SECTION 16342 - METAL CLAD SWITCHGEAR CONSTRUCTION STANDARD PART 1: GENERAL This section of the design standard includes basic requirements for the design of the metal clad switchgear used at the building service entrances. All breakers designed and specified shall use vacuum interrupting technology. This design guideline is to be used in conjunction with Section 16271 – Pad Mounted Transformers and Section 16362 – Service Entrance Equipment to comprise the service entrance double-ended substation. This is a design standard and is not intended to be used as a guideline or construction specification. PART 2: PRODUCTS A. Design and construct the switchgear in accordance with the latest referenced specifications including NEMA, ANSI, and IEEE standards applicable to switchgear. B. All switchgear parts shall be new and free from defects in material and workmanship. C. The switchgear shall be rated 13,800 volts, metal clad, and shall operate on a 12,000-volt nominal, three phase, solidly grounded wye, 60 Hz system. The switchgear shall utilize vacuum breaker technology with a line-up including (2) incoming breakers used as load interrupter switches and (2) breakers used as transformer feeder circuits. D. Enclosure: The switchgear assembly shall consist of individual vertical sections housing various combinations of circuit breakers and auxiliaries, bolted together to form a rigid metal-clad lineup. Each vertical section shall have the capability of stacking breakers two high and auxiliaries four high. E. Main Bus: The main bus shall extend the entire length of the line-up and shall be rated not less than 1200 amp at 12 kV. The bus shall consist of rigidly supported silver-plated copper bars, braced to withstand not less than 1000 MVA symmetrical interrupting duty and a minimum momentary rating of 58 kA at 12 kV. The bus bars shall be of suitable design and cross sectional area to satisfactorily carry the rated current without exceeding the temperature rise as specified in the IEEE and NEMA standards. F. Ground Bus: The ground bus shall be of high conductivity copper with a continuous rating of at least 600 amps and shall extend the entire length of the switchgear. G. Circuit Breakers: 1. All circuit breakers shall be vacuum type and have the following ratings: a. Interrupting Rating: b. Nominal Voltage: c. Continuous Current: d. Maximum symm. I.C: e. Close and latching: f. Rated interrupting time: g. Impulse Level: h. Close Voltage: 1000 MVA 13.8 kV 1200A or as required by design 37 kA RMS @ max. kV 77 kA RMS 5 cycles 95 kV 230 VAC Design & Construction Standards, Revised December, 2000 16342-1 SECTION 16342 - METAL CLAD SWITCHGEAR CONSTRUCTION STANDARD i. Trip Voltage: AC powered capacitor trip 2. The vacuum breakers used as load interrupter switches shall operate on an open loop radial feed system. These breakers shall be used for switching purposes only and shall not require protective type sensing and circuitry. 3. Acceptable breaker element manufacturer’s: a. b. c. d. e. H Cutler Hammer General Electric Powell Square D Siemens Energy Protective Relays: 1. Protective Relays shall be 100% solid state except for the tripping contacts. Electromechanical relays will provide the tripping contacts. These relays shall incorporate three phase (50/51) plus neutral protection (51N) in a single device. The neutral relay functions shall be capable of being turned off. The device shall have a minimum selection of protective time-current curves that shall include a standard relay normal, moderate, very, and extremely inverse designation. The relay shall be powered from the breakers’ 120 VAC source. 2. Protective relay acceptable manufacturers: a. b. c. d. I. Basler BE1-51 Series MultiLin SR735 Series Schweitzer SEL-501 Series General Electric MDP Series Metering: 1. Coordinate location of metering requirements with University of Texas staff. If metering at the metal clad switchgear is required, the design shall adhere to the following: 2. Metering circuits shall be designed such that they may be tested and calibrated without applying test currents and voltages to any other devices. Position KWH meters such that the display registers are eye-level. Must be Transdata Type Mark V meter. 3. The design shall include metering for the following quantities: a. b. c. d. e. f. g. KWH Forward KWH Reverse KVARH Forward KVARH Reverse KQH Reverse KVAH Forward KVAH Reverse 4. Available data displays will include the following for each metered quantity: Design & Construction Standards, Revised December, 2000 16342-2 SECTION 16342 - METAL CLAD SWITCHGEAR CONSTRUCTION STANDARD a. b. c. d. e. f. g. Total Consumption Maximum Demand Time of Maximum Demand Date of Maximum Demand Current Demand Previous Demand Cumulative Demand 5. Available instantaneous displays will include the following: a. b. c. d. e. f. Watts – Three-Phase VARS – Three- Phase Volts – Per Phase Amps – Per Phase Time Day of Week PART 3: DESIGN/DRAWING REQUIREMENTS A. Electrical Engineer shall provide single-line diagram showing gear with draw-out type breakers. B. Floor plans details shall be provided with electric equipment room layouts including switchgear and other substation components drawn to scale. C. Switchgear shall be placed on a 4” housekeeping pad. D. Single line diagram shall clearly indicate dividing lines of points of acquisition and installation responsibility. For example, University of Texas typically provides the 12 kV cable and pad mounted transformers. This should be clearly shown on the single line diagram. END OF STANDARD 16342 Design & Construction Standards, Revised December, 2000 16342-3