PN: 15465:F1 ECN 02-606 Control Communicator MS-5012 Document 12/04/02 #15465 Rev. F Fire Alarm System Limitations While a fire alarm system may lower insurance rates, it is not a substitute for fire insurance! An automatic fire alarm system–typically made up of smoke detectors, heat detectors, manual pull stations, audible warning devices, and a fire alarm control with remote notification capability–can provide early warning of a developing fire. Such a system, however, does not assure protection against property damage or loss of life resulting from a fire. Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a predetermined rate or reaches a predetermined level. Rate-of-rise heat detectors may be subject to reduced sensitivity over time. For this reason, the rate-of-rise feature of each detector should be tested at least once per year by a qualified fire protection specialist. Heat detectors are designed to protect property, not life. The Manufacturer recommends that smoke and/or heat detectors be located throughout a protected premise following the recommendations of the current edition of the National Fire Protection Association Standard 72 (NFPA 72), manufacturer's recommendations, State and local codes, and the recommendations contained in the Guide for Proper Use of System Smoke Detectors, which is made available at no charge to all installing dealers. A study by the Federal Emergency Management Agency (an agency of the United States government) indicated that smoke detectors may not go off in as many as 35% of all fires. While fire alarm systems are designed to provide early warning against fire, they do not guarantee warning or protection against fire. A fire alarm system may not provide timely or adequate warning, or simply may not function, for a variety of reasons: Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in or behind walls, on roofs, or on the other side of closed doors. Smoke detectors also may not sense a fire on another level or floor of a building. A second-floor detector, for example, may not sense a first-floor or basement fire. Particles of combustion or "smoke" from a developing fire may not reach the sensing chambers of smoke detectors because: • Barriers such as closed or partially closed doors, walls, or chimneys may inhibit particle or smoke flow. • Smoke particles may become "cold," stratify, and not reach the ceiling or upper walls where detectors are located. • Smoke particles may be blown away from detectors by air outlets. • Smoke particles may be drawn into air returns before reaching the detector. The amount of "smoke" present may be insufficient to alarm smoke detectors. Smoke detectors are designed to alarm at various levels of smoke density. If such density levels are not created by a developing fire at the location of detectors, the detectors will not go into alarm. Smoke detectors, even when working properly, have sensing limitations. Detectors that have photoelectronic sensing chambers tend to detect smoldering fires better than flaming fires, which have little visible smoke. Detectors that have ionizing-type sensing chambers tend to detect fast-flaming fires better than smoldering fires. Because fires develop in different ways and are often unpredictable in their growth, neither type of detector is necessarily best and a given type of detector may not provide adequate warning of a fire. Smoke detectors cannot be expected to provide adequate warning of fires caused by arson, children playing with matches (especially in bedrooms), smoking in bed, and violent explosions (caused by escaping gas, improper storage of flammable materials, etc.). LimWarLg.p65 01/10/2000 IMPORTANT! Smoke detectors must be installed in the same room as the control panel and in rooms used by the system for the connection of alarm transmission wiring, communications, signaling, and/or power. If detectors are not so located, a developing fire may damage the alarm system, crippling its ability to report a fire. Audible warning devices such as bells may not alert people if these devices are located on the other side of closed or partly open doors or are located on another floor of a building. Any warning device may fail to alert people with a disability or those who have recently consumed drugs, alcohol or medication. Please note that: • Strobes can, under certain circumstances, cause seizures in people with conditions such as epilepsy. • Studies have shown that certain people, even when they hear a fire alarm signal, do not respond or comprehend the meaning of the signal. It is the property owner's responsibility to conduct fire drills and other training exercise to make people aware of fire alarm signals and instruct them on the proper reaction to alarm signals. • In rare instances, the sounding of a warning device can cause temporary or permanent hearing loss. A fire alarm system will not operate without any electrical power. If AC power fails, the system will operate from standby batteries only for a specified time and only if the batteries have been properly maintained and replaced regularly. Equipment used in the system may not be technically compatible with the control. It is essential to use only equipment listed for service with your control panel. Telephone lines needed to transmit alarm signals from a premise to a central monitoring station may be out of service or temporarily disabled. For added protection against telephone line failure, backup radio transmission systems are recommended. The most common cause of fire alarm malfunction is inadequate maintenance. To keep the entire fire alarm system in excellent working order, ongoing maintenance is required per the manufacturer's recommendations, and UL and NFPA standards. At a minimum, the requirements of Chapter 7 of NFPA 72 shall be followed. Environments with large amounts of dust, dirt or high air velocity require more frequent maintenance. A maintenance agreement should be arranged through the local manufacturer's representative. Maintenance should be scheduled monthly or as required by National and/ or local fire codes and should be performed by authorized professional fire alarm installers only. Adequate written records of all inspections should be kept. Installation Precautions Adherence to the following will aid in problem-free installation with long-term reliability: WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all sources of power before servicing. Control unit and associated equipment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until this manual is read and understood. CAUTION - System Reacceptance Test after Software Changes. To ensure proper system operation, this product must be tested in accordance with NFPA 72 Chapter 7 after any programming operation or change in site-specific software. Reacceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring. All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested. In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified. This system meets NFPA requirements for operation at 0-49° C/32-120° F and at a relative humidity of 85% RH (noncondensing) at 30° C/86° F. However, the useful life of the system's standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and all peripherals be installed in an environment with a nominal room temperature of 15-27° C/60-80° F. Verify that wire sizes are adequate for all initiating and indicating device loops. Most devices cannot tolerate more than a 10% I.R. drop from the specified device voltage. Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to lightning-induced transients. Although no system is completely immune from lightning transients and interferences, proper grounding will reduce susceptibility. Overhead or outside aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes. Consult with the Technical Services Department if any problems are anticipated or encountered. Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits. Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifications, verify that they will not interfere with battery, transformer, and printed circuit board location. Do not tighten screw terminals more than 9 in-lbs. Over-tightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal removal. Though designed to last many years, system components can fail at any time. This system contains static-sensitive components. Always ground yourself with a proper wrist strap before handling any circuits so that static charges are removed from the body. Use static-suppressive packaging to protect electronic assemblies removed from the unit. Follow the instructions in the installation, operating, and programming manuals. These instructions must be followed to avoid damage to the control panel and associated equipment. FACP operation and reliability depend upon proper installation by authorized personnel. FCC Warning WARNING: This equipment generates, uses, and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual, may cause interference to radio communications. It has been tested and found to comply with the limits for class A computing device pursuant to Subpart B of Part 15 of FCC Rules, which is designed to provide reasonable protection against such interference when operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interference, in which case the user will be required to correct the interference at his own expense. Canadian Requirements This digital apparatus does not exceed the Class A limits for radiation noise emissions from digital apparatus set out in the Radio Interference Regulations of the Canadian Department of Communications. Le present appareil numerique n'emet pas de bruits radioelectriques depassant les limites applicables aux appareils numeriques de la classe A prescrites dans le Reglement sur le brouillage radioelectrique edicte par le ministere des Communications du Canada. LimWarLg.p65 01/10/2000 Notes 4 Document #15465 Rev.F1 12/04/02 P/N 15465:F1 Table of Contents CHAPTER 1: Product Description ......................................................................................................................... 10 1.1: Product Features ..........................................................................................................................................10 FIGURE 1-1: DP-5012 Cover..............................................................................................................11 1.2: Circuits ........................................................................................................................................................11 1.3: Front Panel Switches ...................................................................................................................................11 1.4: Displays .......................................................................................................................................................12 1.5: Digital Communicator.................................................................................................................................12 1.6: ADM-12 Annunciator Driver Module - Optional .......................................................................................12 FIGURE 1-2: ADM-12/MS-5012........................................................................................................12 1.7: RZA-5F Remote Annunciator .....................................................................................................................13 FIGURE 1-3: RZA-5F Annunciator ....................................................................................................13 1.8: Specifications ..............................................................................................................................................13 CHAPTER 2: Control Panel Operation .................................................................................................................. 16 FIGURE 2-1: Display and Keypad ......................................................................................................16 2.1: Switch Functions in Normal Mode .............................................................................................................16 2.2: Displays .......................................................................................................................................................17 FIGURE 2-2: Communicator Connections and LEDs.........................................................................18 2.3: Operation.....................................................................................................................................................18 2.4: Digital Communicator.................................................................................................................................21 TABLE 2-1: Format Selection Addresses (16 & 42)...........................................................................22 TABLE 2-2: Compatible UL Listed Receivers....................................................................................25 CHAPTER 3: Installation......................................................................................................................................... 26 3.1: Cabinet Mounting Options ..........................................................................................................................26 FIGURE 3-1: Cabinet Dimensions and Knockout Locations..............................................................26 3.2: Input Circuits...............................................................................................................................................27 FIGURE 3-2: Initiating Device Circuits - TB2....................................................................................27 3.3: Output Circuits ............................................................................................................................................28 FIGURE 3-3: Output Circuits - TB3....................................................................................................28 FIGURE 3-4: Driving Relays From Open Collector Outputs..............................................................28 3.4: UL Power-limited Wiring Requirements ....................................................................................................29 FIGURE 3-5: Typical Wiring Diagram for UL Power-limited Requirements ....................................29 TABLE 3-1: Output Normal Conditions .............................................................................................29 3.5: Digital Communicator.................................................................................................................................30 FIGURE 3-6: Wiring Phone Jacks.......................................................................................................30 3.6: Operating Power..........................................................................................................................................31 3.6.1: Primary Power Source (AC) and Earth Ground Connections...........................................................31 3.6.2: Secondary Power Source (batteries) .................................................................................................31 FIGURE 3-7: MS-5012 Power Connections .......................................................................................31 3.6.3: Optional AC Terminal Block ............................................................................................................32 FIGURE 3-8: Optional AC Terminal Block Installation .....................................................................32 3.7: Optional Boards...........................................................................................................................................33 3.7.1: ADM-12 Annunciator Driver Module ..............................................................................................33 FIGURE 3-9: ADM-12 Module...........................................................................................................33 3.7.2: RZA-5F Remote Annunciator...........................................................................................................33 FIGURE 3-10: RZA-5F Remote Annunciator.....................................................................................33 FIGURE 3-11: Mounting the RZA-5F to Single-Gang Electrical Box ...............................................33 FIGURE 3-12: Wiring the RZA-5F to the ADM-12 ...........................................................................34 CHAPTER 4: Programming Instructions............................................................................................................... 35 4.1: Entering Program Mode ..............................................................................................................................35 FIGURE 4-1: First Address .................................................................................................................35 4.2: Switch Functions in Program Mode ...........................................................................................................36 Document 15465 Rev. F1 12/04/02 P/N: 15465:F1 5 Table of Contents FIGURE 4-2: Switch Functions in Program Mode..............................................................................36 4.3: Programming ...............................................................................................................................................36 4.3.1: Programming the Primary Phone Number (00 - 15) .........................................................................36 4.3.2: Programming Primary Number Communication Format (16)..........................................................37 TABLE 4-1: 3+1 and 4+1 Standard and Expanded, 4+2 Expanded Formats......................................37 4.3.3: Programming the Primary Number Account Code (17-20) ..............................................................38 TABLE 4-2: 4+2 Standard Formats.....................................................................................................39 4.3.4: Programming the Primary Number 24 Hour Test Time (21-24).......................................................40 4.3.5: Programming Primary Number 24/12 Hour Test Time (25) .............................................................40 4.3.6: Programming the Secondary Phone Number (26-41) .......................................................................40 4.3.7: Programming Secondary Number Communication Format (42)......................................................41 TABLE 4-3: 3+1 and 4+1 Standard and Expanded, 4+2 Expanded Formats......................................41 4.3.8: Programming the Secondary Number Account Code (43-46) ..........................................................42 TABLE 4-4: 4+2 Standard Formats.....................................................................................................43 4.3.9: Programming the Secondary Number 24 Hour Test Time (47-50)...................................................44 4.3.10: Programming Secondary Number 24/12 Hour Test Time (51) .......................................................44 4.3.11: Programming Zone 3 Functionality (52).........................................................................................44 4.3.12: Programming Waterflow Retard Timer (53-54)..............................................................................44 4.3.13: Programming AC Loss Reporting Delay (55).................................................................................45 4.3.14: Programming Slave Communicator/Fire Panel Selection (56) .......................................................45 4.3.15: Secondary Phone Number Reporting (57) ......................................................................................45 4.3.16: Alarm Verification on Detector Zones 2 and 3 (58)........................................................................45 4.3.17: Silence Inhibit (59)..........................................................................................................................45 4.3.18: Auto Silence (60) ............................................................................................................................45 4.3.19: Trouble Reminder (61) ....................................................................................................................45 4.3.20: Bell Disable (62) .............................................................................................................................46 4.3.21: Annunciator Present (63) ................................................................................................................46 4.3.22: Programming Zone 4 Functionality (64).........................................................................................46 4.3.23: Address (65) - Not used ..................................................................................................................46 4.3.24: Touchtone/Rotary Select (66)..........................................................................................................46 4.3.25: Make/Break Ratio (67)....................................................................................................................46 4.3.26: Programming Event Codes (68-243)...............................................................................................46 4.3.27: End Programming ...........................................................................................................................46 4.3.28: Programming the Real-Time Clock ................................................................................................46 CHAPTER 5: Servicing............................................................................................................................................47 5.1: Walktest Mode.............................................................................................................................................47 5.2: History Mode...............................................................................................................................................48 5.3: Troubleshoot Mode......................................................................................................................................49 FIGURE 5-1: Handset Connection ......................................................................................................50 5.4: Lamp Test ....................................................................................................................................................50 CHAPTER 6: Slave Communicator Configuration ...............................................................................................51 Appendix A: Power Calculations .........................................................................................................................53 TABLE A-1: Total Ampere Hours .....................................................................................................53 TABLE A-2: Regulated Load in Standby ...........................................................................................54 TABLE A-3: Regulated Load in Alarm ..............................................................................................55 Appendix B: Programming Reference Sheets .....................................................................................................56 B.1: Blank System Programming Reference Sheets ........................................................................................56 B.2: Blank Format Programming Reference Sheet ...........................................................................................57 B.3: Programming Reference Sheet Factory Default Settings ..........................................................................58 B.4: Format Programming Reference Sheet Factory Default Sheet ..................................................................59 6 Document 15465 Rev. F1 12/04/02 P/N: 15465:F1 This control panel has been designed to comply with standards set forth by the following regulatory agencies: • Underwriters Laboratories Standard UL 864 • NFPA 72 National Fire Alarm Code for Local, Remote Station Fire Alarm Systems Before proceeding, the installer should be familiar with the following documents. NFPA Standards Intallation, Maintenance and Use of Central Station Fire Alarm Systems Local Fire Alarm Systems Use of Proprietary Fire Alarm Systems Automatic Fire Detectors Installation, Maintenance and Use of Notification Appliances for Fire Alarm Systems Testing Procedures for Fire Alarm Systems. Underwriters Laboratories Documents: UL 38 Manually Actuated Signaling Boxes UL 217 Smoke Detectors, Single and Multiple Station UL 228 Door Closers–Holders for Fire Protective Signaling Systems UL 268 Smoke Detectors for Fire Protective Signaling Systems UL 268A Smoke Detectors for Duct Applications UL 346 Waterflow Indicators for Fire Protective Signaling Systems UL 464 Audible Signaling Appliances UL 521 Heat Detectors for Fire Protective Signaling Systems UL 864 Standard for Control Units for Fire Protective Signaling Systems UL 1481 Power Supplies for Fire Protective Signaling Systems UL 1638 Visual Signaling Appliances UL 1971 Signaling Devices for Hearing Impaired Other: NEC Article 250 Grounding NEC Article 300 Wiring Methods NEC Article 760 Fire Protective Signaling Systems ADA American with Disabilities Act Applicable Local and State Building Codes Requirements of the Local Authority Having Jurisdiction (LAHJ) Fire•Lite Documents Fire•Lite Device Compatibility Document Document #15465 Document #15384 Rev. F1 12/04/02 P/N 15465:F1 7 8 Document #15465 Rev.F1 12/04/02 P/N 15465:F1 The MS-5012 Panel Primary & Secondary Phone Lines Connector for Annunciator Driver Module Piezo 85dB 5 Input Zones 4-Digit LED Display 4 Open Collector Outputs Keypad Holds up to 7 AH Batteries Up to 60 Hrs. of Standby Document #15465 Rev. F1 12/04/02 P/N 15465:F1 9 Product Description CHAPTER 1 Product Description The MS-5012 is a combination FACP (Fire Alarm Control Panel) and digital communicator, all on one circuit board. It is a five-zone panel which uses conventional input devices. The panel accepts waterflow devices, two-wire smoke detectors, four-wire smoke detectors, pull stations and other normally open contact devices. Outputs include NACs (Notification Alarm Circuits), alarm relay, trouble relay, supervisory relay and communicator failure relay drivers. The integral communicator transmits system status (alarms, troubles, AC loss, etc.) to a UL recognized Central Station via the public switched telephone network. The control panel has a built in programmer and may also serve as a slave communicator to a host panel. It also supervises all wiring, AC voltage, telephone line input voltage and battery level. 1.1 • • • • • • • • • • • • • • • • • • • • • • • • • • • • 10 Product Features FACP (Fire Alarm Control Panel) Slave Fire Communicator 12 volt operation Real time clock Telephone line active indicators Trouble reminder One Style D (Class A) zone Four Style B (Class B) zones Programmable zone ID Alarm verification Optional annunciators ✓ RZA-5F remote annunciator (requires ADM-12 Annunciator Driver Module) ✓ LED type annunciators Small size [14.5" (36.83 cm) x 12.5" (31.75 cm) x 2.875" (7.303 cm)] Event history storage Silence inhibit Auto-silence Programmable event codes (all formats) Touchtone/rotary dialing Programmable make/break ratio Communication confirmation (kissoff) LED Fuseless AC loss report meets UL 864 requirements Number of dial attempts (5 minimum, 10 maximum) Programmable channel ID (slave) Programmable zone delay (waterflow only) Four open collector outputs Disable report by event Low AC voltage sense Walktest Document #15465 Rev.F1 12/04/02 P/N 15465:F1 Circuits • • • • Built-in voltmeter Built-in programmer One NFPA Style Y NAC (Notification Appliance Circuit) Optional Dead Panel cover available FIGURE 1-1: DP-5012 Cover 1.2 Circuits Input Circuits ✓ Initiating Device Circuit #1 (Style B) Normally Open contact devices only ✓ Initiating Device Circuit #2 (Style B) Normally Open contact devices and 2-wire smoke detectors ✓ Initiating Device Circuit #3 (Style B/D) Normally Open contact devices, 2-wire smoke detectors (Style B only), waterflow devices ✓ Initiating Device Circuit #4 (Style B) Normally Open contact devices only ✓ Initiating Device Circuit #5 (Style B) Normally Open contact devices only Output Circuits ✓ Notification Appliance Circuit ✓ Resettable Power Circuit ✓ Nonresettable Power Circuit ✓ Relay Driver Output - Alarm ✓ Relay Driver Output - Trouble ✓ Relay Driver Output - Supervisory ✓ Relay Driver Output - Communicator Failure ✓ Primary Telephone Line ✓ Secondary Telephone Line ✓ 12 Volt Battery Charger 1.3 Front Panel Switches Reset Silence Mode Up Arrow Down Arrow 1st Event Enter/Store u v w 123f q 456e r 789d s a0bc t Digits 0 - 9 A B C D E F Document #15465 Rev. F1 12/04/02 P/N 15465:F1 11 Displays 1.4 Displays ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓ 1.5 Alarm - red LED Trouble - yellow LED Supervisory - yellow LED AC Power - green LED Four 7-Segment Displays - red Primary Phone Line Active - red LED Secondary Phone Line Active - red LED 'Kissoff' signal from Central Station - green LED Silence - yellow LED Digital Communicator The integral communicator provides the following functions: ✓ ✓ ✓ ✓ ✓ ✓ 1.6 Line Seizure - takes control of the phone lines disconnecting any premises phones Off/On Hook - perform on and off-hook status to the phone lines Listen for dial tone - 440 hertz tone typical in most networks Dialing the Central Station(s) number - default is Touch-Tone®, programmable to rotary Discern proper 'Ack' and 'Kiss-off' tone(s) - the frequency and time duration of the tone(s) varies with the transmission format. The control panel will adjust accordingly Communicate in the following formats: 12 Tone Burst Types: 20 pps (3+1, 4+1, 4+2, 3+1 Expanded, 4+1 Expanded, 4+2 Expanded) ADM-12 Annunciator Driver Module - Optional The ADM-12 Annunciator Driver Module permits connection of the RZA-5F Remote Annunciator module to the MS-5012 and supervises annunciator wiring for open conditions. The ADM-12 mounts to the MS-5012 main circuit board, occupying one of the two option connectors. FIGURE 1-2: ADM-12/MS-5012 Connect ADM-12 to main circuit board connector J3. Use the supplied nylon spacer. Make all connections with power off. 12 Document #15465 Rev.F1 12/04/02 P/N 15465:F1 RZA-5F Remote Annunciator 1.7 RZA-5F Remote Annunciator The RZA-5F Remote Annunciator mounts on a standard singlegang electrical box and provides LED indications for: ✓ ✓ ✓ ✓ ✓ ✓ FIGURE 1-3: RZA-5F Annunciator Alarm Zone 1 (red) Alarm Zone 2 (red) Alarm Zone 3 (red) Alarm Zone 4 (red) Alarm Zone 5 (red) System Trouble (yellow) A local trouble sounder and tone silence switch are also provided. All LED wiring is supervised for open conditions. Any open will cause the System Trouble LED to turn on. Slide-in paper labels permit an easy change of zone information. The RZA-5F requires the use of the ADM-12 Annunciator Driver Module. 1.8 Specifications AC Power Primary - TB1 Terminals 1 & 2 120 VAC, 50,60 Hz, 0.32 amps 15.0 VAC, 50/60 Hz, 2.0 amps, 25 VA Battery (sealed lead acid only) - Connector J1 Maximum Charging Capacity: 14.3 volts, 0.08 amps Maximum Battery Capacity: 7 AH Initiating Device Circuits - TB2 Terminals 1-2, 9-10, 11-12 Normally Open Contact Zones 1, 4, 5 Power-limited Circuitry Operation: NFPA Style B Normal Operating Voltage: 13.8 VDC (ripple = 100 mV maximum) Short Circuit Current: 4.46 mA maximum Maximum Loop Resistance: 100 ohms End-of-Line Resistor: 2.2K, ½ watt (P/N 27070 UL listed) Standby Current: 2.66 mA Initiating Device Circuits - TB2 Terminals 3-4, 5-8 Detector Zones 2, 3 Power-limited Circuitry Operation: Zone 2 (NFPA Style B), Zone 3 (NFPA Style B, D) Connecting 2-wire detectors on Zone 3 requires NFPA Style B only Normal Operating Voltage: 13.8 VDC (ripple = 100 mV maximum) Alarm Current: 12 mA Short Circuit Current: 24 mA maximum Maximum Detector Current in Standby: 2 mA Maximum Loop Resistance: 30 ohms End-of-Line Resistor: 2.2K, ½ watt (P/N 27070 UL listed) Detector Loop Current is sufficient to ensure operation of one alarmed detector per zone Standby Current: 5.17 mA (including ELR) Document #15465 Rev. F1 12/04/02 P/N 15465:F1 13 Specifications Notification Appliance Circuit - TB3 Terminals 1 & 2 Power-limited Circuitry Nominal Operating Voltage: 12 VDC Requires minimum of 300 mA load Total current available to external devices: 1 amp End-of-Line Resistor: 2.2K, ½ watt (P/N 27070 UL listed) Auxiliary Outputs - TB3 Terminals 4-7 Power-limited Circuitry Type: Open Collector Rating: 40 mA each @ nominal 12 VDC TB3 Terminal 4 Alarm Relay Driver - normally high, active low, sinks up to 40 mA TB3 Terminal 5 Trouble Relay Driver - normally low, active high, sinks up to 40 mA TB3 Terminal 6 Supervisory Relay Driver - normally high, active low, sinks up to 40 mA TB3 Terminal 7 Communicator Failure - normally high, active low, sinks up to 40 mA Four-wire Smoke Detector Power - TB2 Terminals 13 (+) and 14 (-) Power-limited Circuitry Up to 200 mA is available for powering 4-wire smoke detectors Maximum ripple voltage: 100 mV maximum Normal Operating Voltage: 13.8 VDC Nonresettable Power - TB3 Terminal 3 (+) and TB2 Terminal 14 (-) Power-limited Circuitry Available Current: 185 mA Maximum ripple voltage: 100 mV maximum Normal Operating Voltage: 13.8 VDC Telephone Circuitry: Ringer Equivalence Number (REN) = 0.0B AC Impedance 10.0 Mega Ohm Complies with FCC Part 68 Mates with RJ31X Male Connector Supervision Threshold: less than 4.0 volts for 2 minutes The REN is used to determine the quantity of devices which may be connected to the telephone line. Excessive RENs on the telephone line may result in the devices not ringing in response to an incoming call. In most areas (but not all), the sum of the RENs should not exceed five (5.0). To be certain of the number of devices that may be connected to the line, as determined by the total RENs, contact the telephone company to determine the maximum REN for the calling area. 14 Document #15465 Rev.F1 12/04/02 P/N 15465:F1 Specifications Digital Communicator: Before connecting the control panel to the public switched telephone network, the installation of two RJ31X jacks is necessary. The following information is provided if required by the local telephone company: Manufacturer: Fire•Lite Alarms, Inc. One Fire-Lite Place Northford, CT 06472 Product Model Number: MS-5012 FCC Registration Number: 1W6USA-74525-AL-E Ringer Equivalence 0.0B Note: The FCC ID label is located on the inside of the control panel door. Piezo Sounder An on-board piezo sounder will emit three distinctly different audible tones depending on system activity: ✓ Steady on for alarms ✓ One second on and one second off for trouble ✓ ½ second on and ½ second off for supervisory NAC Fault The NFPA Style Y circuit configuration allows for connection of polarized bells, strobes and horns. The wiring to these notification appliances is monitored for opens and shorts. Telephone Company Rights and Warnings The telephone company, under certain circumstances, may temporarily discontinue service and/or make changes in its facilities, services, equipment or procedures which may affect the operation of this control panel. However, the telephone company is required to give advance notice of such changes or interruptions. If the control panel causes harm to the telephone network, the telephone company reserves the right to temporarily discontinue service. Advance notification will be provided except in cases when advance notice is not practical. In such cases, notification will be provided as soon as possible. The opportunity will be given to correct any problems and to file a complaint. DO NOT CONNECT THIS PRODUCT TO COIN TELEPHONE, GROUND START OR PARTY LINE SERVICES. When the control panel activates, premise phones will be disconnected. Two separate phone lines are required. Do not connect both telephone interfaces to the same telephone line. The control panel must be connected to the public switched telephone network upstream of any private telephone system at the protected premises. An FCC compliant telephone cord must be used with this equipment. This equipment is designed to be connected to the telephone network or premises wiring using a compatible RJ31X male modular plug which is Part 68 compliant. Document #15465 Rev. F1 12/04/02 P/N 15465:F1 15 Control Panel Operation CHAPTER 2 Control Panel Operation The MS-5012 has six modes of operation: ✓ ✓ ✓ ✓ ✓ ✓ FIGURE 2-1: Display and Keypad Normal Mode Program Mode Walktest Mode Lamp Test Mode Troubleshoot Mode History Mode Upon initial power-up, the system will be in Normal Mode. This section discusses operation of the control panel in the Normal Mode. Programming is discussed in Chapter 4. Walktest, History and Troubleshoot Modes are discussed in “Servicing” on page 47. 2.1 Switch Functions in Normal Mode u The Reset Switch resets the system and any smoke detectors. Pressing the Reset Switch cause the control panel to: ✓ ✓ ✓ ✓ ✓ ✓ ✓ Clear the display and status LEDs Turn off the Notification Appliance Circuit Reset all zones by temporarily removing power Silence the on board piezo sounder Store 'Reset' message in the History file (see “History Mode” on page 48) Clear all relay driver outputs Temporarily remove power from the resettable power output (TB1 Terminals 13 & 14) Any alarm, supervisory or trouble condition that exists after a system reset, will resound the system, reactivating normal system activity. Upon release of the Reset Switch, the display will rES read for six seconds. v If the Silence Switch is pressed: ✓ ✓ ✓ ✓ The Notification Appliance Circuit will be turned OFF The Silence LED will be turned ON The piezo sounder will be turned OFF 'System Silenced' message will be stored in the History file Upon the occurrence of a subsequent event (alarm or trouble), System Silence is overridden and the control panel will respond to the new event. The System Silence switch will be ignored for waterflow type alarms. 16 Document #15465 Rev.F1 12/04/02 P/N 15465:F1 Displays w Pressing the Mode Switch followed by a valid 4-digit numerical code selects one of the five modes of operation. ☛ To enter Normal Mode from any other mode, press followed by w then 6676 t. 6676 spells NORM on a Touch-Tone ® phone. s The 1st Event switch, along with the Up arrow and Down arrow switches, are used to display any currently active alarm and/or fault conditions present in the system. Press the 1st Event switch at any time to display the 1st event (alarm and/or trouble) that occurred. r q Down arrow - use the Down arrow switch to view other events (older) that have occurred and are active (not yet cleared). Up arrow - use the Up arrow switch to view other events (newer) that have occurred and are active (not yet cleared). t The t switch is not used in Normal Mode. 2.2 Displays Four 7-segment red LED characters provide visual annunciation of status, events and messages. The messages that may appear on the display in Normal Mode are listed below: A A A A A F F F F F F 1 2 3 4 5 1 2 3 4 5 A Alarm Zone 1 Alarm Zone 2 Alarm Zone 3 Alarm Zone 4 Alarm Zone 5 Trouble Zone 1 Trouble Zone 2 Trouble Zone 3 Trouble Zone 4 Trouble Zone 5 Annunciator Fault F E Lo b no b PH 1 PH 2 bELL no 1 no 2 SUP4 AC rES Document #15465 Earth Fault Low Battery No Battery Primary Number Communication Fault Secondary Number Communication Fault Bell Fault Primary Phone Line Fault Secondary Phone Line Fault Supervisory Alarm AC Power Loss Reset Rev. F1 12/04/02 P/N 15465:F1 17 Operation Individual LEDs are provided for: • System Alarm - red LED that lights when an alarm condition is detected • System Trouble - yellow LED indicates that a fault or abnormal condition exists and that the fire alarm system may be inoperative • AC Power ON - green LED that remains on while the AC power supply is operating. If this indicator fails to light under normal conditions, service the system immediately • Supervisory - yellow LED that indicates need for action in connection with the supervision or maintenance of sprinklers, extinguishing systems or other protective systems • System Silence - yellow LED that indicates an Alarm or Trouble has been silenced • Primary Line Active - red LED on the main circuit board that indicates the primary phone line is active • Secondary Line Active - red LED on the main circuit board that indicates the secondary phone line is active • Kiss-off - green LED on the main circuit board that indicates the Central Station has acknowledged receipt of transmitted message FIGURE 2-2: Communicator Connections and LEDs Primary Line Secondary Active LED Secondary Line Kiss-off LED Primary Active LED 2.3 Operation Normal Mode is the standard mode of operation. In this mode, the panel continuously monitors system status. When no alarm or fault conditions exist, the display will be blank and all LEDs will be off (except the AC Power LED). The Notification Appliance Circuit will be off, all relay drivers are deactivated and the on-board piezo sounder will be off. The communicator is not active, and the Primary and Secondary Active LEDs are off. All alarm conditions and fault conditions are annunciated on the control panel's display. The control panel will maintain an 'active event list' as illustrated in “Displays” on page 17. The list will consist of all alarms, supervisory alarms and faults currently active and not cleared, requiring immediate service. When the system is cleared and restored to normal, the display will be blank. All alarms and faults are stored in a history file and may be recalled at any time. Refer to “History Mode” on page 48. 18 Document #15465 Rev.F1 12/04/02 P/N 15465:F1 Operation Higher priority events take precedence over lower priority events. Display of System Activity is accomplished on a priority basis. Priorities are, from highest to lowest: 1. 2. 3. Alarms Supervisory alarms Faults (troubles) The highest priority event will be communicated to the Central Station first. It also is displayed, overriding any other displayed event. Only one event is displayed at a time. Whenever multiple events occur, an authorized user may view each event by pressing the Up and Down arrow switches on the keypad. At any time, the user may press the 1st Event switch to display the first event that occurred (that is, the first event that occurred after the panel was last reset, cleared of all active events and placed into Normal Mode). If the events to be displayed are alarms only (no troubles), the control panel will scroll them on the display. Pressing the 1st Event switch will stop the scrolling and cause the display of the first alarm that occurred. Operation of the Up and Down arrow switches will display all remaining alarms in sequence. Alarm Response The MS-5012 will, upon detection of an alarm condition, perform the following functions: ✓ ✓ ✓ Turn the alarm LED on Activate the alarm relay driver (TB3-4) Display an alarm message as follows: A A A A ✓ ✓ ✓ ✓ 1 2 3 5 Alarm Zone 1 Alarm Zone 2 Alarm Zone 3 Alarm Zone 5 (Note that when Zone 4 is programmed as a supervisory zone, it will not be processed in the same manner as a conventional alarm one. See 'System Supervisory Condition' later in this section.) Communicate the alarm to the Central Station Store the alarm in the History file Turn the Notification Appliance Circuit on Turn the piezo sounder on Alarm Restoral The control panel returns to normal only after all alarms have been cleared (pull stations reset, smoke detectors reset and no smoke is present, waterflow has stopped) and the Reset switch has been pressed. The control panel will perform the following upon restoral of all active alarms: ✓ ✓ ✓ ✓ ✓ ✓ Turn off the alarm LED Deactivate the alarm relay driver (TB3-4) Clear the 4- character display Send all 'Zone Restoral' messages to the Central Station Turn off the Notification Appliance Circuit Turn off the piezo sounder Document #15465 Rev. F1 12/04/02 P/N 15465:F1 19 Operation System Supervisory Condition Zone 4 is factory programmed as a supervisory zone. This zone is primarily used in applications where a waterflow sensing device has been employed and the wiring to the waterflow valve and/or a tamper switch is monitored. If the wiring is cut, a trouble condition will occur. If the Normally Open tamper switch is activated, a supervisory condition will occur. When a supervisory condition occurs, the control panel will: ✓ ✓ Turn on the supervisory LED Activate the supervisory relay driver (TB3-6) ✓ Display the following message - SUP4 ✓ Communicate the supervisory condition to the Central Station Store 'supervisory' message in the History file Pulse the piezo sounder at ½ second On, ½ second Off rate ✓ ✓ When the supervisory condition has been cleared (normal condition is restored and the Reset switch has been pressed), the MS-5012 will perform the following: ✓ ✓ Turn off the supervisory LED Deactivate the supervisory relay driver (TB3-6) ✓ Clear the display of the message - SUP4 ✓ Communicate the 'supervisory restoral' message to the Central Station Shut off the piezo sounder ✓ Trouble Conditions The control panel will perform the following upon detection of a trouble condition: ✓ ✓ ✓ Turn on the trouble LED Activate the trouble relay driver (TB3-5) Display the appropriate trouble message. Following are the trouble messages shown in order of priority, from the highest priority to the lowest: AC F 1 F 3 F 2 F 5 F 4 F E L b no b no 1 no 2 bELL PH 1 PH 2 F A rES 20 AC Loss (must press Up arrow, Down arrow or 1st Event to view) Trouble on Zone 1 Trouble on Zone 3 Trouble on Zone 2 Trouble on Zone 5 Trouble on Zone 4 Ground Fault Low battery No battery Primary Phone Line Fault Secondary Phone Line Fault Bell Circuit (NAC) Fault Primary Number Communication Fault Secondary Number Communication Fault Annunciator Fault Reset Document #15465 Rev.F1 12/04/02 P/N 15465:F1 Digital Communicator ✓ ✓ ✓ Communicate the trouble condition to the Central Station Store the trouble condition in the History file Sound the piezo sounder one second On, one second Off Note: When AC Brownout occurs, the AC LED turns off and the Trouble LED turns on. Should the brownout condition remain, it will be transmitted to the Central Station after a delay (see Program Address 55 in “Programming” on page 36). Trouble Condition Restoral The control panel performs the following upon restoral of a trouble condition: ✓ ✓ ✓ ✓ ✓ Turn off the trouble LED Deactivates the trouble relay driver (TB3-5) Turn on the AC LED upon restoral, if the trouble was loss of AC power Clear the display of the trouble message Communicate the restored trouble condition to the Central Station OFF Normal Reporting Removing the panel from Normal Mode, and placing it into any other mode, causes a transmission of an 'Off Normal' fault message to the Central Station. Returning the panel to Normal Mode causes a transmission of a 'Return to Normal' restoral message. 2.4 Digital Communicator The MS-5012 transmits zone and system status reports to the Central Station via the public switched telephone network. Two supervised telephone line connections are made to interface the control panel to the telephone lines. Two optional 7-foot telephone cords are available for this purpose. Refer to Figure 3-6, “Wiring Phone Jacks,” on page 30, for proper wiring. The control panel supervises both telephone lines for proper voltage. A delay of two minutes will occur before a fault in either phone line connection is reported as a trouble. When a fault is detected, an audible trouble signal will sound, the yellow trouble LED will turn on, the 4-character display will show either no1 for Primary Line or no 2 for Secondary Line, depending upon which telephone line has the fault, and the trouble condition will be reported to the Central Station over the remaining operational phone line. The control panel comes with line seizure capability provided to both the primary and secondary telephone line interfaces. Any time the control panel needs to make a call to the Central Station, line seizure will disconnect any local premises phones sharing the same telephone line. All transmissions to the Central Station will be sent over the Primary phone line. In the event of noisy phone lines, transmissions will be sent over the backup Secondary phone line. Two phone numbers must be programmed, the primary phone number and the secondary phone number. See “Programming” on page 36. All system reports will be transmitted to the primary phone number. Reports will automatically be sent to the secondary phone number if attempts to transmit to the primary phone number are unsuccessful. If 10 attempts to communicate are unsuccessful, the Communicator Failure output will be turned on (TB3, Terminal 7). Note that as an option, all reports may be sent to the secondary phone number. Document #15465 Rev. F1 12/04/02 P/N 15465:F1 21 Digital Communicator The MS-5012 meets NFPA 72 National Fire Alarm Code for Central Station Fire Alarm Systems and for Remote Station Protective Fire Alarm Systems reporting requirements for: (a) the type of signal (b) condition (c) location of the reporting premises. The general priority reporting structure is: 1. 2. 3. 4. Zone Alarms and Restorals Zone Troubles and Restorals System Troubles and Restorals 24-hour test The control panel is capable of reporting detailed messages depending upon the communication format is use. Table 4-1 through Table 4-4 list these messages. Table 2-1 shows the reporting structure for all of the tone burst type formats. TABLE 2-1: 22 Format Selection Addresses (16 & 42) Format # 2, 4, 6, 8 Format # 3, 5, 7, 9 Format # A, C Format # B, D Report 3+1/4+1 Standard 3+1/4+1/Expanded 4+2/Standard 4+2/Expanded Alarm SSS(S) A SSS(S) A AAA(A) Z SSSS AA2 SSSS AZ Alarm Restore SSS(S) RA SSS(S) RA RARARA(RA) Z SSSS RARA2 SSSS RAZ Zone Trouble (Zone Open) SSS(S) TZ SSS(S) TZ SSSS TZTZ2 SSSS TZZ Zone Trouble Restore SSS(S) RTZ SSS(S) RTZ RTZRTZRTZ(RTZ) Z SSSS RTZRTZ2 SSSS RTZZ System Trouble SSS(S) TS SSS(S) TS TSTSTS(TS) Y SSSS TSTS2 SSSS TSY System Trouble Restore SSS(S) RTS SSS(S) RTS RTSRTSRTS(RTS) Y SSSS RTSRTS2 SSSS RTSY Low Battery SSS(S) L SSS(S) L SSSS LL2 SSSS LL2 Low Battery Restore SSS(S) RL SSS(S) RL SSSS RLRL2 SSSS RLRL2 AC Loss SSS(S) P SSS(S) P SSSS PP2 SSSS PP2 AC Loss Restore SSS(S) RP SSS(S) RP SSSS RPRP2 SSSS RPRP2 Supervisory Condition SSS(S) V SSS(S) V VVV(V) Z SSSS VV2 SSSS VV2 Supervisory Condition Restore SSS(S) RV SSS(S) RV RVRVRV(RV) Z SSSS RVRV2 SSSS RVZ Test Report SSS(S) X SSS(S) X SSSS XX2 SSSS XX2 Document #15465 Rev.F1 12/04/02 P/N 15465:F1 Digital Communicator Following is a description of the terms used in the reporting structure in Table 2-1 . SSS or SSSS A A2 Z RA RA2 TZ TZ2 RTZ RTZ2 TS TS2 RTS RTS2 L L2 RL RL2 P P2 RP RP2 V V2 RV RV2 X X2 Y = Subscriber ID = Alarm (1st digit) = Alarm (2nd digit) = Zone Number = Alarm Restore (1st digit) = Alarm Restore (2nd digit) = Zone Trouble (1st digit) = Zone Trouble (2nd digit) = Zone Trouble Restore (1st digit) = Zone Trouble Restore (2nd digit) = System Trouble (1st digit) = System Trouble (2nd digit) = System Trouble Restore (1st digit) = System Trouble Restore (2nd digit) = Low Battery (1st digit) = Low Battery (2nd digit) = Low Battery Restore (1st digit) = Low Battery Restore (2nd digit) = AC Loss (1st digit) = AC Loss (2nd digit) = AC Loss Restore (1st digit) = AC Loss Restore (2nd digit) = Supervisory Condition (1st digit) = Supervisory Condition (2nd digit) = Supervisory Condition Restore (1st digit) = Supervisory Condition Restore (2nd digit) = Test Report (1st digit) = Test Report (2nd digit) = 6 = AC Loss = 7 = Ground Fault = 8 = Low Battery = 9 = No Battery = A = Telco Primary Line Fault = B = Telco Secondary Line Fault = C = Main Bell (NAC) Fault, Annunciator Fault = D = Communication Fault to Primary Number = E = Communication Fault to Secondary Number = F = System Off Normal Fault/System Fault (See “Slave Communicator Configuration” on page 51) Note: For Expanded Reporting, the control panel automatically adds the digit corresponding to the zone number, and the second digit corresponding to any system trouble condition. Only the first digit is programmable. Document #15465 Rev. F1 12/04/02 P/N 15465:F1 23 Digital Communicator Transmittal Priorities The integral communicator transmits highest priority events first. Events in terms of priority are listed below in descending order: 1. 2. 3. 4. 5. Alarms (Highest Priority Level) Pull Stations Waterflow Smoke Detectors Other Alarm Types Supervisory Zone Faults AC Fail Zonal Faults Earth Fault Low Battery/No Battery Telephone Line Fault Bell Circuit (NAC) Fault Communication Trouble Annunciator Trouble Restoral AC Zones Earth Battery Telephone Line Bell (NAC) Communication Annunciator Trouble 24-Hour Test (Lowest Priority) LED Indicators Red LEDs are provided on the control panel circuit board to identify which telephone line is activated. A green LED labeled 'Kissoff', will turn on whenever the control panel has successfully transmitted reports to the Central Station. The 'Kissoff' LED may turn on several times during communications. 24 Document #15465 Rev.F1 12/04/02 P/N 15465:F1 Digital Communicator UL Listed Receivers Compatible with the MS-5012 The following table lists the UL listed receivers which are compatible with the MS-5012 Control Panel. 0 Not Used 1 Not Used 2 3+1/Standard/1800/2300 ✔ ✔ ✔ ✔ ✔ 3 3+1/Expanded/1800/2300 ✔ ✔ ✔ ✔ 4 3+1/Standard/1900/1400 ✔ ✔ 5 3+1/Expanded/1900/1400 ✔ ✔ 6 4+1/Standard/1800/2300 ✔ ✔ 7 4+1/Expanded/1800/2300 ✔ 8 4+1/Standard/1900/1400 9 Surguard MLR-2 (8) ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ ✔ 4+1/Expanded/1900/1400 ✔ ✔ ✔ ✔ ✔ ✔ A 4+2/Standard/1800/2300 ✔ ✔ ✔ ✔ ✔ ✔ B 4+2/Expanded/1800/2300 ✔ ✔ ✔ ✔ ✔ ✔ C 4+2/Standard/1900/1400 ✔ ✔ ✔ ✔ ✔ ✔ D 4+2/Expanded/1900/1400 ✔ ✔ ✔ ✔ ✔ ✔ E Not Used F Not Used ✔ ✔ ✔ (5, 6) Sescoa 3000R (7) Radionics 6000/6500 (5) Osborne Hoffman Models 1 & 2 FBI CP220FB (4) ITI CS-4000 (3) Format # (Addresses 16 & 42) Silent Knight 9000 (2) Compatible UL Listed Receivers Ademco 685 (1) TABLE 2-2: ✔ (5) ✔ (5) (1) With 685-8 Line Card with REV. 4.4d software (2) With 9002 Line Card Rev. 9035 software or 9032 Line Card with 9326A software (3) Rev. 4.0 software (4) FBI CP220FB Rec-11 Line Card with Rev. 2.6 software and a memory card with Rev. 3.8 software (5) Model 6500 with Rev. 600 software (6) Model 6000 with Rev. 204 software (7) With Rev. B control card at Rev. 1.4 software and Rev. C line card at Rev. 1.5 software (8) Version 1.62 software Document #15465 Rev. F1 12/04/02 P/N 15465:F1 25 Installation Installation CHAPTER 3 3.1 Cabinet Mounting Options The cabinet may be either semi-flush or surface mounted. The cover is removable during the installation period. The cabinet mounts using two key slots and two additional 0.250" diameter holes located in the backbox. The key slots are located at the top of the backbox and the two securing holes at the bottom. Refer to Figure 3-1 for cabinet dimensions. FIGURE 3-1: Cabinet Dimensions and Knockout Locations Top 6.000" (15.240 cm) 0.875“ (2.223 cm) 2.000" (5.080 cm) 1.125“ (2.858 cm) 1.250" (3.175 cm) 3.000" (7.620 cm) 12.500" (31.750 cm) Left 0.624" (1.585 cm) 12.500" (31.750 cm) 6.500" (16.510 cm) Right 1.250" (3.175 cm) 3.250” (8.255 cm) 1.750” (4.445 cm) 9.830" (24.968 cm) Cabinet Mounting Holes 5.250” (13.335 cm) 14.500" (36.830 cm) 1.250” (3.175 cm) 3.000” (7.620 cm) 10.000” (25.400 cm) 16.625" 12.625" 3.000” (7.620 cm) 1.250” (3.175 cm) Bottom 14.625" 17.625" TR-3-R (MS-5012) Trim Ring Draw wires through the respective knockout locations. 26 Document #15465 Rev.F1 12/04/02 P/N 15465:F1 Input Circuits 3.2 Input Circuits The MS-5012 has five zone input circuits. The maximum loop resistance limit for each circuit is 100 ohms. All field wiring for each zone is supervised for opens and ground faults. Both conditions are visually and audibly annunciated as well as communicated to the Central Station. • Zone 1 is a Style B Initiating Device Circuit (IDC) designed to accept any Normally Open contact device on TB2, Terminals 1 & 2. It is power-limited to 2.66 mA in standby and 4.46 mA in alarm. The factory default is 'Pull Station'. Refer to “Programming Instructions” on page 35. • Zone 2 is a Style B Initiating Device Circuit designed to accept any Normally Open contact device and conventional 2-wire, 12 volt smoke detectors on TB2, Terminals 3 & 4. It is power-limited to 7.17 mA in standby and 24 mA in alarm. For a list of compatible 2-wire detectors refer to the Fire•Lite Device Compatibility Document. The factory default is '2-wire Detectors'. Refer to “Programming Instructions” on page 35. • Zone 3 is a Style D Initiating Device Circuit. It is designed to accept any Normally Open contact devices, 2wire smoke detectors (Style B only) and waterflow sensing devices on TB2, Terminals 5 - 8. It is power-limited to 7.17 mA in standby and 24 mA in alarm. A maximum of five waterflow devices may be used per NFPA 71. For a list of compatible 2-wire detectors, refer to the Fire•Lite Device Compatibility Document. The factory default is 'waterflow'. Refer to “Programming Instructions” on page 35. Note: When Zone 3 is programmed to accept 2-wire smoke detectors, it will only function as an NFPA Style B Initiating Device Circuit. See Figure 3-2. • Zone 4 is a Style B Initiating Device Circuit designed to function as a supervisory zone or may accept any Normally Open contact device on TB2, Terminals 9 & 10. As a supervisory zone, the circuit may or may not be able to detect a supervisory alarm condition after the occurrence of an open in the loop wiring. It is powerlimited to 2.66 mA in standby and 4.46 mA in alarm. Factory default is 'Supervisory'. Refer to “Programming Instructions” on page 35. • Zone 5 is a Style B Initiating Device Circuit designed as a general purpose 'initiating zone'. It will accept any Normally Open contact device on TB2, Terminals 11 & 12. It’s power-limited to 2.66 mA in standby and 4.46 mA in alarm. Factory default is '4-wire Smoke Detector'. Refer to “Programming Instructions” on page 35. Four wire smoke detectors may be connected to any zone. Resettable power is provided via TB2, Terminals 13 & 14. See Figure 3-2 for proper connection of 4-wire detectors. It is allowable to mix an assortment of device types on any zone, however, it is not recommended. By not mixing device types on one zone, messages sent to the Central Station may be very specific and detailed. FIGURE 3-2: Initiating Device Circuits - TB2 Zone 1 Pull Stations Zone 2 2-Wire Smoke Detectors Zone 3 Waterflow Devices Zone 4 Supervisory Tamper Switches 2-Wire Smoke Detectors Zone 3 TB2 Zone 3 Connection of 2-Wire Smoke Detectors, Style B Only. 4-Wire Smoke Detectors Zone 5 TB2 UL Listed Supervision Relay P/N A77-716-01 Document #15465 Rev. F1 12/04/02 P/N 15465:F1 27 Output Circuits For example, default programming provides the following: • Zone 1 activation will be reported to the Central Station as 'Manual Pull Station Alarm' • Zone 4 activation will be reported to the Central Station as 'Supervisory Alarm' • Zone activation, for reporting formats that do not allow for detailed reports, will be reported to the Central Station as 'Zone 1 Alarm' or 'Zone 4 Alarm'. Refer to “Operation” on page 18 and “Programming” on page 36 for additional information. 3.3 Output Circuits One Style Y Notification Appliance Circuit is provided. This supervised circuit allows for the powering of polarized bells, strobes and horns in an alarm condition. Up to one amp of special purpose power is available. For a list of compatible devices, refer to the Fire•Lite Device Compatibility Document. A minimum 300 mA load is required. FIGURE 3-3: Output Circuits - TB3 Notification Appliances (Bells) +13.8 VDC General Alarm Open Collector Outputs General Trouble Supervisory Communication Fail Note: Active Low 40 mA each (max.) TB3 Two RJ31X style phone jacks are provided for the connection of two independent telephone lines. Telephone line control/command is possible via double line seizure. Refer to Figure 3-6 on page 30. Relay driver outputs, which can be used to drive UL-864 listed remote relays, are available for Alarm, Trouble, Supervisory and Communicator Failure. Refer to Figure 3-4 FIGURE 3-4: Driving Relays From Open Collector Outputs UL Recognized Enclosure +13.8 VDC General Alarm General Trouble Supervisory TB3 Communication Fail Relays 28 Document #15465 Rev.F1 12/04/02 P/N 15465:F1 UL Power-limited Wiring Requirements The control panel's open collector outputs on Terminal TB3 can be used to activate UL-864 listed remote relays. Outputs are rated for 40 mA. The normal condition for each output is as shown below: TABLE 3-1: Output Normal Conditions Output Condition TB3-4 Alarm Off (deenergized) TB3-5 Trouble On (energized) TB3-6 Supervisory Off (deenergized) TB3-7 Communications Failure Off (deenergized) Relays must be placed in a UL-864 recognized enclosure. Wiring from the control panel's terminals on TB3 to the relays must be less than 3 feet (90 cm) in length and enclosed in conduit. Wiring from the relay outputs must remain in the same room as the location of the relay enclosure and be enclosed in conduit. 3.4 UL Power-limited Wiring Requirements Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25" (6.35 mm) away from any nonpower-limited circuit wiring. Furthermore, all power-limited circuit wiring and nonpower-limited circuit wiring must enter and exit the cabinet through different knockouts and/or conduits. A typical wiring configuration for the MS-5012 is shown in Figure 3-5. FIGURE 3-5: Typical Wiring Diagram for UL Power-limited Requirements Power-limited Circuits 123456789 ADM-12 Secondary Active TB2 Power-limited Circuits (optional) Kissoff Primary Active T1 Power-limited Circuits TB3 TB1 750 mA Max charger output J1 AC Power Document #15465 Rev. F1 12/04/02 P/N 15465:F1 29 Digital Communicator 3.5 Digital Communicator Two independent telephone lines can be connected to the MS-5012. Telephone line control/command is made possible via double line seizure as well as usage of RJ31X style interconnections. Note: It is critical that the panel's digital communicator be located as the first device on the incoming telephone circuit to properly function. The control panel's digital communicator is built right into the main circuit board. All that is required to install the system is the connection and wiring of two phone lines as shown in Figure 3-6. FIGURE 3-6: Wiring Phone Jacks (Primary Lines) Incoming Telco Phone Lines Tip Ring Tip Green Wire Green Wire Red Wire Ring Ring To Premises Phone Ring Red Wire (Secondary Lines) Incoming Telco Phone Lines To Premises Phone Tip Tip Note: Shorting bars inside RJ31X Jack removed during male plug insertion Primary Phone Line PH-1 7 Foot Cable (MCBL-7) (not supplied - order separately) Secondary Phone Line PH-2 Male Plug Connectors Modular Female Connectors MS-5012 30 Document #15465 Rev.F1 12/04/02 P/N 15465:F1 Operating Power 3.6 Operating Power 3.6.1 Primary Power Source (AC) and Earth Ground Connections AC power connections are made inside the control panel cabinet. Primary power source is 120 VAC, 50/60 Hz, 0.32 amps. A pair of wires, with a ground conductor, should be connected from the protected premises main breaker box to the black and white primary leads of the MS-5012 system transformer. As per the National Electric Code, use 14 AWG (2.0 mm2) or heavier gauge wire with 600V insulation. No other equipment may be connected to this circuit. In addition, this circuit must be provided with overcurrent protection and may not contain any power disconnect devices. Connect the backbox ground stud to a solid earth ground (a metallic cold water pipe may be suitable in some installations). This connection is vital for maintaining the control panel's immunity to unwanted electrical transients generated by lightning and electrostatic discharge. 3.6.2 Secondary Power Source (batteries) Observe polarity when connecting the battery. Connect the battery cable to J1 on the main circuit board using the plug-in connector provided. The battery charger is current-limited and capable of recharging sealed lead acid type batteries. The charger shuts off when the system is in alarm. CAUTION: Battery contains sulfuric acid which can cause severe burns to the skin and eyes and can destroy fabrics. If contact is made with sulfuric acid, immediately flush the skin or eyes with water for 15 minutes and seek immediate medical attention. FIGURE 3-7: MS-5012 Power Connections Document #15465 Rev. F1 12/04/02 P/N 15465:F1 31 Operating Power 3.6.3 Optional AC Terminal Block An optional AC terminal block is available for the MS-5012 Control Communicator. The terminal block can only be used on the larger backbox [14.5" (36.83 cm) x 12.5" (31.75 cm) x 2.875" (7.303 cm)]. It cannot be installed in the smaller backbox [12.0" (30.48 cm) x 9.0" (22.86 cm) x 2.75" (6.985 cm)]. ! WARNING: Make certain all power (AC and battery) is removed before any connections are made. 1. 2. 3. 4. 5. 6. 7. 8. Mount the optional AC terminal block to the lower left of the MS-5012 backbox using the two supplied screws. Connect AC power wiring to the optional terminal block as shown in Figure 3-8. Connect the black and white wires (primary) from the MS-5012 system transformer to the optional terminal block as illustrated in Figure 3-8. Make certain the black AC wire (Hot) is connected opposite the black transformer wire and the white AC wire (Neutral) is connected opposite the white transformer wire. Make certain that the yellow wires (secondary) from the MS-5012 system transformer are connected to Terminal Block TB1 located in the lower left corner of the MS-5012 main circuit board. Install a jumper between the terminal block and the backbox ground stud as illustrated in Figure 3-8. This will be used to provide lightning protection to the panel. Make certain the jumper is connected opposite the green AC ground wire on the terminal block. Install a solid earth ground connection to the backbox ground stud as illustrated below. This will be used to provide lightning protection to the panel. Press the AC terminal cover firmly into place. Reapply AC and battery power to the MS-5012 Control Communicator. FIGURE 3-8: Optional AC Terminal Block Installation MS-5012 Main Circuit Board MS-5012 Backbox 32 Document #15465 Rev.F1 12/04/02 P/N 15465:F1 Optional Boards 3.7 Optional Boards 3.7.1 ADM-12 Annunciator Driver Module FIGURE 3-9: ADM-12 Module The Annunciator Driver Module supports the RZA-5F Remote Annunciator module. Annunciator wiring is supervised for open conditions by this module. The ADM-12 mounts to the MS-5012 main circuit board, occupying one of the two option connectors (refer to “ADM-12 Annunciator Driver Module - Optional” on page 12). 3.7.2 RZA-5F Remote Annunciator The RZA-5F mounts on a standard single-gang electrical box and provides LED indications of the following: • • • • • • FIGURE 3-10:RZA-5F Remote Annunciator Alarm Zone 1 (red) Alarm Zone 2 (red) Alarm Zone 3 (red) Alarm Zone 4 (red) Alarm Zone 5 (red) System Trouble (yellow) In addition, the remote annunciator provides a local piezo sounder and a remote sounder shut off switch. All LED wiring is supervised for open conditions. Any open condition will cause the System Trouble LED to illuminate and the piezo to sound. Note that the RZA-5F Remote Annunciator requires the use of an ADM-12 Annunciator Driver Module. The following figures illustrate the mounting of the RZA-5F and the wiring of the RZA-5F to the ADM-12. FIGURE 3-11:Mounting the RZA-5F to Single-Gang Electrical Box Screw #6-32 X 1.00” LG Document #15465 Rev. F1 12/04/02 P/N 15465:F1 33 Optional Boards FIGURE 3-12:Wiring the RZA-5F to the ADM-12 12 VDC ADM-12 Note: Make wiring connections with system power off. Maximum wire impedance is 100 ohms per wiring connection. RZA-5F 34 Document #15465 Rev.F1 12/04/02 P/N 15465:F1 Programming Instructions CHAPTER 4 Programming Instructions Programming of the MS-5012 is possible at any time except when an alarm condition is present in the Normal Mode of operation. The MS-5012 has been designed for many different types of applications. After examining your specific application, review the programming options and choose the entries best suited for your system. The MS-5012 has a built-in programmer. All programming selections are stored in nonvolatile EEPROM (Electrically-Erasable Programmable Read-Only Memory). This ensures that the control panel will remember all entries in programming mode even if both AC and battery power are removed. The user must program the primary and secondary phone numbers, account numbers and 24 hour test report times for each Central Station account and the current time. The control panel comes with factory chosen options/features already programmed. Alternate options/features may be programmed if desired. If all factory default settings are acceptable, programming is complete. 4.1 Entering Program Mode w key once (the display will go blank). The user then has ten seconds to start entering the Program Mode code 7764. ☛ 7764 spells PROG on a Touch-Tone phone. To enter Program Mode, press the ® t key. Note that as information If an incorrect key is entered, reenter the proper 4-digit code before pressing the is entered from the keypad, the digits will scroll across the display from right to left. 7 77 776 7764 You are allowed a pause of up to 10 seconds in between each number while entering the code. The control panel will then be in Program Mode with 00 F in the display. A maximum delay of 10 minutes is allowed at this point, before beginning programming, otherwise, the control panel will return to Normal Mode. A maximum of 10 minutes is also allowed between key strokes. While in Programming Mode, the trouble LED will be on, the trouble relay driver will be activated, but the communicator will not be activated to report this trouble. Transmissions started before entering Program Mode will continue during programming. The first three locations from the left represent the memory address which can range from '00' to '243' (alpha characters are not used). The last location (digit farthest right) represents the contents of the memory address. The first address which will be displayed is illustrated in Figure 4-1. FIGURE 4-1: First Address 00 F address data Document #15465 Rev. F1 12/04/02 P/N 15465:F1 35 Switch Functions in Program Mode 4.2 Switch Functions in Program Mode FIGURE 4-2: Switch Functions in Program Mode No function in Program Mode u v w 123f q 456e r 789d s a0bc t These keys can be used for address entry and/or data entry 4.3 Select operating mode Increment memory address Decrement memory address 1st Press - First memory address 2nd Press - Type any address Save data, and then display next address Programming 4.3.1 Programming the Primary Phone Number (00 - 15) Sixteen addresses are set aside for the primary phone number, with 'F' being the factory default. Programming is typically done as follows: ✓ If your phone number is 484-7161, press 4 ✓ The display will read 00_4 t to save the entry to memory and increment to the next address which is 01_F ✓ Press ✓ Enter the remaining numbers in their respective addresses as shown below: Entry 4 8 4 7 Address 00 01 02 03 1 6 1 F F F F 04 05 06 07 08 09 10 F F F 11 12 13 F F 14 15 Valid entries are 0 - F with the numeric digits as dialed numbers and the alpha digits indicating the following: A = * on a Touchtone phone keypad B = # on a Touchtone phone keypad C = look for secondary dial tone for up to two seconds (then dial anyway) D = three second pause E = five second pause F = end of phone number 36 Document #15465 Rev.F1 12/04/02 P/N 15465:F1 Programming 4.3.2 Programming Primary Number Communication Format (16) One location is needed to select the Communication Format for the primary phone number. Address 16 is used for this purpose. The default (factory setting) for this address is 'A', which is 4+2 Standard, 1800 Hz 'Carrier', 2300 Hz 'ACK'. Formats '2' through 'D' may be entered in place of the default value, followed by the [ENTER/ STORE] key. '0' through 'F' represent the following formats: 0: Not used 1: Not used 2: 3+1 Standard 1800 Hz Carrier, 2300 Hz ACK 3: 3+1 Expanded 1800 Hz Carrier, 2300 Hz ACK 4: 3+1 Standard 1900 Hz Carrier, 1400 Hz ACK 5: 3+1 Expanded 1900 Hz Carrier, 1400 Hz ACK 6: 4+1 Standard 1800 Hz Carrier, 2300 Hz ACK 7: 4+1 Expanded 1800 Hz Carrier, 2300 Hz ACK 8: 4+1 Standard 1900 Hz Carrier, 1400 Hz ACK 9: 4+1 Expanded 1900 Hz Carrier, 1400 Hz ACK A: 4+2 Standard 1800 Hz Carrier, 2300 Hz ACK B: 4+2 Expanded 1800 Hz Carrier, 2300 Hz ACK C: 4+2 Standard 1900 Hz Carrier, 1400 Hz ACK D: 4+2 Expanded 1900 Hz Carrier, 1400 Hz ACK E: Not used F: Not used Note: Consult your Central Station for proper selection or consult our factory representatives. For any format chosen, the MS-5012 automatically programs all of the event codes. Refer to Table 4-1 and Table 4-2 . 3+1 and 4+1 Standard and Expanded, 4+2 Expanded Formats If '2, 3, 4, 5, 6, 7, 8, 9, B or D' are entered for address 16, the following data is automatically programmed for the Primary phone number event codes. Enter '0' for the Setting to disable the report. TABLE 4-1: 3+1 and 4+1 Standard and Expanded, 4+2 Expanded Formats Address Factory Settings Description 68 Primary # Zone 1 Alarm Code 1 69 Primary # Zone 2 Alarm Code 1 70 Primary # Zone 3 Alarm Code 1 71 Primary # Zone 4 Alarm Code 8 72 Primary # Zone 5 Alarm Code 1 73 Primary # AC Fault Code F 74 Primary # Zone 1 Fault Code F 75 Primary # Zone 2 Fault Code F 76 Primary # Zone 3 Fault Code F 77 Primary # Zone 4 Fault Code F 78 Primary # Zone 5 Fault Code F 79 Primary # Earth Ground Code F 80 Primary # Low Battery Code F 81 Primary # No Battery Code F 82 Primary # Telco Primary Line Fault Code F 83 Primary # Telco Secondary Line Fault Code F 84 Primary # Bell Fault Code F Document #15465 Rev. F1 12/04/02 P/N 15465:F1 37 Programming TABLE 4-1: 3+1 and 4+1 Standard and Expanded, 4+2 Expanded Formats Address Factory Settings Description 85 Primary # Communication Trouble Primary Number F 86 Primary # Communication Trouble Secondary Number F 87 Primary # Annunciator Fault Code F 88 Primary # System Off Normal Code F 89 Primary # Zone 1 Alarm Restoral Code E 90 Primary # Zone 2 Alarm Restoral Code E 91 Primary # Zone 3 Alarm Restoral Code E 92 Primary # Zone 4 Alarm Restoral Code E 93 Primary # Zone 5 Alarm Restoral Code E 94 Primary # AC Fault Restoral Code E 95 Primary # Zone 1 Fault Restoral Code E 96 Primary # Zone 2 Fault Restoral Code E 97 Primary # Zone 3 Fault Restoral Code E 98 Primary # Zone 4 Fault Restoral Code E 99 Primary # Zone 5 Fault Restoral Code E 100 Primary # Earth Ground Restoral Code E 101 Primary # Low Battery Restoral Code E 102 Primary # No Battery Restoral Code E 103 Primary # Telco Primary Line Fault Restoral Code E 104 Primary # Telco Secondary Line Fault Restoral Code E 105 Primary # Bell Fault Restoral Code E 106 Primary # Communication Trouble Restoral Primary Number E 107 Primary # Communication Trouble Restoral Secondary Number E 108 Primary # Annunciator Fault Restoral E 109 Primary # System Return to Normal Code E 110 Primary # 24 Hour Test Code 9 111 Primary # System Abnormal Test Report F 4+2 Standard Format If 'A' or 'C' are entered for address 16, the following data is automatically programmed for the Primary phone number event codes. Enter '00' for the Setting to disable the report. 4.3.3 Programming the Primary Number Account Code (17-20) A unique Account Code is provided by the Central Station. The Primary Number Account Code takes up four locations at addresses 17-20. The defaults are all '0s'. Valid entries are 0-9 and A-F. The number of digits entered must match the format selection. If programming '2, 3, 4 or 5' into address 16, enter the three digit Account Code provided by the Central Station (location 20 is ignored). If programming '6, 7, 8, 9, A, B, C or D' into address 16, enter the four digit Account Code. 38 Document #15465 Rev.F1 12/04/02 P/N 15465:F1 Programming TABLE 4-2: 4+2 Standard Formats Address Factory Settings Description 68-69 Primary # Zone 1 Alarm Code 11 70-71 Primary # Zone 2 Alarm Code 12 72-73 Primary # Zone 3 Alarm Code 13 74-75 Primary # Zone 4 Alarm Code 84 76-77 Primary # Zone 5 Alarm Code 15 78-79 Primary # AC Fault Code F6 80-81 Primary # Zone 1 Fault Code F1 82-83 Primary # Zone 2 Fault Code F2 84-85 Primary # Zone 3 Fault Code F3 86-87 Primary # Zone 4 Fault Code F4 88-89 Primary # Zone 5 Fault Code F5 90-91 Primary # Earth Ground Code F7 92-93 Primary # Low Battery Code F8 94-95 Primary # No Battery Code F9 96-97 Primary # Telco Primary Line Fault Code FA 98-99 Primary # Telco Secondary Line Fault Code FB 100-101 Primary # Bell Fault Code FC 102-103 Primary # Communication Trouble Primary Number FD 104-105 Primary # Communication Trouble Secondary Number FE 106-107 Primary # Annunciator Fault Code FC 108-109 Primary # System Off Normal Code FF 110-111 Primary # Zone 1 Alarm Restoral Code E1 112-113 Primary # Zone 2 Alarm Restoral Code E2 114-115 Primary # Zone 3 Alarm Restoral Code E3 116-117 Primary # Zone 4 Alarm Restoral Code E4 118-119 Primary # Zone 5 Alarm Restoral Code E5 120-121 Primary # AC Fault Restoral Code E6 122-123 Primary # Zone 1 Fault Restoral Code E1 124-125 Primary # Zone 2 Fault Restoral Code E2 126-127 Primary # Zone 3 Fault Restoral Code E3 128-129 Primary # Zone 4 Fault Restoral Code E4 130-131 Primary # Zone 5 Fault Restoral Code E5 132-133 Primary # Earth Ground Restoral Code E7 134-135 Primary # Low Battery Restoral Code E8 136-137 Primary # No Battery Restoral Code E9 Document #15465 Rev. F1 12/04/02 P/N 15465:F1 39 Programming TABLE 4-2: 4+2 Standard Formats Address 138-139 Factory Settings Description Primary # Telco Primary Line Fault Restoral Code EA 140-141 Primary # Telco Secondary Line Fault Restoral Code EB 142-143 Primary # Bell Fault Restoral Code EC 144-145 Primary # Communication Trouble Restoral Primary Number ED 146-147 Primary # Communication Trouble Restoral Secondary Number EE 148-149 Primary # Annunciator Fault Restoral EC 150-151 Primary # System Return to Normal Code EF 152-153 Primary # 24 Hour Test Code 99 154-155 Primary # System Abnormal Test Report 91 4.3.4 Programming the Primary Number 24 Hour Test Time (21-24) Use military time when entering the 24 hour 'test' time. The 24 hour test time over the primary phone number to the Central Station, takes up four locations at addresses 21-24. The default is 00:00 (12:00 midnight). The limits for each location are as follows (do not use A through F as entries): Address 21 - enter 0 through 2 Address 22 - enter 0 through 9 Address 23 - enter 0 through 5 Address 24 - enter 0 through 9 4.3.5 Programming Primary Number 24/12 Hour Test Time (25) The test message sent to the Primary phone number may be sent every 12 or 24 hours. If the message is to be sent every 24 hours, leave the factory default entry of '0'. If 12 hour test reports are needed, enter a '1' into address 25. 4.3.6 Programming the Secondary Phone Number (26-41) Sixteen addresses are set aside for the secondary phone number, with 'F' being the factory default. Programming is typically done as follows: ✓ If your phone number is 484-7161, press 4 ✓ The display will read 26_4 t to save the entry to memory and increment to the next address which is 27_F ✓ Press ✓ Enter the remaining numbers in their respective addresses as shown below: Entry 4 8 4 7 Address 26 27 28 29 1 6 1 F F F F 30 31 32 33 34 35 36 F F F 37 38 39 F F 40 41 Valid entries are 0 - F with the numeric digits as dialed numbers and the alpha digits indicating the following: A = * on a Touchtone phone keypad B = # on a Touchtone phone keypad C = look for secondary dial tone for up to two seconds (then dial anyway) D = three second pause E = five second pause F = end of phone number 40 Document #15465 Rev.F1 12/04/02 P/N 15465:F1 Programming 4.3.7 Programming Secondary Number Communication Format (42) One location is needed to select the Communication Format for the secondary phone number. Address 42 is used for this purpose. The default (factory setting) for this address is 'A', which is 4+2 Standard, 1800 Hz 'Carrier', 2300 Hz 'ACK'. Formats '2' through 'D' may be entered in place of the default value, followed by the [ENTER/ STORE] key. '0' through 'F' represent the following formats: 0: Not used 1: Not used 2: 3+1 Standard 1800 Hz Carrier, 2300 Hz ACK 3: 3+1 Expanded 1800 Hz Carrier, 2300 Hz ACK 4: 3+1 Standard 1900 Hz Carrier, 1400 Hz ACK 5: 3+1 Expanded 1900 Hz Carrier, 1400 Hz ACK 6: 4+1 Standard 1800 Hz Carrier, 2300 Hz ACK 7: 4+1 Expanded 1800 Hz Carrier, 2300 Hz ACK 8: 4+1 Standard 1900 Hz Carrier, 1400 Hz ACK 9: 4+1 Expanded 1900 Hz Carrier, 1400 Hz ACK A: 4+2 Standard 1800 Hz Carrier, 2300 Hz ACK B: 4+2 Expanded 1800 Hz Carrier, 2300 Hz ACK C: 4+2 Standard 1900 Hz Carrier, 1400 Hz ACK D: 4+2 Expanded 1900 Hz Carrier, 1400 Hz ACK E: Not used F: Not used Note: Consult your Central Station for proper selection or consult our factory representatives. For any format chosen, the MS-5012 automatically programs all of the event codes. Refer to Table 4-3 and Table 4-4 . 3+1 and 4+1 Standard and Expanded, 4+2 Expanded Formats If '2, 3, 4, 5, 6, 7, 8, 9, B or D' are entered for address 42, the following data is automatically programmed for the Secondary phone number event codes. Enter '0' for the Setting to disable the report. TABLE 4-3: 3+1 and 4+1 Standard and Expanded, 4+2 Expanded Formats Address Factory Settings Description 156 Secondary # Zone 1 Alarm Code 1 157 Secondary # Zone 2 Alarm Code 1 158 Secondary # Zone 3 Alarm Code 1 159 Secondary # Zone 4 Alarm Code 8 160 Secondary # Zone 5 Alarm Code 1 161 Secondary # AC Fault Code F 162 Secondary # Zone 1 Fault Code F 163 Secondary # Zone 2 Fault Code F 164 Secondary # Zone 3 Fault Code F 165 Secondary # Zone 4 Fault Code F 166 Secondary # Zone 5 Fault Code F 167 Secondary # Earth Ground Code F 168 Secondary # Low Battery Code F 169 Secondary # No Battery Code F 170 Secondary # Telco Primary Line Fault Code F 171 Secondary # Telco Secondary Line Fault Code F 172 Secondary # Bell Fault Code F Document #15465 Rev. F1 12/04/02 P/N 15465:F1 41 Programming TABLE 4-3: 3+1 and 4+1 Standard and Expanded, 4+2 Expanded Formats Address Factory Settings Description 173 Secondary # Communication Trouble Primary Number F 174 Secondary # Communication Trouble Secondary Number F 175 Secondary # Annunciator Fault Code F 176 Secondary # System Off Normal Code F 177 Secondary # Zone 1 Alarm Restoral Code E 178 Secondary # Zone 2 Alarm Restoral Code E 179 Secondary # Zone 3 Alarm Restoral Code E 180 Secondary # Zone 4 Alarm Restoral Code E 181 Secondary # Zone 5 Alarm Restoral Code E 182 Secondary # AC Fault Restoral Code E 183 Secondary # Zone 1 Fault Restoral Code E 184 Secondary # Zone 2 Fault Restoral Code E 185 Secondary # Zone 3 Fault Restoral Code E 186 Secondary # Zone 4 Fault Restoral Code E 187 Secondary # Zone 5 Fault Restoral Code E 188 Secondary # Earth Ground Restoral Code E 189 Secondary # Low Battery Restoral Code E 190 Secondary # No Battery Restoral Code E 191 Secondary # Telco Primary Line Fault Restoral Code E 192 Secondary # Telco Secondary Line Fault Restoral Code E 193 Secondary # Bell Fault Restoral Code E 194 Secondary # Communication Trouble Restoral Primary Number E 195 Secondary # Communication Trouble Restoral Secondary Number E 196 Secondary # Annunciator Fault Restoral E 197 Secondary # System Return to Normal Code E 198 Secondary # 24 Hour Test Code 9 199 Secondary # System Abnormal Test Report F 4+2 Standard Format If 'A' or 'C' are entered for address 42, the following data is automatically programmed for the Secondary phone number event codes. Enter '00' for the Setting to disable the report. 4.3.8 Programming the Secondary Number Account Code (43-46) A unique Account Code is provided by the Central Station. The Secondary Number Account Code takes up four locations at addresses 43-46. The defaults are all '0s'. Valid entries are (0-9 and A-F). The number of digits entered must match the format selection. If programming '2, 3, 4 or 5' into address 42, enter the three digit Account Code provided by the Central Station (location 46 is ignored). If programming '6, 7, 8, 9, A, B, C or D' into address 42, enter the four digit Account Code. 42 Document #15465 Rev.F1 12/04/02 P/N 15465:F1 Programming TABLE 4-4: 4+2 Standard Formats Address Factory Settings Description 156-157 Secondary # Zone 1 Alarm Code 11 158-159 Secondary # Zone 2 Alarm Code 12 160-161 Secondary # Zone 3 Alarm Code 13 162-163 Secondary # Zone 4 Alarm Code 84 164-165 Secondary # Zone 5 Alarm Code 15 166-167 Secondary # AC Fault Code F6 168-169 Secondary # Zone 1 Fault Code F1 170-171 Secondary # Zone 2 Fault Code F2 172-173 Secondary # Zone 3 Fault Code F3 174-175 Secondary # Zone 4 Fault Code F4 176-177 Secondary # Zone 5 Fault Code F5 178-179 Secondary # Earth Ground Code F7 180-181 Secondary # Low Battery Code F8 182-183 Secondary # No Battery Code F9 184-185 Secondary # Telco Primary Line Fault Code FA 186-187 Secondary # Telco Secondary Line Fault Code FB 188-189 Secondary # Bell Fault Code FC 190-191 Secondary # Communication Trouble Primary Number FD 192-193 Secondary # Communication Trouble Secondary Number FE 194-195 Secondary # Annunciator Fault Code FC 196-197 Secondary # System Off Normal Code FF 198-199 Secondary # Zone 1 Alarm Restoral Code E1 200-201 Secondary # Zone 2 Alarm Restoral Code E2 202-203 Secondary # Zone 3 Alarm Restoral Code E3 204-205 Secondary # Zone 4 Alarm Restoral Code E4 206-207 Secondary # Zone 5 Alarm Restoral Code E5 208-209 Secondary # AC Fault Restoral Code E6 210-211 Secondary # Zone 1 Fault Restoral Code E1 212-213 Secondary # Zone 2 Fault Restoral Code E2 214-215 Secondary # Zone 3 Fault Restoral Code E3 216-217 Secondary # Zone 4 Fault Restoral Code E4 218-219 Secondary # Zone 5 Fault Restoral Code E5 220-221 Secondary # Earth Ground Restoral Code E7 222-223 Secondary # Low Battery Restoral Code E8 224-225 Secondary # No Battery Restoral Code E9 Document #15465 Rev. F1 12/04/02 P/N 15465:F1 43 Programming TABLE 4-4: 4+2 Standard Formats Address 226-227 Factory Settings Description Secondary # Telco Primary Line Fault Restoral Code EA 228-229 Secondary # Telco Secondary Line Fault Restoral Code EB 230-231 Secondary # Bell Fault Restoral Code EC 232-233 Secondary # Communication Trouble Restoral Primary Number ED 234-235 Secondary # Communication Trouble Restoral Secondary Number EE 236-237 Secondary # Annunciator Fault Restoral EC 238-239 Secondary # System Return to Normal Code EF 240-241 Secondary # 24 Hour Test Code 99 242-243 Secondary # System Abnormal Test Report 91 4.3.9 Programming the Secondary Number 24 Hour Test Time (47-50) Use military time when entering the 24 hour 'test' time. The 24 hour test time over the secondary phone number to the Central Station, takes up four locations at addresses 47-50. The default is 00:00 (12:00 midnight). The limits for each location are as follows (do not use A through F as entries): Address 47 - enter 0 through 2 Address 48 - enter 0 through 9 Address 49 - enter 0 through 5 Address 50 - enter 0 through 9 4.3.10 Programming Secondary Number 24/12 Hour Test Time (51) The test message sent to the Secondary phone number may be sent every 12 or 24 hours. If the message is to be sent every 24 hours, leave the factory default entry of '0'. If 12 hour test reports are needed, enter a '1' into address 51. 4.3.11 Programming Zone 3 Functionality (52) The following entries may be selected: • 0 = nonsilenceable waterflow zone (program optional delay in addresses 53-54) • 1 = normally open contact device zone or silenceable waterflow zone • 2 = 2-wire smoke detector zone (Style B only) The factory default setting is '0' for nonsilenceable waterflow zone. 4.3.12 Programming Waterflow Retard Timer (53-54) A maximum delay of 89 seconds can be programmed into addresses 53-54. This will delay activation due to a 'waterflow alarm' if zone 3 is programmed as a nonsilenceable waterflow zone. The panel automatically provides a one second delay. The factory default setting for addresses 53-54 is '00' for no additional delay. Valid entries for address 53 are 0 through 8 and for address 54, 0 through 9. Addresses 53 and 54 should be changed from the default setting only if address 52 is programmed '0' for nonsilenceable waterflow zone and a delay is required. Be careful to consider any built-in waterflow device delays. 44 Document #15465 Rev.F1 12/04/02 P/N 15465:F1 Programming 4.3.13 Programming AC Loss Reporting Delay (55) Enter a digit of '1 through 6' corresponding to the number of hours to be delayed in reporting loss of AC power. The factory default setting is 6 hour delay. Valid entries are as follows: • 0 = 6 hour delay • 1 = 7 hour delay • 2 = 8 hour delay • 3 = 9 hour delay • 4 = 10 hour delay • 5 = 11 hour delay • 6 = 12 hour delay 4.3.14 Programming Slave Communicator/Fire Panel Selection (56) Leaving address 56 at the factory default setting of '0' means the MS-5012 is operating as a fire panel only. Selecting '1' will program the panel to operate as a slave communicator only. Refer to “Slave Communicator Configuration” on page 51. Selecting '2' will program the panel to operate as a fire panel/communicator. 4.3.15 Secondary Phone Number Reporting (57) The factory default setting is '0' which means that reports will be transmitted to the secondary phone number only if calls to the primary number are unsuccessful. Programming a '1' causes all reports to be transmitted to the secondary phone number. 4.3.16 Alarm Verification on Detector Zones 2 and 3 (58) Factory default setting for address 58 is '0' which means no alarm verification. Entering a '1' enables verification for zone 2 and zone 3. Consult the local Authority Having Jurisdiction (AHJ) prior to altering this address. Alarm verification works only on zones programmed as 2-wire smoke detector zones. After detecting an alarm, the panel removes power from all zones for six seconds, resetting all 2-wire smoke detectors. Power is reapplied and a 12 second retard period allows detectors to stabilize. During the retard/reset period of 18 seconds, subsequent alarms by the same initiating zone are ignored. An alarm detected on any other 2-wire detector zone during the retard period will cause immediate verified alarms. A subsequent alarm on the initiating zone occurring within the confirmation time will cause a verified alarm. Note: Mixing devices on zones designated as 2-wire smoke zones is not recommended. During the alarm verification period, access to other modes of operation is prevented. 4.3.17 Silence Inhibit (59) The factory default setting of '0' disables the silence inhibit feature. A '1' will enable the silence inhibit feature which will prevent the silencing of the Notification Appliance Circuit and piezo sounder for 1 minute following activation. Consult the local Authority Having Jurisdiction (AHJ) prior to altering this address. 4.3.18 Auto Silence (60) The factory default setting of '0' disables the Auto Silence feature. A '1' will enable the Auto Silence feature which will cause the panel to automatically silence the Notification Appliance Circuit after 10 minutes of activation. Consult the local Authority Having Jurisdiction (AHJ) prior to altering this address. 4.3.19 Trouble Reminder (61) The factory default setting of '0' disables the Trouble Reminder feature. Selecting '1' will enable the feature which causes a reminding 'beep' every 15 seconds during an alarm and every two minutes during a trouble condition (after the silence switch has been pressed). The 'beeps' from the onboard piezo sounder will continue until the alarm or fault is cleared. Consult the local Authority Having Jurisdiction (AHJ) prior to altering this address. Document #15465 Rev. F1 12/04/02 P/N 15465:F1 45 Programming 4.3.20 Bell Disable (62) The factory default setting of '0' enables the Notification Appliance Circuit. Entering a '1' in address 62 will cause the Notification Appliance Circuit to be disabled during an alarm. In addition, the Trouble LED will turn on while the NAC is disabled and a bell fault message will be sent to the Central Station(s). Consult the local Authority Having Jurisdiction (AHJ) prior to altering this address. 4.3.21 Annunciator Present (63) The factory default setting of '0' indicates that no annunciator is present on the system. Entering a '1' in address 63 indicates an annunciator is connected to the system. 4.3.22 Programming Zone 4 Functionality (64) The factory default setting for address 64 is '0' for supervisory zone (accepts normally open supervisory devices). Changing address 64 to '1' allows Zone 4 to accept any normally open contact device. Note that when address 64 is changed to '1', the messages transmitted to the Central Station(s) must be changed to reflect the new setting. If using 3+1, 4+1 or 4+2 Expanded Formats, address 71 must be changed to '1' and address 159 must be changed to '1'. If using 4+2 Standard Formats, address 74 must be changed to '1' and address 162 must be changed to '1'. 4.3.23 Address (65) - Not used 4.3.24 Touchtone/Rotary Select (66) The factory default setting for address 66 is '0' which enables Touchtone dialing over both phone lines. Entering a '1' will enable rotary dialing. 4.3.25 Make/Break Ratio (67) An entry is required in address 67 only if address 66 has been programmed with a '1' for rotary dialing. The factory default setting for address 67 is '0' for a Make/Break Ratio of 67/33. Enter a '1' to change the ratio to 62/38. 4.3.26 Programming Event Codes (68-243) Table 4-1 through Table 4-4 list messages of 'event codes' that are sent to the Central Station. The selections made for the Primary Number Communication Format (address 16) and the Secondary Number Communication Format (address 42) automatically program addresses 68-243 with factory selections. Any of the event codes may be changed. Consult your Central Station prior to altering the event codes. Entering an event code of '0' will cause the communicator to NOT transmit the message. For the 3+1, 4+1 Formats or the 4+2 Expanded Format, enter a single zero '0'. For the 4+2 Standard Format, enter two zeroes '00' Be certain to disable the reports in pairs. The pair should include both the activation of the event and the restoral of the event. For example, to disable Zone 1 Fault Code from being transmitted, enter a '0' or '00' for the Zone 1 Fault Code plus a '0' or '00' for the Zone 1 Restoral Code. The exception to this is for the 24 Hour Test Reports and the Abnormal Test Reports. 4.3.27 End Programming Exit Programming Mode by pressing the w key, followed by the 4-digit code corresponding to an alternate t key. During Program Mode, if no key is pressed within 10 minutes, the mode of operation, then press the panel will revert to Normal Mode. 4.3.28 Programming the Real-Time Clock Entering an address greater than 243 will cause a display of the current time. On initial power-up, the clock will start running from the factory setting of 00:00 (military time). The far left digit will be flashing, indicating that this will be the first digit to be programmed. Simply enter the correct digits of the current time, followed by t. 46 Document #15465 Rev.F1 12/04/02 P/N 15465:F1 Servicing Servicing CHAPTER 5 5.1 Walktest Mode The MS-5012 provides the capability to perform a one-man walktest of the system without triggering the communicator or the alarm output relay driver. Walktest allows for testing of the five zones (initiating circuits). The first initiating device activated on a zone will cause the Notification Appliance (bell) Circuit to turn on for four seconds. Subsequent device activations on the same zone will cause the NAC to turn on for one second. Any smoke detectors that are activated will be reset. Zonal faults (open circuits) will cause the NAC to remain steadily on. Prior to entering Walktest Mode, check to be certain that all system faults have been cleared. Note that the trouble relay will be activated while the control panel is in Walktest Mode. Placing the control panel in Walktest Mode will only be possible if the system has no active alarms. w key followed by the 4-digit code Pressing the place the control panel into Walktest Mode. ☛ 9255 9255 and then pressing the t key will spells WALK on a Touch-Tone® phone. Once in Walktest Mode, the MS-5012 will immediately: ✓ ✓ ✓ ✓ ✓ ✓ ✓ Turn on the trouble LED Activate/energize the trouble relay driver Turn on the Notification Appliance Circuit output for four seconds for the first alarm event on a zone. Subsequent alarms will sound for one second. Troubles cause the NAC to remain on until cleared Disable the alarm relay Display all alarm conditions as they occur Display ground faults as they occur Continue to communicate any events not yet acknowledged at the Central Station During Walktest Mode, zonal activity is displayed in real-time as it occurs. At the end of Walktesting the system, the display will show the last event that occurred. To view all events stored during Walktest, use the q, r and s keys. The r key moves the Walktest list to show older (previous) events. The q key moves the Walktest list to show newer (more recent) events. Pressing the s key at any time will cause the display of the first event stored upon initial entry into Walktest Mode. While in Walktest Mode, the control panel will store up to 128 events in the Walktest File for later recall and display. To return the MS-5012 to Normal Mode, press the w key, the code numbers 6676 and the t key. Any delay between key entries greater than 10 seconds causes the control panel to remain in Walktest Mode. The control panel will automatically revert back to Normal Mode if no system activity has occurred for 60 minutes. This would include pressing any keys or activity on any zone. Exiting Walktest Mode erases the Walktest File from memory. Document #15465 Rev. F1 12/04/02 P/N 15465:F1 47 History Mode 5.2 History Mode All Normal Mode events are stored in a History File list for future recall. Recall is possible via the 4-character display. The History File list is a first-in/first-out (FIFO). In this manner, only the most recent events may be called up form memory. Old events will be overwritten, i.e. pushed out of FIFO. The number of stored events is 16. The History File is kept in EEPROM memory. Complete power loss will not erase the list. w 4478 t Pressing the key followed by the digits and the key places the control panel into History Mode. This will not occur if there are any active alarm conditions present. The event displayed, is the most recent event. ☛ 4478 spells HIST on a Touch-Tone® phone. Once in History Mode, the control panel will: ✓ ✓ ✓ ✓ ✓ ✓ ✓ Turn on the trouble LED Energize/activate the trouble relay driver Disable the Notification Appliance Circuit output Disable the alarm relay driver Display all events as they occurred since the last time the History File list was cleared. The most recent event will be displayed first Ignore all other keys other than those mentioned in this section Continue to communicate any events not yet acknowledged at the Central Station r q The key moves the History File to show older (previous) events. The key moves the History File to show newer (more recent) events. Shown below is a list of messages as they will appear on the display: DISPLAY A 1 A 2 A 3 A 4 A 5 SuP4 AC F 1 F 2 F 3 F 4 F 5 EVENT DISPLAY Zone 1 Alarm Zone 2 Alarm Zone 3 Alarm Zone 4 Alarm Zone 5 Alarm Supervisory Alarm AC Loss Zone 1 Fault Zone 2 Fault Zone 3 Fault Zone 4 Fault Zone 5 Fault bELL F E F A no 1 no 2 rES PH 1 PH 2 no b Lo b SILE EVENT Bell Fault (open or short) Earth Fault Annunciator Fault Primary Phone Line Fault Secondary Phone Line Fault Reset Switch Pressed Primary Number Communication Fault Secondary Number Communication Fault No Battery Low Battery Silence Switch Pressed To erase the list, press the Silence Key twice before exiting the History Mode. A lack of keyboard activity for a period of 10 minutes will cause the control panel to return to Normal Mode. 48 Document #15465 Rev.F1 12/04/02 P/N 15465:F1 Troubleshoot Mode 5.3 Troubleshoot Mode In this mode, the voltage of the input zones, AC voltage and battery voltage will be displayed on the 4-character display. The internal voltmeter reads the voltage present at: • zone inputs • AC power input • battery terminal leads A lack of keyboard activity for a period of 20 minutes will cause the control panel to return to Normal Mode. w key followed by the digits 8768 and the t key. 8768 spells TROU on a Touch-Tone phone. To enter Troubleshoot Mode, press the ☛ ® Once in Troubleshoot Mode, the MS-5012 will: ✓ ✓ ✓ ✓ ✓ Turn on the trouble LED Energize/activate the trouble relay driver Disable the Notification Appliance Circuit output Disable the alarm relay driver Continue to communicate any events not yet acknowledged at the Central Station a and then t displays the AC input voltage. Pressing b and then t will display the Battery Voltage. Pressing 1 through 5 followed by t displays the zone voltage of the selected zone. The q, r and s keys do not function in this mode. Pressing Listed below are the 'nominal threshold voltages' for each zone: Zone # 1 2 Normal w/E.O.L. 5.15V 11.75V 3 4 5 11.75V 5.15V 5.15V Shorted Ckt. 0.15V 8.7V Open Ckt. 12.V 12.9V 8.7V .15V .15V 12.9V 12.9V 12.9V Readings will vary proportionately depending upon system load and AC line voltage. Listed below is the AC line voltage range. The AC ON indicator will turn off when the AC line voltage drops below the Low Line 'threshold', and the trouble LED will turn on. AC Line Voltage Low Line 102VAC Normal 115VAC High Line 132VAC Below is shown the critical battery threshold conditions: Battery Voltage Normal 13.7V Low Battery 10.2V Note: make measurements after allowing 48 hours to charge a depleted battery. If battery does not show normal reading, replace it. Document #15465 Rev. F1 12/04/02 P/N 15465:F1 49 Lamp Test c t Pressing and then causes seizure of the Primary line and the red LED signifying Primary line active turns on. After a delay of three seconds, the control panel goes off hook to acquire a dial tone. Connecting a telephone handset across the telephone transformer, as illustrated in Figure 5-1, allows number dialing. Pressing then c and t a second time hangs up the call. Repeated entries of c places the phone on and off hook. FIGURE 5-1: Handset Connection Ring (red) Tip (green) Carefully Connect Handset Here T1 5.4 Lamp Test w 5267 t To perform a Lamp Test, press then followed by . This will test all system LEDs except the Primary Active LED and Secondary Active LED. The LEDs will stay on for five seconds, then the control panel will return to Normal Mode. ☛ 50 5267 spells LAMP on a Touch-Tone® phone. Document #15465 Rev.F1 12/04/02 P/N 15465:F1 Slave Communicator Configuration CHAPTER 6 Slave Communicator Configuration The MS-5012 may be used as a slave communicator to a host or 'Master' fire alarm control panel (FACP). All wiring between the Master and the MS-5012 is supervised. 2.2K ohm End-of-Line resistors must be connected as illustrated in the typical wiring diagram in illustrated in this chapter. In slave configuration, the five zones become five channels that may be triggered by the relay outputs of any host FACP: • • • • • Zone1/Channel 1 is used for general alarm Zone 2/Channel 2 is used for general trouble Zone 3/Channel 3 may be programmed to match the FACP relay function Zone 4/Channel 4 is used for supervisory Zone 5/Channel 5 may be programmed to match the FACP relay function The factory settings for Zone 2/Channel 2 activation and restoral are altered as follows: ✓ ✓ If '2, 3, 4, 5, 6, 7, 8, 9, B or D' is entered for address 16 or 42, the report code for Zone 2 Alarm Code (addresses 69 and 157) = F and Zone 2 Restoral Code (addresses 90 and 178) = E If 'A or C' is entered for address 16 or 42, the report code for Zone 2 Alarm Code (addresses 70-71 and 158-159) = FF and Zone 2 restoral code (addresses 112-113 and 200-201) = EF It is important to note that activation of Zone 2 is Slave Communicator Configuration will cause the yellow trouble LED to flash and the trouble sounder to pulse, however, the red alarm LED will not activate and the notification appliances will not sound. Location 56 must be programmed to a '1' to enable the control panel as a slave communicator. When programming the MS-5012 as a slave communicator, first program the communication formats (addresses 16 and 42), followed by the slave communicator selection at address 56. This sequence allows the MS-5012 to automatically program the proper report codes. Do not program location 56 first and then alter the format selections at addresses 16 and 42. If any of the report codes are to be altered from the factory defaults, follow the steps above and exit Program Mode. Next, reenter Program Mode and alter any event codes. After programming is complete, the the t, q or r keys may be used to view programmed entries. Do not use t key to view location 56, since it will reprogram the factory default event codes. Be certain to connect the MS-5012 primary AC power to the same branch circuit as the host FACP. Battery Connection The MS-5012 contains a battery disconnect relay which has multiple purposes. The primary purpose is to disconnect the battery when the battery voltage is less the 7.0 volts during AC loss condition. This prevents the MS-5012 from transmitting erroneous data to the Central Station under unsafe operating power. Also, with AC power applied, the disconnect relay allows for battery voltage measurements in the Normal and Troubleshoot Modes. Document #15465 Rev. F1 12/04/02 P/N 15465:F1 51 Slave Communicator Configuration Due to the presence of the disconnect relay, it is not possible to initially (out of the box) power up an MS-5012 from the battery. AC power must be applied for six seconds. Once AC power is applied, do not connect a low capacity battery (less than 7.0 volts) to the system. When replacing a bad battery, turn off AC power before connecting the new battery. Inputs are supervised and power-limited Relays in the Master FACP activate various input circuits on the MS-5012. Messages (event codes) programmed for a particular input circuit (channel) will be transmitted to the Central Station upon relay activation. 52 Document #15465 Rev.F1 12/04/02 P/N 15465:F1 Power Calculations Power Calculations Appendix A Use the Total Standby and Alarm Load Currents calculated in Table A-1 and Table A-2 for the following battery calculation. TABLE A-1: Total Ampere Hours Standby Load Current (Amps) [ ] X Required Standby Time in Hours (24 or 60 Hours) [ ] = __________ Alarm Load Current (Amps) [ ] X Required Alarm Time in Hours (i.e. 5 min. = 0.084 hours) [ ] = __________ Add Standby and Alarm Load for Required Ampere Hour Battery = __________ Multiply by the Derating Factor of 1.2 x 1.2 __________ Total Ampere Hours (AH) Required = __________ Select a battery with a greater Ampere Hour rating. Notes: 1. 2. NFPA 72 National Fire Alarm Code for Central Station, Local and Proprietary Protected Premises systems require 24 hours of standby. NFPA 72 National Fire Alarm Code for Auxiliary and Remote Station systems require 60 hours of standby. Document #15465 Rev. F1 12/04/02 P/N 15465:F1 53 Power Calculations The MS-5012 provides filtered power for operating the fire alarm control panel, external devices and the standby battery. The power for operating external devices is limited. Use Table A-1 (standby or nonalarm) and Table A-2 (alarm) to determine if external loading is within the capabilities of the power supply. TABLE A-2: Regulated Load in Standby Current (Amps) Total Current (Amps) Device Type # of Devices Main Circuit Board 1 X 0.074 = ADM-12 (1 maximum) X 0.012 = RZA-5F (1 maximum) X 0.012 = 2-wire Detector Heads1 [ ] X [ ] = 4-wire Detector Heads [ ] X [ ] = Power Supervision Relays2 [ ] X 0.025 = 0.074 Auxiliary Outputs: TB3-4 Alarm (1 maximum) X 0 = TB3-5 Trouble (1 maximum) X 0.0403 = TB3-6 Supervisory (1 maximum) X 0 = TB3-7 Comm. Fail (1 maximum) X 0 = Additional Current Draw from TB3 (nonalarm) = Sum Column for Standby Load = Amps 1. Refer to Device Compatibility Document for 2-wire smoke detector standby current. 2. Use compatible listed power supervision relay only. 3. Current draw only if End-of-Line relay is installed between TB3-3 and TB3-5. Current shown is maximum available from TB3 Terminal 5 54 Document #15465 Rev.F1 12/04/02 P/N 15465:F1 Power Calculations TABLE A-3: Regulated Load in Alarm Device Type # of Devices Main Circuit Board 1 Current (Amps) Total Current (Amps) X 0.170 = = ADM-12 (1 maximum) X 0.0321 RZA-5F (1 maximum) X 0.0301 = 4-wire Detector Heads [ ] X [ ] = Power Supervision Relays2 [ ] X 0.025 = 0.170 Auxiliary Outputs: TB3-4 Alarm (1 maximum) X 0.040 = TB3-5 Trouble (1 maximum) X 0.040 = TB3-6 Supervisory (1 maximum) X 0 = TB3-7 Comm. Fail (1 maximum) X 0 = Notification Appliances [ ] X [ ] = Notification Appliances [ ] X [ ] = Additional Current Draw from TB3 (nonalarm) = Sum Column for Alarm Load = Amps 1. Current shown is with all LEDs illuminated. 2. Use compatible listed power supervision relay only. Document #15465 Rev. F1 12/04/02 P/N 15465:F1 55 Programming Reference Sheets Programming Reference Sheets Appendix B B.1 Blank System Programming Reference Sheets To enter Programming Mode, press the Mode key followed by the keys 7764 and then the [ENTER/STORE] key. ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 Addresses 00 to 15 store the Primary Phone Number. Enter 'F' to represent the end of the number. ❏ Primary Communication Format: Enter '0 - F'. ❏ ❏ ❏ ❏ Primary Account Code: Valid entries are '0 - F'. ❏ ❏ ❏ ❏ Primary 24-Hour Test Time. Enter military time (i.e. 1400 for 2:00 PM). ❏ Primary 24/12 Hour Test Time. Enter '1' for 12 hour; '0' for 24 hour. ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ 16 17 18 19 20 21 22 23 24 27 28 29 25 26 30 31 32 33 34 35 36 37 38 39 40 41 Addresses 26 to 41 store the Secondary Phone Number. Enter 'F' to represent the end of the number. ❏ Secondary Communication Format: Enter '0 - F'. ❏ ❏ ❏ ❏ Secondary Account Code: Valid entries are '0 - F'. ❏ ❏ ❏ ❏ Secondary 24-Hour Test Time. Enter military time (i.e. 1400 for 2:00 PM). ❏ Secondary 24/12 Hour Test Time. Enter '1' for 12 hour; '0' for 24 hour. ❏ Zone 3 Function Select ('0' = waterflow,' = normally open contact devices, '2' = 2-wire smoke detectors) ❏ ❏ Waterflow Reporting Delays. Valid keys for field 53 are '0 - 8' and for field 54 are '0 - 9'. ❏ AC Loss. Enter number of hours to delay reporting of AC loss. ('0' = 6 hours, '1' = 7 hours, '2' = 8 hours, '3' 42 43 44 45 46 47 48 4 50 51 52 53 54 55 = 9 hours, '4' = 10 hours, '5' = 11 hours, '6' = 12 hours). ❏ 56 Slave Communicator Selection. '0' for panel only; '1' for slave operation; '2' for fire control/communicator operation. ❏ ❏ ❏ ❏ 57 Secondary Phone Number. Enter '0' for secondary as a backup; '1' to transmit to secondary always. 58 Alarm Verify. Enter '0' for no verification; '1' for verification. 59 Silence Inhibit. Enter '0' to disable silence inhibit; '1' to enable silence inhibit. 60 Auto Silence. Enter '0' to disable auto silence; '1' to automatically silence notification appliances 10 minutes after activation. ❏ 61 Trouble Reminder. Enter '0' to disable trouble reminder; '1' to enable trouble reminder 'beep' (sound every 15 seconds for alarm and every 2 minutes for trouble). ❏ ❏ ❏ ❏ ❏ ❏ 56 62 Bell Disable. Enter '0' to enable the panel Notification Appliance Circuit (NAC); '1' to disable the NAC. 63 Annunciator Present. Enter '0' if no annunciator is wired to system; '1' if annunciator is wired to system. 64 Zone 4 Function Select. Enter '0' for supervisory service; '1' for normally open contact devices. 65 Not used. 66 Touchtone/Rotary Select. Enter '0' for touchtone dialing; '1' for rotary dialing. 67 Make/Break Ratio. Enter '0' for 67/33 make/break ratio; '1' for 62/38 ratio. Document #15465 Rev.F1 12/04/02 P/N 15465:F1 Programming Reference Sheets B.2 Blank Format Programming Reference Sheet ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏❏ ❏ ❏ ❏ ❏ 68 69 70 71 72 73 74 75 76 77 78 79 ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏❏ ❏ ❏ ❏ ❏ 81 82 83 84 85 86 87 88 89 90 91 92 ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ 94 95 96 97 98 99 100 101 102 103 104 105 ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏❏ ❏ ❏ ❏ ❏ 107 108 109 110 111 112 113 114 115 116 117 118 ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏❏ ❏ ❏ ❏ ❏ 120 121 122 123 124 125 126 127 128 129 130 131 ❏ ❏ ❏❏❏ ❏ ❏ ❏❏ ❏ ❏ ❏ ❏ 133 134 135 136 137 138 139 140 141 142 143 144 ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏❏ ❏ ❏ ❏ ❏ 146 147 148 149 150 151 152 153 154 155 156 157 ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏❏ ❏ ❏ ❏ ❏ 159 160 161 162 163 164 165 166 167 168 169 170 ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏❏ ❏ ❏ ❏ ❏ 172 173 174 175 176 177 178 179 180 181 182 183 ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏❏ ❏ ❏ ❏ ❏ 185 186 187 188 189 190 191 192 193 194 195 196 ❏ ❏ ❏❏❏ ❏ ❏ ❏❏ ❏ ❏ ❏ ❏ 198 199 200 201 202 203 204 205 206 207 208 209 ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏❏ ❏ ❏ ❏ ❏ 211 212 213 214 215 216 217 218 219 220 221 222 ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏❏ ❏ ❏ ❏ ❏ 224 225 226 227 228 229 ❏ ❏ ❏ ❏ ❏ ❏ ❏ 237 238 239 240 241 242 230 231 232 233 234 235 80 93 106 119 132 145 158 171 184 197 210 223 236 243 Document #15465 Rev. F1 12/04/02 P/N 15465:F1 57 Programming Reference Sheets B.3 Programming Reference Sheet Factory Default Settings To enter Programming Mode, press the Mode key followed by the keys 7764 and then the [ENTER/STORE] key. F ❏ F ❏ F ❏ F ❏ F ❏ F ❏ F ❏ F ❏ F ❏ F ❏ F ❏ F ❏ F ❏ F ❏ F ❏ F ❏ 00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 Addresses 00 to 15 store the Primary Phone Number. Enter 'F' to represent the end of the number. A Primary Communication Format: A = 4+2 Standard, 1800/2300. ❏ 0 ❏ 0 ❏ 0 ❏ 0 Primary Account Code. ❏ 0 ❏ 0 ❏ 0 ❏ 0 Primary 24-Hour Test Time. 0000 = 12:00 midnight. ❏ 0 Primary 24/12 Hour Test Time. '0' for 24 hour. ❏ F ❏ F ❏ F ❏ F ❏ F ❏ F ❏ F ❏ F ❏ F ❏ F ❏ F ❏ F ❏ F ❏ F ❏ F ❏ F ❏ 16 17 18 19 20 21 22 23 24 27 28 29 25 26 30 31 32 33 34 35 36 37 38 39 40 Addresses 26 to 41 store the Secondary Phone Number. Enter 'F' to represent the end of the number. A Secondary Communication Format: A = 4+2 Standard, 1800/2300. ❏ 0 ❏ 0 ❏ 0 ❏ 0 Secondary Account Code. ❏ 0 ❏ 0 ❏ 0 ❏ 0 Secondary 24-Hour Test Time. 0000 = 12:00 midnight. ❏ 0 Secondary 24/12 Hour Test Time. '0' for 24 hour. ❏ 0 Zone 3 Function Select: '0' = waterflow. ❏ 0 ❏ 0 Waterflow Reporting Delays. 00 = No delays. ❏ 0 AC Loss. '0' = 6 hours. ❏ 42 43 44 45 46 47 48 4 50 51 52 53 54 55 . 0 ❏ 56 0 ❏ 0 ❏ 0 ❏ 0 ❏ 57 Secondary Phone Number. '0' for secondary as a backup. 58 Alarm Verify. '0' for no verification. 59 Silence Inhibit. '0' to disable silence inhibit. 60 Auto Silence. '0' to disable auto silence. 0 ❏ 61 0 ❏ 0 ❏ 0 ❏ 0 ❏ 0 ❏ 0 ❏ 58 Slave Communicator Selection. '0' for panel only. Trouble Reminder. '0' to disable trouble reminder. 62 Bell Disable. '0' to enable the panel Notification Appliance Circuit (NAC). 63 Annunciator Present. '0' for no annunciator wired to system. 64 Zone 4 Function Select. '0' for supervisory service. 65 Not used. 66 Touchtone/Rotary Select. '0' for touchtone dialing. 67 Make/Break Ratio. '0' for 67/33 make/break ratio. Document #15465 Rev.F1 12/04/02 P/N 15465:F1 41 Programming Reference Sheets B.4 Format Programming Reference Sheet Factory Default Sheet 1 ❏ 1 ❏ 1 ❏ 2 ❏ 1 ❏ 3 ❏ 8 ❏ 4 ❏ 1 ❏ 5 ❏ F ❏ 6 ❏ F ❏ 68 69 70 71 72 73 74 75 76 77 78 79 1 ❏ F ❏ 2 ❏ F ❏ 3 ❏ F ❏ 4 ❏ F ❏ 5 ❏ F ❏ 7 ❏ F ❏ 8 ❏ 81 82 83 84 85 86 87 88 89 90 91 92 F ❏ 9 ❏ F ❏ A ❏ F ❏ B ❏ F ❏ C ❏ F ❏ D ❏ F ❏ E ❏ F ❏ 94 95 96 97 98 99 100 101 102 103 104 105 C ❏ F ❏ F ❏ E ❏ 1 ❏ E ❏ 2 ❏ E ❏ 3 ❏ E ❏ 4 ❏ E ❏ 5 ❏ 107 108 109 110 111 112 113 114 115 116 117 118 E 6 E ❏ 1 ❏ E ❏ 2 ❏ E ❏ 3 ❏ E ❏ 4 ❏ E ❏ 5 ❏ E ❏ ❏ ❏ 120 121 122 123 124 125 126 127 128 129 130 131 7 ❏ E 8 E ❏ 9 ❏ E ❏ A ❏ E ❏ B ❏ E ❏ C ❏ E ❏ D ❏ ❏❏ 133 134 135 136 137 138 139 140 141 142 143 144 E ❏ E ❏ E ❏ C ❏ E ❏ F ❏ 9 ❏ 9 ❏ 9 ❏ 1 ❏ 1 ❏ 1 ❏ 1 ❏ 146 147 148 149 150 151 152 153 154 155 156 157 2 ❏ 1 ❏ 3 ❏ 8 ❏ 4 ❏ 1 ❏ 5 ❏ F ❏ 6 ❏ F ❏ 1 ❏ F ❏ 2 ❏ 159 160 161 162 163 164 165 166 167 168 169 170 F ❏ 3 ❏ F ❏ 4 ❏ F ❏ 5 ❏ F ❏ 7 ❏ F ❏ 8 ❏ F ❏ 9 ❏ F ❏ 172 173 174 175 176 177 178 179 180 181 182 183 A ❏ F ❏ B ❏ F ❏ C ❏ F ❏ D ❏ F ❏ E ❏ F ❏ C ❏ F ❏ F ❏ 185 186 187 188 189 190 191 192 193 194 195 196 E ❏ 1 E 2 ❏ E ❏ 3 ❏ E ❏ 4 ❏ E ❏ 5 ❏ E ❏ 6 ❏ E ❏ ❏❏ 198 199 200 201 202 203 204 205 206 207 208 209 1 ❏ E ❏ 2 ❏ E ❏ 3 ❏ E ❏ 4 ❏ E ❏ 5 ❏ E ❏ 7 ❏ E ❏ 8 ❏ 211 212 213 214 215 216 217 218 219 220 221 222 E ❏ 9 ❏ E ❏ A ❏ E ❏ B ❏ E ❏ C ❏ E ❏ D ❏ E ❏ E ❏ E ❏ 224 225 226 227 228 229 C ❏ E ❏ F ❏ 9 ❏ 9 ❏ 9 ❏ 1 ❏ 237 238 239 240 241 242 230 231 232 233 234 235 80 93 106 119 132 145 158 171 184 197 210 223 236 243 Document #15465 Rev. F1 12/04/02 P/N 15465:F1 59 Notes 60 Document #15465 Rev.F1 12/04/02 P/N 15465:F1 Index I IDC 13, 27 see also Initiating Device Circuit 11 inhibit silence 45 Initiating Device Circuit 13 input circuits 11, 27 installation 26 Numerics 1st Event 17 A AC terminal block option 32 AC loss reporting delay 45 AC power 13, 18 LED 12 account code 38, 42 ADM-12 33, 34 see also annunciator driver module 12 alarm 18 LED 12 relay driver 14 response 19 restoral 19 verification 45 annunciator 12, 33 annunciator driver module 12, 33 auto silence 45 K kiss-off 18 kissoff LED 12 L lamp test 50 Lamp Test Mode 16 LED 17, 18 see also display 12 line seizure 12 M mounting cabinet 26 B backbox size 10 battery 13, 31 calculations 54 charging capacity 13 connection 51 N NAC 14, 28 disable 46 fault 15 see also Notification Appliance Circuit 11 nonresettable power 11, 14 Normal Mode 16 normal mode 18 Notification Appliance Circuit 11, 14, 28 C cabinet dimensions 26 mounting 26 circuits 11 clock programming 46 communication format 37, 41 communication formats 12 communicator 12, 15, 21, 30 communicator failure relay driver 14 O off normal reporting 21 off/on hook 12 operation 16 modes 16 output circuits 11, 28 outputs auxiliary 14 D description 10 dial tone 12 digital communicator 12, 15, 21, 30 dimensions cabinet 26 disable NAC 46 display 12, 17 P panel selection 45 panel switches 11 phone line active LED 12 piezo sounder 15 Power AC 31 power AC 13 battery 31 calculations 53 nonresettable 11, 14 resettable 11, 14 power-limited wiring 29 priorities transmit 24 priority events 19 Program Mode 16 program mode 35 programming 35 exit 46 sheets 56 E event code programming 46 F features 10 format addresses 22 communication 12 H History Mode 16 history mode 48 Document #15465 Rev.F1 12/04/02 P/N 15465:F1 61 R receivers UL listed 25 relay 14 relays 11 remote annunciator 12, 13, 33 reporting off normal 21 reset 16 resettable power 11, 14 RZA-5F 13, 33, 34 see also remote annunciator 12 S servicing 47 silence 16, 18 inhibit 45 LED 12 size backbox 10 slave communicator 51 sounder 15 specifications 13 supervisory 18, 20 LED 12 relay driver 14 supervisory zone 20, 27 switch functions 16, 36 switches 11 T telephone wiring 30 telephone circuit 14 telephone line 18 telephone number 36, 40 terminal block AC 32 test time 40, 44 transmittal priorities 24 trouble 18, 20 LED 12 relay driver 14 restoral 21 trouble reminder 45 Troubleshoot Mode 16 troubleshoot mode 49 V verification alarm 45 W walktest 47 Walktest Mode 16 waterflow programming 44 retard timer 44 Z zone programming 44, 46 supervisory 20 62 Document #15465 Rev.F1 12/04/02 P/N 15465:F1 Limited Warranty The manufacturer warrants its products to be free from defects in materials and workmanship for eighteen (18) months from the date of manufacture, under normal use and service. Products are date-stamped at time of manufacture. The sole and exclusive obligation of the manufacturer is to repair or replace, at its option, free of charge for parts and labor, any part which is defective in materials or workmanship under normal use and service. For products not under the manufacturer's date-stamp control, the warranty is eighteen (18) months from date of original purchase by the manufacturer's distributor unless the installation instructions or catalog sets forth a shorter period, in which case the shorter period shall apply. This warranty is void if the product is altered, repaired, or serviced by anyone other than the manufacturer or its authorized distributors, or if there is a failure to maintain the products and systems in which they operate in a proper and workable manner. In case of defect, secure a Return Material Authorization form from our customer service department. Return product, transportation prepaid, to the manufacturer. This writing constitutes the only warranty made by this manufacturer with respect to its products. The manufacturer does not represent that its products will prevent any loss by fire or otherwise, or that its products will in all cases provide the protection for which they are installed or intended. Buyer acknowledges that the manufacturer is not an insurer and assumes no risk for loss or damages or the cost of any inconvenience, transportation, damage, misuse, abuse, accident, or similar incident. THE MANUFACTURER GIVES NO WARRANTY, EXPRESSED OR IMPLIED, OF MERCHANTABILITY, FITNESS FOR ANY PARTICULAR PURPOSE, OR OTHERWISE WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE HEREOF. UNDER NO CIRCUMSTANCES SHALL THE MANUFACTURER BE LIABLE FOR ANY LOSS OF OR DAMAGE TO PROPERTY, DIRECT, INCIDENTAL, OR CONSEQUENTIAL, ARISING OUT OF THE USE OF, OR INABILITY TO USE THE MANUFACTURER'S PRODUCTS. FURTHERMORE, THE MANUFACTURER SHALL NOT BE LIABLE FOR ANY PERSONAL INJURY OR DEATH WHICH MAY ARISE IN THE COURSE OF, OR AS A RESULT OF, PERSONAL, COMMERCIAL, OR INDUSTRIAL USE OF ITS PRODUCTS. This warranty replaces all previous warranties and is the only warranty made by the manufacturer. No increase or alteration, written or verbal, of the obligation of this warranty is authorized. LimWarLg.p65 01/10/2000 World Headquarters One Fire-Lite Place, Northford, CT 06472-1653 USA 203-484-7161 • Fax 203-484-7118 www.firelite.com