MS-5012 - Fire-Lite Alarms by Honeywell

advertisement
PN: 15465:F1
ECN 02-606
Control Communicator
MS-5012
Document
12/04/02
#15465
Rev.
F
Fire Alarm System Limitations
While a fire alarm system may lower insurance
rates, it is not a substitute for fire insurance!
An automatic fire alarm system–typically made up of smoke
detectors, heat detectors, manual pull stations, audible warning devices, and a fire alarm control with remote notification
capability–can provide early warning of a developing fire.
Such a system, however, does not assure protection against
property damage or loss of life resulting from a fire.
Heat detectors do not sense particles of combustion and
alarm only when heat on their sensors increases at a predetermined rate or reaches a predetermined level. Rate-of-rise
heat detectors may be subject to reduced sensitivity over time.
For this reason, the rate-of-rise feature of each detector
should be tested at least once per year by a qualified fire protection specialist. Heat detectors are designed to protect
property, not life.
The Manufacturer recommends that smoke and/or heat detectors be located throughout a protected premise following the
recommendations of the current edition of the National Fire
Protection Association Standard 72 (NFPA 72),
manufacturer's recommendations, State and local codes, and
the recommendations contained in the Guide for Proper Use
of System Smoke Detectors, which is made available at no
charge to all installing dealers. A study by the Federal Emergency Management Agency (an agency of the United States
government) indicated that smoke detectors may not go off in
as many as 35% of all fires. While fire alarm systems are designed to provide early warning against fire, they do not guarantee warning or protection against fire. A fire alarm system
may not provide timely or adequate warning, or simply may not
function, for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot
reach the detectors such as in chimneys, in or behind walls, on
roofs, or on the other side of closed doors. Smoke detectors
also may not sense a fire on another level or floor of a building. A second-floor detector, for example, may not sense a
first-floor or basement fire.
Particles of combustion or "smoke" from a developing fire
may not reach the sensing chambers of smoke detectors because:
• Barriers such as closed or partially closed doors, walls, or
chimneys may inhibit particle or smoke flow.
• Smoke particles may become "cold," stratify, and not reach
the ceiling or upper walls where detectors are located.
• Smoke particles may be blown away from detectors by air
outlets.
• Smoke particles may be drawn into air returns before
reaching the detector.
The amount of "smoke" present may be insufficient to alarm
smoke detectors. Smoke detectors are designed to alarm at
various levels of smoke density. If such density levels are not
created by a developing fire at the location of detectors, the
detectors will not go into alarm.
Smoke detectors, even when working properly, have sensing
limitations. Detectors that have photoelectronic sensing
chambers tend to detect smoldering fires better than flaming
fires, which have little visible smoke. Detectors that have ionizing-type sensing chambers tend to detect fast-flaming fires
better than smoldering fires. Because fires develop in different ways and are often unpredictable in their growth, neither
type of detector is necessarily best and a given type of detector may not provide adequate warning of a fire.
Smoke detectors cannot be expected to provide adequate
warning of fires caused by arson, children playing with
matches (especially in bedrooms), smoking in bed, and violent
explosions (caused by escaping gas, improper storage of
flammable materials, etc.).
LimWarLg.p65
01/10/2000
IMPORTANT! Smoke detectors must be installed in the
same room as the control panel and in rooms used by the system for the connection of alarm transmission wiring, communications, signaling, and/or power. If detectors are not so located, a developing fire may damage the alarm system, crippling its ability to report a fire.
Audible warning devices such as bells may not alert people
if these devices are located on the other side of closed or
partly open doors or are located on another floor of a building.
Any warning device may fail to alert people with a disability or
those who have recently consumed drugs, alcohol or medication. Please note that:
• Strobes can, under certain circumstances, cause seizures
in people with conditions such as epilepsy.
• Studies have shown that certain people, even when they
hear a fire alarm signal, do not respond or comprehend the
meaning of the signal. It is the property owner's responsibility to conduct fire drills and other training exercise to make
people aware of fire alarm signals and instruct them on the
proper reaction to alarm signals.
• In rare instances, the sounding of a warning device can
cause temporary or permanent hearing loss.
A fire alarm system will not operate without any electrical
power. If AC power fails, the system will operate from standby
batteries only for a specified time and only if the batteries
have been properly maintained and replaced regularly.
Equipment used in the system may not be technically compatible with the control. It is essential to use only equipment
listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a
premise to a central monitoring station may be out of service
or temporarily disabled. For added protection against telephone line failure, backup radio transmission systems are recommended.
The most common cause of fire alarm malfunction is inadequate maintenance. To keep the entire fire alarm system in
excellent working order, ongoing maintenance is required per
the manufacturer's recommendations, and UL and NFPA standards. At a minimum, the requirements of Chapter 7 of NFPA
72 shall be followed. Environments with large amounts of
dust, dirt or high air velocity require more frequent maintenance. A maintenance agreement should be arranged
through the local manufacturer's representative. Maintenance
should be scheduled monthly or as required by National and/
or local fire codes and should be performed by authorized professional fire alarm installers only. Adequate written records
of all inspections should be kept.
Installation Precautions
Adherence to the following will aid in problem-free
installation with long-term reliability:
WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all sources
of power before servicing. Control unit and associated equipment may be damaged by removing and/or inserting cards,
modules, or interconnecting cables while the unit is energized.
Do not attempt to install, service, or operate this unit until this
manual is read and understood.
CAUTION - System Reacceptance Test after Software
Changes. To ensure proper system operation, this product
must be tested in accordance with NFPA 72 Chapter 7 after
any programming operation or change in site-specific software. Reacceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring.
All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested.
In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not
directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified.
This system meets NFPA requirements for operation at
0-49° C/32-120° F and at a relative humidity of 85% RH (noncondensing) at 30° C/86° F. However, the useful life of the
system's standby batteries and the electronic components
may be adversely affected by extreme temperature ranges
and humidity. Therefore, it is recommended that this system
and all peripherals be installed in an environment with a nominal room temperature of 15-27° C/60-80° F.
Verify that wire sizes are adequate for all initiating and
indicating device loops. Most devices cannot tolerate more
than a 10% I.R. drop from the specified device voltage.
Like all solid state electronic devices, this system may
operate erratically or can be damaged when subjected to lightning-induced transients. Although no system is completely
immune from lightning transients and interferences, proper
grounding will reduce susceptibility. Overhead or outside
aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes. Consult with the Technical Services Department if any problems are anticipated or
encountered.
Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing,
reaming, or punching of the enclosure. When possible, make
all cable entries from the sides or rear. Before making modifications, verify that they will not interfere with battery, transformer, and printed circuit board location.
Do not tighten screw terminals more than 9 in-lbs.
Over-tightening may damage threads, resulting in reduced
terminal contact pressure and difficulty with screw terminal
removal.
Though designed to last many years, system components
can fail at any time. This system contains static-sensitive
components. Always ground yourself with a proper wrist strap
before handling any circuits so that static charges are removed from the body. Use static-suppressive packaging
to protect electronic assemblies removed from the unit.
Follow the instructions in the installation, operating, and
programming manuals. These instructions must be followed
to avoid damage to the control panel and associated
equipment. FACP operation and reliability depend upon
proper installation by authorized personnel.
FCC Warning
WARNING: This equipment generates, uses, and can
radiate radio frequency energy and if not installed and
used in accordance with the instruction manual, may
cause interference to radio communications. It has
been tested and found to comply with the limits for class
A computing device pursuant to Subpart B of Part 15 of
FCC Rules, which is designed to provide reasonable
protection against such interference when operated in a
commercial environment. Operation of this equipment in
a residential area is likely to cause interference, in which
case the user will be required to correct the interference
at his own expense.
Canadian Requirements
This digital apparatus does not exceed the Class A
limits for radiation noise emissions from digital
apparatus set out in the Radio Interference Regulations
of the Canadian Department of Communications.
Le present appareil numerique n'emet pas de bruits
radioelectriques depassant les limites applicables aux
appareils numeriques de la classe A prescrites dans le
Reglement sur le brouillage radioelectrique edicte par le
ministere des Communications du Canada.
LimWarLg.p65
01/10/2000
Notes
4
Document #15465
Rev.F1
12/04/02
P/N 15465:F1
Table of Contents
CHAPTER 1: Product Description ......................................................................................................................... 10
1.1: Product Features ..........................................................................................................................................10
FIGURE 1-1: DP-5012 Cover..............................................................................................................11
1.2: Circuits ........................................................................................................................................................11
1.3: Front Panel Switches ...................................................................................................................................11
1.4: Displays .......................................................................................................................................................12
1.5: Digital Communicator.................................................................................................................................12
1.6: ADM-12 Annunciator Driver Module - Optional .......................................................................................12
FIGURE 1-2: ADM-12/MS-5012........................................................................................................12
1.7: RZA-5F Remote Annunciator .....................................................................................................................13
FIGURE 1-3: RZA-5F Annunciator ....................................................................................................13
1.8: Specifications ..............................................................................................................................................13
CHAPTER 2: Control Panel Operation .................................................................................................................. 16
FIGURE 2-1: Display and Keypad ......................................................................................................16
2.1: Switch Functions in Normal Mode .............................................................................................................16
2.2: Displays .......................................................................................................................................................17
FIGURE 2-2: Communicator Connections and LEDs.........................................................................18
2.3: Operation.....................................................................................................................................................18
2.4: Digital Communicator.................................................................................................................................21
TABLE 2-1: Format Selection Addresses (16 & 42)...........................................................................22
TABLE 2-2: Compatible UL Listed Receivers....................................................................................25
CHAPTER 3: Installation......................................................................................................................................... 26
3.1: Cabinet Mounting Options ..........................................................................................................................26
FIGURE 3-1: Cabinet Dimensions and Knockout Locations..............................................................26
3.2: Input Circuits...............................................................................................................................................27
FIGURE 3-2: Initiating Device Circuits - TB2....................................................................................27
3.3: Output Circuits ............................................................................................................................................28
FIGURE 3-3: Output Circuits - TB3....................................................................................................28
FIGURE 3-4: Driving Relays From Open Collector Outputs..............................................................28
3.4: UL Power-limited Wiring Requirements ....................................................................................................29
FIGURE 3-5: Typical Wiring Diagram for UL Power-limited Requirements ....................................29
TABLE 3-1: Output Normal Conditions .............................................................................................29
3.5: Digital Communicator.................................................................................................................................30
FIGURE 3-6: Wiring Phone Jacks.......................................................................................................30
3.6: Operating Power..........................................................................................................................................31
3.6.1: Primary Power Source (AC) and Earth Ground Connections...........................................................31
3.6.2: Secondary Power Source (batteries) .................................................................................................31
FIGURE 3-7: MS-5012 Power Connections .......................................................................................31
3.6.3: Optional AC Terminal Block ............................................................................................................32
FIGURE 3-8: Optional AC Terminal Block Installation .....................................................................32
3.7: Optional Boards...........................................................................................................................................33
3.7.1: ADM-12 Annunciator Driver Module ..............................................................................................33
FIGURE 3-9: ADM-12 Module...........................................................................................................33
3.7.2: RZA-5F Remote Annunciator...........................................................................................................33
FIGURE 3-10: RZA-5F Remote Annunciator.....................................................................................33
FIGURE 3-11: Mounting the RZA-5F to Single-Gang Electrical Box ...............................................33
FIGURE 3-12: Wiring the RZA-5F to the ADM-12 ...........................................................................34
CHAPTER 4: Programming Instructions............................................................................................................... 35
4.1: Entering Program Mode ..............................................................................................................................35
FIGURE 4-1: First Address .................................................................................................................35
4.2: Switch Functions in Program Mode ...........................................................................................................36
Document 15465
Rev. F1
12/04/02
P/N: 15465:F1
5
Table of Contents
FIGURE 4-2: Switch Functions in Program Mode..............................................................................36
4.3: Programming ...............................................................................................................................................36
4.3.1: Programming the Primary Phone Number (00 - 15) .........................................................................36
4.3.2: Programming Primary Number Communication Format (16)..........................................................37
TABLE 4-1: 3+1 and 4+1 Standard and Expanded, 4+2 Expanded Formats......................................37
4.3.3: Programming the Primary Number Account Code (17-20) ..............................................................38
TABLE 4-2: 4+2 Standard Formats.....................................................................................................39
4.3.4: Programming the Primary Number 24 Hour Test Time (21-24).......................................................40
4.3.5: Programming Primary Number 24/12 Hour Test Time (25) .............................................................40
4.3.6: Programming the Secondary Phone Number (26-41) .......................................................................40
4.3.7: Programming Secondary Number Communication Format (42)......................................................41
TABLE 4-3: 3+1 and 4+1 Standard and Expanded, 4+2 Expanded Formats......................................41
4.3.8: Programming the Secondary Number Account Code (43-46) ..........................................................42
TABLE 4-4: 4+2 Standard Formats.....................................................................................................43
4.3.9: Programming the Secondary Number 24 Hour Test Time (47-50)...................................................44
4.3.10: Programming Secondary Number 24/12 Hour Test Time (51) .......................................................44
4.3.11: Programming Zone 3 Functionality (52).........................................................................................44
4.3.12: Programming Waterflow Retard Timer (53-54)..............................................................................44
4.3.13: Programming AC Loss Reporting Delay (55).................................................................................45
4.3.14: Programming Slave Communicator/Fire Panel Selection (56) .......................................................45
4.3.15: Secondary Phone Number Reporting (57) ......................................................................................45
4.3.16: Alarm Verification on Detector Zones 2 and 3 (58)........................................................................45
4.3.17: Silence Inhibit (59)..........................................................................................................................45
4.3.18: Auto Silence (60) ............................................................................................................................45
4.3.19: Trouble Reminder (61) ....................................................................................................................45
4.3.20: Bell Disable (62) .............................................................................................................................46
4.3.21: Annunciator Present (63) ................................................................................................................46
4.3.22: Programming Zone 4 Functionality (64).........................................................................................46
4.3.23: Address (65) - Not used ..................................................................................................................46
4.3.24: Touchtone/Rotary Select (66)..........................................................................................................46
4.3.25: Make/Break Ratio (67)....................................................................................................................46
4.3.26: Programming Event Codes (68-243)...............................................................................................46
4.3.27: End Programming ...........................................................................................................................46
4.3.28: Programming the Real-Time Clock ................................................................................................46
CHAPTER 5: Servicing............................................................................................................................................47
5.1: Walktest Mode.............................................................................................................................................47
5.2: History Mode...............................................................................................................................................48
5.3: Troubleshoot Mode......................................................................................................................................49
FIGURE 5-1: Handset Connection ......................................................................................................50
5.4: Lamp Test ....................................................................................................................................................50
CHAPTER 6: Slave Communicator Configuration ...............................................................................................51
Appendix A: Power Calculations .........................................................................................................................53
TABLE A-1: Total Ampere Hours .....................................................................................................53
TABLE A-2: Regulated Load in Standby ...........................................................................................54
TABLE A-3: Regulated Load in Alarm ..............................................................................................55
Appendix B: Programming Reference Sheets .....................................................................................................56
B.1: Blank System Programming Reference Sheets ........................................................................................56
B.2: Blank Format Programming Reference Sheet ...........................................................................................57
B.3: Programming Reference Sheet Factory Default Settings ..........................................................................58
B.4: Format Programming Reference Sheet Factory Default Sheet ..................................................................59
6
Document 15465
Rev. F1
12/04/02
P/N: 15465:F1
This control panel has been designed to comply with standards set forth by the following regulatory agencies:
• Underwriters Laboratories Standard UL 864
• NFPA 72 National Fire Alarm Code for Local, Remote Station Fire Alarm Systems
Before proceeding, the installer should be familiar with the following documents.
NFPA Standards
Intallation, Maintenance and Use of Central Station Fire Alarm Systems
Local Fire Alarm Systems
Use of Proprietary Fire Alarm Systems
Automatic Fire Detectors
Installation, Maintenance and Use of Notification Appliances for Fire Alarm Systems
Testing Procedures for Fire Alarm Systems.
Underwriters Laboratories Documents:
UL 38 Manually Actuated Signaling Boxes
UL 217 Smoke Detectors, Single and Multiple Station
UL 228 Door Closers–Holders for Fire Protective Signaling Systems
UL 268 Smoke Detectors for Fire Protective Signaling Systems
UL 268A Smoke Detectors for Duct Applications
UL 346 Waterflow Indicators for Fire Protective Signaling Systems
UL 464 Audible Signaling Appliances
UL 521 Heat Detectors for Fire Protective Signaling Systems
UL 864 Standard for Control Units for Fire Protective Signaling Systems
UL 1481 Power Supplies for Fire Protective Signaling Systems
UL 1638 Visual Signaling Appliances
UL 1971 Signaling Devices for Hearing Impaired
Other:
NEC Article 250 Grounding
NEC Article 300 Wiring Methods
NEC Article 760 Fire Protective Signaling Systems
ADA American with Disabilities Act
Applicable Local and State Building Codes
Requirements of the Local Authority Having Jurisdiction (LAHJ)
Fire•Lite Documents
Fire•Lite Device Compatibility Document
Document #15465
Document #15384
Rev. F1
12/04/02
P/N 15465:F1
7
8
Document #15465
Rev.F1
12/04/02
P/N 15465:F1
The MS-5012 Panel
Primary & Secondary Phone Lines
Connector for Annunciator
Driver Module
Piezo 85dB
5 Input
Zones
4-Digit LED
Display
4 Open Collector Outputs
Keypad
Holds up to 7 AH Batteries Up
to 60 Hrs. of Standby
Document #15465
Rev. F1
12/04/02
P/N 15465:F1
9
Product Description
CHAPTER 1
Product Description
The MS-5012 is a combination FACP (Fire Alarm Control Panel) and digital communicator, all on one circuit board.
It is a five-zone panel which uses conventional input devices. The panel accepts waterflow devices, two-wire smoke
detectors, four-wire smoke detectors, pull stations and other normally open contact devices. Outputs include NACs
(Notification Alarm Circuits), alarm relay, trouble relay, supervisory relay and communicator failure relay drivers.
The integral communicator transmits system status (alarms, troubles, AC loss, etc.) to a UL recognized Central Station via the public switched telephone network. The control panel has a built in programmer and may also serve as a
slave communicator to a host panel. It also supervises all wiring, AC voltage, telephone line input voltage and battery level.
1.1
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
10
Product Features
FACP (Fire Alarm Control Panel)
Slave Fire Communicator
12 volt operation
Real time clock
Telephone line active indicators
Trouble reminder
One Style D (Class A) zone
Four Style B (Class B) zones
Programmable zone ID
Alarm verification
Optional annunciators
✓ RZA-5F remote annunciator (requires ADM-12 Annunciator Driver Module)
✓ LED type annunciators
Small size [14.5" (36.83 cm) x 12.5" (31.75 cm) x 2.875" (7.303 cm)]
Event history storage
Silence inhibit
Auto-silence
Programmable event codes (all formats)
Touchtone/rotary dialing
Programmable make/break ratio
Communication confirmation (kissoff) LED
Fuseless
AC loss report meets UL 864 requirements
Number of dial attempts (5 minimum, 10 maximum)
Programmable channel ID (slave)
Programmable zone delay (waterflow only)
Four open collector outputs
Disable report by event
Low AC voltage sense
Walktest
Document #15465
Rev.F1
12/04/02
P/N 15465:F1
Circuits
•
•
•
•
Built-in voltmeter
Built-in programmer
One NFPA Style Y NAC (Notification Appliance Circuit)
Optional Dead Panel cover available
FIGURE 1-1: DP-5012 Cover
1.2
Circuits
Input Circuits
✓ Initiating Device Circuit #1 (Style B) Normally Open contact devices only
✓ Initiating Device Circuit #2 (Style B) Normally Open contact devices and 2-wire smoke detectors
✓ Initiating Device Circuit #3 (Style B/D) Normally Open contact devices, 2-wire smoke detectors (Style
B only), waterflow devices
✓ Initiating Device Circuit #4 (Style B) Normally Open contact devices only
✓ Initiating Device Circuit #5 (Style B) Normally Open contact devices only
Output Circuits
✓ Notification Appliance Circuit
✓ Resettable Power Circuit
✓ Nonresettable Power Circuit
✓ Relay Driver Output - Alarm
✓ Relay Driver Output - Trouble
✓ Relay Driver Output - Supervisory
✓ Relay Driver Output - Communicator Failure
✓ Primary Telephone Line
✓ Secondary Telephone Line
✓ 12 Volt Battery Charger
1.3
Front Panel Switches
Reset
Silence
Mode
Up Arrow
Down Arrow
1st Event
Enter/Store
u v w
123f q
456e r
789d s
a0bc t
Digits 0 - 9
A
B
C
D
E
F
Document #15465
Rev. F1
12/04/02
P/N 15465:F1
11
Displays
1.4
Displays
✓
✓
✓
✓
✓
✓
✓
✓
✓
1.5
Alarm - red LED
Trouble - yellow LED
Supervisory - yellow LED
AC Power - green LED
Four 7-Segment Displays - red
Primary Phone Line Active - red LED
Secondary Phone Line Active - red LED
'Kissoff' signal from Central Station - green LED
Silence - yellow LED
Digital Communicator
The integral communicator provides the following functions:
✓
✓
✓
✓
✓
✓
1.6
Line Seizure - takes control of the phone lines disconnecting any premises phones
Off/On Hook - perform on and off-hook status to the phone lines
Listen for dial tone - 440 hertz tone typical in most networks
Dialing the Central Station(s) number - default is Touch-Tone®, programmable to rotary
Discern proper 'Ack' and 'Kiss-off' tone(s) - the frequency and time duration of the tone(s) varies with
the transmission format. The control panel will adjust accordingly
Communicate in the following formats:
12 Tone Burst Types: 20 pps
(3+1, 4+1, 4+2, 3+1 Expanded, 4+1 Expanded, 4+2 Expanded)
ADM-12 Annunciator Driver Module - Optional
The ADM-12 Annunciator Driver Module permits connection of the RZA-5F Remote Annunciator module to the
MS-5012 and supervises annunciator wiring for open conditions. The ADM-12 mounts to the MS-5012 main circuit
board, occupying one of the two option connectors.
FIGURE 1-2: ADM-12/MS-5012
Connect ADM-12 to main circuit
board connector J3. Use the
supplied nylon spacer.
Make all connections with
power off.
12
Document #15465
Rev.F1
12/04/02
P/N 15465:F1
RZA-5F Remote Annunciator
1.7
RZA-5F Remote Annunciator
The RZA-5F Remote Annunciator mounts on a standard singlegang electrical box and provides LED indications for:
✓
✓
✓
✓
✓
✓
FIGURE 1-3: RZA-5F Annunciator
Alarm Zone 1 (red)
Alarm Zone 2 (red)
Alarm Zone 3 (red)
Alarm Zone 4 (red)
Alarm Zone 5 (red)
System Trouble (yellow)
A local trouble sounder and tone silence switch are also provided.
All LED wiring is supervised for open conditions. Any open will
cause the System Trouble LED to turn on. Slide-in paper labels
permit an easy change of zone information. The RZA-5F requires
the use of the ADM-12 Annunciator Driver Module.
1.8
Specifications
AC Power Primary - TB1 Terminals 1 & 2
120 VAC, 50,60 Hz, 0.32 amps
15.0 VAC, 50/60 Hz, 2.0 amps, 25 VA
Battery (sealed lead acid only) - Connector J1
Maximum Charging Capacity: 14.3 volts, 0.08 amps
Maximum Battery Capacity: 7 AH
Initiating Device Circuits - TB2 Terminals 1-2, 9-10, 11-12
Normally Open Contact Zones 1, 4, 5
Power-limited Circuitry
Operation: NFPA Style B
Normal Operating Voltage: 13.8 VDC (ripple = 100 mV maximum)
Short Circuit Current: 4.46 mA maximum
Maximum Loop Resistance: 100 ohms
End-of-Line Resistor: 2.2K, ½ watt (P/N 27070 UL listed)
Standby Current: 2.66 mA
Initiating Device Circuits - TB2 Terminals 3-4, 5-8
Detector Zones 2, 3
Power-limited Circuitry
Operation: Zone 2 (NFPA Style B), Zone 3 (NFPA Style B, D)
Connecting 2-wire detectors on Zone 3 requires NFPA Style B only
Normal Operating Voltage: 13.8 VDC (ripple = 100 mV maximum)
Alarm Current: 12 mA
Short Circuit Current: 24 mA maximum
Maximum Detector Current in Standby: 2 mA
Maximum Loop Resistance: 30 ohms
End-of-Line Resistor: 2.2K, ½ watt (P/N 27070 UL listed)
Detector Loop Current is sufficient to ensure operation of one alarmed detector per zone
Standby Current: 5.17 mA (including ELR)
Document #15465
Rev. F1
12/04/02
P/N 15465:F1
13
Specifications
Notification Appliance Circuit - TB3 Terminals 1 & 2
Power-limited Circuitry
Nominal Operating Voltage: 12 VDC
Requires minimum of 300 mA load
Total current available to external devices: 1 amp
End-of-Line Resistor: 2.2K, ½ watt (P/N 27070 UL listed)
Auxiliary Outputs - TB3 Terminals 4-7
Power-limited Circuitry
Type: Open Collector
Rating: 40 mA each @ nominal 12 VDC
TB3 Terminal 4 Alarm Relay Driver - normally high, active low, sinks up to 40 mA
TB3 Terminal 5 Trouble Relay Driver - normally low, active high, sinks up to 40 mA
TB3 Terminal 6 Supervisory Relay Driver - normally high, active low, sinks up to 40 mA
TB3 Terminal 7 Communicator Failure - normally high, active low, sinks up to 40 mA
Four-wire Smoke Detector Power - TB2 Terminals 13 (+) and 14 (-)
Power-limited Circuitry
Up to 200 mA is available for powering 4-wire smoke detectors
Maximum ripple voltage: 100 mV maximum
Normal Operating Voltage: 13.8 VDC
Nonresettable Power - TB3 Terminal 3 (+) and TB2 Terminal 14 (-)
Power-limited Circuitry
Available Current: 185 mA
Maximum ripple voltage: 100 mV maximum
Normal Operating Voltage: 13.8 VDC
Telephone Circuitry:
Ringer Equivalence Number (REN) = 0.0B
AC Impedance 10.0 Mega Ohm
Complies with FCC Part 68
Mates with RJ31X Male Connector
Supervision Threshold: less than 4.0 volts for 2 minutes
The REN is used to determine the quantity of devices which may be connected to the telephone line. Excessive
RENs on the telephone line may result in the devices not ringing in response to an incoming call. In most areas
(but not all), the sum of the RENs should not exceed five (5.0). To be certain of the number of devices that may
be connected to the line, as determined by the total RENs, contact the telephone company to determine the maximum REN for the calling area.
14
Document #15465
Rev.F1
12/04/02
P/N 15465:F1
Specifications
Digital Communicator:
Before connecting the control panel to the public switched telephone network, the installation of two RJ31X jacks
is necessary. The following information is provided if required by the local telephone company:
Manufacturer: Fire•Lite Alarms, Inc.
One Fire-Lite Place
Northford, CT 06472
Product Model Number: MS-5012
FCC Registration Number: 1W6USA-74525-AL-E
Ringer Equivalence 0.0B
Note: The FCC ID label is located on the inside of the control panel door.
Piezo Sounder
An on-board piezo sounder will emit three distinctly different audible tones depending on system activity:
✓ Steady on for alarms
✓ One second on and one second off for trouble
✓ ½ second on and ½ second off for supervisory
NAC Fault
The NFPA Style Y circuit configuration allows for connection of polarized bells, strobes and horns. The wiring to
these notification appliances is monitored for opens and shorts.
Telephone Company Rights and Warnings
The telephone company, under certain circumstances, may temporarily discontinue service and/or make changes
in its facilities, services, equipment or procedures which may affect the operation of this control panel. However,
the telephone company is required to give advance notice of such changes or interruptions.
If the control panel causes harm to the telephone network, the telephone company reserves the right to temporarily discontinue service. Advance notification will be provided except in cases when advance notice is not practical. In such cases, notification will be provided as soon as possible. The opportunity will be given to correct any
problems and to file a complaint.
DO NOT CONNECT THIS PRODUCT TO COIN TELEPHONE, GROUND START OR PARTY LINE SERVICES.
When the control panel activates, premise phones will be disconnected.
Two separate phone lines are required. Do not connect both telephone interfaces to the same telephone line.
The control panel must be connected to the public switched telephone network upstream of any private telephone
system at the protected premises.
An FCC compliant telephone cord must be used with this equipment. This equipment is designed to be connected
to the telephone network or premises wiring using a compatible RJ31X male modular plug which is Part 68
compliant.
Document #15465
Rev. F1
12/04/02
P/N 15465:F1
15
Control Panel Operation
CHAPTER 2
Control Panel Operation
The MS-5012 has six modes of operation:
✓
✓
✓
✓
✓
✓
FIGURE 2-1: Display and Keypad
Normal Mode
Program Mode
Walktest Mode
Lamp Test Mode
Troubleshoot Mode
History Mode
Upon initial power-up, the system will be in Normal Mode.
This section discusses operation of the control panel in the
Normal Mode. Programming is discussed in Chapter 4.
Walktest, History and Troubleshoot Modes are discussed in
“Servicing” on page 47.
2.1
Switch Functions in Normal Mode
u
The Reset Switch resets the system and any smoke detectors. Pressing the Reset Switch cause the control panel to:
✓
✓
✓
✓
✓
✓
✓
Clear the display and status LEDs
Turn off the Notification Appliance Circuit
Reset all zones by temporarily removing power
Silence the on board piezo sounder
Store 'Reset' message in the History file (see “History Mode” on page 48)
Clear all relay driver outputs
Temporarily remove power from the resettable power output (TB1 Terminals 13 & 14)
Any alarm, supervisory or trouble condition that exists after a system reset, will resound the system, reactivating normal system activity. Upon release of the Reset Switch, the display will rES read for six seconds.
v
If the Silence Switch is pressed:
✓
✓
✓
✓
The Notification Appliance Circuit will be turned OFF
The Silence LED will be turned ON
The piezo sounder will be turned OFF
'System Silenced' message will be stored in the History file
Upon the occurrence of a subsequent event (alarm or trouble), System Silence is overridden and the control panel will
respond to the new event. The System Silence switch will be ignored for waterflow type alarms.
16
Document #15465
Rev.F1
12/04/02
P/N 15465:F1
Displays
w
Pressing the Mode Switch followed by a valid 4-digit numerical code selects one of the five modes of operation.
☛
To enter Normal Mode from any other mode, press
followed by
w then 6676
t. 6676 spells NORM on a Touch-Tone
® phone.
s
The 1st Event switch, along with the Up arrow and Down arrow switches, are used to display any currently active
alarm and/or fault conditions present in the system. Press the 1st Event switch at any time to display the 1st event
(alarm and/or trouble) that occurred.
r
q
Down arrow - use the Down arrow switch to view other events (older) that have occurred and
are active (not yet cleared).
Up arrow - use the Up arrow switch to view other events (newer) that have occurred and are
active (not yet cleared).
t
The
t switch is not used in Normal Mode.
2.2
Displays
Four 7-segment red LED characters provide visual annunciation of status, events and messages. The messages that
may appear on the display in Normal Mode are listed below:
A
A
A
A
A
F
F
F
F
F
F
1
2
3
4
5
1
2
3
4
5
A
Alarm Zone 1
Alarm Zone 2
Alarm Zone 3
Alarm Zone 4
Alarm Zone 5
Trouble Zone 1
Trouble Zone 2
Trouble Zone 3
Trouble Zone 4
Trouble Zone 5
Annunciator Fault
F E
Lo b
no b
PH 1
PH 2
bELL
no 1
no 2
SUP4
AC
rES
Document #15465
Earth Fault
Low Battery
No Battery
Primary Number Communication Fault
Secondary Number Communication Fault
Bell Fault
Primary Phone Line Fault
Secondary Phone Line Fault
Supervisory Alarm
AC Power Loss
Reset
Rev. F1
12/04/02
P/N 15465:F1
17
Operation
Individual LEDs are provided for:
• System Alarm - red LED that lights when an alarm condition is detected
• System Trouble - yellow LED indicates that a fault or abnormal condition exists and that the fire alarm system may be inoperative
• AC Power ON - green LED that remains on while the AC power supply is operating. If this indicator fails to
light under normal conditions, service the system immediately
• Supervisory - yellow LED that indicates need for action in connection with the supervision or maintenance of
sprinklers, extinguishing systems or other protective systems
• System Silence - yellow LED that indicates an Alarm or Trouble has been silenced
• Primary Line Active - red LED on the main circuit board that indicates the primary phone line is active
• Secondary Line Active - red LED on the main circuit board that indicates the secondary phone line is active
• Kiss-off - green LED on the main circuit board that indicates the Central Station has acknowledged receipt of
transmitted message
FIGURE 2-2: Communicator Connections and LEDs
Primary Line
Secondary Active LED
Secondary Line
Kiss-off LED
Primary Active LED
2.3
Operation
Normal Mode is the standard mode of operation. In this mode, the panel continuously monitors system status. When
no alarm or fault conditions exist, the display will be blank and all LEDs will be off (except the AC Power LED).
The Notification Appliance Circuit will be off, all relay drivers are deactivated and the on-board piezo sounder will
be off. The communicator is not active, and the Primary and Secondary Active LEDs are off.
All alarm conditions and fault conditions are annunciated on the control panel's display. The control panel will maintain an 'active event list' as illustrated in “Displays” on page 17. The list will consist of all alarms, supervisory alarms
and faults currently active and not cleared, requiring immediate service. When the system is cleared and restored to
normal, the display will be blank. All alarms and faults are stored in a history file and may be recalled at any time.
Refer to “History Mode” on page 48.
18
Document #15465
Rev.F1
12/04/02
P/N 15465:F1
Operation
Higher priority events take precedence over lower priority events. Display of System Activity is accomplished on a
priority basis. Priorities are, from highest to lowest:
1.
2.
3.
Alarms
Supervisory alarms
Faults (troubles)
The highest priority event will be communicated to the Central Station first. It also is displayed, overriding any other
displayed event. Only one event is displayed at a time. Whenever multiple events occur, an authorized user may
view each event by pressing the Up and Down arrow switches on the keypad. At any time, the user may press the 1st
Event switch to display the first event that occurred (that is, the first event that occurred after the panel was last reset,
cleared of all active events and placed into Normal Mode).
If the events to be displayed are alarms only (no troubles), the control panel will scroll them on the display. Pressing
the 1st Event switch will stop the scrolling and cause the display of the first alarm that occurred. Operation of the Up
and Down arrow switches will display all remaining alarms in sequence.
Alarm Response
The MS-5012 will, upon detection of an alarm condition, perform the following functions:
✓
✓
✓
Turn the alarm LED on
Activate the alarm relay driver (TB3-4)
Display an alarm message as follows:
A
A
A
A
✓
✓
✓
✓
1
2
3
5
Alarm Zone 1
Alarm Zone 2
Alarm Zone 3
Alarm Zone 5
(Note that when Zone 4 is programmed as a supervisory zone, it will not be processed in the same
manner as a conventional alarm one. See 'System Supervisory Condition' later in this section.)
Communicate the alarm to the Central Station
Store the alarm in the History file
Turn the Notification Appliance Circuit on
Turn the piezo sounder on
Alarm Restoral
The control panel returns to normal only after all alarms have been cleared (pull stations reset, smoke detectors reset
and no smoke is present, waterflow has stopped) and the Reset switch has been pressed. The control panel will perform the following upon restoral of all active alarms:
✓
✓
✓
✓
✓
✓
Turn off the alarm LED
Deactivate the alarm relay driver (TB3-4)
Clear the 4- character display
Send all 'Zone Restoral' messages to the Central Station
Turn off the Notification Appliance Circuit
Turn off the piezo sounder
Document #15465
Rev. F1
12/04/02
P/N 15465:F1
19
Operation
System Supervisory Condition
Zone 4 is factory programmed as a supervisory zone. This zone is primarily used in applications where a waterflow
sensing device has been employed and the wiring to the waterflow valve and/or a tamper switch is monitored. If the
wiring is cut, a trouble condition will occur. If the Normally Open tamper switch is activated, a supervisory condition
will occur.
When a supervisory condition occurs, the control panel will:
✓
✓
Turn on the supervisory LED
Activate the supervisory relay driver (TB3-6)
✓
Display the following message - SUP4
✓
Communicate the supervisory condition to the Central Station
Store 'supervisory' message in the History file
Pulse the piezo sounder at ½ second On, ½ second Off rate
✓
✓
When the supervisory condition has been cleared (normal condition is restored and the Reset switch has been
pressed), the MS-5012 will perform the following:
✓
✓
Turn off the supervisory LED
Deactivate the supervisory relay driver (TB3-6)
✓
Clear the display of the message - SUP4
✓
Communicate the 'supervisory restoral' message to the Central Station
Shut off the piezo sounder
✓
Trouble Conditions
The control panel will perform the following upon detection of a trouble condition:
✓
✓
✓
Turn on the trouble LED
Activate the trouble relay driver (TB3-5)
Display the appropriate trouble message. Following are the trouble messages shown in order of priority, from the highest priority to the lowest:
AC
F 1
F 3
F 2
F 5
F 4
F E
L b
no b
no 1
no 2
bELL
PH 1
PH 2
F A
rES
20
AC Loss (must press Up arrow, Down arrow or 1st Event to view)
Trouble on Zone 1
Trouble on Zone 3
Trouble on Zone 2
Trouble on Zone 5
Trouble on Zone 4
Ground Fault
Low battery
No battery
Primary Phone Line Fault
Secondary Phone Line Fault
Bell Circuit (NAC) Fault
Primary Number Communication Fault
Secondary Number Communication Fault
Annunciator Fault
Reset
Document #15465
Rev.F1
12/04/02
P/N 15465:F1
Digital Communicator
✓
✓
✓
Communicate the trouble condition to the Central Station
Store the trouble condition in the History file
Sound the piezo sounder one second On, one second Off
Note: When AC Brownout occurs, the AC LED turns off and the Trouble LED turns on. Should the
brownout condition remain, it will be transmitted to the Central Station after a delay (see Program
Address 55 in “Programming” on page 36).
Trouble Condition Restoral
The control panel performs the following upon restoral of a trouble condition:
✓
✓
✓
✓
✓
Turn off the trouble LED
Deactivates the trouble relay driver (TB3-5)
Turn on the AC LED upon restoral, if the trouble was loss of AC power
Clear the display of the trouble message
Communicate the restored trouble condition to the Central Station
OFF Normal Reporting
Removing the panel from Normal Mode, and placing it into any other mode, causes a transmission of an 'Off Normal'
fault message to the Central Station. Returning the panel to Normal Mode causes a transmission of a 'Return to Normal' restoral message.
2.4
Digital Communicator
The MS-5012 transmits zone and system status reports to the Central Station via the public switched telephone network. Two supervised telephone line connections are made to interface the control panel to the telephone lines. Two
optional 7-foot telephone cords are available for this purpose. Refer to Figure 3-6, “Wiring Phone Jacks,” on page
30, for proper wiring.
The control panel supervises both telephone lines for proper voltage. A delay of two minutes will occur before a fault
in either phone line connection is reported as a trouble. When a fault is detected, an audible trouble signal will sound,
the yellow trouble LED will turn on, the 4-character display will show either no1 for Primary Line or no 2
for Secondary Line, depending upon which telephone line has the fault, and the trouble condition will be reported to
the Central Station over the remaining operational phone line.
The control panel comes with line seizure capability provided to both the primary and secondary telephone line interfaces. Any time the control panel needs to make a call to the Central Station, line seizure will disconnect any local
premises phones sharing the same telephone line.
All transmissions to the Central Station will be sent over the Primary phone line. In the event of noisy phone lines,
transmissions will be sent over the backup Secondary phone line.
Two phone numbers must be programmed, the primary phone number and the secondary phone number. See “Programming” on page 36. All system reports will be transmitted to the primary phone number. Reports will automatically be sent to the secondary phone number if attempts to transmit to the primary phone number are unsuccessful. If
10 attempts to communicate are unsuccessful, the Communicator Failure output will be turned on (TB3, Terminal 7).
Note that as an option, all reports may be sent to the secondary phone number.
Document #15465
Rev. F1
12/04/02
P/N 15465:F1
21
Digital Communicator
The MS-5012 meets NFPA 72 National Fire Alarm Code for Central Station Fire Alarm Systems and for Remote Station Protective Fire Alarm Systems reporting requirements for: (a) the type of signal (b) condition (c) location of the
reporting premises. The general priority reporting structure is:
1.
2.
3.
4.
Zone Alarms and Restorals
Zone Troubles and Restorals
System Troubles and Restorals
24-hour test
The control panel is capable of reporting detailed messages depending upon the communication format is use. Table
4-1 through Table 4-4 list these messages. Table 2-1 shows the reporting structure for all of the tone burst type
formats.
TABLE 2-1:
22
Format Selection Addresses (16 & 42)
Format # 2, 4, 6, 8
Format # 3, 5, 7, 9
Format # A, C
Format # B, D
Report
3+1/4+1 Standard
3+1/4+1/Expanded
4+2/Standard
4+2/Expanded
Alarm
SSS(S) A
SSS(S) A
AAA(A) Z
SSSS AA2
SSSS AZ
Alarm Restore
SSS(S) RA
SSS(S) RA
RARARA(RA) Z
SSSS RARA2
SSSS RAZ
Zone Trouble
(Zone Open)
SSS(S) TZ
SSS(S) TZ
SSSS TZTZ2
SSSS TZZ
Zone Trouble
Restore
SSS(S) RTZ
SSS(S) RTZ
RTZRTZRTZ(RTZ) Z
SSSS RTZRTZ2
SSSS RTZZ
System Trouble
SSS(S) TS
SSS(S) TS
TSTSTS(TS) Y
SSSS TSTS2
SSSS TSY
System Trouble
Restore
SSS(S) RTS
SSS(S) RTS
RTSRTSRTS(RTS) Y
SSSS RTSRTS2
SSSS RTSY
Low Battery
SSS(S) L
SSS(S) L
SSSS LL2
SSSS LL2
Low Battery
Restore
SSS(S) RL
SSS(S) RL
SSSS RLRL2
SSSS RLRL2
AC Loss
SSS(S) P
SSS(S) P
SSSS PP2
SSSS PP2
AC Loss Restore
SSS(S) RP
SSS(S) RP
SSSS RPRP2
SSSS RPRP2
Supervisory
Condition
SSS(S) V
SSS(S) V
VVV(V) Z
SSSS VV2
SSSS VV2
Supervisory
Condition
Restore
SSS(S) RV
SSS(S) RV
RVRVRV(RV) Z
SSSS RVRV2
SSSS RVZ
Test Report
SSS(S) X
SSS(S) X
SSSS XX2
SSSS XX2
Document #15465
Rev.F1
12/04/02
P/N 15465:F1
Digital Communicator
Following is a description of the terms used in the reporting structure in Table 2-1 .
SSS or
SSSS
A
A2
Z
RA
RA2
TZ
TZ2
RTZ
RTZ2
TS
TS2
RTS
RTS2
L
L2
RL
RL2
P
P2
RP
RP2
V
V2
RV
RV2
X
X2
Y
= Subscriber ID
= Alarm (1st digit)
= Alarm (2nd digit)
= Zone Number
= Alarm Restore (1st digit)
= Alarm Restore (2nd digit)
= Zone Trouble (1st digit)
= Zone Trouble (2nd digit)
= Zone Trouble Restore (1st digit)
= Zone Trouble Restore (2nd digit)
= System Trouble (1st digit)
= System Trouble (2nd digit)
= System Trouble Restore (1st digit)
= System Trouble Restore (2nd digit)
= Low Battery (1st digit)
= Low Battery (2nd digit)
= Low Battery Restore (1st digit)
= Low Battery Restore (2nd digit)
= AC Loss (1st digit)
= AC Loss (2nd digit)
= AC Loss Restore (1st digit)
= AC Loss Restore (2nd digit)
= Supervisory Condition (1st digit)
= Supervisory Condition (2nd digit)
= Supervisory Condition Restore (1st digit)
= Supervisory Condition Restore (2nd digit)
= Test Report (1st digit)
= Test Report (2nd digit)
= 6 = AC Loss
= 7 = Ground Fault
= 8 = Low Battery
= 9 = No Battery
= A = Telco Primary Line Fault
= B = Telco Secondary Line Fault
= C = Main Bell (NAC) Fault, Annunciator Fault
= D = Communication Fault to Primary Number
= E = Communication Fault to Secondary Number
= F = System Off Normal Fault/System Fault
(See “Slave Communicator Configuration” on page 51)
Note: For Expanded Reporting, the control panel automatically adds the digit corresponding to the
zone number, and the second digit corresponding to any system trouble condition. Only the first digit
is programmable.
Document #15465
Rev. F1
12/04/02
P/N 15465:F1
23
Digital Communicator
Transmittal Priorities
The integral communicator transmits highest priority events first. Events in terms of priority are listed below in
descending order:
1.
2.
3.
4.
5.
Alarms (Highest Priority Level)
Pull Stations
Waterflow
Smoke Detectors
Other Alarm Types
Supervisory Zone
Faults
AC Fail
Zonal Faults
Earth Fault
Low Battery/No Battery
Telephone Line Fault
Bell Circuit (NAC) Fault
Communication Trouble
Annunciator Trouble
Restoral
AC
Zones
Earth
Battery
Telephone Line
Bell (NAC)
Communication
Annunciator Trouble
24-Hour Test (Lowest Priority)
LED Indicators
Red LEDs are provided on the control panel circuit board to identify which telephone line is activated. A green LED
labeled 'Kissoff', will turn on whenever the control panel has successfully transmitted reports to the Central Station.
The 'Kissoff' LED may turn on several times during communications.
24
Document #15465
Rev.F1
12/04/02
P/N 15465:F1
Digital Communicator
UL Listed Receivers Compatible with the MS-5012
The following table lists the UL listed receivers which are compatible with the MS-5012 Control Panel.
0
Not Used
1
Not Used
2
3+1/Standard/1800/2300
✔
✔
✔
✔
✔
3
3+1/Expanded/1800/2300
✔
✔
✔
✔
4
3+1/Standard/1900/1400
✔
✔
5
3+1/Expanded/1900/1400
✔
✔
6
4+1/Standard/1800/2300
✔
✔
7
4+1/Expanded/1800/2300
✔
8
4+1/Standard/1900/1400
9
Surguard
MLR-2 (8)
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
✔
4+1/Expanded/1900/1400
✔
✔
✔
✔
✔
✔
A
4+2/Standard/1800/2300
✔
✔
✔
✔
✔
✔
B
4+2/Expanded/1800/2300
✔
✔
✔
✔
✔
✔
C
4+2/Standard/1900/1400
✔
✔
✔
✔
✔
✔
D
4+2/Expanded/1900/1400
✔
✔
✔
✔
✔
✔
E
Not Used
F
Not Used
✔
✔
✔ (5, 6)
Sescoa
3000R (7)
Radionics
6000/6500 (5)
Osborne Hoffman
Models 1 & 2
FBI
CP220FB (4)
ITI
CS-4000 (3)
Format #
(Addresses 16 & 42)
Silent Knight
9000 (2)
Compatible UL Listed Receivers
Ademco
685 (1)
TABLE 2-2:
✔ (5)
✔ (5)
(1) With 685-8 Line Card with REV. 4.4d software
(2) With 9002 Line Card Rev. 9035 software or 9032 Line Card with 9326A software
(3) Rev. 4.0 software
(4) FBI CP220FB Rec-11 Line Card with Rev. 2.6 software and a memory card with Rev. 3.8 software
(5) Model 6500 with Rev. 600 software
(6) Model 6000 with Rev. 204 software
(7) With Rev. B control card at Rev. 1.4 software and Rev. C line card at Rev. 1.5 software
(8) Version 1.62 software
Document #15465
Rev. F1
12/04/02
P/N 15465:F1
25
Installation
Installation
CHAPTER 3
3.1
Cabinet Mounting Options
The cabinet may be either semi-flush or surface mounted. The cover is removable during the installation period. The
cabinet mounts using two key slots and two additional 0.250" diameter holes located in the backbox. The key slots
are located at the top of the backbox and the two securing holes at the bottom. Refer to Figure 3-1 for cabinet
dimensions.
FIGURE 3-1: Cabinet Dimensions and Knockout Locations
Top
6.000" (15.240 cm)
0.875“
(2.223 cm)
2.000" (5.080 cm)
1.125“
(2.858 cm)
1.250"
(3.175 cm)
3.000" (7.620 cm)
12.500" (31.750 cm)
Left
0.624"
(1.585 cm)
12.500" (31.750 cm)
6.500" (16.510 cm)
Right
1.250"
(3.175 cm)
3.250”
(8.255 cm)
1.750”
(4.445 cm)
9.830"
(24.968 cm)
Cabinet
Mounting Holes
5.250”
(13.335 cm)
14.500"
(36.830 cm)
1.250”
(3.175 cm)
3.000”
(7.620 cm)
10.000” (25.400 cm)
16.625"
12.625"
3.000”
(7.620 cm)
1.250”
(3.175 cm)
Bottom
14.625"
17.625"
TR-3-R (MS-5012) Trim Ring
Draw wires through the respective knockout locations.
26
Document #15465
Rev.F1
12/04/02
P/N 15465:F1
Input Circuits
3.2
Input Circuits
The MS-5012 has five zone input circuits. The maximum loop resistance limit for each circuit is 100 ohms. All field
wiring for each zone is supervised for opens and ground faults. Both conditions are visually and audibly annunciated
as well as communicated to the Central Station.
• Zone 1 is a Style B Initiating Device Circuit (IDC) designed to accept any Normally Open contact device on
TB2, Terminals 1 & 2. It is power-limited to 2.66 mA in standby and 4.46 mA in alarm. The factory default
is 'Pull Station'. Refer to “Programming Instructions” on page 35.
• Zone 2 is a Style B Initiating Device Circuit designed to accept any Normally Open contact device and conventional 2-wire, 12 volt smoke detectors on TB2, Terminals 3 & 4. It is power-limited to 7.17 mA in standby
and 24 mA in alarm. For a list of compatible 2-wire detectors refer to the Fire•Lite Device Compatibility Document. The factory default is '2-wire Detectors'. Refer to “Programming Instructions” on page 35.
• Zone 3 is a Style D Initiating Device Circuit. It is designed to accept any Normally Open contact devices, 2wire smoke detectors (Style B only) and waterflow sensing devices on TB2, Terminals 5 - 8. It is power-limited to 7.17 mA in standby and 24 mA in alarm. A maximum of five waterflow devices may be used per
NFPA 71. For a list of compatible 2-wire detectors, refer to the Fire•Lite Device Compatibility Document.
The factory default is 'waterflow'. Refer to “Programming Instructions” on page 35.
Note: When Zone 3 is programmed to accept 2-wire smoke detectors, it will only function as an NFPA
Style B Initiating Device Circuit. See Figure 3-2.
• Zone 4 is a Style B Initiating Device Circuit designed to function as a supervisory zone or may accept any
Normally Open contact device on TB2, Terminals 9 & 10. As a supervisory zone, the circuit may or may not
be able to detect a supervisory alarm condition after the occurrence of an open in the loop wiring. It is powerlimited to 2.66 mA in standby and 4.46 mA in alarm. Factory default is 'Supervisory'. Refer to “Programming
Instructions” on page 35.
• Zone 5 is a Style B Initiating Device Circuit designed as a general purpose 'initiating zone'. It will accept any
Normally Open contact device on TB2, Terminals 11 & 12. It’s power-limited to 2.66 mA in standby and 4.46
mA in alarm. Factory default is '4-wire Smoke Detector'. Refer to “Programming Instructions” on page 35.
Four wire smoke detectors may be connected to any zone. Resettable power is provided via TB2, Terminals 13 & 14.
See Figure 3-2 for proper connection of 4-wire detectors.
It is allowable to mix an assortment of device types on any zone, however, it is not recommended. By not mixing
device types on one zone, messages sent to the Central Station may be very specific and detailed.
FIGURE 3-2: Initiating Device Circuits - TB2
Zone 1
Pull Stations
Zone 2
2-Wire
Smoke
Detectors
Zone 3
Waterflow
Devices
Zone 4
Supervisory
Tamper
Switches
2-Wire
Smoke
Detectors
Zone 3
TB2
Zone 3 Connection
of 2-Wire Smoke Detectors,
Style B Only.
4-Wire
Smoke
Detectors
Zone 5
TB2
UL Listed
Supervision
Relay
P/N A77-716-01
Document #15465
Rev. F1
12/04/02
P/N 15465:F1
27
Output Circuits
For example, default programming provides the following:
• Zone 1 activation will be reported to the Central Station as 'Manual Pull Station Alarm'
• Zone 4 activation will be reported to the Central Station as 'Supervisory Alarm'
• Zone activation, for reporting formats that do not allow for detailed reports, will be reported to the Central
Station as 'Zone 1 Alarm' or 'Zone 4 Alarm'.
Refer to “Operation” on page 18 and “Programming” on page 36 for additional information.
3.3
Output Circuits
One Style Y Notification Appliance Circuit is provided. This supervised circuit allows for the powering of polarized
bells, strobes and horns in an alarm condition. Up to one amp of special purpose power is available. For a list of
compatible devices, refer to the Fire•Lite Device Compatibility Document. A minimum 300 mA load is required.
FIGURE 3-3: Output Circuits - TB3
Notification Appliances (Bells)
+13.8 VDC
General Alarm
Open
Collector
Outputs
General Trouble
Supervisory
Communication Fail
Note: Active Low
40 mA each (max.)
TB3
Two RJ31X style phone jacks are provided for the connection of two independent telephone lines. Telephone line
control/command is possible via double line seizure. Refer to Figure 3-6 on page 30.
Relay driver outputs, which can be used to drive UL-864 listed remote relays, are available for Alarm, Trouble,
Supervisory and Communicator Failure. Refer to Figure 3-4
FIGURE 3-4: Driving Relays From Open Collector Outputs
UL Recognized Enclosure
+13.8 VDC
General Alarm
General Trouble
Supervisory
TB3
Communication Fail
Relays
28
Document #15465
Rev.F1
12/04/02
P/N 15465:F1
UL Power-limited Wiring Requirements
The control panel's open collector outputs on Terminal TB3 can be used to activate UL-864 listed remote relays. Outputs are rated for 40 mA. The normal condition for each output is as shown below:
TABLE 3-1:
Output Normal Conditions
Output
Condition
TB3-4 Alarm
Off (deenergized)
TB3-5 Trouble
On (energized)
TB3-6 Supervisory
Off (deenergized)
TB3-7 Communications Failure
Off (deenergized)
Relays must be placed in a UL-864 recognized enclosure. Wiring from the control panel's terminals on TB3 to the
relays must be less than 3 feet (90 cm) in length and enclosed in conduit. Wiring from the relay outputs must remain
in the same room as the location of the relay enclosure and be enclosed in conduit.
3.4
UL Power-limited Wiring Requirements
Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All power-limited circuit
wiring must remain at least 0.25" (6.35 mm) away from any nonpower-limited circuit wiring. Furthermore, all
power-limited circuit wiring and nonpower-limited circuit wiring must enter and exit the cabinet through different
knockouts and/or conduits. A typical wiring configuration for the MS-5012 is shown in Figure 3-5.
FIGURE 3-5: Typical Wiring Diagram for UL Power-limited Requirements
Power-limited Circuits
123456789
ADM-12
Secondary
Active
TB2
Power-limited Circuits
(optional)
Kissoff
Primary
Active
T1
Power-limited Circuits
TB3
TB1
750 mA Max
charger output
J1
AC Power
Document #15465
Rev. F1
12/04/02
P/N 15465:F1
29
Digital Communicator
3.5
Digital Communicator
Two independent telephone lines can be connected to the MS-5012. Telephone line control/command is made possible via double line seizure as well as usage of RJ31X style interconnections. Note: It is critical that the panel's digital communicator be located as the first device on the incoming telephone circuit to properly function.
The control panel's digital communicator is built right into the main circuit board. All that is required to install the
system is the connection and wiring of two phone lines as shown in Figure 3-6.
FIGURE 3-6: Wiring Phone Jacks
(Primary Lines)
Incoming Telco
Phone Lines
Tip
Ring
Tip
Green Wire
Green Wire
Red Wire
Ring
Ring
To Premises Phone
Ring
Red Wire
(Secondary Lines)
Incoming Telco
Phone Lines
To Premises Phone
Tip
Tip
Note: Shorting bars inside RJ31X Jack
removed during male plug insertion
Primary
Phone Line
PH-1
7 Foot Cable (MCBL-7)
(not supplied - order separately)
Secondary
Phone Line
PH-2
Male Plug Connectors
Modular Female Connectors
MS-5012
30
Document #15465
Rev.F1
12/04/02
P/N 15465:F1
Operating Power
3.6
Operating Power
3.6.1 Primary Power Source (AC) and Earth Ground Connections
AC power connections are made inside the control panel cabinet. Primary power source is 120 VAC, 50/60 Hz, 0.32
amps. A pair of wires, with a ground conductor, should be connected from the protected premises main breaker box
to the black and white primary leads of the MS-5012 system transformer. As per the National Electric Code, use 14
AWG (2.0 mm2) or heavier gauge wire with 600V insulation. No other equipment may be connected to this circuit.
In addition, this circuit must be provided with overcurrent protection and may not contain any power disconnect
devices.
Connect the backbox ground stud to a solid earth ground (a metallic cold water pipe may be suitable in some installations). This connection is vital for maintaining the control panel's immunity to unwanted electrical transients generated by lightning and electrostatic discharge.
3.6.2 Secondary Power Source (batteries)
Observe polarity when connecting the battery. Connect the battery cable to J1 on the main circuit board using the
plug-in connector provided. The battery charger is current-limited and capable of recharging sealed lead acid type
batteries. The charger shuts off when the system is in alarm. CAUTION: Battery contains sulfuric acid which can
cause severe burns to the skin and eyes and can destroy fabrics. If contact is made with sulfuric acid, immediately
flush the skin or eyes with water for 15 minutes and seek immediate medical attention.
FIGURE 3-7: MS-5012 Power Connections
Document #15465
Rev. F1
12/04/02
P/N 15465:F1
31
Operating Power
3.6.3 Optional AC Terminal Block
An optional AC terminal block is available for the MS-5012 Control Communicator. The terminal block can only be
used on the larger backbox [14.5" (36.83 cm) x 12.5" (31.75 cm) x 2.875" (7.303 cm)]. It cannot be installed in the
smaller backbox [12.0" (30.48 cm) x 9.0" (22.86 cm) x 2.75" (6.985 cm)].
!
WARNING: Make certain all power (AC and battery) is removed before any connections are made.
1.
2.
3.
4.
5.
6.
7.
8.
Mount the optional AC terminal block to the lower left of the MS-5012 backbox using the two supplied
screws.
Connect AC power wiring to the optional terminal block as shown in Figure 3-8.
Connect the black and white wires (primary) from the MS-5012 system transformer to the optional terminal
block as illustrated in Figure 3-8. Make certain the black AC wire (Hot) is connected opposite the black transformer wire and the white AC wire (Neutral) is connected opposite the white transformer wire.
Make certain that the yellow wires (secondary) from the MS-5012 system transformer are connected to Terminal Block TB1 located in the lower left corner of the MS-5012 main circuit board.
Install a jumper between the terminal block and the backbox ground stud as illustrated in Figure 3-8. This will
be used to provide lightning protection to the panel. Make certain the jumper is connected opposite the green
AC ground wire on the terminal block.
Install a solid earth ground connection to the backbox ground stud as illustrated below. This will be used to
provide lightning protection to the panel.
Press the AC terminal cover firmly into place.
Reapply AC and battery power to the MS-5012 Control Communicator.
FIGURE 3-8: Optional AC Terminal Block Installation
MS-5012 Main Circuit Board
MS-5012 Backbox
32
Document #15465
Rev.F1
12/04/02
P/N 15465:F1
Optional Boards
3.7
Optional Boards
3.7.1 ADM-12 Annunciator Driver Module
FIGURE 3-9: ADM-12 Module
The Annunciator Driver Module supports the RZA-5F
Remote Annunciator module. Annunciator wiring is
supervised for open conditions by this module. The
ADM-12 mounts to the MS-5012 main circuit board,
occupying one of the two option connectors (refer to
“ADM-12 Annunciator Driver Module - Optional” on
page 12).
3.7.2 RZA-5F Remote Annunciator
The RZA-5F mounts on a standard single-gang electrical
box and provides LED indications of the following:
•
•
•
•
•
•
FIGURE 3-10:RZA-5F Remote Annunciator
Alarm Zone 1 (red)
Alarm Zone 2 (red)
Alarm Zone 3 (red)
Alarm Zone 4 (red)
Alarm Zone 5 (red)
System Trouble (yellow)
In addition, the remote annunciator provides a local piezo
sounder and a remote sounder shut off switch. All LED
wiring is supervised for open conditions. Any open condition will cause the System Trouble LED to illuminate
and the piezo to sound. Note that the RZA-5F Remote
Annunciator requires the use of an ADM-12 Annunciator
Driver Module.
The following figures illustrate the mounting of the RZA-5F and the wiring of the RZA-5F to the ADM-12.
FIGURE 3-11:Mounting the RZA-5F to Single-Gang Electrical Box
Screw #6-32 X 1.00” LG
Document #15465
Rev. F1
12/04/02
P/N 15465:F1
33
Optional Boards
FIGURE 3-12:Wiring the RZA-5F to the ADM-12
12 VDC
ADM-12
Note: Make wiring connections with
system power off. Maximum wire
impedance is 100 ohms per wiring
connection.
RZA-5F
34
Document #15465
Rev.F1
12/04/02
P/N 15465:F1
Programming Instructions
CHAPTER 4
Programming Instructions
Programming of the MS-5012 is possible at any time except when an alarm condition is present in the Normal Mode
of operation. The MS-5012 has been designed for many different types of applications. After examining your specific application, review the programming options and choose the entries best suited for your system.
The MS-5012 has a built-in programmer. All programming selections are stored in nonvolatile EEPROM (Electrically-Erasable Programmable Read-Only Memory). This ensures that the control panel will remember all entries in
programming mode even if both AC and battery power are removed.
The user must program the primary and secondary phone numbers, account numbers and 24 hour test report times for
each Central Station account and the current time. The control panel comes with factory chosen options/features
already programmed. Alternate options/features may be programmed if desired. If all factory default settings are
acceptable, programming is complete.
4.1
Entering Program Mode
w key once (the display will go blank). The user then has ten seconds to start
entering the Program Mode code 7764.
☛ 7764 spells PROG on a Touch-Tone phone.
To enter Program Mode, press the
®
t key. Note that as information
If an incorrect key is entered, reenter the proper 4-digit code before pressing the
is entered from the keypad, the digits will scroll across the display from right to left.
7
77
776
7764
You are allowed a pause of up to 10 seconds in between each number while entering the code. The control panel will
then be in Program Mode with 00 F in the display. A maximum delay of 10 minutes is allowed at this point,
before beginning programming, otherwise, the control panel will return to Normal Mode. A maximum of 10 minutes
is also allowed between key strokes.
While in Programming Mode, the trouble LED will be on, the trouble relay driver will be activated, but the communicator will not be activated to report this trouble. Transmissions started before entering Program Mode will continue
during programming.
The first three locations from the left represent the memory address which can range from '00' to '243' (alpha characters are not used). The last location (digit farthest right) represents the contents of the memory address. The first
address which will be displayed is illustrated in Figure 4-1.
FIGURE 4-1: First Address
00 F
address
data
Document #15465
Rev. F1
12/04/02
P/N 15465:F1
35
Switch Functions in Program Mode
4.2
Switch Functions in Program Mode
FIGURE 4-2: Switch Functions in Program Mode
No function in Program Mode
u v w
123f q
456e r
789d s
a0bc t
These keys can be
used for address entry
and/or data entry
4.3
Select operating mode
Increment memory address
Decrement memory address
1st Press - First memory address
2nd Press - Type any address
Save data, and then display next address
Programming
4.3.1 Programming the Primary Phone Number (00 - 15)
Sixteen addresses are set aside for the primary phone number, with 'F' being the factory default. Programming is
typically done as follows:
✓ If your phone number is 484-7161, press 4
✓ The display will read 00_4
t to save the entry to memory and increment to the next address which is 01_F
✓
Press
✓
Enter the remaining numbers in their respective addresses as shown below:
Entry
4
8
4
7
Address
00 01 02 03
1
6
1
F
F
F
F
04 05 06 07 08 09 10
F
F
F
11 12 13
F
F
14
15
Valid entries are 0 - F with the numeric digits as dialed numbers and the alpha digits indicating the following:
A = * on a Touchtone phone keypad
B = # on a Touchtone phone keypad
C = look for secondary dial tone for up to two seconds (then dial anyway)
D = three second pause
E = five second pause
F = end of phone number
36
Document #15465
Rev.F1
12/04/02
P/N 15465:F1
Programming
4.3.2 Programming Primary Number Communication Format (16)
One location is needed to select the Communication Format for the primary phone number. Address 16 is used
for this purpose. The default (factory setting) for this address is 'A', which is 4+2 Standard, 1800 Hz 'Carrier',
2300 Hz 'ACK'. Formats '2' through 'D' may be entered in place of the default value, followed by the [ENTER/
STORE] key. '0' through 'F' represent the following formats:
0: Not used
1: Not used
2: 3+1 Standard 1800 Hz Carrier, 2300 Hz ACK
3: 3+1 Expanded 1800 Hz Carrier, 2300 Hz ACK
4: 3+1 Standard 1900 Hz Carrier, 1400 Hz ACK
5: 3+1 Expanded 1900 Hz Carrier, 1400 Hz ACK
6: 4+1 Standard 1800 Hz Carrier, 2300 Hz ACK
7: 4+1 Expanded 1800 Hz Carrier, 2300 Hz ACK
8: 4+1 Standard 1900 Hz Carrier, 1400 Hz ACK
9: 4+1 Expanded 1900 Hz Carrier, 1400 Hz ACK
A: 4+2 Standard 1800 Hz Carrier, 2300 Hz ACK
B: 4+2 Expanded 1800 Hz Carrier, 2300 Hz ACK
C: 4+2 Standard 1900 Hz Carrier, 1400 Hz ACK
D: 4+2 Expanded 1900 Hz Carrier, 1400 Hz ACK
E: Not used
F: Not used
Note: Consult your Central Station for proper selection or consult our factory representatives. For any format
chosen, the MS-5012 automatically programs all of the event codes. Refer to Table 4-1 and Table 4-2 .
3+1 and 4+1 Standard and Expanded, 4+2 Expanded Formats
If '2, 3, 4, 5, 6, 7, 8, 9, B or D' are entered for address 16, the following data is automatically programmed for the
Primary phone number event codes. Enter '0' for the Setting to disable the report.
TABLE 4-1: 3+1 and 4+1 Standard and Expanded, 4+2 Expanded Formats
Address
Factory
Settings
Description
68
Primary # Zone 1 Alarm Code
1
69
Primary # Zone 2 Alarm Code
1
70
Primary # Zone 3 Alarm Code
1
71
Primary # Zone 4 Alarm Code
8
72
Primary # Zone 5 Alarm Code
1
73
Primary # AC Fault Code
F
74
Primary # Zone 1 Fault Code
F
75
Primary # Zone 2 Fault Code
F
76
Primary # Zone 3 Fault Code
F
77
Primary # Zone 4 Fault Code
F
78
Primary # Zone 5 Fault Code
F
79
Primary # Earth Ground Code
F
80
Primary # Low Battery Code
F
81
Primary # No Battery Code
F
82
Primary # Telco Primary Line Fault Code
F
83
Primary # Telco Secondary Line Fault Code
F
84
Primary # Bell Fault Code
F
Document #15465
Rev. F1
12/04/02
P/N 15465:F1
37
Programming
TABLE 4-1:
3+1 and 4+1 Standard and Expanded, 4+2 Expanded Formats
Address
Factory
Settings
Description
85
Primary # Communication Trouble Primary Number
F
86
Primary # Communication Trouble Secondary Number
F
87
Primary # Annunciator Fault Code
F
88
Primary # System Off Normal Code
F
89
Primary # Zone 1 Alarm Restoral Code
E
90
Primary # Zone 2 Alarm Restoral Code
E
91
Primary # Zone 3 Alarm Restoral Code
E
92
Primary # Zone 4 Alarm Restoral Code
E
93
Primary # Zone 5 Alarm Restoral Code
E
94
Primary # AC Fault Restoral Code
E
95
Primary # Zone 1 Fault Restoral Code
E
96
Primary # Zone 2 Fault Restoral Code
E
97
Primary # Zone 3 Fault Restoral Code
E
98
Primary # Zone 4 Fault Restoral Code
E
99
Primary # Zone 5 Fault Restoral Code
E
100
Primary # Earth Ground Restoral Code
E
101
Primary # Low Battery Restoral Code
E
102
Primary # No Battery Restoral Code
E
103
Primary # Telco Primary Line Fault Restoral Code
E
104
Primary # Telco Secondary Line Fault Restoral Code
E
105
Primary # Bell Fault Restoral Code
E
106
Primary # Communication Trouble Restoral Primary Number
E
107
Primary # Communication Trouble Restoral Secondary Number
E
108
Primary # Annunciator Fault Restoral
E
109
Primary # System Return to Normal Code
E
110
Primary # 24 Hour Test Code
9
111
Primary # System Abnormal Test Report
F
4+2 Standard Format
If 'A' or 'C' are entered for address 16, the following data is automatically programmed for the Primary phone
number event codes. Enter '00' for the Setting to disable the report.
4.3.3 Programming the Primary Number Account Code (17-20)
A unique Account Code is provided by the Central Station. The Primary Number Account Code takes up four
locations at addresses 17-20. The defaults are all '0s'. Valid entries are 0-9 and A-F. The number of digits entered
must match the format selection. If programming '2, 3, 4 or 5' into address 16, enter the three digit Account Code
provided by the Central Station (location 20 is ignored). If programming '6, 7, 8, 9, A, B, C or D' into address 16,
enter the four digit Account Code.
38
Document #15465
Rev.F1
12/04/02
P/N 15465:F1
Programming
TABLE 4-2:
4+2 Standard Formats
Address
Factory
Settings
Description
68-69
Primary # Zone 1 Alarm Code
11
70-71
Primary # Zone 2 Alarm Code
12
72-73
Primary # Zone 3 Alarm Code
13
74-75
Primary # Zone 4 Alarm Code
84
76-77
Primary # Zone 5 Alarm Code
15
78-79
Primary # AC Fault Code
F6
80-81
Primary # Zone 1 Fault Code
F1
82-83
Primary # Zone 2 Fault Code
F2
84-85
Primary # Zone 3 Fault Code
F3
86-87
Primary # Zone 4 Fault Code
F4
88-89
Primary # Zone 5 Fault Code
F5
90-91
Primary # Earth Ground Code
F7
92-93
Primary # Low Battery Code
F8
94-95
Primary # No Battery Code
F9
96-97
Primary # Telco Primary Line Fault Code
FA
98-99
Primary # Telco Secondary Line Fault Code
FB
100-101
Primary # Bell Fault Code
FC
102-103
Primary # Communication Trouble Primary Number
FD
104-105
Primary # Communication Trouble Secondary Number
FE
106-107
Primary # Annunciator Fault Code
FC
108-109
Primary # System Off Normal Code
FF
110-111
Primary # Zone 1 Alarm Restoral Code
E1
112-113
Primary # Zone 2 Alarm Restoral Code
E2
114-115
Primary # Zone 3 Alarm Restoral Code
E3
116-117
Primary # Zone 4 Alarm Restoral Code
E4
118-119
Primary # Zone 5 Alarm Restoral Code
E5
120-121
Primary # AC Fault Restoral Code
E6
122-123
Primary # Zone 1 Fault Restoral Code
E1
124-125
Primary # Zone 2 Fault Restoral Code
E2
126-127
Primary # Zone 3 Fault Restoral Code
E3
128-129
Primary # Zone 4 Fault Restoral Code
E4
130-131
Primary # Zone 5 Fault Restoral Code
E5
132-133
Primary # Earth Ground Restoral Code
E7
134-135
Primary # Low Battery Restoral Code
E8
136-137
Primary # No Battery Restoral Code
E9
Document #15465
Rev. F1
12/04/02
P/N 15465:F1
39
Programming
TABLE 4-2:
4+2 Standard Formats
Address
138-139
Factory
Settings
Description
Primary # Telco Primary Line Fault Restoral Code
EA
140-141
Primary # Telco Secondary Line Fault Restoral Code
EB
142-143
Primary # Bell Fault Restoral Code
EC
144-145
Primary # Communication Trouble Restoral Primary Number
ED
146-147
Primary # Communication Trouble Restoral Secondary Number
EE
148-149
Primary # Annunciator Fault Restoral
EC
150-151
Primary # System Return to Normal Code
EF
152-153
Primary # 24 Hour Test Code
99
154-155
Primary # System Abnormal Test Report
91
4.3.4 Programming the Primary Number 24 Hour Test Time (21-24)
Use military time when entering the 24 hour 'test' time. The 24 hour test time over the primary phone number to
the Central Station, takes up four locations at addresses 21-24. The default is 00:00 (12:00 midnight). The limits
for each location are as follows (do not use A through F as entries):
Address 21 - enter 0 through 2
Address 22 - enter 0 through 9
Address 23 - enter 0 through 5
Address 24 - enter 0 through 9
4.3.5 Programming Primary Number 24/12 Hour Test Time (25)
The test message sent to the Primary phone number may be sent every 12 or 24 hours. If the message is to be sent
every 24 hours, leave the factory default entry of '0'. If 12 hour test reports are needed, enter a '1' into address 25.
4.3.6 Programming the Secondary Phone Number (26-41)
Sixteen addresses are set aside for the secondary phone number, with 'F' being the factory default. Programming
is typically done as follows:
✓ If your phone number is 484-7161, press 4
✓ The display will read 26_4
t to save the entry to memory and increment to the next address which is 27_F
✓
Press
✓
Enter the remaining numbers in their respective addresses as shown below:
Entry
4
8
4
7
Address
26 27 28 29
1
6
1
F
F
F
F
30 31 32 33 34 35 36
F
F
F
37 38 39
F
F
40
41
Valid entries are 0 - F with the numeric digits as dialed numbers and the alpha digits indicating the following:
A = * on a Touchtone phone keypad
B = # on a Touchtone phone keypad
C = look for secondary dial tone for up to two seconds (then dial anyway)
D = three second pause
E = five second pause
F = end of phone number
40
Document #15465
Rev.F1
12/04/02
P/N 15465:F1
Programming
4.3.7 Programming Secondary Number Communication Format (42)
One location is needed to select the Communication Format for the secondary phone number. Address 42 is used
for this purpose. The default (factory setting) for this address is 'A', which is 4+2 Standard, 1800 Hz 'Carrier',
2300 Hz 'ACK'. Formats '2' through 'D' may be entered in place of the default value, followed by the [ENTER/
STORE] key. '0' through 'F' represent the following formats:
0: Not used
1: Not used
2: 3+1 Standard 1800 Hz Carrier, 2300 Hz ACK
3: 3+1 Expanded 1800 Hz Carrier, 2300 Hz ACK
4: 3+1 Standard 1900 Hz Carrier, 1400 Hz ACK
5: 3+1 Expanded 1900 Hz Carrier, 1400 Hz ACK
6: 4+1 Standard 1800 Hz Carrier, 2300 Hz ACK
7: 4+1 Expanded 1800 Hz Carrier, 2300 Hz ACK
8: 4+1 Standard 1900 Hz Carrier, 1400 Hz ACK
9: 4+1 Expanded 1900 Hz Carrier, 1400 Hz ACK
A: 4+2 Standard 1800 Hz Carrier, 2300 Hz ACK
B: 4+2 Expanded 1800 Hz Carrier, 2300 Hz ACK
C: 4+2 Standard 1900 Hz Carrier, 1400 Hz ACK
D: 4+2 Expanded 1900 Hz Carrier, 1400 Hz ACK
E: Not used
F: Not used
Note: Consult your Central Station for proper selection or consult our factory representatives. For any format
chosen, the MS-5012 automatically programs all of the event codes. Refer to Table 4-3 and Table 4-4 .
3+1 and 4+1 Standard and Expanded, 4+2 Expanded Formats
If '2, 3, 4, 5, 6, 7, 8, 9, B or D' are entered for address 42, the following data is automatically programmed for the
Secondary phone number event codes. Enter '0' for the Setting to disable the report.
TABLE 4-3: 3+1 and 4+1 Standard and Expanded, 4+2 Expanded Formats
Address
Factory
Settings
Description
156
Secondary # Zone 1 Alarm Code
1
157
Secondary # Zone 2 Alarm Code
1
158
Secondary # Zone 3 Alarm Code
1
159
Secondary # Zone 4 Alarm Code
8
160
Secondary # Zone 5 Alarm Code
1
161
Secondary # AC Fault Code
F
162
Secondary # Zone 1 Fault Code
F
163
Secondary # Zone 2 Fault Code
F
164
Secondary # Zone 3 Fault Code
F
165
Secondary # Zone 4 Fault Code
F
166
Secondary # Zone 5 Fault Code
F
167
Secondary # Earth Ground Code
F
168
Secondary # Low Battery Code
F
169
Secondary # No Battery Code
F
170
Secondary # Telco Primary Line Fault Code
F
171
Secondary # Telco Secondary Line Fault Code
F
172
Secondary # Bell Fault Code
F
Document #15465
Rev. F1
12/04/02
P/N 15465:F1
41
Programming
TABLE 4-3:
3+1 and 4+1 Standard and Expanded, 4+2 Expanded Formats
Address
Factory
Settings
Description
173
Secondary # Communication Trouble Primary Number
F
174
Secondary # Communication Trouble Secondary Number
F
175
Secondary # Annunciator Fault Code
F
176
Secondary # System Off Normal Code
F
177
Secondary # Zone 1 Alarm Restoral Code
E
178
Secondary # Zone 2 Alarm Restoral Code
E
179
Secondary # Zone 3 Alarm Restoral Code
E
180
Secondary # Zone 4 Alarm Restoral Code
E
181
Secondary # Zone 5 Alarm Restoral Code
E
182
Secondary # AC Fault Restoral Code
E
183
Secondary # Zone 1 Fault Restoral Code
E
184
Secondary # Zone 2 Fault Restoral Code
E
185
Secondary # Zone 3 Fault Restoral Code
E
186
Secondary # Zone 4 Fault Restoral Code
E
187
Secondary # Zone 5 Fault Restoral Code
E
188
Secondary # Earth Ground Restoral Code
E
189
Secondary # Low Battery Restoral Code
E
190
Secondary # No Battery Restoral Code
E
191
Secondary # Telco Primary Line Fault Restoral Code
E
192
Secondary # Telco Secondary Line Fault Restoral Code
E
193
Secondary # Bell Fault Restoral Code
E
194
Secondary # Communication Trouble Restoral Primary Number
E
195
Secondary # Communication Trouble Restoral Secondary Number
E
196
Secondary # Annunciator Fault Restoral
E
197
Secondary # System Return to Normal Code
E
198
Secondary # 24 Hour Test Code
9
199
Secondary # System Abnormal Test Report
F
4+2 Standard Format
If 'A' or 'C' are entered for address 42, the following data is automatically programmed for the Secondary phone
number event codes. Enter '00' for the Setting to disable the report.
4.3.8 Programming the Secondary Number Account Code (43-46)
A unique Account Code is provided by the Central Station. The Secondary Number Account Code takes up four
locations at addresses 43-46. The defaults are all '0s'. Valid entries are (0-9 and A-F). The number of digits
entered must match the format selection. If programming '2, 3, 4 or 5' into address 42, enter the three digit
Account Code provided by the Central Station (location 46 is ignored). If programming '6, 7, 8, 9, A, B, C or D'
into address 42, enter the four digit Account Code.
42
Document #15465
Rev.F1
12/04/02
P/N 15465:F1
Programming
TABLE 4-4:
4+2 Standard Formats
Address
Factory
Settings
Description
156-157
Secondary # Zone 1 Alarm Code
11
158-159
Secondary # Zone 2 Alarm Code
12
160-161
Secondary # Zone 3 Alarm Code
13
162-163
Secondary # Zone 4 Alarm Code
84
164-165
Secondary # Zone 5 Alarm Code
15
166-167
Secondary # AC Fault Code
F6
168-169
Secondary # Zone 1 Fault Code
F1
170-171
Secondary # Zone 2 Fault Code
F2
172-173
Secondary # Zone 3 Fault Code
F3
174-175
Secondary # Zone 4 Fault Code
F4
176-177
Secondary # Zone 5 Fault Code
F5
178-179
Secondary # Earth Ground Code
F7
180-181
Secondary # Low Battery Code
F8
182-183
Secondary # No Battery Code
F9
184-185
Secondary # Telco Primary Line Fault Code
FA
186-187
Secondary # Telco Secondary Line Fault Code
FB
188-189
Secondary # Bell Fault Code
FC
190-191
Secondary # Communication Trouble Primary Number
FD
192-193
Secondary # Communication Trouble Secondary Number
FE
194-195
Secondary # Annunciator Fault Code
FC
196-197
Secondary # System Off Normal Code
FF
198-199
Secondary # Zone 1 Alarm Restoral Code
E1
200-201
Secondary # Zone 2 Alarm Restoral Code
E2
202-203
Secondary # Zone 3 Alarm Restoral Code
E3
204-205
Secondary # Zone 4 Alarm Restoral Code
E4
206-207
Secondary # Zone 5 Alarm Restoral Code
E5
208-209
Secondary # AC Fault Restoral Code
E6
210-211
Secondary # Zone 1 Fault Restoral Code
E1
212-213
Secondary # Zone 2 Fault Restoral Code
E2
214-215
Secondary # Zone 3 Fault Restoral Code
E3
216-217
Secondary # Zone 4 Fault Restoral Code
E4
218-219
Secondary # Zone 5 Fault Restoral Code
E5
220-221
Secondary # Earth Ground Restoral Code
E7
222-223
Secondary # Low Battery Restoral Code
E8
224-225
Secondary # No Battery Restoral Code
E9
Document #15465
Rev. F1
12/04/02
P/N 15465:F1
43
Programming
TABLE 4-4:
4+2 Standard Formats
Address
226-227
Factory
Settings
Description
Secondary # Telco Primary Line Fault Restoral Code
EA
228-229
Secondary # Telco Secondary Line Fault Restoral Code
EB
230-231
Secondary # Bell Fault Restoral Code
EC
232-233
Secondary # Communication Trouble Restoral Primary Number
ED
234-235
Secondary # Communication Trouble Restoral Secondary Number
EE
236-237
Secondary # Annunciator Fault Restoral
EC
238-239
Secondary # System Return to Normal Code
EF
240-241
Secondary # 24 Hour Test Code
99
242-243
Secondary # System Abnormal Test Report
91
4.3.9 Programming the Secondary Number 24 Hour Test Time (47-50)
Use military time when entering the 24 hour 'test' time. The 24 hour test time over the secondary phone number to
the Central Station, takes up four locations at addresses 47-50. The default is 00:00 (12:00 midnight). The limits
for each location are as follows (do not use A through F as entries):
Address 47 - enter 0 through 2
Address 48 - enter 0 through 9
Address 49 - enter 0 through 5
Address 50 - enter 0 through 9
4.3.10 Programming Secondary Number 24/12 Hour Test Time (51)
The test message sent to the Secondary phone number may be sent every 12 or 24 hours. If the message is to be
sent every 24 hours, leave the factory default entry of '0'. If 12 hour test reports are needed, enter a '1' into address
51.
4.3.11 Programming Zone 3 Functionality (52)
The following entries may be selected:
• 0 = nonsilenceable waterflow zone (program optional delay in addresses 53-54)
• 1 = normally open contact device zone or silenceable waterflow zone
• 2 = 2-wire smoke detector zone (Style B only)
The factory default setting is '0' for nonsilenceable waterflow zone.
4.3.12 Programming Waterflow Retard Timer (53-54)
A maximum delay of 89 seconds can be programmed into addresses 53-54. This will delay activation due to a
'waterflow alarm' if zone 3 is programmed as a nonsilenceable waterflow zone. The panel automatically provides
a one second delay. The factory default setting for addresses 53-54 is '00' for no additional delay. Valid entries for
address 53 are 0 through 8 and for address 54, 0 through 9. Addresses 53 and 54 should be changed from the
default setting only if address 52 is programmed '0' for nonsilenceable waterflow zone and a delay is required. Be
careful to consider any built-in waterflow device delays.
44
Document #15465
Rev.F1
12/04/02
P/N 15465:F1
Programming
4.3.13 Programming AC Loss Reporting Delay (55)
Enter a digit of '1 through 6' corresponding to the number of hours to be delayed in reporting loss of AC power.
The factory default setting is 6 hour delay. Valid entries are as follows:
• 0 = 6 hour delay
• 1 = 7 hour delay
• 2 = 8 hour delay
• 3 = 9 hour delay
• 4 = 10 hour delay
• 5 = 11 hour delay
• 6 = 12 hour delay
4.3.14 Programming Slave Communicator/Fire Panel Selection (56)
Leaving address 56 at the factory default setting of '0' means the MS-5012 is operating as a fire panel only. Selecting '1' will program the panel to operate as a slave communicator only. Refer to “Slave Communicator Configuration” on page 51. Selecting '2' will program the panel to operate as a fire panel/communicator.
4.3.15 Secondary Phone Number Reporting (57)
The factory default setting is '0' which means that reports will be transmitted to the secondary phone number only
if calls to the primary number are unsuccessful. Programming a '1' causes all reports to be transmitted to the secondary phone number.
4.3.16 Alarm Verification on Detector Zones 2 and 3 (58)
Factory default setting for address 58 is '0' which means no alarm verification. Entering a '1' enables verification
for zone 2 and zone 3. Consult the local Authority Having Jurisdiction (AHJ) prior to altering this address.
Alarm verification works only on zones programmed as 2-wire smoke detector zones. After detecting an alarm,
the panel removes power from all zones for six seconds, resetting all 2-wire smoke detectors. Power is reapplied
and a 12 second retard period allows detectors to stabilize. During the retard/reset period of 18 seconds, subsequent alarms by the same initiating zone are ignored. An alarm detected on any other 2-wire detector zone during
the retard period will cause immediate verified alarms. A subsequent alarm on the initiating zone occurring
within the confirmation time will cause a verified alarm.
Note: Mixing devices on zones designated as 2-wire smoke zones is not recommended.
During the alarm verification period, access to other modes of operation is prevented.
4.3.17 Silence Inhibit (59)
The factory default setting of '0' disables the silence inhibit feature. A '1' will enable the silence inhibit feature
which will prevent the silencing of the Notification Appliance Circuit and piezo sounder for 1 minute following
activation. Consult the local Authority Having Jurisdiction (AHJ) prior to altering this address.
4.3.18 Auto Silence (60)
The factory default setting of '0' disables the Auto Silence feature. A '1' will enable the Auto Silence feature
which will cause the panel to automatically silence the Notification Appliance Circuit after 10 minutes of activation. Consult the local Authority Having Jurisdiction (AHJ) prior to altering this address.
4.3.19 Trouble Reminder (61)
The factory default setting of '0' disables the Trouble Reminder feature. Selecting '1' will enable the feature which
causes a reminding 'beep' every 15 seconds during an alarm and every two minutes during a trouble condition
(after the silence switch has been pressed). The 'beeps' from the onboard piezo sounder will continue until the
alarm or fault is cleared. Consult the local Authority Having Jurisdiction (AHJ) prior to altering this address.
Document #15465
Rev. F1
12/04/02
P/N 15465:F1
45
Programming
4.3.20 Bell Disable (62)
The factory default setting of '0' enables the Notification Appliance Circuit. Entering a '1' in address 62 will cause
the Notification Appliance Circuit to be disabled during an alarm. In addition, the Trouble LED will turn on while
the NAC is disabled and a bell fault message will be sent to the Central Station(s). Consult the local Authority
Having Jurisdiction (AHJ) prior to altering this address.
4.3.21 Annunciator Present (63)
The factory default setting of '0' indicates that no annunciator is present on the system. Entering a '1' in address 63
indicates an annunciator is connected to the system.
4.3.22 Programming Zone 4 Functionality (64)
The factory default setting for address 64 is '0' for supervisory zone (accepts normally open supervisory devices).
Changing address 64 to '1' allows Zone 4 to accept any normally open contact device. Note that when address 64
is changed to '1', the messages transmitted to the Central Station(s) must be changed to reflect the new setting. If
using 3+1, 4+1 or 4+2 Expanded Formats, address 71 must be changed to '1' and address 159 must be changed to
'1'. If using 4+2 Standard Formats, address 74 must be changed to '1' and address 162 must be changed to '1'.
4.3.23 Address (65) - Not used
4.3.24 Touchtone/Rotary Select (66)
The factory default setting for address 66 is '0' which enables Touchtone dialing over both phone lines. Entering a
'1' will enable rotary dialing.
4.3.25 Make/Break Ratio (67)
An entry is required in address 67 only if address 66 has been programmed with a '1' for rotary dialing. The factory default setting for address 67 is '0' for a Make/Break Ratio of 67/33. Enter a '1' to change the ratio to 62/38.
4.3.26 Programming Event Codes (68-243)
Table 4-1 through Table 4-4 list messages of 'event codes' that are sent to the Central Station. The selections
made for the Primary Number Communication Format (address 16) and the Secondary Number Communication
Format (address 42) automatically program addresses 68-243 with factory selections.
Any of the event codes may be changed. Consult your Central Station prior to altering the event codes. Entering
an event code of '0' will cause the communicator to NOT transmit the message. For the 3+1, 4+1 Formats or the
4+2 Expanded Format, enter a single zero '0'. For the 4+2 Standard Format, enter two zeroes '00'
Be certain to disable the reports in pairs. The pair should include both the activation of the event and the restoral
of the event. For example, to disable Zone 1 Fault Code from being transmitted, enter a '0' or '00' for the Zone 1
Fault Code plus a '0' or '00' for the Zone 1 Restoral Code. The exception to this is for the 24 Hour Test Reports
and the Abnormal Test Reports.
4.3.27 End Programming
Exit Programming Mode by pressing the
w key, followed by the 4-digit code corresponding to an alternate
t key. During Program Mode, if no key is pressed within 10 minutes, the
mode of operation, then press the
panel will revert to Normal Mode.
4.3.28 Programming the Real-Time Clock
Entering an address greater than 243 will cause a display of the current time. On initial power-up, the clock will
start running from the factory setting of 00:00 (military time). The far left digit will be flashing, indicating that
this will be the first digit to be programmed. Simply enter the correct digits of the current time, followed by
t.
46
Document #15465
Rev.F1
12/04/02
P/N 15465:F1
Servicing
Servicing
CHAPTER 5
5.1
Walktest Mode
The MS-5012 provides the capability to perform a one-man walktest of the system without triggering the communicator or the alarm output relay driver. Walktest allows for testing of the five zones (initiating circuits). The first initiating device activated on a zone will cause the Notification Appliance (bell) Circuit to turn on for four seconds.
Subsequent device activations on the same zone will cause the NAC to turn on for one second. Any smoke detectors
that are activated will be reset. Zonal faults (open circuits) will cause the NAC to remain steadily on. Prior to entering Walktest Mode, check to be certain that all system faults have been cleared. Note that the trouble relay will be
activated while the control panel is in Walktest Mode. Placing the control panel in Walktest Mode will only be possible if the system has no active alarms.
w
key followed by the 4-digit code
Pressing the
place the control panel into Walktest Mode.
☛
9255
9255 and then pressing the t key will
spells WALK on a Touch-Tone® phone.
Once in Walktest Mode, the MS-5012 will immediately:
✓
✓
✓
✓
✓
✓
✓
Turn on the trouble LED
Activate/energize the trouble relay driver
Turn on the Notification Appliance Circuit output for four seconds for the first alarm event on a zone.
Subsequent alarms will sound for one second. Troubles cause the NAC to remain on until cleared
Disable the alarm relay
Display all alarm conditions as they occur
Display ground faults as they occur
Continue to communicate any events not yet acknowledged at the Central Station
During Walktest Mode, zonal activity is displayed in real-time as it occurs. At the end of Walktesting the system, the
display will show the last event that occurred. To view all events stored during Walktest, use the
q, r
and
s keys. The r key moves the Walktest list to show older (previous) events. The q key moves the Walktest list to show newer (more recent) events. Pressing the s key at any time will cause the display of the first
event stored upon initial entry into Walktest Mode. While in Walktest Mode, the control panel will store up to 128
events in the Walktest File for later recall and display.
To return the MS-5012 to Normal Mode, press the
w key, the code numbers 6676
and the
t key. Any delay between key entries greater than 10 seconds causes the control panel to remain in Walktest
Mode.
The control panel will automatically revert back to Normal Mode if no system activity has occurred for 60 minutes.
This would include pressing any keys or activity on any zone. Exiting Walktest Mode erases the Walktest File from
memory.
Document #15465
Rev. F1
12/04/02
P/N 15465:F1
47
History Mode
5.2
History Mode
All Normal Mode events are stored in a History File list for future recall. Recall is possible via the 4-character display. The History File list is a first-in/first-out (FIFO). In this manner, only the most recent events may be called up
form memory. Old events will be overwritten, i.e. pushed out of FIFO.
The number of stored events is 16. The History File is kept in EEPROM memory. Complete power loss will not
erase the list.
w
4478
t
Pressing the
key followed by the digits
and the
key places the control panel into
History Mode. This will not occur if there are any active alarm conditions present. The event displayed, is the most
recent event.
☛
4478
spells HIST on a Touch-Tone® phone.
Once in History Mode, the control panel will:
✓
✓
✓
✓
✓
✓
✓
Turn on the trouble LED
Energize/activate the trouble relay driver
Disable the Notification Appliance Circuit output
Disable the alarm relay driver
Display all events as they occurred since the last time the History File list was cleared. The most recent
event will be displayed first
Ignore all other keys other than those mentioned in this section
Continue to communicate any events not yet acknowledged at the Central Station
r
q
The
key moves the History File to show older (previous) events. The
key moves the History File to
show newer (more recent) events. Shown below is a list of messages as they will appear on the display:
DISPLAY
A 1
A 2
A 3
A 4
A 5
SuP4
AC
F 1
F 2
F 3
F 4
F 5
EVENT
DISPLAY
Zone 1 Alarm
Zone 2 Alarm
Zone 3 Alarm
Zone 4 Alarm
Zone 5 Alarm
Supervisory Alarm
AC Loss
Zone 1 Fault
Zone 2 Fault
Zone 3 Fault
Zone 4 Fault
Zone 5 Fault
bELL
F E
F A
no 1
no 2
rES
PH 1
PH 2
no b
Lo b
SILE
EVENT
Bell Fault (open or short)
Earth Fault
Annunciator Fault
Primary Phone Line Fault
Secondary Phone Line Fault
Reset Switch Pressed
Primary Number Communication Fault
Secondary Number Communication Fault
No Battery
Low Battery
Silence Switch Pressed
To erase the list, press the Silence Key twice before exiting the History Mode. A lack of keyboard activity for a
period of 10 minutes will cause the control panel to return to Normal Mode.
48
Document #15465
Rev.F1
12/04/02
P/N 15465:F1
Troubleshoot Mode
5.3
Troubleshoot Mode
In this mode, the voltage of the input zones, AC voltage and battery voltage will be displayed on the 4-character display. The internal voltmeter reads the voltage present at:
• zone inputs
• AC power input
• battery terminal leads
A lack of keyboard activity for a period of 20 minutes will cause the control panel to return to Normal Mode.
w key followed by the digits 8768 and the t key.
8768 spells TROU on a Touch-Tone phone.
To enter Troubleshoot Mode, press the
☛
®
Once in Troubleshoot Mode, the MS-5012 will:
✓
✓
✓
✓
✓
Turn on the trouble LED
Energize/activate the trouble relay driver
Disable the Notification Appliance Circuit output
Disable the alarm relay driver
Continue to communicate any events not yet acknowledged at the Central Station
a and then t displays the AC input voltage. Pressing b and then t will display the Battery
Voltage. Pressing 1 through 5 followed by t displays the zone voltage of the selected zone. The q,
r and s keys do not function in this mode.
Pressing
Listed below are the 'nominal threshold voltages' for each zone:
Zone #
1
2
Normal w/E.O.L.
5.15V
11.75V
3
4
5
11.75V
5.15V
5.15V
Shorted Ckt.
0.15V
8.7V
Open Ckt.
12.V
12.9V
8.7V
.15V
.15V
12.9V
12.9V
12.9V
Readings will vary proportionately depending upon system load and AC line voltage. Listed below is the AC line
voltage range. The AC ON indicator will turn off when the AC line voltage drops below the Low Line 'threshold',
and the trouble LED will turn on.
AC Line Voltage
Low Line
102VAC
Normal
115VAC
High Line
132VAC
Below is shown the critical battery threshold conditions:
Battery Voltage
Normal
13.7V
Low Battery
10.2V
Note: make measurements after allowing 48 hours to charge a depleted battery. If battery does not show normal
reading, replace it.
Document #15465
Rev. F1
12/04/02
P/N 15465:F1
49
Lamp Test
c
t
Pressing
and then
causes seizure of the Primary line and the red LED signifying Primary line active turns
on. After a delay of three seconds, the control panel goes off hook to acquire a dial tone. Connecting a telephone
handset across the telephone transformer, as illustrated in Figure 5-1, allows number dialing. Pressing
then
c and
t a second time hangs up the call. Repeated entries of c places the phone on and off hook.
FIGURE 5-1: Handset Connection
Ring (red)
Tip (green)
Carefully Connect
Handset Here
T1
5.4
Lamp Test
w
5267
t
To perform a Lamp Test, press
then
followed by
. This will test all system LEDs
except the Primary Active LED and Secondary Active LED. The LEDs will stay on for five seconds, then the control
panel will return to Normal Mode.
☛
50
5267
spells LAMP on a Touch-Tone® phone.
Document #15465
Rev.F1
12/04/02
P/N 15465:F1
Slave Communicator Configuration
CHAPTER 6
Slave Communicator Configuration
The MS-5012 may be used as a slave communicator to a host or 'Master' fire alarm control panel (FACP). All wiring
between the Master and the MS-5012 is supervised. 2.2K ohm End-of-Line resistors must be connected as illustrated
in the typical wiring diagram in illustrated in this chapter.
In slave configuration, the five zones become five channels that may be triggered by the relay outputs of any host
FACP:
•
•
•
•
•
Zone1/Channel 1 is used for general alarm
Zone 2/Channel 2 is used for general trouble
Zone 3/Channel 3 may be programmed to match the FACP relay function
Zone 4/Channel 4 is used for supervisory
Zone 5/Channel 5 may be programmed to match the FACP relay function
The factory settings for Zone 2/Channel 2 activation and restoral are altered as follows:
✓
✓
If '2, 3, 4, 5, 6, 7, 8, 9, B or D' is entered for address 16 or 42, the report code for Zone 2 Alarm Code
(addresses 69 and 157) = F and Zone 2 Restoral Code (addresses 90 and 178) = E
If 'A or C' is entered for address 16 or 42, the report code for Zone 2 Alarm Code (addresses 70-71 and
158-159) = FF and Zone 2 restoral code (addresses 112-113 and 200-201) = EF
It is important to note that activation of Zone 2 is Slave Communicator Configuration will cause the yellow trouble
LED to flash and the trouble sounder to pulse, however, the red alarm LED will not activate and the notification
appliances will not sound.
Location 56 must be programmed to a '1' to enable the control panel as a slave communicator. When programming
the MS-5012 as a slave communicator, first program the communication formats (addresses 16 and 42), followed by
the slave communicator selection at address 56. This sequence allows the MS-5012 to automatically program the
proper report codes. Do not program location 56 first and then alter the format selections at addresses 16 and 42.
If any of the report codes are to be altered from the factory defaults, follow the steps above and exit Program Mode.
Next, reenter Program Mode and alter any event codes.
After programming is complete, the
the
t, q or r keys may be used to view programmed entries. Do not use
t key to view location 56, since it will reprogram the factory default event codes.
Be certain to connect the MS-5012 primary AC power to the same branch circuit as the host FACP.
Battery Connection
The MS-5012 contains a battery disconnect relay which has multiple purposes. The primary purpose is to disconnect
the battery when the battery voltage is less the 7.0 volts during AC loss condition. This prevents the MS-5012 from
transmitting erroneous data to the Central Station under unsafe operating power. Also, with AC power applied, the
disconnect relay allows for battery voltage measurements in the Normal and Troubleshoot Modes.
Document #15465
Rev. F1
12/04/02
P/N 15465:F1
51
Slave Communicator Configuration
Due to the presence of the disconnect relay, it is not possible to initially (out of the box) power up an MS-5012 from
the battery. AC power must be applied for six seconds. Once AC power is applied, do not connect a low capacity
battery (less than 7.0 volts) to the system. When replacing a bad battery, turn off AC power before connecting the
new battery.
Inputs are supervised
and power-limited
Relays in the Master FACP activate various input circuits on the MS-5012. Messages (event codes) programmed for
a particular input circuit (channel) will be transmitted to the Central Station upon relay activation.
52
Document #15465
Rev.F1
12/04/02
P/N 15465:F1
Power Calculations
Power Calculations
Appendix A
Use the Total Standby and Alarm Load Currents calculated in Table A-1 and Table A-2 for the following battery
calculation.
TABLE A-1:
Total Ampere Hours
Standby Load Current
(Amps)
[
]
X
Required Standby Time in Hours
(24 or 60 Hours)
[
]
=
__________
Alarm Load Current
(Amps)
[
]
X
Required Alarm Time in Hours
(i.e. 5 min. = 0.084 hours)
[
]
=
__________
Add Standby and Alarm Load for Required Ampere Hour Battery
=
__________
Multiply by the Derating Factor of 1.2
x 1.2
__________
Total Ampere Hours (AH) Required
=
__________
Select a battery with a greater Ampere Hour rating.
Notes:
1.
2.
NFPA 72 National Fire Alarm Code for Central Station, Local and Proprietary Protected Premises systems
require 24 hours of standby.
NFPA 72 National Fire Alarm Code for Auxiliary and Remote Station systems require 60 hours of standby.
Document #15465
Rev. F1
12/04/02
P/N 15465:F1
53
Power Calculations
The MS-5012 provides filtered power for operating the fire alarm control panel, external devices and the standby battery. The power for operating external devices is limited. Use Table A-1 (standby or nonalarm) and Table A-2
(alarm) to determine if external loading is within the capabilities of the power supply.
TABLE A-2:
Regulated Load in Standby
Current
(Amps)
Total Current
(Amps)
Device Type
# of Devices
Main Circuit Board
1
X
0.074
=
ADM-12
(1 maximum)
X
0.012
=
RZA-5F
(1 maximum)
X
0.012
=
2-wire Detector Heads1
[
]
X
[
]
=
4-wire Detector Heads
[
]
X
[
]
=
Power Supervision Relays2
[
]
X
0.025
=
0.074
Auxiliary Outputs:
TB3-4 Alarm
(1 maximum)
X
0
=
TB3-5 Trouble
(1 maximum)
X
0.0403
=
TB3-6 Supervisory
(1 maximum)
X
0
=
TB3-7 Comm. Fail
(1 maximum)
X
0
=
Additional Current Draw
from TB3 (nonalarm)
=
Sum Column for Standby Load
=
Amps
1. Refer to Device Compatibility Document for 2-wire smoke detector standby current.
2. Use compatible listed power supervision relay only.
3. Current draw only if End-of-Line relay is installed between TB3-3 and TB3-5. Current shown is maximum available from TB3 Terminal 5
54
Document #15465
Rev.F1
12/04/02
P/N 15465:F1
Power Calculations
TABLE A-3:
Regulated Load in Alarm
Device Type
# of Devices
Main Circuit Board
1
Current
(Amps)
Total Current
(Amps)
X
0.170
=
=
ADM-12
(1 maximum)
X
0.0321
RZA-5F
(1 maximum)
X
0.0301
=
4-wire Detector Heads
[
]
X
[
]
=
Power Supervision Relays2
[
]
X
0.025
=
0.170
Auxiliary Outputs:
TB3-4 Alarm
(1 maximum)
X
0.040
=
TB3-5 Trouble
(1 maximum)
X
0.040
=
TB3-6 Supervisory
(1 maximum)
X
0
=
TB3-7 Comm. Fail
(1 maximum)
X
0
=
Notification Appliances
[
]
X
[
]
=
Notification Appliances
[
]
X
[
]
=
Additional Current Draw
from TB3 (nonalarm)
=
Sum Column for Alarm Load
=
Amps
1. Current shown is with all LEDs illuminated.
2. Use compatible listed power supervision relay only.
Document #15465
Rev. F1
12/04/02
P/N 15465:F1
55
Programming Reference Sheets
Programming Reference Sheets
Appendix B
B.1
Blank System Programming Reference Sheets
To enter Programming Mode, press the Mode key followed by the keys 7764 and then the [ENTER/STORE] key.
❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏
00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
Addresses 00 to 15 store the Primary Phone Number. Enter 'F' to represent the end of the number.
❏ Primary Communication Format: Enter '0 - F'.
❏ ❏ ❏ ❏ Primary Account Code: Valid entries are '0 - F'.
❏ ❏ ❏ ❏ Primary 24-Hour Test Time. Enter military time (i.e. 1400 for 2:00 PM).
❏ Primary 24/12 Hour Test Time. Enter '1' for 12 hour; '0' for 24 hour.
❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏
16
17
18
19
20
21
22
23
24
27
28
29
25
26
30
31
32
33
34
35
36
37
38
39
40
41
Addresses 26 to 41 store the Secondary Phone Number. Enter 'F' to represent the end of the number.
❏ Secondary Communication Format: Enter '0 - F'.
❏ ❏ ❏ ❏ Secondary Account Code: Valid entries are '0 - F'.
❏ ❏ ❏ ❏ Secondary 24-Hour Test Time. Enter military time (i.e. 1400 for 2:00 PM).
❏ Secondary 24/12 Hour Test Time. Enter '1' for 12 hour; '0' for 24 hour.
❏ Zone 3 Function Select ('0' = waterflow,' = normally open contact devices, '2' = 2-wire smoke detectors)
❏ ❏ Waterflow Reporting Delays. Valid keys for field 53 are '0 - 8' and for field 54 are '0 - 9'.
❏ AC Loss. Enter number of hours to delay reporting of AC loss. ('0' = 6 hours, '1' = 7 hours, '2' = 8 hours, '3'
42
43
44
45
46
47
48
4
50
51
52
53
54
55
= 9 hours, '4' = 10 hours, '5' = 11 hours, '6' = 12 hours).
❏
56
Slave Communicator Selection. '0' for panel only; '1' for slave operation; '2' for fire control/communicator
operation.
❏
❏
❏
❏
57
Secondary Phone Number. Enter '0' for secondary as a backup; '1' to transmit to secondary always.
58
Alarm Verify. Enter '0' for no verification; '1' for verification.
59
Silence Inhibit. Enter '0' to disable silence inhibit; '1' to enable silence inhibit.
60
Auto Silence. Enter '0' to disable auto silence; '1' to automatically silence notification appliances 10 minutes
after activation.
❏
61
Trouble Reminder. Enter '0' to disable trouble reminder; '1' to enable trouble reminder 'beep' (sound every 15
seconds for alarm and every 2 minutes for trouble).
❏
❏
❏
❏
❏
❏
56
62
Bell Disable. Enter '0' to enable the panel Notification Appliance Circuit (NAC); '1' to disable the NAC.
63
Annunciator Present. Enter '0' if no annunciator is wired to system; '1' if annunciator is wired to system.
64
Zone 4 Function Select. Enter '0' for supervisory service; '1' for normally open contact devices.
65
Not used.
66
Touchtone/Rotary Select. Enter '0' for touchtone dialing; '1' for rotary dialing.
67
Make/Break Ratio. Enter '0' for 67/33 make/break ratio; '1' for 62/38 ratio.
Document #15465
Rev.F1
12/04/02
P/N 15465:F1
Programming Reference Sheets
B.2
Blank Format Programming Reference Sheet
❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏❏ ❏ ❏ ❏ ❏
68
69
70
71
72
73
74
75
76
77
78
79
❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏❏ ❏ ❏ ❏ ❏
81
82
83
84
85
86
87
88
89
90
91
92
❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏
94
95
96
97
98
99
100
101
102
103
104
105
❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏❏ ❏ ❏ ❏ ❏
107
108
109
110
111
112
113
114
115
116
117
118
❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏❏ ❏ ❏ ❏ ❏
120
121
122
123
124
125
126
127
128
129
130
131
❏ ❏ ❏❏❏ ❏ ❏ ❏❏ ❏ ❏ ❏ ❏
133
134
135
136
137
138
139
140
141
142
143
144
❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏❏ ❏ ❏ ❏ ❏
146
147
148
149
150
151
152
153
154
155
156
157
❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏❏ ❏ ❏ ❏ ❏
159
160
161
162
163
164
165
166
167
168
169
170
❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏❏ ❏ ❏ ❏ ❏
172
173
174
175
176
177
178
179
180
181
182
183
❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏❏ ❏ ❏ ❏ ❏
185
186
187
188
189
190
191
192
193
194
195
196
❏ ❏ ❏❏❏ ❏ ❏ ❏❏ ❏ ❏ ❏ ❏
198
199
200
201
202
203
204
205
206
207
208
209
❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏❏ ❏ ❏ ❏ ❏
211
212
213
214
215
216
217
218
219
220
221
222
❏ ❏ ❏ ❏ ❏ ❏ ❏ ❏❏ ❏ ❏ ❏ ❏
224
225
226
227
228
229
❏ ❏ ❏ ❏ ❏ ❏ ❏
237
238
239
240
241
242
230
231
232
233
234
235
80
93
106
119
132
145
158
171
184
197
210
223
236
243
Document #15465
Rev. F1
12/04/02
P/N 15465:F1
57
Programming Reference Sheets
B.3
Programming Reference Sheet Factory Default Settings
To enter Programming Mode, press the Mode key followed by the keys 7764 and then the [ENTER/STORE] key.
F ❏
F ❏
F ❏
F ❏
F ❏
F ❏
F ❏
F ❏
F ❏
F ❏
F ❏
F ❏
F ❏
F ❏
F ❏
F
❏
00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
Addresses 00 to 15 store the Primary Phone Number. Enter 'F' to represent the end of the number.
A Primary Communication Format: A = 4+2 Standard, 1800/2300.
❏
0 ❏
0 ❏
0 ❏
0 Primary Account Code.
❏
0 ❏
0 ❏
0 ❏
0 Primary 24-Hour Test Time. 0000 = 12:00 midnight.
❏
0 Primary 24/12 Hour Test Time. '0' for 24 hour.
❏
F ❏
F ❏
F ❏
F ❏
F ❏
F ❏
F ❏
F ❏
F ❏
F ❏
F ❏
F ❏
F ❏
F ❏
F ❏
F
❏
16
17
18
19
20
21
22
23
24
27
28
29
25
26
30
31
32
33
34
35
36
37
38
39
40
Addresses 26 to 41 store the Secondary Phone Number. Enter 'F' to represent the end of the number.
A Secondary Communication Format: A = 4+2 Standard, 1800/2300.
❏
0 ❏
0 ❏
0 ❏
0 Secondary Account Code.
❏
0 ❏
0 ❏
0 ❏
0 Secondary 24-Hour Test Time. 0000 = 12:00 midnight.
❏
0 Secondary 24/12 Hour Test Time. '0' for 24 hour.
❏
0 Zone 3 Function Select: '0' = waterflow.
❏
0 ❏
0 Waterflow Reporting Delays. 00 = No delays.
❏
0 AC Loss. '0' = 6 hours.
❏
42
43
44
45
46
47
48
4
50
51
52
53
54
55
.
0
❏
56
0
❏
0
❏
0
❏
0
❏
57
Secondary Phone Number. '0' for secondary as a backup.
58
Alarm Verify. '0' for no verification.
59
Silence Inhibit. '0' to disable silence inhibit.
60
Auto Silence. '0' to disable auto silence.
0
❏
61
0
❏
0
❏
0
❏
0
❏
0
❏
0
❏
58
Slave Communicator Selection. '0' for panel only.
Trouble Reminder. '0' to disable trouble reminder.
62
Bell Disable. '0' to enable the panel Notification Appliance Circuit (NAC).
63
Annunciator Present. '0' for no annunciator wired to system.
64
Zone 4 Function Select. '0' for supervisory service.
65
Not used.
66
Touchtone/Rotary Select. '0' for touchtone dialing.
67
Make/Break Ratio. '0' for 67/33 make/break ratio.
Document #15465
Rev.F1
12/04/02
P/N 15465:F1
41
Programming Reference Sheets
B.4
Format Programming Reference Sheet Factory Default Sheet
1 ❏
1 ❏
1 ❏
2 ❏
1 ❏
3 ❏
8 ❏
4 ❏
1 ❏
5 ❏
F ❏
6 ❏
F
❏
68
69
70
71
72
73
74
75
76
77
78
79
1 ❏
F ❏
2 ❏
F ❏
3 ❏
F ❏
4 ❏
F ❏
5 ❏
F ❏
7 ❏
F ❏
8
❏
81
82
83
84
85
86
87
88
89
90
91
92
F ❏
9 ❏
F ❏
A ❏
F ❏
B ❏
F ❏
C ❏
F ❏
D ❏
F ❏
E ❏
F
❏
94
95
96
97
98
99
100
101
102
103
104
105
C ❏
F ❏
F ❏
E ❏
1 ❏
E ❏
2 ❏
E ❏
3 ❏
E ❏
4 ❏
E ❏
5
❏
107
108
109
110
111
112
113
114
115
116
117
118
E 6
E ❏
1 ❏
E ❏
2 ❏
E ❏
3 ❏
E ❏
4 ❏
E ❏
5 ❏
E
❏
❏ ❏
120
121
122
123
124
125
126
127
128
129
130
131
7 ❏
E
8
E ❏
9 ❏
E ❏
A ❏
E ❏
B ❏
E ❏
C ❏
E ❏
D
❏
❏❏
133
134
135
136
137
138
139
140
141
142
143
144
E ❏
E ❏
E ❏
C ❏
E ❏
F ❏
9 ❏
9 ❏
9 ❏
1 ❏
1 ❏
1 ❏
1
❏
146
147
148
149
150
151
152
153
154
155
156
157
2 ❏
1 ❏
3 ❏
8 ❏
4 ❏
1 ❏
5 ❏
F ❏
6 ❏
F ❏
1 ❏
F ❏
2
❏
159
160
161
162
163
164
165
166
167
168
169
170
F ❏
3 ❏
F ❏
4 ❏
F ❏
5 ❏
F ❏
7 ❏
F ❏
8 ❏
F ❏
9 ❏
F
❏
172
173
174
175
176
177
178
179
180
181
182
183
A ❏
F ❏
B ❏
F ❏
C ❏
F ❏
D ❏
F ❏
E ❏
F ❏
C ❏
F ❏
F
❏
185
186
187
188
189
190
191
192
193
194
195
196
E ❏
1
E
2 ❏
E ❏
3 ❏
E ❏
4 ❏
E ❏
5 ❏
E ❏
6 ❏
E
❏
❏❏
198
199
200
201
202
203
204
205
206
207
208
209
1 ❏
E ❏
2 ❏
E ❏
3 ❏
E ❏
4 ❏
E ❏
5 ❏
E ❏
7 ❏
E ❏
8
❏
211
212
213
214
215
216
217
218
219
220
221
222
E ❏
9 ❏
E ❏
A ❏
E ❏
B ❏
E ❏
C ❏
E ❏
D ❏
E ❏
E ❏
E
❏
224
225
226
227
228
229
C ❏
E ❏
F ❏
9 ❏
9 ❏
9 ❏
1
❏
237
238
239
240
241
242
230
231
232
233
234
235
80
93
106
119
132
145
158
171
184
197
210
223
236
243
Document #15465
Rev. F1
12/04/02
P/N 15465:F1
59
Notes
60
Document #15465
Rev.F1
12/04/02
P/N 15465:F1
Index
I
IDC 13, 27
see also Initiating Device Circuit 11
inhibit
silence 45
Initiating Device Circuit 13
input circuits 11, 27
installation 26
Numerics
1st Event 17
A
AC
terminal block option 32
AC loss
reporting delay 45
AC power 13, 18
LED 12
account code 38, 42
ADM-12 33, 34
see also annunciator driver module 12
alarm 18
LED 12
relay driver 14
response 19
restoral 19
verification 45
annunciator 12, 33
annunciator driver module 12, 33
auto silence 45
K
kiss-off 18
kissoff
LED 12
L
lamp test 50
Lamp Test Mode 16
LED 17, 18
see also display 12
line seizure 12
M
mounting
cabinet 26
B
backbox
size 10
battery 13, 31
calculations 54
charging capacity 13
connection 51
N
NAC 14, 28
disable 46
fault 15
see also Notification Appliance Circuit 11
nonresettable power 11, 14
Normal Mode 16
normal mode 18
Notification Appliance Circuit 11, 14, 28
C
cabinet
dimensions 26
mounting 26
circuits 11
clock
programming 46
communication format 37, 41
communication formats 12
communicator 12, 15, 21, 30
communicator failure
relay driver 14
O
off normal reporting 21
off/on hook 12
operation 16
modes 16
output circuits 11, 28
outputs
auxiliary 14
D
description 10
dial tone 12
digital communicator 12, 15, 21, 30
dimensions
cabinet 26
disable
NAC 46
display 12, 17
P
panel selection 45
panel switches 11
phone line active
LED 12
piezo sounder 15
Power
AC 31
power
AC 13
battery 31
calculations 53
nonresettable 11, 14
resettable 11, 14
power-limited
wiring 29
priorities
transmit 24
priority events 19
Program Mode 16
program mode 35
programming 35
exit 46
sheets 56
E
event code
programming 46
F
features 10
format
addresses 22
communication 12
H
History Mode 16
history mode 48
Document #15465
Rev.F1
12/04/02
P/N 15465:F1
61
R
receivers
UL listed 25
relay 14
relays 11
remote annunciator 12, 13, 33
reporting
off normal 21
reset 16
resettable power 11, 14
RZA-5F 13, 33, 34
see also remote annunciator 12
S
servicing 47
silence 16, 18
inhibit 45
LED 12
size
backbox 10
slave communicator 51
sounder 15
specifications 13
supervisory 18, 20
LED 12
relay driver 14
supervisory zone 20, 27
switch
functions 16, 36
switches 11
T
telephone
wiring 30
telephone circuit 14
telephone line 18
telephone number 36, 40
terminal block
AC 32
test time 40, 44
transmittal priorities 24
trouble 18, 20
LED 12
relay driver 14
restoral 21
trouble reminder 45
Troubleshoot Mode 16
troubleshoot mode 49
V
verification
alarm 45
W
walktest 47
Walktest Mode 16
waterflow
programming 44
retard timer 44
Z
zone
programming 44, 46
supervisory 20
62
Document #15465
Rev.F1
12/04/02
P/N 15465:F1
Limited Warranty
The manufacturer warrants its products to be free from defects in materials and workmanship
for eighteen (18) months from the date of manufacture, under normal use and service. Products
are date-stamped at time of manufacture. The sole and exclusive obligation of the manufacturer
is to repair or replace, at its option, free of charge for parts and labor, any part which is
defective in materials or workmanship under normal use and service. For products not under
the manufacturer's date-stamp control, the warranty is eighteen (18) months from date of
original purchase by the manufacturer's distributor unless the installation instructions or catalog
sets forth a shorter period, in which case the shorter period shall apply. This warranty is void
if the product is altered, repaired, or serviced by anyone other than the manufacturer or its
authorized distributors, or if there is a failure to maintain the products and systems in which
they operate in a proper and workable manner. In case of defect, secure a Return Material
Authorization form from our customer service department. Return product, transportation
prepaid, to the manufacturer.
This writing constitutes the only warranty made by this manufacturer with respect to its
products. The manufacturer does not represent that its products will prevent any loss by fire
or otherwise, or that its products will in all cases provide the protection for which they are
installed or intended. Buyer acknowledges that the manufacturer is not an insurer and assumes
no risk for loss or damages or the cost of any inconvenience, transportation, damage, misuse,
abuse, accident, or similar incident.
THE MANUFACTURER GIVES NO WARRANTY, EXPRESSED OR IMPLIED, OF
MERCHANTABILITY, FITNESS FOR ANY PARTICULAR PURPOSE, OR OTHERWISE
WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE HEREOF. UNDER
NO CIRCUMSTANCES SHALL THE MANUFACTURER BE LIABLE FOR ANY LOSS
OF OR DAMAGE TO PROPERTY, DIRECT, INCIDENTAL, OR CONSEQUENTIAL,
ARISING OUT OF THE USE OF, OR INABILITY TO USE THE MANUFACTURER'S
PRODUCTS. FURTHERMORE, THE MANUFACTURER SHALL NOT BE LIABLE FOR
ANY PERSONAL INJURY OR DEATH WHICH MAY ARISE IN THE COURSE OF, OR
AS A RESULT OF, PERSONAL, COMMERCIAL, OR INDUSTRIAL USE OF ITS
PRODUCTS.
This warranty replaces all previous warranties and is the only warranty made by the
manufacturer. No increase or alteration, written or verbal, of the obligation of this warranty
is authorized.
LimWarLg.p65
01/10/2000
World Headquarters
One Fire-Lite Place, Northford, CT 06472-1653 USA
203-484-7161 • Fax 203-484-7118
www.firelite.com