Swirl diffuser DRS Installation and Maintenance NAD Klima® 144 Léger St, Sherbrooke (Qué) J1L 1L9 (819) 780-0111 1 866 531-1739 www.nadklima.com CONFIGURATION The different layouts possible with DRS meet many requirements. The variety of sizes available meet the most exacting performance needs. DRS - R - 100 DRS - Q - 100/300 DRS - Q - 100/603 The DRS is installed directly on the air duct via an adapted connector. It can be set up with a square front plate (12"X12" or 24"X24") DRS - R - 125 DRS - Q - 125/300 DRS - Q - 125/603 DRS - R - 180 DRS -Q - 180/300 DRS -Q - 180/603 DRS -Q - 215/300 DRS - R - 215 DRS - Q - 215/603 DRS - R - 250 DRS - Q - 250/603 DRS - R - 315 DRS - Q - 315/603 DRS - R - 355 DRS - Q - 355/603 2 COMPOSITION AND METHOD OF OPERATION conduit Structure The DRS air diffuser is composed of a front plate (1) with blades that are integrated into the exit of the diffuser (2).The diffuser is held up by a concealed central screw (3). raccord adapté (spigot) Operation The blades divide the airflow into numerous single high-induction airflows. The blades integrated into the exit of the diffuser ensure a horizontal air flow even at a slow rate, while cooling up to a minimum of 25% in variable air volume (VAV). MAINTENANCE LThe diffuser DRS of NAD Klima requires no special maintenance other than periodic cleaning. We recommend cleaning the diffuser with a multi-filament brush or duster microfiber that you will pass softly on the diffuser. Thermolacquered finish for easy cleaning of the diffuser as dust does not stick to it. 3 INSTALLATION IN A CEILING GYPSUM DRS-Q A) Opening in the gypsum Choose one of the three (3) options instalation shown at right. Option 1 et 2 Calculate the dimensions of the diffuser - Add 13 mm (1/2 ") in width and 13 mm (1/2 ") in length - Cut the square in the gypsum corresponding to these measures (Diffuser size + 13 mm) - Around this hole, insert a plaster frame and fix it NOTE : Make sure the final square hole is 13 mm (1/2 ") wider than the diffuser. Option 3 Calculate the dimensions of the diffuser - Remove 13 mm (1/2”) - Cut the square in the gypsum corresponding to these measures (Diffuser size - 13 mm) - Around this hole, insert a plaster frame and fix it NOTE : Make sure the final square hole is 13 mm (1/2 ") smaller than the diffuser. B) Install the plenum The plenum will be suspended through four (4) suspension holes provided for this purpose and use a metal wire. As indicated in the drawing to the right, install the plenum by adjusting its height ; according to option 1 and 2, the base of the plenum must enter 1/8 " in the hole or, option 3, the base plenum will press the drywall outside the hole Option 1 diffuser flush with the ceiling Plenum Gypsum Diffuser Plaster frame Option 2 diffuseur on T frame Plenum Gypsum Diffuser Plaster frame Option 3 diffuser under the ceiling Gypsum Plaster frame Diffuser Plenum Suspension hole . Cross bar . Balancing Damper Diffuser DRS-Q C) Install the diffuser Place the diffuser and fix it with the anchor screws provided for this purpose, in the cross bar at the center of the plenum anchor screw 4 Plenum INSTALLATION IN A CEILING GYPSUM DRS-R Option 1 A) Opening in the gypsum Choose one of the two (2) options instalation shown at right. Option 1 - Measure the diameter ( ØD ) of the diffuser - ADD 1/2 inch or (13 mm) - Cut a circle in the gypsum equivalent to this new measure [ ØD+1/2 inch (13 mm)] - Around this hole, place the gypsum guide and fix it. Note : Make sure that the final diameter of the hole is well from 6.5 to 10 mm (1/4 "to 3/8") wider than the diameter of the diffuser. Option 2 - Measure the diameter (ØD) of the diffuser - REMOVE 1/2 inch or (13 mm) - Cut a circle in the gypsum equivalent to this new measure [ØD-1/2 inch (13 mm)] - Around this hole, place the gypsum guide and fix it. Note : Make sure that the final diameter of the hole is well 13 mm to 19 mm (1/2 "to 3/4") smaller that the diameter of the diffuser. diffuser flush with the ceiling Gypsum Plenum Diffuser Plaster frame Option 2 diffuser below the ceiling Gypsum Plaster frame Plenum Diffuser Plenum Hanging plate (3) Cross bar Diffuseur DRS B) Install the plenum box The plenum shall be hanged by the hanging plate (3) with metal wire. As shown in the drawing on the right, install the plenum and adjust its height; according to option 1, the base of the plenum must enter 1/8 "into the hole. Or, according to option 2, the base of the plenum will press gypsum outside the hole. Anchor screw Gypsum C) Install the diffuser Fix the diffuser using the anchor screw provided for this purpose, in the center of the cross-piece in the plenum. Plaster frame 5 INSTALLATION IN A SUSPENDED CEILING DRS A) Grids moulding Make sure that the grid moldings of the suspended ceiling match the dimensions of the diffuser face. Also, make sure that the moldings of ceiling are firmly anchored. Diffuser B) Install the diffuser to the plenum box Place the diffuser in the plenum and using the screw anchors provided for this indeed, in the center through internal plenum C) Install the plenum and the diffuser Slowly move the diffuser and plenum box in the ceiling space. Important Secure the support by suspending the plenum by four (4) holes of suspension provided for this purpose with metal wire. Plenum Gypsum Grid moulding Plenum Hole for suspension . . Cross bar Anchor screw Pannel of suspended ceiling 6 Grid moulding