B50 Installation Instructions FLUORESCENT EMERGENCY BALLAST U.S. Patent No. 6,339,296 ! IMPORTANT SAFEGUARDS ! WHEN USING ELECTRICAL EQUIPMENT, BASIC SAFETY PRECAUTIONS SHOULD ALWAYS BE FOLLOWED, INCLUDING THE FOLLOWING: READ AND FOLLOW ALL SAFETY INSTRUCTIONS 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. To prevent high voltage from being present on red & yellow output leads prior to installation, inverter connector must be open. Do not join inverter connector until installation is complete and AC power is supplied to the emergency ballast. This product is for use with one 17 W through 215 W (2’ - 8’) or two 17 W through 40 W (2’ - 4’) single pin or bipin fluorescent lamps, including standard, energy saving, HO, VHO, circline, U-shaped and rapid-start (4-pin) long compact fluorescent lamps. Make sure all connections are in accordance with the National Electrical Code and any local regulations. To reduce the risk of electric shock, disconnect both normal and emergency power supplies and inverter connector of the emergency ballast before servicing. This emergency ballast is for factory or field installation in either the ballast channel or on top of the fixture. This product is for use in indoor fixtures except air handling heated air outlets, and wet, damp, or hazardous locations. An unswitched AC power source is required (120 or 277 VAC, 60 Hz). Do not install near gas or electric heaters. Do not attempt to service the battery. A sealed, no-maintenance battery is used that is not field replaceable. Contact the manufacturer for information on service. The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition. Do not use this product for other than intended use. Servicing should be performed by qualified service personnel. SAVE THESE INSTRUCTIONS Ni - Cd THIS PRODUCT CONTAINS A RECHARGEABLE NICKEL-CADMIUM BATTERY. THE BATTERY MUST BE RECYCLED OR DISPOSED OF PROPERLY. 09/14/09 © Philips Emergency Lighting A Division of Philips Electronics North America Corporation 236 Mt. Pleasant Rd. • Collierville, TN USA 38017-2752 • Tech Support 888-263-4638 • Fax 901-854-1630 • www.philips.com/bodine 75000037 INSTALLATION WARNING: TO PREVENT HIGH VOLTAGE FROM BEING PRESENT ON RED & YELLOW OUTPUT LEADS PRIOR TO INSTALLATION, INVERTER CONNECTOR MUST BE OPEN. DO NOT JOIN INVERTER CONNECTOR UNTIL INSTALLATION IS COMPLETE AND AC POWER IS SUPPLIED TO THE EMERGENCY BALLAST. NOTE: STEP #1 Make sure the necessary branch circuit wiring is available. An unswitched source of power is required. The emergency ballast must be fed from the same branch circuit as the AC ballast. INSTALLING THE EMERGENCY BALLAST > Disconnect AC power from the fixture. Remove the ballast channel cover and install the emergency ballast either in the ballast channel or on top of the fixture.* Remote mounting distance must be less than half the maximum remote mounting distance for the AC ballast. Consult AC ballast manufacturer before remote installation. > Depending on the type of fixture in use install emergency ballast using one of the methods illustrated below. InsideBallast Ballast Channel Inside Channel Inside strip Strip Fixture Inside fixture On top Top of of Fixture on fixture * For installation on top of the fixture, wire bundle covers (RMC-60) may be required by state or local codes. These covers are available from the manufacturer as an accessory kit and must be ordered separately. Call your local distributor or the factory for complete information. Fixture STEP #2 INSTALLING THE TEST SWITCH 1/2” Hole > Refer to the illustrations above and install the test switch through the ballast channel cover of a troffer or through the side of a strip fixture. Push to Test > Drill a 1/2" hole and install the switch as shown. > Refer to the diagrams on page 4 and wire the test switch so that it removes AC power from the unswitched hot line to the emergency ballast. STEP #3 Hex Nut Test Button Test Switch Leads Hex Nut INSTALLING THE CHARGING INDICATOR LIGHT > Install the CHARGING INDICATOR LIGHT as shown on the following illustration so that it will be visible after the fixture is installed. TROFFER STYLE FIXTURE STRIP STYLE FIXTURE Fixture Fixture Charging Indicator Light Charging Indicator Light Violet (+) Violet (+) Brown (–) Brown (–) 5/8" Black Bushing 1/2" White Bushing 1/2" White Bushing 5/8" Black Bushing 1/2" Punch NOTE: After installing the charging indicator light and test switch, mark each with the appropriate label. 2 INSTALLATION STEP #4 WIRING THE EMERGENCY BALLAST > Determine the type of AC ballast installed in the fixture. > Select the appropriate wiring diagram on back to connect the emergency ballast to the AC ballast and lamp(s). Make sure all connections are in accordance with the National Electrical Code and any local regulations. > After installation is complete, supply AC power to the emergency ballast and join the inverter connector. > At this point, power should be connected to both the AC ballast and the emergency ballast, and the Charging Indicator Light should illuminate indicating the battery is charging. > A short-term discharge test may be conducted after the emergency ballast has been charging for one hour. Charge for 24 hours before conducting a long-term discharge test. Refer to OPERATION. > In a readily visible location, attach the label "CAUTION - This Unit Has More Than One Power Connection Point. To Reduce The Risk Of Electric Shock, Disconnect Both The Branch Circuit-Breakers Or Fuses And Emergency Power Supplies Before Servicing." OPERATION When AC power is applied, the charging indicator light is illuminated, indicating the battery is being charged. When power fails, the emergency ballast automatically switches to emergency power, operating one or two lamps at reduced illumination. When AC power is restored, the emergency ballast returns to the charging mode and delays AC ballast operation for approximately three seconds to prevent false-tripping of AC ballast (end-of-lamp-life) shutdown circuits. This emergency ballast will operate the rated lamp load for a minimum of 90 minutes. MAINTENANCE Although no routine maintenance is required to keep the emergency ballast functional, it should be checked periodically to ensure that it is working. The following schedule is recommended: 1. Visually inspect the Charging Indicator Light monthly. It should be illuminated. 2. Test the emergency operation of the fixture at 30-day intervals for a minimum of 30 seconds. One or two lamps should operate at reduced illumination. 3. Conduct a 90-minute discharge test once a year. One or two lamps should operate at reduced illumination for at least 90 minutes. ! REFER ANY SERVICING INDICATED BY THESE CHECKS TO QUALIFIED PERSONNEL ! WIRING DIAGRAMS The following diagrams are typical schematics only. May be used with other ballasts. Consult the factory for other wiring diagrams. Emergency Ballast and AC Ballast must be fed from the SAME BRANCH CIRCUIT. IMPORTANT TEXT: REFER TO TABLE 1 REGARDING BROWN CONNECTOR Table 1 LAMP BASE TYPE T8,T9,T10,T12 Single or Bipin (DIAMETER) (1”, 1¼”, 1½”) WATTAGE (Length) 17 - 40 W (2'-4') 40 - 215 W (5' -8') NO. of LAMPS (EMERGENCYMODE) BROWN CONNECTOR 1 CLOSED 2 OPEN 1 OPEN 1 CLOSED 2 OPEN 1 CLOSED 18 - 39 W LONG COMPACT 4-PIN (2G11) 40 - 55 W 3 EMERGENCY BALLAST AND AC BALLAST MUST BE FED FROM THE SAME BRANCH CIRCUIT TYPICAL SCHEMATICS ONLY. MAY BE USED WITH OTHER BALLASTS. CONSULT THE FACTORY FOR OTHER WIRING DIAGRAMS. WIRING DIAGRAM for 1-LAMP emergency operation FIG 104 TWO (2) LAMP INSTANT START BALLAST FIG 133 TWO (2) LAMP RAPID START BALLAST WALL SWITCH WALL SWITCH HOT WHT/RED B L K TEST SWITCH B L K RED INVERTER CONNECTOR WHITE VIOLET (+) CHARGING INDICATOR BROWN (-) (CAP UNUSED LEAD) BLACK 120V OR ORANGE 277V WHITE WHT/BLK COMMON E M E R G E N C Y B A L L A S T HOT BROWN BROWN RED YELLOW YEL/BLK BLU/WHT BLUE WHT/RED WARNING: Refer to Table 1 before connecting B L K TEST SWITCH LAMP 1(EMERGENCY) BLUE BLUE 2 LAMP INSTANT START BALLAST BLACK WHITE INVERTER CONNECTOR CHARGING INDICATOR B L K LAMP 2 (CAP UNUSED LEAD) RED RED INVERTER CONNECTOR WHITE VIOLET (+) CHARGING INDICATOR BROWN (-) (CAP UNUSED LEAD) BLACK 120V OR ORANGE 277V WHITE WHT/BLK COMMON E M E R G E N C Y B A L L A S T YELLOW YEL/BLK BLU/WHT BLUE B L K TEST SWITCH LAMP 1(EMERGENCY) BLUE BLUE 3 LAMP INSTANT START BALLAST INVERTER CONNECTOR CHARGING INDICATOR B L K LAMP 2 (CAP UNUSED LEAD) RED INVERTER CONNECTOR WHITE VIOLET (+) CHARGING INDICATOR BROWN (-) (CAP UNUSED LEAD) BLUE BLUE BLUE RED RED LAMP 2 YELLOW YELLOW VIOLET (+) BROWN (-) BLACK 120V OR ORANGE 277V LAMP 3 E M E R G E N C Y BROWN BROWN RED B A L L A S T WARNING: Refer to Table 1 before connecting YELLOW YEL/BLK BLU/WHT BLUE LAMP 1 (EMERGENCY) BLUE BLUE BLU/WHT YELLOW YELLOW 3 LAMP RAPID START BALLAST BLACK WHITE RED LAMP 2 BLU/WHT LAMP 3 RED RED FIG 120 FOUR (4) LAMP RAPID START BALLAST WALL SWITCH WHT/RED B L K RED WHITE WHITE WHT/BLK COMMON BLUE WALL SWITCH TEST SWITCH LAMP 1 (EMERGENCY) BLU/WHT 2 LAMP RAPID START BALLAST WHT/RED WARNING: Refer to Table 1 before connecting FIG 121 FOUR (4) LAMP INSTANT START BALLAST B L K BLACK 120V OR ORANGE 277V WARNING: Refer to Table 1 before connecting RED YELLOW YEL/BLK FIG 105 THREE (3) LAMP RAPID START BALLAST HOT BROWN BROWN RED BLACK WHITE HOT BROWN (-) BROWN BROWN B A L L A S T WALL SWITCH WHT/RED B L K VIOLET (+) E M E R G E N C Y BLACK WHITE WALL SWITCH HOT TEST SWITCH WHITE WHITE WHT/BLK COMMON FIG 106 THREE (3) LAMP INSTANT START BALLAST B L K RED BLACK 120V OR ORANGE 277V WHITE WHT/BLK COMMON E M E R G E N C Y B A L L A S T BROWN BROWN RED YELLOW YEL/BLK BLU/WHT BLUE HOT WARNING: Refer to Table 1 before connecting LAMP 1 (EMERGENCY) BLUE 4 LAMP INSTANT START BALLAST BLACK WHITE INVERTER CONNECTOR TEST SWITCH YELLOW BLUE WHT/RED B L K CHARGING INDICATOR B L K LAMP 2 (CAP UNUSED LEAD) VIOLET (+) BROWN (-) BLACK 120V OR ORANGE 277V WHITE WHT/BLK COMMON RED RED WHITE LAMP 3 E M E R G E N C Y BROWN BROWN RED B A L L A S T LAMP 1 (EMERGENCY) BLU/WHT RED YELLOW BLUE RED YELLOW YELLOW RED WARNING: Refer to Table 1 before connecting YELLOW YEL/BLK BLACK WHITE LAMP 4 4 LAMP RAPID START BALLAST BLU/WHT BLU/WHT LAMP 2 LAMP 3 BRN BRN BLUE BLUE LAMP 4 FIG 124 TWO (2) LAMP RAPID START STEP DIMMING BALLAST COMMON WHT/RED RED INVERTER CONNECTOR WHITE VIOLET (+) CHARGING INDICATOR BROWN (-) TEST SWITCH HOT BLK WHITE BLK (CAP UNUSED LEAD) BLACK 120V OR ORANGE 277V E M E R G E N C Y B A L L A S T BROWN BROWN RED WARNING: Refer to Table 1 before connecting YELLOW YEL/BLK WHT/BLK WHITE BLACK BLACK S1 S2 The white/black lead must connect to the white lead of the step-dimming ballast associated with the emergency ballast only. Connections to other ballasts or fixtures could result in abnormal operation and cause product damage. LAMP 1 (EMERGENCY) BLUE BLUE BLU/WHT BLUE 2 LAMP RAPID START STEP DIMMING BALLAST RED RED LAMP 2 YELLOW YELLOW WIRING DIAGRAMS for 2-LAMP emergency operation (2´- 4´, 17- 40 W lamps only) FIG 140 TWO (2) LAMP RAPID START BALLAST FIG 125 TWO (2) LAMP INSTANT START BALLAST WALL SWITCH WALL SWITCH HOT WHT/RED B L K TEST SWITCH B L K INVERTER CONNECTOR CHARGING INDICATOR (CAP UNUSED LEAD) COMMON RED WHITE VIOLET (+) BROWN (-) BLACK 120V OR ORANGE 277V WHITE WHT/BLK E M E R G E N C Y B A L L A S T BROWN BROWN RED YELLOW YEL/BLK BLU/WHT BLUE HOT WARNING: Do NOT connect brown connector LAMP 1 RED BLUE BLUE BLACK WHITE WHT/RED B L K INVERTER CONNECTOR TEST SWITCH CHARGING INDICATOR B L K LAMP 2 (CAP UNUSED LEAD) 2 LAMP INSTANT START BALLAST COMMON TEST SWITCH B L K CHARGING INDICATOR (CAP UNUSED LEAD) COMMON BLACK 120V OR ORANGE 277V WHITE WHT/BLK WARNING: Do NOT connect brown connector LAMP 1 BLUE BLUE BLU/WHT BLUE RED RED 2 LAMP RAPID START BALLAST LAMP 2 YELLOW YELLOW WALL SWITCH BROWN BROWN WHT/RED INVERTER CONNECTOR BROWN (-) BROWN BROWN YELLOW YEL/BLK RED B A L L A S T FIG 129 FOUR (4) LAMP INSTANT START BALLAST WALL SWITCH B L K VIOLET (+) E M E R G E N C Y BLACK WHITE FIG 127 THREE (3) LAMP INSTANT START BALLAST HOT RED WHITE RED WHITE VIOLET (+) BROWN (-) BLACK 120V OR ORANGE 277V WHITE WHT/BLK E M E R G E N C Y B A L L A S T YELLOW RED BLUE BLUE BLACK WHITE 3 LAMP INSTANT START BALLAST BLUE WHT/RED B L K LAMP 1 (EMERGENCY) YEL/BLK BLU/WHT BLUE HOT WARNING: Do NOT connect brown connector INVERTER CONNECTOR TEST SWITCH CHARGING INDICATOR B L K LAMP 2 (EMERGENCY) (CAP UNUSED LEAD) COMMON LAMP 3 RED WHITE VIOLET (+) BROWN (-) BLACK 120V OR ORANGE 277V WHITE WHT/BLK E M E R G E N C Y BROWN BROWN RED YELLOW YEL/BLK BLU/WHT BLUE B A L L A S T WARNING: Do NOT connect brown connector LAMP 1 (EMERGENCY) YELLOW BLUE BLACK WHITE RED BLUE 4 LAMP INSTANT START BALLAST RED LAMP 2 (EMERGENCY) LAMP 3 YELLOW RED LAMP 4 WIRING DIAGRAMS for Emergency-Only fixtures FIG 109 ONE (1) 17-215 W LAMP WITHOUT AC BALLAST HOT (CAP) B L K TEST SWITCH B L K INVERTER CONNECTOR CHARGING INDICATOR WHT/RED RED WHITE VIOLET (+) BROWN (-) BLACK 120V (CAP UNUSED LEAD) OR ORANGE 277V COMMON (CAP) WHITE WHT/BLK E M E R G E N C Y BROWN BROWN B A L L A S T HOT WARNING: Refer to Table 1 before connecting RED YELLOW YEL/BLK BLU/WHT BLUE FIG 110 TWO (2) 17-40 W LAMPS WITHOUT AC BALLAST (CAP) B L K LAMP TEST SWITCH (CAP) (CAP) B L K INVERTER CONNECTOR CHARGING INDICATOR RED WHITE VIOLET (+) BROWN (-) BLACK 120V (CAP UNUSED LEAD) OR ORANGE 277V COMMON (CAP) 4 WHT/RED WHITE WHT/BLK E M E R G E N C Y B A L L A S T BROWN BROWN WARNING: Do NOT connect brown connector RED YELLOW YEL/BLK BLU/WHT BLUE LAMP 1 (CAP) (CAP) LAMP 2