Model SI-L-A
Small Inverter
240W, 350W, 500W, 1000W, 1500W, or 2000W
FEATURES
- No individual battery packs to replace means lower maintenance costs, quicker testing, and greatly reduced electronic waste - only batteries need
to be replaced, not entire battery packs with electronics.
- High effiency, pure sine-wave inverter delivers full output throughout 90 minute operation.
- Automatic diagnostics for connected loads through patented RLS. Every day testing alerts room occupants and custodians of problems
with tubes, ballasts. When room switch is turned off emergency lights stay on for 2.5 seconds to ensure compliance with NFPA 101 and
eliminate lengthy and costly monthly testing procedures, which, in some districts, requires fire marshal supervision.
The SI-L-A is housed in a custom, powder coated, metal panel engineered for strength, but still lightweight to reduce shipping charges and allow
easy, single person handling and installation. All individual parts weigh less than 50 lbs.
-
Innovative battery harness with disconnects makes installation and servicing safe and easy. No factory startup required.
Modular Design - All major components are field replaceable.
Provides line voltage to any load you specify, compatible with fluorescent, incandescent, LED, halogen, and CFL loads.
Designated emergency fixtures will operate at full brightness, eliminating tedious calculations and guesswork.
-
Visible LED indicators supervise input, output, and charging circuits (2 LED’s)
Self resetting protection for overload, reverse polarity, shorts, temperature-controlled fan and more.
Designed for 25 year trouble-free operation
Full 3 year warranty on electronic components
6 year pro-rata warranty on batteries
UL924 Listed
Emergency fixtures operate at full output (2800 lumen for F32T8) during power failure for 90 minutes
Standard Battery Packs provide only 600-100 lumens per tube
Regular Room
Designated
Fixtures
Emergency Fixtures
Up to 2000W of
Fluorescent, Incandescent,
LED, Halogen, and CFL
Loads
CATALOG #
SI-L-A-240W-120V
SI-L-A-240W-277V
SI-L-A-350W-120V
SI-L-A-350W-277V
SI-L-A-500W-120V
SI-L-A-500W-277V
SI-L-A-1000W-120V
SI-L-A-1000W-277V
SI-L-A-1500W-120V
SI-L-A-1500W-277V
SI-L-A-2000W-120V
SI-L-A-2000W-277V
Regular
Lighting
Circuit
120V or 277V
Utility Input
Regular Room
Designated
Fixtures
Emergency Fixtures
Regular
Lighting
Circuit
RLS Control
120V or 277V
Emergency Output
Dedicated
20 Amp
Circuit
Utility Power Unit
SI-L-A
RLS Control
[To additional rooms]
Transfer
Control
Charger
Emergency
Output
RL1 RL2
Batteries
Charger
LED
Inverter
Fuse
Utility Power
Supervision & Test
Utility Power
LED
OPTIONS
208V - 208V
EELP • 2577 Neshaminy Interplex Drive - KOR A, Suite 102 - Trevose, PA 19053 • Phone: 800-490-4496 • Fax: 877-634-6887 • www.eelp.net
SI-L-A 08082016
NORMAL OPERATION
-- The SI-L-A Transfer Control will feed Utility Power through RL1 (see
diagram). This will supply all emergency loads connected to the SIL-A.
-- Supervisory LED’s will indicate that utility feed, inverter, and charger
are all energized and operating properly.
-- Test switch is easily accessible without opening cover and may be
pressed to switch SI-L-A to emergency mode.
TRANSFER
- Upon power failure the SI-L-A will transfer from utility power
to inverter power through relays RL1 and RL2 (see diagram).
- These relays are electronically interlocked with a time delay,
which prevents arcing when transfering between two out
of phase power sources. This safety feature protects the
SI-L-A, loads, as well as expensive equipment on both
sides of the inverter.
EMERGENCY OPERATION
- The SI-L-A Transfer Control will feed pure sine wave Inverter
Power through RL2 (see above). This will supply all emergency
loads connected to the SI-L-A for up to 90 minutes.
- Optional RLS emergency lighting controls in each room allow
emergency fixtures to be controlled from regular wall
switches, occupancy sensors, or dimmers during normal operation,
but will automatically illuminate emergency fixtures at
full brightness during emergency operation.
SAFE GUARDS AND SPECIAL FEATURES
- Self-resetting overload protection and fused output
- 120VAC or 277VAC Pure Sine Wave Output
2000W, 1500W, 1000W, 500W, 350W, or 240W load for 90 minutes
- Automatic Output Voltage Tracking maintains output
voltage at full load ± 3%
- Operates fluorescents, dimmable fluorescent ballasts,
CFL, LED, halogen & incandescent loads.
- Distortion (THD): Less than ± 3%
- EMI in compliance with FCC Class A Regulation
- Test switch to simulate utility power loss.
- Efficiency: 99% at Full Load
- Sealed Lead Calcium batteries provide long life and are
maintenance free.
- 3/6 Warranty (3 year replacement warranty on electronics, 6 year
pro-rata warranty on batteries)
- Small footprint: 2000W Model: 25” (L) x 28“ (H) x 12.5” (D)
1500W Model: 25” (L) x 28“ (H) x 12.5” (D)
1000W Model: 25” (L) x 17“ (H) x 12.5” (D)
500W Model: 25" (L) x 17" (H) x 12.5" (D)
350W / 240W Models: 27.5” (L) x 9” (H) x 7.5” (D)
- Thermostat Controlled Silent Cooling Fan
- Load Power Factor: 0.9 leading to 0.9 lagging
- 1.5 seconds transfer time to protect against momentary ON/OFF
voltage surges caused by power line hitting wet pavement or other
power lines during a storm.
- Operating Temperature: 40°F to 100°F
- Frequency Regulation: ± 5%
- 10W Input power (2000W) or 5W Input Power Consumption (all other
models) when batteries are fully charged.
- Automatic low voltage battery disconnect, deep discharge protection,
over-temperature shut down, and reverse polarity protection.
- Automatic Emergency Fixture Diagnostics when used in conjunction
with EPC-A-1 to eliminate monthly test of emergency fixtures.
- GFCI Protection for 120V models
SI-L-A-240W
SI-L-A-350W
SI-L-A-1000W
SI-L-A-1500W
SI-L-A-2000W
Status LED Indicators
120VAC Utility Power On