Instantaneous Voltage Regulated Seamless Transfer Control Strategy for Utility-interconnected Fuel cell Inverters with an LCL-filter Guoqiao Shen, Dehong Xu Xiaoming Yuan College of Electrical Engineering, Zhejiang University, General Electric Corporate R&D-Shanghai Yugu Lu, Hangzhou, P. R. China, 310027 200233, Shanghai, China xdh@cee.zju.edu.cn xiaoming.yuan@geahk.ge.com Abstract—This paper proposes a new control strategy for the transition between grid-tied mode and off-grid mode of the utility interconnected fuel cell inverters with an LCL filter. During the transition from grid-tied mode to stand-alone mode, the inverter control is switched to voltage-controlled mode from the beginning of the transition, using inverter instantaneous output voltage regulation to reduce the output grid current of the inverter quickly, so that the static transfer switch is turned off immediately and the inverter maintain a continuous voltage output. It will result in a short transition time and minimum voltage fluctuation on the load. The algorithm is described along with their transition performances. Simulations and experiments on a 5kW fuel cell inverter prototype are provided to validate the algorithm. I. INTRODUCTION Fuel cell generation now is regarded as one of the most competitive energy source for the distributed energy generations due to its advantages of higher efficiency, lower emissions, and higher power density. Most of the utility interactive fuel cell inverters have the capability to operate in two modes, a) utility interactive mode for peak shaving to reduce the overall cost of power by generating during peak hours, b) stand-alone mode to provide power during utility outages until service can be restored.[1] In the case of sensitive and mission critical loads at the user end, a continuous uninterrupted AC power is of utmost importance. So it is very valuable for fuel cell inverters to be able to operate in both grid-tied and off-grid modes with seamless transitions between the two modes. When the inverter is grid-connected, it is operated in current-controlled mode. In the stand-alone mode, the inverter is operated in the voltage-controlled mode. Heretofore, many researches have made on these two modes of inverters [2], but no enough attention has been paid to the issue of a seamless transition between the two modes. The control algorithm reported in [3] switches the inverter from current-controlled mode to voltage-controlled mode after the grid-disconnecting switch (SCR) current goes to zero free-wheeling, so the output voltage on the load is uncontrolled from the instant of utility fault to the time of the first zero crossing of the 1-4244-0449-5/06/$20.00 ©2006 IEEE grid current. To overcome the turn-off delay and reduce the voltage uncontrolled time during the transfer, the voltage amplitude regulation algorithm (VAR) and the voltage phase regulation algorithm (VPR) are introduced to reduce the grid current promptly [4]. However, they both depend on the in-phase running for the grid voltage and current, which in some case, will be of a problem. Focusing on the seamless transition between grid-tied and off-grid modes of operation, this paper proposes a new control algorithm based on voltage-controlled method for utility-interactive fuel cell inverters with an LCL filter, the instantaneous voltage regulation algorithm (IVR), which is introduced to implement forced current commutation between the grid and the inverter. The algorithm and its transition performances are described and discussed in this paper. Simulations results on a 5kVA single-phase inverter are presented using PSPICE. The results show the feasibility of the proposed approaches and the effectiveness of the algorithms in minimizing voltage transients across the inverter and loads, even at the moment of utility fault. A 5kVA DSP controlled inverter prototype has been made, and the present control strategy is validated. II. TOPOLOGY AND RUNNING MODES OF THE INVERTER Fig.1 shows the system topology for the utility interactive fuel cell inverter. The topology comprise a fuel cell stack, a DC to DC converter, a PWM inverter, a low-pass LCL filter and a grid-disconnecting transfer switch (STS). Due to the advantages of short turn-off time, large current capacity and low cost, SCR is selected as the static transfer switch to enable the inverter disconnect from the grid rapidly. The LCL form of low-pass filter offers the potential for improved harmonic performance at lower switching frequencies [5], which is a significant advantage in higher-power applications, (e.g. several hundreds kilowatt inverters). For sensitive and mission critical loads at the user end, a continuous uninterrupted AC power is required when the utility is abnormal. IPEMC 2006 L1 DC/AC DC/DC L2 i1 DC+ STS ig i2 Fuelcell Booster LCL-Filter Disconnect Load the static switch continuous uninterrupted AC power across the load, - quickly turning-off of the SCR and earlier voltage L2 L1 PCS Vo i2 C PCC STS controlling of the inverter output are required. III. PRINCIPLE AND PERFORMANCE OF Lg TRANSFER STRATEGIES Vg Local Load VS Grid A. Control algorithm with grid current free-wheeling (CFW)[3] PWM Gi i2*+ by voltage-controlled mode. In order to maintain a + i1 I2* grid inverter control method from current-controlled mode to (a)Voltage-controlled stand-alone mode DCBUS the for the SCR current to go down to zero. b) Change Grid PID Vc* from control algorithm should ensure appropriate conditions VS PWM Voltage controlled Grid (SCR).Because SCR has no self turn-off capability, the ig C Vg - Lg PCC i1 Vo VS - System topology for the utility interactive fuel cell inverter L1 PCS DCBUS - Inverter Fig.1 Local Loads Vo ~ DC- + + + C Lg PCC For the transfer from utility-interactive mode to - stand-alone Current controller Sin (b)Current-controlled utility-interactive mode Fig.2 Schematic diagram of the converter in different modes mode, the inverter is initially current-controlled and the grid maintains the voltage at the PCC. When the inverter starts to switch to the stand-alone mode, the drive of the SCR is removed firstly. Fig.2a shows the schematic diagram of the The grid current is freewheeling through the SCR, as it converter when it is disconnected from the grid. The has no self turn-off capability. The grid is disconnected inverter is operated in voltage-controlled mode. Voltage until the line current goes to zero, and the SCR has been feedback is used to regulate the voltage across the load. turned off. At this instant, the PWM inverter is shifted Fig.2b shows the schematic diagram of the converter from current controlled mode to the voltage controlled when it is grid-connected. The Inverter is operated in mode. Thus there is no current spike during the transition. current-controlled mode at this time. It is controlled But in the case of a utility fault, the voltage across the through current feedback to regulate the current injected load may be dropped within half a line cycle (in addition into the grid. The utility is assumed to be relatively strong to the time required to detect the fault) due to the delay of and maintains the voltage across the load. switching inverter to voltage-controlled mode. For the transition from stand-alone to grid-connected, B. Control Algorithm with VAR and VPR [4] it is relatively easy and well known as in the With VAR transfer control, the grid current is in uninterruptible power supply (UPS), so no more phase with the grid voltage before switching, because a descriptions is given here. For the transition from unity power factor is required. The drive of the SCR is grid-connected mode to stand-alone mode, there are two removed at the beginning of the operation mode transition. essential work should be done for the control algorithm: a) At the same time, the inverter is shifted to the voltage-controlled mode with the desired output voltage on the grid side inductance in despite of the waveforms of Vo being lower or higher than the grid voltage Vs (Fig.3a), the grid voltage and current. Fig. 4a shows the waveforms introduces a voltage drop VL across the line inductance of the grid voltage Vg, the corresponding desired output and filter inductance L2, just being opposite to the grid voltage Vo of the inverter for the proposed IVR transition current Ig . So the grid current is forced to decrease control, and consequently the voltage drop VL introduced quickly. Once the grid current goes to zero, the SCR is on the grid side inductance L2 by the IVR control. turned off, and the output voltage is changed to the rated Whenever the transition is carried out, and no matter the value soon. Consequently, it takes less time to complete grid voltage is distorted, the voltage across the inductance the transfer, and the voltage transition across the load is L2 is same because the inverter output voltage is minimized (Fig.3). controlled to follow the grid voltage with a constant voltage difference. Fig.4b shows the waveforms of the Vo Ig Vs grid voltage and current and the inverter output voltage before and after the transition. Before the transition, the inverter was running in current-controlled mode as shown in Fig.4b, so the inverter output voltage was nearly the VL same as the grid voltage. When the transition began at t0, the inverter turned to voltage-controlled mode, and the inverter output voltage was controlled to follow the grid (a) Current and voltage waveforms during transition L INV + Vo C SCR Lg Ig + VL - voltage with a fixed difference, as shown in Fig.4a, so that the grid current fell down to zero at t1, after a delay, at the time of t2, the inverter output voltage turned to trace the standard waveform. Load Vs Vg Vg Vo (b) Topology of the utility-interactive inverter Vo Ig Ig Fig.3 Control algorithm with voltage amplitude regulation (VAR) VL = Vo - Vg For the VPR control algorithm, instead of the voltage amplitude, the voltage phase of the inverter output voltage is regulated according to the current waveform, so a opposite voltage is introduced upon the (a) Grid voltage and the desired inverter output voltage proposed for grid side inductance to transfer the grid current to the IVR control transition inverter. Vo It can be seen that both VPR and VAR method are depend upon the waveform of the grid voltage and grid current, in-phase running are required, so they are limited to be used. For the moment of utility fault, the waveforms of the grid voltage and current are always distorted. C. Proposed Control Algorithm with the Instantaneous Voltage Regulation (IVR) The proposed control algorithm is an improvement of VAR. Here, the instantaneous voltage of the inverter output is controlled according to the direction of the grid current with a fixed voltage difference to the grid voltage, so that a voltage opposite to the grid current is introduced VS Ig t 0 t1 t2 V L = Vo - Vg (b)Waveforms during the IVR control transition, the inverter output voltage from t0 to t2 is controlled to decrease , as shown in (a) Fig.4 Control algorithm with instantaneous voltage regulation (IVR) In this control algorithm, the grid current falling time can be expressed as ∆t, ∆ t = t1 − t 0 = L inverter output voltage will result in 1ms less falling time of the grid current and a short transition period. ig VL For a fixed VL value, the grid current falling time is proportional to the instant current value. When the grid current is given, then the grid current falling time under different control voltage difference VL can be calculated, as shown in fig.5a. For normal utility condition transition, the maximum grid current falling time is occur at the current peak, so it can be derived as: ∆t = SIMULATION AND EXPERIMENT RESULTS IV. The simulation is realized by PSPICE on a single-phase half-bridge inverter and a six-switch 3-phase inverter, as shown in Fig.6a and Fig.6b. The rated power of each phase is around 5kVA. The voltage of DC bus is 800V, the current injected into grid is 0~30A, the switching frequency is 20 kHz. The parameters of the filter are: L1=1.6mH, C=12µF, the grid side inductance is assumed to be 10µH~2.0mH, including the additional 1 ωβ (1 − α ) (1) inductance. where β is the radio of grid voltage amplitude to the voltage amplitude across the grid side inductance L2 L1 DC+ VS VSM = VL ω L2 I SM + V L i1 caused by the grid current in normal operating condition, β= L2 Vo + - DC- C Local Loads STS Lg + ig Vg - + VS - PCC α=Vo/Vs is the amplitude radio of the desired inverter output voltage to the grid voltage during the transition. a) Schematic diagram of a single-phase half-bridge inverter Current Falling Time DT(mS) 6 5 i= 2 4 A i= 1 6 A 4 i= 8 A 3 2 1 0 10 20 30 40 50 60 V o lta g e o n th e G rid -s id e In d u c ta n c e V L(V ) Grid current falling time a) Grid current falling time under different voltage difference (VL) b) Schematic diagram of a six-switch 3-phase inverter Fig.6 Schematic diagram of grid-tied inverters for simulation 5 4 The voltage and current waves of the inverter during 3 the transition from grid-connected to stand-alone in the 2 case of a utility fault are shown in Fig.7. Where, Fig.7a is 1 under the traditional grid current free-wheeling control. 0 0.6 β = 20 0.7 0.8 0.9 1 Voltage ratio β = 50 1.1 β = 100 α 1.2 1.3 1.4 β = 1 000 Fig.7b is under the voltage amplitude regulation control. The utility fault takes place at the time of t0, and grid voltage has fallen to 50% of the normal value. The b) Maximum grid current falling time for normal grid condition detecting time of fault is 1ms. The result shows that the Fig.5 Grid current falling time vs voltage difference duration of voltage drop under the traditional grid current Fig.5b shows the maximum grid current falling time free-wheeling control is comparative longer (7ms), vs. the voltage phase difference between the inverter whereas the duration of voltage drop under the IVR output voltage and the grid voltage for different β values. control is only 1.2ms. The grid side inductance is 1.6mH. The grid current falling time is decreasing as enlarges. For β=20, 15% voltage difference between the grid voltage and the Delta Power Electronic Technology and Education Fund, and the support of GE (China) Research & Development Center Co., Ltd. a) Under traditional grid current free-wheeling control (3_ Grid current, 20A/div. 4_Voltage on local load ) Fig.8 Experimental results for transition from grid-tied mode to off-grid mode under IVR near current zero-cross b) Under IVR control Fig.7 Transition in the case of a fault on the grid A 5kVA DSP controlled inverter prototype has been made. The experimental results are shown as Fig.8 to Fig.9. Fig.8 shows the grid current (curve1#) and the load voltage (curve2#) under IVR when the transitions start near current zero-cross points. Fig.9 shows the waveforms when the transitions start at current peak points. Whenever the transition is carried out, the transition time is very short, and the voltage on load is (1_ Grid current, 20A/div. 2_Voltage on local load ) Fig.9 Experimental results for transition from grid-tied mode to off-grid mode under IVR at current peak point. REFERENCES [1] Coles, L.R.; Chapel, S.W.; Iamucci, J.J.; continuous. “Valuation of Modular Generation, Storage, and Targeted Demand-side Management”, V. CONCLUSIONS A novel control algorithm for the transition between Energy Conversion, IEEE Transactions on , Volume: 10 Issue: 1 , Mar 1995 ,Page(s): 182 –187 grid-tied and off-grid modes of the utility-interactive inverters is [2] O'Sullivan, G.A.;“Fuel Cell Inverters for Utility Applications”, proposed. The principle and performances have been discussed. Power Electronics Specialists Conference, 2000 , Volume: 3 , The simulation and experimental results show that the output Page(s): 1191 -1194 vol.3 instantaneous voltage regulation algorithm can provide seamless [3] Tirumala, R.; Mohan, N.; Henze, C., “Seamless Transfer of transfers between the two modes for the inverter, avoiding the Grid-connected PWM Inverters between Utility-interactive and temporarily uncontrolled output voltage of the inverter,which Stand-alone modes”, IEEE APEC2002. Volume: 2 , pp.1081 -1086. occurs during the time of grid current free-wheeling under the [4] Guoqiao Shen, Dehong Xu, Danji Xi, “Novel seamless transfer traditional control algorithm. The algorithm presented in this strategies for fuel cell inverters from grid-tied mode to off-grid paper is valid even in the event of a fault on the grid. mode”, APEC2005, March 2005, Pages:109-113 [5] Guoqiao Shen, Dehong Xu, Danji Xi, “An Improved Control ACKNOWLEDGEMENGT The authors would like to acknowledge the support of Strategy for Grid-Connected Voltage Source Inverters with a LCL Filter”, APEC2006, Session 29.1, March 2006