Safety, Health, Environment & Risk Management WATERLOO| Brantford | Kitchener | Toronto Workplace Electrical Safety Program Document No. FACL-001-02 1. INTENT Wherever possible, work on electrical systems should be performed while the equipment is in a de-energized state and safely locked out (in accordance with the university’s lockout program). While this is an ideal scenario, the university recognizes that working on energized electrical equipment is necessary to complete certain activities, such as troubleshooting and testing. Exposure to electrical energy is hazardous and can result in death, serious injury, and/or damage to equipment. In order to ensure the safety of employees in contact with electrical infrastructure on a day to day basis, this policy must be adhered to any time an employee works on energized electrical equipment. Specifically, this pertains to electrical systems and equipment operating between 50 and 750 Volts AC (phase to phase or phase to neutral), or greater than 50 volts DC (phase to phase or phase to neutral). For the purposes of this document, electrical systems and equipment operating at levels above 750 volts AC are considered as high voltage, and are not covered under this program. Only a specially trained, High Voltage Electrical Contractor shall perform any work (including testing or troubleshooting) on equipment with voltages above 750 volts AC. The Workplace Electrical Safety Program applies to any work on, testing of, or troubleshooting that involves exposed energized electrical parts where a person, their tools, or test probes could come into contact with power. Where work on, testing of, or troubleshooting is required on live exposed electrical equipment, appropriate PPE must be worn as specified by the Arc Flash/Hazard Analysis label, or as outlined in the CSA Z462-12 standard. Where this information is not available, please refer to Appendices D, E and F of this document for basic requirements. If unsure of the PPE requirements for work being undertaken, please confer with the Lead Hand or Area Facilities Manager prior to commencing work. Please note that this program is not intended to be a substitute for working on equipment where electrical lockout can be applied. Work on exposed energized equipment must NEVER be carried out except in compliance with this program. Whenever possible, electrical equipment will be locked out before any work is started in accordance with the Lockout Program (see SHERM document FACL-003-01). This program will be strictly enforced. It is the responsibility of all people involved in work (worker, supervisor, SHERM) under this program to ensure that all work performed on energized electrical equipment is both necessary and will be performed in compliance with this program. Page 1 of 34 Facilities Operations Prepared by Physical Resources – Safety, Health, Environment & Risk Management WATERLOO| Brantford | Kitchener | Toronto 2. DEFINITIONS Accessible Admitting close approach because the equipment is not guarded by locked doors, elevation, or other effective means. Arc Flash Hazard A dangerous condition associated with the possible release of energy caused by an electric arc. Notes: 1) An arc flash hazard can exist when energized electrical conductors or circuit parts are exposed or are within equipment in a guarded or enclosed condition, if a person is interacting with the equipment in a manner that could cause an electric arc. Under normal operating conditions, enclosed energized equipment that has been properly installed and maintained is not likely to pose an arc flash hazard. 2) See Appendix D (Tables 3 and 4) for examples of activities that could pose an arc flash hazard. Arc Flash Hazard Analysis A study investigating a worker’s potential exposure to arc flash energy, conducted for the purpose of injury prevention and the determination of safe work practices, arc flash boundaries, and the appropriate level of personal protective equipment. Once an analysis has been completed, this information will be posted in the form of an arc flash hazard analysis label. See Appendix F (Figure 3) for an example of a label. Authorized/Qualified Person One who has skills and knowledge related to the construction and operation of electrical equipment and installations and has received safety training to recognize and mitigate the hazards involved. Boundary, arc flash When an arc flash hazard exists, an approach limit at a distance from a prospective arc source within which a person could receive a second-degree burn if an arc flash were to occur. Note: 1) A second-degree burn is possible by an exposure of unprotected skin to an electric arc flash above the incident-energy level of 5 J/cm2 (1.2 cal/cm2). Boundary, limited approach An approach limit at a distance from an exposed energized electrical conductor or circuit part within which a shock hazard exists. Page 2 of 34 Facilities Operations Prepared by Physical Resources – Safety, Health, Environment & Risk Management WATERLOO| Brantford | Kitchener | Toronto Boundary, prohibited approach An approach limit at a distance from an exposed energized electrical conductor or circuit part within which work is considered the same as making contact with the electrical conductor or circuit part. Boundary, restricted approach An approach limit at a distance from an exposed energized electrical conductor or circuit part within which there is an increased risk of shock, due to electrical arc over combined with inadvertent movement, for personnel working in close proximity to the energized electrical conductor or circuit part. Circuit Breaker A device designed to open and close a circuit by non-automatic means and to open the circuit automatically on a predetermined overcurrent without damage to itself when properly applied within its ratings. Control Circuit A circuit that carries electric signals directing the performance of a control device, but does not carry the power which the device controls. Controller A device or a group of devices that govern, in some predetermined manner, the electric power delivered to the apparatus to which they are connected. Dead (also de-energized) Free from an electrical connection to a source of potential difference and from electrical charge (ie. not having a potential different from that of the earth). Dead Front Without live parts exposed to a person on the operating side of the equipment. Device A unit of an electrical system that carries or controls electric energy as its principal function. Disconnecting Means A device, group of devices, or other means by which the conductors of a circuit can be disconnected from their source of supply. Page 3 of 34 Facilities Operations Prepared by Physical Resources – Safety, Health, Environment & Risk Management WATERLOO| Brantford | Kitchener | Toronto Electrical Equipment Any apparatus, appliance, device, instrument, fitting, fixture, luminaire, machinery, material, or thing used in or for, or capable of being used in or for, the generation, transformation, transmission, distribution, supply or utilization of electric power or energy, and, without restricting the generality of the foregoing, includes any assemblage or combination of materials or things that is used, or is capable of being used or adapted, to serve or perform any particular purpose or function when connected to an electrical installation, notwithstanding that any of such materials or things may be mechanical, metallic, or non-electric in origin. Electrical Hazard A dangerous condition such that contact or equipment failure can result in electric shock, arc flash burn, thermal burn or blast. Exposed Capable of being inadvertently touched or approached nearer than a safe distance by a person. This term is applied to electrical conductors or circuit parts that are not suitably guarded, isolated or insulated. Flame-Resistant (FR) The property of a material whereby combustion is prevented, terminated, or inhibited following the application of a flaming or non-flaming source of ignition, with or without subsequent removal of the ignition source. Note: 1) Flame resistance can be an inherent property of a material or can be imparted by a specific treatment applied to a material. Guarded Covered, shielded, fenced, enclosed, or otherwise protected by suitable covers, casings, barriers, rails, screens, mats, or platforms to remove the likelihood of approach or contact or approach by persons or objects to a point of danger. Incident Energy The amount of energy, impressed on a surface a certain distance from the source, generated during an electrical arc event. Insulated Separated from other conducting surfaces by a dielectric (including air space) offering a high resistance to the passage of current. Note: 1) When an object is said to be insulated, it is understood to be insulated for the conditions to which it is normally subject. Otherwise, it is considered to be uninsulated. Page 4 of 34 Facilities Operations Prepared by Physical Resources – Safety, Health, Environment & Risk Management WATERLOO| Brantford | Kitchener | Toronto Isolated Securely physically separated or blocked with non-conductive material sufficient to ensure that equipment cannot be energized by identified power sources. Live (or Energized) Electrically connected to, or having a source of voltage. Lockout Placement of a lock on an energy-isolating device in accordance with an established procedure, thereby indicating that the energy-isolating device is not to be operated until removal of the lock or in accordance with an established procedure. Near Working close enough to exposed live equipment such that deliberate or accidental movement could cause the person to come into contact with the live equipment. Person in Charge A Manager or Supervisor. Someone having authority over one or more employees performing work on a machine or piece of equipment, or a person designated by one of the above as the person in charge of the work. Readily Accessible Capable of being reached quickly for operation, renewal, or inspection without requiring persons seeking access to climb over or remove obstacles, or to resort to portable ladders, etc. Testing/Troubleshooting Metering voltage with an approved testing apparatus complete with properly protected probes in order to diagnose an electrical fault condition that is not possible to do while de-energized and locked out. Activities are only performed while wearing the personal protective equipment as listed in Appendix C (Table 3 and/or Table 4) in this policy. Voltage The greatest root-mean-square (rms) (effective) difference of potential between two conductors of a circuit. Voltage (Nominal) A nominal value assigned to a circuit or system for the purpose of conveniently designating its voltage class (eg. 120/240 V, 480Y/277 V, or 600 V). Page 5 of 34 Facilities Operations Prepared by Physical Resources – Safety, Health, Environment & Risk Management WATERLOO| Brantford | Kitchener | Toronto Working on (energized electrical conductors or circuit parts) Intentionally coming in contact with energized electrical conductors or circuit parts with the hands, feet, other body parts, or with tools, probes, or test equipment, regardless of the personal protective equipment a person is wearing. Notes: 1) There are two categories of working on: a. Diagnostic (Testing) – Taking readings or measurements of electrical equipment with approved test equipment that does not require making a physical change to the equipment. b. Repair – Physical alteration of electrical equipment, eg. making or tightening connections, removing or replacing components. 3. ROLES AND RESPONSIBILITIES Authorized and Qualified Employees Only authorized and qualified employees will perform the work on, testing or troubleshooting of, verification on, or other work near exposed live electrical equipment. To be qualified, an employee must meet the description of a qualified person outlined in the definition section of this document (Section 2) and have completed training required by this program. Responsibilities It is the responsibility of any person assigned to work on any exposed energized electrical equipment to comply with this Workplace Electrical Safety Program. For all other work on electrical equipment, the Wilfrid Laurier University Lockout Program will be followed to ensure the equipment is safely de-energized. Management Shall: • Allow only qualified employees to perform work on, or near, exposed live equipment. • Provide personal protective equipment to meet the hazards of the work to be undertaken and ensure that the equipment is maintained in a safe and reliable condition. • Ensure regular testing of protective gloves in accordance with industry standard practices and as detailed in ASTM F 496. • Provide training to employees required to work on live exposed electrical equipment as detailed in these procedures and maintain documentation of training. • Maintain documentation of glove assignment and testing. • Apply appropriate corrective action when these work practices are not followed. Page 6 of 34 Facilities Operations Prepared by Physical Resources – Safety, Health, Environment & Risk Management WATERLOO| Brantford | Kitchener | Toronto • Provide a copy of this program to all employees required to work on, or near, exposed live electrical equipment. Supervisor Shall: • Have a technical knowledge of the electrical systems being worked on by their direct reports. • Ensure the procedures set forth in this document are understood and followed. • Inform employees of known hazards and the required protection equipment when assigning work. • Report violations of these procedures to the Area Manager, Facilities Operations in the Physical Resources Department. Page 7 of 34 Facilities Operations Prepared by Physical Resources – Safety, Health, Environment & Risk Management WATERLOO| Brantford | Kitchener | Toronto Authorized/Qualified Employee Shall: • Follow the Workplace Electrical Safety Program at all times when working on exposed live electrical equipment. • Use personal protective equipment as required by this program. • Use only approved meters as specified in Appendix B (Table 1). • Inform your Supervisor of any problems or concerns related to the procedures as soon as they arise. • Inspect voltage rated rubber gloves prior to every use. Report any damage found during inspection to the supervisor immediately. Do not under any circumstances, use the damaged PPE. • Report any incidents, such as arcing, arc flash, or other events that may affect the performance of meters, gloves or other safety equipment. • Sign-off that they have received a copy of the Workplace Electrical Safety Program and understand the contents. • Apply the Lockout Program whenever possible instead of working on exposed energized equipment. Page 8 of 34 Facilities Operations Prepared by Physical Resources – Safety, Health, Environment & Risk Management WATERLOO| Brantford | Kitchener | Toronto 4. GENERAL GUIDELINES The following work practices apply to all personnel working on energized equipment that poses an electrical hazard. a.) Only qualified persons are permitted to work on electrical systems or components where there is a potential for exposure to energized and/or exposed components. b.) Only qualified persons shall place equipment into an electrically safe work condition before performing work. The exception to this statement is where de-energizing this equipment introduces additional hazards, or is infeasible to do so. c.) Do not endanger oneself or others by attempting to rescue shock victims unless trained in appropriate first aid response and are qualified to disconnect the means of energization. d.) When actuating any disconnecting means, it is important to stand to one side of the device and using the left hand (while facing away) operate the disconnecting means. e.) All electrical equipment, circuits and conductors shall be considered to be energized until voltage verification is performed. Only approved meters as specified in Appendix B (Table 1) will be used to verify the absence of voltage. f.) While performing work on any de-energized equipment, a personal lock (coupled with an approved hasp) shall be applied in accordance with the WLU Lockout Program. If the lockout is required to extend beyond a scheduled shift, the personal lock shall be substituted for a trade lock. g.) All rings, bracelets, other jewelry and any other conductive material shall not be worn while performing any energized work on electrical equipment. h.) Only fiberglass fish tapes shall be used when fishing conductors through an existing installation. In applications where there may be the exposure to energized parts, equipment shall be placed into an electrically safe work condition before performing work. i.) Adequate lighting is necessary to perform all electrical tasks. If general building/emergency lighting is not available, the use of a portable light source such as a head lamp or portable work light is recommended. Do not under any circumstances; attempt to work in the dark. Page 9 of 34 Facilities Operations Prepared by Physical Resources – Safety, Health, Environment & Risk Management WATERLOO| Brantford | Kitchener | Toronto 5. PROCEDURES 5. 1 Electrical System Safe Work Practices a.) No university personnel shall work on any electrical equipment, systems or machines above 750 volts unless specifically trained and authorized to perform the work. For the purposes of this document, such work shall be classified as ‘High Voltage’. b.) Personal Protective Equipment (PPE) and other related safety equipment shall be stored and used in accordance with manufacturer’s recommendations. Regular tests and inspections will be required to ensure that any equipment is still fit for purpose and use. Equipment can include, but is not limited to: voltage-rated gloves, flame resistant (FR) clothing, hearing protection, face shields, double layer hoods and eye protection. c.) All arc-rated clothing shall be laundered and maintained as per Westex Inc. cleaning and maintenance guide for Flame Resistance Protective Clothing Fabrics. Prior to establishing an electrically safe work condition (Lockout), all qualified persons working within the arc flash protection boundary of an exposed energized component must be suitably protected with personal protective equipment for that specific hazard/risk category (Level). Once an electrically safe work condition has been established and verified, some personal protective equipment may be removed. d.) Conductive articles of clothing, jewelry (such as watchbands, bracelets, rings, key chains, necklaces, metal frame glasses, etc.) shall not be worn where they present an electrical contact hazard with energized parts. e.) Electrically insulated tools (1000V rated) shall be used whenever working on electrically energized equipment. f.) Blind reaching into electrical enclosures is prohibited. Employees must ensure they have enough illumination to perform a job safely. g.) Elevated work above 3 meters on energized electrical systems or equivalent shall be performed in an approved personnel lift. h.) Under no circumstances shall an electrical bus be used to support a ladder. i.) Only non-conductive (fiberglass or wooden) ladders shall be used by Physical Resources. j.) While performing work in a confined space that contains exposed energized parts, the use of non-conductive shields, barriers, tools or insulating materials is required to avoid inadvertent contact with these parts. For additional information on working in confined space environments, please refer to the SHERM document (FACL-026). k.) Any person who does not meet the requirements of an ‘Authorized/Qualified Person’ as described in the Definition section of this document (Section 2), or any person not suitably equipped to perform the task in question, shall maintain a minimum distance of 10 feet from any exposed energized Page 10 of 34 Facilities Operations Prepared by Physical Resources – Safety, Health, Environment & Risk Management WATERLOO| Brantford | Kitchener | Toronto electrical equipment unless indicated otherwise on an arc flash hazard analysis label. 5.2 Portable Electric Tools a.) Portable electric tools shall be CSA approved and double insulated, and be suitable for the application, environment and voltage they are to be used in/on. b.) All portable electric tools shall be visually inspected prior to each use. The casing (housing) of the equipment and cords connected to these tools shall be free of damage. Any damaged electric tool shall be immediately removed from service and reported to the supervisor for replacement. c.) Portable ground fault interrupters shall be used at all times while working in wet areas. 5.3 Maintenance, Repair, Overhaul and Installation Work Work shall never be performed on energized equipment. All sources of power must be disconnected and locked out prior to work commencing. However, a qualified Wilfrid Laurier University tradesperson, wearing appropriate PPE and using listed and rated insulated tools, may perform the following work on energized equipment: a.) Testing - Including voltage, current, phasing meter checks, system tuning and other testing functions. b.) Exploratory - Circuit identification/tracing. c.) Maintenance - Replacing fuses, which are not under load and de-energized, on electrical systems operating at 600 Volts or below. d.) Installation - Install devices rated at 120 VAC or below and designed/engineered by the manufacturer to be installed or removed without de-energizing. 5.4 Arc Flash Hazard Analysis As part of ongoing safety improvement initiatives, electrical systems in all owned University buildings are now beginning to use an arc flash hazard analysis to determine the potential hazards when performing live work. The arc flash hazard analysis, performed by a licensed engineering services company, shall determine the following information as it pertains to a given system: a) The arc flash boundary; b) The incident energy at the working distance; and c) The PPE that personnel within the arc flash boundary shall use. Where a detailed arc flash hazard analysis has been performed, the information in section 5.4.1 shall apply. This information is shown on a sample label in Appendix F (Figure 2). In all other cases, the information in section 5.4.2 shall be adhered to. Page 11 of 34 Facilities Operations Prepared by Physical Resources – Safety, Health, Environment & Risk Management WATERLOO| Brantford | Kitchener | Toronto Note: 1) The hazard analysis shall be updated whenever a significant modification or renovation takes place. It shall also be updated no more than 5 years to the date from the initial assessment, to account for any other modifications to the system potentially affecting the results of the current analysis. 5.4.1 Selection Based on Incident Energy Analysis An incident energy analysis shall determine the incident energy exposure to the worker (in cal/cm2). The incident energy level indicated shall be based on the working distance of the worker’s upper body from a prospective arc source for the task to be performed. Arc-rated clothing and PPE shall be used by the worker and selected on the basis of the incident energy exposure associated with the specific task. As incident energy levels raise the closer a worker is to a hazard, additional PPE may be required for any parts of the body closer than the distance identified in the assessment. For assistance in selection of PPE to suit the task being performed, please refer to Appendix C (Table 2). Note: 1) Where an incident energy analysis has been performed, this information shall supersede any hazard/risk category and/or PPE recommendations made in Appendix D (Tables 3 and 4) 5.4.2 Selection Based on Hazard/Risk Categories Where an incident energy analysis (as part of the arc flash hazard assessment) has not been performed, the information in Appendix D (Tables 3 and 4) shall be used to determine the appropriate hazard/risk category. Notes: 1) The information in Appendix C is taken directly from the CSA Z462-12 standard and is for use in situations where an incident energy calculation has not been performed. 2) Where a specific task is not listed in Appendix C, live work cannot safely proceed until an incident energy assessment is performed. This may include systems with larger than assumed short-circuit current capacity, or in systems with longer than assumed fault clearing times. 5.5 Personal Protective Equipment All Personal Protective Equipment (PPE) has an intended use and must be used as directed by the manufacturer’s literature. Using PPE for purposes outside of its intended use may result in injury to the user. PPE is selected based on the hazard to which employees are exposed. PPE designed to provide protection from electrical shock might not be adequate for protecting people from flash hazards. Similarly, PPE designed for flash protection may not provide protection from electrical shock. Voltage-rated gloves may be used for flash protection only when used with leather protectors. Page 12 of 34 Facilities Operations Prepared by Physical Resources – Safety, Health, Environment & Risk Management WATERLOO| Brantford | Kitchener | Toronto Prior to performing work, every authorized/qualified employee will determine the level of protection to be applied based on the information provided in Appendix C (Table 2). If at any time the authorised/qualified employee determines that additional PPE, or safety devices, are required for the work to be performed safely, they may request this and items required will be made available to them. PPE requirements shall be determined by the highest voltage that the worker is exposed to while performing the work, regardless of the voltage of the actual testing location. For example, if working near exposed live equipment of 600 volts while testing exposed live equipment of 120 volts, the requirements for 600 volts will apply. Selection of Personal Protective Equipment PPE will be selected and provided by the Physical Resources department with the assistance of Safety, Health, Environment and Risk Management (SHERM). Selection will take into account the anticipated hazards, voltage levels and conditions of the work to be performed. Additional factors that will be considered include: • The condition and age of the equipment to be worked on • The equipment design • Any barriers that may exist on/around the equipment General PPE Inspection and Maintenance All PPE used must be inspected in accordance with the manufacturer’s instructions and at a minimum, before each use. Where specific instructions exist for inspection of PPE, they shall be adhered to by the employee. Damaged PPE must never be used. Defective PPE must be tagged defective until repaired or destroyed. The employee’s immediate supervisor must be notified once a piece of PPE has been deemed unfit for use. Note: 1) The term PPE includes: FR clothing, voltage rated gloves, leather protectors, eye protection, safety footwear and any additional protective equipment provided by the Physical Resources department. 5.5.1 Shock Protection Voltage-rated Gloves Voltage-rated gloves (Class “0” Insulated Rubber Gloves) shall be used for electrical shock prevention. Only Type-II gloves, which are ozone-resistant and made of an elastomer, or combination of elastomeric compounds, and with a minimum class of "0" will be used. Note: 1) Class "0" gloves are rated to 1,000 volts, however are not to be used on any circuit greater than 750 volts. Page 13 of 34 Facilities Operations Prepared by Physical Resources – Safety, Health, Environment & Risk Management WATERLOO| Brantford | Kitchener | Toronto Inspection and Maintenance of Voltage-rated Gloves Prior to every use of the voltage-rated gloves, they must be visually inspected for any cuts, punctures, holes or damage that may affect their rating or effectiveness. The leather protector gloves must also be inspected before each use and be free of holes, tears, or other contamination. The insides of the leather protectors shall also be inspected for sharp or pointed objects that may otherwise damage voltage-rated rubber gloves. Any cleaning or maintenance of the voltage-rated gloves and/or leather protectors must be done as instructed by the manufacturer. Only approved powder is recommended for use on voltage-rated rubber products to prevent deterioration of the rubber. Voltage-rated Rubber Glove Testing Voltage-rated rubber gloves must be tested to ensure they are still effective on a regular schedule. Every in-service voltage-rated rubber glove and leather protector combination must be tested every 3 months. The testing will be done by a qualified external vendor in accordance with the Electrical & Utilities Safety Association (EUSA) Handbook. • WLU employees that have been issued voltage-rated gloves will be provided with a second pair while the initial pair of gloves is sent out for testing. Voltage-rated gloves returned from testing will be held in storage until the pair in use requires testing. Any voltage-rated rubber glove held in stock longer than four (4) months after a test will be retested before being placed in service. Voltage-rated Glove Storage Voltage-rated gloves shall be stored in a cool, dry place, not exposed to sunlight or ozone. Voltage-rated gloves will be allowed to take their natural shape while stored. They must be kept inside of protectors or in a bag, box, or container that is designed for and used exclusively for the gloves. They shall be inserted into their protective container with the fingers pointed upward. Voltage-rated gloves shall not be stored folded, creased, inside out, compressed, or in any manner that will cause stretching or compression. Voltage-rated gloves must be stored away from exposure to solvents, oils, greases or from vapours produced by these materials. Page 14 of 34 Facilities Operations Prepared by Physical Resources – Safety, Health, Environment & Risk Management WATERLOO| Brantford | Kitchener | Toronto Voltage-rated Glove Protectors Leather protectors for voltage rated-rubber gloves must be worn over the rubber gloves to protect from abrasion, cuts or punctures. The leather protectors shall not be used alone for shock protection at any time. Leather protectors are only used with the voltage-rated rubber gloves and are not to be used as general work glove. Where ever possible, the leather protectors must be kept clean and free of oil, grease or solvent contamination. Protectors that have been used for other purposes must not be used to protect voltage-rated rubber gloves and should be removed from service immediately. Removal from Service All voltage-rated rubber products that have been rejected by external testing, or have been found to be damaged during inspections, shall be defaced, cut up, or otherwise marked to identify that they are not to be used for electrical service, and then be disposed of from the workplace. All gloves to be removed from service should be reported to the supervisor immediately. A replacement pair of gloves should be ordered as soon as possible to replace the pair to be disposed of. 5.5.2 Arc Flash Protective Equipment Arc flash protective equipment shall be sufficient to protect the worker from the flash hazard associated with the task to be performed. For the purposes of this document, the arc flash protection is considered to be the outermost garment worn. Hand Protection Gloves used for flash protection must be long enough to cover body parts such as hands, wrists, and arms that are exposed to the flash hazard. Gloves shall be of sufficient length to cover exposed body parts until they overlap other flash protection, such as the sleeve of a flash-protection garment. The glove must cover any openings in the sleeve, such as the slit for the cuff. Arm Protection When flash protection is required for the arms, beyond the length that a glove will provide, a long-sleeve arc rated shirt is required. Short sleeves or rolled up sleeves are not permitted when working where there is a risk of flash. Page 15 of 34 Facilities Operations Prepared by Physical Resources – Safety, Health, Environment & Risk Management WATERLOO| Brantford | Kitchener | Toronto Eye Protection Safety glasses shall be used to protect the eyes from impact injuries due to flying or falling objects. Safety glasses must be worn while performing testing, troubleshooting or verification where there is a possibility of arc flash. Safety glasses worn shall be UV and IR rated, as well as CSA approved. Face shields shall be used to provide additional protection to the face. Face shields are not a replacement for safety glasses and safety glasses must be worn underneath the face shield at all times. Face shields must not be cracked or broken. All face shields shall be arc rated with a minimum Arc Thermal Performance value of 10 cal/cm2. Safety Footwear All Physical Resources employees are required to wear CSA approved safety footwear while performing any work. Employees who may work near live exposed electrical equipment must purchase and wear safety footwear approved by CSA for impact protection with a minimum rating of Class 1 (green tag or green triangle), and displaying the Ohm symbol (Ω) on a tag indicating they have been tested for electrical shock resistance. 5.5.3 Emergency Spotter The requirement for an emergency spotter does not apply to testing, troubleshooting or verification as outlined in Section 42.1(4) of Regulation 851 (Industrial Establishments). When performing work other than troubleshooting, testing or verification near energized electrical equipment with a nominal voltage of 300 volts or greater, there shall be a spotter present to assist in an emergency. The spotter must be certified in in appropriate first aid response and be qualified to disconnect the means of energization. The emergency spotter shall be in visual contact with the authorized/qualified person performing the work at all times, such that they can clearly see if the person is in difficulty and carry out a rescue in an emergency. It is imperative that the emergency spotter does not participate in the work near energized electrical equipment. The spotter shall be equipped with a suitable non-conductive device to remove a person from contact with the energized current in the event of an emergency. The spotter shall also be equipped with a suitable communication device (ie. cellular phone, 2 way radio) to contact Special Constable Service in order to activate the emergency protocol in the case of an accident. Page 16 of 34 Facilities Operations Prepared by Physical Resources – Safety, Health, Environment & Risk Management WATERLOO| Brantford | Kitchener | Toronto 5.6 Testing Equipment and Tools The following general directions shall apply to electrical test equipment, special tools, and their accessories: • They shall be rated for the circuits and equipment to which they are to be connected. • They shall be used in accordance with the manufacturer’s recommendations and are to be used only as intended. • They shall be CSA approved and have a 1000 VAC rating (or higher) and have a minimum Category III Rating. See Appendix B (Table 1) for additional information on the required test equipment. Voltage Testers The use of voltage testers shall be based upon the purpose of the work to be performed. Different types of voltage testers exist with specific uses and limitations. When testing for the absence or presence of voltage, a contact or noncontact voltage meter may be used, depending on the desired result of the metering. Each type of tester must comply with the requirements of this section. Contact Voltage Testers - Measuring Voltage and Troubleshooting The following features are required for meters used in measuring voltage and performing troubleshooting: • Grip protection on test probes. • Self-contained fault protection or limitation devices, such as internal currentlimiting fuses or probe current-limiting resistors. • Voltage/current path isolation between the probes and the selector switching device. • Compliance with applicable CSA standards and appropriate category/voltage ratings. Inspection - Before Use Electrical test instruments and all associated test leads, cables, power cords, probes, and connectors shall be visually inspected for external defects or damage before each use. If visible defects or evidence of damage that might expose an employee to injury are evident, the defective or damaged item shall not be used until any required repairs and tests have been made. The following items must be inspected prior to each use: • Grip protection on test probes is present and in good condition. Protection of Meters The employee shall maintain electrical test equipment in good working condition in accordance with the manufacturer's instructions. The employee is responsible to ensure that electrical test equipment and associated probes are stored in a manner that will protect them from moisture, dust, and will prevent damage or premature deterioration. Protective cases should be purchased with the equipment for storage purposes. Page 17 of 34 Facilities Operations Prepared by Physical Resources – Safety, Health, Environment & Risk Management WATERLOO| Brantford | Kitchener | Toronto Special tools Any tools or equipment that may be used in the course of testing, troubleshooting or verification must not be capable of conducting electrical current to the employee if they come into contact with an exposed live conductor. Fuse-Pullers Only devices designed for the purpose of pulling fuses shall be used to remove and install fuses. The fuse-pullers shall be of the appropriate size and style. 5.7 Barriers and Guarding The purpose of barriers and guarding are to provide insulation from and physical separation between an energized energy source and the worker. Wherever possible, barriers and guards will be permanently installed to reduce and eliminate inadvertent exposure to live electrical equipment. The installation of barriers or guarding requires planning and an appropriate risk assessment to avoid creating additional hazards. Insulation Insulating barriers can be made of voltage-rated rubber products, voltage-rated tape, certain plastics or composites. The material used for the barrier depends upon the task to be performed. Insulating barriers may be placed directly on energized conductors and parts to prevent inadvertent contact with body parts and tools. The barriers must be rated according to ASTM standards for, or above, the circuit voltage involved. An insulating barrier is normally not adequate to restrain significant physical force or to stop a puncture. The installation of insulating barriers should always be combined with the use of adequate PPE. Guarding Physical guarding shall never be placed directly on an energized part, or within the prohibited boundary, as defined by the hazard assessment of the work to be performed. Barriers are installed to provide a physical restraint to prevent body parts or tools from getting near energized parts. Physical guards may only be constructed of approved materials and only at the direction of the Area Manager, Facilities Operations or designate. No temporary guard of any material is to be used for any type of insulating or physical barrier without the specific permission of the Area Manager, Facilities Operations or designate. The installation of guards should always be combined with the use of adequate PPE. Page 18 of 34 Facilities Operations Prepared by Physical Resources – Safety, Health, Environment & Risk Management WATERLOO| Brantford | Kitchener | Toronto 5.8 Training Training will be provided to every qualified/authorized person who will be working on exposed energized electrical equipment. Only employees who have successfully completed this training program will be considered qualified to apply the Workplace Electrical Safety Program. Training in this policy will be provided to: • Electricians • HVAC Technicians • Gas Technicians • Operating Engineers • Others as determined by Wilfrid Laurier University SHERM department and Physical Resources. The content of the training will include the following: • Applicable legislation and codes • Hazards likely to be encountered working on energized electrical equipment • Safe Work Practices • Use of gloves and other PPE • Inspection and maintenance of gloves and other PPE • Common errors and misconceptions • Correct application and use of meters and tools • Limitations of meters and tools • Inspection of the meters and tools • Understanding of instrument indication or information provided • Proper inspection, maintenance and storage of meters and tools Successful completion of training requires: • Full attendance of the course with no interruptions or temporary absences • Completion and passing of a comprehension test at the end of the course • The instructor is satisfied the participant has learned and understood the procedures Page 19 of 34 Facilities Operations Prepared by Physical Resources – Safety, Health, Environment & Risk Management WATERLOO| Brantford | Kitchener | Toronto 6. APPENDICES Appendix A: Relevant Standards/Legislation/Policies • • • • • • • • Ontario Occupational Health and Safety Construction Regulations Ontario Regulation 851 (Industrial Establishments) Ontario Electrical Safety Code - 25th Edition/ 2012 Canadian Standards Association (CSA) Canadian Electrical Code (C22.1) – 2012 Revision Canadian Standards Association (CSA) Control of Hazardous Energy - Lockout and Other Methods (CSA Z460) – 2010 Revision Canadian Standards Association (CSA) Workplace Electrical Safety (CSA Z462) – 2012 Revision NFPA 70E- Standard for Electrical Safety in the Workplace EUSA- Electrical Utilities Safety Association, Handbook Appendix B: Required Test Equipment Table 1 Required Meter Equipment Type Voltmeter - (CSA approved 1000 volt AC and/or Cat. III rated) as a minimum Multimeter - (CSA approved 1000 volt AC and/or Cat. III rated) as a minimum (Fluke 87V or equivalent) Clamp-on Meter - (CSA approved 1000 volt AC and/or Cat. III rated) as a minimum (Fluke 375 or equivalent) Page 20 of 34 Facilities Operations Prepared by Physical Resources – Safety, Health, Environment & Risk Management WATERLOO| Brantford | Kitchener | Toronto Appendix C: Minimum PPE Requirement for Common Low Voltage Tasks The contents of this section are taken directly from the CSA Z462-12 standard on Workplace Electrical Safety. Please note that these are to be used only as a guideline for PPE requirements. Where arc flash hazard labeling exists on equipment, this information shall supersede these guidelines. Please refer to section 4.3.7.3.15 of the CSA standard for additional information. Protective Clothing and Personal Protective Equipment Table 2 Hazard/risk category Protective clothing and PPE 0 Protective clothing, non-melting or untreated natural fibre (ie. untreated cotton, wool, rayon, silk, or blends of these materials) with a fabric weight at least 4.5 oz/yd2: • Shirt (long sleeve) • Pants (long) Protective equipment: • Safety glasses or safety goggles (SR) • Hearing protection (ear canal inserts) • Heavy duty leather gloves (AN) (Note 1) 1 Arc-rated clothing, minimum arc rating of 4 cal/cm2 (Note 3): • Arc-rated long-sleeve shirt and pants or arc-rated coverall • Arc-rated face shield or arc flash suit hood (Note 2) • Arc-rated jacket, parka, rainwear, or hard hat liner (AN) Protective equipment: • Hard Hat • Safety glasses or safety goggles (SR) • Hearing protection (ear canal inserts) • Heavy duty leather gloves (AN) (Note 1) • Leather work shoes (AN) 2 Arc-rated clothing, minimum arc rating of 8 cal/cm2 (Note 3): • Arc-rated long-sleeve shirt and pants or arc-rated coverall • Arc-rated flash suit hood; or arc-rated face shield (Note 2) and arc-rated balaclava • Arc-rated jacket, parka, rainwear, or hard hat liner (AN) Protective equipment: • Hard Hat • Safety glasses or safety goggles (SR) • Hearing protection (ear canal inserts) • Heavy duty leather gloves (AN) (Note 1) • Leather work shoes (AN) Page 21 of 34 Facilities Operations Prepared by Physical Resources – Safety, Health, Environment & Risk Management WATERLOO| Brantford | Kitchener | Toronto Table 2 (Continued) Hazard/risk category Protective clothing and PPE 3 Arc-rated clothing, selected so that the system arc rating meets the required minimum arc rating of 25 cal/cm2 (Note 3): • Arc-rated long-sleeve shirt (AR) • Arc-rated pants (AR) • Arc-rated coverall (AR) • Arc-rated arc flash suit jacket (AR) • Arc-rated arc flash suit pants (AR) • Arc-rated arc flash suit hood • Arc-rated gloves (Note 1) • Arc-rated jacket, parka, rainwear, or hard hat liner (AN) Protective equipment: • Hard Hat • Safety glasses or safety goggles (SR) • Hearing protection (ear canal inserts) • Leather work shoes 4 Arc-rated clothing, selected so that the system arc rating meets the required minimum arc rating of 40 cal/cm2 (Note 3): • Arc-rated long-sleeve shirt (AR) • Arc-rated pants (AR) • Arc-rated coverall (AR) • Arc-rated arc flash suit jacket (AR) • Arc-rated arc flash suit pants (AR) • Arc-rated arc flash suit hood • Arc-rated gloves (Note 1) • Arc-rated jacket, parka, rainwear, or hard hat liner (AN) Protective equipment: • Hard Hat • Safety glasses or safety goggles (SR) • Hearing protection (ear canal inserts) • Leather work shoes Legend: AN = as needed (optional) AR = as required SR = selection required Notes: (1) If rubber insulating gloves with leather protectors are required by Appendix C (Table 3), additional leather or arc-rated gloves shall not be required. The combination of rubber insulating gloves with leather protectors satisfies the arc flash protection requirement. (2) Face shields shall meet the requirements of clause 4.3.7.3.10 (c). An arc flash suit hood may be worn in lieu of a face shield. Arc rating is defined in the Definition section of this document (Section 2). Page 22 of 34 Facilities Operations Prepared by Physical Resources – Safety, Health, Environment & Risk Management WATERLOO| Brantford | Kitchener | Toronto Appendix D: Hazard Hazard/risk category classifications and use of PPE – AC Equipment Table 3 Panelboards or other equipment rated 240 V and below Parameters: Maximum of 25 kA short circuit current available Maximum of 0.03 s (2 cycle) fault clearing time Minimum 455 mm (18 in) working distance Potential arc flash boundary using above parameters: 470 mm (19 in) Task(s) performed on energized equipment Perform infrared thermography and other non-contact inspections outside the restricted approach boundary Circuit breaker (CB) or fused-switch operation with covers on CB or fused-switch operation with covers off Work on exposed energized electrical conductors and circuit parts, including voltage testing Remove/install CBs or fused switches Removal of bolted covers (to expose bare energized electrical conductors and circuit parts) Opening hinged covers (to expose bare energized electrical conductors and circuit parts) Work on exposed energized electrical conductors and circuit parts of utilization equipment fed directly by a branch circuit of the panelboard Hazard/Risk Category Rubber Insulating Gloves Required? 0 N Insulated and insulating hand tools required? N 0 N N 0 Y* N 1 Y Y 1 1 Y N Y N 0 N N 1 Y Y * Designates an enhancement to the recommendations posted in the CSA Z462-12 standard. This applies only to the use of Rubber Insulating Gloves. Page 23 of 34 Facilities Operations Prepared by Physical Resources – Safety, Health, Environment & Risk Management WATERLOO| Brantford | Kitchener | Toronto Panelboards or switchboards rated more than 240 V and up to 600 V (with moulded-case or insulated-case circuit breakers) Parameters: Maximum of 25 kA short circuit current available Maximum of 0.03 s (2 cycle) fault clearing time Minimum 455 mm (18 in) working distance Potential arc flash boundary using above parameters: 755 mm (30 in) Task(s) performed on energized equipment Perform infrared thermography and other non-contact inspections outside the restricted approach boundary CB or fused-switch operation with covers on CB or fused-switch operation with covers off Work on exposed energized electrical conductors and circuit parts, including voltage testing Remove/install CBs or fused switches Removal of bolted covers (to expose bare, energized electrical conductors and circuit parts) Opening hinged covers (to expose bare, energized electrical conductors and circuit parts) Work on exposed energized electrical conductors and circuit parts of utilization equipment fed directly by a branch circuit of the panelboard or switchboard Hazard/Risk Category Rubber Insulating Gloves Required? 1 N Insulated and insulating hand tools required? N 0 N N 1 Y N 2 Y Y 2 Y Y 1 N N 0 N N 2 Y Y * Designates an enhancement to the recommendations posted in the CSA Z462-12 standard. This applies only to the use of Rubber Insulating Gloves. Page 24 of 34 Facilities Operations Prepared by Physical Resources – Safety, Health, Environment & Risk Management WATERLOO| Brantford | Kitchener | Toronto 600 V (nominal) class motor control centres (MCCs) Parameters: Maximum of 65 kA short circuit current available Maximum of 0.03 s (2 cycle) fault clearing time Minimum 455 mm (18 in) working distance Potential arc flash boundary using above parameters: 1.35 m (53 in) Task(s) performed on energized Hazard/Risk Rubber equipment Category Insulating Gloves Required? Perform infrared thermography and other non-contact inspections outside the restricted approach boundary CB, fused-switch, or starter operation with enclosure doors closed Reading a panel meter while operating a meter switch CB, fused-switch, or starter operation with enclosure doors open Work on exposed energized electrical conductors and circuit parts, including voltage testing Work on control circuits with exposed energized electrical conductors and circuit parts 120 V or below, exposed Work on control circuits with exposed energized electrical conductors and circuit parts greater than 120 V, exposed Application of temporary protective grounding equipment after voltage test Work on exposed energized electrical conductors and circuit parts of utilization equipment fed directly by a branch circuit of the panelboard or switchboard 1 N Insulated and insulating hand tools required? N 0 N N 0 N N 1 Y* N 2 Y Y 0 Y Y 2 Y Y 2 Y N 2 Y Y * Designates an enhancement to the recommendations posted in the CSA Z462-12 standard. This applies only to the use of Rubber Insulating Gloves. Page 25 of 34 Facilities Operations Prepared by Physical Resources – Safety, Health, Environment & Risk Management WATERLOO| Brantford | Kitchener | Toronto 600 V (nominal) class motor control centres (MCCs) Parameters: Maximum of 42 kA short circuit current available Maximum of 0.33 s (20 cycle) fault clearing time Minimum 455 mm (18 in) working distance Potential arc flash boundary using above parameters: 4.20 m (165 in) Task(s) performed on energized Hazard/Risk Rubber Insulated equipment Category Insulating and Gloves insulating Required? hand tools required? Insertion or removal of individual 4 Y N starter “buckets” from MCC Removal of bolted covers (to expose 4 N N bare electrical conductors and circuit parts) Opening of hinged covers (to expose 1 N N bare electrical conductors and circuit parts) * Designates an enhancement to the recommendations posted in the CSA Z462-12 standard. This applies only to the use of Rubber Insulating Gloves. Page 26 of 34 Facilities Operations Prepared by Physical Resources – Safety, Health, Environment & Risk Management WATERLOO| Brantford | Kitchener | Toronto 600 V (nominal) class switchgear (with power circuit breakers or fused switches) and 600 V Class switchboards Parameters: Maximum of 35 kA short circuit current available Maximum of 0.5 s (30 cycle) fault clearing time Minimum 455 mm (18 in) working distance Potential arc flash boundary using above parameters: 5.90 m (233 in) Task(s) performed on energized equipment Perform infrared thermography and other non-contact inspections outside the restricted approach boundary CB or fused-switch operation with enclosure doors closed Reading a panel meter while operating a meter switch CB or fused-switch operation with enclosure doors open Work on exposed energized electrical conductors and circuit parts, including voltage testing Work on control circuits with exposed energized electrical conductors and circuit parts 120 V or below, exposed Work on control circuits with exposed energized electrical conductors and circuit parts greater than 120 V, exposed Insertion or removal (racking) of CBs from cubicles, doors open or closed Application of safety grounds after voltage test Removal of bolted covers (to expose bare energized electrical conductors and circuit parts) Opening of hinged covers (to expose bare energized electrical conductors and circuit parts) Hazard/Risk Category Rubber Insulating Gloves Required? 2 N Insulated and insulatin g hand tools required? N 0 N N 0 N N 1 Y* N 2 Y Y 0 Y Y 2 Y Y 4 Y* N 2 Y N 4 N N 2 N N * Designates an enhancement to the recommendations posted in the CSA Z462-12 standard. This applies only to the use of Rubber Insulating Gloves. Page 27 of 34 Facilities Operations Prepared by Physical Resources – Safety, Health, Environment & Risk Management WATERLOO| Brantford | Kitchener | Toronto Other 600V class (277 to 600V, nominal) equipment Parameters: Maximum of 65 kA short circuit current available Maximum of 0.03 s (2 cycle) fault clearing time Minimum 455 mm (18 in) working distance Potential arc flash boundary using above parameters: 1.35 m (53 in) Lighting or small power transformers (600V nominal) Task(s) performed on energized Hazard/Risk equipment Category Removal of bolted covers (to expose bare energized electrical conductors and circuit parts) Opening of hinged covers (to expose bare energized electrical conductors and circuit parts) Work on exposed energized electrical conductors and circuit parts, including voltage testing Application of temporary protective grounding equipment after voltage test Revenue meters (kW-h at primary voltage and current) insertion or removal Cable trough or tray cover removal or installation Miscellaneous equipment cover removal or installation Work on energized electrical conductors and circuit parts, including voltage testing Application of temporary protective grounding equipment after voltage test Insertion or removal of plug-in devices into or from busways Rubber Insulating Gloves Required? Insulated and insulatin g hand tools required? 2 N N 1 N N 2 Y Y 2 Y N 2 Y N 1 N N 1 N N 2 Y Y 2 Y N 2 Y* N * Designates an enhancement to the recommendations posted in the CSA Z462-12 standard. This applies only to the use of Rubber Insulating Gloves. Page 28 of 34 Facilities Operations Prepared by Physical Resources – Safety, Health, Environment & Risk Management WATERLOO| Brantford | Kitchener | Toronto Hazard/risk category classifications and use of PPE – DC Equipment Table 4 Storage batteries, direct current switchboards and other DC supply sources, greater than 100 V, less than 250V Parameters: Voltage: 250 V Maximum arc duration and working distance: 2 s at 455 mm (18 in) Task(s) performed on energized equipment Work on energized electrical conductors and circuit parts, including voltage testing where arcing current is greater than 1 kA and less than 4 kA. Potential arc flash boundary using above parameters at 4 kA = 910 mm (36 in) Work on energized electrical conductors and circuit parts, including voltage testing where arcing current is greater than 4 kA and less than 7 kA. Potential arc flash boundary using above parameters at 1 kA = 1.20 m (48 in) Work on energized electrical conductors and circuit parts, including voltage testing where arcing current is greater than 7 kA and less than 15 kA. Potential arc flash boundary using above parameters at 15 kA = 1.85 m (72 in) Hazard/ Risk Category* Rubber Insulating Gloves Required? 1 Y Insulated and insulatin g hand tools required? Y 2 Y Y 3 Y Y * If acid exposure is possible, the clothing shall be protective from acid and arc rated to the hazard in accordance with ASTM F1891 or equivalent and evaluated by ASTM F1296 for acid protection. Page 29 of 34 Facilities Operations Prepared by Physical Resources – Safety, Health, Environment & Risk Management WATERLOO| Brantford | Kitchener | Toronto Storage batteries, direct current switchboards and other DC supply sources, greater than 250 V, less than 600V Parameters: Voltage: 600 V Maximum arc duration and working distance: 2 s at 455 mm (18 in) Task(s) performed on energized equipment Hazard/ Risk Category * Rubber Insulating Gloves Required? Insulated and insulatin g hand tools required? Y Work on energized electrical 1 Y conductors and circuit parts, including voltage testing where arcing current is greater than 1 kA and less than 1.5 kA. Potential arc flash boundary using above parameters at 1.5 kA = 910 mm (36 in) Work on energized electrical 2 Y Y conductors and circuit parts, including voltage testing where arcing current is greater than 1.5 kA and less than 3 kA. Potential arc flash boundary using above parameters at 3 kA = 1.20 m (48 in) Work on energized electrical 3 Y Y conductors and circuit parts, including voltage testing where arcing current is greater than 3 kA and less than 7 kA. Potential arc flash boundary using above parameters at 7 kA = 1.85 m (72 in) Work on energized electrical 4 Y Y conductors and circuit parts, including voltage testing where arcing current is greater than 7 kA and less than 10 kA. Potential arc flash boundary using above parameters at 10 kA = 2.45 m (96 in) * If acid exposure is possible, the clothing shall be protective from acid and arc rated to the hazard in accordance with ASTM F1891 or equivalent and evaluated by ASTM F1296 for acid protection.Notes: See Appendix C (Table 2) for a list of protective clothing and PPE for each hazard/risk category. Page 30 of 34 Facilities Operations Prepared by Physical Resources – Safety, Health, Environment & Risk Management WATERLOO| Brantford | Kitchener | Toronto Appendix E: Approach Boundaries to Energize Parts for Shock Protection Approach boundaries to energized electrical conductors or circuit parts for shock protection Table 5 Nominal voltage conductor to ground Less than 50 V 50 – 300 V 301 – 750 V 751 – 15 kV Limited Approach Boundary(1) Exposed Exposed movable fixed circuit conductor(2) part Not specified Not specified 3.0 m 1.0 m (10 ft 0 in) (3 ft 6 in) 3.0 m 1.0 m (10 ft 0 in) (3 ft 6 in) 3.0 m 1.5 m (10 ft 0 in) (5 ft 0 in) Restricted Approach Boundary(1) Prohibited Approach Boundary(1) Not specified Avoid Contact Not specified Avoid Contact 0.3 m (1 ft 0 in) 0.7 m (2 ft 2 in) 25 mm (0 ft 1 in) 0.2 m (0 ft 7 in) Notes: 1. The specified boundaries are minimum safe working distances from exposed energized electrical conductors. These values are to be added onto the minimum air insulation distances, as specified in Appendix D (Table 6). 2. A condition in which the distance between the conductor and a person is not under the control of the person. The term is normally applied to overhead line conductors supported by poles. 3. For systems 50 V or greater, the arc flash boundary is defined as the distance at which the incident energy equals 5 J/cm2 (1.2 cal/cm2). Minimum air insulation distances for avoiding flashover Table 6 Voltage Distance Less than or equal to 300 V 301 – 750 V 751 V – 2 kV 2.1 – 15 kV 1 mm (0 ft 0.03 2 mm (0 ft 0.07 5 mm (0 ft 0.19 39 mm (0 ft 1.5 Page 31 of 34 Facilities Operations in) in) in) in) Prepared by Physical Resources – Safety, Health, Environment & Risk Management WATERLOO| Brantford | Kitchener | Toronto Appendix F: Supporting Information for Electrical Safety Program Limits of Approach Figure 1 Boundaries for Arc Flash and Shock Protection Figure 2 Page 32 of 34 Facilities Operations Prepared by Physical Resources – Safety, Health, Environment & Risk Management WATERLOO| Brantford | Kitchener | Toronto Arc Flash Hazard Analysis Label Figure 3 Page 33 of 34 Facilities Operations Prepared by Physical Resources – Safety, Health, Environment & Risk Management WATERLOO| Brantford | Kitchener | Toronto 7. REVISION HISTORY Revision 00 01 02 Date October 1, 2007 January 9, 2009 July 29, 2014 Page 34 of 34 Facilities Operations Comments SOP comes into effect Annual Review, no changes Review as per new CSA Z46212 standard. Major modifications to document. Initials EOHS EOHS Physical Resources Prepared by Physical Resources –