Contactless Power Supply System for Transmission Line Inspection Robots João Pedro Trindade Caxias Ferreira Dissertação para obtenção do Grau de Mestre em Engenharia Electrotécnica e de Computadores Júri Presidente: Prof. Paulo José da Costa Branco Orientador: Prof. José Fernando Alves da Silva Co-orientador: Prof. João Silva Sequeira Vogal: Prof. João Carlos Pires da Palma Outubro de 2010 5 Abstract The power lines have today an important role in the electric power grid. Transporting energy in the best conditions is a goal of all electricity companies in the world. The premise of this work is to develop an innovative power system for use in a robot, with a nominal power of 800 W. The main purpose of this robot is inspect the high voltage power lines. The purpose of the power supply system is to provide a stable DC voltage to the robot so that it is energetically self-sustaining. This is obtained from the magnetic energy surrounding a power line, using a current transformer, a system for monitoring the output voltage in conjunction with an internal control system of chain, and an AC / DC converter in full-wave bridge. When simulated, this method achieves the objectives of the project. The results prove a good regulation of output voltage and small disturbances in the power line. The yield of the circuit is highly dependent on the amplitude of the current line being above 90% for most of the amplitudes considered. i 5 Resumo As linhas de alta tensão têm nos dias de hoje um papel importante na rede de energia eléctrica. Fazer chegar a energia a todos nas melhores condições é uma das metas de todas as companhias de electricidade em todo o mundo. A premissa do presente trabalho visa desenvolver um sistema de alimentação inovador para ser usado num robô, com uma potência nominal de 800 W. A principal finalidade deste robô é vir a inspecionar as linhas eléctricas de média e alta tensão. O objectivo do sistema de alimentação é de proporcionar uma tensão DC estável ao robô para que este seja energicamente auto-sustentável. Esta é obtida a partir da energia magnética envolvente a uma linha de alta tensão, com recurso a um transformador de corrente, a um sistema de controlo da tensão de saída conjugado com um sistema de controlo interno de corrente, e a um conversor AC/DC em ponte de onda completa. Quando simulado, este método atinge os objectivos do projeto. Os resultados provam uma boa regulação da tensão de saída e pequenas perturbações na linha de alta tensão. O rendimento do circuito é altamente dependente da amplitude da linha actual sendo acima dos 90% para a maioria das amplitudes consideradas. ii 5 Acknowledgments I would like to express my heartfelt gratitude to my project coordinator, José Fernando. Silva, for his constant guidance and support through all this work. His insightful academic advice is very much appreciated. I was very fortunate to have worked with him over all these months. I would like to thanks my project co-ordinator, João Sequeira, for his implication to create a so attractive topic as a final thesis, and to do all the research that becomes it possible. My thanks are also extended to my fellow friends who along my studies I could exchange so long gratitude and good moments. With their support was not possible to get so far. I am deeply grateful to my parents and my brother, as all the other family members for their endless love, support, and encouragement in all my endeavours. Without their sacrifice and love, I could not reach so interesting and motivating course. iii Table of Contents 1 INTRODUCTION .............................................................................................................. 1 1.1 MOTIVATION ................................................................................................................... 3 1.2 OBJECTIVE ..................................................................................................................... 3 1.3 W ALKTHROUGH .............................................................................................................. 4 2 POWER SUPPLY CONFIGURATION ............................................................................. 5 2.1 CLAMP-ON TRANSFORMER (COT) ................................................................................... 6 2.2 CIRCUIT COMPONENTS SIZING ....................................................................................... 11 2.2.1 Full-Bridge inverter semiconductors characteristics ........................................... 11 2.2.2 DC output capacitor ............................................................................................ 12 2.2.3 AC input low pass 3 order filter ........................................................................ 14 2.2.4 Resonant second harmonic band-stop filter ....................................................... 16 2.3 RECTIFIER CONTROLLER ............................................................................................... 17 2.3.1 Full-Bridge inverter PWM generator ................................................................... 17 2.3.2 Control of the DC Output Voltage ....................................................................... 19 3 4 rd SIMULATIONS ............................................................................................................... 22 3.1 OUTPUT VOLTAGE IN STEADY STATE FOR DIFFERENT LINE CURRENTS .............................. 23 3.2 START UP TRANSIENT .................................................................................................... 24 3.2.1 Study of a initial current on the high voltage power line .......................... 24 3.2.2 Study of a initial current on the high voltage power line ........................ 25 3.3 CURRENT STEP RESPONSE ............................................................................................ 26 3.4 SECONDARY TRANSFORMER VOLTAGE IN STEADY STATE FOR DIFFERENT LINE CURRENTS . 27 3.5 PWM VOLTAGE AND 3 ORDER FILTER SIMULATION ....................................................... 27 3.6 TRANSFORMER PARAMETERS SIMULATION ...................................................................... 28 RD 3.6.1 Open-circuit test ................................................................................................. 28 3.6.2 Short-circuit test .................................................................................................. 29 3.7 PRIMARY TRANSFORMER VOLTAGE AND CURRENT WHEN HAPPENS A STEP ....................... 31 3.8 RESULTS DISCUSSION ................................................................................................... 31 3.9 MODEL EFFICIENCY ....................................................................................................... 32 CONCLUSIONS ............................................................................................................. 33 iv Table of Figures Figure 1 - RIOL virtual prototype model [2] ................................................................................... 2 Figure 2 - Power supply system model ......................................................................................... 6 Figure 3 - COT lateral cut to describe core magnetization ........................................................... 6 Figure 4 – COT upper view to describe secondary coil induction ................................................. 7 Figure 5 - Hysteresis loop curve .................................................................................................... 8 Figure 6 - Clamp-on current transformer equivalent circuit ........................................................... 8 rd Figure 7 – Low pass 3 order filter circuit ................................................................................... 14 rd Figure 8 - Bode diagram of AC input low pass 3 order filter ..................................................... 15 Figure 9 – Output filters solution ................................................................................................. 16 Figure 10 – Full-bridge inverter PWM generator ......................................................................... 19 Figure 11 - Ouput voltage control block diagram ........................................................................ 20 Figure 12 - Linear output voltage control block diagram ............................................................. 20 Figure 13 - Output voltage (upper graph) and current (lower graph) in stready state for 100 A ................................................................................................................................... 23 Figure 14 - Output voltage (upper graph) and current (lower graph) in stready state for 500 A ................................................................................................................................... 23 Figure 15 - Output voltage (upper graph) and current (lower graph) in stready state for 1000 A ................................................................................................................................. 24 Figure 16 - Start up transient load voltage (upper graph) and load current (lower graph) for 100 A................................................................................................................... 24 Figure 17 - Start up transient secondary transformer voltage (upper graph), PWM voltage (center graph) and secondary transformer current (lower graph) for 100 A ...... 25 Figure 18 - - Start up transient load voltage (upper graph) and load current (lower graph) for 1000 A................................................................................................................. 25 Figure 19 - Start up transient secondary transformer voltage (upper graph), PWM voltage (center graph) and secondary transformer current (lower graph) for 1000 A .... 26 Figure 20 - Load voltage (upper graph) and current start-up transient (lower graph) and response to AC line current from 100 A to 1000 A .............................................................. 26 Figure 21 - Secondary transformer voltage in steady state for 100 A ................................... 27 v Figure 22 - Secondary transformer voltage in steady state for 500 A ................................... 27 Figure 23 - PWM voltage ............................................................................................................. 28 Figure 24 - Secondary transformer voltage (upper graph) and current (lower graph) ...... 28 Figure 25 - Simulink/SimPowerSystems implementation of the open-circuit test ....................... 28 Figure 26 - Simulink/SimPowerSystems implementation of the open-circuit test ....................... 30 Figure 27 - Primary transformer voltage (upper graph) and current vi (lower graph) ........... 31 List of Tables Table 1 – Transformer characteristics ................................................................................................... 11 Table 2 – Input current amplitude simulation steps ............................................................................... 22 vii List of Acronyms IST Instituto Superior Técnico RIOL Robot Inspection Over Power Lines COT Clamp-on Transformer PVC Polyvinyl chloride dof Degrees of freedom MOSFET Metal Oxide Semiconductor Field Effect Transistor PWM Pulse Width Modulated PI Proportional integral controller DC Direct current AC Alternating current RMS Root mean square LiPo Lithium ion polymer viii List of Symbols Time variant Thévenin equivalent Transformer nominal power Current on the primary transformer side RMS value of Voltage on the primary transformer side RMS value of Current on the secondary transformer side RMS value of Voltage on the secondary transformer side RMS value of Transformer turns ratio Primary, secondary transformer winding losses Primary, secondary transformer inductances Transformer magnetizing inductance Transformer magnetizing resistance Primary transformer impedance Secondary transformer impedance Transformer power losses Instantaneous rectifier input power Instantaneous rectifier output power Arms transistors state functions MOSFET semiconductors of full-bridge Output filter capacitance Rectifier input voltage Rectifier input voltage average PWM wave period Output voltage (applied on the load) DC component of Peak voltage ripple Rectifier ouput current component (applied on the load) DC component of ix Current at robot input 3rd order filter components Thévenin equivalent resistor (seen from the transformer) Voltage difference between output voltage and reference one Product between efficiency and the power factor Rectifier DC gain Feedback gain Efficiency Ouput voltage error margin Damping factor Controller delay PI controller pole PI controller zero Model nominal frequency RMS voltage when secondary transformer has no load RMS current when secondary transformer has no load Power on the primary transformer under no load conditions RMS voltage when secondary transformer is short circuited RMS current when secondary transformer is short circuited Power on the secondary transformer when short circuited x Chapter 1 1 Introduction The electric power transportation system uses very high voltage overhead lines. For reliability, these lines must be structurally and electrically inspected to detect ageing and prevent short-circuits and other malfunctions. To ensure continuity of service, inspections must be carried out while the lines are energized using helicopters and expert workers and methods, besides the high costs and precision required. Costs can be lowered using dedicated autonomous robots. These robots need to gather power from the overhead high voltage lines to ensure high autonomy, not possible to achieve using the robot onboard batteries. This work aims at developing an energy harvesting system to use with a RIOL [1], for inspection of high voltage overhead power lines. The power supply operating principle is based on harvesting the magnetic energy around the power supply lines [3], by clamping a transformer around the line [6] to produce power enough for the robot. The robot described is a 5 degrees-of-freedom articulated multi-body with three claws used for cable grasping. The body structure is made mainly of PVC and link couplings of light metal alloys. The robot is able to overcome support towers and most of the obstacles arising in power lines, e.g. the spherical aviation markers. The energy harvesting transformers are to be mounted at the claws. 1 Figure 1 - RIOL virtual prototype model [2] Two types of locomotion gaits are used. In absence of obstacles the motion is generated by traction wheels located in the grasping claws. Under this gait the robot essentially becomes a suspended cart when moving along obstacle free catenaries between support towers. In this case the clamp on transformer surrounds the line and the system operates normally. The second gait is suitable to overcome obstacles. It is inspired by the concertina (contractanchor-extend) motion of some invertebrates. Each of the three claws can (i) grabs the cable tightly; (ii) grabs the cable loosely, allowing the claw to slide along; (iii) disengage from the line. To overcome an obstacle the robot disengages each of the claws in sequence such that there are always two claws grabbing the cable, thus ensuring static stability. Under this gait, the clamp transformer opens so that the claws can disengage from the line. [1][2] The robot is equipped with a lithium ion polymer (LiPo) battery pack that provides energy while overcoming an obstacle and crossing a support tower. When moving along catenaries, and in the absence of obstacles, the supply system feeds the robot and can also recharge the battery pack. It is considered that robot operates on power cables carrying currents from nearly roughly to . When transmission current drops below a certain limit the robot hibernates and a signal is sent to the operation centre, and when the current exceeds the maximum the clamp-on transformer is opened to prevent damage to the robot. 2 1.1 Motivation Nowadays the procedure to detect imperfections on the power lines is subject of the experience of one technician who inspects those using helicopters. Since the beginnings of 90's researchers are studying solutions for new approaches to this problem. In Sawada at 1991, the first model is reported. On the following years some others projects were published later e.g. Peungsungwal in 2000. All these projects had limitations connected with power autonomy. Full autonomy is the key factor when assessing the economical advantages in use robots with such functions. Monitoring the power lines network during long periods and long distances will permit to detect failures easily and this way increase the power network quality, by reporting on real time the line problems. A 100 % autonomous robot, 80 % of operation time powered by a robot external source, will permit it to operate without any interruptions for recharging or refuelling operation breaks. The only times without be in operation will happen for check up the robot components. Following the work already developed by Luis Tavares and João Sequeira, their suggestion for a future work the development of a power source based on the magnetic power surrounding the transmission line that supports the robot. The present work main goal is to obtain the robot autonomous power supply. Full autonomy doesn’t mean full power dependence from the power source developed here. Batteries should still be used to pass line obstacles, or for any other emergency situation. [1] 1.2 Objective The objective of this research work is to study a power supply solution consisting on a COT and a full MOSFET bridge rectifier. In this work is studied the clamp-on transformer (COT), together with the MOSFET bridge rectifier, and implemented a control system for the rectifier. The control system applies an output voltage controller with an inner loop input current controller. Well known unity power factor rectifiers cannot be used in this case, because if the clamp-on transformer was ideal, it would operate as a current transformer and not as a voltage source (as usually required by these rectifiers). Furthermore, a current mode controlled unity power factor rectifier is not suited for this application due to possible iron saturation arising from the DC bias of the AC current introduced by the fast dynamic action of the DC voltage controller, as revealed in preliminary approaches. The control is done by using a pulse width modulation (PWM) signal and devised to obtain a voltage proportional to the secondary current so the power converter and the load are seen as a resistance at COT secondary terminals. Since the primary current depends on the high voltage line transmitted powers, this resistance must vary in order to provide the robot needed power, despite the tenfold line current variation. 3 Using this control approach is expected a higher efficiency, comparing with other topologies, a model with line current variation control and a power factor close to unit. 1.3 Walkthrough This thesis is organized as follows. On Chapter 2 is explained the converter, transformer and controller modules. This knowledge leads us to develop the new power converter model to use on the robot. It starts with the clamp on transformer study. This study regards core magnetization, and parameters dimension. Inside the same chapter is dimensioned the full-bridge inverter semiconductors, and the filters components used. To end up with this chapter is studied in detail the rectifier controller, considering just rectifier dynamics. In Chapter 3, is applied to show you the results obtained by model simulation, and in the end of this chapter the simulation results are discussed and new philosophies for the job model are presented. To conclude this work, Chapter 4 has of work made summary and directions for future researches. 4 Chapter 2 2 Power Supply Configuration A power supply must provide power with the characteristics required by the load from a primary power source. When the load requires DC, and the primary power source is AC, the power supply to use is an AC/DC converter, also called a rectifier. Figure 2 shows the design of the proposed power supply system. The maximum power absorbed by the robot (800 W) is much lower than the high voltage line transmitted power. With this in mind, the current in the high voltage line is almost not disturbed by the robot power supply and can be assumed to be a sinusoidal current source rd with a frequency of 50 Hz. Through a low pass 3 order filter to reduce high frequency switching harmonics, the clamp-on transformer feeds a power MOSFET fullbridge converter, the DC filter and the load, robot, ant the battery charger. The MOSFET bridge is operated as a PWM converter and controlled to convert to DC the AC current of the transformer secondary winding. The PWM is devised to obtain a proportional to the secondary current voltage so the power converter and the load are seen as a resistance. Since the primary current depends on the high voltage lines transmitted power, this resistance must vary (slowly) in order to provide the robot needed power, despite the tenfold line current variation. 5 Figure 2 - Power supply system model 2.1 Clamp-On Transformer (COT) To permit the transformer clamping around a power line, a COT is used. This device has two jaws that open when obstacles appear on the power line, e.g. aviation markers. This option permits to use the magnetic energy around the line without a physical contact. A wire coil is wound round both jaws, forming the secondary winding, and the conductor clamped by the transformer forms the one turn primary. An energised power line induces on the secondary coil a sinusoidal voltage which can originate a current through the full bridge converter. The connected filters and the AC/DC converter, work as non-linear load at the transformer terminals. The clamp-on transformer can be seen, on a first approach, as a linear current transformer. On the primary is imposed a sinusoidal current, . Figure 3 - COT lateral cut to describe core magnetization 6 The power line current density is obtained by (1) where L is the power line section. The magnetic field surrounding the line can be obtained by applying the Ampere Law (2) where surface S enclosed by the curve C means the transformer core. The magnetic flux on the core is obtained by (3) where R is the side surface. Figure 4 – COT upper view to describe secondary coil induction The voltage induced across the secondary coil, may be calculated from Faraday's Law (4) When the COT has a load connected on the secondary terminals, a linear ratio sinusoidal current is obtained on the secondary output, . (5) where is the ratio between the number of turns in the primary and the secondary coils. When the load attached to the transformer is not linear, it will not work on linear region. This situation can saturate the transformer. 7 Saturatio n Linear Saturatio Region Figure 5 - Hysteresis loop curve n When transformer is surrounding by an energised high voltage AC power line, the COT primary current is (6) where is the primary current amplitude, and is rad/s. In steady state the transformer losses are easily explained with the help of equivalent circuit, show in Figure 6, where and are primary and secondary winding resistances; primary and secondary leakage inductances; resistance and are is the magnetizing inductance in parallel with the . The transformer will operate for a low frequency of . For such frequency the stray capacitance of windings is negligible. Figure 6 - Clamp-on current transformer equivalent circuit When the leakage flux increases, the linkage flux and, consequently, the secondary winding inducted voltage decreases. Moreover, the leakage inductances increase, causing the secondary current to decrease and the algebraic value of the ratio error to decrease [6]. Between jaws an air gap exists when it closes around the line and it must be taken in consideration on the flux leakage prediction. 8 Power losses in the windings, represented on the schematic as and , are the main factors causing the transformer heating. The power losses vary with the square of the RMS current on its terminals (7) The COT nominal power needs to be adjusted depending on the load attached. Considering that the maximum load power is around 800 W [1] and a safety margin of 25 % over-dimensioned, a 1 kW nominal power transformer is used and sized for this project. Regarding the fact that the primary current power is imposed by the power line, and the nominal is established by design, the RMS value of the primary side voltage , considering near unitary power factor and efficiency, can be defined as (8) In this case it is relevant to know the maximum value that can be measured up. It happens when the power transmitted is the smallest possible for robot operation ( current line is . When this situation occurs a ), or it means when primary COT voltage or higher is expected. Considering this voltage applied on the line, it is predicted that the robot will almost not affect the line power losses on the line stretch of its localization. To deliver the predicted power to the load, is necessary to define the COT turns ratio Considering a voltage drop on the full-bridge rectifier semiconductors of . , the RMS secondary voltage is given for (9) Using the values obtained for and the ratio between turns is (10) The equivalent circuit present at Figure 6 is used to facilitate the computation of various operating quantities such as losses, voltage regulation, and efficiency. The parameters of the equivalent circuit can be obtained from the open-circuit and short-circuit tests of a real transformer. The open-circuit test is performed in order to determine exciting branch parameters of the equivalent circuit, the no-load loss, the no-load exciting current, and the no-load power factor. While secondary winding is open circuited, a rated voltage is applied to the primary winding, and the input voltage, ; input current, ; and input real power, , to the transformer should be measured. 9 The short-circuit test is conducted by short-circuiting the secondary terminal of the transformer, and applying a reduced voltage to the primary side, such that the rated current flows through the windings. The input voltage, ; input current, ; and input real power, , to the transformer should be measured. For this project these tests are simulated and results are compared with theoretical values at Chapter 3.6. Theoretical values are idealized for a common current transformer. Regarding that on this transformers the biggest voltage drop happens on the magnetization branch, the primary losses are consider to be a small part of the total voltage drop. For this circuit it is considered a 0.5 % of the total voltage drop. Using the following expression to obtain the impedance of the primary side (11) the values for primary winding losses and primary leakage inductance can be quantified as (12) (13) Core magnetization current and magnetic reluctance caused by the air gap of the core material should be minimized. Consider the maximum value for voltage drop when the secondary circuit is interrupted (10 V), a factor of 1.5 permit to define the value for magnetizing inductance (14) Considering that 1% of efficiency losses due to core losses, the equivalent resistance can be calculated as With a similar approach to the transformer secondary, the theoretical values are idealized for secondary losses of of the total voltage drop. Using the following expression to obtain the impedance of the secondary side (15) where a transformer efficiency of was considered. 10 The values for secondary winding losses and secondary leakage inductance can be quantified as (16) (17) The values obtained are resumed at Table 1. Regardless the voltage level, the transformer characteristics are present on per-unit system at Table 2. Table 1 – Transformer characteristics In per-unit system 0.160 pu 0.082 pu 100.0 pu 0.869 pu 0.097 pu 1.500 pu 2.2 Circuit components sizing 2.2.1 Full-Bridge inverter semiconductors characteristics The power semiconductors used should support drain-source voltages amplitude as load voltage with the same . The semiconductors used has to have (18) Regarding the circuit configuration present at Figure 2, the current in each transistor is given by (19) Using the average values of each expression component, (20) where is the average drain current in each semiconductor . 11 Using the same expression, the maximum and RMS drain current are given by (21) (22) The protection diodes should support (23) 2.2.2 DC output capacitor The RIOL robot needs DC, and consumes to (including power needed to recharge the batteries). In steady state, the voltage applied on the robot should have an error less than smaller error corresponds to a bigger capacitor with such size that will not fit on the robot. The error measured in the voltage is due to the voltage ripple in the DC capacitor The full bridge rectifier input current .A . has a fundamental component at and high frequency components that arise from the semiconductors switching action. The instantaneous power injected in the rectifier can be obtained from (24) where F is the product between efficiency and the power factor. Focusing our study on the fundamental frequency, and are (25) (26) Neglecting the switching components, since they must be small compared to the fundamental component [6], it equals the instantaneous output power : (27) 12 Applying the trigonometry relation (28) it is obtained (29) Then when resolved for , it permits to conclude (30) The capacitor voltage ripple can be obtained integrating the AC component of current obtained at Equation 30 (31) The peak voltage ripple must be less than VDC < 0.025 VDC as said in the beginning on this sub chapter. The variation around the average value can be so written as (32) Using Equation 30 the capacitance is obtained (33) When robot is operating at its maximum power, it needs a load average current around 15 A. The output capacitor should be dimensioned for this worst case. Applying the values to Equation 33 a capacitance of 35 mF should be used for . 13 2.2.3 AC input low pass 3rd order filter To reduce the amount of voltage harmonics on the line injected by the voltage, a filter rd between the transformer and the rectifier is used. A low pass 3 order filter is consider to fulfil the premises to reduce mainly the high frequency harmonics present at Assuming a Thévenin equivalent network resistor . seen from the transformer, and, as before a close to unitary , the resistor can be dimensioned as (34) From Equation 43, and applying for the smallest possible current on power line, it is obtained a Thévenin equivalent network resistor of . The filter output should be a current, so an inductor ( ) should be the filter component rd connected to the converter. Assuming it, the low pass 3 order filter represented at Figure 7 is used. Figure 7 – Low pass 3rd order filter circuit To design the filter components, let’s consider the voltage transfer function (35) Assuming a Chebyshev approach with a pass-band ripple equal to of at least and cut-off frequency times upper than the fundamental frequency, the approach equates the denominator coefficients with the Chebyshev polynomial (36) 14 From last equations is possible to write the following three equations (37) Solving it, for a close to the following components values are obtained ® Using MATLAB application the Bode diagram for this filter can be obtained. Studying the result it is observed that filter has an attenuation of fundamental frequency per decade. The rectifier input voltage , or it means in the maximum around frequency the attenuation is . Figure 8 - Bode diagram of AC input low pass 3rd order filter 15 has a . For this 2.2.4 Resonant second harmonic band-stop filter Regarding the size of the DC output capacitor obtained at Section 2.2.2, an extra filter in parallel is dimensioned. The combination of both filters will permit to decrease decrease the load voltage oscillation size, or will permit to . For this case it is used a resonant band-stop filter. With this filter, the load part of circuit looks as described at Figure 11. Resonant second harmonic band-stop filter if Figure 9 – Output filters solution These filter is resonant, and them natural frequency can be defined as ( 38) At resonant frequency the inductive reactance magnitude equals the capacitive reactance (39) As the components used are not ideal, is consider an internal inductance resistance . The existence of this resistance is the reason why all second harmonic is not attenuated, and still a voltage drop happens on this branch. Regarding this (40) For this model is consider a voltage drop , or it means the components will be 16 2.3 Rectifier controller The rectifier controller approach at this work considers all components ideal, as well as all the circuit filters. This simplification is important to don’t create a higher order system more difficult to be analysed and warranty its stability. 2.3.1 Full-Bridge inverter PWM generator The rectifier controller emulates a slow time varying resistor at the secondary transformer terminals. If a simple resistive load was connected at the COT terminals, it would be working on the linear zone. Considering the secondary winding current as a ratio of (Equation 5), and applying the Ohm’s Law, the transformer should see a secondary winding voltage (41) in phase with the input sinusoidal current, (42) Considering the input low pass 3 voltage rd order filter (Chapter 2.2.3) as nearly ideal, the secondary is the low frequency contents of the PWM voltage output of the full-bridge inverter. Therefore, the PWM is devised to obtain a average voltage, , within a switching period , proportional to the secondary current (43) A three level PWM (+1, 0, -1) to minimize voltage and current ripple will be used. When the modulating waveform is higher that the carrier (level +1), it means system should increase output. When it is lower than the carrier (level -1), it acts by decreasing output. When modulation waveform equals the input signal, the system is inside the expected values, so no power should be transferred (level 0). (44) 17 Regarding the full bridge rectifier design, the previous expression results on (45) Recording that the circuit in study is a MOSFET full-bridge converter, with two arms, and each one containing two transistors, the two switching variables and can be defined (46) Using the switching variables on Equation 42 the instantaneous value of the voltage of the bridge can also be written as (47) As said, must in each switching period constant at each switching period since equals the desired voltage, considered is much smaller than the line period ( ). Therefore, it can be written: (48) Considering the voltage error as (49) Regarding the stability of the controller, an error and its variation should be always negative (50) Considering the last equations and a sufficiently small quantity , then Equation 51 – 18 This switching law gives the full-bridge PWM modulator (Figure 10), where the gain before the integrator is and helps to define the switching frequency in addition to the value. The switching law (Equation 47) is implemented using two hysteretic comparators with different hysteresis widths and , that directly give the switching variables and . The switching signals for the lower semiconductors are obtained using two inverter gates. Figure 10 – Full-bridge inverter PWM generator 2.3.2 Control of the DC Output Voltage The dynamics of the DC output voltage represented by an equivalent resistor ( can be written, assuming all the DC loads ): (52) This equation means that, in steady-state ( is the DC gain , the average value of the term of the full bridge rectifier, given by: (53) Considering that the full-bridge rectifier is almost conservative and the rectifier input power factor is almost unitary, the input power (54) nearly equals the output power (55) 19 Then, the DC current conversion gain can be defined as (56) The DC output voltage dynamics (Equation 48) can be rewritten for average values: (57) Considering Equation 54, the term is (58) Then, the control block diagram can be represented in Figure 11, where the action of the controller (Equation 49) is assumed to have a delay approximated by a first order polynomial (since (pole in the origin and a zero at , whose transfer function has been is very small). A simple PI controller was chosen ), to increase speed and guarantee zero steady state error. Figure 11 - Ouput voltage control block diagram Linearizing around the DC operating point, the control linear block diagram is represented in Figure 12. Figure 12 - Linear output voltage control block diagram 20 nd Cancelling the load pole ( dynamics whose damping factor ) with the PI zero, the obtained system has a 2 can be used to determine the order value. Therefore, the PI parameters are: (59) (60) To ensure stability it is useful to consider . Making: ; , The PI gains are respectively and 21 . Chapter 3 3 Simulations ® The power supply system has been modelled and simulated with MATLAB/Simulink . The simulation values were obtained for a power transmission line with currents ranging from to . They include circuit analysis for steady state and for circuit answer to current steps, and the circuit start-up is shown in detail. The increasing steps temporization is described at Table 2. Table 2 – Input current amplitude simulation steps Simulation time (s) 0 – 0.6 0.6 – 0.8 0.8 – 1.0 Power transmission line current in study 100 A 200 A 400 A 22 1.0 – 1.2 1.2 – 1.4 500 A 700 A 1.4 – 1.6 1.6 – 2.0 900 A 1000 A 3.1 Output voltage in steady state for different line currents In steady state, simulation results shown that for load currents near oscillation of . It means of the predict ripple will be 0.4 % for DC currents near , can be measured an voltage. This way the peak to peak voltage , and are obtained in steady-state at primary currents of . Figure 13 - Output voltage (upper graph) and current (lower graph) in stready state for 100 A This error decreases for other line AC currents in study, except for be measured an oscillation of Figure 14 - Output voltage , of line. In this case can , or it means a peak to peak voltage ripple of (upper graph) and current 23 (lower graph) in stready state for 500 A . Figure 15 - Output voltage (upper graph) and current (lower graph) in stready state for 1000 A 3.2 Start up transient 3.2.1 Study of a initial current on the high voltage power line The start up transient for a current line of stable with the predict output voltage after amplitude of is present at Figure 16. It shows that circuit get . An over voltage is present on with a maximum . Figure 16 - Start up transient load voltage (upper graph) and load current 24 (lower graph) for 100 A It is interesting to look for waveforms of secondary transformer voltage and current, as well as the PWM voltage (Figure 17). During the first the transformer is not working on linear zone due to strong initial magnetization. Figure 17 - Start up transient secondary transformer voltage (upper graph), PWM voltage graph) and secondary transformer current (lower graph) for 100 A 3.2.2 Study of a (center initial current on the high voltage power line The start up transient for a current line of is present at Figure 18. It shows that circuit get stable with the predict output voltage after . An over voltage is present with a maximum amplitude of . Figure 18 - - Start up transient load voltage (upper graph) and load current 25 (lower graph) for 1000 A It is interesting to look for waveforms of secondary transformer voltage and current, as well as the PWM voltage (Figure 19). Figure 19 - Start up transient secondary transformer voltage (upper graph), PWM voltage graph) and secondary transformer current (lower graph) for 1000 A (center 3.3 Current step response When is applied the current steps present at Table 2, the following output is obtained. It shows that the DC voltage stays close to its set-point ( ) even when occur strong AC current variations. The results suggest a good line regulation with step changes, and a satisfactory sensitivity to disturbances. The worst case happens on the step from the load voltage, or it means an increase of to that perturbation increases in . Figure 20 - Load voltage (upper graph) and current start-up transient (lower graph) and response to AC line current from 100 A to 1000 A 26 3.4 Secondary transformer voltage in steady state for different line currents Looking back for Section 2.4.2, the Thévenin equivalent network resistor is obtained for the smallest possible current on power line. When circuit is simulated for this line current is obtained the Figure 21 simulations. Figure 21 - Secondary transformer voltage in steady state for 100 A rd When current on power line changes, the 3 order filter is not so accurate dimensioned anymore. Regarding it, when circuit is simulated for (Figure 22) is possible to see the effect of other signal frequencies that not only the fundamental. Figure 22 - Secondary transformer voltage in steady state for 500 A 3.5 PWM voltage and 3rd order filter simulation At Figure 23 is present the PWM voltage at the converter input. The pulse waveform obtained is the reason why a 3 rd filter is used to reduce the high frequency content and to obtain a primary voltage close to a sine-wave. 27 Figure 23 - PWM voltage The secondary transformer voltage and the current are shown at Figure 24. The current still has some high frequency harmonics due to the fact that filter added between transformer and bridge was not designed for the current but for the voltage. However, the current ripple is small enough and will have detrimental effect on the power supply behaviour. Figure 24 - Secondary transformer voltage (upper graph) and current (lower graph) 3.6 Transformer parameters simulation 3.6.1 Open-circuit test To do the following test was used in Simulink/SimPowersystems the Figure 25 implementation. Figure 25 - Simulink/SimPowerSystems implementation of the open-circuit test 28 A AC voltage source is applied to the primary side to obtain a current of . Since in Simulink environment, all elements must be electrically connected, the secondary side of the transformer cannot be left open and a load has to be connected. In order to simulate no-load condition, a high impedance model to reflect loading is used, and the resistance and inductance values are set to very large numbers while the value of the capacitor is set to a very small number On the primary side, current, and voltage measurement blocks are used to measure the instantaneous current and voltage. The output of each meter is connected to a RMS block, to determine the RMS values of primary current and voltage. The magnitude of the excitation admittance from the open-circuit voltage and current is (61) The phase angle of the admittance can be found from the knowledge of the power factor. The open-circuit power factor, , is given by (62) For this circuit were obtained Regarding this values These values are not so close to the ones explain at Chapter 2.1. The reason why this situation happens is because primary leakage inductance 3.6.2 is not so small, and affects this test results. Short-circuit test To do the following test was used in Simulink/SimPowersystems the Figure 26 implementation. A AC voltage source is applied to the primary side. The rest of the model is similar with short- circuit one. The only difference is that secondary side is short circuited. 29 Figure 26 - Simulink/SimPowerSystems implementation of the open-circuit test Since a reduced voltage is applied to the primary windings, a negligible current flows through the excitation branch. Ignoring this current, the magnitude of the series impedance referred to the primary side of the transformer can easily be computed as (63) Neglecting the core loss at the low value of , the series resistance and leakage reactance equivalent can be found by (64) (65) For this circuit were obtained Regarding this values 30 3.7 Primary transformer voltage and current when happens a step Figure 27 shows the voltage at the transformer primary at primary currents of to . The voltage amplitude is small, meaning that the power supply system will not disturb the normal operation of the AC transmission power line. Figure 27 - Primary transformer voltage (upper graph) and current (lower graph) 3.8 Results discussion The simulation results obtained are a prove that the theory concepts used at this work could be used for a future prototype of a power supply for an autonomous robot moving on active high voltage power lines. Simulation results show that the DC voltage is well regulated (disturbances are lower than the predicted ) in all the AC line current range from to components were tuning, in steady-state, ripples are smaller than lower than . In fact, when all the and disturbances sensitivity . The RIOL robot power needs of is reached using this model, and the use of a clamp on transformer to obtain such amount of power is proved that can work for such applications. The AC voltages injected in the transformer primary are low enough for the AC line ( smaller of the line voltage for the worst case ( rd line)). Even, by using a 3 order low pass filter, the harmonic distortion is decreased, and the robot by itself doesn’t increase line THD. 31 When the circuit is tested with different transformer characteristics from the specified ones at this work, the results obtained are similar with the ones presented. This way is expected that circuit will be able to accept some characteristics variations when a prototype will be implemented. 3.9 Model efficiency Predicted efficiency is lower than desired at high AC currents ( the normal operating AC currents ( at at ), but it is good at ), and very good for low AC currents ( at ). For high AC currents the model efficiency is related with transformer saturation. To increase the efficiency for such high AC current lines it is needed to consider another power supply topology, or study thoroughly the clamp on transformer. 32 Chapter 4 4 Conclusions The current thesis intended to demonstrate that a power supply for the RIOL can be done to permit its autonomy. The circuit solution described at this work was designed and tested on ® MATLAB software, and the results obtained let a door open for creating a future model to be implemented on the robot. The power supply harvests magnetic energy from active overhead power lines, using a clamp-on transformer around the line. The transformer supplies a full bridge MOSFET based rd rectifier with a DC output filters through a 3 order Chebyshev low-pass filter. The control systems uses sliding mode in the inner AC voltage control loop to emulate a resistor, and a linear PI controller in the outer DC voltage loop. The value of the time dependent virtual resistor is obtained using a PI to deliver the desired output voltage (55V ± 2.5%) and power (maximum 800 W). The controller laws and parameters, together with transformer and filter design were addressed. The energy absorbed by the robot comes from the line, producing an increment in the line impedance and, therefore, a slight voltage drop in the point of the line where the robot is located during the inspection. This voltage drop is very small compared with the voltage level of the high voltage transmission line. It affects, for the worst case, transmission line. 33 ( ) the voltage On this project was not discussing some aspects that can be important for future development. RIOL deal with some constrains that should be consider about on future researches. Nowadays high voltage overhead power lines are full of line obstacles, e.g. aviation balloons. The robot in develop is already prepared for this situation, but its dimension and/or weight distribution should be prepared for the case this will happen often on a line. The extraction of energy from a transmission line in a quantity important enough to feed an inspection robot can be achieved by means of the proposed system. The continuous circulation of current along the phase conductors ensures the feeding of the robot in such a way that the batteries can be size optimized and hence its weight. The next steps for developing this work pass through analyse in depth the transformer characteristics, and to build a prototype to give consistency to all the theoretical approach used on this work. 34 Bibliography [1] Sequeira, J.; Tavares, L., “RIOL - robotic inspection over power lines”. 6th IFAC Symposium on Intelligent Autonomous Vehicles, September 2007. [2] Tavares, L.., “Avaliação dinâmica do robot RIOL: Aspectos de um protótipo experimental”, IST academic press, TULisbon, Portugal, September 2007. [3] Zangl, H.; Bretterklieber, T.; Brasseur, G., "Energy Harvesting for Online Condition Monitoring of High Voltage Overhead Power Lines," Instrumentation and Measurement Technology Conference Proceedings, 2008. IMTC 2008. IEEE , vol., no., pp.1364-1369, May 2008. [4] San Segundo, H.B.; Fuster, V.; Perez, L.; Mayorga, P., "Automated Inspection of Electric Transmission Lines: The power supply system," IEEE Industrial Electronics, IECON 2006 - 32nd Annual Conference on , vol., no., pp.3788-3792, Nov. 2006. [5] Esser, A.; Skudelny, H.-C., "A new approach to power supplies for robots," Industry Applications, IEEE Transactions on , vol.27, no.5, pp.872-875, Sep/Oct 1991. [6] Elhaffar, A.; Lehtonen, M., "High Frequency Current Transformer Modeling for Traveling Waves Detection," Power Engineering Society General Meeting, 2007. IEEE, vol., no., pp.1-6, 24-28 June 2007ю [7] Silva, F; Pinto, S., “Control Methods for Switching Power Converters”. M. H. Rashid (Editor), “Power Electronics Handbook”, 2nd edition, Academic Press, Elsevier, 1172 pp. ISBN ISBN 13:978-0-12-088479-7, ISBN 10:0-12-088479-8, USA. [8] Hung, J.Y.; Gao, W.; Hung, J.C., "Variable structure control: a survey," Industrial Electronics, IEEE Transactions on , vol.40, no.1, pp.2-22, Feb 1993 [9] Silva, F., “Sistemas de Energia e Telecomunicações”. IST, TULisbon, Portugal, 2009/2010. [10] Baliga, J., “Power Semiconductor Devices”. PWS Publishing Company, 1996. [11] Sedra, A; Smith, K., “Microelectronic Circuits”. Oxford University Press, 4th edition, 1997. [12] Silva, F., “Electrónica Industrial”, F. Calouste Gulbenkian, 1998 35