Technical Bulletin Issue Date November 15, 2002 7351J Very Intelligent Early Warning (VIEW) Laser Smoke Detector Introduction 2 Prerequisites 2 General Description 3 Installation Procedures 5 Pre-Installation Guidelines 5 Detector Installation Procedure 6 Limiting Dust Exposure 6 Testing and Maintenance Procedures 7 Testing 7 Maintenance 10 Laser Safety Information 12 Limitations 13 © 2002 Johnson Controls, Inc. Code No. LIT-408092 1 www.johnsoncontrols.com Introduction This document contains important information about installing, maintaining, testing, and operating the Johnson Controls 7351J VIEW laser detector. This detector is manufactured by System Sensor for use with Johnson Controls fire alarm systems. If you install this detector for someone else to use, leave a copy of this document with the user. Prerequisites Before you install any 7351J VIEW laser detectors, read and become familiar with the following: • the installation manual for the control panel system • the requirements of the Authority Having Jurisdiction (AHJ) Select the publications that are relevant to this installation: • National Fire Protection Association (NFPA) 72 National Fire Alarm Code • for non-United States installations, the applicable codes and standards specific to the country and locality of installation ! CAUTION: Risk of Equipment Failure. Failure to follow these directions may result in failure of this device to report an alarm or trouble condition or respond properly to an alarm condition. Johnson Controls is not responsible for devices that were improperly installed, tested, or maintained by others. Standards As is the case with all installations under NFPA, Underwriter’s Laboratories®, Inc. (UL), Underwriter’s Laboratories of Canada (ULC), or Canadian Electrical Code classification, final written approval of permissible operation and configuration rests with the Authority Having Jurisdiction (AHJ). Johnson Controls smoke detectors are marked with a compatibility identifier—the last digit of the five-digit code stamped on the base of the product. Connect detectors to compatible control units only. For a list of UL-Listed control units and detectors, refer to the Johnson Controls Device Compatibility Technical Bulletin (LIT-445180). 2 7351J Very Intelligent Early Warning (VIEW) Laser Smoke Detector Technical Bulletin General Description The 7351J is a plug-in type smoke sensor that has a laser-based photoelectronic sensing chamber. Using FlashScan® communication protocol on the Signaling Line Circuit (SLC), the sensor uses analog-addressable communications to transmit smoke density and other information to the central panel. The use of a laser diode provides substantial improvements in signal-to-noise ratio compared to a traditional Light-Emitting Diode (LED) light source. The sensor transmits an analog representation of smoke density over a multiplexed SLC to the Intelligent Fire Controller (IFC) control panel. Rotary switches are provided for setting the IFC panel’s SLC sensor address (1-159). The sensor has two multicolored LEDs controlled by the panel to indicate sensor status. Flashing green indicates normal operation and steady red indicates alarm, pre-alarm, or trouble. An output is provided for connection to an optional remote LED alarm annunciator (Model RA400Z). Test LED Laser Diode and Intergral Lens Assembly Smoke Direction Baffles Sensing Chamber Laser Beam Mirror Detail Light Trap Photo Receiver Mirror (See detail at right.) lpx751_1 Figure 1: Inside the 7351J 7351J Very Intelligent Early Warning (VIEW) Laser Smoke Detector Technical Bulletin 3 Table 1: Technical Specifications Operating Voltage Range 15 to 32 VDC Maximum Standby Current 230 microamperes at 24 VDC (no communication) Maximum Average Standby Current 330 microamperes at 24 VDC (one communication every 5 seconds with LED blink enabled) Maximum Alarm Current 6.5 milliamperes at 24 VDC (LED on) Operating Humidity Range 10 to 93% RH, noncondensing Operating Temperature Range 0 to 38°C (32 to 100°F) UL Listed range Shipping Weight 164 g (5.8 oz) Agency Listings UL Listed (S1948), FM approved, MSFM, MEA, CSFM Dimensions (Installed in Specified Base) B210LPJ Height: Diameter: 43 mm (1.7 in.) 155 mm (6.1 in.) B501J Height: Diameter: 43 mm (1.7 in.) 104 mm (4.1 in.) B501H and B501BHT Height: Diameter: 56 mm (2.2 in.) 152 mm (6 in.) B224BI and B224RB Height: Diameter: 51 mm (2 in.) 155 mm (6.1 in.) Accessories 4 Part Number Standard United States Low Profile Base B210LPJ Standard European Flangless Surface Base B501J Sounder base; includes B501 Base B501BH Intelligent Relay Base B224RB Intelligent Isolator Base; Isolates Signaling Line Circuit from Electrical Shorts B224BI Retrofit Replacement Flange for B501BJ Base F110 Remote LED Annunciator RA400Z Surface Mounting Kit (B501J Bases only) SMK400 Test Magnet M02-04-01 Detector Removal Tool XR-2 Extension Pole for XR-2 XP-4 7351J Very Intelligent Early Warning (VIEW) Laser Smoke Detector Technical Bulletin Installation Procedures Pre-Installation Guidelines This section contains information for Johnson Controls 7351J laser smoke detectors. It includes guidelines for spacing the detectors and for installing wiring. ! WARNING: Risk of Personal Injury. Use of control, adjustments, or performance of procedures other than those specified in this technical bulletin may result in hazardous radiation exposure. Spacing Sensors Wiring Installation Guidelines Follow these guidelines for spacing sensors: • Space the sensors in compliance with NFPA 72. • In low airflow applications with smooth ceilings, space the sensors to provide a maximum coverage of 81 square meters (900 square feet) under ideal conditions. • Refer to NFPA 72 for specific information regarding sensor spacing, placement, and special applications. Follow these guidelines to install wiring: • Install all wiring in compliance with the National Electrical Code (NEC), applicable local codes, and the special requirements of the Authority Having Jurisdiction and the system control panel’s SLC requirements. • Use proper wire size. • Use color-coded installation wires to limit wiring mistakes and to ease system troubleshooting. Improper connections prevent a system from responding properly in a fire. 7351J Very Intelligent Early Warning (VIEW) Laser Smoke Detector Technical Bulletin 5 Detector Installation Procedure ! CAUTION: Risk of Equipment Damage. Installation with power on may damage the detector and the fire alarm control panel. Always remove power from the SLC communication line before installing detectors. Use the following procedure to install a detector: 1. Install and wire the detector base (supplied separately). As a guide, use the wiring diagram in the technical bulletin for the detector base. 2. Use the detector rotary switches to set the detector to the desired Signaling Line Circuit (SLC) address. Figure 2 illustrates SLC Address 14. To set the address switch, do the following: • Rotate the right dial so that the arrow points to the address unit digit. • Rotate the left dial so that the arrow points to the address 10s digit. IO's 67 8 9 5 10 4 11 3 12 13 2 1 0 15 14 Units 56 4 3 2 10 789 rotary Figure 2: Rotary SLC Address Switches Limiting Dust Exposure 3. Write the address on the label located on the base. 4. Install the detector by pushing the detector into the base while turning it clockwise. This secures it in place. 5. After installing all the detectors, apply power to connect to the fire alarm control panel, the SLC, and program the detector into the system. 6. Test the sensors using the procedures in the Testing section of this technical bulletin. Use dust covers to limit dust entry to the detector during construction, remodeling, or other activities which produce significant amounts of dust. However, dust covers are not a substitute for removing the detector during building construction. If detectors are mounted in a construction area (with or without the dust cover in place), thoroughly clean, inspect, and test each detector when construction is complete. IMPORTANT: service. 6 Remove all dust covers before placing the system in 7351J Very Intelligent Early Warning (VIEW) Laser Smoke Detector Technical Bulletin Testing and Maintenance Procedures All detectors must be tested after installation and after periodic maintenance. Testing methods must satisfy the Authority Having Jurisdiction. Detectors offer maximum performance when they are tested and maintained in compliance with NFPA 72 National Fire Alarm Code. Testing This section provides procedures for testing the 7351J smoke detector. Before You Begin Testing Before you begin testing: Before You Test Each Detector 1. Notify the proper authorities that the system is undergoing maintenance and is out of service temporarily. 2. Disable specific system functions to prevent unwanted alarms. Before you test each detector, verify that the green LEDs blink (indicating SLC polling). 1. 2. If they do not blink, and LEDs on the other detectors and/or addressable modules on the same SLC blink, check the following: • the connection between the SLC and the detector • the control panel’s program to verify that the detector is programmed correctly • the SLC connections at the control panel If the LEDs on the detector still do not blink, return the detector to Johnson Controls for service. After You Test Each Detector After you set a detector into alarm by one of the following test methods and remove the alarm activating device from the detector, reset the system at the control panel before testing additional detectors. However, if the Walk Test function of the IFC control panel is being used, reset is unnecessary. After Testing and Maintenance Are Complete When you complete maintenance and all subsequent testing, do the following: 1. Enable the system functions that you previously disabled. 2. Notify the authorities that the system is again in normal service. 7351J Very Intelligent Early Warning (VIEW) Laser Smoke Detector Technical Bulletin 7 Testing Frequency The sensitivity and function of each detector must be tested after the initial installation and periodically thereafter. Refer to the NFPA 72 National Fire Alarm Code for the required frequency. Check with your local authority for the requirements in your area. Test Procedures This section describes the procedures you use to verify detector operation. It includes four tests; each one tests a different portion of the detector’s functionality. The tests include: Table 2: Test Functions Test If a Test Fails When Each Test Is Complete When All Testing Is Complete 8 Description Functional Test Use a magnet to test the functioning of the detector. Smoke Entry Test Use canned smoke to test for smoke entry. High Sensitivity Setting Test For smoke-free, environmentally controlled applications If a sensor fails any of the tests, do the following: 1. Clean the sensor by following the directions under the Maintenance section of this technical bulletin. 2. Retest the detector. 3. If the detector fails again, replace it and return it for repair. After using any of these methods to cause an alarm, and before resetting the system control panel, you must do the following: 1. Remove the alarm source (magnet or aerosol). 2. Allow the detector sensor to return to its non-alarm state. When testing is complete: 1. Restore the system to normal operation. 2. Notify the proper authorities that the system is again in operation. 7351J Very Intelligent Early Warning (VIEW) Laser Smoke Detector Technical Bulletin Four Tests Functional Test You can test the functioning of this detector using a test magnet (M02-04-01). This magnet electronically simulates smoke in the sensing chamber, testing the detector electronics and connections to the control panel. To test the detector, hold the test magnet in the magnet test area as illustrated in Figure 3. If the detector is functioning properly, the following occur: • Both LEDs latch on within 30 seconds, indicating an alarm. • The control panel registers an alarm from the detector. LED 2 Test Magnet Painted Surface T Ma e st gn et Painted Surface LED 1 position Figure 3: Test Magnet Position Sensitivity Test You may initiate a sensitivity test either manually or automatically by the Intelligent Fire Controller panel, if the panel is designed and UL Listed to perform such a test. To verify this, check the technical manual for the fire alarm control panel. Smoke Entry Test Use the Gemini Model 501 aerosol generator to test for smoke entry as follows: 1. Set the generator to represent 4% per ft to 5% per ft obscuration as described in the manual for the Gemini 501 generator. 2. Use the bowl-shaped applicator and apply aerosol until the detector alarms. It should alarm after 30 seconds. Smoke entry can also be simulated from the control panel. 7351J Very Intelligent Early Warning (VIEW) Laser Smoke Detector Technical Bulletin 9 High Sensitivity Setting Test The use of the 0.03% to 0.5% per ft sensitivity setting requires a 90-day test period to ensure that the detector’s environment is suitable for this setting. For each detector intended for 0.03% to 0.5% per ft alarm application, follow the steps below to meet Johnson Controls and UL requirements for this high sensitivity application. 1. Set the initial alarm setting 0.5% per ft obscuration alarm level. 2. Set the initial pre-alarm setting for the detector to the intended alarm setting of the system. 3. Set the pre-alarm for nonlatching operation. Notes: Detectors set at 0.03% to 0.5% per ft are intended for use in smoke-free, environmentally controlled applications, such as computer rooms and clean rooms. To determine if an environment is suitable for installation, operate the detectors continuously for 90 days with all environmental factors (such as temperature, humidity, air flow, occupancy) similar to the intended application for these detectors. Use an electronic history file or printer to record all events associated with the detectors under testing. At the end of 90 days, a Johnson Controls branch representative (or end user trained by a Johnson Controls branch representative), should inspect the results of the test by reviewing the data collected in the history file of the system control panel or the record on the system’s printer. If no alarms or pre-alarms are recorded for the detectors under testing, set the system to the tested pre-alarm level in the 0.03% to 0.5% per ft range. Maintenance This section contains procedures for cleaning the devices. IMPORTANT: This detector must be tested and maintained regularly following NFPA requirements. Clean the detector at least once a year and more frequently in dirty environments. Before Cleaning Before cleaning a device: 1. Notify the proper authorities that the system is undergoing maintenance and is out of service temporarily. 2. Disable the system to prevent unwanted alarms. ! WARNING: Risk of Personal Injury. Remove power before disassembling the unit. 10 7351J Very Intelligent Early Warning (VIEW) Laser Smoke Detector Technical Bulletin When Testing and Maintenance Are Complete Detector Cleaning Procedure When maintenance and all subsequent testing are complete: 1. Enable the system functions previously disabled for maintenance. 2. Notify the authorities that the system is back in service. Use this procedure to clean the detector. 1. Remove the detector to be cleaned from its mounting base. 2. Remove the detector cover using a small, standard screwdriver to release each of four cover removal tabs that hold the cover in place (see Figure 4). 3. Carefully vacuum the outside of the assembly screen (the Smoke Sensing Chamber Cover/Screen in Figure 4) without removing it. 4. Remove the detector screen assembly by pulling it straight away from the sensing chamber base (see Table 1). 5. Use a vacuum or clean compressed air to remove dust and debris from the sensing chamber. 6. Re-install the screen assembly. 7. Align the arrow on the screen assembly with the arrow on the sensor that points toward the sensing chamber. Push the screen down carefully until it snaps into place. 8. Make sure that one of the screen contacts touches the circuit board contact. 9. Re-install the detector cover using the LEDs to align the cover with the detector. Snap the cover into place. 10. Check the rotary SLC address switches to verify that the correct address is set for the detector mounting base location. 11. Re-install the detector in its mounting base. 12. Restore system operation for testing purposes when all detectors are clean. 13. Test the detectors as described in the Testing section of this technical bulletin. 7351J Very Intelligent Early Warning (VIEW) Laser Smoke Detector Technical Bulletin 11 Detector Cover RF Shield Cover Removal Tabs Chamber Cover Smoke Sensing Chamber Cover/Screen Photo Diode Circuit Board Smoke Sensing Chamber Base Spring Contact To Bug Screen Contacts to Mounting Brackets Smoke Detector Base lpx751_2 Figure 4: Screen Assembly and Sensing Chamber Laser Safety Information This smoke detector does not produce any hazardous laser radiation. It is certified as a Class 1 laser product under the United States Department of Health and Human Services (DHHS) Radiation Performance Standard according to the Radiation Control for Health and Safety Act of 1968. The radiation emitted inside the smoke detector is completely within the protective housings and external covers. The laser beam cannot escape from the detector during any phase of operation. The Center of Devices and Radiological Health (CDRH) of the United States Food and Drug Administration implemented regulations for laser products on August 2, 1976. These regulations apply to laser products manufactured after August 1, 1976. Compliance is mandatory for products marketed in the United States. 12 7351J Very Intelligent Early Warning (VIEW) Laser Smoke Detector Technical Bulletin This smoke detector is designed to activate and initiate emergency action but does so only when used with other equipment. This detector is designed for installation in accordance with NFPA Standard 72 National Fire Alarm Code, or equivalent codes and standards applicable to country of installation. Limitations Consider the following: Controls Group 507 E. Michigan Street P.O. Box 423 Milwaukee, WI 53201 • Smoke detectors do not work without power. Power is provided to this detector when the SLC wiring provides an electrical connection between the detector and the properly powered and programmed IFC panel. • Smoke detectors do not sense fires that start where smoke does not reach the detectors. Smoke from fires in chimneys, in walls, on roofs, or on the other side of closed doors may not reach the smoke detector and alarm it. • A detector may not detect a fire developing on another level of a building. For this reason, detectors should be located on every level of a building. • Smoke detectors have sensing limitations. Ionization detectors offer a broad range fire-sensing capability, but they are better at detecting fast, flaming fires than slow, smoldering fires. Photoelectronic detectors sense smoldering fires better than flaming fires. Because fires develop in different ways and are often unpredictable in their growth, neither type of detector is always best, and a given detector may not always provide warning of a fire. In general, detectors cannot be expected to provide warnings for fires resulting from inadequate fire protection practices, violent explosions, escaping gas, improper storage of flammable liquids like cleaning solvents, other safety hazards, or arson. • This detector is UL Listed to operate in a maximum air velocity of 1219 m (4000 ft) per min. Air velocity, along with other factors, may affect detector sensitivity. See the NFPA 72-National Fire Alarm Code for information. • At least semiannually, test your smoke detector system according to NFPA 72 National Fire Alarm Code or equivalent codes and standards applicable to the country of installation. • Clean and take care of your smoke detectors regularly. Taking care of the fire detection system you have installed measurably reduces your product liability risks. Published in U.S.A. www.johnsoncontrols.com 7351J Very Intelligent Early Warning (VIEW) Laser Smoke Detector Technical Bulletin 13