B
V
L
S
ENIOR
P
ROJECT
E LECTRICAL E NGINEERING D EPARTMENT
C ALIFORNIA P OLYTECHNIC S TATE U NIVERSITY
S
AN
L
UIS
O
BISPO
2015
1
I would like to thank Dr. Shaban and Dr. Nafisi for giving me a solid foundation in power systems analysis and protection. Their knowledge and ability to teach has been unparalleled. Thanks to Jaime and the other support staff for the work they do to support the lab equipment and students in their projects.
2
The objective of this senior project is to protect a three terminal transmission line during fault conditions using the SEL-311L microprocessor based relay and communication assisted permissive over-reaching transfer trip protection. The SEL-311L’s directional distance elements are programmed to trip on internal faults while faults external to the zones of protection are ignored.
Upon sensing a fault condition, the relay issues a trip command to the local breaker and a permissive key for tripping to the remote relay via fiber optic communication. When a permissive key is received and all other permissive conditions have been satisfied, the remote relay issues a trip command to its breaker. Included in this senior project are lab materials for students who wish to complete the lab or for integration into a power protection laboratory in the future. The lab introduces Over-reach concepts and Zone 2 protection. Students gain experience in programming
SEL relays, testing protection functionality, and protective relay logic.
3
2 REQUIREMENTS, SPECIFICATIONS, AND BLOCK DIAGRAM ....................................... 12
4
SEL 311-L PILOT PROTECTION LABORATORY MANUAL ........................................ 48
TABLE 2-2 LEVEL 0 BLOCK DIAGRAM INPUT / OUTPUT FUNCTIONALITY .................. 15
TABLE 2-3 LEVEL 1 BLOCK DIAGRAM INPUT / OUTPUT FUNCTIONALITY ................. 17
5
6
Implementation of a Permissive Overreaching Transfer Trip protection (POTT) scheme relies on the application of at least two directional distance (21) units. Distance units require monitoring of both current and voltage to determine the impedance of the connected circuit. During low impedance conditions, the relay is programmed to trip the breaker to prevent over-current conditions from damaging the transmission line and connected equipment. To achieve POTT protection, the directional distance units or relays are connected via a communications channel.
When either relay detects a fault condition internal to the line, a distance element bit is asserted and the relay waits for a permissive trip signal from the opposite relay. In order to receive the trip signal, the other relay must sense the fault condition, issue the trip signal, and send it via the communications channel. Once both of the distance elements have asserted and the permissive trip or key bits have been asserted, the relays close their respective trip contacts. The trip signal is then sent to the trip coil of the breaker causing the breaker to operate and open. Once both breakers have opened, any fault condition that existed in the protected region of the line is now electrically isolated.
1.1
PROJECT DEVELOPMENT
Dr.Shaban originally developed the idea and gave it to me for further development and implementation. The experiment will hopefully be included in the EE444 or a Power Protection laboratory class and executed by students interested in power systems protection and SEL relays.
The project requirements and specifications were developed over a series of conversations with
Dr.Shaban. Upon completion of the lab, students will be able to implement POTT and PUTT impedance protection schemes on a tapped multi-source transmission line using the SEL-311L relays and fiber optic communication. In the future, the power faculty hopes to establish an operational micro-grid with the intent of integrating protection and analyzing system functionality when fault conditions appear at different locations in the system. This project represents one piece of that system. The lab’s delivery date is June 2015, at which time the lab will be fully documented and operational.
7
The transmission line consists of 100mH inductors in series with 10Ω power resistors. The line connects to a tapped load comprised of three wye connected power resistors. System breakers were available and chosen based on past student design. The breaker boxes consist of manual trip/close contacts and a three-pole contactor which simulates the fast operation of a high-voltage circuit breaker. The circuit breaker can be automatically operated by connecting the SEL relay to the appropriate coil contacts. The source(s) are three-phase at 208VLL which is available at all of the lab benches in the power labs.
My knowledge of power protection was minimal at the beginning of this project and required me to rely on the SEL-311L instruction manuals provided by Schweitzer Engineering Laboratories (SEL).
SEL produces thorough documentation for their relays including application notes on advanced configurations such as POTT and PUTT. SEL allows students to enroll in a Computer Based
Training (CBT 101) to gain basic familiarity with their relaying system. The CBT allowed me to understand the fundamentals of communicating and programming the relay. The department was able to purchase CBT 104 which further introduced relay logic programming. Dr. Shaban’s EE518 class notes, and Protective Relaying Principles, and Applications 4th Edition , by J. L. Blackburn, and T. J.
Domin, were heavily utilized as resources for this project [1].
1.2
THEORY OF OPERATION
Distance protection requires measurement of both current and voltage to determine the impedance of a line and connected load at a given time. The impedance for a transmission line network is determined during design phase and is used as a starting point for the design of the distance protection system. The transmission line impedance is a physical quantity that remains generally constant under normal operating conditions. Any impedance detected by the relay lower than 100% of the line impedance indicates a fault condition on that line. The non-directional distance relay zone of protection is represented graphically by Figure 1-1. The diagram consists of a circle centered at zero. The circle’s radius represents the complex impedance value at which the relay will pick up and issue a trip. The non-directional nature of this configuration poses a problem for protection engineers because of limitations it poses for coordination. Regardless of whether the low impedance condition is caused by a fault internal to the line or external to the line, the relay will see a low impedance and pickup. This becomes an issue when designing non radial systems, commonly
8
referred to as loop systems, because the low impedance condition could cause the relay to pick-up and the breaker to open a non-faulted zone. Adding directional capabilities to the relay allows the engineer to design the system so that fault conditions are cleared by the most appropriate protection devices. The appropriate device is that which causes the least amount of system to be disconnected while maintaining system stability. The graphical representation below in figure 1-2 depicts the opening of a non-faulted transmission line.
FIGURE 1-1 NON-DIRECTIONAL R-X DIAGRAM
FIGURE 1-2 RING TOPOLOGY
For loop systems (ring topology) and other non-radial systems, adding a directional unit and communication to the distance relay allows the protection engineer to create zones of protection that do not necessarily extend into other devices areas of protection. Multiple zones with varying impedances and time delay settings can be used to create backup protection for other devices close to the line if necessary. Protection for a line is accomplished with two relays who both look towards opposite ends of the transmission line as shown in figure 1-3. Each relay’s zone of protection
9
overlaps. During internal Zone 2 fault conditions, the relays should detect the fault, issue a trip key command to the relay at the opposite end of the line, and assert its own zone 2 element.
FIGURE 1-3 RELAY ZONES OF PROTECTION
FIGURE 1-4 DIRECTIONAL DISTANCE MHO DIAGRAM
The two most popular schemes for communication assisted distance relaying are POTT and PUTT protection. Permissive Overreaching Transfer Trip requires the distance element (impedance element) to assert as well as receive a trip key command from the relay at the remote end of the line as shown in the logic diagram below. Permissive Under-reaching Transfer Trip scheme is beyone the scope of this project.
10
FIGURE 1-5 POTT LOGIC
11
2.1
CUSTOMER REQUIREMENTS
Two separate meetings with Dr. Shaban early this year identified his needs and requirements. The system’s main objective is to protect a transmission line using the permissive overreaching transfer trip scheme (POTT). Two SEL311-L relays connected via fiber optic communication protect a transmission line fed from two independent sources. At the center of the line, a third terminal is connected which feeds a wye connected load. The sources will both feed the load under normal load conditions. Fault conditions are then introduced into the system at different nodes internal and external to the transmission line system. Single line to ground (SLG), double line to ground (DLG), line to line (LL), and line to line to line (LLL) fault conditions are applied to the system at the locations specified in Figure 3-1. Faults internal to the transmission line will result in a trip while external faults at the load and beyond the transmission line are ignored. The relays detect Zone 2 faults. All Zone 2 trips will require a permissive trip key from each relay to trip the circuit breakers.
The associated lab materials found in the appendix introduce distance relays and basic relay programming concepts to senior level electrical engineering students. The laboratory allows students to gain hands-on experience with the SEL 311-L relay and implement an operational POTT protection scheme.
The requirements and specifications found below in Table 2-1 are based on the customer needs assessment and follow the IEEE1233 standard for requirements development [3]. Marketing requirements were developed through analyzing the ‘Customer Needs Assessment’ (1.2). The requirements analyzed and Engineering Specifications developed satisfy marketing and customer requirements. The engineering specifications developed using the IEEE1233-6.2 ‘Properties of a
Requirement’ (p.12) [3].
12
2.2
ENGINEERING SPECIFICATIONS
TABLE 2-1 REQUIREMENTS AND SPECIFICATIONS
Customer
Requirements
2
1
1
1
1
1
1
2
2
2
2, 3
2
1, 2, 3
Engineering
Specifications
Justification
2.2.1.1 Use Schweitzer Engineering
Laboratories relay SEL-311L.
2.2.1.2 Use copper wire rated for at least 15 A continuous current or greater.
2.2.1.3 All components have 600V insulation rating or greater.
Teaching SEL 311-L is the main objective of the laboratory.
Minimum gauge of wire provides margin of safety.
All lab voltages below 600V. Safety
2.2.1.4 Transmission Line model connection points labeled and referenced in accompanying lab manual.
2.2.1.5 Transmission Line model capable of accepting banana type connectors.
2.2.2.1 SEL 311-L relays shall be programmed via Desktop PC over existing serial connection.
2.2.2.2 SEL 311-L relays achieves pilot communication via fiber optic communication.
Labeling increases safety and decrease lab setup time. Lab manual reference conveys added information and increases learning efficacy.
Speeds lab setup. Increases safety through recessing and guarding live parts.
Required by equipment manufacturer for connectivity and programming.
Enables POTT protection. Teaches students about pilot protection and relay communication.
2.2.2.3 Laboratory capable of SCADA via SEL-2032 RTAC.
Allows me to further my knowledge about
SEL SCADA. Teaches students about relay communication.
2.2.2.4 Relay programmed using distance protection.
Enables POTT protection scheme.
2.2.2.5 Transmission line ends sourced separately.
Facilitates students learning: over-reach, under-reach, and zone protection.
2.2.2.6 Manual fault propagation.
Student controlled fault condition and location.
Provides student control. Allows for internal and external fault locations.
2.2.2.7 Zone 1 and Zone 2 protection. Satisfies zone protection requirement
2.2.2.8 Low Current (less than 5 A) relay inputs.
Provides margin of safety and prevents relay damage.
13
2, 3, 4
1
1
2.2.4.1 The Laboratory costs less than
$500 (not including SEL relays).
Low cost increases lab feasibility decreases EE department economic burden.
2.2.5.1 Laboratory designed February
20, 2015.
2.2.5.2 Laboratory building begins
March 1, 2015.
Milestone facilitates timely graduation.
Milestone facilitates timely graduation.
5, 7
8
2.2.5.3 Laboratory testing and programming begins April 1, 2015.
2.2.5.4 Supporting documentation completed June 12, 2015.
Milestone facilitates timely graduation.
Milestone facilitates timely graduation.
8
2.2.6.1 Student laboratory manual.
2.2.6.2 Instructor laboratory manual.
Facilitates learning and meets customer requirements.
Customer Requirements
1.
Senior-level power students build and operate system safely.
2.
Teaches students programming concepts related to SEL-311L POTT protection and communication.
3.
Introduces over-reach and under-reach concepts.
4.
Pilot & zone protection concepts introduced.
5.
Completed during three hour lab period.
6.
Accompanying lab documentation.
7.
Low Cost.
8.
Senior Project completed before graduation June 2015.
2.3
BLOCK DIAGRAM LEVEL 0
The level 0 block diagram in Figure 2-1 consists of a single block and describes the basic inputs and outputs from the SEL311-L relay system, breaker, transmission line, and communication system.
The left side of the block diagram describes the inputs and outputs from the West end of the Line and the right side describes the inputs and outputs from the East side of the Line. The left and right sides of the diagram contain both voltage and current inputs from the line. These measurements are used to calculate the perceived impedance of the line to determine if fault conditions are present.
The top of the block represents relay and device power and communication connections. Relay equipment is powered via 120V AC. Breaker control and contactor voltage is 125V DC. The bottom of the block describes inputs and outputs from the relays and breakers to remote annunciator panels typically found in control rooms and on medium voltage switch gear. Figure 2-2 provides a level two-block diagram view of the system and provides more insight into the physical connection of the
14
equipment. A fiber optic connection provides a communications path between the relays. Serial connections provide SCADA throughput to peripheral devices.
TABLE 2-2 LEVEL 0 BLOCK DIAGRAM INPUT / OUTPUT FUNCTIONALITY
1. West Line Current Input From CT (Ia, Ib, Ic)
2. West Line Voltage Input From PT (Va, Vb,
Vc)
Input / Output
3. West Pilot Communication (Tx, Rx)
4. West SCADA (Serial)
5. West Trip Alarm Breaker
6. West Alarm Breaker
7. East Line Current Input From CT (Ia, Ib, Ic)
8. East Line Voltage Input From PT (Va, Vb, Vc)
9. East Pilot Communication (Tx, Rx)
10. East SCADA (Serial)
11. East Trip Alarm Breaker
12. East Alarm Breaker
13. Power 120V AC
14. Station Battery 125VDC
15. PC Communication
Functionality
Current inputs processed by relay microprocessor and analyzed for presence of fault conditions. (I)
Voltage used in conjunction with current determines line impedance and presence of fault conditions. (I)
Communication via fiber optics, ensures high speed tripping and establishes pilot communication capabilities. (IO)
Establishes information channel and data aggregation for HMI and remote control. (IO)
Provides relay with breaker trip confirmation. (I)
Provides relay with breaker status. (I)
Current inputs processed by relay microprocessor and analyzed for presence of fault conditions. (I)
Voltage used in conjunction with current determines line impedance and presence of fault conditions. (I)
Communication via fiber optics, ensures high speed tripping and establishes pilot communication capabilities. (IO)
Establishes information channel and data aggregation for HMI and remote control. (IO)
Provides relay with breaker trip confirmation. (I)
Provides relay with breaker status. (I)
Power for relay equipment. (I)
Power for simulate breaker equipment. (I)
Provides user serial access programming capabilities. (I)
15
FIGURE 2-1 LEVEL 0 BLOCK DIAGRAM
16
2.4
BLOCK DIAGRAM LEVEL 1
TABLE 2-3 LEVEL 1 BLOCK DIAGRAM INPUT / OUTPUT FUNCTIONALITY
Input / Output
1. West Line Current Input From CT (Ia, Ib, Ic)
2. West Line Voltage Input From PT (Va, Vb, Vc)
3. West Pilot Communication (Tx, Rx)
4. West SCADA (Serial)
5. West Trip Alarm Breaker
6. West Alarm Breaker
7. East Line Current Input From CT (Ia, Ib, Ic)
8. East Line Voltage Input From PT (Va, Vb, Vc)
9. East Pilot Communication (Tx, Rx)
10. East SCADA (Serial)
11. East Trip Alarm Breaker
12. East Alarm Breaker
13. Power 120V AC
14. Station Battery 125VDC
15. PC Communication
16. Manual Open / Close (TYP)
17. Trip / Close (TYP)
Functionality
Current inputs processed by relay microprocessor and analyzed for presence of fault conditions. (I)
Voltage used in conjunction with current determines line impedance and presence of fault conditions. (I)
Communication via fiber optics, ensures high speed tripping and establishes pilot communication capabilities. (IO)
Establishes information channel and data aggregation for HMI and remote control. (IO)
Provides relay with breaker trip confirmation. (I)
Provides relay with breaker status. (I)
Current inputs processed by relay microprocessor and analyzed for presence of fault conditions. (I)
Voltage used in conjunction with current determines line impedance and presence of fault conditions. (I)
Communication via fiber optics, ensures high speed tripping and establishes pilot communication capabilities. (IO)
Establishes information channel and data aggregation for HMI and remote control. (IO)
Provides relay with breaker trip confirmation. (I)
Provides relay with breaker status. (I)
Power for relay equipment. (I)
Power for simulate breaker equipment. (I)
Provides user serial access programming capabilities. (I)
Manually opens and closes breaker contactor.
Relay Issued trip/close command
17
FIGURE 2-2 LEVEL 1 BLOCK DIAGRAM
18
The design began with the development of a single line diagram of the system as shown in Figure 3-
1. The single-line diagram identifies the systems main components shows how they are electrically connected.
FIGURE 3-1 SINGLE LINE DIAGRAM
The three terminal transmission line network consists of a line and load tapped at the center of the line. The relays are located at the west and east ends and look towards opposite ends of the line. The relays monitor phase current and voltage. The load consists of three wye connected resistor-inductor pairs. Datasheets and instruction manuals for all the equipment in the system was gathered and the nominal system parameters are tabulated in Table 3-1.
19
TABLE 3-1 TRANSMISSION LINE & LOAD PARAMETERS
West
L1
L2
L3
Load
Source
Resistance
(Ω) / phase
21
21
21
10.5
10.5
Inductance
(H) / phase
200mH
200mH
200mH
Inductive
Reactance (Ω)
75.698
75.698
75.698
37.698
The impedance seen at a relay is affected by the load conditions on the system. Seven possible load flow states were identified and taken into consideration when designing the system. Figure 3-2 identifies the possible states the system can enter under normal operation. Figure 3-2-A (A) was implemented in the lab. Time did not permit for further in-depth study of the effect of load conditions found in Figure 3-2 on system functionality.
20
FIGURE 3-2 LOAD FLOW STATES
21
The design constraints for relay Zone 2 impedance protection require that the relays overreach the line by 120% of the line. Consideration of the load impedance magnitude with respect to each relay and source was taken into consideration in order to prevent overreaching into the load.
Overreaching in to the load could cause false tripping during high load conditions and underreaching the transmission line would result in non-operation during internal faults near the relays.
To prevent non-operation and ensure overlapping Zone 2 protection the relay settings were chosen to be 120% of line impedance. To achieve tripping, the Zone 2 mho circles were overlapped and set to reach 120% of the impedance of the line. Since the load is fed by two sources, the perceived impedance increases because of load sharing. Under normal load conditions, the relays should see an impedance of 200% of the line. If load conditions change and current reverses direction, the relays should block operation further testing would be required to verify operation.
For faults near one of the relays, the effective impedance seen by the remote relay, shown in
Equation 1. Will be one half the impedance of the line in parallel with connected load plus one half of the line. Equation 2 calculates the perceived impedance of the line when a fault condition exists at the remote relay. Equation 3 calculates 120% of the perceived impedance of the line when a fault condition exists at the remote relay.
π
πΉπ π
= (
π
πΏπΌππΈ
2
||π
πΏππ΄π·
) +
π
πΏπΌππΈ Ω
2
π
πΉπ π
= (
21 + 75.698π
2
)||(10 + 37.698π)) + (
21 + 75.698π
2
)Ω
π
πΉπ π
= 0.75 × π
πΏπΌππΈ
Ω
π
πΉπ π
= 58.918∠ 74.5 Ω
1.2 π
πΉπ π
= 70.70∠ 74.5 Ω
2π
πΏπΌππΈ
= 157.11∠ 74.5 Ω
Eq.1
Eq.2
Eq.3
Eq.4
22
0.8
0.7
0.6
0.5
0.4
0.3
0.2
0.1
0
0 0.1
0.2
0.3
0.4
DISTANCE FROM CENTER OF TRANSMISSION LINE
0.5
FIGURE 3-3 RELAYS PERCEIVED IMPEDANCE
DESIGN EQUATIONS:
π2π₯ = 1.2(21 + 75.698π) Eq. 5
π2π₯ = 94.268 ∠ 75° Ω
π2π =
94.268
cos(75°−75.698°)
Ω Eq. 6
π2π ≈ 94Ω
Z2P represents the diameter of the Zone 2 Mho circle at 75 degrees. Equation 5 and Equation 6 calculate the appropriate diameter for the Mho circle based strictly on the physical impedance of the line. Consideration of the load conditions are not taken into account in these equations. Loads or faults whose impedances fall within the circle and seen by both relays, will operate the Zone 2 elements and trip the breakers.
23
For this project, loading and perceived impedance was taken into account. The settings applied to the relays allow for Zone 2 impedance overlapping based on the calculated Z
FRR
. The SEL-311 maximum reach setting is 64Ω. Without additional equipment to reduce the secondary impedance to the relay, full 120% distance line protection is not possible.
POTT relies on communication between the relays for keying. Only when a relay receives a key signal and sees a fault on the line will the relay trip. In this configuration if communication is lost, the relay will still operate but must wait for the Zone timer to timeout before tripping. Waiting for the timer to timeout increases, the total energy released, and increases the probability of equipment damage and system instability. The timer allows for downstream device coordination and breaker tripping. Figure 3-3 depicts the systems MHO diagram.
FIGURE 3-4 MHO DIAGRAM
24
4.1
EQUIPMENT
The project required the following equipment:
(2) SEL-311L
(6) Power Resistor / Inductor combination unit (20+37j) Ω
(1) SEL-2924 Serial to Bluetooth Adapter
(100’) #14 Wire
(50) #14 Fork Terminals
(1) Multi-meter
(2) Circuit Breakers
(1) Wire Strippers
(1) Terminal Crimper
(20) 3’ Banana to Banana Leads
(10) Short Banana to Banana Leads
4.1.1
CIRCUIT BREAKER
The circuit breakers used in this project were built by Dr. Shaban’s student. The circuit breaker includes automatic and manual trip/close capability. The SEL relay outputs can be wired to the breaker unit allowing remote trip/ close commands to be sent from the relay to operate the breaker automatically. For testing faults at a node, the built-in fault switch can be wired to introduce fault conditions into the test circuit. The line-side fault switch terminals are connected to the three phases of the node and the load side terminals of the fault switch are connected together in the desired fault condition.
25
4.1.2
SEL-311L
The SEL-311L is a differential current relay used to protect high voltage transmission lines. The relay includes 4 zone phase distance and ground distance capabilities. Differential and other communications assisted protection schemes, including POTT, utilize the relays fiber optic communications channel for data transfer between system IEDs.
4.1.3
LINE IMPEDANCE
Line impedance was achieved using available electrical engineering department resistor & reactor units built by the department’s lab technicians. The unit consists of (2) 10 ohm power resistors rated at 160W and a 100mH 5A reactor all connected in series. Each electrical node is available for use via a banana type connector standoff.
Part Numbers:
(1) Hammond Manufacturing 195T5 Reactor
(2) Ohmite WFH160 Power Resistor
4.1.4
SEL-2924
EIA-232 to Bluetooth serial adapter allows communication between the relay and computer terminal. The adapter is useful when working with RS-232 devices in the field and is a wireless substituted for its wired counterpart. The adapter comes with a USB rechargeable lithium battery.
4.2
CONSTRUCTION
The lab required approximately 6 hours to wire and confirm the connections. Three-quarters of a standard power lab bench was needed to house the required equipment. Connections were made directly to the back of the relays and source using #14 wire and fork terminal connectors. Relay mimic panels are currently being manufactured by students to allow all lab connections to be made with banana to banana type cables and connectors. Once the mimic panels are completed, overall
26
wiring time should be reduced to under one hour. For this system, the same source was connected to each end of the system to model a loop system connection. For integration into the Cal Poly micro grid separate synchronized generation can be applied to the system with similar functionality obtained.
4.3
CONFIGURATION
The relays were programmed with the impedance settings calculated in the design section. Line parameters neglect the effect of the load and treat the line as a continuous line impedance from the local to remote relay terminal. The CT and VT settings were set to 1 because no PTs or VTs were used in the project and no ratio from primary to secondary exists. All voltage and current inputs to the relays are actual system values. Figure 4-1 & 4-2 show the line parameter settings and distance settings entered into the AcSELerator.
27
FIGURE 4-1 LINE PARAMETERS
28
FIGURE 4-2 PHASE DISTANCE
The following settings (Figures 4-3 - 4-6) represent the trip logic equations, output contacts, and communication settings required to achieve POTT. Figure 4-3 shows the Words when asserted will close the output contacts on the relays. OUT103 when asserted will trip the circuit breaker and is asserted when word !TRIP*!OC are asserted. OUT102 is high when the Close command is asserted.
The breaker requires a momentary close and will remain closed until the trip command has been issued. Although differential protection was not used in this project, the 87 differential settings were left active to allow for utilization of the 87 channel communication via the fiber optic connection.
29
FIGURE 4-3 OUTPUT CONTACTS
30
FIGURE 4-4 LINE CURRENT DIFFERENTIAL SETTINGS
31
FIGURE 4-5 CLOSE & RECLOSE LOGIC
32
FIGURE 4-6 COMMUNICATIONS ASSISTED TRIPPING
33
FIGURE 4-7 87L TRANSMIT EQUATIONS
4.4
OPERATION
After wiring and system functionality has been verified, the sources can be applied and breakers closed. Special care was taken to ensure that the power resistors were not being overheated by the power dissipated through them. Fault conditions are then applied to the nodes specified on the single line construction drawing located in the appendix. The system is energized and fault switched on momentarily. If the relays are functioning as designed, they should immediately operate and open both breakers, which can be confirmed by the red breaker closed lights transition to two green
34
breaker open lights located on the circuit breaker boxes. In addition, the relays targets displayed on the front panel should light up when a fault condition is sensed. All wiring changes including moving the fault nodes to a different location should be performed with the system de-energized.
5.1
TEST PROCEDURES
The following are test procedures for verifying the circuit’s electrical and mechanical connections prior to energizing the circuit. Verifying the circuit’s electrical and mechanical connections are imperative to protect both the student and equipment from inadvertent damage.
POINT TO POINT AND MECHANICAL CHECK
The mechanical connections should be checked. With the circuit de-energized, gently pull on the wires and look for wire movement or displacement at the mechanical connection. If the wire connections move, further steps need to be taken to secure the connection. A point to point check using the construction drawings should be done to verify that all connections have been appropriately made. These tests should help eliminate wiring errors and decrease the likely hood a loose or misplaced wire.
WIRING CONTINUITY CHECK
With the load open-circuited and sources de-energized and open-circuited, a continuity / resistance check should be made from the source to the load using a standard multi-meter. All three phases from both sides of the line should be recorded and verified for consistency across all 6 of test points. If any of the test points show a low resistance, resistance difference of 25% or more, or infinite resistance the circuit should not be energized and all connections should be verified. Do not energize the circuit until resistances are equal and approximately 35 ohms from source to load.
35
5.1.1
BREAKER CONTROL VERIFICATION
With the three phase ac source de-energized, energize the DC control voltage and test manual open close breaker functionality prior to energizing the circuit. Verify that the trip and close commands can be issued from the serial terminal within the AcSELerator terminal and that the breaker responds accordingly.
5.1.2
MULTI-SOURCE SYSTEM
If utilizing multiple sources, care must be taken to ensure the systems are synchronized and have proper phasing prior to closing the breaker. Failing to properly synchronize and phase independent sources can result in equipment damage and injury. Procedures for synchronizing and phasing are beyond the scope of this senior project.
36
Internal line to line faults were selected for analysis because they result in the lowest fault current. By analyzing relay functionality at the lowest fault current magnitude possible, we can deduce that the relay will operate under more extreme fault current conditions.
6.1
INTERNAL LL
FIGURE 6-1 LINE TO LINE FAULT WEST
In Figure 6-1 and Figure 6-2 Phases A & B have been faulted. Figure 6-1 the system is faulted at the
West node as shown on the single line diagram. Figure 6-2 the system is faulted at the Center node
37
as shown on the single line diagram. As seen in the event diagram the fault causes increases in current and decreases in the voltages seen on those phases. The relay word bit M2P picks up indicating that a Zone 2 fault has been detected similarly M1P has not picked up indicating the fault impedance is higher and outside the zone 1 impedance circle. Shortly after the M2P word bit goes high, a permissive key is received shown as the COMM signal and the trip command issued. Both breakers opened successfully.
FIGURE 6-2 LINE TO LINE FAULT CENTER
When fault conditions external to the relays were applied, the relays blocked the trip and did not operate. Blocking trips for faults external to the line allow protection engineers to better coordinate protection and predict system operation after a fault condition has been cleared.
38
Permissive over-reaching transfer trip protection is a useful way to provide security to vital transmission line infrastructure. By overreaching the transmission line and requiring both relays to sense a fault internal to the line, false trips on faults external to the line become unlikely. The SEL-
311L offers a robust set of protection elements and fiber optic connections for high speed reliable communication between relays. For long distance transmission lines, POTT is a more secure alternative to phase distance and overcurrent alone. The multi-source and tapped load system forced me to think about how system operating and load conditions affect the perceived impedance at the relays. Careful consideration of system conditions need to be part of a protection analysis to avoid false trips and non-operation.
39
8.1
WBS, COST ESTIMATE, AND GANTT CHART
TABLE 8-1 WBS
1 SEL 311 T RANSMISSION L INE D IFFERENTIAL P ROTECTION P ROJECT T IME T IME T IME
1.1 Concept & Preliminary Design
1.1.1 Customer Requirements Development
1.1.1.1 Customer Requirements Elicitation
1.1.1.2
1.1.1.3
1.1.1.4
1.1.1.5
2.1.3
2.1.4
Requirements Document Development
Literature Research
Communications Architecture
Customer Review & Acceptance
1.3.1 Engineering Specifications Development
1.3.1.1 Specification Document Development
1.3.1.2
1.3.1.3
Customer Review & Acceptance
Specification Verification & Traceability
2.1 Detailed Design
2.1.1 Protection Scheme Design
2.1.1.1
2.1.1.2
Protection Specification &
Engineering
ETAP Model
2.1.2
2.1.1.3
2.1.1.4
2.1.1.5
Fault Analysis
Preliminary Test Plan
Development
Customer Review
Programming Design
2.1.2.1
2.1.2.2
Differential Trip Pickup
Protection Functionality
( A )
1.5
3
6
( M
2
4
8
1.5 2
3 4
3 4
0.75 1
4.5 6
) ( B )
4 2.25
8 4.5
16 9
4
8
8
2.25
4.5
4.5
2 1.125
12 6.75
15 20 40 22.5
4.5 6
1.5 2
2.25 3
2.1.2.3
2.1.2.4
Calibration & Parameters
PILOT Protection
2.1.1.5 Customer Review
Design Documentation Development
0.75 1
3.75 5
3.75 5
3.75 5
3.75 5
0.75 1
2.1.4.1
2.1.4.2
2.1.4.3
2.1.4.4
Wiring Diagrams
Communications Diagrams 2.25 3
Bill of Materials
Customer Review
Customer Design Final Review and
Acceptance
2.1.4.1 Document Review
2.25 3
3 4
0.75 1
0.75 1
12
4
6
2
6
6
8
2
2
6.75
2.25
3.375
1.125
10 5.625
10 5.625
10 5.625
10 5.625
2 1.125
3.375
3.375
4.5
1.125
1.125
40
2.1.4.2
2.1.4.3
3.1 Procurement
3.1.1
3.1.2
3.1.3
3.1.4
Quotation
Purchase
Program review
Engineering Review
Locate Available Equipment
Vendor Qualification
4.1 Construct
4.1.1 Initial Setup
4.1.2
4.1.3
4.1.4
4.1.5
4.1.6
5.1 Test
Wire
Programming
Communication Wiring
Communication Programming
Systems Integration
5.1.1
5.1.2
5.1.3
5.1.4
Finalize Test Plan Development
Test Plan Customer Acceptance
Fault Testing
Communications Testing
5.1.5 Factory Acceptance Test
6.1 Project Deliverable
6.1.1 Customer Delivery
7.1 Report Deliverables
7.1.1
7.1.2
7.1.3
7.1.4
Functional Specification
Lab Student Material
Lab Instructor Materials
Customer Review & Acceptance
* Time (a) x.75 multiplier
* Time (m) x1.0 multiplier
* Time (b) x2.0 multiplier
M ATERIAL C OST E STIMATE
3
4
Items Provided by Student
Item
# QTY: Item:
1
2
3
1
500' #14 Stranded
100 fork terminations
1
1
Misc. Electrical Parts
Misc. Admin
Unit
Cost Total Cost
$60.00 $180.00
$25.00 $25.00
$50.00 $50.00
$50.00 $50.00
Subtotal $305.00
0.75 1
0.75 1
1.5 2
1.5 2
1.5 2
3 4
3
6
6
1.5 2
5.25 7
6 8
4
8
8
4
4
4
8
2
2
4 2.25
14 7.875
16 9
8 4.5
16 9
16 9
1.125
1.125
2.25
2.25
2.25
4.5
2.25 3
0.75 1
6 8
3.75 5
1.5 2
0.75 1
4
2
6
2
3.375
1.125
16 9
10 5.625
2.25
1.125
3.75 5
6 8
6 8
1.5 2
10
16
16
4
5.625
9
9
2.25
Time Time Time Estimated Labor
(a) (m) (b) Hours
141 188 376 211.5
41
Sale
Tax 9.00%
6
7
8
9
Items Provided by Dr. Shaban
Item
# QTY: Item:
5 6 Transformers
2
1
2
4
Sale
Tax
SEL 311-L
SEL 2042
Fiber Optic Cables
Circuit Breaker Simulators
9.00%
Total Material Cost
Total Estimated Labor Hours
Labor Rate
Total Labor Cost
Tax
Total
$125
Tax
Total
$27.45
$332.45
Unit
Cost Total Cost
$50.00 $300.00
$5,000.00 $10,000.00
$2,840.00 $2,840.00
$20.00 $40.00
$200.00 $800.00
Subtotal $13,980.00
$1,258.20
$15,238.20
$15,570.65
211.50
Hourly
$26,375.00
Project estimates developed using previous project experience and a Work Breakdown Structure further identifying work tasks. The total cost estimates how much the project would cost if contracted to organizations for implementation and engineering for development of a differential impedance protection system using the SEL-311L.
42
43
TABLE 8-2 GANTT CHART
44
8.2
CONSTRUCTION DRAWING
PAGE INTENTIONALLY LEFT BLANK
SEL 311
FIBER PILOT COMMUNICATION
SCALE: NONE
SEL 311
C-1001
C-1001
C-1001-1 C-1001-2
WIRE / CABLE
NUMBER:
C-1001-1
C-1001-2
C-1003
C-1004
C-1005
C-1006
TERMINATION #1
LOCATION:
RELAY EAST CHANNEL X (TX)
RELAY EAST CHANNEL X (RX)
TERMINATION #2
LOCATION:
RELAY WEST CHANNEL X
(RX)
RELAY WEST CHANNEL X
(TX)
TYPE:
930 NM FIBER OPTIC
930 NM FIBER OPTIC
DESCRIPTION:
87 CHANNEL COMMUNICATIONS
87 CHANNEL COMMUNICATIONS
WALL OUTLET (120VAC) Z25, Z26, Z27 RELAY EAST
Z25, Z26, Z27 RELAY WEST
RELAY EAST SERIAL PORT 2
RELAY WEST SERIAL PORT 2
WALL OUTLET (120VAC)
PC SERIAL PORT
PC SERIAL PORT
POWER CORD 16/2
POWER CORD 16/2
DB-9 CONNECTOR
FM-FM
DB-9 CONNECTOR
FM-FM
RELAY POWER CONNECTION
RELAY POWER CONNECTION
SERIAL COMMUNICATIONS FOR RELAY
PROGRAMMING AND TERMINAL
ACCESS
SERIAL COMMUNICATIONS FOR RELAY
PROGRAMMING AND TERMINAL
ACCESS
NOTES:
NOTICE RX-TX ROLLOVER BETWEEN
RELAYS
NOTICE RX-TX ROLLOVER BETWEEN
RELAYS
ONLY CONNECTED WHEN RELAY IS
LOCALLY ACCESSED BY PERSONELL
ONLY CONNECTED WHEN RELAY IS
LOCALLY ACCESSED BY PERSONELL
C1005
C1001-2 C1001-1
C-1006
C1003
C-1004
SCALE: NONE
W-1121
W-1124
W-1122
W-1125
W-1123
W-1126
W-1127
W-1130
W-1128
W-1131
W-1129
W-1132
W-1133
W-1134
W-1135
W-1136
W-1137
W-1138
WIRE / CABLE
NUMBER:
W-1121
W-1122
W-1123
W-1124
W-1125
W-1126
W-1127
W-1128
W-1129
W-1130
W-1131
W-1132
W-1133
W-1134
W-1135
W-1136
W-1137
W-1138
WIRE / CABLE SCHEDULE
TERMINATION #1 LOCATION: TERMINATION #2 LOCATION:
SOURCE #1 IMPEDANCE PHASE A
SOURCE #1 IMPEDANCE PHASE B
SOURCE #1 IMPEDANCE PHASE C
EAST LINE RELAY CURRENT PHASE A
EAST LINE RELAY CURRENT PHASE B
EAST LINE RELAY CURRENT PHASE C
SOURCE #2 IMPEDANCE PHASE A
SOURCE #2 IMPEDANCE PHASE B
SOURCE #2 IMPEDANCE PHASE C
WEST LINE RELAY CURRENT PHASE A
WEST LINE RELAY CURRENT PHASE B
WEST LINE RELAY CURRENT PHASE C
SOURCE #1 PHASE A
SOURCE #1 PHASE B
SOURCE #1 PHASE C
SOURCE #2 PHASE A
SOURCE #2 PHASE B
SOURCE #2 PHASE C
EAST LINE RELAY CURRENT PHASE A DOTTED
EAST LINE RELAY CURRENT PHASE B DOTTED
EAST LINE RELAY CURRENT PHASE C DOTTED
EAST LINE INDUCTANCE PHASE A
EAST LINE INDUCTANCE PHASE B
EAST LINE INDUCTANCE PHASE C
WEST LINE RELAY CURRENT PHASE A DOTTED
WEST LINE RELAY CURRENT PHASE B DOTTED
WEST LINE RELAY CURRENT PHASE C DOTTED
WEST LINE INDUCTANCE PHASE A
WEST LINE INDUCTANCE PHASE B
WEST LINE INDUCTANCE PHASE C
EAST LINE RELAY VOLTAGE PHASE A
EAST LINE RELAY VOLTAGE PHASE B
EAST LINE RELAY VOLTAGE PHASE C
WEST LINE RELAY VOLTAGE PHASE A
WEST LINE RELAY VOLTAGE PHASE B
WEST LINE RELAY VOLTAGE PHASE C
TYPE:
#14 THHN (BLK)
#14 THHN (RED)
#14 THHN (BLUE)
#14 THHN (BLK)
#14 THHN (RED)
#14 THHN (BLUE)
#14 THHN (BLK)
#14 THHN (RED)
#14 THHN (BLUE)
#14 THHN (BLK)
#14 THHN (RED)
#14 THHN (BLUE)
#14 THHN (BLK)
#14 THHN (RED)
#14 THHN (BLUE)
#14 THHN (BLK)
#14 THHN (RED)
#14 THHN (BLUE)
SCALE: NONE
W-1149
W-1150
W-1151
W-1152
W-1149
W-1150
W-1151
W-1152
125 VDC SOURCE
LAB BENCH
208V 3 PHASE SOURCE
LAB BENCH
LOAD SIDE BREAKER
REFER TO DRAWING
POTT_0151-05.DWG
W-1145
W-1146
W-1101
W-1102
W-1103
W-1107
W-1108
W-1109
W-1153
W-1154
W-1155
W-1156
W-1153
W-1154
W-1155
W-1156
125 VDC SOURCE
LAB BENCH
208V 3 PHASE SOURCE
LAB BENCH
LOAD SIDE BREAKER
REFER TO DRAWING
POTT_0151-05.DWG
W-1147
W-1148
W-1104
W-1105
W-1106
W-1110
W-1111
W-1112
WIRE / CABLE SCHEDULE
TERMINATION #2 LOCATION: TYPE:
CB EAST LINE PHASE A #14 THHN (BLK)
CB EAST LINE PHASE B #14 THHN (RED)
CB EAST LINE PHASE C #14 THHN (BLUE)
CB WEST LINE PHASE A #14 THHN (BLK)
CB WEST LINE PHASE B #14 THHN (RED)
CB WEST LINE PHASE C #14 THHN (BLUE)
EAST LINE IMPEDANCE PHASE A #14 THHN (BLK)
EAST LINE IMPEDANCE PHASE B #14 THHN (RED)
EAST LINE IMPEDANCE PHASE C #14 THHN (BLUE)
WEST LINE IMPEDANCE PHASE A #14 THHN (BLK)
WEST LINE IMPEDANCE PHASE B #14 THHN (RED)
WEST LINE IMPEDANCE PHASE C #14 THHN (BLUE)
EAST LINE CB +125VDC #14 THHN (BLK)
EAST LINE CB 125DC COMMON #14 THHN (WHT)
WEST LINE CB +125VDC #14 THHN (BLK)
WEST LINE CB 125DC COMMON
EAST LINE CB OPEN (CB-1001)
EAST LINE CB OPEN (CB-1002)
EAST LINE CB TRIP (CB-1003)
#14 THHN (WHT)
#14 THHN (BLUE)
#14 THHN (BLUE)
#14 THHN (RED)
EAST LINE CB TRIP (CB-1004)
WEST LINE CB OPEN (CB-1001)
WEST LINE CB OPEN (CB-1002)
WEST LINE CB TRIP (CB-1003)
WEST LINE CB TRIP (CB-1004)
#14 THHN (RED)
#14 THHN (BLUE)
#14 THHN (BLUE)
#14 THHN (RED)
#14 THHN (RED)
DESCRIPTION:
SOURCE TO LINE SIDE CB CONNECTION
SOURCE TO LINE SIDE CB CONNECTION
SOURCE TO LINE SIDE CB CONNECTION
SOURCE TO LINE SIDE CB CONNECTION
SOURCE TO LINE SIDE CB CONNECTION
SOURCE TO LINE SIDE CB CONNECTION
LOAD SIDE CB TO LINE IMPEDANCE
LOAD SIDE CB TO LINE IMPEDANCE
LOAD SIDE CB TO LINE IMPEDANCE
LOAD SIDE CB TO LINE IMPEDANCE
LOAD SIDE CB TO LINE IMPEDANCE
LOAD SIDE CB TO LINE IMPEDANCE
NOTES:
WIRE / CABLE NUMBER: TERMINATION #1 LOCATION:
W-1101 SOURCE #1 PHASE A
W-1102 SOURCE #1PHASE B
W-1111
W-1112
W-1145
W-1146
W-1147
W-1148
W-1149
W-1150
W-1151
W-1103
W-1104
W-1105
W-1106
W-1107
W-1108
W-1109
W-1110
W-1152
W-1153
W-1154
W-1155
W-1156
SOURCE #1 PHASE C
SOURCE #2 PHASE A
SOURCE #2PHASE B
SOURCE #2 PHASE C
CB EAST LOAD PHASE A
CB EAST LOAD PHASE B
CB EAST LOAD PHASE C
CB WEST LOAD PHASE A
CB WEST LOAD PHASE B
CB WEST LOAD PHASE C
125VDC SOURCE
125VDC COMMON SOURCE
125VDC SOURCE
125VDC COMMON SOURCE
EAST LINE RELAY OUT101-1
EAST LINE RELAY OUT101-2
EAST LINE RELAY OUT102-1
EAST LINE RELAY OUT102-2
WEST LINE RELAY OUT101-1
WEST LINE RELAY OUT101-2
WEST LINE RELAY OUT102-1
WEST LINE RELAY OUT102-2
SCALE: NONE
SCALE: NONE
WIRE / CABLE
NUMBER:
W-1101
W-1102
W-1119
W-1120
W-1121
W-1122
W-1123
W-1124
W-1125
W-1126
W-1127
W-1128
W-1129
W-1130
W-1131
W-1132
W-1111
W-1112
W-1113
W-1114
W-1115
W-1116
W-1117
W-1118
W-1103
W-1104
W-1105
W-1106
W-1107
W-1108
W-1109
W-1110
TERMINATION #1 LOCATION:
SOURCE #1 PHASE A
SOURCE #1PHASE B
SOURCE #1 PHASE C
SOURCE #2 PHASE A
SOURCE #2PHASE B
SOURCE #2 PHASE C
CB EAST LOAD PHASE A
CB EAST LOAD PHASE B
CB EAST LOAD PHASE C
CB WEST LOAD PHASE A
CB WEST LOAD PHASE B
CB WEST LOAD PHASE C
EAST LINE IMPEDANCE PHASE A
EAST LINE IMPEDANCE PHASE B
EAST LINE IMPEDANCE PHASE C
WEST LINE IMPEDANCE PHASE A
WEST LINE IMPEDANCE PHASE B
WEST LINE IMPEDANCE PHASE C
LOAD PHASE A
LOAD PHASE B
SOURCE #1 IMPEDANCE PHASE A
SOURCE #1 IMPEDANCE PHASE B
SOURCE #1 IMPEDANCE PHASE C
EAST LINE RELAY CURRENT PHASE A
EAST LINE RELAY CURRENT PHASE B
EAST LINE RELAY CURRENT PHASE C
SOURCE #2 IMPEDANCE PHASE A
SOURCE #2 IMPEDANCE PHASE B
SOURCE #2 IMPEDANCE PHASE C
WEST LINE RELAY CURRENT PHASE A
WEST LINE RELAY CURRENT PHASE B
WEST LINE RELAY CURRENT PHASE C
WIRE / CABLE SCHEDULE
TERMINATION #2 LOCATION:
CB EAST LINE PHASE A
CB EAST LINE PHASE B
CB EAST LINE PHASE C
CB WEST LINE PHASE A
CB WEST LINE PHASE B
CB WEST LINE PHASE C
EAST LINE IMPEDANCE PHASE A
EAST LINE IMPEDANCE PHASE B
EAST LINE IMPEDANCE PHASE C
WEST LINE IMPEDANCE PHASE A
WEST LINE IMPEDANCE PHASE B
WEST LINE IMPEDANCE PHASE C
LOAD IMPEDANCE PHASE A
LOAD IMPEDANCE PHASE B
LOAD IMPEDANCE PHASE C
LOAD IMPEDANCE PHASE A
LOAD IMPEDANCE PHASE B
LOAD IMPEDANCE PHASE C
LOAD PHASE B
LOAD PHASE C
EAST LINE RELAY CURRENT PHASE A DOTTED
EAST LINE RELAY CURRENT PHASE B DOTTED
EAST LINE RELAY CURRENT PHASE C DOTTED
EAST LINE INDUCTANCE PHASE A
EAST LINE INDUCTANCE PHASE B
EAST LINE INDUCTANCE PHASE C
WEST LINE RELAY CURRENT PHASE A DOTTED
WEST LINE RELAY CURRENT PHASE B DOTTED
WEST LINE RELAY CURRENT PHASE C DOTTED
WEST LINE INDUCTANCE PHASE A
WEST LINE INDUCTANCE PHASE B
WEST LINE INDUCTANCE PHASE C
TYPE:
#14 THHN (BLK)
#14 THHN (RED)
#14 THHN (BLUE)
#14 THHN (BLK)
#14 THHN (RED)
#14 THHN (BLUE)
#14 THHN (BLK)
#14 THHN (RED)
#14 THHN (BLUE)
#14 THHN (BLK)
#14 THHN (RED)
#14 THHN (BLUE)
#14 THHN (BLK)
#14 THHN (RED)
#14 THHN (BLUE)
#14 THHN (BLK)
#14 THHN (RED)
#14 THHN (BLUE)
#14 THHN (BLK)
#14 THHN (BLK)
#14 THHN (BLK)
#14 THHN (RED)
#14 THHN (BLUE)
#14 THHN (BLK)
#14 THHN (RED)
#14 THHN (BLUE)
#14 THHN (BLK)
#14 THHN (RED)
#14 THHN (BLUE)
#14 THHN (BLK)
#14 THHN (RED)
#14 THHN (BLUE)
DESCRIPTION:
SOURCE TO LINE SIDE CB CONNECTION
SOURCE TO LINE SIDE CB CONNECTION
SOURCE TO LINE SIDE CB CONNECTION
SOURCE TO LINE SIDE CB CONNECTION
SOURCE TO LINE SIDE CB CONNECTION
SOURCE TO LINE SIDE CB CONNECTION
LOAD SIDE CB TO LINE IMPEDANCE
LOAD SIDE CB TO LINE IMPEDANCE
LOAD SIDE CB TO LINE IMPEDANCE
LOAD SIDE CB TO LINE IMPEDANCE
LOAD SIDE CB TO LINE IMPEDANCE
LOAD SIDE CB TO LINE IMPEDANCE
LINE IMPEDANCE TO LOAD
LINE IMPEDANCE TO LOAD
LINE IMPEDANCE TO LOAD
LINE IMPEDANCE TO LOAD
LINE IMPEDANCE TO LOAD
LINE IMPEDANCE TO LOAD
WYE LOAD CONNECTION
WYE LOAD CONNECTION
NOTES:
DOTTED TERMINAL
DOTTED TERMINAL
DOTTED TERMINAL
DOTTED TERMINAL
DOTTED TERMINAL
DOTTED TERMINAL
REFER TO DRAWING
POTT_0151-03.DWG
REFER TO DRAWING
POTT_0151-03.DWG
W-1116
CIRCUIT BREAKER
REFER TO DRAWING
POTT_0151-04.DWG
W-1113 W-1120 REFER TO DRAWING
POTT_0151-03.DWG
CIRCUIT BREAKER
REFER TO DRAWING
POTT_0151-04.DWG
REFER TO DRAWING
POTT_0151-03.DWG
W-1117
W-1110
W-1111
W-1112
W-1104
W-1105
W-1106
REFER TO DRAWING
POTT_0151-03.DWG
REFER TO DRAWING
POTT_0151-03.DWG
W-1101
W-1102
W-1103
W-1107
W-1108
W-1109
W-1114 REFER TO DRAWING
POTT_0151-03.DWG
REFER TO DRAWING
POTT_0151-03.DWG
W-1118
W-1119 W-1115
SCALE: NONE
QTY:
6
3
2
50'
AR
MANUFACTURER:
LAB EQUIPMENT
LAB EQUIPMENT
LAB EQUIPMENT
SOUTHWIRE
IDEAL
BOM
PRODUCT:
TWIN RESISTOR & INDUCTOR LOAD
SINGLE RESISTOR & INDUCTOR LOAD
CIRCUIT BREAKER / FAULT BOXES
#14 THHN WIRE BLK, RED, BLUE
#14-#24 RED NARROW FORK TERMINAL
DESCRIPTION:
SEL OUTPUT NORMALLY OPEN (CLOSE CB)
SEL OUTPUT NORMALLY OPEN (CLOSE CB)
SEL OUTPUT NORMALLY CLOSED (TRIP CB)
SEL OUTPUT NORMALLY CLOSED (TRIP CB)
+125VDC STATION BATTERY
0VDC (COMMON TERMINAL) STATION BATTERY
CB LINE PHASE C
CB LINE PHASE B
CB LINE PHASE A
CB LOAD PHASE A
CB LOAD PHASE B
CB LOAD PHASE C
FAULT SW. LINE PHASE C
FAULT SW. LINE PHASE B
FAULT SW. LINE PHASE A
FAULT SW. LOAD PHASE A
FAULT SW. LOAD PHASE B
FAULT SW. LOAD PHASE C
CB-1001
CB-1002
CB-1003
CB-1004
CB-1005
CB-1006
CB-1007
CB-1008
CB-1009
CB-1010
CB-1011
CB-1012
CB-1013
CB-1014
CB-1015
CB-1016
CB-1017
CB-1018
SCALE: NONE
CIRCUIT BREAKER INSTRUCTIONS:
1.
From source, connect phases to 'CB Line' connections
(CB-1007, CB-1008, and CB-1009.)
2.
3.
Connect the protected load to 'CB Load' connections (CB-1010,
CB-1011, and CB-1012.)
Connect a 125VDC source to 'Station Battery' terminals
(CB-1005, CB-1006.)
4.
5.
Connect protective relay output contacts (ex. SEL-311L
OUT101 and OUT102) to Normally Open (NO) output contacts for 'CLOSE CB' (CB-1001, CB-1002) and Normally Closed
(NC) output contacts for 'TRIP CB' (CB-1003, CB-1004.)
Check Connections.
6.
7.
FAULT SIMULATOR CONFIGURATION:
1.
De-energize equipment.
2.
Energize 125VDC control circuit.
Test Breaker Manual Trip / Close functionality.
3.
4.
Connect 'Fault SW. Line' terminals to circuit nodes that are to be faulted using banana leads.
Connect 'Fault SW. Load' terminals together in desired fault configurations (SLG, DLG, LL, LLL) using short leads. Example:
CB-1016 connected to CB-1017 for Line-to-Line fault across
Phase A and B.
Check Connections. Verify Fault Switch in Normal Position
(OFF). Energize Circuit. Toggle Fault Switch.
8.3
CIRCUIT BREAKER OPERATION
CIRCUIT BREAKER CONFIGURATION:
1.
From source, connect phases to ‘CB Line’ connections (CB-1007, CB-1008, and CB-1009.)
2.
Connect the protected load to ‘CB Load’ connections (CB-1010, CB-1011, and CB-1012.)
3.
Connect a 125VDC source to ‘Station Battery’ terminals (CB-1005, CB-1006.)
4.
Connect protective relay output contacts (ex. SEL-311L OUT101 and OUT102) to Normally Open (NO) output contacts for ‘CLOSE CB’
(CB-1001, CB-1002) and Normally Closed (NC) output contacts for ‘TRIP CB’ (CB-1003, CB-1004.)
5.
Check Connections.
6.
Energize 125VDC control circuit.
7.
Test Breaker Manual Trip / Close functionality.
FAULT SIMULATOR CONFIGURATION:
1.
De-energize equipment.
2.
Connect ‘Fault SW. Line’ terminals to circuit nodes that are to be faulted using banana leads.
3.
Connect ‘Fault SW. Load’ terminals together in desired fault configurations (SLG, DLG, LL, LLL) using short leads. Example: CB-1016 connected to CB-1017 for Line-to-Line fault across Phase A and B.
4.
Check Connections. Verify Fault Switch in Normal Position (OFF). Energize Circuit. Toggle Fault Switch.
47 | P a g e
Setting Range Value
Group : 1
RID Range = ASCII string with a maximum length of SEL-311
30.
TID
CTR
Range = ASCII string with a maximum length of
30.
EXAMPLE: BUS B,
BREAKER 3
Range = 1 to 6000 1
APP
EHST
EHSDT
T
Select: 87L, 87L21, 87L21P, 87LSP, 311L
EADVS Select: Y, N
E87L Select: 2, 3, 3R, N
Select: 1-6, N
Select: Y, N
N
N
311L
N
2
EDD
ETAP
Select: Y, N
Select: Y, N
EOCTL Select: Y, N
PCHAN Select: X, Y
EHSC Select: Y, N
Y
N
N
X
N
1 CTR_X Range = 1 to 6000
TA_X
RA_X
Select: 1-16
Select: 1-16
CTR_Y Range = 1 to 6000
TA_Y Select: 1-16
RA_Y
87LPP
87L2P
87LGP
CTALR
M
Select: 1-16
Range = 1.00 to 10.00, OFF
Range = 0.50 to 5.00, OFF
Range = 0.50 to 5.00, OFF
Range = 0.50 to 10.00
87LR Range = 2.0 to 8.0
87LANG Range = 90 to 270
1
2
200
3
4
6.00
0.50
OFF
0.50
6.0
195
ETP
T51PP
Select: Y, N
Range = 0.50 to 16.00, OFF
N
OFF
T51PC Select: U1, U2, U3, U4, U5, C1, C2, C3, C4, C5 U3
T51PTD
T51PRS
Range = 0.50 to 15.00
Select: Y, N
2.00
N
T50PP Range = 0.50 to 100.00, OFF
T50PD Range = 0.00 to 16000.00, OFF
ETG Select: Y, N
T51GP Range = 0.50 to 16.00, OFF
OFF
0.00
N
0.75
<Filter is Empty>
1 Of 16 5/20/2015 2:51 PM
Setting
T51GC
Range
Select: U1, U2, U3, U4, U5, C1, C2, C3, C4, C5
Value
U3
T51GTD Range = 0.50 to 15.00
2.00
T51GRS Select: Y, N Y
T50GP
T50GD
ETQ
Range = 0.50 to 100.00, OFF
Range = 0.00 to 16000.00, OFF
Select: Y, N
OFF
0.00
N
T51QP Range = 0.50 to 16.00, OFF
T51QC Select: U1, U2, U3, U4, U5, C1, C2, C3, C4, C5
2.20
U3
T51QT
D
Range = 0.50 to 15.00
T51QRS Select: Y, N
T50QP Range = 0.50 to 100.00, OFF
T50QD Range = 0.00 to 16000.00, OFF
CTRP Range = 1 to 6000
PTR Range = 1.00 to 10000.00
PTRS Range = 1.00 to 10000.00
Z1MAG Range = 0.05 to 255.00
Z1ANG Range = 5.00 to 90.00
Z0MAG Range = 0.05 to 255.00
Z0ANG Range = 5.00 to 90.00
LL Range = 0.10 to 999.00
EFLOC Select: Y, N
E21P Select: N, 1-4, 1C-4C
ECCVT Select: Y, N
Z1P Range = 0.05 to 64.00, OFF
Z2P
Z3P
Z4P
Range = 0.05 to 64.00, OFF
Range = 0.05 to 64.00, OFF
Range = 0.05 to 64.00, OFF
50PP1
50PP2
Range = 0.50 to 170.00
Range = 0.50 to 170.00
50PP3 Range = 0.50 to 170.00
50PP4 Range = 0.50 to 170.00
E21MG Select: N, 1-4
Z1MG
Z2MG
Z3MG
Range = 0.05 to 64.00, OFF
Range = 0.05 to 64.00, OFF
Range = 0.05 to 64.00, OFF
Z4MG Range = 0.05 to 64.00, OFF
E21XG Select: N, 1-4
2.00
N
1.87
OFF
0.50
0.50
0.50
0.50
3
40.00
60.00
60.00
OFF
N
78.00
75.00
100.00
Y
2
N
40.00
60.00
OFF
0.00
1
1.00
1.00
78.00
75.00
<Filter is Empty>
2 Of 16 5/20/2015 2:51 PM
Setting
XG1
XG2
XG3
XG4
RG1
RG2
RG3
Range
Range = 0.05 to 64.00, OFF
Range = 0.05 to 64.00, OFF
Range = 0.05 to 64.00, OFF
Range = 0.05 to 64.00, OFF
Range = 0.05 to 50.00
Range = 0.05 to 50.00
Range = 0.05 to 50.00
RG4 Range = 0.05 to 50.00
XGPOL Select: I2, IG
TANG
50L1
50L2
Range = -45.0 to 45.0
Range = 0.50 to 100.00
Range = 0.50 to 100.00
50L3
50L4
Range = 0.50 to 100.00
Range = 0.50 to 100.00
50GZ1 Range = 0.50 to 100.00
50GZ2 Range = 0.50 to 100.00
50GZ3 Range = 0.50 to 100.00
50GZ4 Range = 0.50 to 100.00
k0M1 Range = 0.000 to 6.000
k0A1 k0M k0A
Z1PD
Z2PD
Z3PD
Z4PD
Z1GD
Z2GD
Range = -180.00 to 180.00
Range = 0.000 to 6.000
Range = -180.00 to 180.00
Range = 0.00 to 16000.00, OFF
Range = 0.00 to 16000.00, OFF
Range = 0.00 to 16000.00, OFF
Range = 0.00 to 16000.00, OFF
Range = 0.00 to 16000.00, OFF
Range = 0.00 to 16000.00, OFF
Z3GD
Z4GD
Z1D
Z2D
Z3D
Z4D
E50P
Range = 0.00 to 16000.00, OFF
Range = 0.00 to 16000.00, OFF
Range = 0.00 to 16000.00, OFF
Range = 0.00 to 16000.00, OFF
Range = 0.00 to 16000.00, OFF
Range = 0.00 to 16000.00, OFF
Select: N, 1-3
50P1P Range = 0.25 to 100.00, OFF
50P2P
50P3P
Range = 0.25 to 100.00, OFF
Range = 0.25 to 100.00, OFF
67P1D Range = 0.00 to 16000.00
67P2D Range = 0.00 to 16000.00
67P3D Range = 0.00 to 16000.00
<Filter is Empty>
20.00
OFF
OFF
OFF
20.00
OFF
OFF
OFF
0.50
0.50
0.50
0.726
-3.69
0.726
-3.69
OFF
OFF
OFF
OFF
1
3.00
OFF
OFF
0.00
0.00
0.00
0.05
I2
-3.0
0.50
0.50
0.50
0.50
0.50
Value
6.24
9.36
1.87
OFF
2.50
5.00
6.00
3 Of 16 5/20/2015 2:51 PM
Setting
E50G
Range
Select: N, 1-4
50G1P Range = 0.25 to 100.00, OFF
50G2P Range = 0.25 to 100.00, OFF
50G3P Range = 0.25 to 100.00, OFF
50G4P Range = 0.25 to 100.00, OFF
67G1D Range = 0.00 to 16000.00
67G2D Range = 0.00 to 16000.00
67G3D Range = 0.00 to 16000.00
67G4D Range = 0.00 to 16000.00
E50Q Select: N, 1-4
50Q1P Range = 0.25 to 100.00, OFF
50Q2P Range = 0.25 to 100.00, OFF
50Q3P Range = 0.25 to 100.00, OFF
50Q4P Range = 0.25 to 100.00, OFF
67Q1D Range = 0.00 to 16000.00
67Q2D Range = 0.00 to 16000.00
67Q3D Range = 0.00 to 16000.00
67Q4D Range = 0.00 to 16000.00
E51P Select: Y, N
51PP Range = 0.25 to 16.00, OFF
51PC Select: U1-U5, C1-C5
51PTD Range = 0.50 to 15.00
51PRS Select: Y, N
E51G
51GP
Select: Y, N
Range = 0.25 to 16.00, OFF
51GC Select: U1-U5, C1-C5
51GTD Range = 0.50 to 15.00
51GRS Select: Y, N
E51Q
51QP
51QC
Select: Y, N
Range = 0.25 to 16.00, OFF
Select: U1-U5, C1-C5
51QTD Range = 0.50 to 15.00
51QRS Select: Y, N
EOOS Select: Y, N
OOSB1 Select: Y, N
OOSB2 Select: Y, N
OOSB3 Select: Y, N
OOSB4 Select: Y, N
OSBD Range = 0.50 to 8000.00
EOOST Select: N, I, O
OSTD Range = 0.50 to 8000.00
<Filter is Empty>
Y
0.75
U3
2.00
Y
Y
2.20
U3
0.00
0.00
0.00
N
OFF
U3
2.00
N
N
N
2.00
N
N
N
N
2.00
N
0.50
0.00
0.00
N
OFF
OFF
OFF
OFF
0.00
Value
N
OFF
OFF
OFF
OFF
0.00
0.00
4 Of 16 5/20/2015 2:51 PM
Setting
X1T6
X1T5
R1R6
R1R5
X1B6
X1B5
R1L6
Range
Range = 0.05 to 96.00
Range = 0.05 to 96.00
Range = 0.05 to 70.00
Range = 0.05 to 70.00
Range = -96.00 to -0.05
Range = -96.00 to -0.05
Range = -70.00 to -0.05
R1L5 Range = -70.00 to -0.05
50ABCP Range = 1.00 to 100.00
UBD Range = 0.50 to 120.00
UBOSBF Range = 1.00 to 10.00
ZLR
PLAF
NLAF
PLAR
NLAR
ELOAD Select: Y, N
ZLF Range = 0.05 to 64.00
Range = 0.05 to 64.00
Range = -90.00 to 90.00
Range = -90.00 to 90.00
Range = 90.00 to 270.00
Range = 90.00 to 270.00
E32
ELOP
Select: Y, AUTO
Select: Y, Y1, N
EBBPT Select: Y, N
DIR3
DIR4
Select: F, R
Select: F, R
ORDER Select: I, Q, V, OFF
Z2F Range = -64.00 to 64.00
Z2R Range = -64.00 to 64.00
50QFP Range = 0.25 to 5.00
50QRP Range = 0.25 to 5.00
a2 Range = 0.02 to 0.50
k2
50GFP
Range = 0.10 to 1.20
Range = 0.25 to 5.00
50GRP Range = 0.25 to 5.00
a0 Range = 0.02 to 0.50
Z0F Range = -64.00 to 64.00
Z0R Range = -64.00 to 64.00
EVOLT Select: Y, N
27P Range = 0.00 to 150.00, OFF
59P Range = 0.00 to 150.00, OFF
59N1P Range = 0.00 to 150.00, OFF
59N2P Range = 0.00 to 150.00, OFF
<Filter is Empty>
Value
96.00
90.00
70.00
65.00
-96.00
-90.00
-70.00
-65.00
1.00
0.50
4.00
39.10
N
OFF
OFF
OFF
OFF
0.50
0.25
0.10
0.20
0.50
0.25
0.10
39.00
AUTO
Y
N
R
F
QVI
39.00
39.10
Y
9.22
9.22
30.00
-30.00
150.00
210.00
5 Of 16 5/20/2015 2:51 PM
Setting
59QP
Range
Range = 0.00 to 100.00, OFF
59V1P Range = 0.00 to 150.00, OFF
27SP Range = 0.00 to 150.00, OFF
59SP
27PP
59PP
E25
Range = 0.00 to 150.00, OFF
Range = 0.00 to 260.00, OFF
Range = 0.00 to 260.00, OFF
Select: Y, N
25VLO Range = 0.00 to 150.00
25VHI Range = 0.00 to 150.00
25SF Range = 0.005 to 0.500
25ANG1 Range = 0.00 to 80.00
25ANG2 Range = 0.00 to 80.00
SYNCP Select: VA, VB, VC, VAB, VBC, VCA
TCLOSD Range = 1.00 to 60.00, OFF
E81 Select: N, 1-6
27B81P Range = 20.00 to 150.00
81D1P Range = 41.00 to 65.00, OFF
81D1D Range = 2.00 to 16000.00
81D2P Range = 41.00 to 65.00, OFF
81D2D Range = 2.00 to 16000.00
81D3P Range = 41.00 to 65.00, OFF
81D3D Range = 2.00 to 16000.00
81D4P Range = 41.00 to 65.00, OFF
81D4D Range = 2.00 to 16000.00
81D5P Range = 41.00 to 65.00, OFF
81D5D Range = 2.00 to 16000.00
81D6P Range = 41.00 to 65.00, OFF
81D6D Range = 2.00 to 16000.00
E79 Select: N, 1-4
79OI1
79OI2
Range = 0.00 to 999999.00
Range = 0.00 to 999999.00
79OI3 Range = 0.00 to 999999.00
79OI4 Range = 0.00 to 999999.00
79RSD Range = 0.00 to 999999.00
79RSLD Range = 0.00 to 999999.00
79CLSD Range = 0.00 to 999999.00, OFF
ESOTF Select: Y, N
<Filter is Empty>
40.00
VA
3.00
N
20.00
Value
OFF
OFF
OFF
OFF
OFF
OFF
N
60.00
75.00
0.042
25.00
OFF
60.00
OFF
60.00
N
0.00
0.00
0.00
OFF
60.00
OFF
60.00
OFF
60.00
OFF
60.00
0.00
1800.00
300.00
OFF
Y
6 Of 16 5/20/2015 2:51 PM
Setting
CLOEN
D
Range
Range = 0.00 to 16000.00, OFF
52AEND Range = 0.00 to 16000.00, OFF
SOTFD Range = 0.50 to 16000.00
ECOMM Select: N, POTT, DCUB1, DCUB2, DCB
Z3RBD Range = 0.00 to 16000.00
EBLKD Range = 0.00 to 16000.00, OFF
ETDPU Range = 0.00 to 16000.00, OFF
EDURD Range = 0.00 to 16000.00
EWFC Select: Y, N
27PPW Range = 0.0 to 260.0
59NW Range = 0.0 to 150.0
GARD1
D
Range = 0.00 to 16000.00
UBDUR
D
Range = 0.25 to 16000.00
UBEND Range = 0.00 to 16000.00
Z3XPU Range = 0.00 to 16000.00
Z3XD
BTXD
21SD
Range = 0.00 to 16000.00
Range = 0.00 to 16000.00
Range = 0.00 to 60.00
67SD
EMBA
Range = 0.00 to 60.00
Select: Y, N
RXIDA Range = 1 to 4
TXIDA Range = 1 to 4
EMBB Select: Y, N
RXIDB Range = 1 to 4
TXIDB Range = 1 to 4
EZ1EXT Select: Y, N
Z1EXTD Range = 0.00 to 16000.00
Z1EXTM Range = 1.00 to 4.00
EDEM
DMTC
Select: THM, ROL
Select: 5, 10, 15, 30, 60
PDEMP Range = 0.50 to 16.00, OFF
GDEMP Range = 0.50 to 16.00, OFF
QDEMP Range = 0.50 to 16.00, OFF
TDURD Range = 2.00 to 16000.00
TOPD Range = 2.00 to 8000.00
CFD Range = 0.00 to 16000.00, OFF
<Filter is Empty>
1
2
N
1
2
1.00
N
N
0.50
1.00
5.00
0.00
1.00
180.00
1.30
5.00
10.00
2.00
4.00
N
0.0
150.0
10.00
9.00
THM
60
OFF
OFF
OFF
9.00
2.00
60.00
Value
OFF
10.00
30.00
POTT
7 Of 16 5/20/2015 2:51 PM
Setting
3POD
OPO
27PO
50LP
ELAT
EDP
ESV
Range
Range = 0.00 to 60.00
Select: 27, 52
Range = 0.00 to 150.00
Range = 0.25 to 100.00, OFF
Select: N, 1-16
Select: N, 1-16
Select: N, 1-16
SV1PU Range = 0.00 to 999999.00
SV2PU Range = 0.00 to 999999.00
SV3PU Range = 0.00 to 999999.00
SV4PU Range = 0.00 to 999999.00
SV5PU Range = 0.00 to 999999.00
SV6PU Range = 0.00 to 999999.00
SV7PU Range = 0.00 to 16000.00
SV8PU Range = 0.00 to 16000.00
SV9PU Range = 0.00 to 16000.00
SV10PU Range = 0.00 to 16000.00
SV11PU Range = 0.00 to 16000.00
SV12PU Range = 0.00 to 16000.00
SV13PU Range = 0.00 to 16000.00
SV14PU Range = 0.00 to 16000.00
SV15PU Range = 0.00 to 16000.00
SV16PU Range = 0.00 to 16000.00
SV1DO Range = 0.00 to 999999.00
SV2DO Range = 0.00 to 999999.00
SV3DO Range = 0.00 to 999999.00
SV4DO Range = 0.00 to 999999.00
SV5DO Range = 0.00 to 999999.00
SV6DO Range = 0.00 to 999999.00
SV7DO Range = 0.00 to 16000.00
SV8DO Range = 0.00 to 16000.00
SV9DO Range = 0.00 to 16000.00
SV10D
O
Range = 0.00 to 16000.00
SV11D
O
Range = 0.00 to 16000.00
SV12D
O
Range = 0.00 to 16000.00
<Filter is Empty>
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
16
16
N
Value
0.50
52
40.00
0.25
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
8 Of 16 5/20/2015 2:51 PM
Setting
SV13D
O
Range
Range = 0.00 to 16000.00
SV14D
O
Range = 0.00 to 16000.00
SV15D
O
Range = 0.00 to 16000.00
SV16D
O
Range = 0.00 to 16000.00
Value
0.00
0.00
0.00
0.00
Group : 2
Group : 3
Group : 4
Group : 5
Group : 6
Group : DNPA
Group : DNPB
Group : G
Group : L1
TR Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
87CHFAIL*(M1P+M
2P+Z1G+Z2G)
TRCOM
M
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
M2P+Z2G
TRSOTF Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
DTT Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
E3PT
ULTR
PT1
PT2
LOG1
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
!(50L+51G)
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
R1X
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
LOG2
BT
52A
52AA
52AB
52AC
CL
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
IN101
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
CC
<Filter is Empty>
9 Of 16 5/20/2015 2:51 PM
Setting
ULCL
79RI
79RIS
Range
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
Value
TRIP+TRIP87
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
79DTL Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
79DLS Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
79SKP Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
79STL Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
79BRS Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
79SEQ Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
79CLS Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
SET1 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
SET2
SET3
SET4
SET5
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
SET6
SET7
SET8
SET9
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
SET10 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
SET11 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
SET12 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
SET13 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
SET14 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
SET15 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
<Filter is Empty>
10 Of 16 5/20/2015 2:51 PM
Setting
SET16
RST1
Range
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
Value
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
RST2 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
RST3
RST4
RST5
RST6
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
RST7
RST8
RST9
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
RST10 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
RST11 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
RST12 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
RST13 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
RST14 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
RST15 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
RST16 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
67P1TC Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
1
67P2TC Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
1
67P3TC Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
1
67G1TC Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
1
67G2TC Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
1
67G3TC Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
1
67G4TC Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
1
67Q1TC Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
1
<Filter is Empty>
11 Of 16 5/20/2015 2:51 PM
Setting Range
67Q2TC Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
Value
1
67Q3TC Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
1
67Q4TC Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
1
51PTC Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
1
51GTC Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
1
51QTC Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
1
T51PTC Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
1
T51GTC Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
1
T51QTC Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
1
T50PTC Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
1
T50GTC Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
1
T50QTC Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
1
87LTC
SV1
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
1
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
SV2 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
SV3
SV4
SV5
SV6
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
SV7
SV8
SV9
SV10
SV11
SV12
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
<Filter is Empty>
12 Of 16 5/20/2015 2:51 PM
Setting
SV13
SV14
SV15
Range
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
Value
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
SV16 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
OUT101 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
OUT102 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
CLOSE
OUT103 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
!TRIP*!OC
OUT104 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
OUT105 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
OUT106 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
OUT107 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
87HWAL
OUT201 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
OUT202 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
OUT203 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
OUT204 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
OUT205 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
OUT206 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
OUT301 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
OUT302 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
OUT303 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
OUT304 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
OUT305 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
OUT306 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
OUT307 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
OUT308 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
<Filter is Empty>
13 Of 16 5/20/2015 2:51 PM
Setting Range
OUT309 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
Value
0
OUT310 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
OUT311 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
OUT312 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
DP1
DP2
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
52A
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
CHXAL
DP3 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
CHYAL
DP4
DP5
DP6
DP7
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
DP8
DP9
DP10
DP11
DP12
DP13
DP14
DP15
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
DP16
SS1
SS2
SS3
SS4
SS5
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
<Filter is Empty>
14 Of 16 5/20/2015 2:51 PM
Setting
SS6
ER
Range
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
Value
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
/B87L2+/M2P+/Z2
G+/51G+/51Q+/50
P1+/LOP
FAULT Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
51G+51Q+M2P+Z2
G
BSYNC
H
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
CLMON Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
BKMON Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
E32IV Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
1
ESTUB Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
TMB1A Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
TMB2A Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
TMB3A Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
TMB4A Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
TMB5A Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
TMB6A Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
TMB7A Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
TMB8A Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
TMB1B Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
TMB2B Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
TMB3B Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
TMB4B Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
TMB5B Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
TMB6B Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
TMB7B Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
TMB8B Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
T1X Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
KEY
<Filter is Empty>
15 Of 16 5/20/2015 2:51 PM
Setting
T2X
T3X
T4X
T1Y
T2Y
T3Y
T4Y
Range
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
Value
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Group : L2
Group : L3
Group : L4
Group : L5
Group : L6
Group : P1
Group : P2
Group : P3
Group : P4
Group : P5
Group : R
Group : T
Group : X
EADDC
X
Select: Y, G, N
TA_X
RA_X
Select: 1-16
Select: 1-16
RBADXP Range = 1 to 1000
Y
1
2
10
AVAXP Range = 1 to 5000
DBADX
P
Range = 1 to 24
RC422X Select: R, F
TC422X Select: R, F
10
10
R
R
TIMRX Select: I, E
Group : Y
E
<Filter is Empty>
16 Of 16 5/20/2015 2:51 PM
Setting Range Value
Group : 1
RID Range = ASCII string with a maximum length of
30.
SEL-311
TID
CTR
Range = ASCII string with a maximum length of
30.
EXAMPLE: BUS B,
BREAKER 3
Range = 1 to 6000 1
APP Select: 87L, 87L21, 87L21P, 87LSP, 311L
EADVS Select: Y, N
311L
N
2 E87L
EDD
ETAP
Select: 2, 3, 3R, N
EHST Select: 1-6, N
EHSDT
T
Select: Y, N
Select: Y, N
Select: Y, N
N
N
EOCTL
PCHAN
EHSC
Select: Y, N
Select: X, Y
Select: Y, N
N
X
Y
N
N
CTR_X Range = 1 to 6000
TA_X Select: 1-16
RA_X Select: 1-16
CTR_Y
TA_Y
RA_Y
87LPP
87L2P
87LGP
CTALR
M
Range = 1 to 6000
Select: 1-16
Select: 1-16
Range = 1.00 to 10.00, OFF
Range = 0.50 to 5.00, OFF
Range = 0.50 to 5.00, OFF
Range = 0.50 to 10.00
87LR Range = 2.0 to 8.0
87LANG Range = 90 to 270
1
1
2
200
3
4
6.00
0.50
OFF
0.50
6.0
195
ETP
T51PP
Select: Y, N
Range = 0.50 to 16.00, OFF
N
OFF
T51PC Select: U1, U2, U3, U4, U5, C1, C2, C3, C4, C5 U3
T51PTD
T51PRS
T50PP
T50PD
ETG
Range = 0.50 to 15.00
Select: Y, N
Range = 0.50 to 100.00, OFF
Range = 0.00 to 16000.00, OFF
Select: Y, N
2.00
N
OFF
0.00
N
<Filter is Empty>
1 Of 16 5/20/2015 2:58 PM
Setting
T51GP
Range
Range = 0.50 to 16.00, OFF
Value
0.75
T51GC Select: U1, U2, U3, U4, U5, C1, C2, C3, C4, C5 U3
T51GTD
T51GRS
Range = 0.50 to 15.00
Select: Y, N
2.00
Y
T50GP Range = 0.50 to 100.00, OFF
T50GD Range = 0.00 to 16000.00, OFF
ETQ Select: Y, N
T51QP Range = 0.50 to 16.00, OFF
T51QC Select: U1, U2, U3, U4, U5, C1, C2, C3, C4, C5 U3
OFF
0.00
N
2.20
T51QT
D
Range = 0.50 to 15.00
T51QRS Select: Y, N
2.00
N
T50QP Range = 0.50 to 100.00, OFF
T50QD Range = 0.00 to 16000.00, OFF
CTRP
PTR
PTRS
Range = 1 to 6000
Range = 1.00 to 10000.00
Range = 1.00 to 10000.00
Z1MAG Range = 0.05 to 255.00
Z1ANG Range = 5.00 to 90.00
Z0MAG Range = 0.05 to 255.00
Z0ANG Range = 5.00 to 90.00
LL Range = 0.10 to 999.00
EFLOC Select: Y, N
E21P Select: N, 1-4, 1C-4C
ECCVT Select: Y, N
Z1P
Z2P
Z3P
Range = 0.05 to 64.00, OFF
Range = 0.05 to 64.00, OFF
Range = 0.05 to 64.00, OFF
Z4P
50PP1
Range = 0.05 to 64.00, OFF
Range = 0.50 to 170.00
50PP2 Range = 0.50 to 170.00
50PP3
50PP4
Range = 0.50 to 170.00
Range = 0.50 to 170.00
E21MG Select: N, 1-4
Z1MG
Z2MG
Z3MG
Z4MG
Range = 0.05 to 64.00, OFF
Range = 0.05 to 64.00, OFF
Range = 0.05 to 64.00, OFF
Range = 0.05 to 64.00, OFF
60.00
1.87
OFF
0.50
0.50
0.50
0.50
3
40.00
60.00
60.00
OFF
75.00
78.00
75.00
100.00
Y
2
N
40.00
OFF
0.00
1
1.00
1.00
78.00
<Filter is Empty>
2 Of 16 5/20/2015 2:58 PM
Setting
E21XG
Range
Select: N, 1-4
XG1
XG2
XG3
Range = 0.05 to 64.00, OFF
Range = 0.05 to 64.00, OFF
Range = 0.05 to 64.00, OFF
XG4
RG1
RG2
Range = 0.05 to 64.00, OFF
Range = 0.05 to 50.00
Range = 0.05 to 50.00
RG3
RG4
Range = 0.05 to 50.00
Range = 0.05 to 50.00
XGPOL Select: I2, IG
TANG Range = -45.0 to 45.0
50L1
50L2
50L3
50L4
Range = 0.50 to 100.00
Range = 0.50 to 100.00
Range = 0.50 to 100.00
Range = 0.50 to 100.00
k0M1 k0A1 k0M k0A
Z1PD
Z2PD
Z3PD
Z4PD
Z1GD
50GZ1 Range = 0.50 to 100.00
50GZ2 Range = 0.50 to 100.00
50GZ3 Range = 0.50 to 100.00
50GZ4 Range = 0.50 to 100.00
Range = 0.000 to 6.000
Range = -180.00 to 180.00
Range = 0.000 to 6.000
Range = -180.00 to 180.00
Range = 0.00 to 16000.00, OFF
Range = 0.00 to 16000.00, OFF
Range = 0.00 to 16000.00, OFF
Range = 0.00 to 16000.00, OFF
Range = 0.00 to 16000.00, OFF
Z2GD
Z3GD
Z4GD
Z1D
Z2D
Z3D
Z4D
E50P
Range = 0.00 to 16000.00, OFF
Range = 0.00 to 16000.00, OFF
Range = 0.00 to 16000.00, OFF
Range = 0.00 to 16000.00, OFF
Range = 0.00 to 16000.00, OFF
Range = 0.00 to 16000.00, OFF
Range = 0.00 to 16000.00, OFF
Select: N, 1-3
50P1P
50P2P
Range = 0.25 to 100.00, OFF
Range = 0.25 to 100.00, OFF
50P3P Range = 0.25 to 100.00, OFF
67P1D Range = 0.00 to 16000.00
67P2D Range = 0.00 to 16000.00
<Filter is Empty>
OFF
20.00
OFF
OFF
OFF
20.00
OFF
OFF
0.50
0.50
0.50
0.50
0.726
-3.69
0.726
-3.69
OFF
OFF
OFF
OFF
1
3.00
OFF
OFF
0.00
0.00
6.00
0.05
I2
-3.0
0.50
0.50
0.50
0.50
Value
N
6.24
9.36
1.87
OFF
2.50
5.00
3 Of 16 5/20/2015 2:58 PM
Setting
67P3D
Range
Range = 0.00 to 16000.00
E50G Select: N, 1-4
50G1P Range = 0.25 to 100.00, OFF
50G2P Range = 0.25 to 100.00, OFF
50G3P Range = 0.25 to 100.00, OFF
50G4P Range = 0.25 to 100.00, OFF
67G1D Range = 0.00 to 16000.00
67G2D Range = 0.00 to 16000.00
67G3D Range = 0.00 to 16000.00
67G4D Range = 0.00 to 16000.00
E50Q Select: N, 1-4
50Q1P Range = 0.25 to 100.00, OFF
50Q2P Range = 0.25 to 100.00, OFF
50Q3P Range = 0.25 to 100.00, OFF
50Q4P Range = 0.25 to 100.00, OFF
67Q1D Range = 0.00 to 16000.00
67Q2D Range = 0.00 to 16000.00
67Q3D Range = 0.00 to 16000.00
67Q4D Range = 0.00 to 16000.00
E51P
51PP
51PC
Select: Y, N
Range = 0.25 to 16.00, OFF
Select: U1-U5, C1-C5
51PTD Range = 0.50 to 15.00
51PRS Select: Y, N
E51G Select: Y, N
51GP
51GC
Range = 0.25 to 16.00, OFF
Select: U1-U5, C1-C5
51GTD Range = 0.50 to 15.00
51GRS Select: Y, N
E51Q Select: Y, N
51QP Range = 0.25 to 16.00, OFF
51QC Select: U1-U5, C1-C5
51QTD Range = 0.50 to 15.00
51QRS Select: Y, N
EOOS Select: Y, N
OOSB1 Select: Y, N
OOSB2 Select: Y, N
OOSB3 Select: Y, N
OOSB4 Select: Y, N
OSBD Range = 0.50 to 8000.00
EOOST Select: N, I, O
<Filter is Empty>
N
Y
0.75
U3
2.00
Y
Y
2.20
0.00
0.00
0.00
0.00
N
OFF
U3
2.00
N
N
N
N
N
U3
2.00
N
2.00
N
0.00
0.00
0.00
N
OFF
OFF
OFF
OFF
Value
0.00
N
OFF
OFF
OFF
OFF
0.00
4 Of 16 5/20/2015 2:58 PM
Setting
OSTD
X1T6
X1T5
R1R6
R1R5
X1B6
X1B5
Range
Range = 0.50 to 8000.00
Range = 0.05 to 96.00
Range = 0.05 to 96.00
Range = 0.05 to 70.00
Range = 0.05 to 70.00
Range = -96.00 to -0.05
Range = -96.00 to -0.05
R1L6
R1L5
Range = -70.00 to -0.05
Range = -70.00 to -0.05
50ABCP Range = 1.00 to 100.00
UBD Range = 0.50 to 120.00
UBOSBF Range = 1.00 to 10.00
ELOAD Select: Y, N
ZLF
ZLR
Range = 0.05 to 64.00
Range = 0.05 to 64.00
PLAF
NLAF
PLAR
Range = -90.00 to 90.00
Range = -90.00 to 90.00
Range = 90.00 to 270.00
NLAR
E32
ELOP
Range = 90.00 to 270.00
Select: Y, AUTO
Select: Y, Y1, N
EBBPT Select: Y, N
DIR3 Select: F, R
DIR4 Select: F, R
ORDER Select: I, Q, V, OFF
Z2F Range = -64.00 to 64.00
Z2R Range = -64.00 to 64.00
50QFP Range = 0.25 to 5.00
50QRP Range = 0.25 to 5.00
a2 k2
Range = 0.02 to 0.50
Range = 0.10 to 1.20
50GFP Range = 0.25 to 5.00
50GRP Range = 0.25 to 5.00
a0
Z0F
Z0R
Range = 0.02 to 0.50
Range = -64.00 to 64.00
Range = -64.00 to 64.00
EVOLT Select: Y, N
27P
59P
Range = 0.00 to 150.00, OFF
Range = 0.00 to 150.00, OFF
59N1P Range = 0.00 to 150.00, OFF
<Filter is Empty>
Value
0.50
96.00
90.00
70.00
65.00
-96.00
-90.00
-70.00
-65.00
1.00
0.50
4.00
39.00
39.10
N
OFF
OFF
OFF
39.10
0.50
0.25
0.10
0.20
0.50
0.25
0.10
210.00
AUTO
Y
N
R
F
QVI
39.00
Y
9.22
9.22
30.00
-30.00
150.00
5 Of 16 5/20/2015 2:58 PM
Setting
59N2P
Range
Range = 0.00 to 150.00, OFF
59QP
59V1P
Range = 0.00 to 100.00, OFF
Range = 0.00 to 150.00, OFF
27SP
59SP
27PP
59PP
Range = 0.00 to 150.00, OFF
Range = 0.00 to 150.00, OFF
Range = 0.00 to 260.00, OFF
Range = 0.00 to 260.00, OFF
E25 Select: Y, N
25VLO Range = 0.00 to 150.00
25VHI
25SF
Range = 0.00 to 150.00
Range = 0.005 to 0.500
25ANG1 Range = 0.00 to 80.00
25ANG2 Range = 0.00 to 80.00
SYNCP Select: VA, VB, VC, VAB, VBC, VCA
TCLOSD Range = 1.00 to 60.00, OFF
E81 Select: N, 1-6
27B81P Range = 20.00 to 150.00
81D1P Range = 41.00 to 65.00, OFF
81D1D Range = 2.00 to 16000.00
81D2P Range = 41.00 to 65.00, OFF
81D2D Range = 2.00 to 16000.00
81D3P Range = 41.00 to 65.00, OFF
81D3D Range = 2.00 to 16000.00
81D4P Range = 41.00 to 65.00, OFF
81D4D Range = 2.00 to 16000.00
81D5P Range = 41.00 to 65.00, OFF
81D5D Range = 2.00 to 16000.00
81D6P Range = 41.00 to 65.00, OFF
81D6D Range = 2.00 to 16000.00
E79
79OI1
Select: N, 1-4
Range = 0.00 to 999999.00
79OI2 Range = 0.00 to 999999.00
79OI3
79OI4
Range = 0.00 to 999999.00
Range = 0.00 to 999999.00
79RSD Range = 0.00 to 999999.00
79RSLD Range = 0.00 to 999999.00
79CLSD Range = 0.00 to 999999.00, OFF
<Filter is Empty>
VA
3.00
N
20.00
60.00
OFF
60.00
OFF
60.00
N
0.00
0.00
OFF
60.00
OFF
60.00
OFF
60.00
OFF
0.00
0.00
1800.00
300.00
OFF
Value
OFF
OFF
OFF
OFF
OFF
OFF
OFF
N
60.00
75.00
0.042
25.00
40.00
6 Of 16 5/20/2015 2:58 PM
Setting
ESOTF
Range
Select: Y, N
CLOEN
D
Range = 0.00 to 16000.00, OFF
52AEND Range = 0.00 to 16000.00, OFF
SOTFD Range = 0.50 to 16000.00
ECOMM Select: N, POTT, DCUB1, DCUB2, DCB
Z3RBD Range = 0.00 to 16000.00
EBLKD Range = 0.00 to 16000.00, OFF
ETDPU Range = 0.00 to 16000.00, OFF
EDURD Range = 0.00 to 16000.00
EWFC Select: Y, N
27PPW Range = 0.0 to 260.0
59NW Range = 0.0 to 150.0
GARD1
D
Range = 0.00 to 16000.00
UBDUR
D
Range = 0.25 to 16000.00
UBEND Range = 0.00 to 16000.00
Z3XPU Range = 0.00 to 16000.00
Z3XD Range = 0.00 to 16000.00
BTXD
21SD
67SD
Range = 0.00 to 16000.00
Range = 0.00 to 60.00
Range = 0.00 to 60.00
EMBA
RXIDA
Select: Y, N
Range = 1 to 4
TXIDA Range = 1 to 4
EMBB
RXIDB
Select: Y, N
Range = 1 to 4
TXIDB Range = 1 to 4
EZ1EXT Select: Y, N
Z1EXTD Range = 0.00 to 16000.00
Z1EXTM Range = 1.00 to 4.00
EDEM
DMTC
Select: THM, ROL
Select: 5, 10, 15, 30, 60
PDEMP Range = 0.50 to 16.00, OFF
GDEMP Range = 0.50 to 16.00, OFF
QDEMP Range = 0.50 to 16.00, OFF
TDURD Range = 2.00 to 16000.00
TOPD Range = 2.00 to 8000.00
<Filter is Empty>
180.00
1.30
THM
60
OFF
OFF
OFF
9.00
2.00
N
1
1.00
1.00
2
0.50
1.00
5.00
0.00
2
N
N
1
5.00
10.00
2.00
4.00
N
0.0
150.0
10.00
9.00
Value
Y
OFF
10.00
30.00
POTT
7 Of 16 5/20/2015 2:58 PM
Setting
CFD
3POD
OPO
27PO
50LP
ELAT
EDP
Range
Range = 0.00 to 16000.00, OFF
Range = 0.00 to 60.00
Select: 27, 52
Range = 0.00 to 150.00
Range = 0.25 to 100.00, OFF
Select: N, 1-16
Select: N, 1-16
ESV Select: N, 1-16
SV1PU Range = 0.00 to 999999.00
SV2PU Range = 0.00 to 999999.00
SV3PU Range = 0.00 to 999999.00
SV4PU Range = 0.00 to 999999.00
SV5PU Range = 0.00 to 999999.00
SV6PU Range = 0.00 to 999999.00
SV7PU Range = 0.00 to 16000.00
SV8PU Range = 0.00 to 16000.00
SV9PU Range = 0.00 to 16000.00
SV10PU Range = 0.00 to 16000.00
SV11PU Range = 0.00 to 16000.00
SV12PU Range = 0.00 to 16000.00
SV13PU Range = 0.00 to 16000.00
SV14PU Range = 0.00 to 16000.00
SV15PU Range = 0.00 to 16000.00
SV16PU Range = 0.00 to 16000.00
SV1DO Range = 0.00 to 999999.00
SV2DO Range = 0.00 to 999999.00
SV3DO Range = 0.00 to 999999.00
SV4DO Range = 0.00 to 999999.00
SV5DO Range = 0.00 to 999999.00
SV6DO Range = 0.00 to 999999.00
SV7DO Range = 0.00 to 16000.00
SV8DO Range = 0.00 to 16000.00
SV9DO Range = 0.00 to 16000.00
SV10D
O
Range = 0.00 to 16000.00
SV11D
O
Range = 0.00 to 16000.00
<Filter is Empty>
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
N
0.00
0.00
0.00
0.00
0.00
0.00
0.00
Value
60.00
0.50
52
40.00
0.25
16
16
0.00
0.00
0.00
0.00
0.00
8 Of 16 5/20/2015 2:58 PM
Setting
SV12D
O
Range
Range = 0.00 to 16000.00
SV13D
O
Range = 0.00 to 16000.00
SV14D
O
Range = 0.00 to 16000.00
SV15D
O
Range = 0.00 to 16000.00
SV16D
O
Range = 0.00 to 16000.00
Value
0.00
0.00
0.00
0.00
0.00
Group : 2
Group : 3
Group : 4
Group : 5
Group : 6
Group : DNPA
Group : DNPB
Group : G
Group : L1
TR Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
87CHFAIL*(M1P+M
2P+Z1G+Z2G)
TRCOM
M
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
M2P+Z2G
TRSOTF Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
M2P
DTT
E3PT
ULTR
PT1
PT2
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
!(50L+51G)
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
R1X
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
LOG1
LOG2
BT
52A
52AA
52AB
52AC
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
IN101
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
<Filter is Empty>
9 Of 16 5/20/2015 2:58 PM
Setting
CL
ULCL
79RI
Range
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
Value
CC
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
TRIP+TRIP87
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
79RIS
79DTL
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
79DLS Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
79SKP Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
79STL Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
79BRS Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
79SEQ Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
79CLS Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
SET1
SET2
SET3
SET4
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
SET5
SET6
SET7
SET8
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
SET9
SET10
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
SET11 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
SET12 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
SET13 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
SET14 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
<Filter is Empty>
10 Of 16 5/20/2015 2:58 PM
Setting
SET15
Range
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
Value
0
SET16 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
RST1
RST2
RST3
RST4
RST5
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
RST6
RST7
RST8
RST9
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
RST10 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
RST11 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
RST12 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
RST13 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
RST14 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
RST15 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
RST16 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
67P1TC Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
1
67P2TC Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
1
67P3TC Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
1
67G1TC Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
1
67G2TC Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
1
67G3TC Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
1
67G4TC Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
1
<Filter is Empty>
11 Of 16 5/20/2015 2:58 PM
Setting Range
67Q1TC Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
Value
1
67Q2TC Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
1
67Q3TC Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
1
67Q4TC Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
1
51PTC Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
1
51GTC Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
1
51QTC Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
1
T51PTC Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
1
T51GTC Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
1
T51QTC Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
1
T50PTC Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
1
T50GTC Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
1
T50QTC Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
1
87LTC Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
1
SV1 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
SV2
SV3
SV4
SV5
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
SV6
SV7
SV8
SV9
SV10
SV11
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
<Filter is Empty>
12 Of 16 5/20/2015 2:58 PM
Setting
SV12
SV13
Range
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
Value
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
SV14 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
SV15
SV16
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
OUT101 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
OUT102 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
CLOSE
OUT103 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
!TRIP*!OC
OUT104 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
OUT105 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
OUT106 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
OUT107 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
87HWAL
OUT201 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
OUT202 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
OUT203 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
OUT204 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
OUT205 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
OUT206 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
OUT301 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
OUT302 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
OUT303 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
OUT304 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
OUT305 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
OUT306 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
OUT307 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
<Filter is Empty>
13 Of 16 5/20/2015 2:58 PM
Setting Range
OUT308 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
Value
0
OUT309 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
OUT310 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
OUT311 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
OUT312 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
DP1 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
52A
DP2 Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
CHXAL
DP3
DP4
DP5
DP6
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
CHYAL
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
DP7
DP8
DP9
DP10
DP11
DP12
DP13
DP14
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
DP15
DP16
SS1
SS2
SS3
SS4
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
<Filter is Empty>
14 Of 16 5/20/2015 2:58 PM
Setting
SS5
SS6
Range
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
Value
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
ER Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
/B87L2+/M2P+/Z2
G+/51G+/51Q+/50
P1+/LOP
FAULT Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
51G+51Q+M2P+Z2
G
BSYNC
H
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
CLMON Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
BKMON Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
E32IV Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
1
ESTUB Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
TMB1A Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
TMB2A Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
TMB3A Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
TMB4A Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
TMB5A Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
TMB6A Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
TMB7A Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
TMB8A Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
TMB1B Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
TMB2B Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
TMB3B Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
TMB4B Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
TMB5B Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
TMB6B Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
TMB7B Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
TMB8B Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
<Filter is Empty>
15 Of 16 5/20/2015 2:58 PM
Setting
T1X
T2X
T3X
T4X
T1Y
T2Y
T3Y
T4Y
Range
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
Value
KEY
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Valid range = Boolean equation using word bit elements and the legal operators: ! / \ ( ) * +
0
Group : L2
Group : L3
Group : L4
Group : L5
Group : L6
Group : P1
Group : P2
Group : P3
Group : P4
Group : P5
Group : R
Group : T
Group : X
EADDC
X
Select: Y, G, N
TA_X Select: 1-16
RA_X Select: 1-16
RBADXP Range = 1 to 1000
Y
2
1
10
AVAXP Range = 1 to 5000
DBADX
P
Range = 1 to 24
RC422X Select: R, F
10
10
R
TC422X Select: R, F
TIMRX Select: I, E
Group : Y
R
I
<Filter is Empty>
16 Of 16 5/20/2015 2:58 PM
8.4
SEL 311-L PILOT PROTECTION LABORATORY MANUAL
PAGE INTENTIONALLY LEFT BLANK
ELECTRICAL ENGINEERING DEPARTMENT
California Polytechnic State University
EE 444
Permissive Over-reaching Transfer Trip Protection (POTT)
Experiment #
Introduction:
Permissive Over-reaching Transfer Trip Protection (POTT) is a communication based protection scheme that relies on phase distance protection elements. Protection of transmission lines in a nonradial systems is difficult to coordinate with other connected transmission lines and distribution because power flow is not static or in one direction all of the time. For the protection of transmission lines, differential protection is not possible because of the losses along the line (I in
≠
I out
). The basic topology of the system consists of a transmission line with a SEL-311L relay at each end connected via a fiber optic communications line. The relays phase distance Zone 2 elements are set to pick-up at 120% of the line. The difference between phase distance and POTT is in the trip logic and communications link. A trip will only be issued if both relays Zone 2 elements pick-up and both of the relays receive a “key” from the other acknowledging that they too could see the Zone 2
Fault. The logic can be better explained by referring to the logic diagram below in Figure 1.
Figure 1. POTT Trip Logic
2
2
6
EQUIPMENT:
SEL 311-L relays
Circuit breakers
Inductor / double power resistors boards (100mH+ (2) 10Ω)
1
1
35 Long banana-to banana leads
1 Bag of short leads
Multi-meter
SEL serial data cable
49 | P a g e
3 High resistance / impedance load
PROCEDURE:
1.
Download and print the construction document set.
2.
Using banana to banana leads, wire the system according to the wiring diagrams in the construction drawing set.
3.
With the power off, test the systems resistance of each phase to the center of the load wye connection. Resistance values should be 20 ohms + (load resistance / impedance) disconnected from the sources for resistance from each phase.
4.
With the power off, verify the resistance between phases at the source is greater than 20 ohms. a.
A to B b.
B to C c.
C to A
5.
Wire Breaker and connect breaker to the SEL relay as shown in the construction drawing set.
6.
Test manual breaker functionality by only energizing the 125VDC and pressing Open/ Close to verify breaker operation.
7.
Program relay using settings found in the appendix of this document.
8.
Upload the settings following the directions found in the appendix.
9.
Based on the Single Line drawing in the construction drawing set. Connect the fault switch to the nodes internal to the transmission line zone of protection.
10.
Apply fault conditions based on the procedure outlined in the “Breaker Operation” section. The fault switch should only be turned on momentarily. The switch should be returned to the off position within 5 seconds of being turned on to prevent equipment overheating and damage.
11.
Apply SLG, LL, LLL faults for internal faults only. Download and view events to AcSELerator
Analytic Assistant.
50 | P a g e
APPENDIX:
The relay settings below should be edited to provide proper system POTT protection.
Step 1. Open AcSELerator
Step 2. Click File new and choose SEL311-L. Based on the serial number of your relay enter the required information.
Step 3. Connect serial cable to the serial port located on the front of the relay and to the lab bench desktop
Step 4. Under the communications menu, select parameters. Confirm that the active connection type is set to serial and the settings in Figure 2 have been selected.
Figure 2. Communications Settings
Step 5. Click Connect. The bottom right hand corner of the window should display “Connected.”
Step 6. Edit Settings.
Step 7. Click Send Active settings button.
51 | P a g e
Figure 3. Line Current Differential Settings
Figure 4. 87L Transmit Equations
52 | P a g e
Figure 5. Close/Reclose Logic
Figure 6. Phase Distance
53 | P a g e
Figure 7. Trip/Comm – Assisted Trip Logic
54 | P a g e
Figure 8. Output Contacts
55 | P a g e
8.5
REFERENCES
[1] J. L. Blackburn, and T. J. Domin, Protective Relaying Principles and Applications 4th
Edition. Boca Raton, FL: Taylor & Francis Group, LLC, 2014.
[2] Schweitzer Engineering Laboratories, SEL-311L-1 -7 Relay Protection and Automation
System Instruction Manual, Pullman, Washington: Schweitzer Engineering Laboratories, 2003-2014.
[3] IEEE Guide for Developing System Requirements Specifications," IEEE Std 1233-1996 , vol., no., pp.i,, 1996 doi: 10.1109/IEEESTD.1996.81000
[4] Schweitzer Engineering Laboratories, “SEL-311L Line Current Differential Protection and
Automation System (Data Sheet),” Schweitzer Engineering Laboratories. [Online]. Available: https://www.selinc.com/SEL-311L/ [Accessed: Jan, 22, 2015]
[4] Bogdan Z. Kasztenny, Normann Fischer, "Transformer differential protection,“ U.S. Patent:
8 553 379, issued date October 8, 2013. Available: http://patft1.uspto.gov/netacgi/nph-
Parser?patentnumber=8553379
[5] Schweitzer Engineering Laboratories, “SEL-2032 Communications Processor Instruction
Manual,” Schweitzer Engineering Laboratories. [Online]. Available: https://www.selinc.com/SEL-
2032/ [Accessed: Jan, 22, 2015]
[6] IEEE Recommended Practice for Industrial and Commercial Power System Analysis,"
IEEE Std 399-1990 , vol., no., pp.1,384, Dec. 15 1990
[7] IEEE Guide for Protective Relay Applications to Transmission Lines," IEEE Std C37.113-
1999 , vol., no., pp.i,, 2000
[8] Ghanizadeh Bolandi, T.; Seyedi, H.; Hashemi, S.M.; Soleiman Nezhad, P., "Impedance-
Differential Protection: A New Approach to Transmission-Line Pilot Protection," Power Delivery,
IEEE Transactions on , vol.PP, no.99, pp.1,1
[9] IEEE Guide for Protecting Power Transformers," IEEE Std C37.91-2008 (Revision of
IEEE Std C37.91-2000) , vol., no., pp.1,139, May 30 2008 doi: 10.1109/IEEESTD.2008.4534870
56 | P a g e
[10] IEEE Guide for Determining Fault Location on AC Transmission and Distribution Lines,"
IEEE Std C37.114-2014 (Revision of IEEE Std C37.114-2004) , vol., no., pp.1,76, Jan. 30 2015
57 | P a g e