DSX-1034 Intelligent Input Controller

advertisement
DSX-1034 Intelligent Input Controller
Ñ 32 Programmable 2, 3 and 4 State monitoring points
Ñ Flexible I/O Linking - Local & Panel to Panel
Ñ UL 294 Listed
Ñ LED status for each Input
break detectors. It can also be used to monitor other systems such as
HVAC or lighting systems. The DSX-1034 can even be used to
monitor temperature sensors, water level sensors, gas sensors or any
other device providing a dry set of contacts. With the linking
capabilities of the WinDSX System almost any requirement for input
and output control can be met without the use of external timers or
relays.
Controller Architecture
Ñ Incremental Downloading of changes only
The DSX-1034 Intelligent Controller is comprised of a 1030P Processor and a 1034I/O Termination Board. The 1030P contains the V20
processor, ROM and RAM memory. The 1034I/O contains the power
supply and removable field wiring terminals. The DSX-1034 has 32
EOL supervised inputs for point monitoring. The 1034 has 4 programmable open collector outputs that are programmed and utilized
the same as all other controller outputs.
Ñ Point to Point RS-485 4-wire Panel Communications
Memory
Ñ 4 Time/Day Schedules per Input/Output
Ñ Real Time Clock and Calendar for Input Control
The DSX-1034 has a standard configuration of 64K of ROM and 64K
of RAM. The RAM memory allocation is dynamic between database
and event storage and set for optimum use by the Host PC according
to data entered for that location. The RAM memory may be expanded
from 64K to 192K by adding up to four 32K RAM chips. When
upgrading the ROM in this panel to the new operating it may be
necessary to add a single RAM chip due to the new operating
system having slightly higher memory requirements. When the panel
is in service the amount of RAM and the version of ROM can be
viewed from the DSX communications software.
Inputs
The DSX-1034 has 32 supervised inputs used for alarm monitoring.
Each input has an LED to indicate its electrical status regardless of
the armed state. One of the inputs must be connected to the door
tamper switch and programmed with a 24-hour Time Zone for U.L.
Installations. Each input on the DSX-1034 can be controlled with up
to 4 Time Zones. This allows the inputs to be armed and disarmed up
to four times per day.
General Applications
The DSX-1034 is engineered for those applications where large
numbers of inputs are needed. This 32 input controller could be for
alarm and other point monitoring and control. There are many
applications for the DSX-1034. The 1034 can be used to monitor door
and window contacts, motion detectors, panic buttons, and glass
Each Input has an individual Abort Delay Time. The Abort Delay
Time determines how long the input has to be faulted before it goes
into alarm. Each input can optionally have a shared or unique Action
Message. The action message displays on the PC and instructs the
operator on what action to take when the input goes into Alarm.
The inputs on the DSX-1034 support two, three and four state
monitoring, with five input configurations to choose from. Three and
Four state input circuits support trouble conditions.
DSX Access Systems, Inc. 10731 Rockwall Road Dallas, Texas 75238
888-419-8353 Phone 214-553-6140 Phone 214-553-6147 Fax www.dsxinc.com
Outputs
The DSX-1034 has 4 Outputs. These Outputs are open collector rated
at 100ma. The Outputs can be controlled by up to 4 time zones each
which provides the ability to turn each output on and off up to four
times per day. Each Output of the DSX-1034 can be individually set
for fail-safe or fail secure. The 4 outputs can be expanded to 8 or 16
with the addition of a DSX-1036 (4 relays) or a 1033EX (12 relays)
output extender module.
Communications:
The DSX-1034 Intelligent Controller can communicate with the Comm
Server (Host PC) via direct serial port connection or dial-up modem
communications.
Direct Connect Communications to the PC from the Master 1034
Controller is performed with either RS-232 or RS-485 since the
controller has a dual host communications port. The RS-232 host port
is used for short distance direct serial port connections. The RS-485
host communications port is used when the direct serial port connection is from 50 to 4000 feet from panel to PC. A DSX MCI module can
be placed at the PC to covert the RS-232 signal to RS-485. The
controller communicates with the PC at a default baud rate of 9600.
As long as the communications signal arrives at the Master as RS232/485 and RS-232 at the PC in an asynchronous, full duplex mode,
operating at 9600 baud, the method in between can be just about any
mode of transport such as Direct Wire, T1, Lease Line, or Fiber
Optics.
speed of the panel’s actions and reactions, providing more stability
and security to the overall system. The Controllers are downloaded
with all parameters the first time they are brought on-line. Once the
initial full download occurs all database changes such as the adding
and deleting of card holders are sent to the controllers by way of
incremental downloads. In other words the panels are downloaded
just the changes and only require a full download on power up or in
the event that the system data integrity check determines there is a
discrepancy in the synchronized database held by one of the panels.
Diagnostic, Supervisory and Status LEDs
The DSX-1034 has 51 diagnostic LED’s to indicate panel status.
Thirty two are for Input Status, four are for Output Status, two are for
panel to panel communications, two are for PC to Master communications, one for AC power input Status, five are for Processor Status,
two are used for Power Supply Fuse Status, two for High and Low
AC Power and one for Low Battery. High and Low AC and Low
Battery report to the PC as alarms.
Input / Output / Code Linking
The DSX-1034 Intelligent Controller has new Linking capabilities that
provide even greater input and output control. All I/O Linking is
performed at a local level as well as a global level. This is the ability
for inputs, outputs, and cards from one controller to link to inputs
and outputs on any and all other controllers in the location without
the PC being on-line. It also allows each panel to link to its own
inputs and outputs when panel to panel communications are down.
Dial-Up Modem Communications from the DSX-1034 Master
Controller to the PC utilizes a DSX 9600 baud modem at the Controller
and the same modem at the PC. At the 1034 Master, the RS-232 Host
Communications Port connects to the Modem. The Modem derives
its power from the 1034 panel. The Controller will auto-dial to the PC
all Alarm and supervisory conditions. The controller can also be
programmed to dial the PC when its event storage buffer is 80% full.
Codes, Inputs, and Outputs can Link to other Inputs and Outputs, on
the same or different controller, in order to control their armed or on
and off state. Linking to inputs allows for control of their armed state.
Linking to outputs allows for control of their on and off state. Inputs
can Link to Inputs and Outputs. Outputs can link to Outputs and
Inputs. Codes can link to both Inputs and Outputs.
Panel to Panel Communications is a true point to point, regenerative,
RS-485, 4-wire communications method. This allows the panel to
panel network communications to be regenerated at each controller
allowing up to 4000 feet of distance between controllers over two
twisted pair cable. Panel to Panel communications can be configured
in a series loop, star configuration, or both. The panels are wired in a
series loop configuration unless a DSX-1035 Quadraplexor is used.
With the DSX-1035, a STAR wiring configuration can be achieved.
The Quadraplexor can be placed anywhere on the RS-485 circuit after
the Master panel to provide four RS-485 branch loops. Any number
of panels can be placed on each RS-485 loop without regard to panel
address.
The Links can be responded to in 1 of 5 ways. The responses can be
Toggle, Pulse, Latch, Time Zone, and Follow. Inputs can initiate a link
on the transition from normal to abnormal or on an alarm condition.
Outputs can initiate a link on the transition from on to off or from off
to on. Outputs can be used as software timers to control a delay-on
link to other inputs and/or outputs. For example an input, output or
code initiates a link to an output which pulses the output from 1 - 999
seconds or 1 - 546 minutes. The output links secure and when the
pulse timer expires the output returns open thereby initiating a
subsequent link to an output group consisting of inputs and/or
outputs. If the first output continues to receive a link its pulse time
gets reset.
DataBase Downloads
The linking state of the relay outputs should be carefully planned in
elevator and HVAC control systems. The linking state of the relays
should be set so that when the relays are open (de-energized), the
elevator or HVAC system is active, not disabled. This will ensure a
fail-safe system. It is always advised that the outputs be energized to
disable a function and de-energized to enable a function.
The Controllers utilize a synchronized database that is maintained
with the incremental and automatic or scheduled downloading of
changes only. This intelligent independent processing increases the
DSX Access Systems, Inc. 10731 Rockwall Road Dallas, Texas 75238
888-419-8353 Phone 214-553-6140 Phone 214-553-6147 Fax www.dsxinc.com
DSX-1034 Specifications
Size
Cabinet
1030P
1034I/O
16.0" W x 20.0" H x 4.375" D
8.5" W x 8.75" H x 2.0" D
8.75" W x 14.0" H x 2.5" D
Cabinet
1030P
1034I/O
Package Total
16.00 lb.
2.00lb.
5.50lb.
23.50 lb.
Weight
Finish
Black Powder Coat with White Silkscreen.
Temperature
Operating
Storage
32 to 131 F
-35 to 150 F
Operating
0 to 95%, relative
Humidity
Supply Voltage
Panel Voltage
16.5 VAC 40VA
Power Requirements
33 Watts (.031 BTU)
Panel Current Draw
700 ma (Current will vary depending on panel voltage output loads).
UL Listed or CSA Certified Class II Transformer Required.
Output Voltage
Modem Power
Aux 12
Inputs
9VDC 300ma - current limited
12VDC 1A - fused
Supervised
32
UL Installations require a Tamper Switch to be connected to an Input programmed with a 24hr Time Zone.
Outputs
Programmable
4 100 ma - Open Collector / expandable with 1036 (4) and 1033EX (12) Output extender Modules
Battery Charging Output
Trickle Charge
13.5 VDC 500ma Fused
Standby Time for the 1034 under Maximum Load is 3.5 hours.
For UL Installations, battery must be Powersonic PS-1270 or an Interstate PC-1270.
Communication Ports
RS-232 In
RS-485 In
RS-485 Out
1
2
1
Intel 80C88 or V20
8Mhz
Processor
RAM Memory
Master to PC
1 for Master to PC, 1 From Slave
To Subsequent Slaves
Standard
64K
Expandable to
192K with the addition of up to 4 32K RAM chips
* The transaction buffer automatically adjusts to utilize any RAM not allocated for system parameters.
Packaging
The DSX-1034 comes complete with 1034I/O, 1030P, Ribbon Cable, 32-1K ohm EOL Resistors, Enclosure, Lock & Key, Anchors and Wire Ties,
Tamper Switch, and External AC Power Indicator.
DSX Access Systems, Inc. 10731 Rockwall Road Dallas, Texas 75238
888-419-8353 Phone 214-553-6140 Phone 214-553-6147 Fax www.dsxinc.com
DSX-1034 Typical Connections
Input Circuit Type 0
1k
E.O.L.
1
1k
E.O.L.
Normally Open & Normally Closed
Circuit Short = Alarm
Circuit Open = Alarm
No Trouble
Input Circuit Type 1
1k
E.O.L.
1k
E.O.L.
1k
E.O.L.
2
INPUT 1
3
INPUT 2
Input Circuit Type 4
1034
ALARM INPUT PANEL
SIDE A
SIDE B
1
INPUT 1
2
INPUT 2
3
LED ON = INPUT NORMAL
LED OFF = INPUT ABNORMAL
4
4
5
INPUT 3
INPUT 3
5
6
INPUT 4
INPUT 4
6
7
DIGITAL OUTPUT 1 (-100mA)
8
DIGITAL OUTPUT 2 (-100mA)
(-100mA) DIGITAL OUTPUT 2
9
1k
E.O.L.
1k
E.O.L.
1k
E.O.L.
Normally Open & Normally Closed
Circuit Open = Alarm
Circuit Short = Trouble
INPUT 5
11
INPUT 6
2 & 3 - State Wiring
(Circuit types 0, 1 & 2)
12
13
INPUT 7
14
INPUT 8
15
1 k ohm
1 k ohm
NO
NO
4 - State Wiring
(Circuit types 3 & 4)
180
180
ohm
ohm
INPUT 5
10
INPUT 6
11
12
INPUT 7
13
INPUT 8
14
NC
16
1k
E.O.L.
NC
17
1k
E.O.L.
1k
E.O.L.
1k
E.O.L.
Normally Open
Circuit Short = Alarm
Circuit Open = Trouble
820 ohm E.O.L.
Normally Closed
Switch Open = Alarm
Circuit Short = Trouble
Circuit Open = Trouble
1k
E.O.L.
17
18
Type 1
19
INPUT 10
INPUT 10
19
Type 2
20
1k
E.O.L.
20
21
INPUT 11
22
INPUT 12
Common
NC
Common
Circuit Type
0
1
2
Circuit Type
3
4
Switch Type
NO or NC
NC
NO
25
1k
E.O.L.
1k
E.O.L.
820
ohm
INPUT 9
23
820 ohm E.O.L.
1k
E.O.L.
Type 0
INPUT 9
24
180
ohm
E.O.L.
1k
E.O.L.
NO
820
ohm
NC
Normally Open
Switch Closed = Alarm
Circuit Short = Trouble
Circuit Open = Trouble
1k
1 k E.O.L.
E.O.L.
Enclosed Door Tamper
18
Input Circuit Type 3
180
ohm
E.O.L.
NC
180
ohm
E.O.L.
15
NC
16
Input Circuit Type 2
820 ohm E.O.L.
UL requires the door tamper
to be connected to a 24 hour
armed input.
9
10
180
ohm
E.O.L.
7
8
(-100mA) DIGITAL OUTPUT 1
The Digital Outputs on the 1034
are open collector (switched negative)
outputs. These are programmed and
have the same capabilities as
those on the 1032.
1k
E.O.L.
1k
E.O.L.
820 ohm E.O.L.
INPUT 11
21
INPUT 12
22
23
NC
Switch Type
NC
NO
Circuit type is set in software
25
INPUT 13
INPUT 13
26
27
INPUT 14
INPUT 14
27
29
INPUT 15
INPUT 15
29
30
INPUT 16
INPUT 16
30
31
12VDC OUTPUT
32
NEGATIVE
28
28
1k
E.O.L.
1k
E.O.L.
1k
E.O.L.
1k
E.O.L.
12V Sounder
+12 Volts Unswitched
32
LOW AC
MASTER-SLAVE/
SLAVE-SLAVE COMM.
RS-485 OUT
T T R R
X X X X
+ - + 45 46 47 48
RS-485 IN
T T R R
X X X X
+ - + 41 42 43 44
OUTPUT
EXTENDER
37 38 39 40
The Output will
pull low at 1/3 of
the Door Hold
Open Time.
Automatically
shuts off when
Door is closed.
T31
T8
MOV
LOW BATTERY 12VDC FUSE
180
ohm
E.O.L.
Note ///
All unused Inputs must be
terminated with a 1k ohm
EOL Resistor.
31
12VDC OUTPUT
NEGATIVE
BATTERY FUSE
820 ohm E.O.L.
Type 4
24
26
1 AMP TOTAL
180
ohm
E.O.L.
Type 3
12V
Relay
HIGH AC
PC-MASTER COMM.
M
O
D
E
RS-232 M
RS-485
T R N P T T R R
X X E W X X X X
G R + - + 49 50 51 52 53 54 55 56
N
E
G
A
T
I
V
E
57
B
A
T
T
E
R
Y
+
58
+ 12V
- GND
E
A
R
T
H
G
N
D
59
All coil driven devices require
a MOV across power input.
16.5
VAC
60 61
NC
Primary AC
Power Source
110 VAC Transformer
Providing 16.5 VAC 40VA
Modem
Requires:
Power,
Data,
Phone Line
RS-232
Communications
1036 Output Extender
Side A
Output 3
Output 3
NC
C
NO
Side B
NC
C
NO
Output 4
Output 4
NC
C
NO
NC
C
NO
T32
Panel to Panel RS-485
Communications
Master to Slave
RS-485"IN" to RS-485"IN"
TX to RX
RX to TX
Slave to Slave
1036
37
38
39
40
12V
GND
GND
-
RS-232 Connectors at
Modems
T31
RS-485"OUT" to RS-485"IN"
TX to TX
RX to RX
Polarity
Always + to + and - to -
Modem
DB25
1030
Controller
Pin 2
Pin 3
Pin 7
Pin 4,5,8
Pin 6,20
Terminal 49
Terminal 50
Terminal 51
Together
Together
9VDC
Modem
18AWG 25 feet max.
+DB25 to Modem
For UL Applications the AC Power "ON" LED
must be wired in parrallel with the
16.5VAC 40VA primary power transformer
Data
Earth Ground
(Cold Water Pipe)
Phone
Line
or
RS-232 Direct Connect
PC
DB9
PC
DB25
1030
Controller
Pin 2
Pin 3
Pin 5
Pin 3
Pin 2
Pin 7
Term 49
Term 50
Term 51
Enclosed AC Power
"ON" LED
+
Data
DB25 to PC
To Modem
at PC
12V / 7AH
Battery
DSX Access Systems, Inc. 10731 Rockwall Road Dallas, Texas 75238
888-419-8353 Phone 214-553-6140 Phone 214-553-6147 Fax www.dsxinc.com
Win1034b.p65