Presentation 1 TeSys motor starters - open version TeSys U starter-controllers 1 521288 Presentation The TeSys U starter controller is a D.O.L. starter (1) which performs the following functions: b protection and control of single-phase or 3-phase motors: v breaking function, v overload and short-circuit protection, v thermal overload protection and power switching, b control of the application: v protection function alarms, v application monitoring (running time, number of faults, motor current values, ...), v logs (last 5 faults saved, together with motor parameter values). These functions can be added by selecting control units and function modules which simply clip into the power base. The product can therefore be customised at the last moment. Setting-up accessories simplify or completely eliminate wiring between components. 6 2 1 3 4 Basic starter-controller Consists of a power base and a control unit. Power base 1 Is independent of the control voltage and of the motor power. It incorporates the breaking function with a breaking capacity of 50 kA at 400 V, total coordination (continuity of service) and the switching function. b 2 ratings are available: 0…12 A and 0…32 A. b Non-reversing (LUB) and reversing (LU2B). Control units 2 These must be selected according to the control voltage, the power of the motor to be protected and the type of protection required. b Standard control unit (LUCA): satisfies the basic protection requirements for motor starters: thermal overload and short-circuit (for details see page 1/55). b Advanced control unit (LUCB, LUCC or LUCD): allows additional advanced functions such as alarm, fault differentiation, … (for details see page 1/56). b Multifunction control unit (LUCM): suitable for the most sophisticated control and protection requirements (for details see page 1/57). The control units are interchangeable without rewiring and without using tools. They have a wide range of adjustment (range of 4) and low heat dissipation. Control options 5 8 7 Function modules can be used to increase the functions of the starter-controller. Function modules 3 Must be used with advanced control units. 4 types are available: b thermal overload alarm (LUF W10), b thermal fault and manual reset (LUF DH11), b thermal fault and automatic or remote reset (LUF DA01 and LUF DA10), b indication of motor load (LUF V), which can also be used with the multifunction control unit. All alarm and fault information processed by these modules is available on digital contacts. Communication modules 3 The information processed is exchanged: b via a parallel bus: v parallel wiring module (LUF C00), b via a serial bus: v AS-Interface modules (ASILUF C5 and ASILUF C51), v Modbus modules (LUL C031, LUL C032 and LUL C033). They must be used in conjunction with a c 24 V control unit and require a c 24 V control voltage. Connection to other protocols such as FIPIO, Profibus-DP and DeviceNet is possible via gateway modules (LUFP). Auxiliary contact modules (LUFN) 3 3 possible configurations 2 N/O, 1 N/O + 1 N/C or 2 N/C. Add-on contact blocks 4 Indicate the following status of power base: ready, fault and pole status. Power options Reverser block 5 Allows a non-reversing power base to be converted to reversing operation. The reverser block (LU2M) is mounted directly beneath the power base without modifying the width of the product (45 mm). The reverser block LU6M is mounted separately from the power base when the height available is limited. Limiter-disconnector LUA LB 6 This unit is mounted directly on the power base. It allows the breaking capacity to be increased up to 130 kA at 400 V. Setting-up accessories Plug-in terminal blocks 7 The control terminal blocks are of the plug-in type, so allowing wiring to be prepared away from the machine or the replacement of products without rewiring. Control circuit pre wiring system 8 Numerous pre-wired accessories provide simple, clip-in connections (e.g. connection of reverser control terminals, ... (1) For use with resistive and inductive loads. Control of d.c. or capacitive loads is not possible. 1/54 1 Presentation 1 TeSys motor starters - open version 1 TeSys U starter-controllers with standard control unit 520726 b b b b Protection against overloads and short-circuits Protection against phase failure and phase imbalance Protection against insulation breaks (equipment protection only) Manual reset 1 3-phase motor Class 10 Power base LUB or LU2B Standard control unit LUCA Status Status and commands transmitted by the bus Parallel bus Blanking cover LU9C 1 Auxiliary contact module LUF N Parallel wiring module LUF C00 Serial bus Modbus AS-Interface communication communication modules ASILUF C5 and ASILUF C51 modules LUL C031, LUL C032 and LUL C033 Status Add-on contact blocks LUA1 Blanking cover LU9C 2 1/55 Presentation 1 TeSys motor starters - open version 1 TeSys U starter-controllers with advanced control unit b b b b 1 Protection against overloads and short-circuits Protection against phase failure and phase imbalance Protection against insulation breaks (equipment protection only) Manual reset (remote or automatic with a function module) 3-phase motor Class 20 Single-phase motor Class 10 533842 3-phase motor Class 10 Power base LUB or LU2B Advanced control unit LUCB Status Blanking cover LU9C 1 Thermal overload signalling and manual reset Auxiliary contact module LUF N Thermal overload signalling and automatic reset Function module LUF DH11 Alarm Function modules LUF DA01 and UF DA10 Advanced control unit LUCD Indication of motor load (analogue) Advanced control unit LUCC Status and commands transmitted by the bus Parallel bus Serial bus b Thermal overload signalling and manual, remote or automatic reset b Alarm b Indication of motor load Function module LUF W10 Function module LUF V Parallel wiring module LUF C00 AS-Interface communication modules ASILUF C5 and ASILUF C51 Modbus communication modules LUL C031, LUL C032 and LUL C033 Status Add-on contact blocks LUA1 1/56 Blanking cover LU9C 2 Presentation 1 TeSys motor starters - open version 1 TeSys U starter-controllers with multifunction control unit b b b b b b b b 565397 Protection against overloads and short-circuits Protection against phase failure and phase imbalance Protection against insulation breaks (equipment protection only) Reset parameters can be set to manual or automatic Protection function alarm Indication on front panel or on remote terminal via Modbus RS 485 port "Log" function "Monitoring" function, indication of main motor parameters on front panel of the control unit or via a remote terminal b Fault signalling b Overtorque, no-load running Single-phase or 3-phase motors Class 5, 10, 15, 20, 25, 30 Power base LUB or LU2B Multifunction control unit LUCM Status Indication of motor load (analogue) Status and commands transmitted by the bus Parallel bus Serial bus Remote programming and monitoring of all functions Blanking cover LU9C 1 Aduxiliary contact module LUF N Function module LUF V Parallel wiring module LUF C00 AS-Interface communication modules ASILUF C5 and ASILUF C51 Modbus communication modules LUL C031, LUL C032 and LUL C033 Status Add-on contact blocks LUA1 Blanking cover LU9C 2 1/57 1 Application examples 1 TeSys motor starters - open version 1 520965 TeSys U starter-controllers Application Starting and protection of a pump. 1 Operating conditions b b b b b v v b Power: 4 kW at 400 V. In: 9 A. Maximum of 10 class 10 starts per hour. Duty class S3. 3-wire control: Start button (S2), Stop button (S1), Control circuit voltage: a 230 V. Products used Products used Power base 12 A with screw clamp connections Standard control unit Item 1 Quantity Reference 1 LUB 12 2 1 LUCA 12FU Page 1/64 1/69 561680 Functions performed b Short-circuit protection with level of protection of 50 kA at 400 V. b Total coordination of protection devices conforming to EN 60947-6-2 (continuity of service) in case of a short-circuit. b Electronic protection against thermal overloads with an adjustment range of 4. b Load switching (2 million operating cycles in category AC-43 at In). b Indication of motor status by N/C or N/O contact. b Interlock between the motor starter control and the selector knob position; not possible to start the motor when the knob is in the OFF position. 230 V 13 5/L3 3/L2 1/L1 Scheme 1/58 A1 6/T3 – A2 4/T2 M 3 W1 V1 U1 2/T1 14 C.U. Application examples 1 TeSys motor starters - open version 1 Application Expansion of an existing installation for improved control of its operation. 1 Operating conditions Monitor the status of the motor and obtain alarm signalling by a digital contact in order to improve operation of the pump and anticipate a complete stoppage due to thermal overload. Additional products used Products used Item Quantity Reference Page Replace the standard control unit with an advanced control unit and insert a thermal overload alarm function module. Advanced control unit Alarm function module 2 3 1 1 LUCB 12FU LUF W10 1/69 1/71 Functions performed b Alarm information is generated by the advanced control unit and is processed by the thermal overload alarm function module to make it usable. b The advanced control unit includes a thermal trip Test button on its front panel. a 230 V 13 5/L3 3/L2 1/L1 Scheme Other versions A1 6/T3 07 Alarms Module 08 To application A2 4/T2 M 3a LUF W10 – W1 V1 2/T1 14 C.U. U1 561681 TeSys U starter-controllers a The advanced control unit can provide other functions, depending on the type of function modules used (instead of the LUF W module described above): - thermal fault signalling with function modules LUF DA01, LUF DA10 or LUF DH11, - indication of motor load with the function module LUF V2. This module delivers a 4-20 mA, analogue signal which is proportional to the average 3-phase current drawn by the motor. This allows the load current to be monitored and provides access to other application functions using this value, or to predictive or preventive maintenance possibilities (replacement of the motor before it breaks down). 1/59 Application examples 1 TeSys motor starters - open version 1 520969 TeSys U starter-controllers Application Monitoring operation of a surface pump in a water treatment plant to avoid running empty, which could lead to destruction of the pump. 1 Operating conditions b b b b b Power: 15 kW at 400 V. In: 28.5 A. Duty class S1. Control circuit voltage: c 24 V. Control-command by PLC and serial link using the Modbus protocol. Products used 510301 Products used Power base 32 A without connections Multifunction control unit Modbus communication module Pre-wired coil connection Connection of communication module output terminals to the coil terminals Connection cable for connecting the communication module to the serial bus T-junction Item 1 2 3 4 Quantity 1 1 1 1 Reference LUB 320 LUCM 32BL LUL C032 LU9B N11C Page 1/64 1/70 1/85 1/85 – 1 VW3 A8 306 Rpp 1/85 – 1 VW3 A8 306 TF03 1/85 Functions performed b Short-circuit protection with level of protection of 50 kA at 400V. b Total coordination of protection devices conforming to EN 60947-6-2 (continuity of service) in case of a short-circuit. b Electronic protection against thermal overloads with an adjustment range of 4. b Load ing (1.5 million operating cycles in category AC-43 at In). b Measurement of load current and detection of no-load running by the multifunction control unit. b Interlock between the motor starter control and the selector knob position; not possible to start the motor when the knob is in the OFF position. b No-load running or operation under load. To use this function, the following parameters must be entered: v trip: the answer yes/no enables or disables the function, v time before tripping: the time period during which the value of the current must be below the tripping threshold in order to cause tripping (adjustable from 1 to 200 s). v tripping threshold: value as a % of the load current ratio in relation to the setting current. If the ratio remains below this threshold for the time specified in the previous parameter, the product trips (adjustable from 30 to 100 %). b Indication of the various motor starter status and currents. 1/60 4 5 8 LU9B N11C Pre wired coil 24 V 24 V c Aux COM D (B) D (A) Gnd Modbus Module LUL C032 LO1 LI1 LI2 Multifunction Control Unit D (B) D (A) Gnd 5/L3 LUCM 24 V Aux 4 5 8 V1 4/T2 C.U. W1 6/T3 Bit 0 Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6 Bit 7 Bit 8 Bit 9 Bit 10 Bit 11 Bit 12 Bit 13 Bit 14 Bit 15 Status (Register 455) Ready (available) Poles closed Fault Alarms Tripped Reserved reset enabled A1-A2 powered Motor running Motor current % (bit 0) Motor current % (bit 1) Motor current % (bit 2) Motor current % (bit 3) Motor current % (bit 4) Motor current % (bit 5) Reserved Motor starting U1 2/T1 Modbus profile IEC 64915 Commands (Register 704) Forward running Reverse running Reserved Reset Reserved Connection test Reserved Reserved Reserved Reserved Reserved Reserved Reserved 3-phase control Reserved Reserved Reserved 3/L2 1/L1 Schemes M 3a c 24 V + Modbus VW3 A8 306 TF03 Other functions The multifunction control unit incorporates other control and protection functions, such as: monitoring and control of phase current, alarm, … Module LUL C032 also provides a programmable output and two programmable discrete inputs. Application examples 1 TeSys motor starters - open version 1 520967 TeSys U starter-controllers Application Starting and control of a packing machine conveyor belt. 1 Operating conditions b b b b b Power: 0.37 kW at 400 V. In: 0.98 A. Duty class S1. Control circuit voltage: c 24 V Control and command by the AS-Interface cabling system. Products used Item 1 2 3 Quantity 1 1 1 Reference LUB 120 LUCA 1XBL ASILUF C5 Page 1/64 1/69 1/82 – 1 XZ CG0142 1/83 4 1 LU9B N11C 1/83 Functions performed b Short-circuit protection with level of protection of 50 kA at 400 V. b Total coordination of protection devices conforming to EN 60947-6-2 (continuity of service) in case of a short-circuit. b Electronic protection against thermal overloads with an adjustment range of 4. b Load switching (2 million operating cycles in category AC-43 at In). b Indication of motor status by N/C or N/O contact. b Interlock between the motor starter control and the selector knob position; not possible to start the motor when the knob is in the OFF position. b Start/Stop commands and Ready, Running and Stopped motor status are transmitted by the bus. The AS-Interface 7.D.F.O profile of the new AS-Interface V2 protocol, implemented in the starter-controller, ensures total compatibility with that of the LF enclosed starter range. b Indication of module operation and communication status by 2 LEDs on the front panel of the communication module. b Addressing of the module is achieved using adjustment console ASI TERV2 or console XZ MC11. Using pre-wired coil connector LU9B N11C avoids having to wire the control connections. However, easy access to the control connector on the front panel of the starter allows any control schemes required by the user to be included in the line (local controls, emergency stop, safety contact, .....) 5/L3 3/L2 1/L1 Scheme ASILUF C5 LU9B N11C Pre wired coil AS-Interface Module 24 V + AS-i + C.U. 2/T1 4/T2 6/T3 V1 W1 + U1 521489 Products used Power base 12 A without connections Standard control unit AS-Interface Communication module Tap-off for connecting the communication module to the serial bus Pre-wired coil connection Connection of communication module output terminals to the coil terminals M 3 24 V AS-i XZ CG0142 1/61 Application examples 1 TeSys motor starters - open version 1 520971 TeSys U starter-controllers Application Manual control of a 2-position turntable. 1 Operating conditions b b b b b v v v b b Power: 2.2 kW at 400 V. In: 6 A. 30 starts per hour Duty class S4. 3-wire control: Pushbutton for Position 1 (S1), Pushbutton for Position 2 (S2), Stop button (S5), Stopping at the positions is achieved by limit switches S3 and S4. Control circuit voltage: a 115 V. Products used 523761 Products used Power base reversing, 12 A with screw clamp connections Standard control unit 1 2 Item 1 Quantity Reference 1 LU2B 12FU 2 1 Page 1/65 LUCA 12FU 1/69 Functions performed b Short-circuit protection with level of protection of 50 kA at 400V. b Total coordination of protection devices conforming to EN 60947-6-2 (continuity of service) in case of a short-circuit. b Electronic protection against thermal overloads with an adjustment range of 4. b Load switching (2 million operating cycles in category AC-43 at In). b Interlock between the motor starter control and the selector knob position; not possible to start the motor when the knob is in the OFF position. Electrical interlocking is ensured by pre-wired connector LU9M R1C (item 3) included on base LU2B 12. The design of the reversing power block makes mechanical interlocking unnecessary. 4/T2 V1 6/T3 115 V A2 A1 B3 A3 1/62 W1 U1 2/T1 C.U. M 3 Reverser Motor Controller LU2B B1 5/L3 3/L2 1/L1 Scheme (manual control) Application examples TeSys motor starters - open version 1 1 520973 TeSys U controllers Application Detection of a rock crusher blockage by monitoring the motor current. 1 Operating conditions b b b b b Power: 90 kW at 400 V. In: 185 A. Duty class S1. Control circuit voltage: a 230 V Control-command by PLC and serial link using the Modbus protocol. Products used Products used Controller Multifunction control unit Modbus communication module Current transformer Contactor Circuit-breaker Item 1 2 3 4 5 6 Quantity 1 1 1 3 1 1 Reference LUT M20BL LUCM T1BL LUL C032 LUT C4001 LC1 F185P7 NS 250HMA Page 1/77 1/77 1/85 1/77 – – Functions performed 523762 b Short-circuit protection with level of protection of 70 kA at 400V. b Electronic protection against thermal overloads with an adjustment range of 4. b Detection of crusher blockage by monitoring the induced overcurrent. To use the "overtorque or jam" function, the following parameters must be entered : v trip: the answer yes/no enables or disables the function, v time before tripping: the time period during which the value of the current must be above the tripping threshold in order to cause tripping (adjustable from 1 to 30 s). v tripping threshold: value as a % of the load current ratio in relation to the setting current. If the ratio remains above this threshold for the time specified in the previous parameter, the product trips (adjustable from 100 to 800 %). 6 4 1 2 It is possible to set the parameter for an alarm at a preset threshold under the same conditions as above. 5 3 – KA1 4 5 8 96 24 V 24 V c Aux COM D (B) D (A) Gnd LI2 I.7 I.6 L3 LI1 24 V Aux S1 L1 L2 D (B) D (A) Gnd 6/T3 4/T2 – KA1 From S1/T1, S1/T2, S1/ T3, S2/T1, S2/T2, S2/T3 – KA1 – T2 S1 – Q6 – Q6 To –KA1 A1 S1 – KM1 + 5/L3 3/L2 1/L1 A2 S2 S2 – KM1 – T3 13 2/T1 230 V a Modbus Module 4 5 8 S1 S2 – KA1 LUL C032 S2 – Q6 – T1 – KA1 Controller LUT M20BL I.3 LUCM T1BL Multifunction Control Unit LO1 5/L3 3/L2 1/L1 Scheme c 24 V W1 6T3 V1 4T2 U1 2T1 – KM1 – KA1 Modbus VW3 A8 306 TF03 a M 3a Other functions The multifunction control unit incorporates other control and protection functions, such as: monitoring and control of phase currents, alarm, … Communication module LUL C032 also provides a programmable output and two programmable inputs. 1/63 References 1 TeSys motor starters - open version 1 TeSys U starter-controllers 561330 Two versions of control connection are available: b connection by screw terminals, plug-in control terminal block, b without connection. This version enables wiring to be prepared in advance and is recommended when a communication module is required (allowing the use of control connection prewiring accessories) or when a reverser block is to be mounted by the customer. Power bases for non-reversing D.O.L. starting (1) Connection Power Control Item (2) Rating ≤ 440 V 500 V A A Reference Weight 690 V A kg These bases have 2 auxiliary contacts: 1 N/O (13-14) and 1 N/C (21-22) which indicate the closed or open position of the power poles. LUB p2 A low power internal contact allows power supply to the control unit to be switched off when the control knob is no longer in the ON position. LUB p20 The power bases must be used in conjunction with a control unit, see pages 1/68 to 1/70. Screw clamp Screw terminals clamp terminals 520740 1 520739 Non-reversing power bases 1 + 2 + 3 12 +4 32 Without 1+2 connections 1 2 12 9 LUB 12 0.900 23 21 LUB 32 0.900 12 12 9 LUB 120 0.865 32 23 21 LUB 320 0.865 Terminal block for power bases without connections Connection Screw clamp terminals 4 3 LUB p2 1/64 Dimensions : pages 1/102 and 1/103 LUB 120 or 320 Item (2) 3+4 Reference LU9B N11 Weight kg 0.045 (1) Rated breaking capacity for operation on short-circuit (Ics), see table below. For higher values, use current limiters, see page 1/67. Volts 230 440 500 690 (3) kA 50 50 10 4 (2) The various sub-assemblies are supplied assembled but they are easy to separate, as shown in the illustration. (3) For 690 V, use phase barrier LU9 SP0. Other versions Characteristics : pages 1/88 and 1/89 For base Schemes : pages 1/104 to 1/107 Power bases without built-in short-circuit protection device (short-circuit protection by circuit-breaker or separate fuses). Please consult your Regional Sales Office. References 1 TeSys motor starters - open version 1 TeSys U starter-controllers 561270 Reversing power bases Two versions of control connection are available: b connection by screw terminals, plug-in control terminal block, b without connection. This version enables wiring to be prepared in advance and is recommended when a communication module is required, allowing the use of control connection pre-wiring accessories. Power bases for reversing D.O.L. starting, pre-assembled Connection Power Item (1) Control Rating ≤ 440 V 500 V 690 V A A A Reference, to be completed (2) Weight kg These bases have two N/O common point contacts (81-82-84) which indicate nonreversing and reversing operating status. Screw clamp Screw terminals clamp terminals Without connections 1 + 2 + 3 12 + 4 + 5 32 12 23 9 21 LU2B 12pp LU2B 32pp 1.270 1.270 1 + 2 + 3 12 +5 32 12 23 9 21 LU2B A0pp LU2B B0pp 1.270 1.250 Power bases for reversing D.O.L. starting, for customer assembly A reverser block should preferably be combined with a non-reversing power base without connections to create a reversing starter-controller. The built-in N/O (13-14) and N/C (21-22) contacts are used for electrical interlocking between the reverser block and the base; they are therefore no longer available as output contacts. The reverser block has two N/O common point contacts (81-82-84) which indicate non-reversing and reversing operating status. LU2B p2 520741 32 A reverser block 1 For mounting directly beneath the power base For mounting separately from the base (screw or rail fixing) 2 Connection Power Control Item (1) Reference, to be completed (2) 3 LU2M B0pp Screw clamp terminals Screw clamp terminals Without connections Without 6 connections LU6M B0pp Weight kg 0.400 0.425 Accessories Description Control terminal block Item Application Reference 4 Reversing power base without connections LU2B A0pp or B0pp Reverser block LU2M B0pp for direct mounting beneath power base Reverser block LU6M B0pp for mounting separately from power base Reverser block LU6M B0pp for mounting separately from power base LU9 M1 Weight kg 0.025 LU9 M1 0.025 LU9 M1 0.025 LU9M R1 0.030 3 7 5 Control circuit pre-wiring components Description Weight kg Pre-wired connector (3) 5 LU9M R1C 0.035 (1) The various sub-assemblies are supplied assembled but they are easy to separate, as shown in the illustration. (2) Select the same control voltage as that of the control unit. Standard control circuit voltages: Volts 24 48…72 110…240 c BL – – a B – – c or a – ES (4) FU (5) (3) For control connection between a power base and a reverser block, for direct mounting. (4) c : 48…72 V, a : 48 V. (5) c : 110…220 V, a : 110...240 V. 4 520826 LU2B p2 6 Other versions 7 Item Reference Power bases without built-in short-circuit protection device (short-circuit protection by circuit-breaker or separate fuses). Please consult your Regional Sales Office. 4 LU6M + LU9 M1 + LU9M R1 Characteristics : pages 1/88 and 1/89 Dimensions : pages 1/102 and 1/103 Schemes : pages 1/104 to 1/107 1/65 1 TeSys motor starters - open version Presentation, references 1 TeSys U starter-controllers 1 Add-on contact blocks and auxiliary contact modules Contact states 1 Product status Position of Indication N/O pole control on front contact handle panel References of add-on contact blocks and auxiliary contact modules Terminal referencing – – – or – – – or – – or – – LUF N20 33-34 43-44 LUF N11 43-44 or – – Off LU9B N11 13-14 N/C pole contact N/O contact N/C contact any fault any fault N/O contact product ready LUF N11 LUA1 C20 LUA1 C11 LUA1 C20 31-32 97-98 95-96 17-18 LUF N02 LUA1 C200 LUA1 C110 LUA1 C200 31-32 no terminal no terminal no terminal 41-42 block block block LU9B N11 – – LUA1 C11 21-22 17-18 – – – – – – LUA1 C110 no terminal block – 0 OFF Ready to operate 0 Start 1 Tripped on short-circuit Tripped on thermal overload Manual reset mode TRIP I>> TRIP 0 Automatic reset on thermal overload fault mode 0 Remote reset mode 0 N/O contact in closed position. N/O contact in open position References Add-on contact blocks 561521 Signalling and composition 3 4 2 Reference Screw clamp terminals Without connections 1+2 LUA1 C11 1 LUA1 C110 0.012 1+2 LUA1 C20 0.030 1 LUA1 C200 0.012 Screw clamp terminals Without connections 2 N/O contacts (33-34 and 43-44) 1 N/C contact (31-32) and 1 N/O contact (43-44) 2 N/C contacts (31-32 and 41-42) Item Reference 3 3 3 LUF N20 LUF N11 LUF N02 Item Reference 2 2 LU9B C11 LU9B C20 For use on Blanking covers Location for auxiliary contact, 4 communication or function module Location for add-on contact blocks 5 1/66 Schemes : page 1/88 Weight kg 0.050 0.050 0.050 Accessories Screw clamp LUA1 C110 terminal blocks LUA1 C200 Characteristics : page 1/90 Weight kg 0.030 Auxiliary contact modules for connection by screw clamp terminals Module with 2 contacts indicating the status of the starter-controller power poles Operation: a or c 24…250 V, I th: 5 A Description LUB + LUA1 + LUF N Item Composition 1 5 1 N/C fault signalling contact (95-96) and 1 N/O contact (17-18) indicating control handle in “ready” position 1 N/O fault signalling contact (97-98) and 1 N/O contact (17-18) indicating control handle in “ready” position Connection Weight kg 0.022 0.022 LU9C 1 0.020 LU9C 2 0.010 References 1 TeSys motor starters - open version 1 TeSys U starter-controllers 533843 Power connection pre-wired system, limiter blocks and accessories Pre-wired system for power connections up to 63 A Description 4 1 8 Application Pitch mm 45 54 45 54 45 54 54 – 2 Sets of 3-pole 63 A busbars 3 2 tap-offs 3 tap-offs 533844 4 tap-offs 5 Protective end cover Terminal block for supply to one or more busbar sets 6 5 tap-offs For unused busbar outlets Connection – from the top Item 2 – – – 1 – – 4 Sold in lots of 1 1 1 1 1 1 1 5 Unit reference GV2 G245 GV2 G254 GV2 G345 GV2 G354 GV2 G445 GV2 G454 GV2 G554 GV1 G10 3 1 GV1 G09 Weight kg 0.036 0.038 0.058 0.060 0.077 0.085 0.100 0.005 0.040 Pre-wired system for power connections up to 160 A The busbar system can be screw-mounted onto any type of support. Set of 4-pole busbars: 3-phase + neutral or 3-phase + common Number of Item tap-offs at 18 mm intervals 18 5 Length mm 452 For mounting in enclosure width mm 800 Reference AK5 JB144 Weight kg 0.900 Removable 3-phase power sockets Number of points Thermal used on the current busbar system 2 16 32 Item Cable lengths Sold in Unit lots of reference 6 6 200 250 1000 6 6 6 AK5 PC13 (1) AK5 PC33 (1) AK5 PC33L (1) Weight kg 0.040 0.045 0.060 Limiter blocks and accessories 533845 Application Limiterdisconnector (3) (6) Current limiters (3) Limiter cartridge Clip-in marker holder 7 10 8 Item 7 + 10 Breaking Mounting capacity Iq ≤ 440 V 690 V kA kA 130 70 Direct on power base Unit reference Weight LUA LB1 (2) kg 0.310 8 100 35 Separate LA9 LB920 0.320 10 – 130 – 70 – Limiter-disconnector LUA LF1 On power base, LAD 90 (4) on reverser block, on parallel link splitter box 0.135 0.001 561524 Phase barrier 9 Phase barrier LU9 SP0 must be used: b To build a UL 508 type E certified starter (Self Protected Starter). Without the phase barrier, the starter-controller is certified UL 508. b If the starter-controller is to be used on an operational voltage of 690 V. Description Phase barrier Item Application Mounting Reference 9 LUB or LU2B 12 or 120 LUB or LU2B 32 or 320 LUA LB1 Direct on LU9 SP0 terminals L1, L2, L3 Weight kg 0.030 561425 Door interlock mechanisms Description 11 12 13 Item Reference Weight kg 0.490 0.150 0.150 Fixing kit (5) (7) 11 + 12 LU9 AP00 Door-mounted black handle/blue front plate, IP54 13 LU9 AP11 Door-mounted red handle/yellow front plate, IP54 13 LU9 AP12 (1) The maximum permissible peak current for power sockets AK5 PCpp is 6 kA. When used in association with power bases LUBpp, the prospective short-circuit current must not exceed 7 kA (2) Supplied with limiter cartridge. (3) These devices make it possible to increase the breaking capacity of the power base. (4) Sold in lots of 100. (5) The fixing kit includes a shaft extension (maximum depth 508 mm). (6) The limiter must be mounted on an LUB or LU2B power base. The limiter can therefore not be common to several motor starters. (7) To use the fixing kit with a D.O.L. reversing power base, only reverser block LU6 M must be used. Dimensions : pages 1/102 and 1/103 1/67 1 Selection 1 TeSys motor starters - open version TeSys U starter-controllers Control units Operating characteristics 1 Control units Standard LUCA Thermal overload protection Overcurrent protection Advanced LUCB LUCC LUCD 14.2 x the setting current Short-circuit protection Protection against phase loss Multifunction LUCM 3 to 17 x the setting current 14.2 x the max. current Protection against phase imbalance Earth fault detection (equipment protection only) Tripping class Motor type 10 3-phase 10 20 Single-phase 3-phase 5…30 Single-phase and 3-phase Thermal overload test function Overtorque No-load running Long starting times Reset mode Manual Automatic or remote Parameters can be set With function module or parameters can Parameters can be set be set via the bus with a communication module, see chart below. Parameters can be set via the bus with a communication module (see below). Thermal overload alarm only with function module or communication module, see below. Alarm "Log" function Display of main motor parameters on front panel of the control unit via remote terminal, via PC or via PDA (1). "Monitoring" function With function modules Possible for each type of fault. Indication on front panel of the control unit, via remote terminal, via PC or via PDA (1). With communication modules to make use of these alarms via a bus, see below. Log of the last 5 trips. Number of starts, number of trips, number of operating hours. (2) Thermal overload alarm Thermal overload signalling and manual reset With module LUF W With module LUF DH11 Thermal overload signalling and automatic or remote reset Indication of motor load (analogue) With modules LUF DA01 and LUF DA10 With module LUF V With communication module or via Modbus port on control unit LUCM (2) Starter status (ready, running, fault) Reset mode Alarm Remote reset via the bus Indication of motor load With any communication module Parameters can be set via the bus With Modbus modules LUL C031, LUL C032 and LUL C033 (thermal overload alarm only). Fault signalling and differentiation Remote programming and monitoring of all functions "Log" function "Monitoring" function Built-in function (1) PDA: Personal Digital Assistant. (2) Mounting possibilities: 1 function module or 1 communication module. 1/68 With Modbus modules LUL C031, LUL C032 and LUL C033 and Modbus port on the control unit (alarm possible for all types of fault). With Modbus modules LUL C031, LUL C032 and LUL C033 and Modbus port on the control unit. Function provided with accessory 1 References 1 TeSys motor starters - open version 1 TeSys U starter-controllers 530655 Standard and advanced control units Description 1 5 2 4 Extraction and locking handle Test button (on advanced control unit only) Ir adjustment dial Locking of settings by sealing the transparent cover Sealing of locking handle 3 1 Standard control units Maximum standard power ratings of 3-phase motors 50/60 Hz 400/440 V 500 V 690 V kW kW kW 0.09 – – 0.25 – – 1.5 2.2 3 5.5 5.5 9 7.5 9 15 15 15 18.5 520735 LUCA pppp LUCB pppp 1 2 3 4 5 Setting range Clip-in mounting on power base Rating Reference to be completed by adding the voltage code (1) A 0.15…0.6 0.35…1.4 1.25…5 3…12 4.5…18 8…32 A 12 12 12 12 32 32 LUCA LUCA LUCA LUCA LUCA LUCA and and and and 32 32 32 32 X6pp 1Xpp 05pp 12pp 18pp 32pp Weight kg 0.135 0.135 0.135 0.135 0.135 0.135 Advanced control units Pressing the Test button on the front panel simulates tripping on thermal overload. Class 10 for 3-phase motors 0.09 0.25 1.5 5.5 7.5 15 – – 2.2 5.5 9 15 – – 3 9 15 18.5 0.15…0.6 0.35…1.4 1.25…5 3…12 4.5…18 8…32 12 12 12 12 32 32 and and and and 32 32 32 32 LUCB LUCB LUCB LUCB LUCB LUCB X6pp 1Xpp 05pp 12pp 18pp 32pp 0.140 0.140 0.140 0.140 0.140 0.140 0.15…0.6 0.35…1.4 1.25…5 3…12 4.5…18 8…32 12 12 12 12 32 32 and and and and 32 32 32 32 LUCC LUCC LUCC LUCC LUCC LUCC X6pp 1Xpp 05pp 12pp 18pp 32pp 0.140 0.140 0.140 0.140 0.140 0.140 0.15…0.6 0.35…1.4 1.25…5 3…12 4.5…18 8…32 12 12 12 12 32 32 and and and and 32 32 32 32 LUCD LUCD LUCD LUCD LUCD LUCD X6pp 1Xpp 05pp 12pp 18pp 32pp 0.140 0.140 0.140 0.140 0.140 0.140 Class 10 for single-phase motors – 0.09 0.55 2.2 4 7.5 520736 LUB p2 + LUCA pppp – – – – – – – – – – – – Class 20 for 3-phase motors 0.09 0.25 1.5 5.5 7.5 15 – – 2.2 5.5 9 15 – – 3 9 15 18.5 (1) Standard control circuit voltages: Volts 24 48…72 110…240 c BL (2), (3) – – a B – – c or a – ES (4) FU (5) (2) Voltage code to be used for a starter-controller with communication module. (3) d.c. voltage with maximum ripple of ± 10 %. (4) c : 48…72 V, a : 48 V. (5) c : 110…220 V, a : 110...240 V. LUB p2 + LUCB pppp Characteristics : pages 1/88 and 1/91 Schemes : pages 1/104 to 1/107 1/69 References 1 TeSys motor starters - open version 1 TeSys U starter-controllers 530656 Multifunction control units Description 6 1 1 2 3 5 LUCM ppBL 4 1 Extraction and locking handle 2 Built-in display window (2 lines, 12 characters) 3 4-button keypad 4 c 24 V auxiliary power supply 5 Modbus RS485 communication port. Connection by RJ45 connector. 6 Sealing of locking handle The display window 2 and keypad 3 allow: b in configuration mode: local configuration of protection functions and alarms, b in run mode: display of parameter values and events. The Modbus communication port 5 is used to connect: b an operator terminal, b a PC, b a Personal Digital Assistant (PDA). Multifunction control units 520737 Parameter entry, monitoring of parameter values and consultation of logs are carried out: b either on the front panel, using the built-in display window/keypad, b or via an operator terminal, b or via a PC or a PDA with PowerSuite software, b or remotely, via a Modbus communication bus. Programming of the product via the keypad requires a c 24 V auxiliary power supply. LUB p2 + LUCM ppBL Maximum standard power ratings of 3-phase motors 50/60 Hz 400/415 V 500 V 690 V kW kW kW 0.09 – – 0.25 – – 1.5 2.2 3 Setting range Clip-in mounting on power base Rating A 0.15…0.6 0.35…1.4 1.25…5 A 12 and 32 12 and 32 12 and 32 LUCM X6BL LUCM 1XBL LUCM 05BL kg 0.175 0.175 0.175 5.5 7.5 15 3…12 4.5…18 8…32 12 and 32 32 32 LUCM 12BL LUCM 18BL LUCM 32BL 0.175 0.175 0.175 5.5 9 15 9 15 18.5 Reference (1) Weight TeSys U user's manual (2) Application On CD-Rom Language Reference Multi-language (3) LU9 CD1 Weight kg 0.022 Operator terminal 521335 This compact Magelis terminal enables the parameters of multifunction control unit LUCM to be read and modified. It is supplied pre-configured to provide dialogue with 8 TeSys U starter-controllers (Modbus protocol, application pages and alarm pages loaded). Starter-controller alarm and fault management takes priority. Language Multi-language (3) XBT NU400 Display window Supply voltage Reference 4 lines of 20 characters c 24 V XBT NU400 Type Reference Weight kg 0.150 Connecting cable (4) Function Length Weight kg 0.200 Connects terminal XBT NU400 2.5 m SUB-D 25-way XBT Z938 to a multifunction control unit. female - RJ45 (1) Input voltage c 24 V with maximum ripple of ± 10 %. (2) The CD-Rom contains user's manuals for the AS-Interface and Modbus communication modules, multifunction control units and gateway modules, as well as the gateway programming software. (3) English, French, German, Italian, Spanish (4) If a terminal is used with several control units, this cable can be connected to a Modbus hub or to T-junctions (see page 1/85). Characteristics : pages 1/88 and 1/91 1/70 Schemes : pages 1/104 to 1/107 References 1 TeSys motor starters - open version 1 TeSys U starter-controllers Function modules Function modules Output Item Application Reference Weight kg 533846 Thermal overload signalling and manual reset Module LUF DH11 makes it possible to differentiate thermal overload and shortcircuit faults. (The short-circuit fault can then be signalled via add-on contact blocks LUA1 C). The module includes two contacts for thermal overload signalling, as well as an LED on the front panel. To reset the motor starter, the operator must use the rotary knob on the power base. The module can only be used with an advanced control unit and requires an a/c 24…240 V external powr supply. 4 3 2 1 N/O + 1 N/C 3 a or c 24…250 V LUF DH11 0.060 Thermal overload signalling and automatic or remote reset These modules make it possible to differentiate thermal overload and short-circuit faults. (The short-circuit fault can then be signalled via add-on contact blocks LUA1 C). The modules include one contact for thermal overload signalling, as well as an LED on the front panel. A second contact (terminals Z1-Z2) must be wired in series with terminal A1 of the motor starter. In the event of a thermal overload fault, this wiring allows motor control to be switched off. The rotary knob on the power base will then stay in the "ready position" . Resetting of the motor starter is automatic after the required motor cooling time if terminals X1-X2 are linked by a strap, or remote by pulsed closing of a volt-free contact connected to terminals X1-X2. These modules can only be used with an advanced control unit and require an a/c 24…240 V external powr supply. 510445 LUB p2 + LUCB pppp + LUFW 10 or LUF Vp 1 Note : Terminals X1-X2 are not isolated from the signalling module power supply. For remote resetting, use a volt-free contact specifically for each module to be reset. 1 N/C 4 a or c 24…250 V LUF DA01 1 NO 4 a or c 24…250 V LUF DA10 0.055 0.055 Thermal overload alarm Through load shedding, this module makes it possible to avoid stoppages in operation due to overload tripping. Imminent thermal overload tripping is displayed as soon as the thermal state exceeds the threshold of 105 % (hysteresis = 5 %). Signalling is possible via an LED on the front panel of the module and externally by an N/O relay output. It can only be used with an advanced control unit, from which it takes its power. % 200 100 1 2 3 4 1 N/O 1 2.2 kW 2 4 kW 3 7.5 kW 12 mA 20 mA a or c 24…250 V LUF W10 0.055 Indication of motor load This module provides a signal which is representative of the motor load status (I average/Ir). b I average = average value of the rms currents in the 3 phases, b Ir = value of the setting current. The value of the signal (4-20 mA) corresponds to a load status of 0 to 200 % (0 to 300 % for a single-phase load). It can be used with an advanced or multifunction control unit. Module LUF V2 requires a c 24 V external power supply. 4 - 20 mA Characteristics : pages 1/88 and 1/93 1 2 – LUF V2 0.050 Schemes : pages 1/104 to 1/107 1/71 1 534513 Presentation, functions PowerSuite software workshop 1 1 Presentation 1 The PowerSuite software workshop for PC is a user-friendly tool designed for setting up control devices for the following Telemecanique brand motors: b TeSys U controller-starters b Altistart soft start/soft stop units b Altivar variable speed drives. It includes various functions designed for setup phases such as: b Preparing configurations b Start-up b Maintenance. In order to simplify the start-up and maintenance phases, the PowerSuite software workshop can use the Bluetooth ® wireless link. Functions (1) PowerSuite screen on PC Installed base management Preparing configurations The PowerSuite software workshop can be used on its own to generate the device configuration. It can be saved, printed and exported to office automation software. The PowerSuite software workshop can also be used to convert: b An Altivar 28 drive configuration to an Altivar 31 drive configuration b An Altivar 38 drive configuration to an Altivar 61 drive configuration b An Altivar 58 or Altivar 58F drive configuration to an Altivar 71 drive configuration. Start-up 533181 When the PC is connected to the device, the PowerSuite software workshop can be used to: b Transfer the generated configuration b Adjust b Monitor. This option has been enhanced with new functions such as: v The oscilloscope v The high speed oscilloscope (minimum time base: 2 ms) v Displaying communication parameters b Control b Save the final configuration. PowerSuite screen on PC View of PI regulator function parameters Maintenance 533182 In order to simplify maintenance operations, the PowerSuite software workshop can be used to: b Compare the configuration of a device currently being used with a saved configuration b Manage the user’s installed base of equipment, in particular: v Organize the installed base into folders (electrical equipment, machinery, workshops, etc.) v Store maintenance messages v Simplify Ethernet connection by storing the IP address. User interface PowerSuite screen on PC Monitoring control panel (cursor, gauge) The PowerSuite software workshop can be used to: b Present the device parameters arranged by function in the form of illustrated views of diagrams or simple tables b Customize the parameter names b Create: v A user menu (choice of particular parameters) v Monitoring control panels with graphic elements (cursors, gauges) b Perform sort operations on the parameters b Display text in five languages (English, French, German, Italian and Spanish). The language changes immediately and there is no need to restart the program. It also has online contextual help: b On the PowerSuite tool b On the device functions by direct access to the user manuals. (1) Some functions are not available for all devices. See the table of function availability, page 1/73. References: page 1/74 1/72 Functions (continued) 1 PowerSuite software workshop 1 Function availability for the PowerSuite software workshop Functions not listed in the table are available for all devices. Function available with devices Controllerstarter TeSys U Soft start/soft Drives stop unit ATS 48 ATV 11 1 ATV 31 ATV 61 ATV 71 Monitoring Oscilloscope High speed oscilloscope Display of communication parameters Control Customization of parameter names Creation of a user menu Creation of monitoring control panels Sort operation on parameters Functions available Functions not available 522793 Connections (1) Modbus communication bus The PowerSuite software workshop can be connected directly to the device terminal port or Modbus network port via the serial port on the PC. PowerSuite Two types of connection are possible: b With a single device (point-to-point connection), using a VW3 A8 106 PC serial port connection kit b With a number of devices (multidrop connection), using the XGS Z24 interface. RS 232 XGS Z24 RS 485 Modbus bus ATV 31 ATV 61 ATV 71 TeSys U ATS 48 Modbus multidrop connection Ethernet TCP/IP communication network The PowerSuite software workshop can be connected to an Ethernet TCP/IP network. In this case, the devices can be accessed: b Using a VW3 A58 310 communication card for the Altivar 61 and 71 drives b Using a 174 CEV 300 20 Ethernet-Modbus bridge. Bluetooth® wireless link The PowerSuite software workshop can communicate via a Bluetooth ® radio link with a device equipped with a Bluetooth ® - Modbus VW3 A8 114 adapter. The adapter plugs into the device terminal port or Modbus network port and has a range of 10 m (class 2). 522794 PLC (2) PowerSuite If the PC does not have Bluetooth ® technology, use the VW3 A8 115 USB-Bluetooth® adapter. Ethernet TCP/IP network Remote maintenance Using a simple Ethernet connection, the PowerSuite software workshop can be used for remote monitoring and diagnostics. When devices are not connected to the Ethernet network, or it is not directly accessible, various remote transmission solutions may be possible (modem, teleprocessing gateway, etc.). Please consult your Regional Sales Office. Bridge Modbus bus (1) Please refer to the compatibility table on page 1/75. (2) Please refer to our specialist “Automation platform Modicon Premium and Unity - PL7 software” and “Automation platform Modicon TSX Micro - PL7 software” catalogues. ATV 31 ATS 48 ATV 61 ATV 71 Ethernet connection Presentation: page 1/72 References: page 1/74 1/73 References 1 PowerSuite software workshop 1 PowerSuite software workshop 522838 Description VW3 A8 104 VW3 A8 114 Presentation: page 1/72 1/74 Composition Reference Weight kg 0.100 b 1 program for PC in English, French, German, Italian VW3 A8 104 and Spanish b Variable speed drive and starter technical manuals. PowerSuite update b 1 program for PC in English, French, German, Italian VW3 A8 105 0.100 CD-ROM (1) and Spanish b Variable speed drive and starter technical manuals. Connection kit for PC serial b 1 x 3 m cable with 2 RJ45 connectors VW3 A8 106 0.350 port b 1 RS 232/RS 485 converter with one 9-way female SUB-D for point-to-point Modbus connector and 1 RJ45 connector connection b 1 converter for the ATV 11 drive, with one 4-way male connector and one RJ45 connector b 1 RJ45/9-way male SUB-D adapter for connecting ATV 38/58/58F drives b 1 RJ45/9-way female SUB-D adapter for connecting ATV 68 drives. RS 232-RS 485 interface 1 multidrop Modbus converter for connection XGS Z24 0.105 for multidrop Modbus connection to screw terminals. Requires a 24 V c (20...30 V), 20 mA power supply (3). b 1 Bluetooth® adapter (10 m range, class 2) VW3 A8 114 0.155 Modbus-Bluetooth® adapter (2) with 1 RJ45 connector b 1 x 0.1 m cable with 2 RJ45 connectors for PowerSuite b 1 x 0.1 m cable with 1 RJ45 connector and 1 mini DIN connector for TwidoSoft b 1 RJ45/9-way male SUB-D adapter for connecting ATV 38/58/58F drives. This adapter is required for a PC which is not equipped VW3 A8 115 0.290 USB-Bluetooth® adapter with Bluetooth® technology. It is connected to a USB port on the PC. for PC Range of 10 m (class 2). (1) Updates a version u V1.50 with the latest available version. For versions < V1.50, you should order the PowerSuite CD-ROM, VW3 A8 104. (2) Can also be used to communicate between a Twido PLC and the TwidoSoft software workshop. (3) Please consult our “Interfaces, I/O splitter boxes and power supplies” catalogue. PowerSuite CD-ROM 533188 1 Functions: pages 1/72 and 1/73 Compatibility 1 PowerSuite software workshop 1 Compatibility of PowerSuite software workshop with the following devices (1) Connection Modbus Ethernet (device equipped with an Ethernet TCP/IP card) Ethernet via Modbus Ethernet bridge Bluetooth ® Compatible software versions Incompatible software versions Controllerstarter TeSys U V1.40 Soft start/ Drives soft stop unit ATS 48 ATV 11 V1.30 V1.40 ATV 31 V2.0 V1.50 V2.2 V2.0 V2.2 ATV 61 V2.30 V2.30 V2.30 V2.30 1 ATV 71 V2.2 V2.2 V2.2 V2.2 Hardware and software environments The PowerSuite software workshop can operate in the following PC environments and configurations: b Microsoft Windows® 98 SE, Microsoft Windows® 2000, Microsoft Windows® XP b Pentium III, 800 MHz, hard disk with 300 MB available, 128 MB RAM b SVGA or higher definition monitor (1) Software version supplied for the latest version of drive available. Presentation: page 1/72 Functions: pages 1/72 and 1/73 References: page 1/74 1/75 TeSys control components Presentation, combinations 1 1 TeSys U controllers Presentation Above 32 A, the TeSys U controller provides a motor starter management solution identical to that provided by TeSys U starter-controllers. 1 Used in conjunction with a short-circuit protection device and a contactor, it provides a motor starter whose functions are the same as those of a TeSys U starter-controller and, in particular, provides the following functions: overload protection, motor starter control and application monitoring. Composition It consists of a control unit whose adjustment range is compatible with the secondary of current transformers, plus a control base which also allows fitment of a function module or a communication module. It requires a c 24 V external power supply. The secondaries of current transformers, the c 24 V power supply, the 10 inputs and the 5 outputs are connected by screw terminal block. Combinations providing type 2 coordination With circuit-breaker Standard power ratings of 3-phase motors 50-60 Hz in category AC-3 400/415 V P Ie kW A 18,5 35 22 42 30 57 37 69 45 81 55 100 75 135 90 165 110 200 132 240 160 285 200 352 220 388 250 437 Circuit-breaker (1) Reference NS80HMA NS80HMA NS80HMA NS80HMA NS100HMA NS160HMA NS160HMA NS250HMA NS250HMA NS400HMA NS400HMA NS630HMA NS630HMA NS630HMA Rating A 50 50 80 80 100 150 150 220 220 320 320 500 500 500 Irm (2) A 500 650 880 1040 1300 1350 1800 2200 2640 3200 4160 5000 5500 6000 Contactor TeSys U controller Current transformers Reference (3) Reference Reference LUTM + LUTM + LUTM + LUTM + LUTM + LUTM + LUTM + LUTM + LUTM + LUTM + LUTM + LUTM + LUTM + LUTM + 3x 3x 3x 3x 3x 3x 3x 3x 3x 3x 3x 3x 3x 3x LC1 D40 LC1 D50 LC1 D65 LC1 D80 LC1 D95 LC1 D115 LC1 D150 LC1 F185 LC1 F225 LC1 F265 LC1 F330 LC1 F400 LC1 F400 LC1 F500 LUCp LUCp LUCp LUCp LUCp LUCp LUCp LUCp LUCp LUCp LUCp LUCp LUCp LUCp LUT LUT LUT LUT LUT LUT LUT LUT LUT LUT LUT LUT LUT LUT C0501 C1001 C1001 C1001 C1001 C2001 C2001 C2001 C4001 C4001 C4001 C4001 C4001 C8001 With fuses Standard power ratings Switch of 3-phase motors 50-60 Hz disconnector-fuse in category AC-3 400/415 V P Ie Reference kW A 18,5 35 GS1 F 22 42 GS1 J 30 57 GS1 J 37 69 GS1 J 45 81 GS1 J 55 100 GS1 L 75 135 GS1 L 90 165 GS1 N 110 200 GS1 N 132 240 GS1 QQ 160 285 GS1 QQ 200 352 GS1 S 220 388 GS1 S 250 437 GS1 S 315 555 GS1 S (1) Product marketed under the Merlin Gerin brand. (2) Irm: setting current of the magnetic trip (3) For reversing operation, replace the prefix LC1 with LC2. References : page 1/77 1/76 Characteristics : pages 1/94 and 1/95 aM fuses Size 14 x 51 22 x 58 22 x 58 22 x 58 22 x 58 T0 T0 T1 T1 T2 T2 T3 T3 T3 T3 Rating A 40 50 80 100 100 125 160 200 250 315 400 500 500 500 630 Contactor TeSys U controller Current transformers Reference (3) Reference Reference LUTM + LUTM + LUTM + LUTM + LUTM + LUTM + LUTM + LUTM + LUTM + LUTM + LUTM + LUTM + LUTM + LUTM + LUTM + 3x 3x 3x 3x 3x 3x 3x 3x 3x 3x 3x 3x 3x 3x 3x LC1 D40 LC1 D50 LC1 D65 LC1 D80 LC1 D95 LC1 D115 LC1 D150 LC1 F185 LC1 F225 LC1 F265 LC1 F330 LC1 F400 LC1 F400 LC1 F500 LC1 F630 Dimensions, mounting : page 1/78 Schemes : page 1/79 LUCp LUCp LUCp LUCp LUCp LUCp LUCp LUCp LUCp LUCp LUCp LUCp LUCp LUCp LUCp LUT LUT LUT LUT LUT LUT LUT LUT LUT LUT LUT LUT LUT LUT LUT C0501 C1001 C1001 C1001 C1001 C2001 C2001 C2001 C4001 C4001 C4001 C4001 C4001 C8001 C8001 References 1 TeSys control components 1 TeSys U controllers References 532083 Control bases (control circuit voltage c 24 V) Connection Current transformers Screw For use with contactor Reference Control Weight Screw LC1 Dpp LUT M10BL kg 0.800 LC1 Fppp LUT M20BL 0.800 Control units Description Advanced Class 10 For motor Setting range type 3-phase 0.35…1.05 LUCB T1BL Weight kg 0.140 20 3-phase 0.35…1.05 LUCD T1BL 0.140 3-phase 0.35…1.05 LUCM T1BL 0.175 Multifunction 5 to 30 Reference Current transformers LUT M + LUCM T1BL + LUTC pp Operating current Primary Secondary 30 1 Reference Weight kg LUT C0301 0.200 50 1 LUT C0501 0.200 100 1 LUT C1001 0.200 200 1 LUT C2001 0.200 400 1 LUT C4001 0.430 800 1 LUT C8001 0.600 Function modules and communication modules The TeSys U controller is compatible with the modules listed below. b Thermal overload alarm module LUF W10 (1), see page 1/71. b Motor load indication module LUF V2, see page 1/71. b Modbus communication modules LUL C032 and LUL C033, see page 1/84. (1) Module LUF W10 is only compatible with control units LUCB T1BL and LUCD T1BL. Presentation : page 1/76 Characteristics : pages 1/94 and 1/95 Dimensions, mounting : page 1/78 Schemes : page 1/79 1/77 1 TeSys control components Dimensions, mounting 1 TeSys U controllers Dimensions 163 173 1 114 45 171 73 Mounting 114 Presentation : page 1/76 1/78 Ø4 30 Characteristics : pages 1/94 and 1/95 References : page 1/77 Schemes : page 1/79 1 Schemes TeSys control components 1 1 TeSys U controllers Schemes Reversing controller LUT M 1 LUTM LUTM LUTM S2 24 V Aux. I.10 I.9 I.8 I.7 I.5 I.4 I.3 I.2 I.1 L3 L2 L1 I.6 + S1 06/NC (1) 05 (1) 98 97/NC 96/NO 95 23/NO 13/NO LUTM 3-wire control, pulsed start with maintaining contact 24 V c 24…250 V a Any fault – KM1 AR 06 – + + I.9 I.8 I.10 24 V c I.7 SR I.6 SF Reset AV 05 98 97 I.4 I.5 RST Control unit fault I.3 I.2 Channel 2 I.1 Channel 1 96 23 95 – KM2 13 – KM1 – Q1 Trip – KM2 24 V c External fault Stop Control for Modbus communication modules LUL C032 and LUL C033 – KM2 24 V c 24…250 V a Man 1 Any fault “Local”/“remote” Man 2 – KM1 – KM2 AU Modbus network port Free – KM1 Reset – KM2 – Q1 Trip – Q1 On AU “Local”/ “remote” LI2 LI1 OA3 – + + I.10 I.9 24 V c I.8 I.7 SR I.6 SF I.5 RST Control unit fault I.4 I.3 I.2 I.1 Free COM Any fault Channel 1 Channel 2 LO1 Communication module 06 05 98 97 96 95 23 13 Stop OA1 – KM1 24 V c (1) The contacts are represented with controller powered up and not in a fault condition. Présentation : page 1/76 Characteristics : pages 1/94 and 1/95 References : page 1/77 Dimensions, mounting : page 1/78 1/79 References 1 TeSys motor starters - open version 1 TeSys U starter-controllers Parallel wiring module and pre-wired coil connection components Parallel type connection Architecture 1 1 Parallel wiring module LUF C00 4 2 Pre-wired coil connection LU9B N11C 3 Connection cable LU9 Rp with To PLC 2 2 1 1 5 3 one RJ45 connector at each end 4 Splitter box LU9 G02 for 8 motor starters with channel connections on the PLC side by 2 HE 10 connectors and on the starter-controller side by 8 RJ45 connectors. 5 Connection cable TSX CDPppp with one HE 10 connector at each end. 520836 Parallel wiring module 6 6 Outputs for starter commands RJ45 connector for connecting to splitter box 531810 7 7 The parallel wiring system makes it possible to connect starter-controllers to the PLC I/O modules quickly and without any need for tools. It replaces traditional screw terminal and single wire connections. It is used with the Telefast pre-wired system (1). The parallel wiring module provides the status and command information for each starter-controller. It must be used with an LUB 12 or LU2B 12BL power base and a c 24 V control unit LUCp ppBL. Splitter box LU9 G02 distributes information from the PLC I/O modules to each of the starter-controllers connected to it. This splitter box is optimised for use with card TSX DMZ28DTK. When used in conjunction with the Advantys STB distributed I/O solution, the TeSys U starter-controller is ideal in decentralised automation architectures (2). The use of dedicated parallel interface module STB EPI 2145 allows remote connection of 4 starter-controllers. 8 Each of the module’s 4 channels has: b 2 outputs: control of starter forward and reverse running, b 3 inputs: position of the rotary knob, fault indication and position of the poles. 10 Connection to the dedicated module is by means of the following cables: b RJ45 LU9Rpp, for lengths less than 3 metres, b 490 NTW 000pp, for lengths greater than 3 metres. 9 Description 11 12 12 8 Dedicated parallel interface module (STB EPI 2145) 9 Power base 10 c 24 V control unit (LUC B/D/C/M pp BL) 11 Parallel wiring module (LUF C00), 12 Options: add-on contact blocks, reverser blocks 1/80 Parallel wiring module Item Reference 1 LUF C00 Weight kg 0.045 (1) Please consult our "Power Control and connection components catalogue”. (2) Please consult our "Distributed I/O Advantys STB, the open device integration I/O system" catalogue. References 1 TeSys motor starters - open version 1 TeSys U starter-controllers Parallel wiring module and pre-wired coil connection components 520813 Pre-wired components simplify wiring and reduce wiring errors. Connection of communication module output terminals to the coil terminals By pre-wired connector or wire link. b Pre-wired connector: pre-wired coil connection The use of a power base without pre-wired connections is recommended. Description Pre-wired coil connection For use with power base LUB pp Item Reference 2 LU9B N11C LU2B pp 8 LU9M RC Weight kg 0.045 0.030 1 2 LUB + LUF C00 + LU9B b Wire link: Allows insertion, for example, of an emergency stop control or a voltage interface. This type of connection must be used for a reversing starter-controller assembled using an LU6M reverser block for separate mounting. When reverser block LU6M and the power base are mounted side-by-side, a pre-wired connector LU9M RC may be used. Connection of parallel wiring module to the PLC 561420 No tools are required to connect the parallel wiring module to the PLC. Connection is via a splitter box which allows up to 8 starter-controllers to be connected; a maximum of 4 reversing starters per splitter box is allowed. The splitter box requires a c 24 V power supply. Splitter block Connectors PLC side (16I/12O) 2 x HE 10 20-way Starter-controller side 8 x RJ45 Item Reference 4 LU9 G02 (1) Weight kg 0.260 Connection cables to the splitter box Connectors Item 2 x RJ45 connectors 3 1 Length m 0.3 1 3 Reference LU9 R03 LU9 R10 LU9 R30 Weight kg 0.045 0.065 0.125 Weight 8 Connection cables from splitter box to PLC Type of connection PLC side Splitter box side HE 10 20-way HE 10 20-way Gauge C.s.a. Length Reference AWG 22 mm 2 0.324 m 0.5 1 2 3 5 TSX CDP 053 TSX CDP 103 TSX CDP 203 TSX CDP 303 TSX CDP 503 kg 0.085 0.150 0.280 0.410 0.670 28 0.080 1 2 3 ABF H20 H100 ABF H20 H200 ABF H20 H300 0.080 0.140 0.210 22 0.324 3 5 TSX CDP 301 TSX CDP 501 0.400 0.660 LU2B + LUF C00 + LU9M Bare wires HE 10 20-way (1) Allows "run" and "fault" status of each starter-controller to be fed back to the PLC and transmits commands. Characteristics : pages 1/88 and 1/93 Schemes : pages 1/104 to 1/107 1/81 1 References 1 TeSys motor starters - open version 1 TeSys U starter-controllers As-Interface communication modules Series type connection Architecture 1 Communication modules ASI LUF C5 or ASI LUF C51 2 Tap-off XZ CG0142 3 Pre-wired coil connection LU9B N11C 1 1 3 2 c 24 V AS-Interface Information transmitted by the AS-Interface system AS-Interface profiles Data bits (command) 5 531118 4 Data bits (status) Bit value Command Command Command Command D0 D1 D2 D3 Bit value Status D0 Status D1 Status D2 Status D3 (I) (I) (I) (I) 7.D.F.0 profile and 7.A.7.E profile =0 =1 Stop forward Forward running Stop reverse Reverse running Not used Not used Not used Not used (O) (O) (O) (O) =0 Not ready or fault Stopped Not used Not used =1 Ready Running Not used Not used AS-Interface communication modules The AS-Interface communication modules make it easy to connect starter-controllers to the AS-Interface cabling system, and therefore allow remote control and command of these starter-controllers. 6 7 8 Green LED: AS-Interface voltage present Red LED: AS-Interface or module fault 6 Outputs for starter commands 7 Yellow connector for connection to the AS-Interface system 8 Black connector for connection to c 24 V auxiliary power supply 4 5 Module ASILUF C51 incorporates wide mounting rail. The various operating states of the modules (AS-Interface voltage present, communication fault, addressing fault,…) are indicated on the front panel by 2 LEDs (green 4 and red 5). Operation of the modules is continuously monitored by auto-testing, in a way that is totally transparent to the user. The incorporation of AS-Interface V.2.1 functions allows diagnostics to be performed on the modules, either remotely via the line or locally via the ASI TERV2 addressing terminal. The communication modules must be connected to a c 24 V auxiliary supply and must be used in conjunction with a c 24 V control unit, LUCp ppBL. The product is supplied with a yellow connector 6 for connection to the AS-Interface system, a black connector 7 for connection to the c 24 V auxiliary supply and a black connector 8 for connection of the outputs. Description Communication modules 1/82 Item Reference 1 ASI LUF C5 1 ASI LUF C51 Weight kg 0.065 0.065 References (continued) 1 TeSys motor starters - open version 1 TeSys U starter-controllers As-Interface communication modules 531121 Pre-wired components simplify wiring and reduce wiring errors. Connection of communication module output terminals to the coil terminals By pre-wired connector or wire link. b Pre-wired connector: pre-wired coil connection The use of a power base without pre-wired control circuit connections is recommended. 1 Description 3 LUB + ASILUF C5 + LU9B Pre-wired coil connection For use with power base LUB pp Item Reference 3 LU9B N11C LU2B pp 5 LU9M RC Weight kg 0.045 0.030 531122 b Wire link Allows insertion, for example, of an Emergency stop control or a voltage interface. This type of connection must be used for a reversing starter-controller assembled using an LU6M reverser block for separate mounting. When reverser block LU6M and the power base are mounted side-by-side, a pre-wired coil connection LU9M RC may be used. Connection of the communication module (1) Achieved by using a tap-off for connection to 2 ribbon cables: b 1 for AS-Interface (yellow). b 1 for separate c 24 V supply (black). 1 5 Description Tap-off Length m 2 Reference XZ CG0142 Weight kg 0.265 Consoles and cable adapters Description 520898 520899 LU2B + ASILUF C5 + LU9M Reference Addressing terminal Battery operated. Battery charger supplied AS-Interface V.1 and V.2.1 compatible Adjustment and diagnostics console Runs on LR6 batteries Allows addressing of AS-Interface V.2.1 interfaces and diagnostics Cable adapter For console XZ MC11 XZ MC11 Weight kg 0.550 ASI TERV2 0.500 XZ MG12 0.070 Software set-up ASI TERV2 561421 XZ MC11 AS-Interface configuration is carried out using PL7 Micro/Junior/Pro software. From the module declaration screen, it is possible to configure all the slave devices corresponding to all the AS-Interface I/O. Configuration is carried out by following the instructions on the screen. TeSys U user's manual (2) Application On CD-Rom Language Reference Weight kg 0.022 Multi-language LU9 CD1 (3) (1) Degree of protection IP 54. Connection by 4 x 0.34 mm2 wires. Black wire: + 24 V. White wire: 0 V. Blue wire: AS-Interface (–). Brown wire: AS-Interface (+). (2) The CD-Rom contains user's manuals for the AS-Interface and Modbus communication modules, multifunction control units and gateway modules, as well as the gateway programming software. (3) English, French, German, Italian, Spanish. Configuration example with Premium TSX SAY 1000 module 1/83 1 References 1 TeSys motor starters - open version TeSys U starter-controllers Modbus communication modules and pre-wired coil connection components Series type connection Architecture Star topology 1 Bus topology 4 6 2 2 2 2 1 1 1 1 To PLC 3 3 5 1 2 3 4 5 6 5 6 Communication modules LUL C031, LUL C032 or LUL C033 Pre-wired coil connection LU9B N11C Connection cable with one RJ45 connector at each end VW3 A8 306 Rpp Modbus hub LU9 GC3 with channel connections to PLC and to starter-controller with RJ45 connectors, T-junction VW3 A8 306 TFpp LIne terminator VW3 A8 306 R Information carried by the bus Depends on the type of control unit used. Control unit Starter status (ready, running, fault) Alarms (overcurrent, ...) Thermal overload alarm Remote reset via the bus Indication of motor load Fault signalling and differentiation Remote programming and monitoring of all functions "Log" function "Monitoring" function Start and Stop commands Functions performed Standard Advanced Multifunction For more detailed information, please refer to User's Manual LU9 CD1, see page opposite. Modbus communication modules compatibility With starter-controllers and controllers Starter-controllers Controller LUB pp / LU2Bp2 LUT M ppBL Association possible. LUL C031 LUL C032 LUL C033 LUL C031 V2.3 (1) Yes Yes Yes Yes Yes Yes LUL C032 V1.1 (1) No No No No No No LUL C033 V2.2 (1) Yes Yes No Yes No Yes With power bases Software versions of control units LUCA ppBL LUCB ppBL LUCM ppBL (1) And higher versions. Association not permitted. 1/84 – – V1.04 V1.05 V1.06 V1.10 (1) 1 References 1 TeSys motor starters - open version 1 TeSys U starter-controllers Modbus communication modules and pre-wired coil connection components Modbus communication modules compatibility (continued) With controller bases, version 1.200 (1) Software versions of control units LUL C032, LUL C033 535176 535175 LUL C031 LUCB TppBL – LUCM TppBL V2.11 (1) (1) And higher versions. Association not permitted. LUL C031 V2.3 (1) No No LUL C032 V1.1 Yes No LUL C033 V2.1 (1) Yes Yes V1.2 (1) Yes Yes Modbus communication modules Communication modules LUL C031, LUL C032 and LUL C033 enable the TeSys U starter-controller to be connected to the Modbus network. They must have a c 24 V supply and must be used in conjunction with a c 24 V control unit, LUCp ppBL. They incorporate a 0.5 A, c 24 V discrete output for local command requirements. Module LUL C032 and LUL C033 also have two configurable discrete inputs. Description Communication modules 7 8 9 10 11 520810 12 Module status signalling LED 24 V supply connection RJ45 connector for RS485 Modbus link 2 discrete inputs 1 discrete output Outputs for starter commands Item Reference 1 1 1 LUL C031 LUL C032 LUL C033 Weight kg 0.080 0.080 0.080 Pre-wired components simplify wiring and reduce wiring errors. Connection of communication module output terminals to the coil terminals By pre-wired connector or wire link. b Pre-wired connector: pre-wired coil connection The use of a power base without pre-wired control circuit connections is recommended. Description Pre-wired coil connection For use with power base LUB pp Item Reference 2 LU9B N11C LU2B pp 7 LU9M RC Weight kg 0.045 0.030 b Wire link: Allows insertion, for example, of an emergency stop control or a voltage interface. This type of connection must be used for a reversing starter-controller assembled using an LU6M reverser block for separate mounting. When reverser block LU6M and the power base are mounted side-by-side, a pre-wired connector LU9M RC may be used. 1 2 Connection of communication modules on the serial bus Achieved either by means of a Modbus hub or using T-junctions. LUB + LUL C03p + LU9B Description 520811 Modbus hub 8 slaves Cables fitted with 2 x RJ45 connectors T-junctions (1) RS 485 line terminator Length m – Item Reference 4 LU9 GC3 0.3 1 3 0.3 1 – 3 3 3 5 5 6 VW3 VW3 VW3 VW3 VW3 VW3 A8 A8 A8 A8 A8 A8 306 306 306 306 306 306 Weight kg 0.260 R03 R10 R30 TF03 TF10 R 0.045 0.065 0.125 0.032 0.032 0.012 TeSys U user's manual (2) Application Language Reference Multi-language (3) LU9 CD1 1 On CD-Rom 7 Weight kg 0.022 (1) Fitted with 2 RJ45 female connectors (bus side) and a 0.3 m or 1 m length cable supplied with an RJ45 male connector (station side). (2) The CD-Rom contains user's manuals for the AS-Interface and Modbus communication modules, multifunction control units and gateway modules, as well as the gateway programming software. (3) English, French, German, Italian, Spanish. LU2B + LUL C03p + LU9M 1/85 1 TeSys motor starters - open version Presentation, description, setting-up TeSys U starter-controllers Communication gateways LUF P 1 Presentation 1 Communication gateways LUF P allow connection between Modbus and field buses such as Fipio, Profibus DP or DeviceNet. After configuration, these gateways manage information which can be accessed by the Modbus bus and make this information available for read/write functions (command, monitoring, configuration and adjustment) on the field buses. An LUF P communication gateway consists of a box which can be clipped onto a 35 mm omega rail, allowing connection of up to 8 Slaves connected on the Modbus bus. Example of architecture Configuration of gateway by PC TeSys U starter-controllers LUF P 561511 Fipio Profibus DP DeviceNet (1) Modbus 1 ATS 48 ATV 31 (1) Connection kit for PowerSuite software workshop. Description Front panel of the product 1 LED indicating : - communication status of the Modbus buses, - gateway status, - communication status of the Fipio, Profibus DP or DeviceNet bus. 2 Connectors for connection to Fipio, Profibus DP or DeviceNet buses. 2 561512 Underside of product 3 RJ45 connector for connection on the Modbus bus 4 RJ45 connector for link to a PC 5 c 24 V power supply 3 Software set-up 4 For the Fipio bus, software set-up of the gateway is performed using either PL7 Micro/Junior/Pro software or ABC Configurator software. For the Profibus DP and DeviceNet buses, software set-up is performed using ABC Configurator. This software is included: b in the PowerSuite software workshop for PC (see page 1/74), b in the TeSys U user's manual. 5 Characteristics, references: page 1/87 1/86 Dimensions: page 1/87 1 Characteristics, references, dimensions TeSys motor starters - open version 1 TeSys U starter-controllers Communication gateways LUF P 1 Characteristics Bus type Environment Ambient air temperature Degree of protection Electromagnetic compatibility Conforming to IEC 60664 Around the device Emission Immunity Number of Modbus slaves which can be connected Connection Modbus To a PC Field bus Supply Consumption Max. Typical Indication/diagnostics Services Profile Command Monitoring Configuration and adjustment Fipio Profibus DP DeviceNet Degree of pollution: 2 °C + 5…+ 50 IP 20 Conforming to IEC 50081-2: 1993 Conforming to IEC 61000-6-2: 1999 y8 By RJ45 connector conforming to Schneider Electric RS485 standard By RJ45 connector, with PowerSuite connection kit By SUB D9 female By SUB D9 female By 5-way removable connector connector screw connector V External supply, c 24 ± 10 % mA 280 mA 100 By LED on front panel FED C32 or FED C32P – – 26 configurable words (1) 122 configurable words 256 configurable words 26 configurable words (1) 122 configurable words 256 configurable words By gateway mini messaging facility (PKW) (1) If the gateway is configured using PL7 and not ABC Configurator, the I/O capacity is limited to a total of 26 words. References Description Communication gateways For use with With bus type Reference TeSys U starter-controllers, Altistart 48, Altivar 31 Fipio/Modbus Profibus DP/Modbus DeviceNet/Modbus LUF P1 LUF P7 LUF P9 For use with Connectors Reference Weight kg 0.245 0.245 0.245 Connection accessories 822631 Description Connection cables Modbus Length m 3 Fipio 822713 TSX FP ACC 12 Connectors Profibus mid line Profibus line end 490 NAD 911 03 Weight kg VW3 A8 306 D30 0.150 0.3 1 3 – 1 RJ45 type connector and one end with stripped wires 2 RJ45 type connectors 2 RJ45 type connectors 2 RJ45 type connectors 1 SUB-D 9 male connector VW3 A8 306 R03 VW3 A8 306 R10 VW3 A8 306 R30 TSX FP ACC12 – 1 SUB-D 9 male connector 490 NAD 911 04 – – 1 SUB-D 9 male connector 490 NAD 911 03 – 0.050 0.050 0.150 0.040 Documentation Description User's manual for TeSys U range Medium Language Reference Weight kg 0.022 CD-Rom Multilingual: English, French, German, Italian, LU9 CD1 (2) Spanish (2) This CD-Rom contains user's manuals for AS-Interface and Modbus communication modules, multifunction control units and gateways, as well as for the gateway programming software, ABC Configurator. = 120 = Dimensions 75 Presentation, description: page 1/86 27 Setting-up: page 1/86 1/87 1 Characteristics 1 TeSys motor starters - open version TeSys U starter-controllers Environment 1 Product certifications UL, CSA Pending: BV, GL, LROS, DNV, ABS, RINA Conforming to standards V IEC/EN 60947-6-2, CSA C22-2 N°14, Type E UL 508 type E: with phase barrier LU9 SP0 690 V 600 kV 6 V Between the control or auxiliary circuit and the main circuit: 400 Between the control and auxiliary circuits: 400 Rated insulation voltage (Ui) Rated impulse withstand voltage (Uimp) Safety separation of circuits SELV Conforming to IEC/EN 60947-1, overvoltage category III, degree of pollution: 3 Conforming to UL508, CSA C22-2 n°14 Conforming to IEC/EN 60947-6-2 Conforming to IEC/EN 60947-1 appendix N Degree of protection Front panel outside connection Conforming to IEC/EN 60947-1 zone (protection against Front panel and wired terminals direct finger contact) Other faces Protective treatment Ambient air temperature around the device Conforming to IEC/EN 60068 Conforming to IEC/EN 60068-2-30 Conforming to IEC/EN 60068-2-11 Storage Operation IP 20 IP 20 “TH” Cycles 12 h 48 °C - 40…+ 85 °C Power bases and standard and advanced control units: - 25… + 70. (At temperatures above 60°C and up to 70°C, for Ie = 32 A, leave a minimum gap of 9 mm between products). Power bases and multifunction control units: - 25…+ 60. (At temperatures above 45 °C, leave a minimum gap of 9 mm between products. At temperatures above 55 °C up to 60 °C, leave a gap of 20 mm between products.) m Maximum operating altitude Operating positions IP 40 2000 In relation to normal vertical mounting plane 30˚ 90˚ 30˚ Flame resistance Conforming to UL 94 Conforming to IEC/EN 60695-2-12 °C °C V2 960 (parts supporting live components) 650 Environmental restrictions Shock resistance 1/2 sine wave = 11 ms Conforming to IEC/EN60068-2-27 (1) Cadmium and silicone-free, recyclable Power poles open: 10 gn Power poles closed: 15 gn Vibration resistance 5…300 Hz Conforming to IEC/EN 60068-2-6 (1) Power poles open: 2 gn Power poles closed: 4 gn Immunity to electrostatic discharge Conforming to IEC/EN 61000-4-2 kV kV In open air: 8 - Level 3 On contact: 8 - Level 4 Immunity to radiated highfrequency disturbance Immunity to fast transient currents Conforming to IEC/EN 61000-4-3 V/m 10 - Level 3 Conforming to IEC/EN 61000-4-4 kV kV All circuits except for serial link: 4 - Level 4 Serial link: 2 - Level 3 Immunity to dissipated shock waves Conforming to IEC/EN 60947-6-2 kV Uc a 24…240 V, Uc c 48…220 V Uc = 24 V c Immunity to conducted high- Conforming to IEC/EN 61000-4-6 V frequency disturbance (1) Without modifying the contact states, in the most unfavourable direction. References : pages 1/64 to 1/81 1/88 Dimensions : pages 1/102 and 1/103 Common mode 2 Not applicable 10 Schemes : pages 1/104 to 1/107 Serial mode 1 90˚ 1 Characteristics 1 TeSys motor starters - open version 1 TeSys U starter-controllers Power bases and control units Power base and control unit type LUB 12 + LUCA or LUCB or LUCC or LUCD LUB 32 + LUCA or LUCB or LUCC or LUCD LUB 12 + LUCM LUB 32 + LUCM LU2M LU6M 1 Power circuit connection characteristics Connection to Ø 4 mm screw clamp terminals Flexible cable without cable end Flexible cable with cable end Solid cable without cable end 1 conductor 2 conductors 1 conductor 2 conductors 1 conductor 2 conductors Screwdriver Tightening torque mm 2 mm 2 mm 2 mm 2 mm 2 mm 2 N.m 2.5…10 2.5…10 1.5…6 1.5…6 1…6 1…6 1…6 1…6 1…10 1…10 1…6 1…6 Philips n° 2 or flat screwdriver: Ø 6 mm 1.9…2.5 1.9…2.5 2.5…10 1.5…6 1…6 1…6 1…10 1…6 2.5…10 1.5…6 1…6 1…6 1…10 1…6 2.5…10 1.5…6 1…6 1…6 1…10 1…6 1.9…2.5 1.9…2.5 1.9…2.5 0.75…1.5 0.75…1.5 0.75…1.5 0.75…1.5 0.34…1.5 0.34…1.5 0.34…1.5 0.34…1.5 0.75…1.5 0.75…1.5 0.75…1.5 0.75…1.5 Philips n° 1 or flat screwdriver: Ø 5 mm 0.8…1.2 0.8…1.2 0.75…1.5 0.75…1.5 0.34…1.5 0.34…1.5 0.75…1.5 0.75…1.5 0.75…1.5 0.75…1.5 0.34…1.5 0.34…1.5 0.75…1.5 0.75…1.5 0.75…1.5 0.75…1.5 0.34…1.5 0.34…1.5 0.75…1.5 0.75…1.5 0.8…1.2 0.8…1.2 0.8…1.2 24…240 24…240 24…220 24…220 20…27 20…27 20…26.5 20…26.5 a 38.5…72. c 38.5…93 a 88…264 a 88…264 c 88…242 c 88…242 14.5 14.5 14.5 14.5 29 29 55 55 130 220 140 220 280 280 280 280 60 80 70 90 35 45 35 25 2 3 24 V : 70 ; 48 V : 60 ; u 72 V : 50 35 35 3 3 At least 70 % of Uc for 500 ms 15 15 3600 3600 – 24 20…28 – – – – 14.5 – – – 150 – – – 70 – – – 1.7 75 35 3 – 24 20…28 – – – – 14.5 – – – 200 – – – 75 – – – 1.8 65 35 3 15 3600 15 3600 – – – – – – – – – – – 120 2360 2300 1000 120 (2) (2) (2) – – – – – – – Control circuit connection characteristics Connection to Ø 3 mm screw clamp terminals Flexible cable without cable end Flexible cable with cable end Solid cable without cable end 1 conductor 2 conductors 1 conductor 2 conductors 1 conductor 2 conductors Screwdriver Tightening torque mm 2 mm 2 mm 2 mm 2 mm 2 mm 2 N.m Control circuit characteristics Rated voltage of control circuit Voltage limits Operation Drop-out Typical consumption I max while closing I rms sealed Heat dissipation Operating time a 50/60 Hz c c 24 V (1) a 24 V a or c 48…72 V a 110…240 V c 110…220 V c 24 V a 24 V a or c 48…72 V a 110…240 V, c 110…220 V c 24 V a 24 V a or c 48…72 V a 110…240 V, c 110…220 V c 24 V a 24 V a or c 48…72 V a 110…240 V, c 110…220 V Closing Opening Resistance to micro-breaks Resistance to voltage drops IEC/EN 61000-4-11 Mechanical durability In millions of operating cycles Maximum operating rate In operating cycles per hour V V V V V V V V V V V mA mA mA mA mA mA mA mA W ms ms ms Main pole characteristics Number of poles Isolation function To IEC/EN 60947-1 3 3 3 3 Yes Yes Yes Yes 1 padlock with Ø 6.9 mm shank A 12 32 12 32 Rated thermal current θ y 70°C: 12A θ y 70°C: 32A θ y 55°C: 12A θ y 55°C: 32A Rated operating current To IEC/ In cat. AC-41 (Ue y 440V) EN 60947-6-2 In cat. AC-43 θ y 70°C: 12A θ y 70°C: 32A θ y 55°C: 12A θ y 55°C 32A V 690 (3) 690 (3) 690 (3) 690 (3) Rated operating voltage Hz 40…60 40…60 40…60 40…60 Frequency limits Of the operating current A 3 6 9 12 18 25 32 Power dissipated Operating current in the power circuits 0.1 0.3 0.6 1.1 2.4 4.6 7.5 Power dissipated in all three poles W V 230 440 500 690 Rated breaking capacity on short-circuit kA 50 50 10 4 ms 2 2 2 Total breaking time kA²s 90 120 90 120 Thermal stress limit With Isc max on 440 V (1) Voltage with maximum ripple of ± 10 %. (2) No consumption sealed. (3) For 690 V, use phase barrier LU9 SP0. Possible Padlocking – – – – – – – – – – – – – – 1/89 Characteristics TeSys motor starters - open version 1 TeSys U starter-controllers Reversing power bases and auxiliary contacts Specific characteristics of power bases LU2B and reverser blocks LU2M or LU6M Maximum operating time a 50/60 Hz ms ms c ms Without change of direction ms With change of direction 25 15 75 150 General characteristics of auxiliary contacts Conventional thermal For ambient temperature θ < 70 °C current (Ith) Frequency of the operating current U min Minimum switching capacity λ = 10 -8 I min Short-circuit Conforming to IEC/EN 60947-5-1 protection Short-time rating Permissible for 1s 500 ms 100 ms Insulation resistance Non-overlap time Guaranteed between N/C and N/O contacts A 5 Hz V mA A Up to 400 17 5 gG fuse: 4 A A A mΩ ms 30 40 50 10 2 (on energisation and on de-energisation) Specific characteristics of auxiliary contacts built-into the power base Linked contacts Mirror contact Conforming to IEC/EN 60947-4-1 Conforming to draft standard IEC/EN 60947-1 Rated operating voltage (Ue) Rated insulation Conforming to IEC/EN 60947-5-1 voltage (Ui) Conforming to UL, CSA V V V Each power base has 1 N/O contact and 1 N/C contact which are mechanically linked The N/C contact fitted in each power base reliably represents the state of the power contacts (safety scheme) Up to a 690; c 250 690 600 Specific characteristics of auxiliary contacts in modules LUF N, of auxiliary contacts LUA1 and of reverser blocks LU2M and LU6M Rated operating voltage (Ue) Rated insulation Conforming to IEC/EN 60947-5-1 voltage (Ui) Conforming to UL, CSA V V V Up to a 250; c 250 250 250 Operational power of contacts Conforming to IEC/EN 60947-5-1 a.c. supply, categories AC-14 and AC-15 Electrical durability (valid for up to 3600 operating cycles/hour) on an inductive load such as the coil of an electromagnet: making current (cos ϕ 0.7) = 10 times the power broken (cos ϕ = 0.4). 1 million operating cycles 3 million operating cycles 10 million operating cycles d.c. supply, category DC-13 Electrical durability (valid for up to 1200 operating cycles/hour) on an inductive load such as the coil of an electromagnet, without economy resistor, the time constant increasing with the load. V VA 24 60 48 120 115 280 230 560 400 960 440 600 1050 1440 V W 24 120 48 90 125 75 250 68 VA 16 32 80 160 280 300 420 W 70 50 38 33 VA 4 8 20 40 70 80 100 W 25 18 14 12 1 8 7 6 5 4 3 Millions of operating cycles Millions of operating cycles 1 Duration of inrush phase 2 1 0,8 0,7 0,6 0,5 0,4 0,3 References : page 1/64 1/90 2 24 V 48 V 125 V 250 V 1 0,8 0,7 0,6 0,5 0,4 0,3 0,2 0,2 0,1 0,1 1 8 7 6 5 4 3 0,2 0,3 0,4 0,6 0,8 1 0,5 0,7 0,9 2 3 6 8 10 5 7 9 Current broken in A Dimensions : pages 1/102 and 1/103 4 0,1 0,1 Schemes : pages 1/104 to 1/107 0,2 0,3 0,4 0,6 0,8 1 0,5 0,7 0,9 2 3 4 6 8 10 5 7 9 Current broken in A 1 Characteristics 1 TeSys motor starters - open version 1 TeSys U starter-controllers Control units Characteristics of standard control units LUCA Protection Overload protection Short-circuit protection Motor type Conforming to standard Tripping class conforming to UL 508, IEC/EN 60947-6-2 Frequency limits of the operating current Temperature compensation Protection against phase imbalance Tripping threshold Tripping tolerance 3-phase IEC/EN 60947-6-2, UL 508, CSA C22-2 n°14 10 Hz °C 1 40…60 - 25…+ 70 With 14.2 x Ir (setting current) ± 20 % Characteristics of advanced control units LUCB, LUCC and LUCD Control unit type Protection Motor type Conforming to standard Overload protection Short-circuit protection Tripping class conforming to UL 508, IEC/EN 60947-6-2 Frequency limits of the operating current Temperature compensation Protection against phase imbalance Tripping threshold Tripping tolerance LUCB LUCC LUCD 3-phase Single-phase 3-phase IEC/EN 60947-6-2, UL 508, IEC/EN 60947-6-2, UL 508, IEC/EN 60947-6-2, UL 508, CSA C22-2 n°14 CSA C22-2 n°14 CSA C22-2 n°14 10 10 20 Hz °C 40…60 - 25…+ 70 Yes 14.2 x Ir max. ± 20 % 40…60 - 25…+ 55 – 14.2 x Ir max. ± 20 % 40…60 - 25…+ 70 Yes 14.2 x Ir max. ± 20 % Characteristics of multifunction control units LUCM Protection Overload protection Communication interface for terminal on enclosure door Display Auxiliary supply Motor type Conforming to standard Tripping class conforming to UL 508, IEC/EN 60947-6-2 Frequency limits of the operating current Temperature compensation Physical interface Connector Protocol Maximum transmission speed Maximum return time Type Language version Accuracy Resolution External type Heat dissipation Selectable: single-phase or 3-phase IEC/EN 60947-6-2, UL 508 5, 10, 15, 20, 25, 30 (selectable) Hz °C bit/s ms V W 40…60 - 25…+ 55 RS 485 multi-drop RJ45 on front panel Modbus RTU 19 200 (self-configuration up to this value) 200 LCD, 2 lines of 12 characters Multilanguage (English, French, German, Italian, Spanish) ±5% 1 % of Ir c 24, with maximum ripple of ± 10 %. 0.8 Configuration table for protection devices and alarms on multifunction control units LUCM Tripping Alarm Overcurrent Overload Adjustment of tripping threshold Factory setting Factory setting Range Default value Activated (1) – 3…17 Ir 14.2 Activated (1) Activated 0.15…32 A (2) Ir min Adjustment of time before tripping Range Default value – – Class: 5…30 5 Earth fault Phase imbalance Torque limitation No-load running Long starting times Activated Activated Deactivated Deactivated Deactivated 0.1…1.2 s 0.2…20 s 1…30 s 1…200 s 1…200 s Activated Activated Deactivated Deactivated Deactivated 0.2…5 Ir min 10…30 % 1…8 Ir 0.3…1 Ir 1…8 Ir 0.3 Ir min 10 % 2 Ir 0.5 Ir Ir 0.1 s 5s 5s 10 s 10 s Adjustment of alarm threshold Range Default value – – 10…100 % of 85 % the thermal state 0.2…5 Ir min 0.3 Ir min 10…30 % 10 % 1…8 Ir 2 Ir 0.3…1 Ir 0.5 Ir 1…8 Ir Ir Configuration of additional functions on multifunction control units LUCM Reset Time before reset Type of load Language Display Factory setting Manual 120 s 3-phase motor Self-cooled English Average current Setting range Manual, automatic or remote 1…1000 s 3-phase motor, single-phase motor Self-cooled, force cooled English, French, German, Italian, Spanish Average current, thermal state of motor, current in phase 1 / 2 / 3, earth leakage current, phase imbalance, cause of last 5 faults (1) This function cannot be deactivated. (2) The setting range depends on the rating of the control unit used. References : pages 1/69 to 1/71 Dimensions : pages 1/102 and 1/103 Schemes : pages 1/104 to 1/107 1/91 Characteristics 1 TeSys motor starters - open version TeSys U starter-controllers Limiter-disconnector, current limiter, thermal overload alarm function module and thermal overload fault signalling modules Characteristics of limiter-disconnector LUA LB1 1 Rated insulation voltage (Ui) conforming to standard IEC/EN 60947-1 Conventional thermal current (Ith) conforming to standard IEC/EN 60947-1 Operating threshold Breaking capacity V 690 A 32 I rms kA V kA 50 440 690 130 70 Directly on the upstream terminals of the starter-controller 1 2 1 2 1 2 mm2 mm2 mm2 mm2 mm2 mm2 1.5…10 1.5...6 1…10 1…6 1...6 1...6 Phillips n°2 or flat screwdriver Ø 6 mm 1.9…2.5 Mounting Connection Solid cable Flexible cable without cable end Flexible cable with cable end conductor conductors conductor conductors conductor conductors Screwdriver Tightening torque N.m Characteristics of current limiter LA9 LB920 Rated insulation voltage (Ui) conforming to standard IEC/EN 60947-1 Conventional thermal current (Ith) conforming to standard IEC/EN 60947-1 Operating threshold Breaking capacity Mounting Connection Solid cable Flexible cable without cable end Flexible cable with cable end I rms 1 2 1 2 1 2 conductor conductors conductor conductors conductor conductors Screwdriver Tightening torque V 690 A 63 A V kA 1000 440 100 Separate mm2 1.5…25 mm2 mm2 mm2 mm2 mm2 1.5...10 1.5…25 2.5…10 1.5…16 1.5…4 Phillips n°2 or flat screwdriver Ø 6 mm 2.2 N.m 690 35 Characteristics of thermal overload alarm function module LUF W10 Activation threshold Hysteresis between activation and switching off Indication Supply Discrete output characteristics Type AC-15 DC-13 A Conventional thermal current For ambient (Ith) temperature θ < 70 °C Short-circuit protection Conforming to A IEC/EN 60947-5-1 Fixed at 88% of the thermal tripping state 5% By LED on front panel Powered by the control unit N/O contact 230 V max; 400 VA 100 000 operating cycles 24 V; 50 W 100 000 operating cycles 2 gG fuse: 2 Characteristics of thermal overload fault signalling and reset modules Module type Fault signalling External power supply Module consumption V mA Discrete outputs Type AC-15 DC-13 Conventional thermal current (Ith) Short-circuit protection For ambient A temperature θ < 70 °C A Conforming to IEC/EN 60947-5-1 Conductor c.s.a. mm2 m Length Reset input References : page 1/67 1/92 Dimensions : pages 1/102 and 1/103 LUF DH11 LUF DA01 By LED on front panel a/c 24…240 7 at c 24 1.1 at a 240 1 N/C + 1 N/O 1 N/C 230 V max; 400 VA 100 000 operating cycles 24 V; 50 W 100 000 operating cycles 2 gG fuse: 2 0.2 min 500 (R = 50 Ω , L = 52.8 mH, Cp = 93 pF) Schemes : pages 1/104 to 1/107 LUF DA10 1 N/O 1 Characteristics 1 TeSys motor starters - open version 1 TeSys U starter-controllers Function modules and communication modules Characteristics of motor load indication function module LUF V2 Analogue output Signal delivered Load impedance Signal characteristics with advanced control unit Signal characteristics with multifunction control unit Minimum Maximum Typical Precision kΩ Ω Ω 4 - 20 mA Value of I average/Ir ratio within the range of 0 to 2 for LUCB and LUCD Value of I average/Ir ratio within the range of 0 to 3 for LUCC – 500 100 ±6% 1 ± 10 % 1 % of Ir External c 24 V Precision Resolution Supply Characteristics of AS-Interface communication modules ASILUF C5 and ASILUF C51 Modules type Product certification AS-Interface profile Ambient air temperature Cycle time AS-Interface supply Current consumption °C ms V By the AS-Interface system mA mA On 24 V supply for the outputs mA V Auxiliary supply Number of outputs Switching capacity of the solid state outputs Indication/diagnostics ASILUF C5 ASILUF C51 AS-Interface V2.1 n° 52901 AS-Interface V2.1 n° 52303 7.D.F.0 7.A.7.E Operation - 25…+ 70 5 10 29.5...31.5 Normal operation: 25 Fault condition: 30 200 c 24 ± 30 % 2 dedicated to starter-controller coil operation 0.5 A/24 V (outputs protected against short-circuits) By 2 LEDs on front panel Characteristics of Modbus communication modules LUL C03p Module type Physical interface Connector Protocol Maximum transmission speed Maximum return time Addressing Ambient air temperature Logic inputs Nominal input values Response time bit/s ms °C Number Supply Input current Voltage Current Change to state 1 Change to state 0 V mA V mA ms ms Input type Solid state outputs Number Supply Max. current Protection gI fuse Current consumption On 24 V supply for the outputs Switching capacity of the solid state outputs Indication/diagnostics V mA A mA LUL C031 LUL C032 and LUL C033 RS 485 multi-drop RJ45 on front panel Modbus RTU 19 200 (self-configuration up to this value) 30 By switches: from 0...31 Operation - 25…+ 55 – 2 (to be assigned according to configuration) – c 24 – 7 c 24 (positive logic) 7 10 (± 30 %) 10 (± 30 %) Resistive 3, of which 2 dedicated to starter-controller coil operation c 24 500 1 200 0.5 A/24 V By 3 LEDs on front panel Connection characteristics Module type LUF W10, LUF V2 DH11, DA01 and DA10 Connectors Flexible cable without cable end Flexible cable Without insulated with cable end ferrule With insulated ferrule Solid cable without cable end Conductor size Tightening torque Flat screwdriver Pitch 1 conductor 2 identical conductors 1 conductor 2 identical conductors 1 conductor 2 identical conductors (Use a double cable end) 1 conductor 2 identical conductors 1 conductor mm² mm² mm² mm² mm² mm² mm² mm² N.m mm 5.08 0.2…1.5 0.2…1 0.25…1.5 0.25…1 0.25…1.5 0.5…1 3.81 0.14…1 0.14…0.75 0.25…1 0.25…0.34 0.25…0.5 0.5 ASILUF C5 and ASILUF C51 Inputs and Outputs 24 V auxiliary 5.08 3.81 0.2…1.5 0.14…1 0.2…1 0.14…0.75 0.25…1.5 0.25…1 0.25…1 0.25…0.34 0.25…1.5 0.25…0.5 0.5…1 0.5 0.2…1.5 0.2…1 AWG 24 to AWG 16 0.5…0.6 3.5 0.14…1 0.14…0.5 AWG 26 to AWG 16 0.22…0.25 2.5 0.2…1.5 0.2…1 AWG 24 to AWG 16 0.5…0.6 3.5 0.14…1 0.14…0.5 AWG 26 to AWG 16 0.22…0.25 2.5 LUL C031 LUL C032 LUL C033 LUFC 00 3.81 0.14…1 0.14…0.75 0.25…1 0.25…0.34 0.25…0.5 0.5 3.81 0.14…1 0.14…0.75 0.25…1 0.25…0.34 0.25…0.5 0.5 0.14…1 0.14…0.5 AWG 26 to AWG 16 0.22…0.25 2.5 0.14…1 0.14…0.5 AWG 26 to AWG 16 0.22…0.25 2.5 1/93 Characteristics 1 TeSys control components TeSys U controllers Control bases and control units Environment 1 Control base and control unit type LUT M + LUCB T1BL or LUCD T1BL LUT M + LUCM T1BL or LUL C without LUL C UL, CSA Pending: BV, GL, LROS, DNV, PTB IEC/EN 60947-4-1, UL 508, CSA C22-2 N°14 Product certifications Conforming to standards V Rated insulation voltage Conforming to IEC/EN 60947-1, of the outputs overvoltage category III, (Ui) degree of pollution: 3 Conforming to UL508, CSA C22-2 V n°14 Rated impulse withstand Conforming to IEC/EN 60947-4-1 kV voltage of the outputs (Uimp) Degree of protection Front panel (outside connection zone) To IEC/EN 60947-1 Front panel and wired terminals (protection against Other faces direct finger contact) 250 Protective treatment “TH” Conforming to IEC/EN 60068 Conforming to IEC/EN 60068-2-30 Conforming to IEC/EN 60068-2-11 Ambient air temperature Storage around the device Operation Maximum operating altitude Operating positions Without derating Cycles h °C °C m 250 4 IP 40 IP 20 IP 20 12 48 - 40…+ 85 - 25…+ 70 2000 In relation to normal vertical mounting plane - 25…+ 60 30˚ 90˚ 90˚ 30˚ Flame resistance Conforming to UL 94 Conforming to IEC/EN 60695-2-12 Shock resistance 1/2 sine wave = 11 ms Vibration resistance 5…300 Hz Immunity to electrostatic discharge Conforming to IEC/EN60068-2-27 (1) Conforming to IEC/EN 60068-2-6 (1) Conforming to IEC/EN 61000-4-2 Immunity to radiated fields Immunity to fast transient currents °C °C V2 960 (parts supporting live components) 650 15 gn 4 gn kV kV In open air: 8 - Level 3 On contact: 6 - Level 3 Conforming to IEC/EN 61000-4-3 V/m 10 - Level 3 Conforming to IEC/EN 61000-4-4 kV kV CT outputs and inputs: 4 - Level 4 Inputs and supply: 2 - Level 3 V 10 Immunity to radio Conforming to IEC/EN 61000-4-6 electrical fields Control base and control unit relays Immunity to dissipated Conforming to IEC/EN 60947-4-1 shock waves Output relays / power line Inputs Serial communication kV kV kV Common mode Serial mode 4 2 2 2 1 – (1) Without modifying the contact states, in the most unfavourable direction. References : page 1/77 1/94 Dimensions : page 1/77 Schemes : page 1/77 1 Characteristics 1 TeSys control components 1 TeSys U controllers Control bases and control units Control supply characteristics Operating voltage V c 20.4…28.8 Power consumption W 2 max Associated protection A gG fuse, 0.5 Pitch 1 conductor 2 identical conductors mm mm 2 mm 2 5 0.2…2.5 0.2…1.5 1 conductor 2 identical conductors 1 conductor 2 identical conductors (1) 1 conductor 2 identical conductors 1 conductor mm 2 mm 2 0.25…2.5 0.25…1 mm 2 mm 2 0.25…2.5 0.5…1.5 mm 2 mm 2 0.2…2.5 0.2…1 N.m mm AWG 24 to AWG 12 0.5…0.6 3 V c 24 Connection Connectors Flexible cable without cable end Flexible cable with cable end Without insulated ferrule With insulated ferrule Solid cable without cable end Conductor size Tightening torque Flat screwdriver 1 Input characteristics Operating voltage Logic state 1: I u 6 mA - 16 V Logic state 0: I y 1.5 mA - 5 V Logic inputs Discrete output characteristics Control base type Type LUT M10BL Single break volt-free contacts LUT M20BL C 300 24 V/5 A B 300 24 V/5 A Load a.c. supply d.c. supply Permissible power in cat. AC-15 For 500 000 operating cycles VA 180 500 Permissible power in cat. DC-13 For 500 000 operating cycles W 30 30 A gG fuse, 4 gG fuse, 4 Control voltage c 24 V: LP1K, LC1 D09…D95. Control voltage a 100…240 V: LC1K, LC1D, LC1 F185…F500 Associated protection For use in association with contactor (2) Control voltage c 24…240 V: LC1K, LC1D. Characteristics of external current transformers Precision Class 5P Precision limit factor Maximum operating temperature °C 10 70 Transformer ratio Hole diameter Maximum wire c.s.a. mm mm 2 30/1 28 30 x 10 50/1 22 30 x 10 100/1 35 40 x 10 200/1 32 65 x 32 400/1 – 38 x 127 800/1 – 53 x 127 (1) Use a double cable end. (2) For other combinations, use an intermediate relay between the output of controller LUTM and the contactor coil. References : page 1/77 Dimensions : page 1/77 Schemes : page 1/77 1/95 Curves 1 TeSys motor starters - open version TeSys U starter-controllers Tripping curves for control units LUCA, LUCB, LUCD Time (s) Average operating times at 20 °C according to multiples of the setting current, tolerance : ± 20 %. 1000 1 100 2 3 10 1 0,1 1 2 3 4 5 6 7 8 10 12 14 20 30 x the setting current (Ir) 1 LUCD, 3 poles from cold state, class 20. 2 LUCA, LUCB, 3 poles from cold state, class 10. 3 LUCA, LUCB, LUCD, 3 poles from hot state. Tripping curves for control units LUCC Average operating times at 20 °C according to multiples of the setting current, tolerance : ± 20 %. Time (s) 1 1000 1 100 2 10 1 0,1 1 2 1 LUCC, single-phase, cold state. 2 LUCC, single-phase, hot state. References : page 1/69 1/96 3 4 5 6 7 8 10 12 14 20 30 x the setting current (Ir) 1 Curves (continued) 1 TeSys motor starters - open version 1 TeSys U starter-controllers Tripping curves for control units LUCM Cold state curves 1 Time (s) Average operating times at 20 °C according to multiples of the setting current, tolerance : ± 20 %. 10000 1000 100 10 Class 30 Class 25 Class 20 Class 15 Class 10 Class 5 1 0,1 1 2 3 4 5 6 7 8 9 10 12 11 13 14 16 18 20 15 17 19 30 x the setting current (Ir) References : page 1/70 1/97 Curves (continued) 1 TeSys motor starters - open version TeSys U starter-controllers Tripping curves for control units LUCM Hot state curves Average operating times at 20 °C according to multiples of the setting current, tolerance : ± 20 % Time (s) 1 10000 1000 100 10 Class 30 Class 25 Class 20 Class 15 Class 10 Class 5 1 0,1 1 2 3 4 5 6 7 8 9 10 12 11 13 14 16 18 20 15 17 19 30 x the setting current (Ir) References : page 1/70 1/98 1 Curves (continued) TeSys motor starters - open version 1 1 TeSys U starter-controllers Current limitation on short-circuit Maximum current (kA) Ue = 460 V 1 100 1 2 10 3 1 0,1 0,1 0,2 0,4 0,6 0,8 1 2 3 4 6 8 10 20 30 40 60 80 100 Prospective Isc (kA) 1 Maximum peak current 2 32 A power base 3 12 A power base Thermal limit on short-circuit Sum of I²dt (A²s) 103 Ue = 460 V 1000 1 100 2 10 1 0,1 0,2 0,4 0,6 0,8 1 2 3 4 6 8 10 20 30 40 60 80 100 Prospective Isc (kA) 1 32 A power base 2 12 A power base References : pages 1/64 to 1/70 1/99 Selection guide 1 TeSys motor starters - open version TeSys U starter-controllers Millions of operating cycles LUB 12 1 LUB 32 Use in category AC-41 10 8 6 5 4 3 2 1 0,8 0,6 0,5 1 2 3 4 5 6 7 8 9 10 12 32 40 Current broken in A Use in category AC-43 Ue y 440 V 6 5 4 3 2 LUB 32 LUB 12 LUB 32 10 8 Millions of operating cycles Millions of operating cycles LUB 12 Ue = 690 V 10 8 6 5 4 3 2 1 0,8 1 0,8 0,6 0,6 0,5 0,5 1,5 7,5 32 40 Current broken in A 6 7 8 9 10 12 5,5 5 4 2,2 3 0,75 2 0,55 1 15 7,5 11 5,5 4 2,2 1,5 0,75 0,55 230 V 440 V References : pages 1/64 to 1/70 1/100 15 11 7,5 5,5 4 2,2 1,5 0,75 0,55 400 V kW kW kW 1 2 3 4 5 6 7 8 9 10 12 32 40 21 Current broken in A 1 Selection guide 1 TeSys motor starters - open version 1 TeSys U starter-controllers Use in category AC-44 Ue y 440 V 1 LUB 12 LUB 32 1 0,8 Millions of operating cycles Millions of operating cycles LUB 12 LUB 32 Ue = 690 V 0,6 0,5 0,4 0,3 0,2 1 0,8 0,6 0,5 0,4 0,3 0,2 0,1 0,08 0,1 0,08 0,06 0,05 0,04 0,06 0,05 0,04 0,03 0,03 0,02 0,02 0,01 0,01 1 2 3 5 10 20 30 40 50 66 100 200 60 80 170 Current broken in A 1 2 3 5 10 20 30 200 50 60 100 40 54 80 126 Current broken in A References : pages 1/64 to 1/70 1/101 Dimensions 1 TeSys motor starters - open version TeSys U starter-controllers Starter-controllers Non-reversing Reversing X1 126 Rail mounting 126 Screw fixing 30 Ø4 Rail mounting Screw fixing 29 Ø4 135 (1) 45 X2 233 120/125 X1 224 154 163 73 X2 135 (1) 45 Minimum electrical clearance: X1 = 50 mm for Ue = 440 V and 70 mm for Ue = 500 and 690 V, X2 = 0 (1) Maximum depth (with Modbus communication module) Reverser block for mounting separately from power base Rail mounting Screw fixing 115 104 Ø4 113 113 45 36 Sets of busbars and plug-in power sockets GV2 G445 and GV2 G454 GV2 Gppp with terminal block GV1 G09 GV2 G245 and G254 18 a l p l 95 30 GV1 G09 GV2 G445 (2 x 45) GV2 G454 (2 x 54) I 179 206 P 45 54 Number of tap-offs GV2 G445 (2 x 45) GV2 G454 (2 x 54) a 5 224 260 6 269 314 GV2 G554 7 314 368 I 89 98 GV2 G345 (2 x 45) GV2 G354 (2 x 54) I 134 152 l 8 359 422 30 82 45,5 AK5 PC13, PC33, PC33L 79 45 438 452 1/102 GV2 G245 (2 x 45) GV2 G254 (2 x 54) GV2 G345 and G354 260 AK5 JB144 81 1 38 35,5 1 Dimensions TeSys motor starters - open version 1 1 TeSys U starter-controllers Limiter-disconnector LUA LB1 Disconnector LUA LB10 Current limiter LA9 LB920 93 1 6 45 135 (1) 115 103 154 146 2ØM4 51 53,5 (1) Maximum depth (with Modbus communication module). Door interlock mechanisms LU9 AP00 Door cut-out = = 54 55 162 230 = = 54 11,5 508 8 Ø7 Addressing consoles ASI TERV2 195 209 XZ MC11 80 84 30 35 154 163 Modbus hub LU9 GC3 Splitter box LU9 G02 128 45 128 Ø4 30 1/103 Schemes 1 TeSys motor starters - open version TeSys U starter-controllers Starter-controllers, 12 or 32 A With standard, advanced or multifunction control unit 5/L3 3/L2 1/L1 22/NC 6/T3 4/T2 2/T1 21/NC Control Unit A2 A1 6/T3 4/T2 2/T1 Control Unit 14/NO 13/NO 5/L3 3/L2 Reversing 1/L1 Non-reversing Pre-wired With control unit LUCC or LUCM 5 L2 22/NC 21/NC 14/NO 13/NO 82 84 81 A2 B1 A1 B3 A3 6/T3 Control terminal block A2 B1 A1 A3 B3 LU2B Reverser Motor Controller A2 A1 V 6 4 U 2 Control Unit 4/T2 Reverser 2/T1 3 1 L1 Connection of a single-phase motor M Reverser blocks LU2M LU6M 82 84 81 A2 B1 A1 B3 S3 A2 LU6M A2 21 22 S3 S2 A2 B1 A1 B3 A3 S1 14 13 Basic scheme Reverser Motor Controller LU2M S3 Reverser Block LU9M RC Pre-wired coil A1 A3 6/T3 Control terminal block S2 S1 With pre-wired connector LU9M RC LU6M 4/T2 B1 B3 A3 A1 Reverser Block LU6M Reverser S2 S1 S3 S2 S1 5/L3 3/L2 1/L1 Control terminal blocks 2/T1 S1 Start next stage S2 Electrical interlocking S3 Maintaining contact B1 Maintain forward running B3 Maintain reverse running A1 Pulse forward running A2 Common A3 Pulse reverse running (1) Electronically operated bistable electromagnet. A2 A3Reverse A1Forward B3 Reverse (1) B1 Forward 1 Add-on contact blocks Add-on contact modules LUA1 C11 LUFN 20 17/NO 95/NC 1/104 LUA1 C20 LUFN 11 LUFN 02 18/NO 17/NO 18/NO 33/NO 34/NO 43/NO 44/NO 31/NC 32/NC 96/NC 97/NO 98/NO 43/NO 44/NO 31/NC 32/NC 41/NC 42/NC 1 Schemes (continued) 1 TeSys motor starters - open version 1 TeSys U starter-controllers Control units Standard control unit LUCA Advanced control unit (LUCB, LUCC, LUCD) Basic scheme 1 Basic scheme 1 2 3 4 5 6 1 2 3 4 5 6 LUCA LUCp Power Base Interface Sensor L1 Control A.S.I.C. Sensor L2 Power Base Interface Sensor L1 Control A.S.I.C. Sensor L2 tr tr Sensor L3 Sensor L3 Thermal overload memory Thermal overload memory Supply and Detection of start sequence Test Interface module A2 A1 A2 A1 Supply and Detection of start sequence 7 1 and 2 Trips 3 and 4 Electromagnet 5 Power base rating 6 N/C 8 9 10 11 12 1 and 2 Trips 3 and 4 Electromagnet 5 Power base rating 6 N/C 7 Weight 8 Thermal status/Set 9 Reset mode/Reset 10 (lm/Ir) 11 Vc2 12 Vc1 Multifunction control unit LUCM Control terminal block Multifonction Control Unit D(B) D(A) +5V 0V LUCM 24 V Aux 4 5 7 6 8 Basic scheme 1 2 3 4 5 6 LUCM Power Base Interface Sensor L1 Display and Parameter Entry ESC Control A.S.I.C. Sensor L2 Sensor L3 ENT RS485 Supply and detection of start sequence Thermal overload memory D(B) D(A) +5V 0V 4 5 RJ45 7 8 Supply Interface module A2 A1 24 V Aux 7 8 9 10 11 12 1 and 2 Trips 3 and 4 Electromagnet 5 Power base rating 6 N/C 7 Weight 8 N/C 9 Weight 10 (lm/Ir) 11 Rx/Tx 12 Vc1 1/105 Schemes (continued) 1 TeSys motor starters - open version TeSys U starter-controllers Function modules Alarm LUF W10 Indication of motor load LUFV 2 4-20 mA output Alarms Module LUFW 10 Analogue output Module LUFV 2 24 V Aux 08 07 4...20 mA 24 V Aux NC Basic scheme Basic scheme Advanced Control Unit or Multifunction Control Unit Advanced Control Unit or Multifunction Control Unit LUFW 10 Input interface LED Supply LUFV 2 Supply Input interface µP - Analogue/Digital converter Isolation Bistable Relay 08 Digital/Analogue converter 07 1 Voltage/Current converter 4...20 mA c 24 V 100 Ω < load < 500 Ω c 30 V max and 40 mA min 1/106 1 Schemes (continued) 1 TeSys motor starters - open version 1 TeSys U starter-controllers Communication modules Communication modules ASILUF C5 and ASILUF C51 Without pre-wired coil connection AS-Interface Module ASILUF C5 or ASILUF C51 AS-i OA3 OA1 Com ASILUF C5 or ASILUF C51 1 With pre-wired coil connection LU9B N11C AS-Interface Module AS-i LU9B N11C Pre-wired coil With pre-wired coil connection LU9M RC AS-Interface Module ASILUF C5 or ASILUF C51 AS-i LU9M RC Pre-wired coil Basic scheme ASILUF C5 or Ready-Fault-Pole ASILUF C51 LED A2SI OA3 OA1 Com Output Interface c 24 V AS-i 1/107 Schemes (continued) TeSys motor starters - open version 1 TeSys U starter-controllers Communication modules (continued) Modbus communication modules LUL C031 Modbus communication modules LUL C032 and LUL C033 Without pre-wired coil connection Without pre-wired coil connection D(B) D(A) 0V LI2 LI1 LO1 OA3 COM 4 5 8 6 24 V Aux D(B) D(A) 0V LI2 24 V c COM 4 5 8 6 With pre-wired coil connection LU9M RC Basic scheme 24 V Aux D(B) D(A) 0V LU9M RC Pre wired coil 4 5 8 Modbus Module 24 V c LI2 24 V Aux LUL C032 or LUL C033 LI1 D(B) D(A) 0V Modbus Module LUL C031 LO1 With pre-wired coil connection LU9M RC Modbus Module LI1 LU9B N11C Pre wired coil 4 5 8 6 Com 24 V Aux LUL C032 or LUL C033 LO1 24 V Aux Com LO1 D(B) D(A) 0V Modbus Module LO1 Modbus Module 24 V c With pre-wired coil connection LU9B N11C LUL C031 LU9M RC Pre wired coil OA1 4 5 8 6 With pre-wired coil connection LU9B N11C LU9B N11C Pre-wired coil LUL C032 or LUL C033 Com LO1 24 V Aux Com OA3 OA1 Com D(B) D(A) 0V Modbus Module LUL C031 COM 4 5 8 Basic scheme Advanced Control Unit or Multifunction Control Unit Advanced Control Unit or Multifunction Control Unit Controller x6 LULC 031 Control unit interface Input interface Ready-Fault-Pole Address LED D(B) RS485 D(A) 0V Controller interface D(B) 4 5 Modbus RJ45 8 RS485 Supply LI2 LI1 I/O interface LO1 OA3 Com 24 V Aux Output Interface OA1 Com LO1 OA3 OA1 1/108 AL2 D(A) 0V AL1 Supply 24 V LULC 032 or LULC 033 Ready-Fault-Pole Address LED AL1 Output Interface Com 1 AL2 24 V c 24 V Aux COM 4 5 Modbus RJ45 8 1 Schemes (continued) 1 TeSys motor starters - open version 1 TeSys U starter-controllers Communication modules (continued) Parallel wiring modules Without pre-wired coil connection OA3 OA1 Com LUF C00 Parallel bus Module LUF C00 1 With pre-wired coil connection LU9M RC Link // RJ45 1 2 3 4 5 6 7 8 LU9M RC Pre-wired coil Parallel bus Module Link // RJ45 1 2 3 4 5 6 7 8 With pre-wired coil connection LU9B N11C Parallel bus Module LUF C00 Link // RJ45 1 2 3 4 5 6 7 8 LU9B N11C Pre-wired coil Basic scheme LUF C00 1 2 3 4 5 6 7 8 OA1 OA3 Com Poles ReadyFault RJ45 1 2 3 4 5 6 7 8 Forward running Reverse running Output common Knob in position Pole state Reserved Fault Input common 1/109 Schemes (continued) 1 TeSys motor starters - open version TeSys U starter-controllers Communication modules (continued) Wiring hub and splitter box LU9 G02 8 7 6 5 4 3 2 1 RJ 45 X2 8 7 6 5 4 3 2 1 X1 Forward running Reverse running Output common N/C Pole state N/C Fault Input common X9 X2 X9 8 7 6 5 4 3 2 1 RJ 45 X3 RJ 45 N/C N/C N/C D (B) – RJ 45 D (A) + N/C 24 V (1) 0V RJ 45 X3 (2) RJ 45 X4 X4 RJ 45 RJ 45 X5 Colours of TSX CDPppp connection cable wires (4) 20 19 18 17 16 15 14 13 12 1110 9 8 7 6 5 4 3 2 1 LU9 GC3 X1 N/C N/C N/C D (B) – D (A) + RJ 45 N/C N/C 0V Parallel wiring splitter box LU9 G02 Fault X1 Fault X2 Fault X3 Fault X4 Fault X5 Fault X6 Fault X7 Fault X8 Pole state X1 Pole state X2 Pole state X3 Pole state X4 Pole state X5 Pole state X6 Pole state X7 Pole state X8 + 24 V Aux - 24 V Aux + 24 V Aux - 24 V Aux 20 19 18 17 16 15 14 13 12 1110 9 8 7 6 5 4 3 2 1 Modbus hub LU9G C3 Forward running X1 Forward running X2 Forward running X3 Forward running X4 Forward running X5 Forward running X6 Forward running X7 Forward running X8 Reverse running X1 Reverse running X2 Reverse running X3 Reverse running X4 N/C N/C N/C N/C + c 24 V - c 24 V + c 24 V - c 24 V 1 White 2 Brown 3 Green 4 Yellow 5 Grey 6 Pink 7 Blue 8 Red 9 Black 10 Violet 11 Grey-pink 12 Red-blue 13 White-green 14 Brown-green 15 White-yellow 16 Yellow-brown 17 White-grey 18 Grey-brown 19 White-pink 20 Pink-brown Forward running N/C Output common N/C Pole state N/C Fault Input common X10 X6 RJ 45 RJ 45 8 7 6 5 4 3 2 1 X5 RJ 45 X6 X7 RJ 45 RJ 45 X7 Shielding RJ 45 X8 RJ 45 X10 (3) RJ 45 X8 RJ 45 Com 24 V Aux Inputs Com Outputs 0V Shielding 0V D (A) + Shielding c 24 V D (B) – (1) Not connected on connectors X1 to X8. Only present on RJ45 IN and OUT connectors. (2) 20-way HE 10 input connector. (3) 20-way HE 10 output connector. (4) Correspondence between wire colours and HE 10 connector pin numbers. Gateways Gateway Fip I/O - Modbus LUF P1 24 V Aux X2 Fip I/O 1 2 3 4 5 6 7 8 9 1/110 X1 4 5 8 LUF P7 LUF P9 Gateway Profibus - Modbus 24 V Aux X2 Profibus 1 2 3 4 5 6 7 8 9 X1 4 5 8 LUF P9 24 V Aux Gateway DeviceNet - Modbus X2 DeviceNet 1 2 3 4 5 X1 D(B) D(A) 0V LUF P7 D(B) D(A) 0v LUF P1 D(B) D(A) 0V 1 4 5 8 1 Schemes (continued) 1 TeSys motor starters - open version 1 TeSys U starter-controllers Data profile under AS-Interface Control unit present in the product Status Commands D0 D1 D0 D1 Standard Advanced Multifunction Standard Advanced Multifunction Ready (available) Poles closed (running) Forward running Reverse running Register addresses accessible under Modbus Control unit present in the product Marking Register 0…Register 99 Words…Bits Commercial reference, serial number, software version Log Register 100…Register 450 Words…Bits Fault log, Operating log, Log of last 5 trips Status Values Register 451…Register 464 Words…Bits Alarm signalling (bits), Fault signalling (bits) Register 465…Register 473 Words Irms phase 1, phase 2, phase 3. Motor load, thermal status Earth leakage current. Phase imbalance and phase failure Register 474…Register 599 Words…Bits Reserved Configuration Register 600…Register 699 Words…Bits Protection and alarm thresholds, fallback mode and reset mode Commands Register 700…Register 714 Words…Bits Commands Status and values Register 452 Register 455 Register 461 Register 465 Register 466 Configuration Register 602 Register 682 Commands Register 700 Register 704 Bit 0 Bit 1 Bit 2 Bit 0 Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6 Bit 7 Bit 8 Bit 9 Bit 10 Bit 11 Bit 12 Bit 13 Bit 14 Bit 15 Bit 3 Word Word Short-circuit fault Overcurrent fault Thermal overload fault Ready (available) Poles closed Fault Alarms Tripped ("TRIP" position) Fault acknowledgement allowed Reserved Motor running Motor current % (bit 0) Motor current % (bit 1) Motor current % (bit 2) Motor current % (bit 3) Motor current % (bit 4) Motor current % (bit 5) Reserved Motor starting Thermal overload alarm Thermal status value Motor load value (Im/Ir) Bit 0 Bit 1 Bit 2 Value 0 Value 1 Value 2 Value 3 Value 4 Value 5 Manual reset on thermal overload fault Remote reset on thermal overload fault Automatic reset on thermal overload fault Fallback mode validation Outputs OA1 and OA3 unchanged Outputs OA1 and OA3 forced to 0 Outputs OA1 and OA3 unchanged, signalling existence of communication failure Outputs OA1 forced to 1 and OA3 unchanged Outputs OA3 forced to 1 and OA1 unchanged Bit 0 Bit 0 Bit 1 Bit 2 Bit 3 Bit 4 Bit 5 Bit 6…15 LO1 output command OA1 output command OA3 output command Reserved Fault acknowledgement Reserved Trip test Reserved Data accessible 1/111 1 Basic schemes 1 TeSys motor starters - open version TeSys U starter-controllers Non-reversing 5/L3 1/L1 1 3/L2 Non-reversing starter-controllers LUB V1 4/T2 W1 6/T3 U1 2/T1 Control Unit M 3a 2-wire control via 2-position switch A1 3-wire control, pulsed start with maintaining contact A1 A2 Connection of a motor load indicator module LUFV 2 A2 LUFV 2 Start Stop 4...20 mA 24 V Aux 13 Analogue output Module 24 V Aux 14 NC Connection of thermal overload fault signalling modules LUF DA10 Automatic reset Remote reset 07 A1 A2 – QF1 24…230 V X2 X1 Z2 Z1 X1 Z2 Z1 A2 Automatic or remote reset LUF DA10 24…230 V X2 07 08 Automatic or remote reset LUF DA10 08 – V1 – V1 A1 – S2 – QF1 – S1 – S1 Control via Modbus communication module LUL C031 Control via Modbus communication modules LUL C032 and LUL C033 Without pre-wired coil connection Without pre-wired coil connection – S1 1/112 A1 COM D(B) D(A) GND LI2 24 V 24 V c Aux 4 5 8 6 – S2 Modbus Modbus A2 LI1 LO1 OA1 OA3 4 5 8 6 Modbus Module LUL C032 or LUL C033 Com Com LO1 OA3 OA1 Com 24 V Aux D(B) D(A) GND Modbus Module LULC 031 A2 A1 1 Basic schemes (continued) 1 TeSys motor starters - open version 1 TeSys U starter-controllers Non-reversing Non-reversing starter controllers LUB (continued) Control via communication modules ASILUF C5 and ASILUF C51 Without pre-wired coil connection ASILUF C5 or ASILUF C51 1 Without pre-wired coil connection With local control AS-Interface Module ASILUF C5 or ASILUF C51 AS-Interface Module OA3 OA1 Com AS-Interface AS-Interface line Normal A1 A2 With pre-wired coil connection LU9B N11C ASILUF C5 or ASILUF C51 AS-Interface line Adjustment A2 OA3 OA1 Com AS-Interface A1 Without pre-wired coil connection With local control AS-Interface Module ASILUF C5 or ASILUF C51 AS-Interface Module AS-Interface OA3 LU9B N11C Pre wired coil OA1 Com AS-Interface AS-Interface line AS-Interface line Normal A1 Adjustment A2 Without pre-wired coil connection With multifunction control unit LUCM ASILUF C5 or ASILUF C51 AS-Interface Module A2 OA3 OA1 Com AS-Interface A1 LUCM AS-Interface line Multifonction Control Unit D(B) D(A) GND RJ45 24 V Aux 4 5 8 6 Bus Modbus RS 485 1/113 Basic schemes (continued) 1 TeSys motor starters - open version TeSys U starter-controllers Reversing Reversing starter-controllers LU2B 2-wire control via 3-position switch 3-wire control, pulsed start with maintaining contact 5/L3 A2 B1 A1 A3 B3 Reverser Motor Controller LU2B A2 B1 A3 A1 Reverser Motor Controller LU2B B3 3/L2 1/L1 1 Start forward running 6/T3 4/T2 Stop forward running and reverse running forward running Stop reverse running Stop forward running Start reverse running Stop reverse running W1 6/T3 V1 4/T2 U1 2/T1 2/T1 Control Unit M 3 Control via communication modules ASILUF C5 and ASILUF C51 3-wire control, pulsed start with maintaining contact and limit switches With pre-wired coil connection LU9M RC With multifunction control unit LUCM ASILUF C5 or ASILUF C51 AS-Interface Module Reverser Motor Controller LU2B AS-Interface line Stop forward running and reverse running D(B) D(A) GND Multifonction Control Unit LUCM 24 V Aux 4 5 8 6 Bus Modbus RS 485 Control via communication modules ASILUF C5 and ASILUF C51 Without pre-wired coil connection With running direction pilot lights and limit switches OA3 OA1 ASILUF C5/C51 AS-Interface Module Com A2 A1 B3 A3 B1 Reverser Motor Controller LU2B AS-Interface AS-Interface line 53 54 81 84 82 1/114 Limit switch Stop forward forward running running Start forward running Limit switch Stop reverse reverse running running Start reverse running A2 B1 A1 A3 LU9M RC Pre wired coil B3 AS-Interface 1 Basic schemes (continued) TeSys motor starters - open version 1 1 TeSys U starter-controllers Reversing Reversing starter controllers LU2B (continued) Control via Modbus communication module LUL C031 Control via Modbus communication modules LUL C032 and LUL C033 Without pre-wired coil connection. With local control Without pre-wired coil connection. With local control LI2 LO1 LI1 OA1 OA3 24 V c 24 V Aux COM 4 5 8 6 Modbus Adjustment Adjustment NOrmal Start reverse running Start forward running Start reverse running Normal Modbus Start forward running D(B) D(A) GND Modbus Module LULC 032 or LUL C033 Com A2 B1 A1 4 5 8 6 Reverser Motor Controller LU2B B3 Com LO1 OA3 OA1 Com B1 A2 24 V Aux A3 Modbus Module LULC 031 D(B) D(A) GND Reverser Motor Controller A1 B3 A3 LU2B 5/L3 3/L2 1/L1 Reversing starter-controllers LUB + LU6M 5/L3 W1 6/T3 6/T3 3/L2 4/T2 V1 4/T2 1/L1 U1 2/T1 2/T1 Control Unit M 3 3-wire control, pulsed start with maintaining contact 2-wire control via 3-position switch A1 A2 A1 Stop reverse running S7 S3 S2 S1 22 A2 B1 B3 A3 A1 Reverser Block LU6M A2 B1 B3 A1 Reverser Block A3 Stop forward running and Stop forward reverse running running S5 S6 21 22 S3 S2 S1 21 LU6M A2 14 13 Start forward running S8 Start reverse running S9 forward running Stop reverse running 1/115 1