general notes: demolition notes: electrical symbol

advertisement
John W. Riner, P.E.
Florida License #66867
SEAL
ELECTRICAL SYMBOL LEGEND
THREE-WAY SWITCH
S4
FOUR-WAY SWITCH
BRANCH CIRCUIT CONDUIT CONCEALED IN SLAB,
UNDERGROUND OR UNDER FLOOR.
SP
SINGLE POLE SWITCH
WITH PILOT LIGHT
BRANCH CIRCUIT CONDUIT EXPOSED
SWP
SINGLE POLE SWITCH
WITH WEATHERPROOF COVER
SINGLE POLE SWITCH
WITH WEATHERPROOF LOCKING COVER
SK
SINGLE POLE KEY SWITCH
S3K
M
MOTION DETECTOR 360°
CR
CARD READER
K
DIGITAL KEYPAD
BALANCED MAGNETIC DOOR CONTACT
TELEPHONE/COMPUTER RACEWAY SYSTEM
GROUND OR GROUND ROD AS NOTED
CONDUIT STUB
CONDUIT CONTINUED
THREE-WAY KEY SWITCH
(XD/XV)
C = ABOVE THE COUNTER
W = WALL MOUNTED (60"AFF)
D = DATA
V = VOICE
LIGHTING
W
COMMUNICATIONS "INFORMATION OUTLET" MTD. AT
RECEPTACLE HEIGHT UNLESS OTHERWISE NOTED.
PROVIDE BACKBOX AND 1"C. TO ACCESSIBLE
CEILING SPACE. COMMUNICATIONS OUTLETS WILL
HAVE ONE DATA AND ONE VOICE JACK UNLESS NOTED
OTHERWISE. CABLING AND JACKS SHALL BE CAT 6.
60"AFF WALL MOUNTED ANALOG PHONE LINE
FOUR-WAY KEY SWITCH
S4K
SL
SINGLE POLE SWITCH WITH SECURITY LOCKING KEY
SOC
WALL SWITCH WITH OCCUPANCY SENSOR
STRIP LIGHT FIXTURE
FIXTURE DESIGNATION
FAN SWITCH
SM
MANUAL MOTOR STARTER WITH OVERLOAD HEATERS
SMP
MANUAL MOTOR STARTER WITH OVERLOAD HEATERS
AND PILOT LIGHT
SD
DIMMER SWITCH
(1500 WATTS UNLESS OTHERWISE INDICATED)
CIRCUIT NUMBER
A
TTB
a
LOWER CASE LETTER INDICATES CONTROL CIRCUIT SWITCH LEG
WALL MOUNTED LIGHT FIXTURE WITH WALL OUTLET BOX
LIGHT FIXTURE
DUPLEX RECEPTACLE
EXIT LIGHT FIXTURE
DIRECTION ARROWS AS SHOWN
(SHADED QUADRANT INDICATES FACE(S) OF FIXTURE)
PEDESTAL MOUNTED RECEPTACLE
WALL MOUNTED EXIT LIGHT FIXTURE
FLOOR OUTLET BOX AND DUPLEX RECEPTACLE
WITH APPROPRIATE FLANGE.
BATTERY PACK WITH TWIN HEADS
DUAL TECHNOLOGY CEILING MOUNTED OCCUPANCY SENSOR
(PROVIDE ALL ACCESSORIES, POWER PACK, SENSORS, ETC... TO
PROVIDE FULL COVERAGE).
OS
FIRE ALARM/DETECTION SYSTEM
POKE THRU
POWER POLE
PP
3.
REFER TO THE SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
4.
REFER TO MECHANICAL DRAWINGS AND SPECIFICATIONS FOR THE REQUIREMENTS ASSOCIATED
WITH WIRING AND CONNECTION OF INTERLOCKING AND CONTROLS OF MECHANICAL UNITS AND
THERMOSTAT LOCATIONS.
5.
COORDINATE OUTLET BOX LOCATIONS WITH MASONRY TO AVOID CUTTING ON MORTAR JOINTS.
6.
ALL MOUNTING HEIGHTS SHOWN ARE TO THE CENTERLINE OF THE DEVICE UNLESS NOTED
OTHERWISE. VERIFY ALL OUTLET LOCATIONS ON THE JOB PRIOR TO ROUGH-IN.
T
TELEPHONE TERMINAL CABINET
TELEPHONE SYSTEM RACEWAY
TELEVISION
TV
CATV OUTLET LOCATION. PROVIDE EMPTY BOX AND 1" CONDUIT TO
ABOVE ACCESSIBLE CEILING WITH PULL STRING.
DUPLEX RECEPTACLE MOUNTED ABOVE COUNTER
8.
GFI RECEPTACLE MOUNTED ABOVE COUNTER
R = RETURN
S = SUPPLY
J
JUNCTION BOX- WALL MOUNTED
SS
SURGE SUPPRESSOR
ST
SHUNT-TRIP BUTTON - FLUSH MOUNTED UNLESS
OTHERWISE NOTED NEMA 3R FOR EXTERIOR LOCATIONS
5
MOTOR CONNECTION, NUMBER DENOTES HORSEPOWER
VARIABLE FREQUENCY DRIVE
DDC
DIRECT DIGITAL CONTROL PANEL
30AR
NF
XXCD
30AR
20AF
MCP
SIZE
FS
MM
MONITOR MODULE
H
ELECTROMAGNETIC DOOR HOLD OPEN DEVICE
CONNECTION TO CLOSURE/ HOLDER
H
ELECTROMAGNETIC DOOR HOLD OPEN DEVICE
CONNECTION TO CLOSURE/ HOLDER INCLUDES DETECTOR
H
FACP
C:\Local Revit\513029 Homestead Ph2 R13\513029-DMA Homestead Phase 2 - LOCAL -R13.rvt
INTERRUPTION OF SERVICES: CONTRACTOR SHALL COORDINATE SERVICE INTERRUPTION
WITH OWNER AND UTILITY COMPANY AND SHALL NOT INTERRUPT POWER WITHOUT
OWNER/ARCHITECT'S PERMISSION.
9.
ALL EXISTING SURFACE MOUNTED RACEWAY SERVING DEVICES TO REMAIN SHALL BE
CONCEALED.
RECEPTACLES FOR ELECTRIC WATER COOLERS SHALL BE LOCATED DIRECTLY BEHIND ELECTRIC WATER
COOLER, CONCEALED FROM DIRECT VIEW.
29.
ALL LIGHT FIXTURES ARE TO BE LED. PROVIDE APPROPRIATE SWITCHING AND DIMMING DEVICES/
SYSTEMS FOR THE FIXTURE TYPES.
30.
CONTRACTOR SHALL UPSIZE BRANCH CIRCUIT WIRE SIZE AS REQUIRED TO COMPENSATE VOLTAGE
DROP FROM LENGTHENING OF CIRCUITS DUE TO FIELD ROUTING. FINAL INSTALLATION SHALL MEET
FLORIDA BUILDING CODE REQUIREMENT OF: MAXIMUM BRANCH CIRCUIT VOLTAGE DROP OF 3%:
Gurri Matute pa
5001 S.W. 74 CT. Suite 208
Miami, Florida 33155
Telephone (305) 661-0069
Fax (305) 661-0089
JOSE G. MATUTE, AIA, CGC, LEED ® AP
License No. # AR 0014415
Certificate No. # AA 0003454
Civil Engineer
Avino and Associates, Inc.
1350 S.W. 57 Ave. Suite 207
West Miami, FL. 33144
Tel. (305)265-5030
Fax (305)265-5033
Jorge R. Avino, P.E. PSM
License No. PE 22207
Certificate No. EB5098
Structural, Mechanical,
Electrical and Plumbing
Engineer:
TLC Engineering for
Architecture
REFER TO VOLTAGE DROP CHART BELOW FOR CONDUCTOR SIZES FOR BRANCH CIRCUITS
120 VOLT (BASIS 1500 WATT)
CIRCUIT LENGTH
0 - 70'
71' - 115'
116' - 180'
MIN. CONDUCTOR
UP SIZE FOR VOLTAGE DROP
#12 AWG
#10 AWG
#8 AWG
13.
EQUIPMENT SHALL BE OF MATERIALS SUITABLE FOR AND RATED FOR THE ENVIRONMENT IN
WHICH THEY ARE TO BE INSTALLED, WITH APPROPRIATE NEMA ENCLOSURE RATING.
34.
CONTRACTOR SHALL PROVIDE AN OPERATING MANUAL AND MAINTENANCE MANUAL TO OWNER. THE
MANUAL SHALL INCLUDE AT A MINIMUM: (1) SUBMITTAL DATA STATING EQUIPMENT RATING AND
SELECTED OPTIONS FOR EACH PIECE OF EQUIPMENT REQUIRING MAINTENANCE. (2) OPERATION AND
MAINTENANCE MANUALS FOR EACH PIECE OF EQUIPMENT REQUIRING MAINTENANCE. REQUIRED
ROUTINE MAINTENANCE ACTIONS SHALL BE CLEARLY IDENTIFIED. (3) NAMES AND ADDRESSES OF AT
LEAST ONE QUALIFIED SERVICE AGENCY.
35.
CONTRACTOR SHALL PROVIDE TEMPORARY ELECTRICAL SERVICE AS REQUIRED FOR USE BY ALL
TRADES DURING CONSTRUCTION. REMOVE TEMPORARY POWER AT THE COMPLETION OF THE
PROJECT. CONTRACTOR SHALL OBTAIN AND PAY FOR ALL REQUIRED PERMITS TO OBTAIN
TEMPORARY ELECTRICAL SERVICE.
36.
CONTRACTOR SHALL SUBMIT FOR APPROVAL MAIN AND ALL ADJUSTABLE THE "AS SET"
OVERCURRENT PROTECTIVE DEVICE SETTINGS.
C. BOX OPENING SHALL NOT EXCEED 16 SQUARE INCHES.
37.
ALL CONDUCTORS SHALL BE COPPER. ALUMINUM CONDUCTORS ARE NOT PERMITTED.
D. ALL CLEARANCES BETWEEN OUTLET BOX AND GYPSUM BOARD SHALL BE COMPLETELY
FILLED WITH JOINT COMPOUND (OR OTHER APPROVED MATERIAL).
38.
THE ELECTRICAL CONTRACTOR SHALL INSTALL ALL CONDUITS, FOR THE SECURITY ELECTRONICS
SYSTEMS THE SECURITY ELECTRONICS CONTRACTOR (SEC) SHALL PROVIDE AND INSTALL THE WIRE
AND CABLE FOR THE SECURITY ELECTRONICS SYSTEMS AND ALL SECURITY ELECTRONICS EQUIPMENT.
THE SEC SHALL SUPERVISE THE CONDUIT INSTALLATION AND VERIFY EXACT BACK BOX LOCATIONS
AND CONDUIT STUB-UP LOCATIONS IN THE EQUIPMENT ROOMS.
A. WORKING CLEARANCES AND DEDICATED SPACE FOR ELECTRICAL EQUIPMENT SHALL BE
IN COMPLIANCE WITH NEC 110. SUBMIT COORDINATION DRAWINGS OF ELECTRICAL ROOMS
SHOWING COMPLIANCE.
14.
B. BOX OPENING SHALL OCCUR ONLY ON ONE SIDE OF FRAMING SPACE.
E. PROVIDE A WALL AROUND OUTLETS LARGER THAT 16 SQUARE INCHES. THE INTEGRITY
OF THE WALL RATING SHALL BE MAINTAINED.
F. THE TOTAL AGGREGATE SURFACE AREA OF THE BOXES SHALL NOT EXCEED 100 SQUARE
INCHES PER 100 SQUARE FEET.
39.
FIELD VERIFY LOCATION OF AREA SMOKE DETECTORS AND HEAT DETECTORS. DO NOT LOCATE
WITHIN 36" OF A HVAC DIFFUSER (SUPPLY OR RETURN), IN A DIRECT AIR FLOW PATH OR
WITHIN 36" OF A SPRINKLER HEAD. SMOKE DETECTORS FOR DOOR RELEASE SHALL BE
LOCATED ON THE CENTER LINE OF THE DOOR AND A MAXIMUM OF 5 FEET FROM THE DOOR.
THE MINIMUM DISTANCE FROM THE DOOR IS THE DEPTH OF THE WALL SECTION ABOVE THE
DOOR, BUT NOT LESS THAN 12".
40.
LABEL REMOTE ALARM INDICATOR FOR DUCT MOUNTED SMOKE DETECTORS (IE: RTU-1 SUPPLY,
RTU-2 RETURN, FIRE/SMOKE DAMPER, ETC.). DUCT DETECTORS SHOULD BE LOCATED IN THE
AREA BETWEEN 6 AND 10 DUCT EQUIVALENT DIAMETERS OF STRAIGHT, UNINTERRUPTED
DUCTWORK. DUCT DETECTORS FOR FIRE/SMOKE DAMPERS SHOULD BE LOCATED BETWEEN THE
LAST INLET OR OUTLET UPSTREAM OF THE DAMPER AND THE FIRST INLET OR OUTLET
DOWNSTREAM OF THE DAMPER.
G. OUTLET BOXES LOCATED ON OPPOSITE SIDES OF FIRE-RESISTIVE ASSEMBLIES SHALL BE
SEPARATED BY A MINIMUM HORIZONTAL DISTANCE OF 24 INCHES.
874 Dixon Boulevard
Cocoa , FL. 32922
Tel. (321)636-0274
Fax (321)639-8986
Gary C. Krueger
Licenses No. PE 40788
James Wamsley
Licenses No. PE 50343
John W. Riner P.E.
Licenses No. PE 66867
Certificate No. 00015
H. OUTLET BOXES SHALL BE SECURELY FASTENED TO WALL FRAMING MEMBERS.
I. THE OPENING IN THE GYPSUM BOARD FACING SHALL BE CUT NOT TO EXCEED
1/8 INCH BETWEEN THE EDGES OF THE OUTLET BOX AND THE EDGES OF THE OPENING.
15.
ALL CONDUCTORS INSTALLED ABOVE THE ROOF SHALL BE DERATED FOR AMBIENT
TEMPERATURE INCLUDING AMBIENT TEMPERATURE ADJUSTMENT IN ACCORDANCE WITH ARTICLE
310.15 (B)(2)(c).
41.
16.
PROVIDE GFCI PROTECTION FOR ALL RECEPTACLES FOR DRINKING FOUNTAIN, WATER COOLERS,
HEAT TRACE, ELEVATOR ROOMS AND SHAFTS, MECHANICAL ROOM, JANITOR CLOSETS,
OUTDOORS, KITCHENS AND ALL OTHER LOCATIONS WITHIN 6 FEET OF A SINK OR OTHER
WATER SOURCE IN ACCORDANCE WITH THE NEC.
EQUIPMENT SHUTDOWN RELAY SHALL BE LOCATED WITHIN 3 FEET OF THE EQUIPMENT
CONTROLS AND THE WIRING TO THE RELAY SHALL BE MONITORED.
42.
FOR EACH FIRE/SMOKE DAMPER: INTERLOCK WITH FIRE ALARM CONTROL PANEL TO CLOSE
FIRE/SMOKE DAMPER AND TO CONTROL THE ASSOCIATED MECHANICAL UNIT PER THE
MECHANICAL SEQUENCE OF OPERATIONS.
PROVIDE SURGE PROTECTION AS REQUIRED FOR NFPA 780 4.18.2 FOR ANY POWER OR LOW
VOLTAGE (FIRE ALARM, TELECOM, ETC.) CIRCUIT EXITING THE BUILDING.
43.
ALL FIRE ALARM WIRING SHALL BE IN CONDUIT, 1/2" MINIMUM.
ALL CONDUIT IN PUBLIC AREAS SHALL BE CONCEALED UNLESS NOTED OTHERWISE.
44.
COORDINATION DRAWINGS
THIS PROJECT REQUIRES SUBMISSION OF COORDINATION DRAWINGS. THE DIVISION 15
CONTRACTOR IS RESPONSIBLE FOR THE INITIATION AND PREPARATION OF THE COORDINATION
DRAWINGS. THIS CONTRACTOR SHALL PARTICIPATE IN THE COORDINATION DRAWING
PREPARATION PROCESS AND PROVIDE ALL NECESSARY INFORMATION REQUIRED TO
COORDINATE ALL TRADE INFORMATION. REFER TO DIV. 15 SPECIFICATIONS FOR DETAILS.
CEILING HEAT DETECTOR 135° F UNLESS OTHERWISE
INDICATED.
18.
FIRE ALARM CONTROL PANEL/VOICE EVACUATION PANEL
FIRE ALARM TERMINAL CABINET
FAAP
FIRE ALARM ANNUNCIATOR PANEL WITH VOICE EVACUATION MICROPHONE- FLUSH
MOUNTED
LOC
VOICE EVACUATION LOCAL OPERATING CONSOLE
1
NEMA STARTER SIZE
FSD
BRANCH CIRCUIT PANELBOARD, UNDER 250 VOLTS,
FLUSH MOUNTED
8.
28.
FATC
ENCLOSURE NEMA RATING.
BRANCH CIRCUIT PANELBOARD, UNDER 250 VOLTS,
SURFACE MOUNTED
SEE ARCHITECTURAL REFLECTED CEILING PLANS AND ELEVATIONS FOR EXACT LOCATIONS OF LIGHT
FIXTURES IN CEILINGS, AND ON INTERIOR AND EXTERIOR WALLS.
WITHIN 30 DAYS AFTER THE DATE OF SYSTEM ACCEPTANCE CONTRACTOR SHALL PROVIDE RECORD
DRAWINGS OF THE ACTUAL INSTALLATION INCLUDING: SINGLE LINE DIAGRAM OF THE BUILDING
ELECTRICAL DISTRIBUTION SYSTEM, SITE PLANS AND ALL ELECTRICAL FLOOR PLANS.
17.
COMBINATION MAGNETIC MOTOR STARTER, SIZE & # OF POLES
3 POLE UNLESS OTHERWISE NOTED
FIELD VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS PRIOR TO BEGINNING WORK AND
OBTAIN CLARIFICATION FROM ARCHITECT/ENGINEER.
33.
COMBINATION AUDIBLE/VISUAL
NOTIFICATION DEVICE
CD = CANDELA RATING (75CD UNLESS NOTED OTHERWISE)
SPRINKLER WATERFLOW
SWITCH CONNECTION
# OF POLES
30/3
0 3R
7.
RECEPTACLES SHALL BE LOCATED 18 INCHES ABOVE FINISHED FLOOR TO CENTER LINE OF
DEVICE, UNLESS NOTED OTHERWISE. ABOVE-COUNTER RECEPTACLES SHALL BE MOUNTED 6"
ABOVE BACK SPLASH TO CENTERLINE OF DEVICE UNLESS NOTED OTHERWISE.
SPRINKLER TAMPER
SWITCH CONNECTION
TS
AR DENOTES AMP RATING OF SWITCH
AF DENOTES AMP FUSE SIZE
LOCATIONS OF EQUIPMENT SPECIFIED BY OTHER TRADES OR PROVIDED BY OWNER ARE APPROXIMATE.
COORDINATE EXACT LOCATIONS IN FIELD PRIOR TO ROUGHING IN AND ROUTING CONDUIT.
12.
VISUAL SIGNALING UNIT, WALL MOUNTED
(NO AUDIO DEVICE)
F
FUSED DISCONNECT
CONTRACTOR SHALL BE RESPONSIBLE FOR PATCHING ALL OPENINGS IN EXISTING
CONSTRUCTION AFTER REMOVAL OF EQUIPMENT AND ELECTRICAL DEVICES.
REFER TO ARCHITECTURAL DRAWINGS FOR PATCHING/DRYWALL REPLACEMENT INSTRUCTIONS.
PROVIDE BLANK COVERPLATES WHERE DEVICES ARE BEING REMOVED FROM EXISTING WALLS
TO REMAIN. MATCH COLOR OF EXISTING DEVICE.
PROVIDE HACR RATED CIRCUIT BREAKERS FOR ALL HVAC EQUIPMENT.
FIRE ALARM SPEAKER WITH STROBE - CEILING MOUNTED
CD = CANDELA RATING (75CD UNLESS NOTED OTHERWISE)
F
NON-FUSED DISCONNECT SWITCH, SIZE AS NOTED
NF DENOTES NON-FUSED
4.
6.
32.
ELECTROMAGNETIC DOOR HOLD OPEN DEVICE
VFD
ELECTRICAL DEVICES CONCEALED BY STORAGE SHELVING, CASEWORK, FURNITURE, ETC. ARE
TO BE REMOVED AS REQUIRED BY DEMOLITION PLANS.
COORDINATE INSTALLATION OF ANY DEVICE LOCATED IN MILLWORK WITH ARCHITECTURAL DRAWINGS
AND DETAILS PRIOR TO ROUGHING IN BOXES AND ROUTING CONDUIT.
LIGHT SWITCHES SHALL BE MOUNTED 48 INCHES ABOVE FINISHED FLOOR TO CENTER LINE OF
DEVICE, UNLESS NOTED OTHERWISE.
REMOTE INDICATING LAMP FIRE ALARM WITH TEST SWITCH
WALL MOUNTED 72" AFF
UNDER GROUND CONCRETE ENCASED DUCTBANK
J
3.
FOR ALL EQUIPMENT AND WIRING DEVICES BEING REMOVED: REMOVE CONDUCTORS BACK TO
PANEL, TURN BREAKER TO "OFF" AND LABEL THE CIRCUIT "SPARE" ON THE PANEL
DIRECTORY. WHERE THERE ARE WIRING DEVICES TO REMAIN ON THE BRANCH CIRCUIT,
REMOVE CONDUCTORS BACK TO JUNCTION BOX.
EMERGENCY BALLAST BATTERY PACKS AND EMERGENCY EXIT SIGNS, WHERE USED, SHALL BE
CONNECTED TO UNSWITCHED LEG OF CIRCUIT DESIGNATED ON DRAWINGS.
A. ALL ELECTRICAL BOXES SHALL BE METALLIC.
PHOTOCELL, MOUNTED ON ROOF FACING NORTH
JUNCTION BOX
25.
REMOVE ALL CONDUIT LEFT EXPOSED BY REMOVAL OF WALLS AND CEILINGS IN REMODELED
AREAS. PLUG BOTH ENDS OF REMAINING CONDUIT IN WALL OR FLOOR WHERE CUT.
5.
31.
DUCT SMOKE REMOTE ALARM INDICATING LAMP,
W/ TEST SWITCH, WALL MOUNTED 72" AFF
F
PLUG-IN STRIP WITH RECEPTACLES, 18" O.C. UNLESS
OTHERWISE INDICATED
PROVIDE A PERMANENT SIGN ON THE MAIN ELECTRICAL ROOM DOOR TO THE BUILDING STATING THAT
THE MAIN SERVICE DISCONNECTING MEANS ARE LOCATED INSIDE.
2.
181' AND ABOVE TO BE SUBMITTED BY CONTRACTOR AND APPROVED BY ENGINEER.
R
CLOCK RECEPTACLE
GROUND BAR
24.
ALL BRANCH CIRCUIT HOMERUNS SHALL BE ROUTED IN 1/2"C. MINIMUM. MC CABLE IS NOT
ALLOWED.
SUPERVISED CONTROL RELAY
RT
GND
COORDINATE HEIGHTS OF WALL MOUNTED LIGHTING FIXTURES TO CLEAR MIRRORS, CABINETS AND
BUILT-INS.
EACH BRANCH CIRCUIT RACEWAY SHALL HAVE A FULL SIZE EQUIPMENT GROUND CONDUCTOR.
WHERE ISOLATED GROUND CIRCUITS ARE SHOWN ON THE PLANS, PROVIDE AN ISOLATED
GROUND CONDUCTOR THROUGHOUT THE LENGTH OF THE CIRCUIT IN ADDITION TO THE PHASE,
NEUTRAL AND EQUIPMENT GROUND CONDUCTORS.
R
ISOLATED GROUND DUPLEX RECEPTACLE,
(ORANGE DEVICE)
PC
EACH DATA, TELEPHONE, VIDEO OR OTHER SYSTEMS OUTLET REQUIRES 3/4"C. STUBBED TO
ACCESSIBLE CEILING SPACE UNLESS OTHERWISE NOTED ON PLANS. PROVIDE INSULATED
BUSHINGS ON ALL CONDUITS. LABEL CONDUIT TO IDENTIFY ITS INTENDED USE (IE:
TELEPHONE, DATA, ETC.).
WHEN ELECTRICAL BOXES ARE LOCATED IN VERTICAL FIRE-RESISTIVE ASSEMBLIES,
(CLASSIFIED AS FIRE/SMOKE AND SMOKE PARTITIONS), THEY SHALL BE INSTALLED WITHOUT
AFFECTING THE FIRE CLASSIFICATION. ALL OF THE FOLLOWING CONDITIONS SHALL BE MET:
TWO DUPLEX RECEPTACLES WITH COMMON COVER
LIGHTING CONTROL TIME CLOCK
23.
10.
DUCT SMOKE DETECTOR
SPECIAL PURPOSE RECEPTACLE, RATING AS NOTED
COORDINATE THE LOCATION OF ALL DEVICES AND BOXES WITH WINDOWS, BUILT-INS, AND CABINETS
PRIOR TO INSTALLATION OF CONDUITS OR BOXES. CONTRACTOR SHALL CONSULT ALL CONTRACT
DRAWINGS TO ASCERTAIN ANY CONFLICTS PRIOR TO BIDDING. CONTRACTOR SHALL OBTAIN
CLARIFICATION FROM THE ARCHITECT/ENGINEER. CONTRACTOR SHALL NOT BE ENTITLED TO
ADDITIONAL COMPENSATION FOR WORK REQUIRED TO RELOCATE OUTLET BOXES THAT ARE/OR
BECOME NECESSARY FOR COORDINATION WITH OTHER TRADES WORK.
PROVIDE 18" LONG (MIN). CONDUIT SLEEVES THRU ALL WALLS WHERE CABLES ARE INDICATED
OR REQUIRED TO PASS THRU WALLS. PROVIDE BUSHINGS ON BOTH ENDS. SIZE CONDUIT FOR
CABLES INSTALLED. AT CABLE TRAYS, PROVIDE ONE 4" CONDUIT SLEEVE FOR EACH 4" WIDTH
OF CABLE TRAY.
GFI RECEPTACLE. WP DENOTES WEATHERPROOF COVER.
C
22.
9.
CEILING SMOKE DETECTOR, PHOTO-ELECTRIC
TYPE UNLESS OTHERWISE NOTED
WP
IG
ALL BRANCH CIRCUIT CONDUITS SHALL CONTAIN A MINIMUM OF (2) #12AWG INSULATED COPPER
CONDUCTORS, PLUS A MINIMUM OF (1) #12AWG GROUND WIRE UNLESS NOTED OTHERWISE. ALL
BRANCH CIRCUITS AND FEEDERS SHALL HAVE INDIVIDUAL NEUTRAL CONDUCTORS.
MANUAL PULL STATION
F
TWO DUPLEX RECEPTACLES WITH COMMON COVER
MOUNTED ABOVE COUNTER
21.
27.
TELEPHONE/COMPUTER TERMINAL BOARD
7.
TTC
ALL RECEPTACLES SHALL BE MOUNTED SUCH THAT THE GROUND PIN IS MOUNTED UP.
26.
11.
FLOOR OUTLET BOX WITH TWO DUPLEX RECEPTACLES
AND ONE COMBINATION W/ VOICE/DATA OUTLET
P
REFER TO THE ARCHITECTURAL, MECHANICAL, PLUMBING, FIRE PROTECTION, CIVIL,
LANDSCAPE, INTERIOR DESIGN, TECHNOLOGY AND STRUCTURAL DRAWINGS FOR RELATED
INFORMATION AND ADDITIONAL INSTALLATION REQUIREMENTS TO BE PERFORMED AS PART
OF THE WORK.
TELEPHONE OUTLET FLOOR MOUNTED
2
FLOOR OUTLET BOX WITH DUPLEX RECEPTACLE
AND ONE COMBINATION W/ VOICE/DATA OUTLET
2.
PHONE/DATA AS INDICATED ON DRAWINGS.
LIGHT FIXTURE
SF
1. STATE OF FLORIDA.
2. LIFE SAFETY CODE - NFPA 101.
3. UNDERWRITERS LABORATORIES, INC. PUBLICATIONS
4. NATIONAL FIRE PROTECTION ASSOCIATION (NFPA).
5. AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI).
6. NATIONAL ELECTRICAL CODE - NFPA 70.
7. INSTITUTE OF ELECTRICAL AND ELECTRONIC ENGINEERS (IEEE).
8. NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATION (NEMA).
9. REQUIREMENTS OF LOCAL POWER COMPANY.
10. 2010 FLORIDA BUILDING CODE.
11. THE AMERICANS WITH DISABILITIES ACT (ADA)
12. FLORIDA ACCESSIBILITY CODE.
13. MIAMI-DADE COUNTY, CITY OF HOMESTEAD
20.
45.
LOCATE A 20A/1P/120V. RECEPTACLE WITHIN 6" OF EACH DATA OUTLET AT THE SAME
HEIGHT.
46
FACEPLATES FOR ALL DEVICES IN MECHANICAL, ELECTRICAL AND COMM ROOMS SHALL BE
STAINLESS STEEL.
TO THE BEST OF THE ENGINEER'S KNOWLEDGE, THESE PLANS AND
SPECIFICATIONS COMPLY WITH THE 2010 FLORIDA BUILDING CODE.
THE FLORIDA FIRE PREVENTION CODE (2010) AND ALL LOCAL
CODES AND ORDINANCES.
120V FIRE/SMOKE DAMPER
SM
FSD
DH
SMOKE DETECTOR WIRED TO SECURE POWER TO FIRE/SMOKE DAMPERS.
ALSO TO BE MONITORED BY FACP.
SMOKE DETECTOR WIRED TO SECURE POWER TO DOOR HOLD OPEN DEVICES.
ALSO TO BE MONITORED BY FACP.
NOTE: SOME SYMBOLS SHOWN ON THIS LEGEND MAY NOT PERTAIN TO THIS PROJECT.
LIGHTNING PROTECTION SYSTEM
CONTRACTOR SHALL PROVIDE A COMPLETE, FULLY CONCEALED, ROOF AND
SITE MOUNTED LIGHTNING PROTECTION SYSTEM FOR THE ENTIRE FACILITY
PER THE REQUIREMENTS OF THE DIVISION 16 SPECIFICATIONS. SYSTEM SHALL
BE DESIGNED AND INSTALLED PER NFPA 780 & SHALL BE UL LISTED.
PROVIDE LIGHTNING PROTECTION FOR ALL SITE LIGHTING AND FLAGPOLES, ETC.
1
ISSUE
PRELIMINARY DESIGN
100% PROGRESS SET
BID SET
ADDENDUM 2
DATE
03-27-13
01-31-14
03-12-14
03-28-14
DRAWING TITLE
ELECTRICAL
ABBREVIATIONS,
LEGEND,
SYMBOLS AND
NOTES
DATE
MARCH 9, 2009
1304.00
Project No..
3/28/2014 1:40:25 PM
Building 756, Schweinfurt Rd, HOMESTEAD, FL
33092
S3
DESCRIPTION
REFER TO ARCHITECTURAL DEMOLITION DRAWINGS FOR EXTENT OF DEMOLITION WORK. THE
ELECTRICAL CONTRACTOR SHALL DISCONNECT ELECTRICAL SERVICES TO ALL EQUIPMENT
BEING REMOVED. OWNER SHALL HAVE THE OPTION TO RETAIN REUSABLE ITEMS SUCH AS
COVERPLATES, RECEPTACLES, LIGHTS, PANELS, ETC.. NOT BEING USED IN THE FINISHED
WORK. COORDINATE WITH OWNER PRIOR TO STARTING DEMOLITION. PROPERLY AND LEGALLY
DISPOSE OF ALL EQUIPMENT AND MATERIALS BEING REMOVED.
HOMESTEAD NATIONAL GUARD
ARMORY RENOVATION
BRANCH CIRCUIT CONDUIT CONCEALED ABOVE
CEILING OR IN WALL. CONDUIT SHALL INCLUDE
PHASE, NEUTRAL AND GROUND CONDUCTORS
AS REQUIRED FOR CIRCUITS (UNLESS OTHERWISE NOTED).
SINGLE POLE SWITCH
(SUBSCRIPT INDICATES ITEM CONTROLLED)
SWPL
SYMBOL
1.
Project Name:
DESCRIPTION
ALL WIRING DEVICES SHALL BE MOUNTED VERTICALLY, UNLESS NOTED OTHERWISE.
STATE OF FLORIDA
DEPARTMENT OF MILITARY AFFAIRS (DMA)
Sa
SYMBOL
19.
Owner:
DESCRIPTION
ALL WORK AND EQUIPMENT UNDER THIS DIVISION SHALL BE IN STRICT COMPLIANCE WITH THE
CODES, STANDARDS AND PRACTICES LISTED HEREIN, AND THEIR RESPECTIVE DATES ARE
FURNISHED AS THE MINIMUM LATEST REQUIREMENTS.
State Project #:
SYMBOL
DOOR CONTROL SYSTEM
BASIC MATERIALS CONT.
Architect:
1.
207013
BASIC MATERIALS
DEMOLITION NOTES:
GENERAL NOTES:
DRAWN
PJM
CHECK
JWR
SHEET
E0.00
John W. Riner, P.E.
Florida License #66867
SEAL
M1-2,4,6
HVAC CONTROLS
M1-29
M1-30
M1
EXISTING
ENCLOSED YARD
N.I.C.
VFD
J
3 30
*
M1-14,16,18
AHU-4
Architect:
3/4"C FOR CONTROLS
(TYP OF 3)
REC J P1-9
REC J P1-11
P2-26,28
6
REC J P1-15
FSD
6
REC
J P1-10
EXISTING
OFFICE
101
FCU-1
P2-34,36
ELECTRIC
WATER
HEATER
NEW FEMALE
RESTROOM
102
P1-12
72"AFF
P1-35
6
P1-12
NEW MALE
RESTROOM
EF-1 104
P1-14
REC
P2-38,40 J P1-14
EXISTING
OFFICE
105
M
72"AFF
6
LIGHTING
CONTACTOR LC-1
REC
P2-37,39 J P1-16
EXISTING
OFFICE
106
FCU-1
FCU-1
M1-29
J
HVAC
CONTROLS
3
M1-7,9,11
VFD
Gurri Matute pa
3 30
*
60
*
5001 S.W. 74 CT. Suite 208
Miami, Florida 33155
Telephone (305) 661-0069
Fax (305) 661-0089
JOSE G. MATUTE, AIA, CGC, LEED ® AP
License No. # AR 0014415
Certificate No. # AA 0003454
M1-29
M1-1,3,5
EXISTING
OFFICE
125
FCU-1
P2-18,20
J P1-19
6
REC
J
6
ERU-1
HVAC
CONTROLS
M1-30
P3
Civil Engineer
HVAC CONTROLS
Avino and Associates, Inc.
FCU-1
P1-6
EXISTING
CORRIDOR
100
M
P1-29
P1-16
30/3
00
DP-5
EXISTING AHU-1
MECHANICAL
CONNECT
124
TO EDH-1
P1-37
DP DP-4
3 30
P1
*
ELEC. ROOM STO/ELEC.
J
122
123
P2
P1-29
NEW JAN.
CLOSET
103
P1-5
REC J P3-2
EXISTING
SIPR ROOM
REC J P3-4
AC-3 REC J P3-6
N.I.C.
EXISTING PLUGMOLD
TO REMAIN
P1-13
72"AFF
P1-12
6
AC-1
P2-22,24
6
REC J P1-13
6
FSD
M
NEW
OFFICE
119
FCU-1
M
M
P2-30,32
M
NEW
FCU-1OFFICE
118
EXISTING
CONFERENCE ROOM
117
FCU-2
REC
J P3-5
AC-2
J P3-7
J P3-9
REC
REC
6
M1-29
P1-17
3/4"C FOR POWER
(TYP OF 3)
M1-8,10,12
M1-30
J
P1-17
WP
AHU-3
1350 S.W. 57 Ave. Suite 207
West Miami, FL. 33144
Tel. (305)265-5030
Fax (305)265-5033
Jorge R. Avino, P.E. PSM
License No. PE 22207
Certificate No. EB5098
P3-8
6
6
6
REC
P2-33,35 J P1-18
EXISTING
OFFICE
107
REC
P2-29,31 J P1-20
EXISTING
OFFICE
108
REC
P2-25,27 J P1-22
NEW
OFFICE
109
FCU-1
FCU-1
FCU-1
6
REC
J P1-24
P2-21,23
NEW
OFFICE
110
6
REC
J P1-30
EXISTING
OFFICE
FCU-1 112
P2-17,19
N
FCU-1
3
P1-33
Structural, Mechanical,
Electrical and Plumbing
Engineer:
TLC Engineering for
Architecture
MEZZANINE POWER PLAN
1/4" = 1'-0"
J P1-31
874 Dixon Boulevard
Cocoa , FL. 32922
Tel. (321)636-0274
Fax (321)639-8986
Gary C. Krueger
Licenses No. PE 40788
James Wamsley
Licenses No. PE 50343
John W. Riner P.E.
Licenses No. PE 66867
Certificate No. 00015
MATCHLINE 1/E3.01
MATCHLINE 2/E3.01
EXISTING EXTERIOR
RECEPTACLES
2
EXISTING
ENCLOSED YARD
N.I.C.
FIRST FLOOR POWER PLAN
1/8" = 1'-0"
1
CH-1
2
CH-2
2.5
3
4
EXISTING UTILITY
TRANSFORMER
1
EXISTING
METER
K-12
MDP-8
P4-2
WP
3 200
NF
GENERAL NOTES:
MDP-9
DN
3 200
NF
K-20
RELOCATED
FCU-1 OFFICE
176
K-9
1
NEW SERVICE ENTRANCE FUSED DISCONNECT SWITCH. INTERCEPT EXISTING
UNDERGROUND CONDUIT.
2
CONNECT ANY RECEPTACLES LOCATED ON WALLS TO REMAIN (CORRIDOR & EXTERIOR
WALLS, ETC.) TO SAME CIRCUIT USED FOR RECEPTACLES IN EACH ROOM.
3
NEW GENERATOR DOCKING STATION. REFER TO ONE-LINE DIAGRAM.
4
CONNECT FPL UTILITY FEED FROM SERVICE DISCONNECT TO MTS.
DN
6
DN
P6-19,21
P6-8
4
E3.01
P4-38
WP
POWER OUTLET FOR WIFI ACCESS POINT LOCATED ON SHELF ABOVE CEILING.
P4-5
7
EXIST.
COMM.
175
P4-5
P4-6
HVAC
CONTROLS
6
P4-5
P4-4
P5-10
M1-19
REC J P4-27
REC J P4-29
REC J P4-31
72"AFF
M1-19
MATCHLINE 1/E3.01
EXISTING
OFFICE
126
P2-14,16
P6-11
P6-15
NEW RACK
REC J P1-23
6
6
M
P6-13
J
6
P2-2,4
M
P6-15
6
REC
P2-9,11 J P1-34
EXISTING
OFFICE
114
FCU-1
FCU-1
REC J P1-36
P2-5,7EXISTING
OFFICE
115
FCU-1
DOOR HOLD OPEN
P1-27
72"AFF
M
FSD P4-12
M1-13
M1-13
M1-15
M1-17
NEW
OFFICE
159
M1-17
M1-25
NEW MALE
RESTROOMS
162
P4-14
DN
P4-14
72"AFF
6
P1-38
REC J P4-20
EXISTING
WAITING AREA
P6-17
130
REC J P1-38
P2-1,3 EXISTING
OFFICE
116
6
FSD
GWH-1
M1-25
M1-21
VAV-1-9
M1-13
ISSUE
PRELIMINARY DESIGN
100% PROGRESS SET
BID SET
ADDENDUM 2
DATE
03-27-13
01-31-14
03-12-14
03-28-14
NEW MALE
SHOWERS
164
WP
M1-17
M1-15
P5-3
NEW
RECRUITER'S
P5-3 OFFICE
132
FSD
P5-1
P5-3
P5-16
P5-2
P5-7
NEW
P5-11OFFICE
134
P5-11
NEW
OFFICE
133
P5-7
NEW
OFFICE
142
P5-17
VAV-1-6
NEW
OFFICE
143
P5-21
P5-29
P5-25
P5-21
P5-25
CORRIDOR
146
P5-2
72"AFF
NEW
RECRUITER'S
OFFICE
131
P5-5
P5-21
NEW
OFFICE
144
P5-25
P5-2
VAV-1-10
P5-2
72"AFF
P5-15
NEW
OFFICE P5-15
135
P5-15
P5-7
P5-11
P5-15
NEW
OFFICE
P5-29
145
P5-29
72"AFF
P5-11
NEW P5-19
OFFICE
136
P5-19
P5-19
P5-27 NEW P5-27
OFFICE 72"AFF
138
NEW P5-23
OFFICE
137
P5-23
P5-23
DN
6
FSD
P5-17
P5-13
NEW
OFFICE
VAV-1-5 141
P5-13
REC
P4-21 J
P5-28
P5-18
P5-17
NEW
OFFICE
140
P5-9
EXISTING FSD
M
CORRIDOR
160
P4-14
P5-27
P5-27
P5-31 NEW
OFFICE P5-31
139
P5-31
P5-31
P4-14
P5-30
REC J P5-37
EXISTING 6
OFFICE
148
VAV-1-12
VAV-1-11
REC J P5-33
REC J P5-35
EXISTING
6 OFFICE
147
REC J P5-39
EXISTING
OFFICE
149
6
P5-35
72"AFF
P5-39
C
72"AFF
P5-4
6
M
P5-32
DRAWING TITLE
POWER PLAN
REC J P5-4
EXISTING
OFFICE
151
72"AFF EXISTING
OFFICE
6
150
P5-41
REC J P5-41
P5-41
DATE
MARCH 9, 2009
1304.00
Project No..
1
DN
MATCHLINE 1/E3.01
1
M1-32
NEW MALE
DRYING ROOM
163
P5-26
P5-24
60"AFF
2
P5-13
P5-9
P5-9
P5-5
FCU-1
REC
J P4-21
P4-14
J
DN
MATCHLINE 2/E3.01
B
NEW
CORRIDOR
161
M1-17
M1-15
VAV-1-8
P5-20,22
VAV-1-7
M
P5-12,14
FOR MAGLOCK ACCESS
CONTROL POWER
3/28/2014 1:40:29 PM
EXISTING
TRAINING ROOM
155
P4-17
VAV-1-4
M
REC
P2-13,15 J P1-32
EXISTING
OFFICE
113
6
REC J P4-22
REC J P4-24
M1-15
NEW
OFFICE
158
M1-13
NEW
OFFICE
157
REC J P4-28
REC J P4-30
REC J P4-32
EXISTING
TRAINING ROOM
156
P4-42 J
DOOR HOLD OPEN
6
6
M1-32
M1-31
M1-25
P4-32
6
6
P1-29
M1-23
JANITOR
ROOM
171
M1-21
M1-21
M1-19
VAV-1-2
72"AFF
P4-22
P4-18
WP
FSD
REC J P1-27
P1-25
72"AFF
NEW
MAIL ROOM
P4-15
P4-15
152
NEW
STORAGE ROOM
172
NEW
OFFICE
173
M1-19
72"AFF
P4-24
P5-8
M
EXISTING
VAULT
J P4-19
REC
N.I.C.
EXISTING
FCU-1 OFFICE
129
J P4-42
80"AFF
ENLARGED EXIST COMM 175 - POWER
4
1/4" = 1'-0"
EXISTING
OFFICE
128
FCU-1
P2-6,8
REC J P1-25
6
FSD
P6-11
P6-13
EXISTING
OFFICE
127
FCU-1
P2-10,12
REC J P1-21
AC-4
(2) 3/4" CONDUITS TO CU-4
(1) FOR POWER AND
(1) FOR CONTROLS
M
MATCHLINE 2/E3.01
P4-12
72"AFF
P4-12
P4-16
FCU-1
CABLE SCHEDULE AND CABLE
DISTRIBUTION DRAWING.
M1-19
P4-9 P4-10
M
C:\Local Revit\513029 Homestead Ph2 R13\513029-DMA Homestead Phase 2 - LOCAL -R13.rvt
EF-2
UP
M1-27
M1-21
P4-36
P4-11
NEW
P5-6
BREAK ROOM VAV-1-1
153
P4-12
P4-14
P4-12
FSD
72"AFF
P4-14
P4-16
P4-16
A
DN
WP
6
P4-39
NEW FEMALE
SHOWERS
167
NEW
STAIR
178
K-10
NEW FEMALE
RESTROOMS
165
M1-27
P4-3
120V FOR
SPRINKLER BELL
P4-8
NEW FEMALE
DRYING ROOM
166
7
VAV-1-3
P4-37
K-5
P4-35
EXISTING
MEETING ROOM
154
FLUSH FLOOR BOX.
P4-26
BASIS OF DESIGN:
REC J P4-23 WIREMOLD EVOLUTION.
6
REC J P4-25
60"AFF
P4-26
J
FACP J
K-4
GWH-1
P4-13
P6-9
K-7
K
P4-34
AHU-2
MDP-7
EXISTING
MECH ROOM
P4-7
177
HVAC CONTROLS
NEMA L5-30R
TTB
P4-33
P4-41 J VFD
4
K-6
REFER TO MEZZANINE
POWER PLAN ABOVE
P4-4
MDP
EXISTING ELECT.
174
P4 P5 P4-6
MTS
P4-38
3
7
P6
K-14
M
(2) 3/4" CONDUITS TO AC-4
(1) FOR POWER AND
(1) FOR CONTROLS
WP
M1-27
J
DEDICATED SPACE FOR VERTICAL WIREMOLD TO ABOVE CEILING, SEE DETAILS ON E8.02.
ELECTRICAL DEVICES WITHIN THIS ROOM ARE EXISTING TO REMAIN. SURFACE MOUNTED
DEVICES AND CONDUITS SHALL BE RECESSED AND CONCEALED IN WALLS. CIRCUIT
DEVICES TO NEW CIRCUIT(S) IDENTIFIED FOR RECEPTACLES IN EACH ROOM. PROVIDE NEW
RECEPTACLES AS SHOWN. DOCUMENT EXISTING RECEPTACLES ON AS-BUILTS.
K-6
COORDINATE OUTLET QUANTITIES, NEMA
CONFIGURATION, WIRE SIZE AND BREAKER
SIZE WITH KITCHEN EQUIPMENT SELECTIONS.
K-16
K-2
GAS SOLENOID
VALVE
K-6
LIGHTING
CONTACTOR LC-2
CU-4
NEW
KITCHEN
168
K-9
NEW
DRILL HALL
170
K-2
TO KSF-1
ON ROOF
M
CODED NOTES:
P4-1
K-15,17,19
GWH-2
State Project #:
P4-40
P4-1
J J
K-22
Owner:
P4-2
P4-1
M
P4-2
3 30
*
NEW
K-2
PANTRY
J 169
K-8
P4-3
2. FCU-1 AND FCU-2 DISCONNECTS ARE INTEGRAL TO EQUIPMENT.
6
M WP
K-1
1. COORDINATE ANY OUTAGES WITH OWNER.
5
KEF-1
K-13
WP
HOOD CONTROL AND
HOOD LIGHTING
207013
N
STATE OF FLORIDA
DEPARTMENT OF MILITARY AFFAIRS (DMA)
NEW BICYCLE
STORAGE
179
Building 756, Schweinfurt Rd, HOMESTEAD, FL
33092
CU-3
DN
CONNECT TO EDH-3
HOMESTEAD NATIONAL GUARD
ARMORY RENOVATION
P3-15,17
Project Name:
P3-1,3
CU-1
MATCHLINE 1/E3.01
P3-11,13
CU-2
MATCHLINE 2/E3.01
CONNECT TO EDH-4
DRAWN
PJM
CHECK
JWR
DN
SHEET
N
1
FIRST FLOOR POWER PLAN
1/8" = 1'-0"
E3.01
John W. Riner, P.E.
Florida License #66867
SEAL
4
EXISTING
ENCLOSED YARD
N.I.C.
1D
MATCHLINE 1/E4.01
Architect:
DN
S
F
MATCHLINE 2/E4.01
AHU-4
AHU-3
W
1D
W
EXISTING
MECHANICAL
124
5001 S.W. 74 CT. Suite 208
Miami, Florida 33155
Telephone (305) 661-0069
Fax (305) 661-0089
JOSE G. MATUTE, AIA, CGC, LEED ® AP
License No. # AR 0014415
Certificate No. # AA 0003454
EXISTING
OFFICE
125
ERU-1
2
F
FSD
F
F
FSD
NEW JAN.
CLOSET
103
F
72"AFF TV
F
EXISTING
OFFICE
101
NEW FEMALE
RESTROOM
102
2
1
NEW MALE
RESTROOM
104
F
F
EXISTING
OFFICE
105
EXISTING
CORRIDOR
100
8
1D
Civil Engineer
9
Avino and Associates, Inc.
7
1350 S.W. 57 Ave. Suite 207
West Miami, FL. 33144
Tel. (305)265-5030
Fax (305)265-5033
Jorge R. Avino, P.E. PSM
License No. PE 22207
Certificate No. EB5098
8
F
72"AFF TV
EXISTING
OFFICE
106
2
EXISTING
OFFICE
107
2
EXISTING
OFFICE
108
2
NEW
OFFICE
109
NEW
OFFICE
110
EXISTING
OFFICE
112
2
2
2
2
MEZZANINE SYSTEMS PLAN
1/4" = 1'-0"
MATCHLINE 1/E4.01
MATCHLINE 2/E4.01
3
874 Dixon Boulevard
Cocoa , FL. 32922
Tel. (321)636-0274
Fax (321)639-8986
Gary C. Krueger
Licenses No. PE 40788
James Wamsley
Licenses No. PE 50343
John W. Riner P.E.
Licenses No. PE 66867
Certificate No. 00015
NEW BICYCLE
STORAGE
179
N
2
EXISTING
ENCLOSED YARD
N.I.C.
FIRST FLOOR SYSTEMS PLAN
1/8" = 1'-0"
1
2
2.5
3
4
RELAY TO COMMUNICATE ANSUL ACTIVATION
TO FACP AND SHUT GAS SOLENOID VALVE.
DN
GENERAL NOTES:
F
F
1. LOCATE ALL DATA OUTLETS WITHIN 6 INCHES OF A 120V RECEPTACLE.
R
NEW
PANTRY
169
F
F
2D
3
3
WALL MOUNTED ACCESS CONTROL MASTER STATION, AIPHONE AX-8MV.
MOUNT AT 60" AFF.
AHU-2
EXISTING
MECH ROOM
177
S
(2) ANALOG VOICE
JACKS FOR FACP
NEW SPRINKLER BELL
IN EXISTING LOCATION
2" CONDUIT WITH 25 PAIR COPPER FROM AT&T DEMARK IN ROOM 123 TO EXISTING COMM 175.
FIELD COORDINATE ROUTING WITH OTHER TRADES.
B
60"AFF
J
F
60"AFF
1D
(4) 4" CONDUIT SLEEVES
ABOVE CEILING
2D
FACP WITH
VOICE EVAC
TS FS
2D
2D
2D
2D
2D
2D
2D
TV 72"AFF
2
2
EXISTING
OFFICE
126
EXISTING
OFFICE
127
2
2
EXISTING
OFFICE
128
EXISTING
OFFICE
129
2D
2D
EXISTING
TRAINING ROOM
155
C
EXISTING
VAULT
N.I.C.
6
NEW
OFFICE
157
EXISTING
TRAINING ROOM
156
NEW
OFFICE
158
NEW
OFFICE
159
B
NEW
CORRIDOR
161
F
2D
NEW
MAIL ROOM
152
W
2D
2D 2D 2D 2D
2D
F
TV
NEW MALE
SHOWERS
164
NEW MALE
DRYING ROOM
163
60"AFF
1
ISSUE
PRELIMINARY DESIGN
100% PROGRESS SET
BID SET
ADDENDUM 2
DATE
03-27-13
01-31-14
03-12-14
03-28-14
1D
W
NEW PLYWOOD
(3 SIDES)
18" LADDER
TRAY
2D
TV 72"AFF
DH
TV 72"AFF
FSD
FSD
1
F
F
72"AFF
F
PS2420 POWER
SUPPLIES
2
FAAP WITH
LOCAL MIC.
72"AFF TV
EXISTING
OFFICE
113
ENLARGED EXIST COMM 175 - SYSTEMS
1/4" = 1'-0"
2
EXISTING
OFFICE
114
2
EXISTING
OFFICE
115
EXISTING
WAITING AREA
130
EXISTING
OFFICE
116
2
2
2
2
DN
DH
DH
FSD
4
(4) 4" CONDUIT
SLEEVES
10
F?
9
NEW
RACK
30" MIN
DH
DN
EXISTING
CORRIDOR
160
F
FSD
FSD
2
NEW
OFFICE
140
NEW
RECRUITER'S
OFFICE
132
2
NEW
OFFICE
142
2
NEW
OFFICE
143
CORRIDOR
146
8
8
NEW
RECRUITER'S
OFFICE
131
2
NEW
OFFICE
133
2
NEW
72"AFF TV
OFFICE
134
2
TV
72"AFF
2
NEW
OFFICE
137
NEW
OFFICE
136
2
2
NEW TV
OFFICE 72"AFF
138
2
NEW
TV
OFFICE 72"AFF
139
2
MATCHLINE 1/E4.01
2
EXISTING
OFFICE
151
2
EXISTING
OFFICE
147
TV 72"AFF
2
EXISTING
OFFICE
149
2
TV
72"AFF
2
SYSTEMS PLAN
2
EXISTING 2
OFFICE
150
2
2
DN
MATCHLINE 2/E4.01
EXISTING
OFFICE
2
148
2
F
NEW
OFFICE
135
C
DRAWING TITLE
NEW
OFFICE
145
NEW
OFFICE
144
8
F
TV
2
2
F
F
4
2
NEW
OFFICE
141
DN
3/28/2014 1:40:31 PM
NEW MALE
RESTROOMS
162
JANITOR
ROOM
171
2D
2D
NEW
STORAGE ROOM
172
NEW
OFFICE
173
72"AFFTV
TV 72"AFF
TV
72"AFF
2
2D
(2) 4" CONDUIT SLEEVES
2D ABOVE CEILING
TV 72"AFF
2D
5
2D
2D
NEW
BREAK ROOM
153
NEW FEMALE
RESTROOMS
165
F
W
ONE CAT 6E DATA CABLE, CONNECT TO EXISTING SWITCH IN SIPR ROOM. CABLE SHALL BE IN
CONDUIT (1" MIN) ALL THE WAY BACK TO EXISTING COMM 175. FIELD COORDINATE ROUTING
WITH OTHER TRADES.
TRENCH 1" C FOR
A/V CABLE EXISTING
MEETING ROOM
154
F
2D
UP
F
F
1
PROVIDE ONE ANALOG PHONE LINE BACK TO EXISTING COMM ROOM. THE ENTIRE PATH
SHALL BE IN CONDUIT (1" MIN).
A
State Project #:
EXIST.
COMM.
175
EXISTING ELECT.
174
10 PULLBOX AS REQUIRED BY NEC.
C:\Local Revit\513029 Homestead Ph2 R13\513029-DMA Homestead Phase 2 - LOCAL -R13.rvt
2D
NEW FEMALE
SHOWERS
167
NEW FEMALE
DRYING ROOM
166
DN
F
9
COORDINATE WITH OWNER WHICH DATA OUTLETS ARE TO BE CONNECTED TO THE PATCH
PANEL IN THE CLOSET AT THE BACK OF THE ROOM AND WHICH OUTLETS ARE TO BE
CONNECTED INTO THE BUILDING'S NETWORK AT THE MAIN COMM ROOM.
W
F
8
REFER TO MEZZANINE
SYSTEMS PLAN ABOVE
2D
MATCHLINE 2/E4.01
7
NEW
STAIR
178
F
NEW AIPHONE VIDEO DOOR STATION AND CORBY 6522 ACCESS CONTROL KEYPAD.
DN
F
4
4
E4.01
F
DATA DEVICE FOR WIFI ACCESS POINT ON SHELF ABOVE CEILING. COORDINATE WITH HEIGHT
OF SHELF. REFER TO ARCHITECTURAL DRAWINGS.
6
F
LOCATE NEW PHONE/DATA OUTLETS WITHIN 6 INCHES OF 120V RECEPTACLE. CONFIRM WITH
OWNER WHICH WALL THE DATA/VOICE OUTLET IS TO BE INSTALLED IN EACH ROOM PRIOR TO
ROUGH-IN.
3
5
W
NEW LOCATION FOR RACK AND TTB SERVING CLASS ROOM.
MATCHLINE 1/E4.01
2
NEW
KITCHEN
168
NEW
DRILL HALL
170
F?
F
DN
CODED NOTES:
Owner:
RELOCATED
OFFICE
176
1
Structural, Mechanical,
Electrical and Plumbing
Engineer:
TLC Engineering for
Architecture
N
2
Building 756, Schweinfurt Rd, HOMESTEAD, FL
33092
2
ELEC. ROOM STO/ELEC.
122
123
W
7
72"AFF
TV
HOMESTEAD NATIONAL GUARD
ARMORY RENOVATION
2
EXISTING
SIPR ROOM
N.I.C.
NEW
OFFICE
119
1D
Project Name:
NEW
OFFICE
118
Gurri Matute pa
2
STATE OF FLORIDA
DEPARTMENT OF MILITARY AFFAIRS (DMA)
EXISTING
CONFERENCE ROOM
117
2
207013
2
2
2D
2
DATE
MARCH 9, 2009
1304.00
Project No..
DN
DRAWN
PJM
CHECK
JWR
SHEET
N
FIRST FLOOR SYSTEMS PLAN
1
1/8" = 1'-0"
E4.01
John W. Riner, P.E.
Florida License #66867
SEAL
EXISTING FPL
TRANSFORMER
DISCONNECT SWITCH
FOR PORTABLE
GENERATOR.
SEE NOTE 1
MDP
(22,000 AIC)
120/208V, 3 PHASE, 4W
800 AMPS
Architect:
800
NOTES:
150
400
150
100
100
300
50
90
30
2
50
2
1. UNDERGROUND CONDUIT PATHS ARE TO BE REUSED IF POSSIBLE.
AT A MINIMUM, THE CONDUITS FROM THE FP&L TRANSFORMER TO
MDP CAN BE PARTIALLY REUSED AND THE CONDUITS FROM MDP TO
DP4 SHOULD BE REUSED.
600
1
2. ALL EXISTING ELECTRICAL GEAR IS TO BE REMOVED.
SPARE
Gurri Matute pa
EXISTING
600A MTS
SEE NOTE 1
EXISTING
CHILLER
EXISTING
AHU 2
EXISTING
AHU 2
5001 S.W. 74 CT. Suite 208
Miami, Florida 33155
Telephone (305) 661-0069
Fax (305) 661-0089
JOSE G. MATUTE, AIA, CGC, LEED ® AP
License No. # AR 0014415
Certificate No. # AA 0003454
PUMP 4
EM1
DP4
120/208V, 3 PHASE, 4W
600 AMPS
120/208V, 3 PHASE, 4W
400 AMPS
Civil Engineer
600
Avino and Associates, Inc.
50
60
1
100
225
100
100
2
Structural, Mechanical,
Electrical and Plumbing
Engineer:
TLC Engineering for
Architecture
EXISTING
AHU FAN
DP4
DP1
874 Dixon Boulevard
Cocoa , FL. 32922
Tel. (321)636-0274
Fax (321)639-8986
Gary C. Krueger
Licenses No. PE 40788
James Wamsley
Licenses No. PE 50343
John W. Riner P.E.
Licenses No. PE 66867
Certificate No. 00015
EM2
DP2
STATE OF FLORIDA
DEPARTMENT OF MILITARY AFFAIRS (DMA)
EXISTING ELECTRICAL ONE-LINE DIAGRAM - BUILDING A
SCALE: N.T.S.
FEEDER SCHEDULE (CU)
NEW GENERATOR DOCKING STATION WITH NEMA 3R
ENCLOSURE. BASIS OF DESIGN: TRYSTAR
GDS-103P-LM
BOND NEUTRAL AND GROUND, CONNECT TO
EXISTING GROUND ELECTRODE SYSTEM.
EXISTING FPL
TRANSFORMER
1-1/2" RGS
15/3
1
20/3
1
35
200
200
100
100
SPARE
SPARE
30
20
20
20
20
8
28
C:\Local Revit\513029 Homestead Ph2 R13\513029-DMA Homestead Phase 2 - LOCAL -R13.rvt
VD=0.62%
VD=0.40%
VD=0.40%
VD=0.40%
38
3 60
*
3 200
NF
3 200
NF
AHU-2
CH-1
CH-2
10,000 AIC
P4
K
10,000 AIC
P5
65,000 AIC
P6
65,000 AIC
65,000 AIC
1-1/4"
3 AWG
8 AWG
1-1/4"
1-1/4"
3
90/3
1
2 AWG
8 AWG
1-1/2"
4
3
19
100/3
1
1-1/2"
1 AWG
8 AWG
4
2"
1-1/2"
3
21
125/3
1
1 AWG
6 AWG
4
22
2"
1-1/2"
3
23
150/3
M1
1-1/4"
4
16
20
VD=1.62%
8 AWG
3
17
SPD
28
1-1/4"
4 AWG
1
18
26
1-1/4"
4
80/3
100
1-1/4"
10 AWG
3
15
100
1-1/4"
4 AWG
1
14
100
10 AWG
4
13
100
1"
6 AWG
1
12
150
1"
3
70/3
400
10 AWG
4
11
1000
3/4"
8 AWG
1
10
120/208V, 3 PHASE, 4W
1000 AMPS
3/4"
3
60/3
(65,000 AIC)
3/4"
10 AWG
4
9
MDP
3/4"
10 AWG
1
8
50/3
VD=0.39%
3/4"
12 AWG
3
40/3
3 SETS OF
(4) 400KCMIL, #2/0 GND IN 3"C.
3/4"
4
6
1
CONDUIT
3/4"
12 AWG
1
7
CONNECT TO EXISTING GROUND
ELECTRODE SYSTEM. MEASURE
GROUND RESISTANCE PER
SPECIFICATIONS AND ADD
GROUND WIRES IF REQUIRED.
12 AWG
3
30/3
1000A MTS
3-POLE WITH SOLID NEUTRAL
65,000AIC
12 AWG
4
4
5
#3/0
EQUIP. GRD.
3
3
3 SETS OF
(4) 400KCMIL IN 3"C
CONDUCTORS
4
2
3 1000 65,000AIC
1000
FEEDER SIZE
3
1
3 SETS OF
(4) 400KCMIL IN 3"C
S.E. RATED
BOND NEUTRAL
AND GROUND
NUMBER
NUMBER
OF
OF
SETS
CONDUCTORS
1/0 AWG
6 AWG
24
4
2"
25
3
2"
175/3
1
Owner:
DESIG.
FUSE OR
CIRCUIT
BREAKER AMP
RATING/# POLES
State Project #:
METER CAN,
COORDINATE
WITH FPL.
2/0 AWG
6 AWG
26
4
2"
27
3
2"
1
200/3
VD=1.25%
120/208V, 3 PHASE, 4W
400 AMPS
22,000 AIC
400
1
225/3
1
25
100
150
20
60
60
1
VD=1.30%
VD=1.30%
VD=1.30%
4
33
3
3"
1
EDH-1
3"
3"
500 KCMIL
2"
#3/0
4
ONE-LINE
DIAGRAM
3-1/2"
3
2
DRAWING TITLE
3 AWG
4
400/3
38
4 AWG
3
1
36
3 30
*
350 KCMIL
4
37
3 30
*
4 AWG
3"
350/3
5
2-1/2"
250 KCMIL
4
35
20
2-1/2"
32
300/3
24
4 AWG
60
34
20
2-1/2"
4/0 AWG
3
250/3
3 AWG
2 1/2"
AHU-1
DATE
MARCH 9, 2009
1304.00
Project No..
3/28/2014 1:45:12 PM
P1
22,000 AIC
P2
22,000 AIC
P3
22,000 AIC
NEW ELECTRICAL ONE-LINE DIAGRAM - BUILDING A
DATE
03-27-13
01-31-14
03-12-14
03-28-14
2-1/2"
4
30
ISSUE
PRELIMINARY DESIGN
100% PROGRESS SET
BID SET
ADDENDUM 2
6 AWG
3
29
31
100
3/0 AWG
4
28
DP
Building 756, Schweinfurt Rd, HOMESTEAD, FL
33092
DP5
PN2
HOMESTEAD NATIONAL GUARD
ARMORY RENOVATION
PN1
Project Name:
EXISTING
AHU FAN
225
100
207013
50
1350 S.W. 57 Ave. Suite 207
West Miami, FL. 33144
Tel. (305)265-5030
Fax (305)265-5033
Jorge R. Avino, P.E. PSM
License No. PE 22207
Certificate No. EB5098
DRAWN
PJM
CHECK
JWR
SHEET
SCALE: N.T.S.
E6.01
NEW ROOF MOUNTED
PHOTOCELL AIMED NORTH
John W. Riner, P.E.
Florida License #66867
SEAL
PC
1
P1-6
2
C
ELEVATION NOTES:
3
EQUIPMENT RACK FOR FIBER AND COPPER UTP TERMINATIONS.
1
4
5
2
PROVIDE VERTICAL CABLE MANAGEMENT, DOUBLE SIDED, 5" WIDE
WITH COVERS FOR FRONT AND BACK.
5
3
FIBER DISTRIBUTION PANEL (FDP).
7
4
SPACE FOR EXPANSION FDP.
5
GROUP "A" PATCH PANELS FOR TERMINATION OF GRAY DATA
CABLES.
6
AI PHONE CENTRAL EXCHANGE AX-248C WITH RACK MOUNTING
HARDWARE.
7
GROUP "B" PATCH PANELS FOR TERMINATION OF BLUE VOICE
CABLES.
8
GROUP "C" PATCH PANELS FOR TERMINATION OF YELLOW
DATA CABLES.
9
LAST 2RU, PATCH PANELS REPRESENTING THE BEP. EXTEND TO
BACKBOARD BY WAY OF HOUSE CABLES AND TERMINATE ON 66
BLOCKS ADJACENT TO BEP. RED CAT 6 CABLES FOR ANALOG LINES
WILL BE INSTALLED ON THE RIGHT HAND SIDE OF THE BEP PP.
5
ROOM XYZ
7
PATCH
PANEL
LETTER
8
B1
BLUE (VOICE) OUTLET
PATCH PANEL B, PORT 1
SPACE FOR
OWNER PROVIDED
SWITCHES
B1
OUTLET
IDENTIFIER
9
FACE PLATE IDENTIFICATION: WALL PHONE
BUILDING MOUNTED LIGHTS
AND FLAG LIGHT
P1-8
Architect:
SPARE
PROVIDE 2 POLE (MIN) ELECTRICALLY
OPERATED, ELECTRICALLY HELD
LIGHTING CONTACTOR
LIGHTING CONTACTOR - LC1
2
4
NEW ROOF MOUNTED
PHOTOCELL AIMED NORTH
PC
P6-8
Gurri Matute pa
5001 S.W. 74 CT. Suite 208
Miami, Florida 33155
Telephone (305) 661-0069
Fax (305) 661-0089
JOSE G. MATUTE, AIA, CGC, LEED ® AP
License No. # AR 0014415
Certificate No. # AA 0003454
C
1
RACK MOUNTED UPS.
10
W
3
6
P6-10
SOUTH EXTERIOR LIGHTS
10
P6-12
NORTH EXTERIOR LIGHTS
Civil Engineer
NOTE:
LABEL OUTLETS CLOCKWISE FROM DOOR,
NUMBER THE OUTLETS 1,2,3...
Avino and Associates, Inc.
SPARE
1350 S.W. 57 Ave. Suite 207
West Miami, FL. 33144
Tel. (305)265-5030
Fax (305)265-5033
Jorge R. Avino, P.E. PSM
License No. PE 22207
Certificate No. EB5098
PROVIDE 4 POLE (MIN) ELECTRICALLY
OPERATED, ELECTRICALLY HELD
LIGHTING CONTACTOR
SPARE
LIGHTING CONTACTOR - LC2
GRAY (DATA) OUTLET
PATCH PANEL A, PORT 1
No Scale
7
BLUE (VOICE) OUTLET
PATCH PANEL B, PORT 1
A1
A1
OUTLET IDENTIFIER
4
No Scale
LIGHTING CONTACTORS - LC1 AND LC2
1
No Scale
B1
OUTLET
IDENTIFIER
874 Dixon Boulevard
Cocoa , FL. 32922
Tel. (321)636-0274
Fax (321)639-8986
Gary C. Krueger
Licenses No. PE 40788
James Wamsley
Licenses No. PE 50343
John W. Riner P.E.
Licenses No. PE 66867
Certificate No. 00015
DEMOLISH EXISTING CONDUIT
AND HOMERUN WIRING
BLANK
C1
1
0'-3_ "
2
ROOM NUMBER
NEW CONDUIT AND HOMERUN
WIRING. SPLICE INTO EXISTING
BRANCH CIRCUIT IN JBOX.
RELABEL JBOX WITH CIRCUIT
NUMBER
OUTLET IDENTIFIER
1
0'-1_"
2
COMMUNICATIONS
RACK
FACE PLATE IDENTIFICATION: 2 DATA / 1 VOICE
2D/1V
PATCH
PANEL
IDENTIFIER
GRAY (DATA) OUTLET
PATCH PANEL A, PORT 1
A
101 1
101 2
101 3
101 4
102 1
102 2
102 3
GRAY
GRAY
GRAY
GRAY
GRAY
GRAY
GRAY
1
2
3
4
5
6
7
112 1
112 2
112 3
112 4
113 1
113 2
113 3
GRAY
GRAY
GRAY
GRAY
GRAY
GRAY
GRAY
25
26
27
28
29
30
31
KEEP BRANCH CIRCUIT WIRING
AND ABOVE CEILING JBOX
EX: EA125-A
DEF: RACK 'A'
TR EA125
STATE OF FLORIDA
DEPARTMENT OF MILITARY AFFAIRS (DMA)
COLOR OF ICON ON PATCH PANEL
SHALL MATCH THE COLOR OF
CORRESPONDING ICON ON THE
INFORMATION MANAGEMENT OUTLET
WALL SHOWN TO REMAIN
(SEE ARCHITECTURAL PLANS)
ENGRAVED PLASTIC TAG WITH 1/4" HIGH WHITE LETTERS ON
BLACK BACKGROUND. TAG SHALL HAVE ALL EDGES BEVELED
AND SMOOTH. SECURE TAG WITH PERMANENT DOUBLE SIDED
TAG TAPE OFFSET FROM CENTER ON BLANK PLATE AS INDICATED.
ROOM XYZ
PATCH
PANEL
LETTER
BLUE (VOICE) OUTLET
PATCH PANEL B, PORT 1
A1
MFR'S STENCIL PORT NUMBER
B1
Owner:
A1
EXISTING DEVICE IN WALL
TO REMAIN, LABEL WITH
NEW CIRCUIT
OUTLET
IDENTIFIER
ALL LABELING SHALL BE MACHINE GENERATED, AND
INSTALLED UNDER FACTORY PLASTIC COVER.
BLANK
TYPICAL PATCH PANEL LABEL DETAIL
8
No Scale
FACE PLATE IDENTIFICATION: 1 DATA / 1 VOICE
TYPICAL RACK LABEL DETAIL
5
No Scale
WIRING METHOD FOR EXISTING DEVICES
LOCATED IN WALLS TO REMAIN
2
No Scale
#3/0 AWG COPPER CABLE TO
MAIN SERVICE GROUND POST
#3/0 AWG COPPER TO
BUILDING STEEL
State Project #:
BLANK
20"
INSULATOR MOUNTING BRACKET (TYP.)
CPI 10622-000
STUB CONDUIT FOR
PHONE/DATA,
CONTINUE FOR 120V.
GRAY (DATA) OUTLET
PATCH PANEL A, PORT 1
207013
YELLOW (DATA) OUTLET
PATCH PANEL C, PORT 1
DOUBLE LUG (TYP.)
ACT CEILING
ROOM XYZ
CONDUIT 1/2" FOR POWER
1" FOR PHONE/DATA
C:\Local Revit\513029 Homestead Ph2 R13\513029-DMA Homestead Phase 2 - LOCAL -R13.rvt
PATCH
PANEL
LETTER
A1
BLANK
4"
STUD AND DRYWALL (REFER TO
ARCHITECTURAL DRAWINGS).
A1
OUTLET
IDENTIFIER
EXISTING CMU WALL
YELLOW (DATA) OUTLET
PATCH PANEL C, PORT 1
CPI 10622-020
OR EQUAL
DRYVIT COVERING
RELAY RACK BASE
BLANK
RUBBER GROUNDING MAT
FINISHED GRADE
FACE PLATE IDENTIFICATION: 2 DATA
1
ISSUE
PRELIMINARY DESIGN
100% PROGRESS SET
BID SET
ADDENDUM 2
DATE
03-27-13
01-31-14
03-12-14
03-28-14
PROVIDE # 6 COPPER CABLE DOUBLE LUG
CLAMP FOR CABLE CONNECTION DIV. 16
(1) TO EACH RACK PLUS ONE TO PHONE
SWITCH ENTRANCE PROTECTOR.
MOUNTING BOLT
W/ISOLATED WASHERS
C1
FRONT VIEW
2D
DRAWING TITLE
GROUND BUS BAR
FACE PLATE
ELECTRICAL
DETAILS
CUT BLOCK WALL
FOR DEEP BOXES.
STANDOFF BRACKET
CPI 10622-000
ISOMETRIC ELEVATION
INSULATOR
CPI 10622-020 OR EQUAL
NOTE: FOR OUTLET IDENTIFIER, SEE DETAIL THIS SHEET.
DATE
FACE PLATE IDENTIFICATION:
1
3/28/2014 1:40:34 PM
INSULATOR (TYPICAL)
Building 756, Schweinfurt Rd, HOMESTEAD, FL
33092
TELECOMMUNICATIONS EQUIPMENT RACK ELEVATION
Project Name:
PATCH
PANEL
LETTER
Structural, Mechanical,
Electrical and Plumbing
Engineer:
TLC Engineering for
Architecture
HOMESTEAD NATIONAL GUARD
ARMORY RENOVATION
ROOM XYZ
No Scale
10
FLOOR RACK MOUNTING ON SLAB
No Scale
9
DEVICE INSTALLATION IN DRILL HALL
No Scale
6
GROUND BUS BAR
No Scale
3
MARCH 9, 2009
Project No..
1304.00
DRAWN
DS/PJM
CHECK
JWR
SHEET
E8.02