the possible to produce a rotating magnetic field in an electric motor. absence of slip rings or commutators The sum of the currents is always zero and and brushes that may cause sparks) each line returns the current from the other Robust in construction two. Thus a three-phase system can operate Inexpensive with Easier to maintain systems may also have a fourth wire, only particularly three in wires.[3] Three-phase low-voltage distribution, which is the neutral wire. The neutral allows three separate single-phase supplies to be provided at a constant voltage and is commonly used for supplying groups of domestic properties which are each singlephase loads. The connections are arranged so that as far as possible in each group equal power is drawn from each phase. Further up the supply chain in high-voltage distribution Production of rotating magnetic field in a the currents are usually well balanced and it three phase induction motor is therefore normal to omit the neutral wire. In a three-phase system, three circuit Three-phase has properties that make it very conductors carry three alternating currents desirable in electric power systems: (of the same frequency) which reach their instantaneous peak values at one third of a The phase currents tend to cancel out one another, summing to zero in the cycle from each other. Taking one current as case of a linear balanced load. This the reference, the other two currents are makes it possible to reduce the size 4 . of the neutral conductor because it only as single phase. In lower-density areas, carries little to no current; all the only a single phase might be used for phase conductors carry the same distribution. current and so can be the same size, appliances may be powered by three-phase for a balanced load. power, such as electric stoves and clothes Power transfer into a linear balanced dryers. Some large European load is constant, which helps to reduce generator and Wiring for the three phases is typically motor identified by color codes which vary by vibrations. country. Connection of the phases in the Three-phase systems can produce a rotating specified magnetic direction field and with right order is required to ensure the intended a direction of rotation of three-phase motors. constant For example, pumps and fans may not work magnitude, which simplifies the in reverse. Maintaining the identity of design of electric motors. phases is required if there is any possibility Most household loads are single-phase. In two sources can be connected at the same North American residences, three-phase time; a direct interconnection between two power might feed a multiple-unit apartment different phases is a short-circuit. block, but the household loads are connected SPEED CONTROL OF THREE PHASE INDUCTION MOTOR A three phase induction motor is basically a constant speed motor so it’s somewhat difficult to control its speed. The speed control of induction motor is of three phase induction motor as the done at the cost of decrease in efficiency and methods of speed control depends upon low these formulas. Synchronous speed electrical power factor. Before discussing the methods to control the speed of three phase induction motor one should know the basic formulas of speed and torque 5 . Where f = frequency and P is the number of poles When rotor is at sand-still slip, s is one. So • The speed of induction motor is given by, the equation of torque is, Where N is the speed of rotor of induction motor, Ns is the synchronous speed, S is the Where E2 is the rotor emf slip. Ns is the synchronous speed • The torque produced by three phase R2 is the rotor resistance induction motor is given by, X2 is the rotor inductive reactance The Speed of Induction Motor is changed from Both Stator and Rotor Side The speed control of three phase induction Speed Control from Stator Side motor from stator side are further classified 1. V / f control or frequency control - as: Whenever three phase supply is given to 1. V / f control or frequency control three phase induction motor rotating 2. changing the number of stator poles magnetic field is produced which rotates at 3. controlling supply voltage synchronous speed given by 4. adding rheostat in the stator circuit The speed controls of three phase induction motor from rotor side are further classified In three phase induction motor emf is as: induced by induction similar to that of 1. Adding external resistance on rotor side transformer which is given by 2. Cascade control method 3. Injecting slip frequency emf into rotor side 2 . Where K is the winding constant, T is the compared to R2 . So, it can be neglected. So number of turns per phase and f is torque becomes; frequency. Now if we change frequency synchronous speed changes but with decrease in frequency flux will increase and this change in value of flux causes saturation Since rotor resistance, R2 is constant so the of rotor and stator cores which will further equation of torque further reduces to cause increase in no load current of the motor . So, its important to maintain flux, φ constant and it is only possible if we change voltage i.e if we decrease frequency flux We know that rotor induced emf E2 ∝ V. increases but at the same time if we decrease voltage flux will also decease causing no So, T ∝ sV2. change in flux and hence it remains constant. So, here we are keeping the ratio From the equation above it is clear that if we of V/ f as constant. Hence its name is V/ f decrease supply voltage torque will also method. For controlling the speed of three decrease. But for supplying the same load, phase induction motor by V/ f method we the torque must remains the same and it is have and only possible if we increase the slip and if frequency which is easily obtained by using the slip increases the motor will run at converter and inverter set. reduced speed . This method of speed to supply variable voltage control is rarely used because small change 2. Controlling supply voltage: The torque in speed requires large reduction in voltage, produced by running three phase induction and hence the current drawn by motor motor is given by; increases, which cause over heating of induction motor. 3. Changing the number of stator poles : The stator poles can be changed by two methods In low slip region (sX)2 is very very small as • Multiple stator winding method 2 . • Pole amplitude modulation wave P1 be the number of poles of induction method (PAM) motor whose speed is to be controlled P2 be the number of poles of modulation wave • Multiple stator winding method – In this method of speed control of three phase induction motor, the stator is provided by two separate winding . These two stator After modulation resultant mmf wave; windings are electrically isolated from each other and are wound for two different pole numbers. Using switching arrangement, at a time, supply is given to one winding only and hence speed control is possible. Disadvantages of this method are that the smooth speed control is not possible. This method is more costly and less efficient as So we get, resultant mmf wave two different stator winding are required. This method of speed control can only be applied for squirrel cage motor • Pole amplitude modulation method Therefore the resultant mmf wave will have (PAM) – two different number of poles In this method of speed control of three phase induction motor the original sinusoidal mmf wave is modulated by another sinusoidal mmf wave Therefore by changing the number of poles having we can easily change the speed of three different number of poles. phase induction motor 4. Adding rheostat in the stator circuit - In Let f1(θ) be the original mmf wave of this method of speed control of three phase induction motor whose speed is to be induction motor rheostat is added in the controlled f2(θ) be the modulation mmf 3 . stator circuit due to this voltage gets torque must remains constant. So, we dropped .In case of three phase induction increase slip, which will further results in motor torque produced is given by T ∝ sV22. decrease in rotor speed. Thus by adding If we decrease supply voltage torque will additional resistance in rotor circuit we can also decrease. But for supplying the same decrease the speed of three phase induction load , the torque must remains the same and motor. it is only possible if we increase the slip and The main advantage of this method is that if the slip increase motor will run reduced with addition of external resistance starting speed. torque increases but this method of speed control of three phase induction motor also Speed Control from Rotor Side suffers from some disadvantages: 1. Adding external resistance on rotor side – In this method of speed control of .The speed above the normal value is not three phase induction motor external possible resistance are added on rotor side. The • Large speed change requires large value of equation of torque for three phase induction resistance and if such large value of motor is resistance is added in the circuit it will cause large copper loss and hence reduction in efficiency • Presence of resistance causes more losses The three phase induction motor operates in • This method cannot be used for squirrel low slip region .In low slip region term cage induction motor (sX)2 becomes very very small as compared 2. Cascade control method – In this to R2. So, it can be neglected . and also E2 is method of speed control of three phase constant. So the equation of torque after induction motor, the two three phase simplification becomes, induction motor are connected on common shaft and hence called cascaded motor. One motor is the called the main motor and another motor is called the auxiliary motor. Now if we increase rotor resistance, R2 The three phase supply is given to the stator torque decreases but to supply the same load 4 . of the main motor while the auxiliary motor is derived at a slip frequency from the slip ring of main motor. ; Let NS1 be the synchronous speed of main motor; NS2 be the synchronous speed of Now at no load , the speed of auxiliary rotor auxiliary motor; P1 be the number of poles is almost same as its synchronous speed i.e; of the main motor; P2 be the number of N = NS2 poles of the auxiliary motor; F is the supply frequency; F1 is the frequency of rotor induced emf of main motor N is the speed of set and it remains same for Now rearrange the above equation and find both the main and auxiliary motor as both out the value of N, we get, the motors are mounted on common shaft S1 is the slip of main motor; This cascaded set of two motors will now run at new speed having number of poles (P1 + P2). In the above method the torque The auxiliary motor is supplied with same produced by the main and auxiliary motor frequency as the main motor i.e will act in same direction, resulting in number of poles (P1 + P2). Such type of cascading is called cumulative cascading. There is one more type of cascading in which the torque produced by the main motor is in opposite direction to that of auxiliary motor. Such type of is called Now put the value of; differential cascading; resulting in speed corresponds to number of poles (P1 - P2).In this method of speed control of three phase 5 . induction motor, four different speeds can Therefore the efficiency of three phase be obtained; induction motor is reduced by this method of speed control. This slip power loss can be 1. when only main induction motor work, recovered and supplied back in order to having speed corresponds to improve the overall efficiency of three phase induction NS1 = 120 F / P1 motor and this scheme of recovering the power is called slip power 2. when only auxiliary induction motor recovery scheme and this is done by work, having speed corresponds to connecting an external source of emf of slip frequency to the rotor circuit. The injected NS2 = 120 F / P2 3. when cumulative cascading is done, then emf can either oppose the rotor induced emf the complete set runs at a speed of or aids the rotor induced emf. If it oppose the rotor induced emf, the total rotor N = 120F / (P1 + P2) resistance 4. when differential cascading is done, then increases and hence speed decreases and if the injected emf aids the the complete set runs at a speed of main rotor emf the total resistance decreases and hence speed increases. Therefore by N = 120F / (P1 - P2) injecting induced emf in rotor circuit the 3. Injecting slip frequency emf into rotor speed can be easily controlled. The main side - when the speed control of three phase advantage of this type of speed control of induction motor is done by adding resistance three phase induction motor is that wide in rotor circuit, some part of power called, range of speed control is possible whether the slip power is lost as I2R losses. its above normal or below normal speed. 6 . TOPIC FIVE MOTOR ENCLOSURES The enclosures of electrical motors are standardized by NEMA (National Electrical Manufacturers Association) as: 1. Open Drip Proof (ODP) 2. Totally Enclosed Fan Cooled (TEFC) An open motor in which the ventilating openings are so constructed that drops of A motor so enclosed as to prevent the free liquid or solid particles falling on it, at any exchange of air between the inside and angle not greater than 15 degrees for the outside of the case, but not sufficiently vertical, cannot enter either directly or by enclosed to be termed air-tight, and dust striking and running along a surface of the does not enter in sufficient quantity to motor. Designed for reasonably dry, clean, interfere and well ventilated (usually indoors) areas. Cooling is by means of an external fan as an Outdoor installations require the motor to be integral part of the motor. The fan provides protected with a cover that does not restrict cooling by blowing air on the outside of the the flow of air to the motor. Ventilation motor. Suitable where the motor is exposed openings in shield and/or frame prevent to dirt or dampness. Not suited in very moist drops of liquid from falling into motor humid or hazardous (explosive) locations. within up to 15 degree angle from vertical. Same as TENV with an external fan as an Designed for reasonably dry, clean, and well integral part of the motor. The fan provides ventilated (usually indoors) areas. Outdoors cooling by blowing air on the outside of the installation requires the motor. motor to be with satisfactory operation. protected with a cover that does not restrict 3. Totally Enclosed Non Ventilated the flow of air to the motor. (TENV) A motor so enclosed as to prevent the free exchange of air between the inside and outside of the case but not sufficiently 2 . enclosed to be termed air-tight, and dust 5. Totally Enclosed Blower Cooled does not enter in sufficient quantity to interfere with satisfactory (TEBC) operation. A motor so enclosed as to prevent the free Cooling is only by convection and radiation exchange of air between the inside and from the enclosure. Suitable where the outside of the case, but not sufficiently motor is exposed to dirt or dampness. Not enclosed to be termed air-tight, and dust suited in very moist humid or hazardous (explosive) locations. No does not enter in sufficient quantity to ventilation interfere with satisfactory operation. Used openings, enclosed to prevent free exchange on inverter duty motors. Cooled with of air (not airtight). No external cooling fan, external fan on a power supply independent relies on convection cooling. Suitable where of the inverter output. Provides full cooling the motor is exposed to dirt or dampness. even at lower motor speeds. Not suited in very moist humid or hazardous (explosive) air. 6. Explosion Proof 4. Totally Enclosed Air Over (TEAO) A totally enclosed motor whose enclosure is A motor so enclosed as to prevent the free designed and constructed to withstand an exchange of air between the inside and explosion of a specified gas or vapor which outside of the case. A dust-tight enclosure may occur within it and to prevent the used on fan and blower motors for shaft ignition of the specified gas or vapor mounted fans or belt driven fans. The motor surrounding the motor by sparks, flashes, or must be mounted within the airflow of the explosions of the gas or vapor which may fan for cooling. Dust-tight fan and blower occur within the motor housing. motors for shaft mounted fans or belt driven fans. The motors mounted within the airflow 7. Explosion-Proof Non Ventilated of the fan. (EPNV) A non-ventilated explosion proof motor. See TENV and Explosion-Proof above for more information. 2 . 8. Explosion-Proof Fan A fan cooled explosion-proof motor. See Cooled TEFC and Explosion- Proof above for more (EPFC) information. The motor ambient temperature shall not exceed +40oC. 3 . TOPIC SEVEN ELECTRIC MOTOR CONTROLS Once the proper motor is selected, understanding the many various control devices available and their uses and limitations becomes an important part related to reliable operation and protection of the motor and the personnel using the motor. There are four major motor control topics or categories to consider. Each of these has several subcategories and sometimes the subcategories overlap to some extent. Certain pieces of motor control equipment can accomplish multiple functions from each of the topics or categories. The four categories include: An understanding of each of these areas is 1) Starting the Motor necessary to effectively apply motor control Disconnecting Means principles and equipment to effectively Across the Line Starting operate and protect a motor. Reduced Voltage Starting Motor Starting All motors must have a control device to 2) Motor Protection Overcurrent Protection start and stop the motor called a “motor Overload Protection controller”. Other Protection (voltage, phase, etc) Environment 3) Stopping the Motor Coasting Electrical Braking Mechanical Braking 4) Motor Operational Control Speed Control Reversing Jogging Sequence Control 2 . a. Motor Controller A motor controller is the actual device that energizes and de-energizes the circuit to the motor so that it can start and stop. Motor controllers may include some or all of the following motor control functions: S starting, stopping, over-current protection, overload protection, changing, jogging, reversing, plugging, speed sequence control, and pilot light indication. S Controllers range from simple to complex and can provide control for one motor, groups of motors, or auxiliary equipment such as brakes, clutches, solenoids, heaters, or other signals. b. Motor Starter The starting mechanism that energizes the circuit to an induction motor is called the “starter” and must supply the motor with sufficient current to provide adequate starting torque under worst case line voltage and load conditions when the motor is energized. There are several different types of equipment suitable for use as “motor starters” but only two types of starting methods for induction motors: The above are some motor starters i) Across the Line Starting ii). Reduced Voltage Starting 2 . c. Across the Line Starting of Motors 1. Manual Motor Starters Across the Line starting connects the motor A manual motor starter is package windings/terminals directly to the circuit consisting of a horsepower rated switch with voltage “across the line” for a “full voltage one set of contacts for each phase and start”. This is the simplest method of starting corresponding thermal overload devices to a motor. Motors connected across the line provide motor overload protection. The are capable of drawing full in-rush current main advantage of a manual motor starter is and developing maximum starting torque to lower cost than a magnetic motor starter accelerate the load to speed in the shortest with equivalent motor protection but less possible time. motor control capability. Manual motor starters are often used for smaller motors horsepower - motors typically but the fractional National Electrical Code allows their use up to 10 Horsepower. Since the switch contacts All NEMA induction motors up to 200 remain closed if power is removed from the horsepower, and many larger ones, can circuit without operating the switch, the withstand full voltage starts. (The electric motor restarts when power is reapplied distribution system or processing operation which can be a safety concern. They do not may not though, even if the motor will). allow the use of remote control or auxiliary control equipment like a magnetic starter does. d. Across the Line Starters i) 2. Magnetic Motor Starters Manual Starter There are two different types of common A magnetic motor starter is a package “across the line” starters including: consisting of a contactor capable of opening 1. Manual Motor Starters and closing a set of contacts that energize 2. Magnetic Motor Starters and de-energize the circuit to the motor along with additional motor 3 . overload protection equipment. Magnetic be required when: The current in-rush form starters are used with larger motors (required the motor starting adversely affects the above 10 horsepower) or where greater voltage drop on the electrical system; motor control is desired. The main element needed to reduce the mechanical “starting of the magnetic motor starter is the shock” on drive-lines and equipment when contactor, a set of contacts operated by an the motor starts. Reducing the voltage electromagnetic coil. Energizing the coil reduces the current in-rush to the motor and causes the contacts (A) to close allowing also reduces the starting torque available large currents to be initiated and interrupted when the motor starts. by a smaller voltage control signal. All NEMA induction motors can accept The control voltage need not be the same as reduced voltage starting however it may not the motor supply voltage and is often low provide enough starting torque in some voltage allowing start/stop controls to be situations to drive certain specific loads. If located remotely from the power circuit. the driven load or the power distribution Closing the Start button contact energizes system cannot accept a full voltage start, the contactor coil. An auxiliary contact on some type of reduced voltage or "soft" the contactor is wired to seal in the coil starting scheme must be used. Typical circuit. The contactor de-energizes if the reduced voltage starter types include: control circuit is interrupted, the Stop button 1. Solid State (Electronic) Starters is operated, or if power is lost. The overload 2. Primary Resistance Starters contacts are arranged so an overload trip on 3. Autotransformer Starters any phase will cause the contactor to open 4. Part Winding Starters and de-energize all phases. 5. Wye-Delta Starters Reduced Voltage Starting of Motors Reduced voltage starters can only be used Reduced Voltage Starting connects the where low starting torque is acceptable or a motor windings/terminals at lower than means exists to remove the load from the normal line voltage during the initial starting motor or application before it is stopped. period to reduce the inrush current when the motor starts. Reduced voltage starting may 4 . Motor Protection Motor protection safeguards the motor, the fuses or circuit breakers. These devices supply system and personnel from various an extremely heavy overload occurs. Most operating conditions of the driven load, the overcurrent sources produce extremely large supply system or the motor itself. currents very quickly. operate when a short circuit, ground fault or ii. Overload Protection Overload protection is installed in the motor circuit and/or motor to protect the motor from damage from mechanical overload conditions when it is operating/running. The effect of an overload is an excessive rise in Motor protection categories include: temperature in the motor windings due to i. Overcurrent Protection ii. Overload Protection iii. Other Types of Protection. current higher than full load current. Properly overcurrent and protection supply when the heat generated in the motor motors and their conductors be protected both overload disconnects the motor from the power The National Electrical Code requires that from sized circuit or windings approaches a damaging overload level for any reason. conditions. The larger the overload, the more quickly i. Overcurrent Protection Overcurrent protection the temperature will increase to a point that interrupts the is damaging to the insulation and lubrication electrical circuit to the motor upon excessive of the motor. Unlike common instantaneous current demand on the supply system from type fuses and breakers, overload devices either short circuits or ground faults. are designed to allow high currents to flow Overcurrent protection is required to protect personnel, the motor branch briefly in the motor to allow for: circuit conductors, control equipment, and motor Typical motor starting currents of 6 to 8 times normal running from these high currents. Overcurrent current when starting. protection is usually provided in the form of 5 . Short duration overloads such voltage drops below a preset value. The as a slug of product going motor must be manually restarted upon through a system. resumption of normal supply voltage. If the motor inlets and outlets Low Voltage Release - Protection device are covered by a blanket of lint interrupts the circuit when the supply or if a bearing should begin to voltage drops below a preset value and re- lock, excessive heating of the establishes the circuit when the supply motor windings will “overload” voltage returns to normal. the motors insulation which ii. could damage the motor. Phase Failure Protection Interrupts the power in all phases of a threeThe overcurrent device will not react to this phase circuit upon failure of any one phase. low level overload. The motor overload Normal fusing and overload protection may device prevents this type of problem from not adequately protect a polyphase motor severely damaging the motor and also from damaging single phase operation. provides circuit Without this protection, the motor will conductors since it is rated for the same or continue to operate if one phase is lost. less current as the conductors. Overload Large currents can be developed in the protection trips when an overload exists for remaining stator circuits which eventually more than a short time. The time it takes for burn out. Phase failure protection is the only an overload to trip depends on the type of effective way to protect a motor properly overload device, length of time the overload from single phasing. protection for the exists, and the ambient temperature in which iii. the overloads are located. Phase Reversal Protection Used where running a motor backwards (opposite direction from normal) would Other Motor Protection Devices i. Low Voltage Protection cause operational or safety problems. Most three phase motors will run the opposite Low Voltage Disconnects - Protection direction by switching the connections of device operates to disconnect the motor any two of the three phases. The device when the supply interrupts the power to the motor upon 6 . detection of a phase reversal in the three- iv. Ground Fault Protection phase supply circuit. This type of protection Operates when one phase of a motor shorts is used in applications like elevators where it to ground preventing high currents from would be damaging or dangerous for the damaging the stator windings and the iron motor to inadvertently run in reverse. core. 7 . 1 . TOPIC EIGHT: CONTACTORS CONTACTORS A contactor is an electrically controlled switch used for switching a power circuit, similar to a relay except with higher current ratings. A contactor is controlled by a circuit which has a much lower power level than the switched circuit . interrupt a short circuit current. Contactors range from those having a breaking current of several amperes to thousands of amperes and 24 V DC to many kilovolts. The physical size of contactors ranges from a device small enough to pick up with one hand, to large devices approximately a meter (yard) on a side. Contactors are used to control electric motors, lighting, heating, capacitor banks, thermal evaporators, and other electrical loads. A contactor has three components. The contacts are the current carrying part of the contactor. This includes power contacts, auxiliary contacts, and contact springs. The electromagnet (or "coil") provides the driving force to close the contacts. The enclosure is a frame housing the contact and the electromagnet. Enclosures are made of Some contactors insulating materials like Bakelite, Nylon 6, Contactors come in many forms with and thermosetting plastics to protect and varying capacities and features. Unlike a insulate the contacts and to provide some circuit breaker, a contactor is not intended to measure of protection against personnel 2 . touching the contacts. Open-frame A basic contactor will have a coil input contactors may have a further enclosure to (which may be driven by either an AC or protect against dust, oil, explosion hazards DC supply depending on the contactor and weather. design). The coil may be energized at the same voltage as a motor the contactor is Magnetic blowouts use blowout coils to controlling, or may be separately controlled lengthen and move the electric arc. These with a lower coil voltage better suited to are especially useful in DC power circuits. control by programmable controllers and AC arcs have periods of low current, during lower-voltage which the arc can be extinguished with pilot devices. Certain contactors have series coils connected in the relative ease, but DC arcs have continuous motor circuit; these are used, for example, high current, so blowing them out requires for automatic acceleration control, where the the arc to be stretched further than an AC next stage of resistance is not cut out until arc of the same current. The magnetic the motor current has dropped. blowouts in the pictured Albright contactor (which is designed for DC currents) more Applications of Contactors than double the current it can break, 1. Lighting control increasing it from 600 A to 1,500 A. Contactors are often used to provide central Sometimes an economizer circuit is also control of large lighting installations, such installed to reduce the power required to as an office building or retail building. To keep a contactor closed; an auxiliary contact reduce power consumption in the contactor reduces coil current after the contactor coils, latching contactors are used, which closes. A somewhat greater amount of have power is required to initially close a two operating coils. One coil, momentarily energized, closes the power contactor than is required to keep it closed. circuit Such a circuit can save a substantial amount contacts, which are then mechanically held closed; the second coil of power and allow the energized coil to stay opens the contacts. cooler. Economizer circuits are nearly always applied on direct-current contactor coils and on large alternating current contactor coils. 2 . How Contactor Controls an Electric Motor 2. Magnetic starter A magnetic starter is a device designed to provide power to electric motors. It includes a contactor as an essential component, while also providing power-cutoff, under-voltage, and overload protection. 3. Vacuum contactor Vacuum contactors utilize vacuum bottle Control of electric motor with contactor encapsulated contacts to suppress the arc. This arc suppression allows the contacts to When a relay is used to switch a large be much smaller and use less space than air amount of electrical power through its break contacts at higher currents. As the contacts, it is designated by a special name: contacts contactor. are encapsulated, vacuum Contactors typically have contactors are used fairly extensively in multiple contacts, and those contacts are dirty applications, such as mining. Vacuum usually (but not always) normally-open, so contactors are only applicable for use in AC that power to the load is shut off when the systems. coil is de-energized. Perhaps the most common industrial use for contactors is the control of electric motors. The AC arc generated upon opening of the contacts will self-extinguish at the zero- The top three contacts switch the respective crossing of the current waveform, with the phases of the incoming 3-phase AC power, vacuum preventing a re-strike of the arc typically at least 480 Volts for motors 1 across the open contacts. Vacuum contactors horsepower or greater. The lowest contact is are therefore very efficient at disrupting the an “auxiliary” contact which has a current energy of an electric arc and are used when rating much lower than that of the large relatively fast switching is required, as the motor power contacts, but is actuated by the maximum break time is determined by the same armature as the power contacts. The periodicity of the AC waveform. auxiliary contact is often used in a relay logic circuit, or for some other part of the 3 . motor control scheme, typically switching and directly break the circuit as a fuse is 120 Volt AC power instead of the motor designed to do. voltage. Rather, overload heaters are designed to One contactor may have several auxiliary thermally mimic the heating characteristic of contacts, either normally-open or normally- the particular electric motor to be protected. closed, if required. The three “opposed- All motors have thermal characteristics, question-mark” shaped devices in series including the amount of heat energy with each phase going to the motor are generated by resistive dissipation (I2R), the called overload heaters. Each “heater” thermal transfer characteristics of heat element is a low-resistance strip of metal “conducted” to the cooling medium through intended to heat up as the motor draws the metal frame of the motor, the physical current. If the temperature of any of these mass and specific heat of the materials heater elements reaches a critical point constituting the motor, etc. (equivalent to a moderate overloading of the These characteristics are mimicked by the motor), a normally-closed switch contact overload heater on a miniature scale: when (not shown in the diagram) will spring open. the motor heats up toward its critical This normally-closed contact is usually temperature, so will the heater toward its connected in series with the relay coil, so that when it opens the relay critical temperature, ideally at the same rate will and approach curve. Thus, the overload automatically de-energize, thereby shutting contact, in sensing heater temperature with a off power to the motor. thermo-mechanical mechanism, will sense Overload heaters are intended to provide an analogue of the real motor. If the overcurrent protection for large electric overload contact trips due to excessive motors, unlike circuit breakers and fuses heater temperature, it will be an indication which of that the real motor has reached its critical providing overcurrent protection for power temperature (or, would have done so in a conductors. Overload heater function is short while). After tripping, the heaters are often misunderstood. They are not fuses; supposed to cool down at the same rate and that is, it is not their function to burn open approach curve as the real motor, so that serve the primary purpose they indicate an accurate proportion of the 4 . motor’s thermal condition, and will not provide information on the appropriate allow power to be re-applied until the motor heater units to use. is truly ready for start-up again. A white pushbutton located between the Shown here below is a contactor for a three- “T1″ and “T2″ line heaters serves as a way phase electric motor, installed on a panel as to manually re-set the normally-closed part of an electrical control system at a switch contact back to its normal state after municipal water treatment plant. Three- having been tripped by excessive heater phase, 480 volt AC power comes in to the temperature. three normally-open contacts at the top of “overload” switch contact may be seen at the contactor via screw terminals labeled the lower-right of the photograph, near a “L1,” “L2,” and “L3″ (The “L2″ terminal is label reading “NC” (normally-closed). On hidden behind a square-shaped “snubber” this particular overload unit, a small circuit connected across the contactor’s coil “window” with the label “Tripped” indicates terminals). Power to the motor exits the a tripped condition by means of a colored overload heater assembly at the bottom of flag. In this photograph, there is no this device via screw terminals labeled “T1,” “tripped” “T2,” and “T3.” appears clear Wire condition, connections and the to the indicator The overload heater units themselves are black, square-shaped blocks with the label “W34,” indicating a particular thermal response for a certain horsepower and temperature rating of electric motor. If an electric motor of differing power and/or temperature ratings were to be substituted for the one presently in service, the overload heater units would have to be replaced with units having a thermal response suitable for Contactor for a three-phase electric motor the new motor. The motor manufacturer can installed on a panel as part of an electrical control system 5 . TOPIC FOUR PREVENTIVE MAINTENANCE WHY PREVENTIVE MAINTENANCE? Preventive maintenance is predetermined work performed to a schedule with the aim of preventing the wear and tear or sudden failure of equipment components. Preventive maintenance helps to: function following elements: Protect assets and prolong the should incorporate the useful life of production equipment Improve system reliability 1. Planned replacements Decrease cost of replacement Planned replacements of components Decreases system downtime designed around the following: Reduce injury Reliability of components (equipment failure is caused by its Mechanical, process or least reliable component) control equipment failure can have adverse - check manufacturer’s information results in both human and economic - check the costs involved to repair and/or equipment parts industry best practices terms. In addition to down time and replace accepted Maintaining equipment service records or components, there is the risk of injury Scheduling replacement of to operators, and of acute exposures to components at the end of their chemical and/ or physical agents. useful service life Preventive maintenance, therefore, is a Acquiring and maintaining inventories of: very important ongoing accident prevention - east reliable components activity, which you should integrate - critical components into - components your manufacturing operations/ process. product To replacements be effective, your preventive maintenance 1 scheduled for . Replacing service-prone equipment Preventive Maintenance with more reliable performers Identifying Maintenance Hazards By introducing the element of planning The into your maintenance function, you maintenance are likely to reduce your repair and classified as follows: manpower requirements. Safety Hazards maintenance is plant can Mechanical Electrical requirements Pneumatic Hydraulic Thermal specifications of equipment Combustion Past experience with components: Falls - inspection records slippery floors - servicing records working at heights - replacement frequency Health Hazards - inspected component failures Chemical Agents Regularly scheduled include: Operating and performing lubrication process chemicals program: - identify cleaning solvents lubrication points on unexpected equipment - - be live equipment Diagnostic measures to your activities with tools to anticipate and prevent breakdowns. analyze associated equipment 2. Exploratory maintenance Exploratory hazards reaction products colour code in order to identify dusts lubrication frequency other chemical agents consult manufacturer and accepted Physical Agents industry best practices to establish noise schedule vibration other 2 Ergonomic Hazards . Controlling Maintenance Hazards Ideally, the hazards likely to occur Biomechanical lifting, pushing, pulling during maintenance activities should (manual handling) be addressed in the stretching, ending (to reach planning stage. hard to access areas) Work/process design poorly designed tools Process Selection hard to access work locations Depending on the nature of the ill-fitting personal protective process, special precautions may be needed to equipment protect workers when disassembling and cleaning equipment. complex procedures Consider this factor when you make a decision to select one process over Many of these hazards are interrelated. another. Also consider the following Examine your process, the layout of factors which contribute to the level of your process area, and the process risk of your maintenance activities: equipment used, to determine the exact How easy temporary structures nature of the hazards likely to be are to erect encountered during your maintenance How easy they are to access activities. For example, maintenance Support and reassembly of work carried out in confined spaces components carries a greater risk of critical injuries associated agents. with These risks equipment large scale equipment and acute exposures to chemical and physical of Use of hoists and mobile are working platforms and Safe use of ladders especially materials in the space itself and from near live electrical equipment nearby operations. Fatalities are quite How common. much disassembly is required to access affected equipment Need for temporary hoisting equipment 3 . Need for personal protective equipment A clear, step-by-step procedure, in checklist Housekeeping hazards created form, for controlling hazardous energy: at floor level by the presence of 1. Preparing for shutdown dismantled components 2. Shutting down machine, process or equipment Equipment Selection 3. Isolating energy to the machine, The process you select will determine process or equipment the type of equipment you will be 4. Applying lockout devices using. 5. Controlling stored energy However, consider the following: 6. Verification of isolation Reliability: 7. Release from lockout control manufacturer’s data Hazards identification in-plant operating experience Selection and specification of personal trade association data Ease of access to serviceable parts appropriate for the hazard Ease of disassembly proper fit Complexity of repair procedures Ease of frequency of required be used: lubrication right tool for the job Manufacturer/supplier follow-up: in good condition availability of parts appropriate for the environment protective equipment: (non-sparking tools in flammable availability of service time atmospheres) Developing Procedures ergonomic design When servicing equipment, hazards not related to your process operation reason, it is important to prepare servicing procedures Step-by-step procedure for disassembly are likely to be introduced. For this written Selection and specification of tools to Step-by-step checklist for inspection of components (to establish a baseline for that reliability) include the following: 4 . Identification of hazards associated with sub-procedures: Training entering and working in confined Maintenance are often involved in a complex and changing spaces welding in open and confined set of problems. Therefore, they need more thorough training in accident spaces personnel removing insulation prevention cleaning Serious consequences to maintenance handling and using solvents and other workers can result from not erecting temporary structures following using portable equipment procedures (e.g., use of work permits, using ladders lockout procedures, confined space abrasive blasting entry procedures). Ensure that your painting maintenance personnel are well trained Erection scaffolding and disassembly and other than regular established workers. maintenance in, and can demonstrate that they of understand, all relevant procedures. temporary platforms Also provide training in: Disassembly of small-scale equipment Hazard identification Reassembly of small-scale equipment Selection, Support and disassembly of large scale equipment, machine tools, personal equipment protective clothing/equipment, etc., use, and care of required to be used Examine each procedure thoroughly to First-aid and life-saving techniques ensure that the least hazardous method The hazards of and control is selected, and that all precautions methods for substances which may necessary to complete the job safely be encountered in the workplace, are taken. Keep records of all your such as: maintenance activities, indicating the irritating, toxic or corrosive dusts machine(s) gases involved, the part(s) involved, type of maintenance and date vapours on which performed. fluids 5 . How to inspect chains, blocks, fall needed. Train equipment operators to protection devices and ropes recognize the signs of impending How to secure loads failure, Understanding stresses excessive such as abnormal vibration, noise, declining or abnormal output, and to report these immediately to their supervisor. It is a good practice to call the maintenance crew together at the start of each job, in order to discuss the Legislation hazards involved and the method of The following Regulations made under doing it safely. In the course of their the Occupational Health and Safety daily Act contain provisions that deal with work, members of the maintenance: maintenance crew travel throughout the plant, becoming familiar with selected and trained, they can do much identify and correct staff responsible for may also and maintaining portable power tools, of Exposure to (R.R.O. 833/90) be inspecting Control Biological or Chemical Agents unsafe conditions. In small companies, the maintenance Establishments (R.R.O. 851/90) every machine and process. If properly to Industrial Workplace Hazardous Materials Information System (R.R.O. 860/90) extension cords, and the like. If so, special procedures and training are 6 Designated Substances