COMMITTEE OF TESTING LABORATORIES IEC SYSTEM FOR CONFIRMITY TESTING AND CERTIFICATION OF ELECTRICAL EQUIPMENT TESTING AND MEASURING EQUIPMENT/ALLOWED SUBCONTRACTING IEC 60439-3:2001-05, Edition 1.2 Low-voltage switchgear and controlgear assemblies Part 3: Particular requirements for low-voltage switchgear and controlgear assemblies intended to be installed in places where unskilled persons have access for their use; Distribution boards R=Required by Lab S=May be subcontracted 3PPS=Three Phase Power Supply required Clause 8.2.1 Measurement/testing Temperature rise limits 8.2.2 Dielectric properties 8.2.3 Short-circuit withstand strenght 8.2.4.1 July 2006 Effective connection between the exposed conductive parts of the assembly and the protective circuit Testing / measuring equipment / material needed Load resistors, Temperature acquisition unit, Current/voltage source Impulse voltage generator (1,2/50 µs), Oscilloscope, High voltage probe, AC-voltage source (0 - min. 3,5 kV), V-meter (min. 3,5 kV) Short-circuit testing unit for currents higher 10 kA, Measuring devices for voltage, current, cos ϕ, time, I²t-values Ω-meter 1/3 Subcontracting S R S R IEC 60339-3, ed 1.2 COMMITTEE OF TESTING LABORATORIES IEC SYSTEM FOR CONFIRMITY TESTING AND CERTIFICATION OF ELECTRICAL EQUIPMENT Clause 8.2.4.2 8.2.5 8.2.6 8.2.7 Measurement/testing Short-circuit withstand strength of the protective circuit Clearances and creepage distances Mechanical operation Degree of protection 8.2.9 8.2.10 Construction and marking Impact strength 8.2.11 Resistance to rusting 8.2.12 Resistance of insulating materials to heat July 2006 Testing / measuring equipment / material needed Same as for 8.2.3 Sliding gauge None Sphere 50 mm diameter, Jointed test finger, Test rod 2,5 mm diameter, Test wire 1,0 mm diameter, Sphere 12,5 mm diameter, _____________________________________________________ Dust chamber; Drip box; Drip box 15°; Oscillating tube/spray ± 60° or spray nozzle/spray ± 60°; Oscillating tube/spray ± 180°; Water jet hose nozzle - nozzle 6,3 mm diameter, Water jet hose nozzle - nozzle 12,5 mm diamter, Immersion tank None Cooling chamber, Spring impact hammer Ammonium-Chlorid, Balance, Refined petrol or methylchloroform, Climatic chamber, Heating chamber Heating chamber, Ball pressure test apparatus 2/3 Subcontracting S R R R ___________ S R R R R IEC 60339-3, ed 1.2 COMMITTEE OF TESTING LABORATORIES IEC SYSTEM FOR CONFIRMITY TESTING AND CERTIFICATION OF ELECTRICAL EQUIPMENT Clause 8.2.13 8.2.14 8.2.15 Measurement/testing Resistance of insulating materials to abnormal heat and to fire Resistance to humidity Mechanical strength of fastening means of enclosures Testing / measuring equipment / material needed Glow wire test apparatus Climatic chamber, AC-voltage source, V-meter Sliding gauge, Screwdriver or spanner for applying a torque Subcontracting R R R Note: The presence of equipment alone does not indicate a satisfactory situation. Assessors must evaluate the equipment design, calibration, uncertainty and documentation to ensure compliance with the directions of the standard. The requirements of ISO Guide 25 regarding validation are applicable, as the tests of this standard are not standardized tests. July 2006 3/3 IEC 60339-3, ed 1.2