Installation Guide

advertisement
Doc. No. IIEntrada2DMK Rev. 082014
Installation Guide
Entrada2DMK - IP Access FACP Adapter Kit
Entrada2DMR - IP Access FACP Receiver
Entrada2DMT - IP Access FACP Transmitter
I.T.E. 43KC
Overview:
These adapters are specifically designed to interface with Network Door Controllers. They route power (PoE/PoE+) from a
PoE switch or Midspan to the Network Door Controller and accommodate up to two (2) Fail-Secure strikes or Fail-Safe mag
locks. The receiver features a supervised Fire Alarm Disconnect which releases locking devices while maintaining power
to the Network Door Controller. The Fire Alarm Interface feature allows multiple units to be interconnected enabling any
or all to be affected from a single FACP trigger input.
Features:
Ethernet:
Agency Listings:
• UL/CUL Listed for Information Technology Equipment
(UL 60950-1). UL Listed for Access Control
System Units (UL 294).
• CSFM - California State Fire Marshal Approved.
• CE - European Conformity.
Input Power:
•For UL 60950-1 applications, use a UL Listed Endspan/
Midspan LPS limited power source.
For UL 294 applications, use a UL 294 Listed
PoE Midspan or Endspan (IEEE 802.3af/at).
Power Output:
• Both lock outputs are selectable for either 12VDC or
24VDC and rated @ 8W (12V/667mA, 24V/333mA) each maximum (16W combined). Total power rated @ 30W (PoE and lock power).
Trigger Input:
• 12VDC-24VDC shutdown trigger (Receiver).
• Two (2) independent 12VDC-24VDC access control
trigger inputs (Transmitter).
Fire Alarm Disconnect:
• Supervised Fire Alarm Disconnect is selectable for
Normally Open (N.O.) or Normally Closed (N.C.)
trigger input.
• Connectivity: RJ45.
• Wire type: 4-pair CAT-5e or higher structured cable.
• Distance: 100m max.
• Speed: 10/100BaseT.
LED Indicators:
•Entrada2DMR:
Output to Entrada2DMT RJ45 connector:
Green - Remote Aux. OFF, Yellow - N/A.
Midspan/Endspan Input RJ45 connector:
Yellow - PoE UP, Green - N/A.
•Entrada2DMT:
Network Door Controller RJ45 connector:
Yellow - Output 1 ON, Green - Output 2 ON.
Input from Entrada2DMR RJ45 connector:
Green - PoE Output ON, Yellow - PoE Input ON.
Environmental:
• See Temp. specifications and Humidity in
Technical Specifications chart pg. 2.
Mechanical:
• Dimensions (H x W x D approx.):
3.5” x 3.5” x 1” (88.89mm x 88.89mm x 25.4mm).
­­­Installation Instructions:
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI, and with all local codes and
authorities having jurisdiction. Wiring should be UL Listed and/or Recognized wire suitable for the application.
Entrada is not intended to be connected to outside plant leads and must be installed indoors within the protected
premises. Entrada is intended for indoor use only.
Entrada2DMR (Fig. 1, pg. 3):
1. Mount Entrada2DMR Receiver in the desired location utilizing the unit’s mounting hole. Use a #6 fastener with
the proper wall anchor (ie. Ribbed Plastic, Drywall Anchor) when securing Entrada2DMR to the wall.
Note: Anchoring fasteners should accommodate a minimum of 3 lbs.
Unit should be located in proximity to the Midspan/Endspan (head end).
2. Before connecting structured cable from midspan or endspan to RJ45 jack marked [Midspan or Endspan]
shut power off on the Midspan or Endspan.
Note: Structured cable between the Midspan or Endspan and the Entrada2DMR should be a minimum of 26 AWG.
3.Connect structured cable from Entrada2DMT to RJ45 jack marked [Entrada2DMT Transmitter].
4. Connect FACP alarm output relay to terminals marked [Supervised Fire Alarm Input Trigger].
Place a 10K resistor (supplied) at the FACP alarm output relay wired in series for a Normally Closed (N.C.)
FACP trigger input or wired in parallel for a Normally Open (N.O.) FACP trigger input (Fig. 3, pg. 3).
To connect multiple units from a single FACP refer to (Fig. 4, pg. 4).
5. To manually release locking devices a 12VDC-24VDC trigger may be applied to terminals marked [Shutdown
Trigger] (Fig. 1, pg. 3).
Entrada2DMK
-1-
Entrada2DMT (Fig. 1, pg. 3):
Factory Settings: FACP Disconnect is enabled and Lock power outputs are set for 12VDC. If these settings
meet your requirement, skip to Step 5.
1. Remove the four (4) screws from the Entrada2DMT cover.
2. For 24VDC lock outputs slide dip switch marked [SW1] to OFF (1) position,
for 12VDC lock outputs slide dip switch marked [SW1] to ON position (Fig. 2a, pg. 3).
3. To disable FACP Disconnect for either or both lock outputs slide the corresponding dip switches marked [S2]
to the ON position, to enable FACP Disconnect for either or both lock outputs slide the corresponding
dip switches marked [SW2 (1), SW2 (2)] to the OFF position (Fig. 2a, pg. 3).
4. Replace cover and secure it with four (4) screws.
5. Mount Entrada2DMT Transmitter in the desired location utilizing the unit’s mounting hole. Use a #6 fastener with
the proper wall anchor (ie. Ribbed Plastic, Drywall Anchor) when securing Entrada2DMR to the wall.
Note: Anchoring fasteners should accommodate a minimum of 3 lbs.
Unit should be located in proximity to the Locking Devices.
6. Connect structured cable from Listed Door Controller to the RJ45 jack marked [Network Door Controller].
7. Connect locking devices to the terminals marked [Lock Power Outputs + 1 -- , + 2 -- ], carefully observing polarity.
Note: All interconnecting devices must be UL Listed and low-voltage Class 2 power-limited.
8. Connect wet trigger output(s) from Listed Door Controller to the terminals marked [Wet Trigger Input + 1 -- ,
+ 2 -- ], carefully observing polarity.
Note: To ensure proper operation the Listed Door Controller must be programmed to apply power to the
Entrada2DMT terminals marked [Wet Trigger Input] to release Fail-Safe devices (Mag Locks) or programmed
to remove power from the Entrada2DMT to release Fail-Secure devices (Strikes).
9. Connect structured cable from Entrada2DMR to RJ45 jack marked [Entrada2DMR Receiver].
Note: System should be tested at least once a year.
Technical Specifications:
Parameter
Input power
requirements
Description
For UL 60950-1 applications, use a UL Listed Endspan/Midspan LPS limited power source.
For UL 294 applications, use a UL 294 Listed PoE Midspan or Endspan (IEEE 802.3af/at).
Indicators
Entrada2DMR:
Midspan or Endspan RJ45 connector: Yellow - PoE UP.
Entrada2DMT Transmitter RJ45 connector: Green - Remote Aux. OFF.
Entrada2DMT:
Listed Door Controller RJ45 connector: Green - Output 2 ON, Yellow - Output 1 ON.
Entrada2DMR Receiver RJ45 connector: Green - PoE Output ON, Yellow - PoE Input ON.
Environmental
Conditions
Operating Ambient Temperature:
Entrada2DMR:
32ºF to 122ºF (0ºC to 50ºC).
Entrada2DMT:
For 16W @ 12VDC or 24VDC output--- 4ºF to 122ºF (--- 20ºC to 50ºC).
For 14W @ 12VDC or 24VDC output--- 4ºF to 131ºF (--- 20ºC to 55ºC).
Total power DC output plus PoE output not to exceed 30W.
Relative humidity: 85%, +/ --- 5%
Storage Temperature: --- 4ºF to 167ºF (-20ºC to 75ºC).
Operating Altitude: --- 1000 to 6,561.679 ft. (--- 304.8 to 2000m).
Regulatory
Compliance
Weights (approx.)
- 2 -
• UL/CUL Listed for: Information Technology Equipment (UL 60950-1).
• UL Listed for: Access Control System Units (UL 294).
Compliance with IEEE 802.3 (at or af) specifications were not verified as part of UL294/B.
• CSFM - California State Fire Marshal Approved.
• CE - European Conformity.
Entrada2DMR: Product: 0.25 lbs. (0.11kg), Shipping: 0.42 lbs. (0.19kg)
Entrada2DMT: Product: 0.48 lbs. (0.22kg), Shipping: 0.66 lbs. (0.30kg)
Entrada2DMK
Shutdown
Trigger
+ ---
UL 294 Listed
PoE Midspan
or Endspan
N.O. FACP
Output
A
B C
Lock Power
Outputs
+ --- + ---
Entrada2DMT
Transmitter
E
F G
H
Listed Door
Controller
Supervised Fire
Alarm Input Trigger
A
B
C
D
E
F
G
H
Entrada2DMR
Receiver
D
Wet Trigger Input
+ --- + ---
Green - Remote Aux. - OFF
Yellow - N/A
Yellow - PoE UP
Green - N/A
Yellow - Output 1 ON
Green - Output 2 ON
Green - PoE Output ON
Yellow - PoE Input ON
Output Voltage and Fire Alarm Disconnect Options:
Switch
SW1
SW2
Description
Output Voltage
Fire Alarm
Disconnect
1
2
Entrada2DMT
ON
12VDC Output
Fire Alarm
Disconnect Disabled
Fig. 2 - Entrada2DMT PC Board
OFF
24VDC Output
Fire Alarm
Disconnect Enabled
2
--- SW2--FACP
ON
1
ON
2
Fire Alarm
Disconnect Switches
1
--- SW1 --ON OFF
12V 24V
--- SW1 --ON OFF
12V 24V
1
ON
Voltage
Selector Switch
ON
Fig. 2a
1
Entrada2DMREntrada2DMT
Fig. 1
--- SW2--FACP
Typical Application:
Fig. 3
Entrada2DMR
Entrada2DMT
Supervised
Fire Alarm
Input Trigger
FACP
Output
Lock Power
Output
Wet Trigger
Input
1
1
2
2
Shutdown
Trigger
PoE+
Endspan or
Midspan
Category-5e 100m
10K
EOL
10K
EOL
C
NO
N.O. FACP Trigger
Entrada2DMK
FACP Alarm
Output Relay
or
NC
Mag Lock
C
Strike
N.C. FACP Trigger
Lock
Lock
Output 1 Output 2
Listed Door
Controller
-3-
Altronix is not responsible for any typographical errors.
140 58th Street, Brooklyn, New York 11220 USA, 718-567-8181, fax: 718-567-9056
website: www.altronix.com, e-mail: info@altronix.com, Lifetime Warranty, Made in U.S.A.
IIEntrada2DMKC19O
- 4 -
MEMBER
Entrada2DMK
10K EOL
FACP Alarm
Output Relay
10K EOL
NC
C
or
C
NO
N.C. FACP
Trigger
N.O. FACP
Trigger
Midspan
or Endspan
Entrada2DMT
10K EOL
N.O.
FACP
Output
Entrada2DMR
Midspan
or Endspan
Entrada2DMT
N.O.
FACP
Output
Connecting multiple units to a single FACP:
Entrada2DMR
Supervised
Fire Alarm
Input Trigger
Midspan
or Endspan
Entrada2DMT
Note: A 10K resistor
must be placed across
the terminals marked
[N.O. FACP Output]
on all Entrada2DMRs
with the exception
of the last unit
10K EOL
N.O.
FACP
Output
Fig. 4
Access Control Performance levels
Access Control Line Security - I
Destructive Attack - I
Endurance - IV
Standby Power - I
Entrada2DMR
(Last unit)