8
5
IMPORTANT SAFETY INSTRUCTIONS
WARNING: FAILURE TO FOLLOW THESE INSTRUCTIONS AND WARNINGS MAY RESULT
IN DEATH, SERIOUS INJURY OR SIGNIFICANT PROPERTY DAMAGE.
For your protection, read and follow these warnings and instructions carefully before installing or maintaining this equipment. These instructions do not attempt to cover all installation and maintenance situations. If you do not understand these instructions or additional information is required, contact Acuity Brands Lighting or your local Acuity Brands
Lighting distributor.
WARNING: RISK OF ELECTRIC SHOCK.
Never connect to, disconnect from or service while circuit equipment is energized.
WARNING: RISK OF FIRE.
Lamps are hot. Keep combustible materials away from hot parts. Observe lamp manufacturer’s warnings, recommendations and restrictions on lamp operation and maintenance. Make sure lamps are correctly installed. Use supply conductors with a minimum insulation temperature rating as specified on equipment.
WARNING: Do not use abrasive materials, glass cleaners or other solvents on reflector or lens. Use of these substances may damage fixture, which may result in personal injury.
WARNING: RISK OF PERSONAL INJURY.
This equipment may have sharp edges. Wear gloves to prevent cuts or abrasions when removing from carton, handling and maintaining this equipment.
•
Do not install a damaged fixture.
•
•
•
This equipment must be installed in accordance with all applicable installation codes and ordinances.
Proper grounding is required to ensure personal safety.
All service shall be performed by qualified service personnel. This equipment must be installed and maintained in accordance with all applicable installation codes by a person familiar with the construction and operation of this product and any hazards involved.
Observe lamp manufacturer’s recommendations and restrictions on lamp operation, including but not limited to ballast type, burning position, replacement and cycling. We recommend only lamps that comply with applicable ANSI standards.
All fluorescent lamps contain mercury. Follow disposal laws. See www.lamprecycle.org or contact your state environmental protection department for more information.
Acuity Brands Lighting, Inc. assumes no responsibility for claims arising out of improper or careless installation or handling of this product.
SAVE THESE INSTRUCTIONS
Acuity Brands Lighting, Inc.
One Lithonia Way
Conyers, GA 30012
770-922-9000
U21299
REV. A
11/23/2009
Installation Instructions for Fixture Conversion Retrofit Classified by Underwriters Laboratories, Inc.
Reflector Kit Type II: Reflector installation or replacement
Lamp holder relocation, removal or replacement
Ballast relocation, removal, replacement or addition
Installation Instructions
The installation of the Class R reflector kit Type II shall be performed by qualified personnel by completing the steps listed below.
This retrofit kit will consist of:
(1) end bracket/ballast assembly prewired with ballast and sockets mounted (ballast will be Class P with UL approvals and wiring diagram on label)
(1) splice box
(2) reflectors
(1) trim assembly and mounting hardware consisting of:
(2) quarter-turn fasteners
(60) #8 self-drilling TEK screws
Job packs will have screws bulk-packed with each pallet of kits.
Verify the contents of the retrofit kit by using the diagram below.
End Brackets/Splice Box Reflectors Trim
Remove existing components from host fixture.
Locate the fluorescent lighting fixture that is to be retrofitted. Turn off power.
WARNING: Electrical shock can occur during retrofit component installation if power is not turned off.
WARNING: Installation of this retrofit assembly requires a person familiar with the construction and operation of fluorescent luminaire electrical system and the hazard involved.
WARNING: Unless otherwise indicated, do not make or alter any opening in the compartment of wiring or electrical components during installation of this retrofit assembly.
WARNING: Ensure that existing fixture is and remains properly connected to building ground.
Use of any other than Lithonia Lighting supplied screws to install assembly may result in ungrounded fixture components.
Remove existing louver, lamps and channel cover. Identify power supply wires to disconnect. Follow installation step
2 wiring option A or B based on incoming supply wire. Remove ballast, sockets and lampholder bracket. Recycle or properly dispose of all components removed from host fixture.
Step Two:
Install relight assembly.
Install end brackets to 2’ length (socket side) of fixture. Install end bracket assembly by inserting bottom flange between bottom of fixture end plate and tee-bar. Center end bracket and attach using two 8-32 self-drilling TEK screws through the small holes at the top of the bracket (provided). Repeat on opposite end of fixture as shown.
Optional Step:
The 2 RT 8 RT/ 2 RT 5 RT Relight Assembly is shipped with two flexible reveal cover trim pieces. Some installations in existing lensed troffers can leave unsightly gaps between the side rail of the Relight door frames and the existing housing, which can leave old hinge and latch points exposed. The trim kit is designed to cover these to insure an attractive installation.
To install, slide the ends of the trim piece under the Relight end brackets as shown in in the photo. When they are fully in place, slide the notch of the trim piece towards the end bracket to fully seat the part. The part is flexible so this step can typically be completed either before or after full installation of the Relight assembly.
Optional Step:
FLANGE SITS ON T-BAR
BENEATH FIXTURE
BDP FLANGE SITS ON T-BAR
BENEATH FIXTURE
OLD BALLAST INPUT LEADS
BDP
FLANGE SITS ON T-BAR
BENEATH FIXTURE
FLANGE SITS ON T-BAR
BENEATH FIXTURE
END
BRACKET
TEK SCREW
TEK SCREW
END
BRACKET
TEK SCREWS
END
BRACKET
TEK SCREWS
END
BRACKET
BDP
FLANGE SITS ON T-BAR
BENEATH FIXTURE
TEK SCREW
TEK SCREWS
TEK SCREWS
END
BRACKET
BDP
BDP
TEK SCREW
Option A: is ( 2 ) # 18
BDP
Fixture Supply wire
BENEATH FIXTURE
BENEATH FIXTURE
1) Remove splice to existing ballast.
2) Connect # 18 AWG black and white to RT 8 RT/RT 5 RT ballast disconnect.
OLD BALLAST INPUT LEADS
OLD BALLAST INPUT LEADS BDP
FLANGE SITS ON T-BAR
BENEATH FIXTURE
BDP
TEK SCREWS
TEK SCREW
END
BRACKET
TEK SCREWS
END
BRACKET
TEK SCREWS
TEK SCREWS
END
BRACKET
BDP
END
BRACKET
TEK SCREWS
OLD BALLAST INPUT LEADS
BDP
Option B: Fixture supply wire is any other than (
BDP
BDP
2 ) # 18 AWG solid
1) Cut ballast input leads 6 "
TEK SCREWS from splice, and strip lead to
3/8”.
END
BRACKET
2) Connect #18 AWG black and white (old ballast input
END lead) to RT 8 RT/RT 5 RT ballast
BRACKET disconnect.
3) Install splice box to cover input wire splice, using two
TEK screws.
TEK SCREWS
TEK SCREW
BDP
END
BRACKET
Make wire connections and ground assembly to host fixture per option A or B based on existing fixture supply wire.
Option A and B (see photos on next page)
Option A and B (continued)
Install reflectors by inserting notched end of the reflector past lance in end bracket assembly and then rotating opposite end (end accepting twistlock fasteners) into fixture.
Shift reflector until notches are locked in place under lance and attach using a quarter-turn fastener twisting tabs that protrude through the reflectors
(spacers). Rotate second reflector
180° and repeat installation steps.
Install lamps. Use center slot in housing to clear lamp pins.
Install trim assembly by inserting hinge into slot of end bracket and sliding back into the corner. Repeat with opposite hinge, swing louver closed and rotate latches into locked position.
Trim hinges and latches from either side. Simply slide hinge into slot’s universal bracket assembly, close door and engage cam latches.
Help save our environment by recycling all remaining components.
Save these instructions.