Type VAA Auxiliary Relays Auxilliary Relays

advertisement
PROTECTION
VAA
Auxilliary Relays
and will withstand an operation of upto
600 per hour.
General description
VAA relays are voltage operated relays.
The relays are attracted armature units of
compact design with positive action and
a high degree of mechanical stability. The
relays can be supplied with self, or hand
reset contacts and changeover contacts.
See table 1
Standard contacts are of silver/copper
alloy. They are shaped and positioned
to ensure a reliable and low resistance
normally open or normally closed contact.
Standard VAA 11/21 relays are suitable
for ac/dc supply and standard VAA 13/23
relays are suitable for dc supply only.
Type VAA
Auxiliary Relays
Features
• Simple and robust construction
• Positive action and high mechanical
stability
• Heavy duty contact available, where
required
• Slugged relays with delay on operation
/ reset available in ac/dc version.
Application
Control, alarm, indication and other
auxiliary duties in ac or dc systems.
The type VAA Plug-in-relays is specially
designed for industrial control duties
requiring
respetitive
switching
operations. It is capable of providing over
5 million operations without servicing
or drop-off can be supplied on specific
request. Similarly relays with magnetic
blow out contacts can also be supplied on
specific request.
The standard VAA relays provide only instantaneous self or hand reset contacts.
To ensure a longer operating life, the tips
of the silver contacts have a domed profile, the optimum design for the repetitive
operation duties of industrial applications.
Although the standard designs are suitable for dc and full-wave rectified ac
systems only, alternative versions for ac
operation are available.
VAA21/22/23 are double pole versions of
VAA 11/12/13 respectively.
VAA 31/33 are Triple pole versions of VAA
11/12/13 respectively.
When it is necessary to break heavy or
highly inductive dc loads, heavy duty
magnetic blow out type contacts can
be provided. These contacts use the
magnetic field of a small permanent
magnet to force the arc onto the arcing
horns away from the contact tips. The
breaking capacity of the heavy duty
contact is shown by the curves in Figure
1.
Auxiliary relays with delay on pick-up
Customer Benefits
• Auxiliary relay
• Simple
and
robust
construction
• More number of contact
configurations
available
with self/hand reset facility
• Operation annunciation in
the form of flag
• Completely dust proof by
IP5X class protection
GRID
1
VAA
Technical data
Coil rating
DC
VAA operates satisfactorily between 75%-120% of rated volts.
AC
VAA operates satisfactorily between 80% -115% of rated volts.
Minimum operating voltage
Not greater than 70% voltage rating.
Operating times
VAA
15-20 ms typical minimum at nominal voltage
Burdens
VAA 11
3 watts for 30, 125V
6 watts for 50, 250V
VAA ‘Plug’ in:
Nominal 3 watts
Contacts case & operation indicators
Relay type
Standard contacts
Contact reset
Case size
¼ N(15T)
Operation indicator
VAA 11
6 N/O, 2 N/O+ 2 C/O, 3 N/O + 3 N/C,
2 N/O + 4 N/C
Self reset
VAA 12
4 N/O, 3 N/O + 1 N/C, 2 N/O + 2 N/C
Self and hand reset ¼ N(10T)
Mechanically operated hand reset
VAA 13
4 N/O, 3 N/O +1 N/C, 2 N/O + 2 C/O
Hand reset
Mechanically operated hand reset.
¼ N (15T)
Either no flag or a mechanically operated
hand reset flag provided
1.
Contact ratings
2.
Type of Contact Current
Make and carry continuously
Make and carry
3. for 3
seconds
Break
Standard
AC
1250VA with maxima of 5A
and 660V
7500VA with maxima of 30A
and 660V
1250VA with maxima of 5A and 660V
Standard
DC
1250 with maxima of 5A and
660V
7500W with maxima of 30A
and 660V
100W (resistive) or 50W (inductive)
with maxima of 5A and 660V
VAA in magnetic blow-out
Contact ratings
Make and carry
continuously
1875W with maxima
of 7.5A and 660V
Make and carry
for 3 seconds
Break
7500W with maxima Details on application.
of 30A and 660V
Please state duty etc.
Maximum rate of operations: 600 per hour
Insulation
The relay meets the requirements of IS 3231 1965/EC 255-5 series
C-2 kV for 1 minute.
Figure
1 1:
Curve showing breaking capacity of magnetic blowout contacts
2
VAA
Figure 2 : Case and panel cut-out dimensions for case 1/4 N ( all dimensions in mm)
Information
Relay Type: required with your order
VAA11
Relay Type:
Case:
VAA11
1/4N 15Terminals
Case:
Auxiliary
Voltage:
1/4N
15Terminals
YF
24-30VdcVoltage:
/ 48-54Vdc
Auxiliary
110-125Vdc
/ 220-250 Vdc
24-30Vdc / 48-54Vdc
110-125Vac// 220-250
220-250Vdc
Vac
110-125Vdc
YF
025
075
025
575
075
Contact Combination:
110-125Vac
/ 220-250 Vac
6 N/O Combination:
Contact
N/O + 2 C/O
62N/O
N/O++23C/O
N/C
23N/O
2
N/O
+
4
N/C
3 N/O + 3 N/C
575
0
02
23
34
2Flag
N/OOption:
+ 4 N/C
Without
flag
Flag
Option:
With
flag
Without flag
4
A
AB
Issue:flag
With
Factory Defined
Issue:
B
A
Factory Defined
A
VAA 11 Without Time delay on Drop off
VAA 11 Without Time delay on Drop off
Relay Type:
VAA11
Relay Type:
Case:
VAA11
1/4N 15Terminals
Case:
Auxiliary
Voltage:
1/4N
15Terminals
YF
110-125Vdc
/ 220-250 Vdc
Auxiliary
Voltage:
110-125Vac// 220-250
220-250Vdc
Vac
110-125Vdc
YF
875
775
875
Contact Combination:
110-125Vac
/ 220-250 Vac
2 N/O +Combination:
2 C/O
Contact
775
2
2Flag
N/OOption:
+ 2 C/O
Reverse
flag
Flag
Option:
2
C
Issue: flag
Reverse
Factory Defined
Issue:
C
A
Factory Defined
A
VAA 11 With Time delay on Drop-off - 100ms±20ms
VAA 11 With Time delay on Drop-off - 100ms±20ms
3
Relay Type:
1/4N 10Terminals
24-30Vdc
48-50Vdc
110-125Vdc
220-250Vdc
2N/O self reset 2N/O Hand reset
2 N/O self reset 1 N/O 1N/C hand reset
1 N/O 1 N/C self reset 1 N/O 1N/C hand reset
With flag
Factory Defined
Relay Type:
1/4N 15Terminals
24-30Vdc/48-50Vdc
110-125Vdc/220-250Vdc
110-125Vac/220-250ac
4 N/O
3 N/O 1N/C
2 N/O 2 C/O
With flag
Factory Defined
www.grid.alstom.com
0
1
2
Flag Option:
Issue:
B
A
VAA13
Case:
Auxiliary Voltage:
YF
025
075
575
Contact Combination:
0
1
2
Flag Option:
Issue:
B
A
ALSTOM T&D INDIA LIMITED
Pallavaram Works
19/1, G.S.T. Road,
Pallavaram, Chennai - 600 043
Tel: 91-44-2264 8000
Fax: 91-44-2264 0040
“Alstom logo and any alternative version thereof are trademarks and service marks of Alstom. The other names mentioned, registered or not, are the property of their respective
companies. The technical and other data contained in the document are provided for information only. Neither ALSTOM, its officers nor employees accept responsibility for or should
be taken as making any representation or warranty (whether express or implied) as to the accuracy or completeness of such data or the achievements of any projected performance
criteria where these are indicated. No liability is accepted for any reliance placed upon the information contained in this brochure. Alstom reserves the right to revise or change
these data at any time without further notice.”
VAA
VAA12
Case:
YF
Auxiliary Voltage:
025
050
075
010
Contact Combination:
ALSTOM T&D Worldwide Contact Centre:
http://www.alstom.com/contactcentre/
Tel.: +44 (0) 1785 250 070
GRID
4
Download