Mtr3In Standard Control Module Library

advertisement
Mtr3In
On/off motor, three inputs,
maintained or pulsed outputs
Standard Control Module Library
The Mtr3In control module is designed for an on/off motor with
three inputs (feedback), offers a choice of maintained or pulsed
outputs, and provides the following functionality:
CONTROL
MODULE
●
Setting a motor demand
●
Standard supervisory workstation interface
●
Standard software block
●
Status and alarm display
●
Operator faceplate
●
Engineer point display
●
Interlocks
The Mtr3In control module forms part of a library of software
function blocks designed to aid the implementation of motor
control. Associated with each control module is a custom-built
point fascia, an engineering point display and a graphical mimic
icon for the supervisory workstation.
Applications
The control module offers the functionality required to drive a
typical electric motor. It can be applied to motors, pumps, fans,
agitators, etc.
Supervisory Workstation
Icon
Faceplate
TW5_FP
I D M
Point parameter page
X
DBase: PAUL6
Stopped
Interlocked
Hardware Fault
Discrepancy
Fail To Start
Fail To Stop
RESET
A
M
Manual
demand
START
STOP
Mode
Type: Mtr3In
Method: Template
MOTOR01
MANUAL ALM
Description:
MOTOR01
MANUAL ALM
XISM
100
Block: PAUL21
Stopped
Mode
ModeAct
Manual
00000000
Running
Ready
Healthy
FALSE
FALSE
FALSE
AutoDmnd
FALSE
IntlockP
InlkValP
IntlockS
InlkValS
00000000
FALSE
00000000
FALSE
Claims
Acks
00000000
00000000
Param1
Param2
0.0000
0.0000
Demand
DscrpTmr
DscrpTim
PulseTmr
PulseTim
FALSE
0.0000
10.000
0.0000
5.0000
State
StateAct
Stopped
00000000
Hardware
00000000
Reset
FALSE
Availble
FALSE
Options^AuDmdTrk
Options^FrcPulse
Options^Avail1
Options^Avail2
Options^NtAvail1
Options^NtAvail2
FALSE
FALSE
TRUE
TRUE
FALSE
FALSE
Alarms
Software
EvalFail
Hardware
NotHlthy
NotReady
FlToStt
FlToStp
Combined
Pn. In UnAck
1 NO
NO
0 NO
NO
0 NO
NO
0 NO
NO
0 NO
NO
0 NO
NO
0 NO
NO
0 NO
NO
FALSE
Status^CDiscrep
FALSE
Status^AuDiscrp
FALSE
Status^Intlcked
FALSE
Status^Trvling
FALSE
Status^LastDmnd
Interlocked
Hardware Fault
Discrepancy
Fail To Start
Fail To Stop
RESET
A
M
START
STOP
FpltType
Position,
status and
alarms
Control Unit
Auto
demand
System Interface
Primary interlocks
Control Module Logic
Secondary interlocks
I/O
Demand
Feedback
abc
IA027126 Issue 1
Field
OUTLINE SPECIFICATION
I/O
Interlocks
Healthy
Maintained digital (Healthy/Not healthy))
Primary Interlocks
Up to eight maintained digital inputs
Running Input
Maintained digital (Running/Stopped)
Secondary Interlocks
Up to eight maintained digital inputs
Ready Input
Maintained digital (Ready/Not ready)
The interlock demands override the Automatic and Manual
demands, and a Primary Interlock overrides a Secondary.
Maintained Demand Outputs
Maintained digital (Start/ Stop)
Alarms
Hardware
Failure of associated I/O modules if required
Pulsed Demand Outputs
Start pulse
Stop pulse
Motor Position Unknown
Motor Not Healthy
Operating Modes
Motor Not Ready
Manual/Maintenance
Allows manual operation of the motor
Motor Failed to Start
Automatic
Allows automatic operation of the motor
Motor Failed to Stop
Mimic Icon
Notations
I D M
XISM
100
A
M
M (blue background)
I
D
Line 1/Line 2
Automatic mode selected
Manual mode selected
Maintenance
Interlock active
Motor in discrepancy alarm
Textual control module tag or description
Colours
Red
Green
Yellow
Faceplate
Valve Status
Mode
Displays Manual/Auto/Maint
TW5_FP
Derived Status
Displays Running/Stopped/Starting/Stopping
X
MOTOR01
MANUAL ALM
Stopped
Interlocked
Displayed when motor is in an interlock state
Hardware Fault
Displayed when motor has an I/O failure
Interlocked
Hardware Fault
Discrepancy
Fail To Start
Fail To Stop
Discrepancy
Displayed when motor has a discrepancy
alarm
Fail To Start
Displayed when motor fails to start
Fail To Stop
Displayed when motor fails to stop
EUROTHERM LIMITED
Grey
Flashing
Stopped
Running
Starting
Stopping
Not communicating
Flashing
Block alarm
RESET
A
M
START
STOP
http://www.eurotherm.co.uk
UK SALES OFFICE
Eurotherm Ltd
Faraday Close Durrington Worthing BN13 3PL United Kingdom
Sales and support: Tel. +44 (0)1903 205277 Fax +44 (0)1903 236465
Operator Interaction
Reset Button
Resets the latched alarm mode
A Button
Selects automatic mode
M Button
Selects manual mode
Start Button
Starts the motor in manual mode
Stop Button
Stops the motor in manual mode
abcdefghijklmn
© Copyright Eurotherm Limited 2000
All rights strictly reserved. No part of this document may be stored in a retrieval system, or any form or by any means without prior written permission from Eurotherm Limited.
Every effort has been taken to ensure the accuracy of this specification. However in order to maintain our technological lead we are continuously improving our products which
could, without notice, result in amendments or omissions to this specification. We cannot accept responsibility for damage, injury loss or expenses resulting therefrom.
Part No. HA083932U201 Issue 2
Printed in England 09.00