MODU-FIRE® FD 1500-2000 Outdoor Boiler Kit (Rev. 1.0 (09/4/2013) 1004905904 MODU-FIRE® FORCED DRAFT 1500-2000 OUTDOOR BOILER KIT GUIDE This manual is to be used in conjunction with the MODU-FIRE® FD 1500-2000 Installation & Owner’s Manual (latest edition). C.S.A Design-Certified Complies with ANSI Z21.13/CSA 4.9 Gas-Fired Low Pressure Steam and Hot Water Boilers ASME Code, Section IV Certified by Harsco Industrial, Patterson-Kelley C.S.A Design-Certified Complies with ANSI Z21.13/CSA 4.9 Gas-Fired Low Pressure Steam and Hot Water Boilers Model #:_______ Serial #:_____________________ Installation Date: ___________________________________ Harsco Industrial, Patterson-Kelley 155 Burson Street, East Stroudsburg, PA 18301 Telephone: 570.476.7261 Toll Free: 877.728.5351 Facsimile: 570.476.7247 www.harscopk.com © 2014 Harsco Corporation. All Rights Reserved. MODU-FIRE FD 1500-2000 Outdoor Boiler Kit Table of Contents 1.0 INTRODUCTION...................................................................................................................... 5 1.1 RECOMMENDED PIPING MODU-FIRE FD 1500-2000 OUTDOOR BOILER KIT ......................... 5 2.0 INSTALLATION ....................................................................................................................... 6 2.1 REQUIRED TOOLS AND PARTS ............................................................................................. 6 2.1.1 Tools............................................................................................................................... 6 2.1.2 Parts ............................................................................................................................... 6 2.2 OUTDOOR ENCLOSURE INSTALLATION ............................................................................ 7,8,9 2.3 EXHAUST VENT SYTSTEM INSTALLATION .....................................................................10,11,12 2.4 ELECTRICAL CONNECTIONS ............................................................................................... 12 3.0 MAINTENANCE..................................................................................................................... 13 4.0 ASSEMBLY DRAWINGS ................................................................................................. 14,15 4.1 ASSEMBLY DRAWING MODU-FIRE FD 1500-2000........................................................ 14,15 2 MODU-FIRE FD 1500-2000 Outdoor Boiler Kit The information contained in this document is subject to change without notice from Harsco Industrial, Patterson Kelley. The following words are used in this manual to denote the degree of seriousness of the individual hazards. Used to indicate an imminently hazardous situation which, if not avoided, will result in death or serious injury. This signal word is to be limited to the most extreme conditions. or serious injury. Indicates a potentially hazardous situation which, if not avoided, could result in death Used to indicate a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices. NOTICE/NOTE - NOTICE is the preferred signal word to address practices not related to personal injury. The safety alert symbol is not used with this signal word. Extensive safety information is contained in the MODU-FIRE FD 1500-2000 Installation & Owner’s Manual (latest edition) as well as warnings, installation requirements and diagrams. See MODU-FIRE FD 1500-2000 Installation & Owner’s Manual for specific safety requirements, warnings, installation requirements and diagrams. These instructions are a supplemental document which should be used in conjunction with the MODU-FIRE FD 1500-2000 Installation & Owner’s Manual for your specific MODU-FIRE Boiler. The boiler and these instructions is for outdoor use only. Incorrect installation may result in injury or death. 3 MODU-FIRE FD 1500-2000 Outdoor Boiler Kit The MODU-FIRE FD 1500-2000 Installation & Owner’s Manual (latest edition) must be used in conjunction with this manual for safe and proper installation of this boiler. The boiler and these instructions are for outdoor installation. Incorrect installation may result in injury or death. Shut off and lockout / tagout all utilities which may be hazardous, including electricity, gas, water, etc. before installing the MODU-FIRE FD 1500-2000 Outdoor Boiler kit. Improper use or failure to lockout / tagout hazards may result in injury. The boiler and these instructions are for outdoor installation. Do not install in any enclosure without proper venting. All exhaust venting must be outdoors. All installations of venting systems should be done only by qualified venting systems personnel. Venting must be installed in accordance with vent system manufacturer’s installation instructions and this manual. Installing a boiler or vent system using improper installation methods or materials can result in serious injury or death due to fire or asphyxiation from carbon monoxide or other poisonous gases. Breathing exhaust fumes may cause serious personal injury or death. 4 MODU-FIRE FD 1500-2000 Outdoor Boiler Kit 1.0 INTRODUCTION 1.1 RECOMMENDED PIPING MODU-FIRE FD 1500-2000 OUTDOOR BOILER KIT FIG 1 FIG 2 5 MODU-FIRE FD 1500-2000 Outdoor Boiler Kit The completed boiler is shown above. Special field installation procedures are required to complete the outdoor enclosure installation on the boiler. These additional procedures are described in this manual. This manual is a supplement to the MODU-FIRE FD 1500-2000 Installation & Owner’s Manual (latest edition). This and all boilers require proper installation, electrical connections, combustion air and flue vent installation, gas piping, water piping, as well as proper startup and service. This boiler can be used indoors with proper venting to outdoors and standard default parameters. Call Harsco Industrial-Patterson-Kelley service technicians for assistance at (570) 476-8695. Be sure to identify your boiler and its specific installation requirements. 2.0 Installation Additional parts are supplied with the boiler requiring installation in the field. Additional outdoor specific customer supplied parts required as well. 2.1 REQUIRED TOOLS AND PARTS 2.1.1 Tools The following tools are required for the completion of the MODU-FIRE FD 1500-2000 outdoor boiler kit: Screwdriver (Phillips) Screwdriver (Flat Head) Drill power driver T-30 Torx Bit Driver Pliers 2.1.2 Parts (Supplied by Harsco Industrial, Patterson-Kelley) 2300000597: ENCL,FD_MODU,OUT-DOOR,1500-2000 2630000212-1/8 gasket tape 16 FT. 2620000178, ¼-20X3/4 (47) Torx Screws1004500467: (1) Tube Clear RTV Silicone 2300000612- STACK,6",FD_MODU,OUT-DOOR,1500-2000 6 MODU-FIRE FD 1500-2000 Outdoor Boiler Kit 2.2 OUTDOOR ENCLOSURE INSTALLATION 1. Before installing outdoor enclosure, use silicone provided to seal all seams, as shown in figure 3. 2. Remove drain plug from bottom of cabinet. 3. Install gasket to the boiler sides and bottom panel, as shown in Figure 3 threaded holes for front panel should be covered and centered under gasket when installed to ensure proper seal. FIG 3 7 MODU-FIRE FD 1500-2000 Outdoor Boiler Kit FIG 4 FIG 5 8 MODU-FIRE FD 1500-2000 Outdoor Boiler Kit 4. Remove (8) ¼-20X3/4 Philips Screws from the boiler, 2 per corner. 5. Install the 4 mounting brackets, as shown on page 8, (Figure 4 & 5) using the (8) ¼-20X3/4 Torx Screws. The front brackets will be located 25-9/16” from the ground, the brackets on back of boiler will be located 26-1/16” from the ground. Reference picture above for proper bracket orientation. 6. Reference page 14 Assembly drawings for correct bracket height. 7. Install the left and right side panels using (4) ¼-20X3/4 Torx mounting screws, 2620000178, 4 screws per bracket. FIG 6 8. Install lower panels to the front and back sides as shown in Figure 7 using 8X-2620000178 per panel, followed by the top panel to the front and back sides, the top panels will be held in place using the fasteners that are attached to the panel. A flat head screw driver can be used to fasten the top panels. 9. Install the roof of the enclosure as shown in Figure 7 using the fasteners provided. 12X2620000178. 9 MODU-FIRE FD 1500-2000 Outdoor Boiler Kit FIG 7 2.3 EXHAUST VENT SYSTEM INSTALLATION The boiler vent should be installed per this manuals instruction. The information contained herein should be used as a guide only and is not intended to be used in lieu of qualified technical expertise. Failure to comply may result in injury or death. See MODU-FIRE FD 1500-2000 Installation & Owner’s Manual (latest edition) for additional venting requirements. Do not use CPVC venting. The MODU-FIRE FD 1500-2000 Outdoor Boiler requires a category IV exhaust. The exhaust vent must extend at least three (3) feet above the air intake or at least two (2) feet above the highest part of any independent structure within ten (10) feet of the vent. Boiler clearance for combustibles / non-combustibles should be maintained per MODU-FIRE FD 1500- 2000 Installation & Owner’s Manual (latest edition). 10 MODU-FIRE FD 1500-2000 Outdoor Boiler Kit Recommended Venting Kit Venting Kit FD 1500-2000 P/K Part # 2300000612 FIG 8 1. Install 8”-6” UCD Adapter, followed by the 6” 88 Degree Boot Tee. Install (2)6”X48”LG Double Wall Vent Stack as shown in Figure 8. Fasten stack using the 6” Wall Bracket to the stack support bracket as shown in Figure 9. 2. The Vent should have seals or gaskets present to contain the positive pressure exhaust. These seals must be installed properly. When the vent manufacturer requires the use of a silicone sealant, only an approved high temperature RTV silicone shall be used. 11 MODU-FIRE FD 1500-2000 Outdoor Boiler Kit FIG 9 2.4 ELECTRICAL CONNECTIONS Use water proof conduit and seal tight connectors to the boiler. Electrical access plugs are located on the left side of the boiler as shown in Figure 10. Before starting the boiler, check to ensure that the proper electrical service is connected to the boiler. FIG 10 12 MODU-FIRE FD 1500-2000 Outdoor Boiler Kit See MODU-FIRE FD 1500-2000 Installation & Owner’s Manual (latest edition) for specific electrical requirements and diagrams. Incorrect electrical connections may result in severe injury or death. 3.0 Maintenance The MODU-FIRE outdoor boiler requires all of the maintenance as described in MODU-FIRE FD 15002000 Installation & Owner’s Manual (latest edition) as well as the additional maintenance listed below. These additional maintenance items should be performed monthly. 1) Check for flue gas recirculation into the air inlet. Flue gas recirculation indicates that the vent is not installed properly for local conditions. 2) Check for freezing of the condensate lines. Frozen lines will result in boiler malfunction. Operation of the boiler in cold temperatures may require the use of heat trace lines for the boiler condensate trap, relief valve, and drain. 3) Check for inlet air box, stack and safety relief valve obstructions due to outdoor debris such as but not limited to leaves, insects, snow, branches and other blockages. 13 MODU-FIRE FD 1500-2000 Outdoor Boiler Kit 4.0 Assembly Drawings 4.1 ASSEMBLY DRAWING MODU-FIRE FD 1500-2000 14 MODU-FIRE FD 1500-2000 Outdoor Boiler Kit 15 MODU-FIRE FD 1500-2000 Outdoor Boiler Kit NOTES: 16