THE PQ PROTECTION SERIES
SURGE PROTECTION DEVICES
PQC100 SURGE PROTECTION DEVICE
PRODUCT SPECIFICATIONS
Safety Listings:
UL® 1449 3rd Edition
UL® 1449 - Ed. 3 Location Rating:
Type 1 and/or Type 2
IEEE® C62.41 Location Rating:
Category C- High & Category B- Medium
Nominal Discharge Current Rating:
20kA (In)
Maximum Surge Current Rating:
50kA per mode; 100kA per phase
Fault Current (SCCR):
200kAIC
MCOV: 120/240 & 120/208
MCOV: 277/480
L-N, L-G & N-G = 170, L-L = 276
L-N, L-G & N-G = 320, L-L = 550
Product Design:
Compact, thermal protected MOV’s
Connection Method:
Parallel, Supplied with 36” 10AWG leads
Recommended Breaker Size:
30Amp, 3 pole
Protective Components:
Thermal MOV’s and AIC Fusing
Response Time:
< 1 Nanosecond
Frequency:
50/60Hz
Status Indicators:
Indication per phase & Remote Alarm Contacts
Enclosure Type:
NEMA 4, pending UL Type 4
Installation Location:
Indoor or Outdoor
Enclosure Material:
Metal (powder coated aluminum)
Weight:
2.2 lbs.
VPR
VOLTAGE CONFIGURATIONS
L-N
L-L
120/240
120/240, 1 phase, 3W + ground
600
1000
600
600
120/208
120/208, 3 phase, 4W + ground
600
1000
600
600
277/480
277/480, 3 phase, 4W + ground
1000
1800
120
120, 1 phase, 2W + ground*
600
120/240D
120/240D, 3 phase hi-leg delta*
600
240
240, 1 phase, 2W + ground*
1000
347/600
347/600, 3 phase, 4W + ground*
1800
1000
4000
Model number example: PQC100120/240
*Indicates models ETL listed
L-G
1200
N-G
UL® 1449 3rd Edition Listed &
ANSI®/IEEE® Category C3 High Exposure Level
1200
600
500
600
600
1000
1000
1800
1800
•
The PQC100 Model SPD is specifically designed for
critical protection applications and can be installed at
service entrance/MDP’s, distribution panels or directly
at critical loads.
•
The distinctive slim enclosure design of the PQC100
Model allows for installation between electrical panels
where space is often limited – this further allows for a
proper installation where connected lead lengths can
be kept to a minimum.
•
The PQC100 Model is listed as a UL 1449 3rd Edition
Type 1 & Type 2 Device. A Type 1 device is located on
the line (utility) side of the first overcurrent protective
device. A Type 2 device is located on the load side of
the first overcurrent protective device.
•
The PQC100 Model has per phase (e.g., L1, L2 & L3)
status indicators showing whether there is protection
loss and specifically which phase. Remote alarm
contacts are standard for remote monitoring capabilities.
•
A Ten Year product warranty is offered which includes
replacement should the product fail due to transient
voltages or workmanship defects in manufacturing.
•
UL file: www.ul.com/vzca.E335441
VOLTAGES PENDING
PRODUCT OPTIONS
Flush Mounting Kit: Insert “FM” after the model, e.g., PQC100-(Voltage)-FM
Side Mount Kit: Insert “SM” after the model, e.g., PQC100-(Voltage)-SM
HEIGHT – 6”
WIDTH – 3.25”
DEPTH – 3”