9.4 Lightning and surge protection retrofitting for sewage plants Resources of drinking water running short require a more efficient treatment. Therefore, sewage plants play a central role in the circle of drinking water. The necessary high efficiency of sewage plants (Figure 9.4.1) requires the optimisation of the operating procedure at a simultaneous reduction of the running operating costs. For this purpose, considerable financial efforts were made for electronic measuring equipment and decentralised electronic control and automation systems in recent years. Compared to conventional technology, however, the new electronic systems provide only a low resistance against transient surges. The structural conditions of the spacious open-air plants with wastewater treatment technology and the spread measuring devices and controls increase additionally the risk of interferences due to lightning discharges or surges. Thus, a failure of the complete process control system or parts of it, is highly probable to expect, if no protective measures are taken. The consequences of such a failure can be far-reaching. They can reach from the costs for the recovery of the system function to the undefinable costs for the removal of ground water contamination. In order to come up to this threat effectively and increase the availability of the systems, external and internal lightning protection must be provided. Lightning protection zones concept In order to obtain the best technical and economical protection, the sewage plant control is divided into lightning protection zones (LPZ). Subsequently, a risk analysis is carried out for each LPZ and for the relevant types of damage. For the risk analysis acc. to IEC 62305-2 the software tool DEHNsupport can be used. Lastly, the mutual dependences of the LPZs are examined and the finally required protection measures are defined in order to reach the necessary protection aim in all lightning protection zones. The following areas were assigned lightning protection zone LPZ 1 and lightning protection zone LPZ 2: ⇒ Electronic evaluation system in the control room (LPZ 2) pumping draw works rough / fine rake rain overflow basin ventilation / sand /fat catcher black water basin sewage plant control primary sedimentation tank precipitant tank sedimentation tank outlet activated sludge basin nitrification – denitrification Fig. 9.4.1 Schematic structure of a sewage plant 244 LIGHTNING PROTECTION GUIDE www.dehn.de sewage plant control 230 V DG MOD 275 DEHNguard DG MOD 275 N DEHNguard L PE measuring point 1’ 3’ 1’ 3’ 1’ 3’ 1’ 3’ 1’ 3’ protected protected protected protected 2’ 2’ 2’ 4’ 2’ BXT ML4 BE 24 4’ BXT ML4 BE 24 2’ BLITZDUCTOR BXT ML4 BE 24 BLITZDUCTOR 4’ BLITZDUCTOR 4’ BXT ML4 BD EX 24 BLITZDUCTOR 4’ BXT ML4 BE 24 BLITZDUCTOR protected 2 4 2 4 2 4 2 4 2 4 1 3 1 3 1 3 1 3 1 3 MCS O2-value Fig. 9.4.2 Division of a sewage plant control into lightning protection zones ⇒ Oxygen measurement in the aeration tank (LPZ 1) ⇒ Interior of the control room (LPZ 1) According to the lightning protection zones concept of IEC 62305-4 (EN 62305-4), all conductors at the LPZ boundaries must be provided with appropriate protective measures against surges, (Figure 9.4.2). Risk assessment for the sewage plant control The following example was calculated by using IEC 62305-2 (EN 62305-2). It should be pointed out that the procedure is only described as an example. The solution presented is in no way binding and can be replaced by any other equivalent solutions. The following states only the essential characteristics of the example. First, a questionnaire with relevant questions on the structure and its utilisation was discussed with the operator and fixed in writing. This proceeding ensures the elaboration of a lightning protection concept that is comprehensible for all parties involved. This concept represents then the minimum requirements, which, however, can still be technically improved anytime. www.dehn.de Site description The complete process control of the sewage plant is situated centrally in the sewage plant control. Characterised by the extended cable connections to the measuring stations as well as substations, considerable partial lightning currents and surges are imported by these lines into the control rooms at a lightning strike. In the past, this resulted again and again in destruction of the installation and system failures. The same applies to the power supply line and the telephone line (Figure 9.4.3). The sewage plant control itself shall be protected against damage by fire (direct lightning strike), and the electric and electronic systems (control and automation system, telecontrol) against the effects of lightning electromagnetic pulses (LEMP). Additional conditions ⇒ Protective measures against effects of lightning actually are already existing (external lightning protection, surge protective devices (SPD), (previously class B), type VGA 280/4 at the service entrance of the 230/400 V power supply line, SPD, (previously class C) type LIGHTNING PROTECTION GUIDE 245 fixed telecommunication network 230 / 400 V power supply sewage plant control O2 value 1’ L 3’ measuring point N protected 4 3 DG MOD 275 DEHNguard DG MOD 275 BXT ML4 BE 24 2 1 DEHNguard 4’ BLITZDUCTOR 2’ PE 230 V supply 4 - 20 mA Fig. 9.4.3 Electrical lines going into the sewage plant control VM 280 in the switchgear cabinets of the measuring and control system). (this is the same result as stated in VdS publication 2010) ⇒ The following types of damage are relevant: L2 for loss of services (water supply and water disposal) and L4 for economic losses (buildings or structures and their contents). Type of damage L1 (loss of human life) was excluded, since the installation should run fully automatically in future operation. ⇒ Installation of SPDs Type 1 according to EN 61643-11 (power supply) and SPDs, category D1 according to IEC 61643-21 for the data processing lines (data lines of the measuring and control system and telecommunication lines) The result after calculating the actual state is that the calculated risk R for L2 for loss of service is still well above the tolerable risk RT . Now, possible protective measures are initiated in order to obtain R < RT whereas with respect to L4 loss of economic values the most cost effective solution has to be selected: ⇒ Installation of a lightning protection system Class III according to IEC 62305-3 (EN 62305-3) 246 LIGHTNING PROTECTION GUIDE ⇒ SPD Type 2 according to EN 61643-11 (power supply) and surge protective devices, category C2 according to IEC 61643-21 for the data processing lines (data lines of the measuring and control system and telecommunication lines) Lightning protection system The existing lightning protection system of the sewage plant control was upgraded in accordance with the requirements of lightning protection systems Class III (Figure 9.4.4). The existing, indirect connection of the structures mounted on the roof (air conditioning systems) via isolating spark gaps www.dehn.de αϒ 80 70 60 50 Class of LPS 40 30 I 20 II III IV 10 0 0 2 10 20 30 40 50 60 h[m] room, no more partial lightning current can flow into the structure and cause damage. Due to the size of the control room (15 m x 12 m), the number of down conductors (4) did not have to be changed. The local earthing system of the sewage plant control was checked at all measuring points and the values were recorded. Also, no upgrades had to be made here. Lightning equipotential bonding for all cables entering from the outside In principle, all conductive systems entering the sewage plant from the outside must be integrated into the lightning equipotential bonding (Figure 9.4.5) The requirements of lightning equipotential bonding are fulfilled by direct connection of all Fig. 9.4.4 Protective angle method according to IEC 62305-3 (EN 62305-3) was removed. The protection against direct lightning strikes was realised by means of air-termination rods in compliance with requested separation distances and protective angles. Consequently, in the case of a direct lightning strike into the control lightning equipotential bonding external lightning protection system EBB power supply water gas Z cathodic protected tank pipe foundation earth electrode Fig. 9.4.5 Lightning equipotential bonding according to IEC 62305-3 (EN 62305-3) www.dehn.de LIGHTNING PROTECTION GUIDE 247 do not have to be expected, even at a failure. For the application of surge protective devices, the cross section of the earth conductor for equipotential bonding must be minimum 6 mm2 Cu for SPDs for power supply systems, and minimum 4 mm2 Cu for SPDs for information technology. Moreover, in areas with potentially explosive atmospheres the connections of the equipotential bonding conductors must be secured at e.g. equipotential bonding bars against self-loosening (e.g. by means of spring washers). Fig. 9.4.6 DEHNventil installed into a switchgear cabinet for protection of the power supply system metal systems and indirect connection of live systems via surge protective devices. The SPD Type 1 (power supply system) and the SPD Type D1 (information technology) must have a lightning current discharge capability of test waveform 10/350 μs. The lightning equipotential bonding shall preferably be installed near the entrance into the building or structure in order to prevent a penetration of lightning currents into the inside of the building. Equipotential bonding In the entire sewage plant control, a consistent equipotential bonding is carried out according to IEC 60364-4-41 and IEC 60364-5-54. The already existing equipotential bonding is tested to avoid potential differences between different as well as extraneous conductive parts. Also, supporting parts of the building and parts of the construction, pipelines, containers, etc., are included in the equipotential bonding, so that voltage differences 248 LIGHTNING PROTECTION GUIDE Surge protection for the low-voltage power supply In the described application, the SPD type VGA 280/4 installed at the service entrance of the building is replaced by an SPD Type 1 DEHNventil M TNS 255 (Figure 9.4.6), since the “old” SPD does no more comply with the requirements for lightning protection systems according to IEC 62305-3 (EN 62305-3). The SPDs Type 2, (previously class C), Type VM 280, were tested with an arrester test unit, type PM 10. Since the test values were still within the tolerances, there was no reason to remove the SPDs. If further SPDs are installed for protection of the terminal equipment as in the present case, they must be coordinated among each other and with the terminal equipment to be protected. The corresponding instructions given in the enclosed installation instructions must be observed. Otherwise, the use of surge protective devices in low voltage consumer's installations shows no peculiarities compared to other applications and has already been described many times (for more information, please also see publication DS649 E “Surge Protection – Easy Choice”). Surge protection in data processing systems From the protection point of view, the transfer interface of all data processing lines to the sewage plant is the service entrance. At this point SPDs (category D1) type DRL 10B 180 FSD are used, which are capable of carrying lightning currents. From the transfer interface, the cables are led directly to the switchgear cabinets and are connected there. In accordance with the performed risk analysis, the incoming cables must be led via SPDs, types DCO RK ME 24 (20 mA signal) or DCO RK MD 110 (telecontrol). These are suitable for use in the lightning protection zones concept (catego- www.dehn.de Fig. 9.4.7 DCO ME 24 surge protective device installed into a switchgear cabinet for protection of the complete measuring and control system Fig. 9.4.8 DCO ME 24 surge protection device installed into a switchgear cabinet, incoming lines from double bottom ry C2), and are system compatible (Figures 9.4.7 and 9.4.8). This ensures a complete surge protection concept for the data processing cabling. Additional applications for protection of sewage plants can be found in publication DS107 E. This can be downloaded from our website: www.dehn.de. www.dehn.de LIGHTNING PROTECTION GUIDE 249