Duplex Pump Control Panels Metron Duplex Pump Panels are designed for constant speed dual motor control applications. The standard controller consists of a main disconnect switch or circuit breaker, a control transformer, two motor starters including overloads sized for the horsepower of each connected motor and two hand-off-auto selector switches. The Metron Duplex Controllers are supplied standard in a NEMA 3R rated enclosure painted gray. Options available for Metron Duplex Controllers include circuit breakers in lieu of fuses and fuse block, audible and visual alarms, pressure switches, timing features, and protective devices. Optional enclosures include NEMA type 4, 4X and 12. Listings Metron Duplex Controllers are listed by Underwriters’ Laboratories, Inc. under UL 508 Standard for Industrial Control Equipment and meet or exceed the requirements set by the National Electric Code. (N.E.C.). Motor Starters All motor starters supplied in Metron Duplex Controls are internationally rated and have approvals from UL, CSA, Demko, Nenko, Semko, FI and ASE. The overloads are current sensing and are designed to hold during high current demand when starting but will trip when a sustained overload occurs. Tripping class of these overloads is according to UL 508 and IEC 947-4. These overloads are designed to operate from 0 to 400 Hz and are available to cover a wide range of full-load motor currents. The overloads offer manual or automatic reset and are designed to protect AC circuits and motors against overloads, phase failure, and long starting times. Disconnect and Fuses Metron Duplex Pump Panels are supplied with a main disconnect switch or circuit breaker. The switch has door mounted handle with provisions for a padlock. Access to the enclosure can only be gained when the disconnect device is in the “off” position; however, either device does incorporate a defeater mechanism for service situations. Note: All Metron Controls are priced and supplied standard with fuses. Replacement fuses can be supplied separately. Please refer to the Metron power fuse selection chart for sizes and pricing. Operators and Alarms Each Metron Duplex Controller is supplied with two “hand-off-auto” switches. In addition, a wide variety of audible and visual alarms as well as start-stop pushbuttons and overload resets can be supplied as options. Please refer to the option pages for details. Custom Controls While Metron offers a complete line of Simplex, Duplex and Triplex controls available with a myriad of options, we understand that for some applications custom engineered controls may be required. We offer complete engineering and fabrication services for almost any control product need. For application assistance, please consult the factory. Options Sequencing Start-Stop by Maintained Contact Devices Includes all necessary wiring and terminal points for use with remote contact devices. Additive with lead motor shutdown. Option………..SA1 Non-additive with lead motor shutdown. Option………..SN1 Additive with continuous duty lead motor. Option………..SC1 Start-Stop by Momentary Contact Devices Includes all necessary wiring and terminal points for use with the momentary contact devices. Additive with lead motor shutdown. Option……….TA1 Non-additive with lead motor shutdown. Option……….TN1 Additive with continuous duty lead motor. Option……….TC1 Manual Alternation Lead-lag alternation via a door mounted selector switch. Duplex motors 1 and 2. Option………MA1 24-Hour Time Clock Alternation Lead-lag status is switched every 24 hours via a time clock. Duplex motors 1 and 2. Option………DA1 Automatic Alternation Lead-lag is alternated at the end of every run cycle. Duplex motors 1 and 2. Option………AA1 Operators Pressure Switches Externally mounted pressure switches available in two pressure ranges. 0-300 PSI Option………PL2 0-600 PSI Option………PH2 Overload relay reset Door mounted pushbuttons to manually reset the overload relays. Option………DR2 Motor Operation Timers All motor timers are adjustable from .1 seconds to 10 hours and are available for the following features: Motor Start Delay Timer Timer begins on demand signal. Option………MS2 Motor Stop Delay Timer Timer begins when demand signal is satisfied. Option………MT2 Minimum Run Timer Begins timing on motor run. Option………RT2 Elapsed Time Meter A motor running time meter which records to 99,999 hours. Option………ET2 Indicators Power on Light A green pilot light mounted on the enclosure to indicate “power on”. Option………PD Motor Running Pilot Light A pilot light mounted on the enclosure to indicate “motor running”. Option………MR2 Motor Overload Pilot Light A pilot light mounted on the enclosure to indicate “motor overload”. Option………MD2 Protective Devices Voltage Surge Arrestors A surge arrestor in compliance with ANSI/IEEE C62.11.1987. Option………SS Anti Condensation Space Heaters 120 volt space heater supplied with thermostat. Option………HT 120 volt space heater supplied with humidistat. Option………HH Alarms Visible Low Suction Pressure Alarm Door mounted pilot light to indicate low suction pressure. The pressure switch must be ordered separately. Auto Reset - no motor shutdown. Option………CL1 Auto Reset - motor shutdown. Option………CL2 Audible and Visible Low Suction Pressure Alarm Door mounted pilot light and audible alarm to indicate low suction pressure. The pressure switch must be ordered separately. Auto Reset - no motor shutdown. Option………AL1 Auto Reset - motor shutdown. Option………AL2 Visible High Suction Pressure Alarm Door mounted pilot light to indicate high suction pressure. The pressure switch must be ordered separately. Auto Reset - no motor shutdown. Option………CH1 Auto Reset - motor shutdown. Option………CH2 Audible and Visible High Suction Pressure Alarm Door mounted pilot light and audible alarm to indicate high suction pressure. The pressure switch must be ordered separately. Auto Reset - no motor shutdown. Option………AH1 Auto Reset - motor shutdown. Option………AH2 Visible Low System Pressure Alarm Door mounted pilot light to indicate low system pressure. The pressure switch must be ordered separately. Auto Reset - no motor shutdown. Option………CS1 Auto Reset - motor shutdown. Option………CS2 Audible and Visible Low System Pressure Alarm Door mounted pilot light and audible alarm to indicate low system pressure. The pressure switch must be ordered separately. Auto Reset - no motor shutdown. Option………AS1 Auto Reset - motor shutdown. Option………AS2 Visible High System Pressure Alarm Door mounted pilot light to indicate high system pressure. The pressure switch must be ordered separately. Auto Reset - no motor shutdown. Option………CU1 Auto Reset - motor shutdown. Option………CU2 Audible and Visible High System Pressure Alarm Door mounted pilot light and audible alarm to indicate high system pressure. The pressure switch must be ordered separately. Auto Reset - no motor shutdown. Option………AU1 Auto Reset - motor shutdown. Option………AU2 Visable Alarm A door mounted pilot light. Activating contacts by others. Option……….VA Normally Open Normally Closed Dry Contacts for Remote Operation One set of NO./NC dry contacts for each remote alarm. Please specify the alarm function. Option………NC Silenceable Audible and Visual Alarm Door mounted pilot light and audible alarm with silence pushbutton. Please specify alarm function. Auto Reset - no motor shutdown. Option………BA1 Auto Reset - motor shutdown. Option………BA2 Timer for Delay Alarm Activation Timer with setting form .1 seconds to 10 hours. Please specify alarm. Option……….DA Manual Alarm Reset Door mounted pushbutton for alarm reset. Please specify the alarm. Option………AR Modifications Enclosures Metron Control Products are supplied standard in NEMA 3R rated enclosures which are intended for outdoor use and provide a degree of protection against falling rain, sleet, and external ice formation. The following additional enclosures are available as options. NEMA 4 Option………EN1 NEMA 4X Option………EN2 NEMA 12 Option………EN3 Additional enclosure options include: • Mounting feet • Stainless steel enclosures • Additional paint offerings 50 Hertz Operation Metron Control Panels are supplied standard for 60 Hertz operation. Controls designed for 50 Hertz operation can be supplied at no additional charge. Circuit breakers Metron Duplex Control Panels can be supplied with a main circuit breaker in lieu of the disconnect switch. To order controls with a circuit breaker, please substitute the last letter “D” with the letter “C” in the product designation. Please note that some horsepowers and voltages are supplied standard with a main circuit breaker due to the higher amperage ratings required for these models. For pricing of controls with a circuit breaker, please refer to the circuit breaker price sheet. Note: Metron Duplex Control Panels can be supplied with individual circuit breakers for each connected motor in lieu of fuses. For pricing of controls with individual motor circuit breakers, please consult with the factory. Duplex Control Panel Base Part Numbering Chart Horsepower Voltage 208V 230V 380V 460V 0.25 MDD-.25-208 MDD-.25-230 MDD-.25-380 MDD-.25-460 0.33 MDD-.33-208 MDD-.33-230 MDD-.33-380 MDD-.33-460 0.50 MDD-0.5-208 MDD-0.5-230 MDD-0.5-380 MDD-0.5-460 0.75 MDD-.75-208 MDD-.75-230 MDD-.75-380 MDD-.75-460 1.0 MDD-1.0-208 MDD-1.0-230 MDD-1.0-380 MDD-1.0-460 1.5 MDD-1.5-208 MDD-1.5-230 MDD-1.5-380 MDD-1.5-460 2.0 MDD-2.0-208 MDD-2.0-230 MDD-2.0-380 MDD-2.0-460 3.0 MDD-3.0-208 MDD-3.0-230 MDD-3.0-380 MDD-3.0-460 4.0 MDD-4.0-208 MDD-4.0-230 MDD-4.0-380 MDD-4.0-460 5.0 MDD-5.0-208 MDD-5.0-230 MDD-5.0-380 MDD-5.0-460 7.5 MDD-7.5-208 MDD-7.5-230 MDD-7.5-380 MDD-7.5-460 10 MDD-10-208 MDD-10-230 MDD-10-380 MDD-10-460 15 MDD-15-208 MDD-15-230 MDD-15-380 MDD-15-460 20 MDD-20-208 MDD-20-230 MDD-20-380 MDD-20-460 25 MDD-25-208 MDD-25-230 MDD-25-380 MDD-25-460 30 MDC-30-208 MDD-30-230 MDD-30-380 MDD-30-460 40 MDC-40-208 MDC-40-230 MDD-40-380 MDD-40-460 50 MDC-50-208 MDC-50-230 MDD-50-380 MDD-50-460 60 MDC-60-208 MDC-60-230 MDC-60-380 MDD-60-460 75 MDC-75-208 MDC-75-230 MDC-75-380 MDC-75-460 100 MDC-100-208 MDC-100-230 MDC-100-380 MDC-100-460 125 MDC-125-208 MDC-125-230 MDC-125-380 MDC-125-460 150 MDC-150-208 MDC-150-230 MDC-150-380 MDC-150-460 200 MDC-200-208 MDC-200-230 MDC-200-380 MDC-200-460 *For voltages not shown, please consult the factory. Supplied standard with main circuit breaker in lieu of a main disconnect switch 575V MDD-.25-575 MDD-.33-575 MDD-0.5-575 MDD-.75-575 MDD-1.0-575 MDD-1.5-575 MDD-2.0-575 MDD-3.0-575 MDD-4.0-575 MDD-5.0-575 MDD-7.5-575 MDD-10-575 MDD-15-575 MDD-20-575 MDD-25-575 MDD-30-575 MDD-40-575 MDD-50-575 MDD-60-575 MDD-75-575 MDC-100-575 MDC-125-575 MDC-150-575 MDC-200-575 Ordering Information To order Metron Duplex Submersible Pump Panels, choose the correct base part number from the above part numbering chart for the desired horsepower and voltage. For additional options, add the appropriate option code suffix. Example: To order a Duplex Panel with a main disconnect switch for 25 horsepower and 380 volts with: 0-300 PSI pressure switch Option……….PL2 Minimum run timer Option………RT2 Power on Pilot light Option………PD Specify the following part number designation: MDD-25-380, PL2, RT2, PD Example: To order a Duplex Panel with a main circuit breaker for 25 horsepower and 380 volts with: 0-300 PSI pressure switch Option……….PL2 Minimum run timer Option………RT2 Power on Pilot light Option………PD Specify the following part number designation: MDC-25-380, PL2, RT2, PD