DC Current transducer DK-C420 A transducer for the electronic measurement DC current, with galvanic isolation between the primary (High power) and the secondary circuits (Electronic circuit) with current output. Electrical data Features Primary Nominal Current IPN (A.t) 5,10,20 50,75,100 Vc RL Supply voltage (not isolated) Load resistance (max) Vb Vd f Ic Analogue Output Signal1) IOUT (mA) 4-20 4-20 20-50 V DC • DC Measurement Types DK 20 C420 DK 100 C420 22-38 650 V AC Ω Rated voltage (CAT III, PD2) Isolation voltage 150 3 V AC kV Frequency Current consumption (max) DC 100 mA • Unipolar and bipolar measurement • Current output • Jumper selectable ranges • Panel mounting • Extended measuring range. Advantages • Large aperture • High isolation between primary and secondary circuits • Easy to mount • No insertion losses. Accuracy - Dynamic performance data X Accuracy @ IPN, TA=25°C ±1 εL tr Linearity error Response time @ 90% of IPN ± 0.75 < 100 % % mS General data TA Ambient operating temperature (0-95% RH) - 20 .. + 50 °C TS m Ambient storage temperature Mass Protection type Safety EMC - 20 .. + 85 120 IP 20 IEC 61010-1 EN 61326 2) °C g Applications • Battery Banks - Monitors load current - Monitors charging current - Verifies operation. • Transportation Measures traction power or auxiliary loads. • Electric Heating Elements Faster response than temperature sensors. Options on request Options Bipolar output : IPN = 5 .. 100A DK 20 C420 B DK 100 C420 B • • DIN mounting Bipolar output. Notes : 1) For 4-20mA outputs models, no saturation outputs up to 23 mA 2) For IEC 61000-4-3, IEC 61000-4-6 and IEC 61000-4-4 criterion B : temporary impairment to operational behavior. Remark : Temperature of the conductor should not exceed 60°C. 050415/6 LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice. LEM Components page 1/2 www.lem.com Dimensions DK - C420 (unit : mm, 1mm = 0.0394 inch) 73.5 27 63.5 19.1 36 26 98 18 5 85.7 Standard Output Mechanical characteristics output in mA • General tolerance • Primary aperture ± 1 mm 19.1 mm dia. • Panel mounting Distance between holes 2 holes ∅ 4.5 mm 77.3 mm 20 4 Connections • 2 x UNC8 Cylindric Head 20-50 VDC 22-38 22-26 VAC/DC + IP Bipolar Output output in mA Output 20 12 4 - Dead front captive screw terminals - 12-22AWG solid or stranded - IP 0 + IP 050415/6 LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice. LEM Components page 2/2 www.lem.com