Bulletin 140M/190E/190S
Motor Protectors and
Compact Starters
Modular
Solutions
for Motor
Management
File Name: AB_MotorProtectors_140E_cat_D100
1
2
3
4
5
6
7
8
9
11
16
15
13
14
17
12
18
2
1
2
3
4
5
6
7
8
9
10
Commoning Links
Blank Space Cover
Feeder Terminal
Undervoltage Release
Voltage Release
High Break, 25 A
High Break PLUS, 25 A
High Break PLUS, 45 A
Trip Contact, Side Mount
Auxiliary Contact, Side Mount
11
12
13
14
15
16
17
18
Door Coupling/Extension Shaft
Door Coupling Handle
Lockable Handle
Locking Tag
Auxiliary Contact, Front Mount
Combination Trip/
Auxiliary Contact, Front Mount
Connection Module
MCS Contactor
Modular Solutions for a New Era
Sophisticated construction and modern material
technology provide the new capabilities of the
Allen-Bradley 140M Motor Protectors,
completing the Modular Control System
UL/CSA Self-Protected (Type E) Combination Starters
UL/CSA Manual Starter with optional approval –
“Suitable for use as Motor Disconnect”
• Provides both overload and short circuit protection
for individual motors
Current limiting with fast interruption time delivers
excellent short circuit breaking capability
• Eliminates the need for additional short circuit protection
• 65kA at 480Y/277V as Type E, self-protected combination starters
• Eliminates the restrictive NEC/CEC rules that
apply to Group Motor installations
• 65kA at 480V as motor protectors in group motor installations
• Type 2 coordination at 480V without oversizing of contactors
Modular
Solutions
10
Outstanding flexibility through MCS modularity
Three sizes of motor protectors are available:
Three varieties of motor protectors are also available
140M-C
• Standard Trip – Class 10 adjustable bimetallic overload and 13X fixed
short circuit
• Motor protection from 0.10 to 25 A
• 45mm wide x 74mm deep
140M-D
• Motor protection from 1.6 to 25 A
• 45mm wide x 84mm deep
• Additional 10mm depth provides increased short
circuit capability on motors above 10 A
140M-F
• Motor protection from 6.3 to 45 A
• High Trip – Class 10 adjustable bimetallic overload and 16-20X fixed
short circuit
• Mag Only Trip – No overload and 13X fixed short circuit – for use with
MCS-E solid state overload relays
Dimensional and electrical integration with other MCS components
• Provides improved assembly/handling and reduces panel space
Comprehensive range of accessories
• Includes unique front-mounted trip contacts for greater signaling and
control functionality
• 54mm wide x 114mm deep
3
✔ Protection of installation
✔ Protection of circuits
✔ Motor protection
✔ Starter protection
✔ Wide range of ambient
temperature compensation
✔ Phase failure protection
✔ High phase loss sensitivity
The money saving champion
Comparison Type « 2 » co-ordinated
Price
140M-C
0,3 0,4 0,5 0,7 0,9 1,2 1,6
Rockwell Automation
140M
2
140M-D
2,8 3,7 5,3
7
9
12
16
20
23
Conventional solution
with oversizing
140M-F
30
37
43 [A]
Integrated
solutions
Improved Short Circuit Protection
480V Short Circuit Breaking Capacity
65KA
70
Fault Current
60
65KA
50
50
65KA
40
30
25
20
10
140M-F
140M-D
140M-C
10
4
45
32
25
20
16
10
6.3
4.0
2.5
1.6
1.0
0.63
0.25
0. 40
0.16
0
Full Load Current
• With the new 140M you get a superior
price/performance ratio compared to other
solutions.
• No oversizing of contactors necessary, this makes
starters more economical.
• No need for costly integrated starter solutions
thanks to the consistent modular concept.
• Compact starters lead to smaller, more economical
control cabinets and panels.
• The 140M motor protectors set new standards in
breaking capacity and current limiting.
➤ No back-up fuses needed
➤ No current limiters required
➤ No oversizing of contactors
• The 140M meets electrical code requirements for
short circuit protection of individual motors.
Lower Cost Functionality
140M-D.. 25 A | High Break PLUS | Scale 1:1
Smaller footprint than competitive
devices for the same performance.
Where space was needed for
five motor protectors, six 140M motor
protectors fit. A gain of 20%
Open terminals save wiring time
Finger safe terminals
Marking plate for the
Allen-Bradley labeling system
Easy to read data labels with performance
rating on both sides of the 140M
Short-circuit indicator provides
differentiation between
short-circuit trip and
overload trip
Easy mounting onto DIN Rails
Large scale for precise overload setting
Auxiliaries are snapped on
quickly and without tools
Test trip feature checks operation
of trip mechanism
Ergonomic handle provides clear
status indication ON-OFF-Tripped state
45 mm
Unique front mounted
trip/auxiliary contact with no
increase in overall dimensions.
Saves up to 20% of valuable panel space
Motor Protection made simple
Select 140M motor protector according to the rated motor current
• Complete branch circuit motor protection is provided
No current limiter needed
• Adjustable, ambient compensated bimetallic overload protection
• Rationalizes design, saves panel space.
• Short circuit protection is provided with Self-Protected (Type E)
combination starter listing
• You can build more economical and smaller panels.
Type 2 coordination with 100C contactors at 480V can be achieved
without oversizing
• Compared to competitive solutions, you get up to 20%
higher performance per volume unit.
No complicated calculations for multi-motor installations
5
Clear information at a glance
• Positive status indication
• Robust and powerful jump
mechanism leads to enhanced
safety and reliability
• Teaseproof operation
• Ergonomic handle design for ease
of operation
• Enhanced safety – has to be reset
to OFF position before reenergizing
Lockable rotary handles open wide fields of application
6
140M Motor Protectors are approved for application as:
• UL/CSA Self-Protected Combination Motor Controllers (UL508)
• UL/CSA Manual Motor Controller (UL508)
• Optional approval obtained for use as Motor Disconnect
• Disconnector (IEC 947-2)
• Main Switch (IEC 204-1)
• Emergency Off (IEC 204-1)
• Revision Service Switch (IEC947)
Door coupling ensure full
functionality
• Displays status indication of Motor Protector
at the door – OFF, ON and TRIP
• Door interlock when in ON position –
requires tool to override
• Common look and design of the
handles up to 90 A
Superior Actuation and Status Indication
Allen-Bradley 140M
I
ON
O OFF
Short-circuit indicator
• A red flag on the I» magnetic short
circuit trip window shows that a shortcircuit has occurred. This allows the
immediate distinction between a shortcircuit trip and an overload trip
• Saves time in troubleshooting
Other Motor Protectors
I
ON
O OFF
Jump mechanism guarantees clear switching status
• The jump mechanism ensures a very fast closing or opening
of the contacts
• The motor protector is either OFF or ON, 140M is teaseproof
• No more guessing if the motor protection is “ON” or tripped
Manipulation made impossible
• The anti-tamper cover prevents unauthorized
change of the operational current setting
• Clear current setting scale, recessed to
prevent unintentional setting changes
Undervoltage / voltage release
• Undervoltage release
• Undervoltage release with
2 early make contacts
• Voltage release
Front mounting trip /
auxiliary contacts
Side mounting
trip contacts
Side mounting
auxiliary contacts
More indication possibilities
• Different operation and fault conditions can be
transmitted by auxiliary contacts
• The 140M offers more auxiliary combinations than others:
➤ Front mounting: 6 variations
➤ Side mounting: 8 variations
7
Minimal arcing
safety clearance
required
Compact mounting allows
more compact panels
• Compact side by side mounting
saves valuable panel space.
No gaps required in between
devices
No gaps
required
• Lowest arcing safety space
requirements allow denser layouts
• No current limiters required
• No increase in width due to the
unique front mounted trip
indicator/auxiliary contact
• Consistent 9mm spacing simplifies
planning and installation
8
Compact
connection
modules
Faster and easier mounting
Vertical mounting saves space
Auxiliaries easily snap on
• No tools required for DIN Rail
mount/dismount
• Complete starter assemblies can be
snapped on only one DIN Rail for motors
up to 25 A. The new connection modules
mechanically fix the contactor to the
140M motor protector.
• Vertical mounting allows optimal
positioning of wiring channels
close to the components
• No tools required for installation
of auxiliaries
• Simple field modification even
when mounted
Compact Dimensions and Easy Handling
Built for faster wiring
Terminals save wiring time
• Easy fitting of large or different size conductors
• Only one screwdriver (Pozidrive No. 2 or blade type No. 3)
needed for all 140M components
• Dual terminal technology offers more wiring flexibility
• Screw driver guiding shafts speed up connection time
• Insertion funnels and shrouded terminals increase
• Delivered with open terminal screws for immediate wiring
finger protection
The smart concept for fast panel building
• Complete range of commoning links for easy wiring
• Connection modules facilitate the connection of motor
protectors and contactors
• Connection modules and commoning links are required for
building assemblies in compliance with the new regulations
(EN 60 439)
• Wiring accessories help build assemblies quickly, easily
and safely
9
Superior Functionality in Two Versions of
Compact Starters
Mounts to (1) DIN rail
Current adjustment dial
Short circuit trip indication
flag is required for SelfProtected (Type E) starters
140M Motor Protector
Connection module provides physical
and electrical connection of 140M to
100C or 100M up to 25 A
Bulletin 190E Eco Starters
Consists of a Bulletin 140M Motor Protector and
an IEC Contactor assembled into a single unit
using one of the new Connection Modules
• UL/CSA as Type E, Self-Protected Combination
Starters and Group Motor Starters
• Type 2 coordination per IEC947-4-1
• Available with 100-C MCS contactors through 23 A
- AC coils
• Available with 100-M Mini-Contactors
- AC or DC coils
Bulletin 190 Compact Combination Starters
• A Bulletin 190 Compact Combination Starter consists of a Bulletin 140M
Motor Protector and an IEC Contactor assembled into a single unit
• UL/CSA as Self-Protected (Type E) Combination Starters
• Type 2 coordination at 480V per IEC947-4-1
• Available with AC or DC coils
• Bulletin 191 Reversing Compact Combination Starters are also available
10
Wiring channel for control wires
25 A Eco Starter
100C Contactor
Coil terminals at bottom of assembly
for attractive and easy wiring
Bulletin 190S
Compact Starters
Consists of a Bulletin 140M Motor
Protector and an IEC Contactor
assembled into a single unit on a
mounting socket with an integrated
terminal block
• UL/CSA as Type E, Self-Protected
Combination Starters and Group
Motor Starters
• Type 2 coordination per IEC947-4-1
• Prewired terminal block
- (2) auxiliary/trip front mount contacts
from the 140M
- (1) auxiliary contact from the 100-C
contactor
- All control connections are at the
bottom of the starter to for attractive
and cost effective panel wiring
• Available with 100-C MCS contactors
through 43 A
- AC or DC coils
Socket base provides physical support
of 140M and 100C components for
applications up to 45 A
Mounts to (1) or (2) DIN
rails or screw mounts
Current adjustment dial
Short circuit trip
indication flag is
required for
Self-Protected
(Type E) starters
140M Motor
Protector
Front mount, 2 pole
auxiliary/trip
contact is standard
Enhanced unitary
appearance
100C Contactor
25 A Compact Starter
Coil terminals at bottom of assembly
for attractive and easy wiring
140M and 100C auxiliary contacts are
pre-wired to the integrated terminal block
To Supply
Bulletin 190 Compact Combination Starters
Bulletin 140M Motor Protector
Bulletin 100C
Motor Disconnecting Means
Short Circuit/Ground Fault Protection
Motor Overload Protection
190E/190S Compact
Combination Starter
Motor Controller (Contactor)
Motor
11
Bulletin 190E Eco Starters provide an
extremely cost-effective panel solution
• Self-Protected combination starter listing
eliminates NEC/CEC Group Motor rules
- A non-fusible disconnect may be used for
the main panel disconnecting means
• Bulletin 140M Commoning Links eliminate need for
splitter block or daisy chaining of power wiring
• Devices mount on a single DIN rail
- Connection Modules provide
electrical connection between 140M
and 100C or 100M contactors
- The contactor is also physical supported
from the 140M
• Coil terminals at bottom of assembly
for attractive panel wiring.
Bulletin 190S Compact Starters provide an
attractive panel design with value-added
functionality
• Self-Protected combination starter listing eliminates
NEC/CEC Group Motor rules
- A non-fusible disconnect may be used for the main
panel disconnecting means
• Bulletin 140M Commoning Links eliminate need for
splitter block or daisy chaining of power wiring
• Three mounting options are provided: (1) DIN rail,
(2) DIN rails or screw mount
• Auxiliary contacts of 140M and 100C are prewired to
the integrated terminal and coil terminals are also at
the bottom of the assembly, for attractive and cost
effective control wiring.
12
Bulletin 140M
Motor Protectors
0Circuit Breaker
0
Bulletin 140M
Motor Protectors
• Current Range 0.1...45 A
• With 140-CMN up to 90 A
• Type 2 Coordination with
Bulletin 100-C
Contactors
• UL Listed
• “Self-protected” Type E
Manual Combination
Starters
Cat. No. 140M-C2E
• Manual Starter
• Motor Disconnect
• Group Motor
Installation
•
•
•
•
Visible Trip Indication
Rotary Actuator
High Current Limiting
High Switching Capacity
Cat. No. 140M-F8E
TABLE OF CONTENTS
Description
Page
Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Specifications
Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Description
Page
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Type 2 Coordination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Description
The Bulletin 140M Motor Protector provides short circuit and overload protection for
individual motor loads. A wide range of accessories makes installation and wiring
easy. Motor protectors may be applied as Manual Starters, Group Motor Starters,
Motor Disconnects, and Manual Combination Starters.
Conformity to Standards:
Approvals:
IEC 947-1/2/4
CE
IEC 204-1
CSA Certified
CSA, C22.2 No.14
UL Listed
Your order must include:
UL 508
• Cat. No. of the motor protector
selected.
Construction Type E Self-Protected Manual Combination Starter.
• If required, Cat. No. of any
accessories.
Manual Motor Controller suitable for Group Installation.
Meets IEC Circuit Breaker requirements per IEC 947-2.
Does not meet UL489 requirements for molded case circuit breakers in North America.
13
Bulletins 140M and 190S/190E
Motors Protectors/Compact Starters/Eco Starters
Product Overview
General Information
The new Bulletin 140M Motor Protectors provide Class 10
overload protection as well as current limiting short-circuit
protection for individual motor loads. They are approved for use
as circuit breakers per IEC 947-2 for applications outside of
North America, but in the United States and Canada, they are
UL/CSA listed as Manual Starters with the optional approvals
for Motor Disconnecting and Group Motor applications.
400V, 50 Hz, 3-Phase Power Supply
140M-C2E
-C10
Circuit Breaker Applications – IEC
Contactor
Additionally, these new devices are UL/CSA listed as
Self-Protected (Type E) Manual Combination Starters —
eliminating the requirement for additional short-circuit protection
in many applications. This reduces both panel space and cost
in multi-motor installations and eliminates the restrictive NEC/
CEC rules that pertained to Manual Starters used in Group
Motor applications.
The following information is provided to aid in proper system
design utilizing the capabilities of the new Bulletin 140M Motor
Protectors in North American applications. Please be sure to
follow all local and national codes for your particular installation.
Circuit Breaker Applications – IEC
The new Bulletin 140M Motor Protectors are current limiting IEC
circuit breakers (IEC 947-2) that also provide Class 10 motor
overload protection. Additionally, they meet the IEC
requirements for applications such as:
• Disconnector (IEC 947-2)
Motor Protector
as
IEC Circuit Breaker
100-C09
14 AWG
7.6A
Fan #2
5 HP
Motor
480V, 60 Hz, 3-Phase Power Supply
194R-NN030P3
30A
Fusible
Disconnect
FUSE
3 Fuses
Manual Starter Applications – UL/CSA
140M-C2E
-C10
Motor
Protector
as
Manual Starter
• Main Switch (IEC 204-1)
14 AWG
• Emergency Off (IEC 204-1)
The Bulletin 140M Motor Protectors cannot be applied in North
America as circuit breakers, however, since they do not meet
the UL specification for circuit breakers (UL 489).
7.6A
Fan #1
5 HP
Motor
480V, 60 Hz, 3-Phase Power Supply
Manual Starter Applications – UL/CSA
The new Bulletin 140M Motor Protectors are an excellent choice
for manual starting applications. As UL/CSA listed manual motor
controllers they provide motor overload protection, but a
separate short-circuit protective device must still be used. The
fuse or circuit breaker used for the short-circuit protection may
be sized to the maximum allowable per NEC Article 430 in the
U.S. and CEC Rule 28-200 in Canada.
194R-NJ030P3
30A
Fusible
Disconnect
FUSE
3 Fuses
Contactor
100-C09
Motor Disconnecting Applications – UL/CSA
The new Bulletin 140M Motor Protectors are also UL/CSA listed
as manual motor controllers with the optional approval “Suitable
for use as a motor disconnect” when a lockable twist knob is
used. This UL listing is new in 1999 and allows the 140M’s to
be applied as “at-motor” disconnects. All manual starters used
in such applications must be marked as “suitable for use as a
motor disconnect” per UL 508. At motor disconnects are
required by the NEC if the motor cannot be seen from the main
panel disconnect.
193-E
Overload
140M-C2E
Motor Disconnecting Applications – UL/CSA
-C10
14 AWG
7.6A
Fan #1
5 HP
14
Motor Protector
as
At-Motor
Disconnect
Motor
Bulletins 140M and 190S/190E
Motors Protectors/Compact Starters/Eco Starters
Product Overview
Group Motor Applications – UL/CSA
The new 140M Motor Protectors are also UL/CSA listed as manual starters for use in Group Motor installations. This listing allows
the 140M Motor Protectors to be used as manual starters providing individual overload protection with a single set of fuses or a
circuit breaker providing the short-circuit protection for the “Group” of motors.
This is the most popular application for these products in North America and greatly reduces both panel space and cost versus the
traditional use of fuses or circuit breakers in each motor branch circuit. However, there are several NEC rules to follow for Group
Motor installations and one of these rules can dramatically affect panel size and layout. Per NEC Article 430-53(d), the conductors
of any tap supplying a single motor must have an ampacity less than one-third that of the branch-circuit conductors. This limits the
number of motors that can be “grouped” under one set of fuses or circuit breakers. See the following examples of two typical group
motor applications. For further assistance on how to properly apply Bulletin 140M Motor Protectors in Group Motor applications,
please see Publications 0140-2.3 and 6219-NP.
480V, 60 Hz, 3-Phase Power Supply
194R-NJ100P3
100A
80HP
Fuse
45 A
Fusible
Disconnect
3 Fuses
8 AWG
Commoning Links
140M-C2E
140M-C2E
-C10
-C10
-C10
100-C09
100-C09
100-C16
14 AWG
7.6A
Fan #1
5 HP
14 AWG
7.6A
Fan #2
5 HP
140M-C2E
14 AWG
7.5A
Heater #1
140M-C2E
140M-C2E
-C10
-C16
100-C16
14 AWG
100-C16
Motor Protectors
In this example, a single panel controls 5
motors. This Group Installation meets all of
the required NEC rules resulting in a very
compact, cost effective, and attractive panel
design.
Contactors
14 AWG
7.5A
Heater #2
14.0A
Pump #1
10 HP
Motors
480V, 60 Hz, 3-Phase Power Supply
194R-NJ100P3
100A
80HP
FUSE
50A
Fusible
Disconnect
3 Fuses
6 AWG
8 AWG
FUSE
35A
14 AWG
3 Fuses
3 Fuses
8 AWG
FUSE
25A
14 AWG
Commoning Links
140M-C2E
140M-C2E
-C10
-C10
100-C09
100-C09
14 AWG
7.6A
Fan #1
5 HP
14 AWG
7.6A
Fan #2
5 HP
140M-C2E
-C10
100-C16
14 AWG
7.5A
Heater #1
140M-C2E
-C10
100-C16
14 AWG
7.5A
Heater #2
140M-C2E
-C16
100-C16
Motor Protectors
Contactors
14 AWG
14.0A
Pump #1
10 HP
In this example, we have the same group of
5 motors, only now the pump motor is 10
HP rather than 5 HP. This Group Installation
no longer meets the NEC rules since the
wire feeding the group has increased from
#8 AWG to #6 AWG, and the ampacity of
the #14 AWG motor circuit conductors is
less than one third that of the #6 AWG
branch circuit conductors. This forces the
Group to be split, with 1 set of fuses
protecting the 4 small motors, and 1 set of
fuses protecting the 10 HP pump motor.
The third set of fuses just below the
disconnect is for protection of the #6 AWG
branch circuit conductors.
Motors
15
Bulletins 140M and 190S/190E
Motors Protectors/Compact Starters/Eco Starters
Product Overview
Self-Protected (Type E) Manual Combination Starter Applications – UL/CSA
The new 140M Motor Protectors, with improved current limiting and breaking capacity, are now UL/CSA listed as self-protected
(Type E) Manual Combination Starters. This new listing allows the 140M Motor Protectors to be used as short-circuit protection for
individual motors, in addition to overload protection. This eliminates the need for fuses or a circuit breaker to provide short-circuit
protection and also eliminates all of the NEC/CEC Group Motor rules for installations involving multi-motor panels.
The new Bulletin 140M Motor Protectors are standard components of the MCS Modular Control System. This provides for maximum
flexibility and minimum panel size without the restrictive and cumbersome rules involved with typical multi-motor (group) applications.
It should be noted that the 140M Motor Protectors, when used as self-protected (Type E) Manual Combination Starters, are rated
only for (Wye) power systems for voltages above 240V (i.e. 480Y/277V or 600Y/347V).
Self-Protected (Type E) Installations for Multi-Motor Panels
480V, 60 Hz, 3-Phase Power Supply
194R-NJ100P3
100A
80HP
FUSE
50A
Fusible
Disconnect
3 Fuses
6 AWG
480Y/277V, 60 Hz, 3-Phase Power Supply
8 AWG
194R-NN100P3
100A
80HP
FUSE
35A
Non-Fusible
Disconnect
Commoning Links
140M-C2E
140M-C2E
-C10
-C10
-C10
100-C09
100-C09
100-C16
7.6A
Fan #1
5 HP
3 Fuses
8 AWG
6 AWG
14 AWG
14 AWG
3 Fuses
14 AWG
7.6A
Fan #2
5 HP
140M-C2E
14 AWG
7.5A
Heater #1
140M-C2E
140M-C2E
-C10
-C16
100-C16
14 AWG
7.5A
Heater #2
Self-Protected (Type E) Installation
100-C16
Contactors
14.0A
Pump #1
10 HP
Motors
140M-C2E
-C10
-C10
100-C09
100-C09
14 AWG
14 AWG
14 AWG
Commoning Links
140M-C2E
Motor Protectors
FUSE
25A
7.6A
Fan #1
5 HP
14 AWG
7.6A
Fan #2
5 HP
140M-C2E
-C10
100-C16
14 AWG
7.5A
Heater #1
140M-C2E
-C10
100-C16
14 AWG
7.5A
Heater #2
140M-C2E
-C16
100-C16
Motor Protectors
Contactors
14 AWG
14.0A
Pump #1
10 HP
Motors
Group Motor Installation
The new listing of the 140M as a self-protected (Type E) combination starter greatly simplifies multi-motor panel design. As a selfprotected combination starter the 140M provides both overload and short-circuit protection for the motors and the NEC/CEC group
motor rules no longer apply.
In the diagrams above, the same 5 motors are shown in both a self-protected (Type E) installation as well as the previous example
of a Group Motor Installation. The rules in the NEC/CEC codes for the Group Motor Installation do not apply since each motor
already has short circuit protection provided by the 140M’s– i.e. the 5 motors are no longer “grouped” under a single short-circ uit
protective device (fuses or circuit-breaker). The 3 sets of fuses are no longer required and the 140M’s may simply be selected o
fr
each individual motor load according to the motor full-load current. A non-fusible disconnect switch for the main panel disconnecting
function completes the self-protected (Type E) Manual Combination Starter installation. Also, for remote operation a contactor may
be added to the installation Type 2 coordination may be achieved with the 100C in this case (see page 43).
16
Bulletins 140M and 190S/190E
Motors Protectors/Compact Starters/Eco Starters
Product Overview
Self-Protected (Type E) Installations for Single Motor Panels
480V, 60 Hz, 3-Phase Power Supply
194R-NJ100P3
100 A
80 HP
Fusible
Disconnect
FUSE
25 A
3 Fuses
480Y/277V, 60 Hz, 3-Phase Power Supply
140M-C2E
-C16
Motor Protector
100-C16
Contactor
Contactor
100-C16
193-E
14 AWG
14 AWG
14.0A
Pump #1
10 HP
Overload
Relay
Motor
14.0 A
Pump #1
10 HP
Motor
The new listing of the 140M as a self-protected combination starter provides for extremely cost-effective and compact single mot or
installations as well.
In the diagrams above, a panel consisting of a self-protected (Type E) Manual Combination Starter and a contactor is compared
with a traditional fusible combination starter panel. The Type E combination starter consists of a Bulletin 140M and a 100-C contactor.
The Bulletin 140M provides both the overload and short circuit protection as well as the disconnecting function for the motor while
the 100-C contactor allows for remote operation via push buttons. By contrast, the traditional fusible combination starter consists
of a 194R fusible disconnect switch for disconnecting function fuses for short-circuit protection, a 100-C contactor for remote operation
and a 193-E overload relay for overload protection.
17
Bulletin 140M
Motor Protectors
Product Selection
018
Motor Protectors For Use as Manual Starters and Motor Disconnects
Cat. No. 140M-F
Cat. No. 140M-D
Cat. No. 140M-C
Motor Protectors — For Use as Manual Starters
Current Adjustment Range
[A]
Typical
1-phase [HP] ➊
115V
Typical
3-phase [HP] ➊
230V
200V
230V
460V
575V
Cat. No. ➋
140M-C, High Break
0.10…0.16
—
—
—
—
—
—
140M-C2E-A16➌➍
0.16…0.25
—
—
—
—
—
—
140M-C2E-A25➌➍
0.25…0.40
—
—
—
—
—
0.40…0.63
—
—
—
—
—
0.63…1.0
—
—
—
—
1/2
3/4
140M-C2E-B10➌➍
1.0…1.6
—
1/10
—
—
3/4
1
140M-C2E-B16➌➍
1.6…2.5
1/10
1/6
1/2
1/2
1-1/2
2
140M-C2E-B25➌➍
2.5…4
1/8
1/3
1
1
3
3
140M-C2E-B40➌
4…6.3
1/4
3/4
1-1/2
2
3
5
140M-C2E-B63➌
6.3…10
1/2
1-1/2
3
3
7-1/2
10
140M-C2E-C10➌
10…16
1
3
3
5
10
10
140M-C2E-C16➌
14.5…20
1-1/2
3
5
7-1/2
15
20
140M-C2E-C20
18…25
2
3
7-1/2
10
20
25
140M-C2E-C25
140M-C2E-A40➌➍
140M-C2E-A63➌➍
140M-D, High Break PLUS
1.6…2.5
1/10
1/6
1/2
1/2
1-1/2
2
140M-D8E-B25➍
2.5…4
1/8
1/3
1
1
3
3
140M-D8E-B40➍
4…6.3
1/4
3/4
1-1/2
2
3
5
140M-D8E-B63➍
6.3…10
1/2
1-1/2
3
3
7-1/2
10
140M-D8E-C10➍
10…16
1
3
3
5
10
10
140M-D8E-C16➌➍
14.5…20
1-1/2
3
5
7-1/2
15
20
140M-D8E-C20➌➍
18…25
2
3
7-1/2
10
20
25
140M-D8E-C25➍
140M-F, High Break PLUS
6.3…10
1/2
1-1/2
3
3
7-1/2
10
140M-F8E-C10
10…16
1
3
3
5
10
10
140M-F8E-C16
14.5…20
1-1/2
3
5
7-1/2
15
20
140M-F8E-C20
18…25
2
3
5
10
20
25
140M-F8E-C25➌➍
23…32
3
5
10
10
25
30
140M-F8E-C32➌➍
32…45
3
7-1/2
15
15
30
40
140M-F8E-C45➍
140-CMN
16…25
2
5
7-1/2
10
20
25
140-CMN-2500
25…40
3
7-1/2
10
15
30
40
140-CMN-4000
40…63
5
10
20
20
50
60
140-CMN-6300
63…90
7-1/2
20
30
30
60
75
140-CMN-9000
➊ Horsepower ratings shown in the table above are for reference. The final selection of the manual starter depends on the actual motor full load
current and service factor.
• For motor with service factor less than 1.15. Use motor nameplate full load current times 0.9 and choose the motor starter with the appropriate current range.
Example: Motor F.L.C. = 4.2 A; S.F. = 1.0. (4.2 A x 0.9 = 3.78 A.) Select Cat. No. 140M-C2E-B40.
➋ Magnetic trip is fixed at 13x the maximum value of the current adjustment range.
➌ Devices with a fixed magnetic trip set at 16-20x the maximum value of the current adjustment range are available if nuisance tri pping occurs (as with some highefficiency motors). To order these products, change the “E” in the catalog number to a “T” (e.g., Cat. No. 140M-C2E-A16 changes to 140M-C2T-A16).
➍ Devices without a thermal trip (i.e., current adjustment range) are also available if separate motor overload protection is requ ired. To order these products, change
the “E” in the catalog number to an “N” (e.g., Cat. No. 140M-C2E-A16 changes to 140M-C2N-A16).
18
Bulletin 140M
Motor Protectors
Product Selection, Continued
Motor Protectors For Use as Manual Starters in Group Installations
Cat. No. 140M-C
Cat. No. 140M-D
Cat. No. 140M-F
Motor Protectors for Group Installation
For Use With
Cat. No. ➋
Max Fuse or
Circuit
Breaker
[A]
Cat. No. ➊
Max. Short-Circuit Current [kA]
Current Adjustment Range
[A]
480V
0.10…0.16
65
47
100-C09, 100-M05
400
140M-C2E-A16➌➍
0.16…0.25
65
47
100-C09, 100-M05
400
140M-C2E-A25➌➍
0.25…0.40
65
47
100-C09, 100-M05
400
140M-C2E-A40➌➍
0.40…0.63
65
47
100-C09, 100-M05
400
140M-C2E-A63➌➍
0.63…1.0
65
47
100-C09, 100-M05
400
140M-C2E-B10➌➍
1.0…1.6
65
47
100-C09, 100-M05
400
140M-C2E-B16➌➍
1.6…2.5
65
5
100-C09, 100-M05
400
140M-C2E-B25➌➍
2.5…4
65
5
100-C09, 100-M05
400
140M-C2E-B40➌
4…6.3
65
5
100-C09, 100-M05
400
140M-C2E-B63➌
6.3…10
65
5
100-C09, 100-M05
400
140M-C2E-C10➌
10…16
10
5
100-C12
400
140M-C2E-C16➌
14.5…20
10
5
100-C16
400
140M-C2E-C20
18…25
10
5
100-C23
400
140M-C2E-C25
600V
140M-C, High Break
140M-D, High Break PLUS
1.6…2.5
65
10
100-C09, 100-M05
400
140M-D8E-B25➍
2.5…4
65
10
100-C09, 100-M05
400
140M-D8E-B40➍
4…6.3
65
10
100-C09, 100-M05
400
140M-D8E-B63➍
6.3…10
65
10
100-C09, 100-M05
400
140M-D8E-C10➍
10…16
65
10
100-C12
400
140M-D8E-C16➌➍
14.5…20
65
5
100-C16
400
140M-D8E-C20➌➍
18…25
25
5
100-C23
400
140M-D8E-C25➍
140M-F, High Break PLUS
6.3…10
65
10
100-C09
500
140M-F8E-C10
10…16
65
10
100-C12
500
140M-F8E-C16
14.5…20
65
10
100-C16
500
140M-F8E-C20
18…25
65
10
100-C23
500
140M-F8E-C25➌➍
23…32
65
10
100-C30
500
140M-F8E-C32➌➍
32…45
50
10
100-C37
500
140M-F8E-C45➍
140-CMN
16…25
65
42
100-C16
1000
140-CMN-2500
25…40
65
42
100-C30
1000
140-CMN-4000
40…63
65
42
100-C43
1000
140-CMN-6300
63…90
65
30
100-C72
1000
140-CMN-9000
➊ Magnetic trip is fixed at 13x the maximum value of the current adjustment range.
➋ Ratings apply to specified or larger contactor.
➌ Devices with a fixed magnetic trip set at 16-20x the maximum value of the current adjustment range are available if nuisance tripping occurs (as with some highefficiency motors). To order these products, change the “E” in the catalog number to a “T” (e.g., Cat. No. 140M-C2E-A16 changes to 140M-C2T-A16).
➍ Devices without a thermal trip (i.e., current adjustment range) are also available if separate motor overload protection is required. To order these products, change
the “E” in the catalog number to an “N” (e.g., Cat. No. 140M-C2E-A16 changes to 140M-C2N-A16).
➎ For Type 2 coordination see pages 43 and 44.
19
Bulletin 140M
Motor Protectors
Product Selection, Continued
0
Motor Protectors For Use as Self-Protected (Type E) Manual Combination Motor Controllers
Cat. No. 140M-C
Cat. No. 140M-F
Motor Protectors For Use As Self-Protected (Type E) Manual Combination Motor Controller
Current Adjustment
Range [A]
Typical
3-phase [HP] ➊
Typical
1-phase [HP] ➊
115V
Max.
Short-Circuit
Current
[kA]
230V
200V
230V
460V
575V
480Y/277V
Cat. No. ➋
140M-C, High Break
0.10...0.16
—
—
—
—
—
—
65
140M-C2E-A16
0.16...0.25
—
—
—
—
—
—
65
140M-C2E-A25
0.25...0.40
0.40...0.63
—
—
—
—
—
—
—
—
—
—
65
65
140M-C2E-A40
140M-C2E-A63
0.63...1.0
1.0...1.6
—
—
—
—
1/2
3/4
—
1/10
—
—
3/4
1
65
65
140M-C2E-B10
140M-C2E-B16
1.6...2.5
2.5...4
1/10
1/6
1/2
1/2
1-1/2
2
1/8
1/3
1
1
3
3
65
65
140M-C2E-B25
140M-C2E-B40
4...6.3
6.3...10
1/4
3/4
1-1/2
2
3
5
1/2
1-1/2
3
3
7-1/2
10
65
65
140M-C2E-B63
140M-C2E-C10
10...16
14.5...20
1
3
3
5
10
10
1-1/2
3
5
7-1/2
15
20
10
10
140M-C2E-C16
140M-C2E-C20
18...25
2
3
7-1/2
10
20
25
10
140M-C2E-C25
140M-D, High Break PLUS
1.6...2.5
2.5...4
1/10
1/6
1/2
1/2
1-1/2
2
1/8
1/3
1
1
3
3
65
65
140M-D8E-B25
140M-D8E-B40
4...6.3
1/4
3/4
1-1/2
2
3
5
65
140M-D8E-B63
6.3...10
10...16
1/2
1-1/2
3
3
7-1/2
10
1
3
3
5
10
10
65
65
140M-D8E-C10
140M-D8E-C16
14.5...20
18...25
1-1/2
3
5
7-1/2
15
20
2
3
7-1/2
10
20
25
65
25
140M-D8E-C20
140M-D8E-C25
6.3...10
1/2
1-1/2
3
3
7-1/2
10
➌
140M-F8E-C10
10...16
14.5...20
1
3
3
5
10
10
1-1/2
3
5
7-1/2
15
20
➌
➌
140M-F8E-C16
140M-F8E-C20
18...25
23...32
2
3
5—
10
20
25
3
5
10
10
25
30
➌
➌
140M-F8E-C25
140M-F8E-C32
32...45
3
7-1/2
15
15
30
40
➌
140M-F8E-C45
140M-F, High Break PLUS
➊ Horsepower ratings shown in the table above are for reference. The final selection of the manual starter depends on the actual motor
full load current and service factor.
• For motor with service factor less than 1.15. Use motor nameplate full load current times 0.9 and choose the motor starter with the appropriate current range.
Example: Motor F.L.C. = 4.2 A; S.F. = 1.0. (4.2 A x 0.9 = 3.78 A.) Select Cat. No. 140M-C2E-B40.
➋ Magnetic trip is fixed at 13x the maximum value of the current adjustment range.
➌ UL Pending. Contact your local Allen-Bradley Sales Office.
20
Bulletin 140M
Motor Protectors
Accessories
Description
Operator Position ➊
OFF
ON
Tripped
Term.
Desc.
No.
Connection Diagram➋
For Use
With
Cat. No.
13
O
X
O
13-14
N.O. Aux
140M
140M-C-AFA10
140M
140M-C-AFA01
140M
140M-C-AFA11
140M
140M-C-AFA20
140M
140M-C-AFA02
140M
140M-C-ASA20
140M
140M-C-ASA02
140M
140M-C-ASA11
14
I >>
11
X
O
X
11-12
N.C. Aux
12
I >>
Front-Mounted
Auxiliary Contact
• 1-pole or 2-pole
•
•
No additional
space required
For use with
140M
O
X
O
13-14
13
21
14
22
13
23
14
24
N.O. Aux
I >>
X
O
X
21-22
N.C. Aux
O
X
O
13-14
N.O. Aux
I >>
O
X
O
23-24
N.O. Aux
X
O
X
11-12
N.C. Aux
11
21
12
22
I >>
Right Side -Mounted
Auxiliary Contact
• 2-pole
• Adds 9 mm to the
width of the device
• For use with 140M
X
O
X
21-22
N.C. Aux
O
X
O
33-34
N.O. Aux
O
X
O
43-44
N.O. Aux
X
O
X
31-32
N.C. Aux
X
O
X
41-42
N.C. Aux
O
X
O
33-34
N.O. Aux
X
O
X
41-42
N.C. Aux
33
43
34
44
31
41
32
42
I >>
I >>
33
41
34
42
I >>
➊ X = Contact Closed
O = Contact Open
➋
140 M Operator
Overload (thermal) Trip
I >> Short-Circuit (magnetic) Trip
21
Bulletin 140M
Motor Protectors
Accessories, Continued
Description
Operator Position ➊
OFF
ON
Tripped Term.
Desc.
No.
Connection Diagram➋
O
Front-Mounted
Trip Contact
• 2-pole
• Indicates tripping
of device
• No additional
space required
• For use with 140M
X
27-28
X
O
X
11-12
N.C. Aux
O
O
X
27-28
N.O. Trip
(Short-Circuit &
Overload)
O
O
X
57-58
N.O. Trip
(Short-Circuit &
Overload)
67-68
N.O. Trip
(Short-Circuit)
57-58
N.O. Trip
(Short-Circuit &
Overload)
X
X
O
X
O
X
Overload (thermal) Trip
I >> Short-Circuit (magnetic) Trip
22
N.O. Aux
O
X
140 M Operator
13-14
O
O
➊ X = Contact Closed
O = Contact Open
➋
O
N.O. Trip
(Short-Circuit &
Overload)
O
Right Side-Mounted
Trip Contact
• 2-pole
• Indicates tripping
of Motor Protector
• Adds 9 mm to the
width of the circuit
breaker
• For use with 140M
X
O
O
X
X
O
X
X
O
X
X
X
O
O
X
O
O
X
O
65-66
N.C. Trip
(Short-Circuit)
55-56
N.C. Trip
(Short-Circuit &
Overload)
67-68
N.O. Trip
(Short-Circuit)
55-56
N.C. Trip
(Short-Circuit &
Overload)
65-66
N.C. Trip
(Short-Circuit)
77-78
N.O. Trip
(Short-Circuit)
65-66
N.C. Trip
(Short-Circuit)
13
For Use
With
Cat. No.
140M
140M-C-AFAR10A10
140M
140M-C-AFAR10A01
140M
140M-C-ASAR10M10
140M
140M-C-ASAR10M01
140M
140M-C-ASAR01M10
140M
140M-C-ASAR01M01
140M
140M-C-ASAM11
27
I >>
14
28
11
27
12
28
I >>
57
67
58
68
I >>
57
65
58
66
I >>
55
67
56
68
55
65
56
66
I >>
I >>
77
65
78
66
I >>
Bulletin 140M
Motor Protectors
Accessories, Continued
Description
Operator Position ➊
OFF
ON
Tripped
Term.
Desc.
No.
Connection Diagram➋
O
X
O
13-14
N.O. Aux
For Use
With
Cat. No.
140-CMN
140-CA20
13
23
14
24
140-CA20
I >>
O
Front-Mounted
Auxiliary Contacts
• Internal
• 2-Pole
X
X
O
O
X
23-24
11-12
N.O. Aux
N.C. Aux
140-CMN
140-CMN
140-CA02
11
21
12
22
140-CA02
I >>
X
O
X
21-22
N.C. Aux
140-CMN
O
X
O
13-14
N.O. Aux
140-CA11
140-CA11
13
21
14
22
I >>
X
O
X
21-22
N.C. Aux
140-CMN
O
O
X
37-38
N.O. Trip
(Overload)
140-CT10-10
a
37
43
38
44
140-CT10-10
I >>
O
O
X
43-44
N.O. Trip
(Short-Circuit)
b
a) Overload Trip
b) Short-Circuit Trip
140-CMN
X
X
O
35-36
N.C. Trip
(Overload)
140-CT01-01
a
35
41
36
42
140-CT01-01
I >>
Front-Mounted
Trip Indicating
Auxiliary Contacts
• Internal
• 2-Pole
X
X
O
41-42
N.C. Trip
(Short-Circuit)
b
a) Overload Trip
b) Short-Circuit Trip
140-CMN
140-CMN
X
X
O
35-36
N.C. Trip
(Overload)
140-CT01-10
a
35
43
36
44
140-CT01-10
I >>
O
O
X
43-44
N.O. Trip
(Short-Circuit)
b
a) Overload Trip
b) Short-Circuit Trip
140-CMN
O
O
X
37-38
N.O. Trip
(Overload)
140-CT10-01
a
37
41
38
42
140-CT10-01
I >>
X
X
O
41-42
N.C. Trip
(Short-Circuit)
b
a) Overload Trip
b) Short-Circuit Trip
➊
➋
X = Contact Closed
O = Contact Open
140 M Operator
Overload (thermal) Trip
I >> Short-Circuit (magnetic) Trip
23
Bulletin 140M
Motor Protectors
0
Accessories, Continued
Description
Undervoltage Trip
• Left-side mounted
• Adds 18 mm to the width
of the circuit breaker
• Trips motor protector
when voltage is removed
D1
U<
D2
I >>
Shunt Trip
• Left-side mounted
• Adds 18 mm to the width
of the circuit breaker
• Trips motor protector
when voltage is applied
Undervoltage Trip Unit
• Internal, front mounted
• Integrated short-circuit
trip indication
• Trips motor protector
when voltage is removed
For Use
With
Connection Diagram➊
C1
C2
I >>
24V, 50 Hz/28V, 60 Hz
110V, 50 Hz/127V, 60 Hz
220...230V, 50 Hz
240...260V, 60 Hz
240V, 50 Hz/277V, 60 Hz
380...400V, 50 Hz/440...460V, 60 Hz
415V, 50 Hz/480V, 60 Hz
21V, 50 Hz/24V, 60 Hz
110V, 50Hz/27V, 60 Hz
24V, 50 Hz/28V,
110V, 50 Hz/127V,
220...230V,
240...260V,
240V, 50 Hz/277V,
380...400V, 50 Hz/440...460V,
415V, 50 Hz/480V,
21V, 50 Hz/24V,
110V, 50 Hz/127V,
60
60
50
60
60
60
60
60
60
Hz
Hz
Hz
Hz
Hz
Hz
Hz
Hz
Hz
Cat. No.
140M
140M-C-UXK
140M-C-UXD
140M-C-UXF
140M-C-UXA
140M-C-UXT
140M-C-UXN
140M-C-UXB
140M-C-UXJ
140M-C-UXC
140M
140M-C-SNK
140M-C-SND
140M-C-SNF
140M-C-SNA
140M-C-SNT
140M-C-SNN
140M-C-SNB
140M-C-SNJ
140M-C-SNC
140-CMN
140-CUV...
43
b
I >>
D1
U<
24V 50/60 Hz
110V 50 Hz/120V 60 Hz 140-CMN
220V 50 Hz/240V 60 Hz
140-CUV-KJ
140-CUV-D
140-CUV-A
24V 50/60 Hz
110V 50 Hz/120V 60 Hz 140-CMN
220V 50 Hz/240V 60 Hz
140-CRT-KJ
140-CRT-D
140-CRT-A
44
D2
b) Short-Circuit Trip
Shunt Trip Unit
• Internal, front mounted
• Integrated short-circuit
trip indication
• Trips motor protector
when voltage is applied
140-CMN
140-CRT...
43
b
I >>
C1
44
C2
b) Short-Circuit Trip
➊
140 M Operator
Overload (thermal) Trip
I >> Short-Circuit (magnetic) Trip
24
Bulletin 140M
Motor Protectors
Accessories, Continued
Description
For Use With
Cat. No.
140M
140M-C-CA
black
140M
140M-C-KN
red/yellow
140M
140M-C-KRY
Anti Tamper Shield
• Provides protection against inadvertent adjustment of the current setting
Lockable Twist Knob
• For 1 padlock 4...8 mm (5/16") dia. shackle
• Can be locked in OFF position
black
Padlockable Operating Knob
• Accepts 8mm (5/16") padlock — up to three
padlocks.
• Permits padlocking in the off position.
140-KN
140-CMN
red/yellow
140-KRY
140M
140M-C-DN66
140-CMN
140-CDN66
140M
140M-C-DRY66
140-CMN
140-CDRY66
140M-C-DN66
140M-C-DRY66
140M-C-DS
140M-C-DN66
140M-C-DFCN
140M-C-DRY66
140M-C-DFCRY
140M-C-KN
140M-C-KRY
140M-F-KRY
140M-C-M3
IP65 Non-Metallic Enclosure
• Knockouts for PG16 and PG21 fittings
• Suitable for flexible cable with internal ground wire or conduit black handle
when externally grounded around the outside of the
enclosure
140M-C
140M-D
198E-AYTJ2
IP65 Non-Metallic Enclosure
• Knockouts for PG16 and PG21 fittings
red/yellow
• Suitable for flexible cable with internal ground wire or conduit
handle
when externally grounded around the outside of the
enclosure
140M-C
140M-D
198E-AYTG2
Door Coupling Handle
black
• For 3 padlocks 4...8 mm (5/16") in diameter
• IP66 Protection/Type 1,3,3R,4,4x,13
• Interlock override capability
• Can be modified for locking in "ON" position
• Ships with coupling — order extension shaft and legend plate
separately
• Mounting depth (adapter-door):
140-C: 105.5 mm ± 5 mm (4.15" ± 3/16")
140-D: 114.5 mm ± 5 mm (4.5" ± 3/16")
red/yellow
140-F: 137.1 mm ± 5 mm (5.4" ± 3/16")
Extension Shaft
• Cut to required length for mounting depth (adapter-door)
140-C: 117...338 mm (4.6"…13.3")
140-D: 126...347 mm (5.0"…13.7")
140-F: 149...369 mm (5.4"…14.5")
Legend Plate
• Marking: "Haupschalter" and "Main Switch"
• Marking: "Not-Aus" and "Emergency Off"
Locking Tag
• Padlock attachment to the lockable handles
• Up to three padlocks 4...8 mm (5/16") shackle
25
Bulletin 140M
Motor Protectors
Accessories, Continued
Description
For Use With
140M-C
to
100-M
140M-C
to
Connecting Modules - 25 A
• The Eco-connecting modules provide electrical and mechanical interconnection of 100-C09...C23
140M and 100M (with AC or DC coils) or 100C (with AC coils) for use as
140M-D
combination starters
to
• Suitable for reversing and star/delta kits
• Eco-starters mount on single DIN Rail (140M on DIN Rail)
100-C09...C23
140M-F
to
Connecting Modules - 45 A
100-C30...C37
• Electrical interconnection between 140M-F motor protector and 100-C contactors
(with AC coils)
140M-F
• Contactor and motor protector must be mounted separately
to
100-C43
Commoning Link Feeder Terminal
• For supply of commoning links — 600V, 65 A max.
• Top feed — overlaps commoning link
Cat. No.
140M-C-PEM12
140M-C-PEC23
140M-D-PEC23
140M-F-PNC37
140M-F-PNC43
140M-C
140M-D
140M-C-WT
140M-F
140M-F-WT
Three-Phase Commoning Link for 25A Motor Protectors – 63A Max. Continuous Current
•
•
140M-D
140M-C
45 mm spacing
For use with front-mounted auxiliary contact
•
•
54 mm spacing
For use with side-mounted auxiliary contact
•
•
63 mm spacing
For use with side-mounted undervoltage trip and
shunt trip
2 x 3 connections
3 x 3 connections
4 x 3 connections
5 x 3 connections
2 x 3 connections
3 x 3 connections
4 x 3 connections
5 x 3 connections
2 x 3 connections
3 x 3 connections
4 x 3 connections
5 x 3 connections
Jumper for 140M-D to 140M-C
• Accommodates difference in depth from 140M-D
to 140M-C
2 x 3 connections
• Can be used with all other commoning links
• 54 mm spacing
Three-Phase Commoning Link for 45A Motor Protectors
•
•
54 mm spacing
For use with front-mounted auxiliary contact
•
•
63 mm spacing
For use with side-mounted auxiliary contact
2 x 3 connections
3 x 3 connections
3 x 3 connections
4 x 3 connections
Screw Adapter
• For screw arrangement of a motor protector
26
140M-C
140M-D
140M-C
140M-D
140M-D
to
140M-C
140M-F
10 pcs per Pkg
140M-C-W452
140M-C-W453
140M-C-W454
140M-C-W455
140M-C-W542
140M-C-W543
140M-C-W544
140M-C-W545
140M-C-W632
140M-C-W633
140M-C-W634
140M-C-W635
140M-C-WD542
140M-F-W542
140M-F-W543
140M-F-W544
140M-F-W632
4 x 3 connections
2 x 3 connections
Terminal Cover
• For covering of unused connection terminals
• IP2X finger protection
DIN (#3) Symmetrical Rail
• 35mm x 7.5mm x 1m long
• Zinc-plated, yellow chromated
• EN 50022
140M-C
140M-D
140M-F
140M-F-W633
140M-F-W634
140M-C
140M-D
140M-C-WS
140M-F
140M-F-WS
140M
140M-C-N45
199-DR1
Bulletin 140M
Motor Protectors
Specifications
UL / CSA Performance Data
Manual Motor Controller
(UL 508, CSA C22.2 No.14 for Group Installation, in Connection with a Short-Circuit Protection Device)
Cat. No. 140M-C2E-
Rated Operational Current, Ie [A]
Magnetic Release Current
[A]
Max. Short-Circuit Current
480V
[kA]
600V
[kA]
Motor Load, Single-Phase
115V
[HP]
230V
[HP]
Motor Load, Three-Phase
230V
[HP]
460V
[HP]
575V
[HP]
A16
A25
A40
A63
B10
B16
B25
B40
B63
C10
C16
C20
C25
0.16
2.1
0.25
3.3
0.4
5.2
0.63
8.2
1
13
1.6
21
2.5
33
4
52
6.3
82
10
130
16
208
20
260
25
325
65
47
65
47
65
47
65
47
65
47
65
47
65
5
65
5
65
5
65
5
10
5
10
5
10
5
—
—
—
—
—
—
—
—
—
—
—
1/10
1/10
1/6
1/8
2/3
1/4
3/4
1/2
1-1/2
1
3
1-1/2
3
2
3
—
—
—
—
—
—
1/2
1
2
3
5
7-1/2
10
—
—
—
—
—
—
—
—
1/2
3/4
3/4
1
1-1/2
2
3
3
3
5
7-1/2
10
10
10
15
20
20
25
Maximum Rated Current of
Protection Device
[A]
400
Self-Protected (Type E) Manual Combination Motor Controller
(UL 508)
Cat. No. 140M-C2E-
Rated Operational Current, Ie [A]
Magnetic Release Current
Max. Short-Circuit Current
480Y/277V
[kA]
600Y/347V
[kA]
Motor Load, Single-Phase
115V
[HP]
230V
[HP]
Motor Load, Three-Phase
230V
[HP]
460V
[HP]
575V
[HP]
[A]
A16
A25
A40
A63
B10
B16
B25
B40
B63
C10
C16
C20
C25
0.16
2.1
0.25
3.3
0.4
5.2
0.63
8.2
1
13
1.6
21
2.5
33
4
52
6.3
82
10
130
16
208
20
260
25
325
65
65
65
65
65
65
65
65
65
65
10
10
10
➊
➊
➊
➊
➊
➊
➊
➊
➊
➊
➊
➊
➊
—
—
—
—
—
—
—
—
—
—
—
1/10
1/10
1/6
1/8
2/3
1/4
3/4
1/2
1-1/2
1
3
1-1/2
3
2
3
—
—
—
—
—
—
1/2
1
2
3
5
7-1/2
10
—
—
—
—
—
—
—
—
1/2
3/4
3/4
1
1-1/2
2
3
3
3
5
7-1/2
10
10
10
15
20
20
25
➊ Contact your local Allen-Bradley Sales Office.
27
Bulletin 140M
Motor Protectors
Specifications, Continued
UL / CSA Performance Data
Manual Motor Controller
(UL 508, CSA C22.2 No.14 for Group Installation, in Connection with a Short-Circuit Protection Device)
Cat. No. 140M-D8E-
Rated Operational Current, Ie [A]
Magnetic Release Current
[A]
Max. Short-Circuit Current
480V
[kA]
600V
[kA]
Motor Load, Single-Phase
115V
[HP]
230V
[HP]
Motor Load, Three-Phase
230V
[HP]
460V
[HP]
575V
[HP]
Cat. No. 140M-F8E-
B25
B40
B63
C10
C16
C20
C25
C10
C16
C20
C25
C32
C45
2.5
33
4.0
52
6.3
82
10
130
16
208
20
260
25
325
10
130
16
208
20
260
25
325
32
416
45
585
65
10
65
10
65
10
65
10
65
10
65
5
25
5
65
10
65
10
65
10
65
10
65
10
50
10
1/10
1/6
1/8
1/3
1/4
3/4
1/2
1-1/2
1
3
1-1/2
3
2
3
1/2
1-1/2
1
3
1-1/2
3
2
3
3
5
3
7-1/2
1/2
1
2
3
5
7-1/2
10
3
5
7-1/2
10
10
15
1-1/2
2
3
3
3
5
7-1/2
10
10
10
15
20
20
25
7-1/2
10
10
10
15
20
20
25
25
30
30
40
Maximum Rated Current
of Protection Device
[A]
400
500
Cat. No. 140M-D8E-
Cat. No. 140M-F8E-
Type E Combination Motor Controller
(UL 508)
Rated Operational Current, Ie [A]
Magnetic Release Current
Max. Short-Circuit Current
480Y/277V
[kA]
500Y/347V
[kA]
Motor Load, Single-Phase
115V
[HP]
230V
[HP]
Motor Load, Three-Phase
230V
[HP]
460V
[HP]
575V
[HP]
[A]
B25
B40
B63
C10
C16
C20
C25
C10
C16
C20
C25
C32
C45
2.5
33
4.0
52
6.3
82
10
130
16
208
20
260
25
325
10
130
16
208
20
260
25
325
32
416
45
585
65
➊
65
➊
65
➊
65
➊
65
➊
65
➊
25
➊
➊
➊
➊
➊
➊
➊
➊
➊
➊
➊
➊
➊
1/10
1/6
1/8
1/3
1/4
3/4
1/2
1-1/2
1
3
1-1/2
3
2
3
1/2
1-1/2
1
3
1-1/2
3
2
3
3
5
3
7-1/2
1/2
1
2
3
5
7-1/2
10
3
5
7-1/2
10
10
15
1-1/2
2
3
3
3
5
7-1/2
10
10
10
15
20
20
25
7-1/2
10
10
10
15
20
20
25
25
30
30
40
➊ Contact your local Allen-Bradley Sales Office.
28
Bulletin 140M
Motor Protectors
Specifications, Continued
UL / CSA Performance Data
Manual Motor Controller
(UL 508, CSA C22.2 No.14 for Group Installation, in Connection with a Short-Circuit Protection Device)
Cat. No. 140M-C2NRated Operational Current, Ie [A]
Magnetic Release Current
[A]
A16
A25
A40
A63
B10
B16
B25
0.16
2.1
0.25
3.3
0.40
5.2
0.63
8.2
1.0
13
1.6
20
2.5
32
65
47
65
47
65
47
65
47
65
47
65
47
65
5
—
—
—
—
—
—
—
—
—
—
—
1/10
1/10
1/6
—
—
—
—
—
—
—
—
—
—
—
—
—
1/2
3/4
—
3/4
1
1/2
1-1/2
2
Max. Short-Circuit Current
480V
[kA]
600V
[kA]
Motor Load, Single-Phase
115V
[HP]
230V
[HP]
Motor Load, Three-Phase
230V
[HP]
460V
[HP]
575V
[HP]
Maximum Rated Current
[A]
of Protection Device
400
Cat. No. 140M-D8NRated Operational Current, Ie [A]
[A]
Magnetic Release Current
Cat. No. 140M-F8N-
B25
B40
B63
C10
C16
C25
C25
C32
C45
2.5
32
4.0
52
6.3
82
10
130
16
208
25
325
25
325
32
416
45
585
65
10
65
10
65
10
65
10
65
10
25
5
65
10
65
10
50
10
1/10
1/6
1/8
1/3
1/4
3/4
1/2
1-1/2
1
3
2
3
2
3
3
5
3
25
1/2
1
2
3
5
10
10
10
15
1-1/2
2
3
3
3
5
7-1/2
10
10
10
20
25
20
25
25
30
30
40
Max. Short-Circuit Current
480V
[kA]
600V
[kA]
Motor Load, Single-Phase
115V
[HP]
230V
[HP]
Motor Load, Three-Phase
230V
[HP]
460V
[HP]
575V
[HP]
Maximum Rated Current
of Protection Device
[A]
400
500
29
Bulletin 140M
Motor Protectors
Specifications, Continued
UL / CSA Performance Data
Manual Motor Controller
(UL 508, CSA C22.2 No.14 for Group Installation, in Connection with a Short-Circuit Protection Device)
Cat. No. 140M-C2TRated Operational Current, Ie [A]
Magnetic Release Current
[A]
A16
A25
A40
A63
B10
B16
B25
B40
B63
C10
C16
0.16
3.2
0.25
5.2
0.40
8.2
0.63
13
1.0
21
1.6
32
2.5
52
4.0
82
6.3
130
10
208
16
260
65
47
65
47
65
47
65
47
65
47
65
47
65
5
65
5
65
5
65
5
10
5
—
—
—
—
—
—
—
—
—
—
—
1/10
1/10
1/6
1/8
2/3
1/4
3/4
1/2
1-1/2
1
3
—
—
—
—
—
—
—
—
—
—
—
—
—
1/2
3/4
—
3/4
1
1/2
1-1/2
2
1
3
3
2
3
5
3
7-1/2
10
5
10
10
Max. Short-Circuit Current
480V
[kA]
600V
[kA]
Motor Load, Single-Phase
115V
[HP]
230V
[HP]
Motor Load, Three-Phase
230V
[HP]
460V
[HP]
575V
[HP]
Maximum Rated Current
[A]
of Protection Device
400
Cat. No. 140M-D8TRated Operational Current, Ie [A]
Magnetic Release Current
[A]
Cat. No. 140M-F8T-
C16
C20
C25
C32
16
260
20
325
25
416
32
585
65
10
65
10
65
10
65
10
1
3
1-1/2
3
2
3
3
5
5
10
10
7-1/2
15
20
10
20
25
10
25
30
Max. Short-Circuit Current
480V
[kA]
600V
[kA]
Motor Load, Single-Phase
115V
[HP]
230V
[HP]
Motor Load, Three-Phase
230V
[HP]
460V
[HP]
575V
[HP]
Maximum Rated Current
[A]
of Protection Device
30
400
500
Bulletin 140M
Motor Protectors
Specifications, Continued
0
0
0
IEC Performance Data
Cat. No. 140M-C2E-
Rated Operational Current, Ie [A]
Magnetic Release Current [A]
A16
A25
A40
A63
B10
B16
B25
B40
B63
C10
C16
C20
C25
0.16
2.1
0.25
3.3
0.4
5.2
0.63
8.2
1
13
1.6
21
2.5
33
4
52
6.3
82
10
130
16
208
20
260
25
325
0.37
0.55/
0.75
1.1/
1.5
2.2
4.0/
5.5
—
0.75
1.1/1.5
2.2
3.0/
4.0
5.5/
7.5
7.5/10
11
1.1
1.5/2.2
2.5/
3.0
1.8
2.2/3.0
4.0
Switching of Standard
Three-Phase Motors
AC-2, AC-3
0.25/
0.37
0.37/
0.55
0.18/
0.25
0.37/
0.55
0.55/
0.75
0.75/
1.1
➊
➊
➊
➊
➊
➊
➊
➊
➊
➊
➊
➊
➊
➊
16
➊
➊
➊
➊
20
➊
➊
➊
➊
35
➊
➊
➊
➊
50
➊
➊
63
80
50
➊
80
63
80
63
100
100
80
80
63
100
100
80
80
63
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
8
100
100
100
100
8
100
100
100
100
8
100
100
100
100
4
100
100
50
50
4
100
50
10
10
3
50
15
10
6
3
50
15
10
6
3
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
8
100
100
100
100
8
100
100
100
100
8
100
100
100
100
4
100
100
50
50
4
100
50
6
6
3
50
15
6
6
3
50
15
6
6
3
0.06/
0.09
0.12/
0.18
230/240V
[kW]
—
—
—
400/415V
[kW]
0.02
0.06
0.09
500V
[kW]
—
—
—
0.18
690V
[kW]
—
—
—
0.25
➊
➊
➊
➊
➊
➊
➊
➊
➊
➊
➊
➊
➊
➊
➊
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
0.12
0.25
3.0/
4.0
4.0/
6.3
5.5/
7.5
7.5/10
11
15
11/13
15/17
18.5/
22
Back-Up Fuses
gG, gL, only if Icc > Icu
230/240V
[A]
400/415V
[A]
440/460V
[A]
500V
[A]
690V
[A]
Ultimate Short-Circuit
Breaking Capacity
Icu
230/240V
[kA]
400/415V
[kA]
440/460V
[kA]
500V
[kA]
690V
[kA]
Rated Service Short-Circuit
Breaking Capacity
Ics
230/240V
[kA]
400/415V
[kA]
440/460V
[kA]
500V
[kA]
690V
[kA]
➊ No back-up fuse required.
31
Bulletin 140M
Motor Protectors
Specifications, Continued
IEC Performance Data
Cat. No. 140M-D8E-
Rated Operational Current, Ie [A]
Magnetic Release Current [A]
Cat. No. 140M-F8E-
B25
B40
B63
C10
C16
C20
C25
C10
C16
C20
C25
C32
C45
2.5
33
4.0
52
6.3
82
10
130
16
208
20
260
25
325
10
130
16
208
20
260
25
325
32
416
45
585
2.2
3.0/4.0 4.0/5.5
—
2.2
7.5
11/13
3.0/4.0 5.5/7.5 7.5/10
11
Switching of Standard
Three-Phase Motors
AC-2, AC-3
230/240V
[kW]
0.37
0.55/
0.75
1.1/1.5
400/415V
[kW]
0.75
1.1/1.5
2.2
500V
[kW]
1.1
1.5/2.2
690V
[kW]
1.8
2.2/3.0
4.0
➊
➊
➊
➊
20
➊
➊
➊
➊
35
➊
➊
➊
➊
50
➊
➊
➊
➊
50
➊
➊
80
80
63
➊
100
100
80
63
➊
100
100
80
63
➊
80
➋
80
50
➊
100
➋
80
63
➊
100
➋
80
63
➊
100
➋
80
63
➊
125
➋
100
80
➊
125
➋
100
80
100
100
100
100
10
100
100
100
100
10
100
100
100
100
10
100
100
100
40
10
100
100
50
25
6
100
50
50
25
6
100
50
50
25
6
100
50
100
50
100
50
100
50
100
50
100
50
➋
10
6
➋
10
6
➋
10
6
➋
10
6
➋
10
6
➋
10
6
100
100
100
100
10
100
100
100
100
10
100
100
100
100
10
100
100
100
100
6
100
50
50
50
4
100
25
25
25
4
100
25
25
25
4
100
50
➋
10
6
100
50
➋
10
6
100
25
➋
10
6
100
25
➋
10
6
100
25
➋
10
6
100
25
➋
10
4
2.5/3.0 4.0/6.3 7.5/10
5.5/7.5 11/13
11
15/17
15
18.5/
22
3.0/4.0 4.0/5.5 5.5/6.3
3.0/4.0 5.5/7.5 7.5/10
11
15
4.0/6.3 7.5/10
11
15
15/20
18.5/
22
22/30
5.5/7.5 11/13
15/17
18.5/22 22/25
30/40
Back-Up Fuses
gG, gL, only if Icc > Icu
230/240V
[A]
400/415V
[A]
440/460V
[A]
500V
[A]
690V
[A]
Ultimate Short-Circuit
Breaking Capacity
Icu
230/240V
[kA]
400/415V
[kA]
440/460V
[kA]
500V
[kA]
690V
[kA]
Rated Service Short-Circuit
Breaking Capacity
Ics
230/240V
[kA]
400/415V
[kA]
440/460V
[kA]
500V
[kA]
690V
[kA]
➊ No back-up fuse required.
➋ Contact your local Allen-Bradley Sales Office.
32
Bulletin 140M
Motor Protectors
Specifications, Continued
0
0
0
IEC Performance Data
Cat. No. 140M-C2N-
Rated Operational Current, Ie [A]
Magnetic Release Current [A]
A16
A25
A40
A63
B10
B16
B25
0.16
2.1
0.25
3.3
0.4
5.2
0.63
8.2
1
13
1.6
21
2.5
32
—
0.02
—
—
—
0.06
—
—
—
0.09
—
—
➊
➊
➊
➊
➊
➊
➊
➊
➊
➊
➊
➊
➊
➊
➊
➊
➊
➊
➊
➊
➊
➊
➊
➊
➊
➊
➊
➊
➊
16
➊
➊
➊
➊
20
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
8
100
100
100
100
8
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
8
100
100
100
100
8
Switching of Standard
Three-Phase Motors
AC-2, AC-3
230/240V
[kW]
400/415V
[kW]
500V
[kW]
690V
[kW]
0.06/0.09
0.12
0.18/0.25
0.12/0.18
0.25
0.37/0.55
0.18
0.25/0.37 0.55/0.75
0.25
0.37/0.55 0.75/1.1
0.37
0.75
1.1
1.8
Back-Up Fuses
gG, gL, only if Icc > Icu þ
230/240V
[A]
400/415V
[A]
440/460V
[A]
500V
[A]
690V
[A]
Ultimate Short-Circuit
Breaking Capacity
Icu
230/240V
[kA]
400/415V
[kA]
440/460V
[kA]
500V
[kA]
690V
[kA]
Rated Service Short-Circuit
Breaking Capacity
Ics
230/240V
[kA]
400/415V
[kA]
440/460V
[kA]
500V
[kA]
690V
[kA]
➊ No back-up fuse required.
33
Bulletin 140M
Motor Protectors
Specifications, Continued
IEC Performance Data
Cat. No. 140M-D8N-
Rated Operational Current, Ie [A]
Magnetic Release Current [A]
Cat. No. 140M-F8N-
B25
B40
B63
C10
C16
C25
C25
C32
C45
2.5
32
4.0
52
6.3
82
10
130
16
208
25
325
25
325
32
416
45
585
2.2
3.0/4.0
4.0/6.3
5.5/7.5
3.0/4.0
5.5/7.5
7.5/10
11/13
—
11
15
18.5/22
5.5/6.3
11
15
18.5/22
7.5
15
15/20
22/25
11/13
18.5/22
22/30
30/40
Switching of Standard
Three-Phase Motors
AC-2, AC-3
230/240V
[kW]
400/415V
[kW]
500V
[kW]
690V
[kW]
0.37
0.75
1.1
1.8
0.55/0.75 1.1/1.5
1.1/1.5
2.2
1.5/2.2
2.5/3.0
2.2/3.0
4.0
Back-Up Fuses
gG, gL, only if Icc > Icu
230/240V
[A]
400/415V
[A]
440/460V
[A]
500V
[A]
690V
[A]
➊
➊
➊
➊
20
➊
➊
➊
➊
35
➊
➊
➊
➊
50
➊
➊
➊
➊
50
➊
➊
80
80
63
➊
100
100
80
63
➊
100
➋
80
63
➊
125
➋
100
80
➊
125
➋
100
80
100
100
100
100
10
100
100
100
100
10
100
100
100
100
10
100
100
100
10
6
100
100
50
50
6
100
50
50
25
6
100
50
100
50
100
50
➋
10
6
➋
10
6
➋
10
6
100
100
100
100
10
100
100
100
100
10
100
100
100
100
10
100
100
100
100
6
100
100
50
50
4
100
25
25
25
4
100
25
➋
10
6
100
25
➋
10
6
100
25
➋
10
4
Ultimate Short-Circuit
Breaking Capacity
I cu
230/240V
[kA]
400/415V
[kA]
440/460V
[kA]
500V
[kA]
690V
[kA]
Rated Service Short-Circuit
Breaking Capacity
Ics
230/240V
[kA]
400/415V
[kA]
440/460V
[kA]
500V
[kA]
690V
[kA]
➊ No back-up fuse required.
➋ Contact your local Allen-Bradley Sales Office.
34
Bulletin 140M
Motor Protectors
Specifications, Continued
IEC Performance Data
Cat. No. 140M-C2T-
Rated Operational Current, I e [A]
Magnetic Release Current [A]
A16
A25
A40
A63
B10
B16
B25
B40
B63
C10
C16
0.16
3.2
0.25
5.2
0.40
8.2
0.63
13
1.0
21
1.6
32
2.5
52
4.0
82
6.3
130
10
208
16
260
0.37
0.55/
0.75
1.1/1.5
2.2
3.0/4.0
0.75
1.1/1.5
2.2
3.0/4.0
5.5/7.5
1.1
1.5/2.2
2.5/3.0
4.0/6.3
7.5/10
1.8
2.2/3.0
4.0
5.5/7.5
11/13
Switching of Standard
Three-Phase Motors
AC-2, AC-3
0.25/
0.37
0.37/
0.55
0.18/
0.25
0.37/
0.55
0.55/
0.75
0.75/
1.1
➊
➊
➊
➊
➊
➊
➊
➊
➊
➊
➊
➊
➊
➊
16
➊
➊
➊
➊
20
➊
➊
➊
➊
35
➊
➊
➊
➊
50
➊
➊
63
80
50
➊
80
63
80
63
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
8
100
100
100
100
8
100
100
100
100
8
100
100
100
100
4
100
100
50
50
4
100
15
10
6
3
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
8
100
100
100
100
8
100
100
100
100
8
100
100
100
100
4
100
100
50
50
4
100
15
6
6
3
0.06/
0.09
0.12/
0.18
230/240V
[kW]
—
—
—
400/415V
[kW]
0.02
0.06
0.09
500V
[kW]
—
—
—
0.18
690V
[kW]
—
—
—
0.25
➊
➊
➊
➊
➊
➊
➊
➊
➊
➊
➊
➊
➊
➊
➊
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
100
0.12
0.25
Back-Up Fuses
gG, gL, only if Icc > Icu
230/240V
[A]
400/415V
[A]
440/460V
[A]
500V
[A]
690V
[A]
Ultimate Short-Circuit
Breaking Capacity
Icu
230/240V
[kA]
400/415V
[kA]
440/460V
[kA]
500V
[kA]
690V
[kA]
Rated Service Short-Circuit
Breaking Capacity
Ics
230/240V
[kA]
400/415V
[kA]
440/460V
[kA]
500V
[kA]
690V
[kA]
➊ No back-up fuse required.
35
Bulletin 140M
Motor Protectors
Specifications, Continued
IEC Performance Data
Cat. No. 140M-D8T-
Rated Operational Current, Ie [A]
Magnetic Release Current [A]
Cat. No. 140M-F8T-
C16
C20
C25
C32
16
260
20
325
25
416
32
585
3.0/4.0
5.5/7.5
7.5/10
11/13
4.0/5.5
7.5/10
11
15/17
5.5/6.3
11
15
18.5/22
7.5
15
15/20
22/25
➊
80
80
80
63
➊
100
100
80
63
➊
100
➋
80
63
➊
125
➋
100
80
100
50
50
25
6
100
50
50
25
6
100
50
➋
10
6
100
50
➋
10
6
100
25
25
25
4
100
25
25
25
4
100
25
➋
10
6
100
25
➋
10
6
Switching of Standard
Three-Phase Motors
AC-2, AC-3
230/240V
[kW]
400/415V
[kW]
500V
[kW]
690V
[kW]
Back-Up Fuses
gG, gL, only if Icc > Icu
230/240V
[A]
400/415V
[A]
440/460V
[A]
500V
[A]
690V
[A]
Ultimate Short-Circuit
Breaking Capacity
Icu
230/240V
[kA]
400/415V
[kA]
440/460V
[kA]
500V
[kA]
690V
[kA]
Rated Service Short-Circuit
Breaking Capacity
I cs
230/240V
[kA]
400/415V
[kA]
440/460V
[kA]
500V
[kA]
690V
[kA]
➊ No back-up fuse required.
➋ Contact your local Allen-Bradley Sales Office.
36
Bulletin 140M
Motor Protectors
Specifications, Continued
General Data
Cat. No.
140M-C...
140M-D...
140M-F...
Rated Insulation Voltage
690 V
600 V
IEC, SEV, VDE 0660
UL, CSA
Rated Impulse Withstand Voltage
Uimp/pollution degree
6 kV / 3
50/60 Hz
Rated Frequency
Utilization Category:
- IEC 947-2 (Motor Protector)
- IEC 947-4-1 (Motor Starter)
Life Span
A
AC-3
Mechanical
Electrical (Ie max.)
[operations]
[operations]
Switching Frequency
[operations]
100,000
100,000
max. 25 / h. (motor starts)
30,000
30,000
Ambient Temperature
- 40 °C ... + 80 °C
- 25 °C ... + 60 °C
IEC 68-2
to 2,000 m N.N.
IP20 all round, when wired
30 G, 11 ms
IEC 68-2
Storage
Operation
Resistance to Climatic Change
Site Altitude
Protection Class
Resistance to Shock
Resistance to Vibration
Rated Thermal Current Ith
IEC, SEV, VDE 0660
Up to 60 °C ambient temperature
[A]
0.1 ... 25
1.6 ... 25
6.3 ... 45
Overload Protection
Characteristics
Ambient temperature compensation
Phase-failure protection
IEC 947-4-1 Motor protection (except 140M-C2N, 140M-D8N, 140M-F8N)
- 20°C...+ 60°C
yes differential release
Magnetic Release
Response current
fixed setting
13 x Iemax. (for 140M-C2E, 140M-D8E, 140M-F8E, 140M-C2N, 140M-D8N, 140M-F8N)
16…20 x Iemax. (for 140M-C2T, 140M-D8T, 140M-F8T)
Iemax. = maximum values of setting ranges
Total Power Loss Pv
Motor protector at rated load operating
temperature
[W]
6…8
6…8
9…16
37
Bulletin 140M
Motor Protectors
Specifications, Continued
General Data
Cat. No.
140M-C...
140M-D...
140M-F...
IEC 947;
EN 60947;
UL 508; CSA 22.2
CE, UL, CSA
Conformity to Standards
Approvals
Terminal Parts
Type of terminals
Screwdriver
1.conductor
2.conductor
[mm2] / [AWG]
[mm2] / [AWG]
1.conductor
2.conductor
[mm2] / [AWG]
[mm2] / [AWG]
1.conductor
2.conductor
Tightening torque
[mm2] / [AWG]
[mm2] / [AWG]
[Nm] / [lb-in]
Pozidriv No. 2 / Blade No. 3
Pozidriv No. 2 / Blade No. 3
1...4 / No. 16...12
1...4 / No. 16...12
1...6 / No. 16...8
1...6 / No. 16...8
1.5...6 / No. 16...8
1.5...6 / No. 16...8
1…2.5 / 8.9…22
2.5...16 / No.14...6
2.5...10 / No. 14...8
2.5...25 / No. 14...4
2.5...16 / No. 14...6
2.5...25 / No. 14...4
2.5...16 / No. 14...6
1.5...3.5 / 13…31
Accessories for Bulletin 140M Motor Protectors
Rated Thermal Current Ith
at 40°C ambient temperature
at 60°C ambient temperature
Contact Class Coordination
According to NEMA
(UL/CSA-Standards)
Auxiliary Contact Blocks for
Front Mounting
Cat. No. 140M-C-AFA..,
140M-C-AFAR...
Auxiliary Contact Blocks for Right-Side Mounting
Cat. No. 140M-C-ASA.., 140M-C-ASAR...
[A]
[A]
5
4
10
6
AC
DC
B 300
Q 300
10
120
3
120
0.5
B 600
Q 600
10
240
3
240
0.25
Back-Up Fuses gG, gL
[A]
Rated Supply Current
AC-15:
[V]
[A]
DC-13:
[V]
[A]
24
4
24
2
240
1.5
240
0.25
24
6
24
2
120
5
120
0.5
Terminal Parts
Type of terminals
Screwdriver
Pozidriv No. 2 / Blade No. 3
1. conductor
2. conductor
[mm 2] / [AWG]
[mm 2] / [AWG]
1. conductor
2. conductor
[mm 2] / [AWG]
[mm 2] / [AWG]
1. conductor
2. conductor
[mm 2] / [AWG]
[mm 2] / [AWG]
Tightening torque
38
[Nm] / [lb-in]
0.5…2.5 / No. 18…14
0.5…2.5 / No. 18…14
0.75…2.5 / No. 18…14
0.75…2.5 / No. 18…14
0.75…2.5 / No. 18…14
0.75…2.5 / No. 18…14
1.5 / 13.3
415
2
415
0.15
690
0.7
Bulletin 140M
Motor Protectors
Specifications, Continued
Accessories for Bulletin 140M Motor Protectors
Actuating Voltage
Pull-in
Drop-out
Rated Control Voltage
Undervoltage Trip
for Left-Side Mounting
Cat. No. 140M-C-UX...
Undervoltage Trip with 2 Auxiliary
Contacts
for Left-Side Mounting
Cat. No. 140M-C-UC...
0.85...1.1 x Us
0.7...0.35 x Us
0.85...1.1 x Us
0.7...0.35 x Us
0.7...1.1 x Us
min.:
max.:
21V 50 Hz, 24V 60 Hz
600V 50 Hz
21V 50 Hz, 24V 60 Hz
600V 50 Hz
21V 50 Hz, 24V 60 Hz
600V 50 Hz
100%
100%
100%
Pull-in
Hold
8.5 VA, 6 W
3 VA, 1.2 W
8.5 VA, 6 W
3 VA, 1.2 W
8.5 VA, 6 W
3 VA, 1.2 W
On-Time
Coil Rating
Shunt Trip for Left-Side Mounting
Cat. No. 140M-C-SN...
Terminal Parts
Type of terminals
Pozidriv No. 2 / Blade No. 3
Screw Driver
1.conductor [mm2] / [AWG]
2.conductor [mm2] / [AWG]
0.5...2.5 / No. 18...14
0.5...2.5 / No. 18...14
1.conductor [mm2] / [AWG]
2.conductor [mm2] / [AWG]
0.75...2.5 / No. 18...14
0.75...2.5 / No. 18...14
1.conductor [mm2] / [AWG]
2.conductor [mm2] / [AWG]
0.75...2.5 / No. 18...14
0.75...2.5 / No. 18...14
Tightening torque
[Nm] / [lb-in]
1.5 / 13.3
Commoning Link Feeder Terminal
140M-C-WT
Commoning Link
140M-C-W
63
63
1.conductor [mm2] / [AWG]
2.conductor [mm2] / [AWG]
4…16
4…10
—
1.conductor [mm2] / [AWG]
2.conductor [mm2] / [AWG]
6…25 / No. 14…4
6…16 / No. 14…6
—
1.conductor [mm2] / [AWG]
2.conductor [mm2] / [AWG]
6…25 / No. 14…4
6…16 / No. 14…6
—
3 / 27
—
Rated Thermal Current Ith
at 60×C ambient temperature
Tightening torque
[A]
[Nm] / [lb-in]
Weights
Description
Motor Protectors
Auxiliary Contacts
Undervoltage Trip
Anti-tamper Cover
Cat. No.
140M-C2E-...
140M-D8E-...
140M-F8E-...
140M-C2N-...
140M-D8N-...
140M-F8N-...
140M-C2T-...
140M-D8T-...
140M-F8T-...
140M-C-AFA10
140M-C-AFA01
140M-C-AFA11
140M-C-AFA20
140M-C-ASA...
140M-C-AFAR10A...
140M-C-ASAR...M...
140M-C-ASAM11
140M-C-UX...
140M-C-SN...
140M-C-UC...
140M-C-CA
Weight
317 g
373 g
782 g
315 g
365 g
782 g
315 g
365 g
782 g
Description
Lockable Twist Knob
Locking Tag
Door Coupling Handle
Extension Shaft
Legend Plate
Feeder Terminal
10 g
15 g
108 g
110 g
116 g
2g
Commoning Links
Cat. No.
140M-C-KN
140M-C-KRY
140M-C-M3
140M-C-DN66
140M-C-NRY66
140M-C-DS
140M-C-DFC...
140M-C-WT
140M-F-WT
140M-C-W452
140M-C-W453
140M-C-W454
140M-C-W455
140M-C-W542
140M-C-W543
140M-C-W544
140M-C-W545
140M-C-W632
140M-C-W633
140M-C-W634
140M-C-W635
Weight
5g
30 g
123 g
46 g
4g
172 g
47 g
80 g
104 g
132 g
52 g
86 g
118 g
154 g
56 g
92 g
134 g
170 g
39
Bulletin 140M
Motor Protectors
Specifications, Continued
Time-Current Characteristic
140M Motor Protector
1) Thermal Release Trip Current:
The adjustable current-dependent delayed bimetal release
protects motors against overload. The curve shows the mean
operating current at an ambient temperature of 20°C starting
from the cold state. Careful testing and setting ensures
effective motor protection even in the case of single-phasing.
The overload characteristic is also valid for transformer
protection.
10 000
1h
1 000
100
1
2) Magnetic Release Trip Current:
The instantaneous magnetic trip has a fixed operating current
setting. This corresponds to 13 times the maximum value of
setting range. (Transformer protection up to 20 x Ie max.) At
a lower setting it is correspondingly higher.
10
1
2
Tripping time [s]
0.1
0.01
0.001
0.8 1
2
4
6
10
Multiple of set current IeF
40
Current Setting IeF:
20
40 60
100
The overload trip corresponds to a thermal overload relay in
a motor starter conforming to IEC 947-4-1. If a different value
is prescribed (e.g. reduced Ie for cooling medium having a
temperature higher than 40°C or a place of installation higher
than 2000 m above sea level), the setting current is equal to
the reduced rated current Ie of the motor.
Bulletin 140M
Motor Protectors
Approximate Dimensions
Dimensions are shown in millimeters (inches). Dimensions are not intended to be used for manufacturing purposes.
➋
24.8 (31/32)
18
(23/32)
9
(23/64)
45
(1-25/32)
4.5
(3/16)
62 (2-7/16)
4.5
(3/16)
29.4 (1-5/32)
➋
9
(23/64)
➍
54 (2-1/8)
72 (2-53/64)
7.5
(19/64)
140M-D...
45 (1-25/32)
➊
55 (2-11/64)
110 (4-21/64)
55 (2-11/64)
4.5
(3/16)
➌
54
(2-1/8)
7.5
(19/64)
➊
140M-C....
140M-C..., 140M-D...
18
(23/32)
➍
44 (1-47/64)
45 (1-25/32)
45 (1-25/32)
➊
45 (1-25/32)
➌
.
45 (1-25/32)
4.5
(3/16)
90 (3-35/64)
45 (1-25/32)
.
➊
➋
➌
➍
Mounting on 35 mm DIN Rail EN 50 022-35
Auxiliary contact (side-mounted)
Undervoltage trip or Shunt trip
Auxiliary contact (front-mounted)
➍
91 (3-37/64)
4.5
(3/16)
102 (4-1/64)
7.5
(19/64)
140M-F....
˚
90
90
90
˚
90
˚
˚
4.5
min. 100
3.5
1.5...5
35...45
Mounting position 140M-C..., 140M-D..., 140M-F…
b
53.5
a
53.5
+ 5 mm
4...8
a
117...338
126...347
148.6...369.6
b
105.5 ±5
114.5 ±5
137.1 ±5
c1
49.5
49.5
59.35
c2
40.5
40.5
50.35
c2
4.5
c1
140M-C…
140M-D…
140M-F…
2.4
140M-C-D...66
41
Bulletin 140M
Motor Protectors
Approximate Dimensions
Dimensions
Dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes.
Cat. No. 140-CMN
Mounting position of
Cat. No. 140-CMN
42
Bulletin 140M
Motor Protectors
Type 2 Coordination
Type 2 Coordination per UL508E
Voltage: 480V, 60 HZ
Motor Protector
Cat. No.
Thermal Overload
Release
Setting Range
[A]
Magnetic Release
Response Current
[A]
Contactor
Cat. No. ➊
Short-Circuit Current, Iq
[kA]
140M-C2E-A16
140M-C2E-A25
140M-C2E-A40
140M-C2E-A63
140M-C2E-B10
140M-C2E-B16
140M-C2E-B25
140M-C2E-B40
140M-C2E-B63
140M-C2E-C10
140M-C2E-C16
140M-C2E-C20
140M-C2E-C25
140M-D8E-B25
140M-D8E-B40
140M-D8E-B63
140M-D8E-C10
140M-D8E-C16
140M-D8E-C20
140M-D8E-C25
140M-F8E-C10
140M-F8E-C16
140M-F8E-C20
140M-F8E-C25
140M-F8E-C32
140M-F8E-C45
140-CMN-2500
140-CMN-4000
140-CMN-6300
140-CMN-9000
0.10...0.16
0.16...0.25
0.25...0.40
0.40...0.63
0.63...1.0
1.0...1.6
1.6...2.5
2.5...4.0
4.0...6.3
6.3...10.0
10.0...16.0
14.5…20.0
18.0…25.0
1.6...2.5
2.5...4.0
4.0...6.3
6.3...10.0
10.0...16.0
14.5…20.0
18.0…25.0
6.3...10.0
10.0...16.0
14.5…20.0
18.0…25.0
23.0...32.0
32.0...45.0
16.0…25.0
25.0…40.0
40.0...63.0
63.0...90.0
2.1
3.3
5.2
8.2
13
21
33
52
82
130
208
260
325
33
52
82
130
208
260
325
130
208
260
325
416
585
350
560
882
1260
100-C09, 100-M05
100-C09, 100-M05
100-C09, 100-M05
100-C09, 100-M05
100-C09, 100-M05
100-C09, 100-M05
100-C09
100-C30
100-C30
100-C30
100-C30
100-C30
100-C30
100-C09
100-C09
100-C09
100-C09
100-C12
100-C23
100-C23
100-C16
100-C16
100-C23
100-C23
100-C30
100-C37
100-C30
100-C30
100-C43
100-C72
65
65
65
65
65
65
50
50
50
50
10
10
10
65
65
65
65
65
65
50
65
65
65
65
65
50
65
65
65
65
Definition of Type "2" short-circuit coordination per UL 508E:
•
•
The contactor or starter must not endanger persons or plant in the event of a short-circuit.
No damage to the overload relay or other parts may occur with the exception of welding of the contactor or starter contacts if t hese can be
easily separated without appreciable deformation (such as with a screwdriver).
In the event of short-circuit, fast-opening, strong current-limiting Bulletin 140M motor protectors make it possible to build economical, fully shortcircuit coordinated starter combinations in accordance with UL508E, Type "2" coordination.
➊ Ratings apply to specified or larger contactor.
43
Bulletin 140M
Motor Protectors
Type 2 Coordination
Type 2 Coordination according to UL 508E
Voltage: 600V, 60 HZ
Motor Protector
Cat. No.
Thermal Overload
Release
Setting Range
[A]
Magnetic Release
Response Current
[A]
Contactor
Cat. No. ➊
Short-Circuit Current, Iq
[kA]
140M-C2E-A16
140M-C2E-A25
140M-C2E-A40
140M-C2E-A63
140M-C2E-B10
140M-C2E-B16
140M-C2E-B25
140M-C2E-B40
140M-C2E-B63
140M-C2E-C10
140M-C2E-C16
140M-C2E-C20
140M-C2E-C25
140M-D8E-B25
140M-D8E-B40
140M-D8E-B63
140M-D8E-C10
140M-D8E-C16
140M-D8E-C20
140M-D8E-C25
140M-F8E-C10
140M-F8E-C16
140M-F8E-C20
140M-F8E-C25
140M-F8E-C32
140M-F8E-C45
140-CMN-2500
140-CMN-4000
140-CMN-6300
140-CMN-9000
0.10...0.16
0.16...0.25
0.25...0.40
0.40...0.63
0.63...1.0
1.0...1.6
1.6...2.5
2.5...4.0
4.0...6.3
6.3...10.0
10.0...16.0
14.5…20.0
18.0…25.0
1.6...2.5
2.5...4.0
4.0...6.3
6.3...10.0
10.0...16.0
14.5…20.0
18.0...25.0
6.3...10.0
10.0...16.0
14.5…20.0
18.0…25.0
23.0...32.0
32.0...45.0
16.0…25.0
25.0…40.0
40.0...63.0
63.0...90.0
2.1
3.3
5.2
8.2
13
21
33
52
82
130
208
260
325
33
52
82
130
208
260
325
130
208
260
325
416
585
350
560
882
1260
100-C09, 100-M05
100-C09, 100-M05
100-C09, 100-M05
100-C09, 100-M05
100-C09, 100-M05
100-C09, 100-M05
100-C09
100-C16
100-C23
100-C30
100-C30
100-C30
100-C30
100-C09
100-C16
100-C23
100-C30
100-C30
100-C30
100-C30
100-C30
100-C30
100-C30
100-C30
100-C30
100-C37
100-C30
100-C30
100-C43
100-C72
47
47
47
47
47
47
10
5
5
5
5
5
5
10
10
10
10
10
5
5
10
10
10
10
10
10
42
42
30
15
Definition of Type "2" short-circuit coordination per UL 508E:
•
•
The contactor or starter must not endanger persons or plant in the event of a short-circuit.
No damage to the overload relay or other parts may occur with the exception of welding of the contactor or starter contacts if t hese can be
easily separated without appreciable deformation (such as with a screwdriver).
In the event of short-circuit, fast-opening, strong current-limiting Bulletin 140M motor protectors make it possible to build economical, fully shortcircuit coordinated starter combinations in accordance with UL508,Type "2" coordination.
➊ Ratings apply to specified or larger contactor.
44
Bulletin 190
Compact Combination Starters
0Circuit Breaker
0
Bulletin 190
Compact
Combination
Starters
• Power Range 0.1...45 A
• Bulletin 190E Modular
Eco Starters
• Bulletin 190S Pre-wired
Compact Starters
• Uses Bulletin 140M Motor
Protectors and Bulletin
100-C Contactors
• 140M is UL/CSA
Approved as
Self-Protected
(Type E) Manual
Combination Starters
• Type 2 Coordination with
100-C Contactors
• Mounts to DIN Rail(s) or
Screw Mounts
TABLE OF CONTENTS
Description
Page
Product Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Specifications
Factory Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Conformity to Standards:
Approvals:
IEC 947-1/2/4
CE
IEC 204-1
Description
Page
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Approximate Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Type 2 Coordination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Your order must include:
• Cat. No. of the motor protector
selected.
• If required, Cat. No. of any
accessories.
45
Bulletin 190E
Compact Combination Starters
Product Selection
• 190E Modular Eco Starter using 140M Motor Protector and 100M Mini Contactor
• Mounting Options:
- Snap Fixing on (1) 35 mm DIN Rail
• AC or DC Control Coils
Typical 3-phase [HP]
575V
Non-Reversing Starter ➊
Cat. No.
—
—
190E-MN⊗2-CA16X
—
—
—
—
190E-MN⊗2-CA25X
190E-MN⊗2-CA40X
—
0.5
—
0.75
190E-MN⊗2-CA63X
190E-MN⊗2-CB10X
1
1.5
1
2
190E-MN⊗2-CB16X
190E-MN⊗2-CB25X
1
3
3
190E-MN⊗2-CB40X
2
3
3
5
5
5
190E-NN⊗2-CB63X
190E-NN⊗2-CC10X
Thermal Trip
[A]
Magnetic Trip
[A]
Icu
200V
0.10...0.16
2.1
65
—
—
0.16...0.25
0.25...0.40
3.3
5.2
65
65
—
—
—
—
0.40...0.63
0.63...1.00
8.2
13
65
65
—
—
—
—
1.00...1.60
1.60...2.50
21
33
65
65
—
0.5
—
0.5
2.50...4.00
52
65
1
4.00...6.30
6.30...10.0
82
130
65
65
1.5
3
230V
460V
Uses 140M-C, High Break
➊ 1 N.O. auxiliary contact on contactor is standard. See Factory Options on p. 49 for additional auxiliary contact configurations.
⊗ Standard Voltage Suffix Codes for DC Control
Voltage
24V
48V
100V
100…120V
220…230V
230…240V
380V
50 Hz
60 Hz
KD
KD
KH
KH
D
—
—
D
A
—
—
A
KK
KK
DC
24
—
—
—
—
—
—
Factory Installed Options — Page 49
140M Accessories — Page 21
100M Accessories — Publication No. 0100C-1.0.1
46
Bulletin 190E
Compact Combination Starters
Product Selection, Continued
• 190E Modular Eco Starter using 140M Motor Protector and 100C MCS Contactor
• Mounting Options:
- Snap Fixing on (1) 35 mm DIN Rail
• AC Control Coils
Typical 3-phase [HP]
575V
Non-Reversing Starter ➊
Cat. No.
—
—
190E-AN⊗2-CA16X
—
—
—
—
190E-AN⊗2-CA25X
190E-AN⊗2-CA40X
—
0.5
—
0.75
190E-AN⊗2-CA63X
190E-AN⊗2-CB10X
—
0.5
1
1.5
1
2
190E-AN⊗2-CB16X
190E-AN⊗2-CB25X
1
1.5
1
2
3
3
3
5
190E-AN⊗2-CB40X
190E-AN⊗2-CB63X
65
10
2
3
3
5
7.5
10
10
10
190E-BN⊗2-CC10X
190E-CN⊗2-CC16X
260
325
10
10
5
5
7.5
7.5
15
15
15
15
190E-DN⊗2-CC20X
190E-DN⊗2-CC25X
1.60…2.50
33
65
0.5
0.5
1.5
2
190E-AN⊗2-DB25X
2.50…4.00
4.00…6.30
52
82
65
65
1
1.5
1
2
3
3
3
5
190E-AN⊗2-DB40X
190E-AN⊗2-DB63X
Thermal Trip
[A]
Magnetic Trip
[A]
Icu
200V
0.10...0.16
2.1
65
—
—
0.16...0.25
0.25...0.40
3.3
5.2
65
65
—
—
—
—
0.40...0.63
0.63...1.00
8.2
13
65
65
—
—
—
—
1.00...1.60
1.60...2.50
21
33
65
65
—
0.5
2.50...4.00
4.00...6.30
52
82
65
65
6.30...10.0
10.0…16.0
130
208
14.5…20.0
18.5…25.0
230V
460V
Uses 140M-C, High Break
Uses 140M-D, High Break PLUS
6.30…10.0
130
65
2
3
7.5
10
190E-BN⊗2-DC10X
10.0…16.0
14.5…20.0
208
260
65
65
3
5
5
7.5
10
15
10
15
190E-CN⊗2-DC16X
190E-DN⊗2-DD20X
18.5…25.0
325
25
5
7.5
15
15
190E-DN⊗2-DD25X
➊ 1 N.O. auxiliary contact on contactor is standard. See Factory Options on p. 49 for additional auxiliary contact configurations.
⊗ Standard Voltage Suffix Codes for AC Control
Type
[V]
12
24
50 Hz
R
60 Hz
Q
50/60 Hz
[V]
190E
32
36
42
48
100
K
V
J
—
W
X
Y
KP
V
—
X
—
—
KJ
—
—
—
KY
KP
220…
230
230
230…
240
240
277
347
380
100…
110
110
120
—
D
KP
—
—
200…
220
200…
230
208
208…
240
KG
—
—
—
—
—
KG
—
H
L
—
KG
—
KL
—
—
440
480
500
550
600
—
127
200
P
S
D
—
KD
—
380...
400
400
400…
415
50 Hz
F
—
VA
T
—
—
—
N
—
G
B
—
M
C
60 Hz
—
—
—
A
T
I
E
—
—
—
N
B
—
—
C
50/60 Hz
—
KF
—
KA
—
—
—
—
KN
—
KB
—
—
—
—
Factory Installed Options — Page 49
140M Accessories — Page 21
100M Accessories — Publication No. 0100C-1.0.1
47
Bulletin 190S
Compact Combination Starters
Product Selection, Continued
• 190S Compact Combination Starter using 140M Motor Protector and 100-C Contactor
• Auxiliary Contacts Wired to Terminal Block at Bottom of Starter Assembly
• Mounting Options:
- Screw Fixing
- Snap Fixing on (1) or (2) 35 mm DIN Rails
- Snap Fixing on (1) 75 mm DIN Rail
• AC or DC Control Coils
Typical 3-phase [HP]
Non-Reversing Starter ➊
Cat. No.
Thermal Trip
[A]
Magnetic Trip
[A]
Icu
0.10...0.16
0.16...0.25
2.1
3.3
65
65
190S-AN⊗2-CA16C
190S-AN⊗2-CA25C
0.25...0.40
0.40...0.63
5.2
8.2
65
65
190S-AN⊗2-CA40C
190S-AN⊗2-CA63C
0.63...1.00
1.00...1.60
13
21
65
65
1.60...2.50
2.50...4.00
33
52
65
65
0.5
1
4.00...6.30
6.30...10.0
82
130
65
65
10.0...16.0
14.5...20.0
208
260
10
10
18.5...25.0
325
10
200V
230V
460V
575V
Uses 140M-C, High Break
0.5
1
0.75
1
190S-AN⊗2-CB10C
190S-AN⊗2-CB16C
0.5
1
1.5
3
2
3
190S-AN⊗2-CB25C
190S-AN⊗2-CB40C
1.5
2
2
3
3
7.5
5
10
190S-AN⊗2-CB63C
190S-BN⊗2-CC10C
3
5
5
7.5
10
15
10
15
190S-CN⊗2-CC16C
190S-DN⊗2-CC20C
5
7.5
15
15
190S-DN⊗2-CC25C
2
3
190S-AN⊗2-DB25C
190S-AN⊗2-DB40C
Uses 140M-D, High Break PLUS
1.60...2.50
2.50...4.00
33
52
65
65
0.5
1
0.5
1
1.5
3
4.00...6.30
82
65
1.5
2
3
5
190S-AN⊗2-DB63C
6.30...10.0
10.0...16.0
130
208
65
65
2
3
3
5
7.5
10
10
10
190S-BN⊗2-DC10C
190S-CN⊗2-DC16C
14.5...20.0
18.5...25.0
260
325
65
25
5
5
7.5
7.5
15
15
15
15
190S-DN⊗2-DC20C
190S-DN⊗2-DC25C
tions on p. 50 for additional auxiliary
➊ 1 N.O. + 1 N.C. auxiliary contacts on 140M is standard. 1 N.O. auxiliary contact on 100C contactor is standard. See Factory Op
contact configurations.
⊗ Standard Voltage Suffix Codes for AC Control
[V]
50 Hz
60 Hz
190S
12
24
32
36
42
48
100
100110
110
120
127
200
200220
200230
208
208240
R
Q
K
J
V
—
W
V
X
—
Y
X
KP
—
—
KP
D
—
P
D
S
—
KG
—
—
KG
—
—
—
H
—
L
—
—
—
KY
KP
—
KD
—
—
KG
—
KL
—
—
KJ
—
220230
230
230240
240
277
347
380
380400
400
400415
440
480
500
550
600
50 Hz
F
—
VA
T
—
—
—
N
—
G
B
—
M
C
—
60 Hz
50/60 Hz
—
—
—
KF
—
—
A
KA
T
—
I
—
E
—
—
—
—
KN
—
—
N
KB
B
—
—
—
—
—
C
—
50/60 Hz
[V]
⊗ Standard Voltage Suffix Codes for DC Control
190S Voltage [V]
Code
6…12
12
24
24 w/
diode
36
48
60
64
72
80
110
115
125
220
230
240
ZR
ZQ
ZJ
DJ
ZW
ZY
ZZ
ZB
ZG
ZE
ZD
ZP
ZS
ZA
ZF
ZT
Factory Installed Options — Page 50
140M Accessories — Page 21
100M Accessories — Publication No. 0100C-1.0.1
48
Bulletin 190
Compact Combination Starters
Specifications
190E Factory Options:
• For modifications add (option code ➊) and — (option code ➋) for desired features to catalog number.
➊ Replace option code X with desired auxiliary contact: 190E-MND2-CA16X
140M Auxiliary and Trip Contacts
X
Without Auxiliary and Trip Contacts (STANDARD)
A
Auxiliary Contact 1 N.C.
B
Auxiliary Contact 1 N.C.
C
Auxiliary Contact 1 N.O. + 1 N.C.
D
Auxiliary Contact 2 N.O.
R
1 N.O. Trip + 1 N.C. Auxiliary Contact
S
1 N.O. Trip + 1 N.O. Auxiliary Contact
➋ Add desired option codes AFTER auxiliary contact option code: 190E-MND2-CA-16X-Y
Modifications, Accessories
JE
Electronic Interfaces (100-C)
R
Surge Suppressor RC (100-C)
V
Surge Suppressor Varistor (100-C)
D
Surge Suppressor Diode (100-C)
KN
Lockable Twist Knob (140M) - Black
KY
Lockable Twist Knob (140M) - Red/Yellow
Additional Contactor Auxiliaries (Side Mount)
S01
1 N.C.
S10
1 N.O.
S11
1 N.O. + 1 N.C.
S20
2 N.O.
Additional Contactor Auxiliaries (Front Mount)
F11
1 N.O. + 1 N.C.
F20
2 N.O.
F22
2 N.O. + 2 N.C.
Additional 140M Auxiliaries (Side Mount)
A02
2 N.C.
A20
2 N.O.
A11
1 N.O. + 1 N.C.
Additional 140M Trip Contacts (Side Mount)
R00
1 N.O. Thermal-Mag + 1 N.O. Mag Only
R01
1 N.O. Thermal-Mag + 1 N.C. Mag Only
R10
1 N.C. Thermal-Mag + 1 N.O. Mag Only
M11
1 N.O. Mag Only + 1 N.C. Mag Only
49
Bulletin 190
Compact Combination Starters
Specifications, Continued
190S Factory Options:
• For modifications add (option code ➊) and — (option code ➋) for desired features to catalog number.
➊ Replace option code C with desired auxiliary contact: 190S-AND2-CA16C
140M Auxiliary and Trip Contacts
C
Auxiliary Contact 1 N.O. + 1 N.C. (STANDARD)
D
Auxiliary Contact 2 N.O.
R
1 N.O. Trip + 1 N.C. Auxiliary Contact
S
1 N.O. Trip + 1 N.O. Auxiliary Contact
➋ Add desired option codes AFTER auxiliary contact option code: 190S-AND2-CA16C-Y
Modifications, Accessories
JE
Electronic Interfaces (100-C)
R
Surge Suppressor RC (100-C)
V
Surge Suppressor Varistor (100-C)
D
Surge Suppressor Diode (100-C)
SP
Socket and Plug for Control Circuit
KN
Lockable Twist Knob (140M) - Black
KY
Lockable Twist Knob (140M) - Red/Yellow
Additional Contactor Auxiliaries (Side Mount)
S01
1 N.C.
S10
1 N.O.
S11
1 N.O. + 1 N.C.
S20
2 N.O.
Additional 140M Auxiliaries (Side Mount)
A02
2 N.C.
A20
2 N.O.
A11
1 N.O. + 1 N.C.
Additional 140M Trip Contacts (Side Mount)
R00
1 N.O. Thermal-Mag + 1 N.O. Mag Only
R01
1 N.O. Thermal-Mag + 1 N.C. Mag Only
R10
1 N.C. Thermal-Mag + 1 N.O. Mag Only
M11
1 N.O. Mag Only + 1 N.C. Mag Only
50
Bulletin 190
Compact Combination Starters
Wiring Diagrams
Wiring Diagram 190S-A…D
L1 L2 L3
190S-A...D
L1 L2 L3
190S-A...D
1 3 5
1 3 5
With Electronic
Interface JE
Trip Contact
2 4 6
2 4 6
1 3 5
1 3 5
N1
+
A1
13
14
21
22
13
A1
2 4 6
A2
A2
T1 T2 T3
A2
K1M
K1M
2 4 6
A2
T1 T2 T3
A2
A1
B
A
14
13
14
27
28
13
A1
A1
A1
B
A2 E1 E2 A1
A
14
- JE Option
23
24
21
B
A
22
21
B
A
22
190S-_ _ _ 2-_ _ _ _ C
190S-_ _ _ 2-_ _ _ _ S
Wiring Diagram 190S-E…G
L1 L2 L3
190S-E...G
1 3 5
21
13
1 3 5
13
14
22
14
L1 L2 L3
190S-E...G
Q
Q
2 4 6
With Electronic
Interface JE
27
28
Trip Contact
2 4 6
N1
+
21
13
13
14
21
23
22
13
1 3 5
14
K1M
22
14
14
A1
2 4 6
A2
T1 T2 T3
A2
A1
B
A
21
13
14
27
28
13
13
21
14
K1M
22
14
14
23
23
24
24
24
24
B
A
190S-_ _ _ 2-_ _ _ _ C
A1
2 4 6
A2
A2
T1 T2 T3
A2
A1
23
B
A2 E1 E2 A1
A
24
23
A1
A1
21
23
24
1 3 5
- JE Option
B
A
190S-_ _ _ 2-_ _ _ _ S
51
Bulletin 190
Compact Combination Starters
Approximate Dimensions
Dimensions are shown in millimeters. Dimensions are not intended for manufacturing purposes.
190E Approximate Dimensions
b1
3 (3/32)
b
b2
b
b2
b1
c1
a
Cat. No.
a
a
190E Eco Starters
190E-MN…190E-NN
45 (1-25/32)
190E-AN…190E-DN
191E Reversing Eco Starters
191E-MN…191E-NN
191E-AN…191E-DN
52
45 (1-25/32)
a1
a1
0
0
c
a
b
164 (6-15/32)
178 (7)
164 (6-15/32)
178 (7)
b1
b2
45 (1-25/32)
—
45 (1-25/32)
—
c
45 (1-25/32)
83.5 (3-19/64)
45 (1-25/32)
83.5 (3-19/64)
c1
70 (2-49/64)
70 (2-49/64)
Bulletin 190
Compact Combination Starters
Approximate Dimensions, Continued
Dimensions are shown in millimeters. Dimensions are not intended for manufacturing purposes.
140M + 100-C/104-C Approximate Dimensions – Separate Mount
b1
3 (3/32)
b
b2
b
b2
b1
c1
a
a
140M + 100-C
Cat. No.
a1
c
a
140M + 104-C
a
a1
b
b1
b2
140M-C2 OR 140M-D8 + 100C…(must be separately mounted on 2 DIN Rails)
100-C09ZU…100-C16ZU
45 (1-25/32)
0
178 (7)
45 (1-25/32)
100-C23ZU
140M-C2 OR 140M-D8 + 104C…(must be separately mounted on 2 DIN Rails)
—
100-C09ZU…100-C16ZU
100-C23ZU
—
45 (1-25/32)
10 (25/64)
178 (7)
45 (1-25/32)
140M-F8 + 100-C Contactors (must be separately mounted on 2 DIN Rails)
100-C30…100-C37
45 (1-25/32)
0
164 (6-15/32)
55 (2-11/64)
100-C30Z…100-C37Z
100-C43
54 (2-1/8)
0
178 (7)
55 (2-11/64)
100-C43Z
140M-F8 + 104-C Reversing Contactors (must be separately mounted on 2 DIN Rails)
100-C30…100-C37
45 (1-25/32)
10 (25/64)
164 (6-15/32)
55 (2-11/64)
100-C30Z…100-C37Z
100-C43
54 (2-1/8)
10 (25/64)
178 (7)
55 (2-11/64)
100-C43Z
105 (4-9/64)
105 (4-9/64)
105 (4-9/64)
105 (4-9/64)
c
109 (4-19/64)
127 (5)
109 (4-19/64)
127 (5)
101 (4)
145 (5-45/64)
104 (4-1/8)
148 (5-13/16)
101 (4)
145 (5-45/64)
104 (4-1/8)
148 (5-13/16)
c1
70 (2-49/64)
70 (2-49/64)
110 (4-21/64)
110 (4-21/64)
110 (4-21/64)
110 (4-21/64)
53
Bulletin 190
Compact Combination Starters
Approximate Dimensions, Continued
Dimensions are shown in millimeters. Dimensions are not intended for manufacturing purposes.
190S-A…D Approximate Dimensions
A
5.5
9
45
8
4
Ø5.4
9
215
178
18
9
Ø5.4
5.5
34
B
C
5.5
A
[mm]
190S-AN
190S-BN
190S-CN
190S-DN
190S-ANZ
190S-BNZ
190S-CNZ
190S-DNZ
54
140M-C
B
[mm]
112
140M-D
122
140M-C
134.5
140M-D
144.5
140M-C
140M-D
157
167
C
[mm]
107
100-FA, 100-FC
100-FPT
100-FL
138
157
160
132.5
100-FA, 100-FC
163.5
150
100-FA, 100-FC
181
Bulletin 190
Compact Combination Starters
Approximate Dimensions, Continued
;;
;;
;;
;;
Dimensions are shown in millimeters. Dimensions are not intended for manufacturing purposes.
190S-A…D Approximate Dimensions
˚
11
5˚
25˚
90
90
˚
25
25
Safety Clearance
;;;
; ;;
;;;;
yy
; ;;
;yy
;
3.5
21
135
101.5
35
46.2
11
15
75
35
125±1
7.5
25
55
Bulletin 190
Compact Combination Starters
Approximate Dimensions, Continued
Dimensions are shown in millimeters. Dimensions are not intended for manufacturing purposes.
190S-E and 190S-F Approximate Dimensions
A
9
8
5.5
4
54
Ø5.4
9
238
200
18
9
Ø5.4
B
C
43
5.5
5.5
A
[mm]
B
[mm]
135
124
100-FB
100-FPT
100-FL
154.5
173.5
176.5
179
168
100-FB
198.5
190S-EN
190S-FN
190S-ENZ
190S-FNZ
56
140M-F
C
[mm]
Bulletin 190
Compact Combination Starters
Approximate Dimensions, Continued
Dimensions are shown in millimeters. Dimensions are not intended for manufacturing purposes.
190S-G Approximate Dimensions
A
9
8
5.5
4
54
Ø5.4
9
238
200
18
9
Ø5.4
B
C
43
5.5
5.5
190S-GN
A
[mm]
B
[mm]
135
118.5
100-FB
100-FPT
100-FL
157
176
179
179
162.5
100-FB
201
140M-F
190S-GNZ
C
[mm]
57
Bulletin 190
Compact Combination Starters
Approximate Dimensions, Continued
;;
;;;
Dimensions are shown in millimeters. Dimensions are not intended for manufacturing purposes.
190-E…G Approximate Dimensions
90
˚
25˚
DC
AC
90
25˚
˚
90
˚
25
25
Safety Clearance
75
35
56
125±1
58
7.5
;
;y
;y
;
21
145.5
;
;
3.5
25
Bulletin 190E
Compact Combination Starters
Type 2 Coordination
Type 2 Coordination per UL 508E
•
190E Modular Eco Starter using 140M Motor Protector and 100M Mini Contactors or 100-C MCS Contactors
Voltage: 480V, 60 HZ
Eco Starter
Cat. No.
Thermal Overload Release
Setting Range
[A]
Magnetic Release
Response Current
[A]
Short-Circuit Current, Iq
[kA]
190E-MN⊗
⊗2-CA16X
190E-MN⊗
⊗2-CA25X
190E-MN⊗
⊗2-CA40X
190E-MN⊗
⊗2-CA63X
190E-MN⊗
⊗2-CB10X
190E-MN⊗
⊗2-CB16X
190E-AN⊗
⊗2-CA16X
190E-AN⊗
⊗2-CA25X
190E-AN⊗
⊗2-CA40X
190E-AN⊗
⊗2-CA63X
190E-AN⊗
⊗2-CB10X
190E-AN⊗
⊗2-CB16X
190E-AN⊗
⊗2-CB25X
190E-AN⊗
⊗2-DB25X
190E-AN⊗
⊗2-DB40X
190E-AN⊗
⊗2-DB63X
190E-BN⊗
⊗2-DC10X
190E-CN⊗
⊗2-DC16X
190E-DN⊗
⊗2-DC20X
190E-DN⊗
⊗2-DC25X
0.10...0.16
0.16...0.25
0.25...0.40
0.40...0.63
0.63...1.0
1.0...1.6
0.10...0.16
0.16...0.25
0.25...0.40
0.40...0.63
0.63...1.0
1.0...1.6
1.6…2.5
1.6…2.5
2.5...4.0
4.0...6.3
6.3...10.0
10.0...16.0
14.5...20.0
18.0...25.0
2.1
3.3
5.2
8.2
13
21
2.1
3.3
5.2
8.2
13
21
33
33
52
82
130
201
260
325
65
65
65
65
65
65
65
65
65
65
65
65
50
65
65
65
65
65
65
50
Eco Starter
Cat. No.
Thermal Overload Release
Setting Range
[A]
Magnetic Release
Response Current
[A]
Short-Circuit Current, Iq
[kA]
190E-MN⊗
⊗2-CA16X
190E-MN⊗
⊗2-CA25X
190E-MN⊗
⊗2-CA40X
190E-MN⊗
⊗2-CA63X
190E-MN⊗
⊗2-CB10X
190E-MN⊗
⊗2-CB16X
190E-AN⊗
⊗2-CA16X
190E-AN⊗
⊗2-CA25X
190E-AN⊗
⊗2-CA40X
190E-AN⊗
⊗2-CA63X
190E-AN⊗
⊗2-CB10X
190E-AN⊗
⊗2-CB16X
190E-AN⊗
⊗2-CB25X
190E-AN⊗
⊗2-DB25C
0.10...0.16
0.16...0.25
0.25...0.40
0.40...0.63
0.63...1.0
1.0...1.6
0.10...0.16
0.16...0.25
0.25…0.40
0.40…0.63
0.63…1.0
1.0…1.6
1.6…2.5
1.6…2.5
2.1
3.3
5.2
8.2
13
21
2.1
3.3
5.2
8.2
13
21
33
33
47
47
47
47
47
47
47
47
47
47
47
47
10
10
Voltage: 600V, 60 HZ
Definition of Type "2" short-circuit coordination per UL 508E:
•
•
The contactor or starter must not endanger persons or plant in the event of a short-circuit.
No damage to the overload relay or other parts may occur with the exception of welding of the contactor or starter contacts if t hese can be
easily separated without appreciable deformation (such as with a screwdriver).
In the event of short-circuit, fast-opening, strong current-limiting Bulletin 140M motor protectors make it possible to build economical, fully shortcircuit coordinated starter combinations in accordance with UL 508E, Type "2" coordination.
59
Bulletin 190S
Compact Combination Starters
Type 2 Coordination
Type 2 Coordination per UL 508E
•
190S Compact Combination Starter using 140M Motor Protector and 100-C Contactor
Voltage: 480V, 60 HZ
Compact Starter
Cat. No.
Thermal Overload Release
Setting Range
[A]
Magnetic Release
Response Current
[A]
Short-Circuit Current, Iq
[kA]
190S-AN⊗
⊗2-CA16C
190S-AN⊗
⊗2-CA25C
190S-AN⊗
⊗2-CA40C
190S-AN⊗
⊗2-CA63C
190S-AN⊗
⊗2-CB10C
190S-AN⊗
⊗2-CB16C
190S-AN⊗
⊗2-CB25C
190S-AN⊗
⊗2-DB25C
190S-AN⊗
⊗2-DB40C
190S-AN⊗
⊗2-DB63C
190S-BN⊗
⊗2-DC10C
190S-CN⊗
⊗2-DC16C
190S-DN⊗
⊗2-DC20C
190S-DN⊗
⊗2-DC25C
0.10...0.16
0.16...0.25
0.25...0.40
0.40...0.63
0.63...1.0
1.0...1.6
1.6…2.5
1.6…2.5
2.5…4.0
4.0…6.3
6.3…10.0
10.0…16.0
14.5…20.0
18.0…25.0
2.1
3.3
5.2
8.2
13
21
33
33
52
82
130
208
260
325
65
65
65
65
65
65
65
65
65
65
65
65
65
50
Compact Starter
Cat. No.
Thermal Overload Release
Setting Range
[A]
Magnetic Release
Response Current
[A]
Short-Circuit Current, Iq
[kA]
190S-AN⊗
⊗2-CA16C
190S-AN⊗
⊗2-CA25C
190S-AN⊗
⊗2-CA40C
190S-AN⊗
⊗2-CA63C
190S-AN⊗
⊗2-CB10C
190S-AN⊗
⊗2-CB16C
190S-AN⊗
⊗2-CB25C
190S-AN⊗
⊗2-DB25C
0.10...0.16
0.16...0.25
0.25...0.40
0.40...0.63
0.63...1.0
1.0...1.6
1.6…2.5
1.6…2.5
2.1
3.3
5.2
8.2
13
21
33
33
47
47
47
47
47
47
10
10
Voltage: 600V, 60 HZ
Definition of Type "2" short-circuit coordination per UL 508E:
•
•
The contactor or starter must not endanger persons or plant in the event of a short-circuit.
No damage to the overload relay or other parts may occur with the exception of welding of the contactor or starter contacts if t hese can be
easily separated without appreciable deformation (such as with a screwdriver).
In the event of short-circuit, fast-opening, strong current-limiting Bulletin 140M motor protectors make it possible to build economical, fully shortcircuit coordinated starter combinations in accordance with UL 508E, Type "2" coordination.
60
Publication 140M-SG001A-US-P — January 2000
© 1999 Rockwell International Corporation. All rights reserved. Printed in USA.