Duplex Pump Control Panels

advertisement
Duplex Pump Control Panels
Metron Duplex Pump Panels are designed for constant speed dual motor control
applications.
The standard controller consists of a main disconnect switch or circuit breaker, a control
transformer, two motor starters including overloads sized for the horsepower of each
connected motor and two hand-off-auto selector switches. The Metron Duplex Controllers
are supplied standard in a NEMA 3R rated enclosure painted gray.
Options available for Metron Duplex Controllers include circuit breakers in lieu of fuses and
fuse block, audible and visual alarms, pressure switches, timing features, and protective
devices. Optional enclosures include NEMA type 4, 4X and 12.
Listings
Metron Duplex Controllers are listed by Underwriters’ Laboratories, Inc. under UL 508
Standard for Industrial Control Equipment and meet or exceed the requirements set by the
National Electric Code. (N.E.C.).
Motor Starters
All motor starters supplied in Metron Duplex Controls are internationally rated and have
approvals from UL, CSA, Demko, Nenko, Semko, FI and ASE. The overloads are current
sensing and are designed to hold during high current demand when starting but will trip when
a sustained overload occurs. Tripping class of these overloads is according to UL 508 and
IEC 947-4. These overloads are designed to operate from 0 to 400 Hz and are available to
cover a wide range of full-load motor currents. The overloads offer manual or automatic
reset and are designed to protect AC circuits and motors against overloads, phase failure, and
long starting times.
Disconnect and Fuses
Metron Duplex Pump Panels are supplied with a main disconnect switch or circuit breaker.
The switch has door mounted handle with provisions for a padlock. Access to the enclosure
can only be gained when the disconnect device is in the “off” position; however, either device
does incorporate a defeater mechanism for service situations.
Note: All Metron Controls are priced and supplied standard with fuses. Replacement fuses
can be supplied separately. Please refer to the Metron power fuse selection chart for sizes
and pricing.
Operators and Alarms
Each Metron Duplex Controller is supplied with two “hand-off-auto” switches. In addition, a
wide variety of audible and visual alarms as well as start-stop pushbuttons and overload
resets can be supplied as options. Please refer to the option pages for details.
Custom Controls
While Metron offers a complete line of Simplex, Duplex and Triplex controls available with
a myriad of options, we understand that for some applications custom engineered controls
may be required. We offer complete engineering and fabrication services for almost any
control product need. For application assistance, please consult the factory.
Options
Sequencing
Start-Stop by Maintained Contact Devices
Includes all necessary wiring and terminal points for use with remote contact devices.
Additive with lead motor shutdown.
Option………..SA1
Non-additive with lead motor shutdown.
Option………..SN1
Additive with continuous duty lead motor.
Option………..SC1
Start-Stop by Momentary Contact Devices
Includes all necessary wiring and terminal points for use with the momentary contact devices.
Additive with lead motor shutdown.
Option……….TA1
Non-additive with lead motor shutdown.
Option……….TN1
Additive with continuous duty lead motor.
Option……….TC1
Manual Alternation
Lead-lag alternation via a door mounted selector switch.
Duplex motors 1 and 2.
Option………MA1
24-Hour Time Clock Alternation
Lead-lag status is switched every 24 hours via a time clock.
Duplex motors 1 and 2.
Option………DA1
Automatic Alternation
Lead-lag is alternated at the end of every run cycle.
Duplex motors 1 and 2.
Option………AA1
Operators
Pressure Switches
Externally mounted pressure switches available in two pressure ranges.
0-300 PSI
Option………PL2
0-600 PSI
Option………PH2
Overload relay reset
Door mounted pushbuttons to manually reset the overload relays.
Option………DR2
Motor Operation Timers
All motor timers are adjustable from .1 seconds to 10 hours and are available for the
following features:
Motor Start Delay Timer
Timer begins on demand signal.
Option………MS2
Motor Stop Delay Timer
Timer begins when demand signal is satisfied.
Option………MT2
Minimum Run Timer
Begins timing on motor run.
Option………RT2
Elapsed Time Meter
A motor running time meter which records to 99,999 hours.
Option………ET2
Indicators
Power on Light
A green pilot light mounted on the enclosure to indicate “power on”.
Option………PD
Motor Running Pilot Light
A pilot light mounted on the enclosure to indicate “motor running”.
Option………MR2
Motor Overload Pilot Light
A pilot light mounted on the enclosure to indicate “motor overload”.
Option………MD2
Protective Devices
Voltage Surge Arrestors
A surge arrestor in compliance with ANSI/IEEE C62.11.1987.
Option………SS
Anti Condensation Space Heaters
120 volt space heater supplied with thermostat.
Option………HT
120 volt space heater supplied with humidistat.
Option………HH
Alarms
Visible Low Suction Pressure Alarm
Door mounted pilot light to indicate low suction pressure. The pressure switch must be
ordered separately.
Auto Reset - no motor shutdown.
Option………CL1
Auto Reset - motor shutdown.
Option………CL2
Audible and Visible Low Suction Pressure Alarm
Door mounted pilot light and audible alarm to indicate low suction pressure. The pressure
switch must be ordered separately.
Auto Reset - no motor shutdown.
Option………AL1
Auto Reset - motor shutdown.
Option………AL2
Visible High Suction Pressure Alarm
Door mounted pilot light to indicate high suction pressure. The pressure switch must be
ordered separately.
Auto Reset - no motor shutdown.
Option………CH1
Auto Reset - motor shutdown.
Option………CH2
Audible and Visible High Suction Pressure Alarm
Door mounted pilot light and audible alarm to indicate high suction pressure. The pressure
switch must be ordered separately.
Auto Reset - no motor shutdown.
Option………AH1
Auto Reset - motor shutdown.
Option………AH2
Visible Low System Pressure Alarm
Door mounted pilot light to indicate low system pressure. The pressure switch must be
ordered separately.
Auto Reset - no motor shutdown.
Option………CS1
Auto Reset - motor shutdown.
Option………CS2
Audible and Visible Low System Pressure Alarm
Door mounted pilot light and audible alarm to indicate low system pressure. The pressure
switch must be ordered separately.
Auto Reset - no motor shutdown.
Option………AS1
Auto Reset - motor shutdown.
Option………AS2
Visible High System Pressure Alarm
Door mounted pilot light to indicate high system pressure. The pressure switch must be
ordered separately.
Auto Reset - no motor shutdown.
Option………CU1
Auto Reset - motor shutdown.
Option………CU2
Audible and Visible High System Pressure Alarm
Door mounted pilot light and audible alarm to indicate high system pressure. The pressure
switch must be ordered separately.
Auto Reset - no motor shutdown.
Option………AU1
Auto Reset - motor shutdown.
Option………AU2
Visable Alarm
A door mounted pilot light. Activating contacts by others.
Option……….VA
Normally Open Normally Closed Dry Contacts for Remote Operation
One set of NO./NC dry contacts for each remote alarm. Please specify the alarm function.
Option………NC
Silenceable Audible and Visual Alarm
Door mounted pilot light and audible alarm with silence pushbutton. Please specify alarm
function.
Auto Reset - no motor shutdown.
Option………BA1
Auto Reset - motor shutdown.
Option………BA2
Timer for Delay Alarm Activation
Timer with setting form .1 seconds to 10 hours. Please specify alarm.
Option……….DA
Manual Alarm Reset
Door mounted pushbutton for alarm reset. Please specify the alarm.
Option………AR
Modifications
Enclosures
Metron Control Products are supplied standard in NEMA 3R rated enclosures which are
intended for outdoor use and provide a degree of protection against falling rain, sleet, and
external ice formation. The following additional enclosures are available as options.
NEMA 4
Option………EN1
NEMA 4X
Option………EN2
NEMA 12
Option………EN3
Additional enclosure options include:
• Mounting feet
• Stainless steel enclosures
• Additional paint offerings
50 Hertz Operation
Metron Control Panels are supplied standard for 60 Hertz operation. Controls designed for 50
Hertz operation can be supplied at no additional charge.
Circuit breakers
Metron Duplex Control Panels can be supplied with a main circuit breaker in lieu of the
disconnect switch. To order controls with a circuit breaker, please substitute the last letter
“D” with the letter “C” in the product designation. Please note that some horsepowers and
voltages are supplied standard with a main circuit breaker due to the higher amperage ratings
required for these models. For pricing of controls with a circuit breaker, please refer to the
circuit breaker price sheet.
Note: Metron Duplex Control Panels can be supplied with individual circuit breakers for each
connected motor in lieu of fuses. For pricing of controls with individual motor circuit
breakers, please consult with the factory.
Duplex Control Panel Base Part Numbering Chart
Horsepower
Voltage
208V
230V
380V
460V
0.25
MDD-.25-208 MDD-.25-230 MDD-.25-380 MDD-.25-460
0.33
MDD-.33-208 MDD-.33-230 MDD-.33-380 MDD-.33-460
0.50
MDD-0.5-208 MDD-0.5-230 MDD-0.5-380 MDD-0.5-460
0.75
MDD-.75-208 MDD-.75-230 MDD-.75-380 MDD-.75-460
1.0
MDD-1.0-208 MDD-1.0-230 MDD-1.0-380 MDD-1.0-460
1.5
MDD-1.5-208 MDD-1.5-230 MDD-1.5-380 MDD-1.5-460
2.0
MDD-2.0-208 MDD-2.0-230 MDD-2.0-380 MDD-2.0-460
3.0
MDD-3.0-208 MDD-3.0-230 MDD-3.0-380 MDD-3.0-460
4.0
MDD-4.0-208 MDD-4.0-230 MDD-4.0-380 MDD-4.0-460
5.0
MDD-5.0-208 MDD-5.0-230 MDD-5.0-380 MDD-5.0-460
7.5
MDD-7.5-208 MDD-7.5-230 MDD-7.5-380 MDD-7.5-460
10
MDD-10-208
MDD-10-230
MDD-10-380
MDD-10-460
15
MDD-15-208
MDD-15-230
MDD-15-380
MDD-15-460
20
MDD-20-208
MDD-20-230
MDD-20-380
MDD-20-460
25
MDD-25-208
MDD-25-230
MDD-25-380
MDD-25-460
30
MDC-30-208
MDD-30-230
MDD-30-380
MDD-30-460
40
MDC-40-208
MDC-40-230
MDD-40-380
MDD-40-460
50
MDC-50-208
MDC-50-230
MDD-50-380
MDD-50-460
60
MDC-60-208
MDC-60-230
MDC-60-380
MDD-60-460
75
MDC-75-208
MDC-75-230
MDC-75-380
MDC-75-460
100
MDC-100-208 MDC-100-230 MDC-100-380 MDC-100-460
125
MDC-125-208 MDC-125-230 MDC-125-380 MDC-125-460
150
MDC-150-208 MDC-150-230 MDC-150-380 MDC-150-460
200
MDC-200-208 MDC-200-230 MDC-200-380 MDC-200-460
*For voltages not shown, please consult the factory.
Supplied standard with main circuit breaker in lieu of a main disconnect switch
575V
MDD-.25-575
MDD-.33-575
MDD-0.5-575
MDD-.75-575
MDD-1.0-575
MDD-1.5-575
MDD-2.0-575
MDD-3.0-575
MDD-4.0-575
MDD-5.0-575
MDD-7.5-575
MDD-10-575
MDD-15-575
MDD-20-575
MDD-25-575
MDD-30-575
MDD-40-575
MDD-50-575
MDD-60-575
MDD-75-575
MDC-100-575
MDC-125-575
MDC-150-575
MDC-200-575
Ordering Information
To order Metron Duplex Submersible Pump Panels, choose the correct base part number
from the above part numbering chart for the desired horsepower and voltage. For additional
options, add the appropriate option code suffix.
Example:
To order a Duplex Panel with a main disconnect switch for 25 horsepower and 380 volts
with:
0-300 PSI pressure switch
Option……….PL2
Minimum run timer
Option………RT2
Power on Pilot light
Option………PD
Specify the following part number designation: MDD-25-380, PL2, RT2, PD
Example:
To order a Duplex Panel with a main circuit breaker for 25 horsepower and 380 volts with:
0-300 PSI pressure switch
Option……….PL2
Minimum run timer
Option………RT2
Power on Pilot light
Option………PD
Specify the following part number designation: MDC-25-380, PL2, RT2, PD
Download