Eaton® MSDI
Class I & II/Cat D & C, Three Phase Surge Diverter
The MSDI surge diverter is designed to provide point-of-entry
protection against power surges caused by external sources
such as lightning strikes & substation switching. Common-mode
protection is available for sites remote from the M.E.N. point
including industrial sites & rooftops in multi-storey
buildings. An ideal device for all Category locations.
The MSDI surge diverters utilise MOV protection for both
differential & common-mode protection. Multiple MOV devices
are used in parallel for primary circuit redundancy. The status of
protective devices is continuously monitored & displayed using
LED bar-graph indicators. All MOV devices are thermally fused
& isolated by ceramic fuses.
Shunt Surge Diverter, 3 Phase 200kA
Typical applications:
• All Power Circuits including "Point-of-Entry"
• Telecommunications Systems & Rectifiers
• Process & Control Systems & UPS Systems
• Computer & Medical Systems
• Multi-storey buildings
• All sensitive Electronic Equipment
MSDI unit is provided with an alarm relay. The alarm function
provides a summary alarm output for protection degradation as
well as power failure. The alarm may be configured to indicate
either partial or total protection failure. The level of protection
remaining is indicated by LED bar-graph indicators on the front
panel. A summary alarm relay contacts provide remote
signalling to remote equipment.
Key Features:
• 3 Mode, 2 Stage Surge Diverter
• Surge suppression rating of 200kA
• Enclosed in IP24 cabinet
• LED Bargraph display on each phase
• Protection Fail Alarm Relay
• 5 Year Warranty
Surge Category
The MSDI is suitable
for use in category
locations:
Class II/Cat D
(6kV/30KA) Point of
Entry, High Exposure
Class II/Cat C
(6kV/15kA) Point of
Entry/ Service Entrance
www.eaton.com/powerquality
www.eatonelectric.com.au
Eaton® MSDI
Specifications
Technical Specifications
MSD200CM60i
Input voltage
200 - 250VAC (380 - 440VAC 3 Phase)
Maximum continuous voltage (MCOV)
320VAC
Temporary overvoltage - TOV
350VAC, 15 mins
Service type
TT, TN, TN C-S or any 3-phase system with a grounded neutral
Energy Absorption rating - per mode (Joules)
Primary Protection L-N = 3,000J/ph, 9,000J total
Common mode protection L-E = 710J/ph, 2,130J total
Common mode protection N-E = 2,130J total
Aggregate rating 13,260J
Recommended max. overcurrent protection
125A GL HRC fuse
Protection modes
Line-Neutral, Line-Earth, Neutral-Earth
In 8/20us (Line-Neutral) Nom. surge life
75kA per phase x 20 times
In 8/20us (Line-Earth) Nom. surge life
15kA per phase x 20 times
In 8/20us (Neutral-Earth) Nom. surge life
45kA x 20 times
Ismax 8/20us (Line-Neutral) Max. surge life
200kA
Ismax 8/20us (Line-Earth) Max. surge life
40kA
Ismax 8/20us (Neutral-Earth) Max. surge life
120kA
Initial clamp voltage (Line-Neutral)
560V (350Vac RMS)
Initial clamp voltage (Line-Earth)
680V (420Vac RMS)
Initial clamp voltage (Neutral-Earth)
680V (420Vac RMS)
Internal protection (fusing)
All surge diverter connections are fused via HRC fuses to IEC269-2-1
Alarms/indicators
Bargraph display for protection remaining, dry contact alarm relay output – 250Vac/32Vdc, 10A, 4kV
isolation, Alarm under-voltage cutoff 180Vac.
Enclosure rating
IP24
Design Standards:
IEC61643-1, IEC610006-1,2,3,4 ANSI/IEEE C62.41 Cat B,C,D,E AS1768-2007 Cat B,C,D,E AS3000,
AS3100, CE mark
Dimensions & Weight
370 x 160 x 560 mm (W x D x H), 14kg
Environment
-10 to 65°C, 10 to 90%RH (non-condensing)
Due to continual product improvement specifications are subject to change without notice. Copyright 2010 Eaton Corporation.
C
M
Y
CM
2
4
3
D
Differential protection.
One phase shown, all phases identical
LINE
t is to be us ed in c onjunc tion with
T O LOADS
FPRI
C
t cables phys ically s eparated at all times.
nce 500mm.
red to MC B s for connection to main S W B .
ation guide for details .
within 3m (cable length) of the main s ystem
k for point-of-entry application. G reater
ction.
per operation of this MS D it is es s ential that
ly s hort earth connection be made to the
ith reference to local wiring standards,
ally s ized agains t a thermal rating,
ted fault currents , (5,000 to 25,000 amps).
S D however, the ins taller mus t be aware
an exceed 50,000 amps, and therefore
nerally required to limit voltage drops
ns . T o achieve these requirements, the
ld be s elected to be equal to, or greater
ming cable into the MS D. T his ensures that
earth cable are minimis ed.
er-carrying conductors s hall be sized
pplicable s tandards . It is recommended
utral conductor be s ized the same as (or
e conducts as it is the primary return for
MY
D
Diverter Ins tallation G uide
vs s Doc #510065)
connections via 8mm bolts .
M8 s tud, lower right of enclos ure.
connection points .
e earth cable, even if the unit is bolted to
CY
K
Min distance
to ceiling 300mm
550192_msdi_cnx_dia_a4.pdf 6/10/2008 1:30:27 PM
1
S urge Diverter
c tion Diagram
CMY
C
M
Y
CM
MY
K
CY
CMY
Connection & Line Diagram
C
L-N protection
INP UT
L3
L2
L1
F US E
N
E
E AR T H S T UD
ON C AS E
8mm
NEUTRAL
L3
N-E protection
L2
Min distance
to floor 600mm
L1
L-E protection
NO
Protection alarm
B
NC
EARTH STUD
MAIN S W B
Common-mode protection.
One phase shown, all phases
identical
< 3m line distance
Important: Before installing the device,
please read & follow the installation &
operation instructions.
2/23/2005
2/23/2005
LC
MAIN
E AR T HING
P OINT (S W B )
FROM OTHER PHASES
Title
A
Size
A4
Date:
File:
MS Di S eries
550192
B
COM
NE UT R AL LINK
OR
M.E .N.
1
2
A
MSD LINE DIAGRAM
Number
Revision
550250
7-Aug-2006
Shee1
t of1
JDP
C:\tvss engineering\Product_engineering\current\MSF\MSF.ddb
Drawn By:
3
Eaton Low Voltage Surge Protection - Australia & new Zealand
1300 3 EATON (1300 3 332 866)
www.eaton.com/powerquality www.eatonelectric.com.au
4
0
Download