Sound, Security, Alarm Cable Substitution Chart Per 2005 NEC ® NEC ARTICLES FIRE-RESISTANCE LEVEL Test Requirements 800 725 760 820 770 830 PLENUM 4 (Highest) CMP COAX MULTI-CONDUCTOR NFP A 262 (UL-910 Steiner Tunnel) CL3P FPLP CATVP NONCONDUCTIVE CONDUCTIVE OFNP OFCP BLP CMP CL3P CL2P RISER 3 COAX MULTI-CONDUCTOR CMR UL-1666 (Vertical Shaft) BMR CL3R CATVR FPLR OFNR OFCR CL2R GENERAL PURPOSE CMG CM 2 COAX MULTI-CONDUCTOR FPL UL-1 685 Vertical Tray or CSA FT4 (UL 1581) BM PLTC CATV OFNG OFCG CL3 CL2 BLX RESIDENTIAL COAX CMX 1 (Lowest) CATVX CL3X VW -1 (Vertical Flame) All cables other than “Network-Powered Broadband Cables” (BMR, BM, BLP, BLX) shall be coaxial cables. CL2X CMR CL3R CMG CM CL3 CMX CL3X Cables indicated can be substituted. NEC Type CMP, CMR, CMG, CM, CMX CL3P, CL3R, CL3, CL3X, CL2P, CL2R, CL2, CL2X FPLP, FPLR, FPL CATVP, CATVR, CATV, CATVX OFNP, OFNR, OFNG, OFN OFCP, OFCR, OFCG, OFC PLTC BMR, BM, BLP, BLX Definition Communications Cables Class 2 and Class 3 Remote-Control, Signaling and Power Limited Cables Power Limited Fire Alarm Cables Community Antenna Television and Radio Distribution Cables Nonconductive Optical Fiber Cables Conductive Optical Fiber Cables Power Limited Tray Cables Network-powered Broadband Communications Cables National Electrical Code and NEC are registered trademarks of the National Fire Protection Association, Inc., Quincy, MA www.ptsupply.com marketing@ptsupply.com 800-238-7514 1 Sound, Security, Alarm Multi-Conductor Unshielded, Non-Plenum Listed by UL as Type CMR and/or CL3R cables for use in NEC® Article 800 and/or 725 installations. Specifications Conductors Stranded or solid, bare copper Insulation Premium-grade color-coded S-R PVC Jacket Gray PVC Suitable for use from -20°C to 75°C Suggested voltage rating of 300V Applications Wiring of intercom, security, audio, background music and power limited control circuits (2-4 conductor recommended for single channel use only). No. of Cond. AWG Conductor Stranding Nom. Ins. Thick. (in) Nom. Jacket Thick. (in) Nom. O.D. (in) Weight (lbs/M-ft) 2C22B7NS 2 22 7/30 .008 .015 .122 10 3C22B7NS 3 22 7/30 .008 .015 .129 10 4C22B7NS 4 22 7/30 .008 .015 .156 20 6C22B7NS 6 22 7/30 .008 .015 .164 20 8C22B7NS 8 22 7/30 .008 .015 .180 30 10C22B7NS 10 22 7/30 .008 .015 .212 30 12C22B7NS 12 22 7/30 .008 .015 .219 40 2C20B7NS 2 20 7/28 .008 .015 .134 10 3C20B7NS 3 20 7/28 .008 .015 .134 15.5 4C20B7NS 4 20 7/28 .008 .015 .142 20 2C18B1NS 2 18 Solid .009 .015 .144 20 2C18B7NS 2 18 7/26 .009 .015 .156 20 3C18B7NS 3 18 7/26 .009 .015 .166 25 4C18B7NS 4 18 7/26 .009 .015 .187 32 2C16B19NS 2 16 19/.0117 .009 .015 .178 25 4C16B19NS 4 16 19/.0117 .009 .015 .214 47 2C14B19NS 2 14 19/.0147 .013 .015 .224 40 2C12B19NS 2 12 19/.0185 .013 .015 .260 60 Part No. (CL3R only per NEC) See referenced pages in the Hardware & Supplies section: Installation Hardware • Acme 25A or 75A Staple Gun - I-3 Suggested Prep Tool • 721 Multi-Wire Stripper/Cutter - I-9 2 www.ptsupply.com marketing@ptsupply.com 800-238-7514 Sound, Security, Alarm Multi-Conductor Shielded, Non-Plenum Listed by UL as Type CMR and/or CL3R cables for use in NEC® Article 800 and/or 725 installations. Specifications Conductors Stranded or solid, bare copper Insulation Premium-grade color-coded S-R PVC Shield Overall polyester-supported aluminum foil, with a stranded, tinned copper drain wire to facilitate grounding Jacket Gray PVC Suitable for use from -20°C to 75°C Suggested voltage rating of 300V Applications Wiring of intercom, security, audio, background music and power limited control circuits. Part No. No. of Cond. 2 1P22B1PS AWG Conductor Stranding Nom. Ins. Thick. (in) Nom. Jacket Thick. (in) Nom. O.D. (in) Weight (lbs/M-ft) 22 Solid .008 .015 .120 11 12.5 1P22B7PS 2 22 7/30 .008 .015 .132 3C22B70S 3 22 7/30 .008 .015 .135 15 4C22B70S 4 22 7/30 .008 .015 .147 18 6C22B70S 6 22 7/30 .008 .015 .173 29 8C22B70S 8 22 7/30 .008 .015 .195 32 10C22B70S 10 22 7/30 .008 .018 .230 42 12C22B70S 12 22 7/30 .008 .015 .235 49 2C20B70S 2 20 7/28 .008 .015 .142 17 3C20B70S 3 20 7/28 .008 .015 .151 21 4C20B70S 4 20 7/28 .008 .015 .171 26 2C18B10S 2 18 Solid .009 .015 .151 21 2C18B70S 2 18 7/26 .009 .015 .164 23 3C18B70S 3 18 7/26 .009 .015 .173 30 4C18B70S 4 18 7/26 .009 .015 .192 37 1P16B19PS 2 16 19/.0117 .010 .015 .189 32 (CL3R only per NEC) 1P14B19PS 2 14 19/.0147 .013 .015 .245 50 1P12B19PS 2 12 19/.0185 .013 .015 .281 67 www.ptsupply.com marketing@ptsupply.com See referenced pages in the Hardware & Supplies section: Installation Hardware • Acme 25A or 75A Staple Gun - I-3 Suggested Prep Tool • 721 Multi-Wire Stripper/Cutter - I-9 800-238-7514 3 Sound, Security, Alarm Multi-Conductor Unshielded, Plenum NEC® 725 and/or 800, UL listed as to fire and smoke only. Insulated and jacketed cable designed for installation through air plenums without metal conduit. Specifications Conductors Stranded or solid, bare copper Insulation Low-smoke, low-flame approved compound Jacket Low-smoke, low-flame approved compound Applications Security, audio, intercom, power limited control circuits Weight (lbs/M-ft) Solid Bare .108 15 22 7/30 Bare .120 15 18 3C22B7NSP 3 22 7/30 Bare .127 4C22B1NSP 4 22 Solid Bare .124 18 4C22B7NSP 4 22 7/30 Bare .139 20 6C22B7NSP 6 22 7/30 Bare .164 25 8C22B7NSP 8 22 7/30 Bare .178 31 10C22B7NSP 10 22 7/30 Bare .205 43 12C22B7NSP 12 22 7/30 Bare .215 48 3C18B1NSP 3 18 Solid Bare .150 24 3C18B7NSP 3 18 7/26 Bare .166 26 4C18B1NSP 4 18 Solid Bare .165 30 4C18B7NSP 4 18 7/26 Bare .187 39 5C18B1NSP 5 18 Solid Bare .165 40 5C18B7NSP 5 18 7/26 Bare .205 45 6C18B1NSP 6 18 Solid Bare .200 47 6C18B7NSP 6 18 7/26 Bare .225 51 8C18B1NSP 8 18 Solid Bare .220 61 8C18B7NSP 8 18 7/26 Bare .240 67 10C18B1NSP 10 18 Solid Bare .260 75 10C18B7NSP 10 18 7/26 Bare .285 82 See referenced pages in the Hardware & Supplies section: Installation Hardware • Acme 25A or 75A Staple Gun - I-3 Suggested Prep Tool • 721 Multi-Wire Stripper/Cutter - I-9 Color Ordering Chart or 22 2 or 2 2C22B7NSP ct Nom. O.D. (in) du 2C22B1NSP Conductor or Conductor Stranding ct or AWG du No. of Cond. Part No. Bare .185 30 Bare .195 37 4C16B19NSP 4 16 19/29 Bare .215 52 1P14B19NSP 2 14 19/.0117 Bare .225 39 3C14B19NSP 3 14 19/.0117 Bare .240 56 4C14B19NSP 4 14 19/.0117 Bare .265 73 4 Green 10 Gray Brown 11 Pink Blue 12 Tan C Black 7 Orange 2 Red 8 Yellow 3 White 9 Violet 1P12B7NSP 2 12 19/.0185 Bare .267 60 4C12B7NSP 4 12 19/.0185 Bare .298 110 6 www.ptsupply.com marketing@ptsupply.com C C 1 5 4 ol 19/29 19/29 on 16 16 C ol 2 3 on 1P16B19NSP 3C16B19NSP 800-238-7514 Sound, Security, Alarm Multi-Conductor Shielded, Plenum NEC® 725 and/or 800, UL listed as to fire and smoke only. Insulated and jacketed cable designed for installation through air plenums without metal conduit. Specifications Conductors Stranded or solid, bare copper Insulation Low-smoke, low-flame approved compound Shield Overall Mylar/aluminum foil tape with a stranded, tinned copper drain wire Jacket Low-smoke, low-flame approved compound Applications Security, audio, intercom, power limited control circuits. No. of Cond. AWG Conductor Stranding Nom. O.D. (in) Weight (lbs/M-ft) 1P22B10SP 2 22 Solid 1P22B70SP 2 22 7/30 Bare .118 15 Bare .120 3C22B70SP 3 22 7/30 15 Bare .129 18 4C22B70SP 4 22 5C22B70SP 5 22 7/30 Bare .135 20 7/30 Bare .150 24 6C22B70SP 6 8C22B70SP 8 22 7/30 Bare .175 30 22 7/30 Bare .199 35 10C22B70SP 12C22B70SP 10 22 7/30 Bare .224 42 12 22 7/30 Bare .236 50 1P18B10SP 2 18 Solid Bare .150 22 1P18B70SP 2 18 7/26 Bare .160 24 3C18B70SP 3 18 7/26 Bare .170 31 4C18B70SP 4 18 7/26 Bare .190 38 5C18B70SP 5 18 7/26 Bare .205 48 6C18B70SP 6 18 7/26 Bare .230 52 8C18B70SP 8 18 7/26 Bare .245 66 10C18B70SP 10 18 7/26 Bare .265 83 1P16B190SP 2 16 19/29 Bare .190 33 3C16B190SP 3 16 19/29 Bare .205 45 4C16B190SP 4 16 19/29 Bare .225 59 2C14B190SP 2 14 19/27 Bare .225 51 4C14B190SP 4 14 19/27 Bare .270 76 Part No. Other sizes available upon request. Conductor See referenced pages in the Hardware & Supplies section: Installation Hardware • Acme 25A or 75A Staple Gun - I-3 Suggested Prep Tool • 721 Multi-Wire Stripper/Cutter - I-9 www.ptsupply.com marketing@ptsupply.com 800-238-7514 5 Sound, Security, Alarm Twisted Pair, Shielded Each Pair Individually Shielded NEC® Type CM. Specifications Conductors Stranded, tinned copper Insulation PVC Shield Overall Mylar/aluminum foil tape with a stranded, tinned copper drain wire on each pair Jacket Gray PVC Applications Intercom systems, computer interconnects. No. of Pairs Part No. AWG Cond. Stranding Nom. Ins. Thick. (in) Nom. Jacket Thick. (in) Nom. O.D. (in) Weight (lbs/M-ft) 2P22T7EPS 2 22 7/30 .010 .045 .190 42 3P22T7EPS 3 22 7/30 .010 .045 .295 53 6P22T7EPS 6 22 7/30 .010 .045 .375 87 9P22T7EPS 9 22 7/30 .010 .045 .430 113 11P22T7EPS 11 22 7/30 .010 .045 .465 130 12P22T7EPS 12 22 7/30 .010 .045 .480 143 15P22T7EPS 15 22 7/30 .010 .060 .565 187 19P22T7EPS 19 22 7/30 .010 .060 .620 234 27P22T7EPS 27 22 7/30 .010 .060 .709 346 3P20T10EPS 3 20 10/30 .013 .045 .340 57 6P20T10EPS 6 20 10/30 .013 .045 .435 101 9P20T10EPS 9 20 10/30 .013 .060 .550 148 12P20T10EPS 12 20 10/30 .013 .060 .617 188 253 15P20T10EPS 15 20 10/30 .013 .060 .689 3P18T16EPS 3 18 16/30 .016 .045 .404 79 6P18T16EPS 6 18 16/30 .016 .045 .495 166 9P18T16EPS 9 18 16/30 .016 .060 .655 232 12P18T16EPS 12 18 16/30 .016 .070 .735 312 15P18T16EPS 15 18 16/30 .016 .070 .819 373 Some air plenum designs also stocked. See referenced pages in the Hardware & Supplies section: Installation Hardware • Acme 25A, 37A or 75A Staple Gun - I-3 Suggested Prep Tool • 721 Multi-Wire Stripper/Cutter - I-9 6 www.ptsupply.com marketing@ptsupply.com 800-238-7514 Sound, Security, Alarm Siamese Coaxial Cable Available with either dual coaxial cables or coaxial cable with a twisted pair and also in a plenum-rated design for installation in a drop ceiling or a raised floor. These cables are easier to install than standard coaxial cables and are ideal for dual Direct Broadcast System (DBS) applications where one dish is used to serve two receivers. They also are critical for satellite hookup where a powered-pair cable is desired. Other applications for these coaxial cables include sound and security surveillance cameras where the coaxial cable transmits the audio/video signal and the twisted pair is used to control the pan and tilt function of the closed-circuit television (CCTV) camera. In today’s uncertain world, security installations are occurring at a double-digit growth rate. Security cameras are being installed in virtually every office, school and government facility, on highways and in traffic control centers and in most industrial, commercial and manufacturing facilities. Part No. Description AWG Conductor Shield Ohms Jacket Nom. OD (in) 2C18WI6DUAL RG-6 - CATV 18 Solid CCS Foil + 60% Alum. Braid 75 PVC .270 x .595 RG-6 - CATV Pair 18 Stranded Unshielded 18 Solid BC Foil + 95% TC 75 PVC .270 x .493 3C22X759U RG-59 - CATV + 1 Pr. 22 Shielded 22 Stranded BC 95% BC w/Foil on 76 PVC 3C20X159U1 RG-59 - CATV + 1 Pr. 18 Unshielded 20 Solid BC 95% BC 75 PVC .238 x .440 3C20B059UP RG-59 - CMP + 1 Pr. 18 Unshielded 20 Solid BC 95% BC 75 Plenum .200 x .383 3C18BIRG6U .242 x .445 See referenced pages in the Hardware & Supplies section: Installation Hardware • Collapsible Cable Caddy - I-3 Suggested Prep Tools • Drop Cable Slitter - I-8 • Universal Drop Trimmer - I-9 For 59, 6, and 11 or SDT 596-250 for 59 and 6 series cables and SDT11-250 for 11 series cable • Coaxial Cable Cutter - I-5 www.ptsupply.com marketing@ptsupply.com 800-238-7514 7 Sound, Security, Alarm Composite Access Control Cable Belden’s Banana Peel® Cables Help Ensure Limited Access Into a Secure Area Banana Peel cables offer the installers of access control devices - including electronic identification equipment such as card readers, retina scanners and hand-scanning devices - a host of labor-saving and easy-identification features. Whether the installation takes place in a commercial building, hospital, school, corporate site or government facility, these control cables bring a whole new level of ease and convenience to the work site. Features & Benefits: • Available in both jacketed and jacketless configurations • Banana Peel jacketless cables eliminate a step in the process because there is no overall jacket to strip • Smaller O.D. than traditional composites, improv- ing the cable’s overall bend radius for faster, easier installation • Breakout versatility is certain since the individual cables can be connected to the junction box or re-routed to the application site Call for a specification sheet. • Short circuits, caused by contact with the center conductor while stripping off the outer jacket, can be prevented • The individual cables are color-coded by application for easy identification, minimizing termination problems due to incorrect choice of cable • Cables have the application printed on the individual cable components: Lock Power, Card Reader, Door Contact and Request Exit (Rex/Spare) ensuring correct cable choice • The individual cable jackets are sequentially marked at 2' intervals and the cables are available in 1,000'/305m put-ups Sample configurations: Riser and Plenum (Jacketed) Standard - Riser and Plenum Part No. 558AFJ - Riser-rated (Plenum also available) NEC® 800, Type CMR CEC Type CMG FT4 Part No. 558AFS - Riser-rated (Plenum also available) NEC® 800, Type CMR CEC Type CMG FT4 Specifications Specifications Conductors Insulation Jackets 3 shielded multi-conductors, 1 shielded multi-pair PVC PVC (components and overall) Conductors Insulation Jacket 3 shielded multi-conductors, 1 shielded multi-pair PVC PVC (components only) Type 2 - Riser and Plenum Exit Reader Type - Riser and Plenum Part No. 558GMS - Riser-rated (Plenum also available) NEC® 800, Type CMR CEC Type CMG FT4 Part No. 558GFS - Riser-rated (Plenum also available) NEC® 800, Type CMR CEC Type CMG FT4 Specifications Specifications Conductors Insulation Jacket 8 3 unshielded multi-conductors, 1 shielded multi-conductor Flamarrest® PVC (components only) www.ptsupply.com marketing@ptsupply.com Conductors Insulation Jacket 2 shielded multi-conductors, 2 shielded multi-pairs Flamarrest® PVC (components only) 800-238-7514 Sound, Security, Alarm Combination Cable Listed by UL as Type CM and/or CL2 cables for use in NEC® Article 725 installations. Specifications Conductors Stranded bare and/or tinned copper Insulation Premium-grade, color-coded PVC, polypropylene or PE Shield Polyester-supported aluminum foil with a tinned copper drain wire Jacket Premium-grade gray PVC Suitable for use from -20°C to 75°C Suggested voltage rating of 300V See referenced pages in the Hardware & Supplies section: Applications Suitable for wiring security, sound/audio, intercom, and background music systems. Installation Hardware • Acme 25A Staple Gun - I-3 Suggested Prep Tool Nom. Ins. Thick. (in) Nom. Jacket Nom. O.D. (in) Weight (lbs/M-ft) Part No. No. of Cond AWG Conductor Stranding 2P22T7PIP0 2 shielded 2 unshielded 22 22 7/30 TC 7/30 TC .01 .02 .178 19 2P0T7PIP0 2 shielded 2 unshielded 20 18 7/28 TC 7/26 TC .01 .02 .210 39.5 3C22T7PIC0 2 shielded 1 unshielded 22 22 7/28 TC 7/28 TC .01 .02 .199 28 2P20T7PIP0 2 shielded 2 unshielded 20 20 7/28 TC 7/28 TC .01 .02 .201 34.8 • 721 Multi-Wire Stripper/Cutter - I-9 Thermostat Cable Listed by UL as Type CL2 cable for use in NEC Article 725 installations. No. of Cond. AWG Conductor Nom. O.D. (in) Weight (lbs/M-ft) 2C18B1STAT 2 18 Solid .140 19 3C18B1STAT 3 18 Solid .149 26 4C18B1STAT 4 18 Solid .158 35 5C18B1STAT 5 18 Solid .174 40 6C18B1STAT 6 18 Solid .184 47 8C18B1STAT 8 18 Solid .208 56 10C18B1STAT 10 18 Solid .227 68 12C18B1STAT 12 18 Solid .245 78 Part No. Brown jacket, also available in white. www.ptsupply.com marketing@ptsupply.com See referenced pages in the Hardware & Supplies section: Installation Hardware • Acme 18A Staple Gun - I-3 Suggested Prep Tool • 721 Multi-Wire Stripper/Cutter - I-9 800-238-7514 9 Sound, Security, Alarm Power Limited Alarm Wire Non-Plenum, Shielded Listed by UL as Type FPLR or FPL cable for use in NEC® Article 760 installations. Specifications Conductors Solid, bare copper Insulation Premium-grade, color-coded S-R PVC on FPLR premium. Approved thermoplastic compound on mid-cap. Shield Overall polyester-supported aluminum foil with a stranded, tinned copper wire to facilitate grounding Jacket Premium-grade red PVC suitable for use from 20°C to 75°C Suggested voltage rating of 300V Applications Wiring of fire alarms, smoke detectors, voice communications, burglar alarms and other dedicated fire protective circuits. FPLR, Cabled Conductors No. of Conductors AWG Jacket Thickness (in) Nom. O.D. (in) Weight (lbs/M-ft) 1 pair 18 .015 .160 23 4C18B1FPLRS 4 18 .015 .185 36 1P16B1FPLRS 1 pair 16 .015 .182 29 4C16B1FPLRS 4 16 .015 .210 50 1P14B1FPLRS 1 pair 14 .015 .222 43 4C14B1FPLRS 4 14 .015 .270 70 1P12B1FPLRS 1 pair 12 .015 .255 66 4C12B1FPLRS 4 12 .015 .295 107 Part No. 1P18B1FPLRS FPL “Mid Cap” Shielded These products are designed to meet the demanding lower-capacitance requirements of microprocessor-controlled fire alarm systems. No. of Conductors AWG Jacket Thickness (in) Nom. O.D. (in) Weight (lbs/M-ft) 1P18B1FPLSM 2 18 .02 .189 22 1P16B1FPLSM 2 16 .02 .212 30 Part No. For capacitance between conductors and capacitance between one conductor and other conductors connected to shield, please check with your sales representative. See referenced pages in the Hardware & Supplies section: Installation Hardware • Acme 25A or 75A Staple Gun - I-3 Suggested Prep Tool • 721 Multi-Wire Stripper/Cutter - I-9 10 www.ptsupply.com marketing@ptsupply.com 800-238-7514 Sound, Security, Alarm Power Limited Alarm Wire Non-Plenum, Unshielded Listed by UL as Type FPLR or FPL cable for use in NEC® Article 760 installations. Specifications Conductors Solid, bare copper Insulation Premium-grade, color-coded S-R PVC on FPLR premium. Approved thermoplastic compound on mid-cap. Jacket Premium-grade red PVC suitable for use from 20°C to 75°C Suggested voltage rating of 300V FPLR, Parallel Construction This is an unlimited rip design, using solid, bare copper conductors with a .032" thick PVC insulation. Conductor polarity is identified by a ridge and legend printed on the insulation of one conductor. No. of Cond. AWG Nom. O.D. (in) Weight (lbs/M-ft) Colors Avail. 2C18B1FPLR 2 18 .106 x .210 21 1,2,3,4,5 2C16B1FPLR 2 16 .125 x .223 27 1,2,3 2 Red 2C14B1FPLR 2 14 .130 x .259 41 2 3 Black 2C12B1FPLR 2 12 .172 x .286 60 2 4 Blue 5 Brown Part No. Color Chart 1 White FPLR, Cabled Conductors No. of Conductors AWG Jacket Thickness (in) Nom. O.D. (in) Weight (lbs/M-ft) 1P18B1FPLR 1 tw. pair 18 .015 .146 17 4C18B1FPLR 4 18 .015 .178 33 6C18B1FPLR 6 18 .015 .208 43 8C18B1FPLR 8 18 .015 .238 58 10C18B1FPLR 10 18 .015 .262 73 Part No. 12C18B1FPLR 12 18 .015 .285 82 1 tw. pair 16 .015 .173 24 4C16B1FPLR 4 16 .015 .205 45 1P14B1FPLR 1 tw. pair 14 .018 .200 45 4C14B1FPLR 4 14 .018 .255 65 1P12B1FPLR 1 tw. pair 12 .018 .250 53 4C12B1FPLR 4 12 .018 .294 99 1P16B1FPLR FPL “Mid Cap” These products are designed to meet the demanding lower-capacitance requirements of microprocessor-controlled fire alarm systems. No. of Conductors 1P18B1FPLM 1P16B1FPLM Part No. AWG Jacket Thickness (in) Nom. O.D. (in) Weight (lbs/M-ft) 2 18 .02 .18 22 2 16 .02 .21 32 See referenced pages in the Hardware & Supplies section: Installation Hardware • Acme 25A or 75A Staple Gun - I-3 Suggested Prep Tool • 721 Multi-Wire Stripper/Cutter - I-9 For capacitance between conductors, please check with your sales representative. www.ptsupply.com marketing@ptsupply.com 800-238-7514 11 Sound, Security, Alarm Power Limited Alarm Wire Plenum Listed by UL as Type FPLP cable for use in NEC® Article 760 installations. Specifications Conductors Solid, bare copper to ASTM B-3 Insulation Plenum-approved thermoplastic compound Shield Overall polyester-supported aluminum foil with a stranded, tinned copper wire to facilitate grounding Jacket Applications Plenum-approved compound, suitable for use from 20°C to 75°C Suggested voltage rating of 300V Wiring of fire alarms, smoke detectors, voice communications, burglar alarms and other dedicated fire protective circuits. FPLP, Unshielded Part No. No. of Cond. AWG Nom. O.D. (in) Weight (lbs/M-ft) 1P18B1FPLP 1 tw. pair 18 .140 30 4C18B1FPLP 4 18 .165 40 6C18B1FPLP 6 18 .186 46 1P16B1FPLP 1 tw. pair 16 .180 45 4C16B1FPLP 4 16 .195 55 1P14B1FPLP 1 tw. pair 14 .190 50 4C14B1FPLP 4 14 .225 80 1P12B1FPLP 1 tw. pair 12 .250 60 4C12B1FPLP 4 12 .274 100 AWG Nom. O.D. (in) Weight (lbs/M-ft) FPLP, Shielded Part No. No. of Cond. 1P18B1FPLPS 1 tw. pair 18 .145 33 4C18B1FPLPS 4 18 .170 45 1P16B1FPLPS 1 tw. pair 16 .185 48 4C16B1FPLPS 4 16 .198 60 1P14B1FPLPS 1 tw. pair 14 .195 55 4C14B1FPLPS 4 14 .230 84 1P12B1FPLPS 1 tw. pair 12 .259 65 4C12B1FPLPS 4 12 .283 114 FPLP “Mid Cap” These products are designed to meet the demanding lower-capacitance requirements of microprocessor-controlled fire alarm systems. No. of Cond. AWG Jacket Thickness (in) Nom. O.D. (in) 1P18B1FPLPM* 2 18 .015 .164 18 1P16B1FPLPM* 2 16 .015 .193 30.5 1P18B1FPPMS** 2 18 .015 .169 22.2 Part No. Weight (lbs/M-ft) See referenced pages in the Hardware & Supplies section: Installation Hardware • Acme 25A or 75A Staple Gun - I-3 Suggested Prep Tool • 721 Multi-Wire Stripper/Cutter - I-9 1P16B1FPPMS** 2 16 .015 .198 34.7 For capacitance between conductors and capacitance between one conductor *Unshielded and other conductors connected to shield, please check with your sales representative. **Shielded 12 www.ptsupply.com marketing@ptsupply.com 800-238-7514 Sound, Security, Alarm CI 2-Hour Fire-Rated Survivability Achieved With Code-Recognized Cable and Installation Practices Qualified to UL 2196 - “Standard for Tests for Fire Resistive Cables” which includes a two-hour fire exposure (accepted as representing an intense, fully-developed fire within a building), water exposure and several electrical tests and monitoring to assure its circuit integrity performance. All of this in a robust, non-armored fire alarm cable that is flexible, easy to install and requires no special procedures to meet code requirements. Features & Benefits • Recognized two-hour fire-rating • UL Listed as Type FPLR-CI • Considerable economic savings over other recognized fire rating methods • No special procedures to meet code requirements • Robust, flexible construction provides ease of installation • Lowest available capacitance rating of any standard fire alarm cable Performance • Meets National Fire Alarm Code (NFPA 72) requirements for survivability • UL Standard 1424 Cables for Power-Limited Fire Alarm Circuits • UL Standard 2196 Standard for Tests for Fire Resistive Cables • UL Standard 1666 Test for flame propagation height of electrical ... cables installed vertically in shafts Unshielded — UL Listing: NEC Type FPLR-CI Overall Diameter inch mm Copper AWG Size STRAND No. of Conductors 18 - solid 2 .330 8.4 54 80 15 48 6.7 18 - solid 4 .375 9.5 78 116 15 48 6.7 18 - solid 6 .435 11.0 107 159 15 48 6.7 18 - solid 8 .510 13.0 140 208 15 48 6.7 16 - solid 2 .350 8.9 64 95 17 56 4.2 16 - solid 4 .400 10.2 96 143 17 56 4.2 14 - 7 str 2 .390 9.9 82 122 19 62 2.6 14 - 7 str 4 .445 11.3 127 189 19 62 2.6 Weight lbs/M-ft kg/km Nominal Capacitance pf/ft pf/m DC Resistance (ohms/M-ft) 12 - 7 str 2 .425 10.8 104 155 21 69 1.7 12 - 7 str 4 .490 12.4 170 253 21 69 1.7 Shielded Overall — UL Listing: NEC Type FPLR-CI Nominal Capacitance pf/ft pf/m Copper AWG Size STRAND No. of Conductors 18 - solid 2 .310 7.9 54 80 26 85 6.7 18 - solid 4 .355 9.0 77 115 26 85 6.7 Overall Diameter inch mm Weight lbs/M-ft kg/km DC Resistance (ohms/M-ft) 18 - solid 6 .415 10.5 106 158 26 85 6.7 18 - solid 8 .490 12.4 139 207 26 85 6.7 16 - solid 2 .330 8.4 63 94 30 98 4.2 16 - solid 4 .375 9.5 96 143 30 98 4.2 14 - 7 str 2 .370 9.4 81 121 36 118 2.6 14 - 7 str 4 .425 10.8 126 188 36 118 2.6 12 - 7 str 2 .405 10.3 103 153 42 138 1.7 12 - 7 str 4 .470 11.9 168 250 42 138 1.7 www.ptsupply.com marketing@ptsupply.com See referenced pages in the Hardware & Supplies section: Installation Hardware • Acme 25A or 75A Staple Gun - I-3 Suggested Prep Tool • 721 Multi-Wire Stripper/Cutter - I-9 800-238-7514 13 Sound, Security, Alarm CIC 2-Hour Fire-Rated Maintain Circuit Integrity and Physical Protection with a Simple, In-Conduit Solution A cost-effective means of providing “survivability” as required by the National Fire Alarm Code (NFPA 72). Additionally, it can dramatically increase the reliability of any fire alarm system when it needs it the most (i.e. system is under attack by fire and water). Flexible and easy to install without the need for any special tools, hardware or instructions. Another benefit of the fire-rated construction is extremely low-capacitance, improving system performance and eliminating the need for special mid-cap cables. See referenced pages in the Hardware & Supplies section: Features & Benefits • Recognized two-hour fire-rating when installed in common 1/2" (or • • • larger) EMT conduit Maximum physical protection is provided by conduit installation Considerable economic savings over other recognized fire-rating methods Lowest available capacitance rating of any standard fire alarm cable (see data table below) Installation Hardware • Acme 25A or 75A Staple Gun - I-3 Suggested Prep Tool • 721 Multi-Wire Stripper/Cutter - I-9 Performance • Meets National Fire Alarm Code (NFPA 72) requirements for survivability • Classified two-hour fire-rating per UL Standard for Tests for Fire Resistive Cables, UL 2196, with exposure • • up to 1,850°F, immediate application of water and maintenance of full utilization voltage and electrical load throughout the test UL Listed as NEC® Type FPL Fire Alarm Cable per UL Standard #1424 and UL Listed as NEC® Type NPLF per UL Standard #1425 Electrical Circuit Protective System (FHIT) #24 of the UL Fire Resistance Directory Unshielded — Dual UL Listing: NEC Type FPLR-CIC and NEC Type NPLF Overall Diameter inch mm Copper AWG Size STRAND No. of Conductors 8 - solid 2 .33 18 - solid 4 .37 9.4 18 - solid 6 .43 10.9 18 - solid 8 .51 13.0 16 - solid 2 .33 16 - solid 4 .4 0 8.4 Weight lbs/M-ft kg/km 53 Nominal Capacitance pf/ft pf/m DC Resistance (ohms/M-ft) 79 15 48 6.5 76 113 15 48 6.5 104 155 15 48 6.5 136 202 15 48 6.5 8.4 62 92 17 56 4.1 10.2 94 140 17 56 4.1 Strand sizes 14 and 12 also available. Shielded Overall — Dual UL Listing: NEC Type FPLR-CIC and NEC Type NPLF Copper AWG Size STRAND No. of Conductors Overall Diameter inch mm Weight lbs/M-ft kg/km Nominal Capacitance pf/ft pf/m DC Resistance (ohms/M-ft) 8 - solid 2 .33 8.4 57 85 26 85 6.5 18 - solid 4 .38 9.7 81 121 26 85 6.5 18 - solid 6 .44 11.2 110 164 26 85 6.5 18 - solid 8 .51 13.0 142 211 26 85 6.5 16 - solid 2 .35 8.9 66 98 30 98 4.1 16 - solid 4 .40 10.2 99 147 30 98 4.1 Strand sizes 14 and 12 also available. 14 www.ptsupply.com marketing@ptsupply.com 800-238-7514 Sound, Security, Alarm RHH 2-Hour Fire-Rated A Low-Cost, High-Reliability Fire-Rated Cable System A cost-effective means for providing two hour fire protection as required for your most critical circuits; it replaces Mineral Insulated (MI) cable, concrete encasement or construction of unnecessary fire barriers as the optimum way to protect critical circuits against attack by fire and water. Beyond the obvious economical advantage, RHH cable can be installed in long lengths (using standard pull through fittings and labor rates), does NOT require special tools or connectors and (with proper planning) circuit expansion, replacement or resizing can readily be accomplished. See referenced pages in the Hardware & Supplies section: Features & Benefits • Recognized two-hour fire-rating • UL Listed type RHH 600V, 90°C Rating • Installs in common 1/2" (or larger) EMT conduit • Physical protection provided by conduit • LOOKS, FEELS and INSTALLS like standard RHH • No special tools, connectors or procedures • Meets requirements of NEC® Article 517 Healthcare Facilities • No cable length restrictions Performance Installation Hardware • Acme 25A or 75A Staple Gun - I-3 Suggested Prep Tool • 721 Multi-Wire Stripper/Cutter - I-9 • Exceeds fire rating requirements of NEC® Articles 695 and 700 • Classified two-hour fire rating per UL Standard for Tests for Fire Resistive Cables, UL 2196, with exposure • • up to 1,850°F, immediate application of water hose stream and maintenance of full utilization voltage and electrical load throughout the test Meets all of the requirements of UL Subject #44 for rubber-insulated Type RHH Electrical Circuit Protective System (FHIT) #25 of the UL Fire Resistance Directory Copper Size AWG/MCM No. of Strands RHH14 14 7 .045 RHH12 12 7 .045 RHH10 10 7 .045 RHH8 8 7 .060 RHH6 6 7 .060 RHH4 4 7 .060 1.52 RHH3 3 7 .060 1.52 Part No. Insulation Thickness inch mm Jacket Thickness inch mm Overall Diameter inch mm Approx. Weight lbs/M-ft kg/km Ampacity* Amps 75°C 90°C EMT Size*** 3 4 Cond. Cond. 1.14 .015 .38 .197 5.00 30 45 15** 15** 1/2" 3/4" 1.14 .015 .38 .216 5.49 40 60 20** 20** 1/2" 3/4" 1.14 .015 .38 .248 6.30 56 83 30** 30** 3/4" 3/4" 1.52 .030 .76 .337 8.56 97 144 50 55 1" 1-1/4" 1.52 .030 .76 .369 9.37 135 201 65 75 1" 1-1/4" .030 .76 .418 1.62 193 287 85 95 1-1/4" 1-1/4" .030 .76 .445 11.30 233 347 100 110 1-1/4" 1-1/2" RHH2 2 7 .060 1.52 .030 .76 .478 12.14 283 421 115 130 1-1/4" 1-1/2" RHH1 1 19 .080 2.03 .045 1.14 .590 14.99 389 579 130 150 2" 2" RHH10 1/0 19 .080 2.03 .045 1.14 .631 16.03 471 701 150 170 2-1/2" 2" RHH20 2/0 19 .080 2.03 .045 1.14 .674 17.12 571 850 175 195 2" 2-1/2" RHH30 3/0 19 .080 2.03 .045 1.14 .725 18.42 700 1,042 200 225 2" 2-1/2" 4/0 19 .080 2.03 .045 1.14 .780 19.81 855 1,272 230 260 2-1/2" 2-1/2" RHH40 When installed per UL Electrical Circuit Protective System (FHIT) #25 and all provisions of the National Electical Code (NFPA 70) * Ampacity based on three current carrying conductors in a conduit and a 30ºC (88ºF) ambient temperature. ** See national electrical code (NFPA 70) section 240-3. *** Electrical metallic tubing (EMT) per NFPA 70. For rigid metal conduit see NFPA 70, Chapter 9. NOTE: Table does not take voltage drop into consideration. www.ptsupply.com marketing@ptsupply.com 800-238-7514 15 Sound, Security, Alarm MC Cable - Fire Alarm/Control Cable™ Suitable for use in plenums, ducts or other spaces used for environmental air. Color-coded red. Standard sizes are 12-14 AWG. Specifications Armor Conductors Insulation Assembly Cover Max. Temp. Rating Galvanized Steel Interlocked Armor (Color-Coded Red) Max. Voltage Rating Copper Ground Solid Copper Nylon Thermoplastic TFN or THHN Insulation TFN and/or THHN Polyester assembly tape; optional laminated aluminum/Mylar® shield with tinned copper drain wire One or more grounding conductors may be bare or insulated green. See chart below. 300V (FPLP)/600V (MC) 430.2, 518, 530, 645, 725, 760, 760.71(D) • Federal Specification A-A59544 (formerly J-C-30B) Grounding Conductor AWG Approx. Weight/ 1,000'(lbs) Armor Min. O.D. (in) 18-2 Solid 18 bare 115 .410 18-4 Solid 18 bare 130 .430 18-6 Solid 18 bare 170 .490 18-8 Solid 18 bare 190 .510 16-2 Solid 16 bare 130 .420 16-4 Solid 16 bare 155 .440 16-6 Solid 16 bare 205 .510 16-8 Solid 16 bare 230 .520 14-2 Solid 14 green 175 .470 14-4 Solid 14 green 230 .510 14-6 Solid 14 green 250 .520 14-8 Solid 14 green 325 .585 12-2 Solid 12 green 215 .495 • NEC® Listed for Cable Tray • One-, two- and three-hour through penetration Fire Wall Rated File R-14929 • NFPA 262 (formerly UL 910) Plenum Rated - FPLP 12 green 295 .565 Tw. Shielded Pairs 12-4 Solid 18-2 Solid (1 pair) 18 tinned*** 120 .420 18-2 Solid (1 pair) & 14-2 Solid (1 pr) 14 tinned*** 290 .640 16-2 Solid (1 pair) 16 tinned*** 135 .430 16-4 Solid (2 pair) 16 tinned*** 160 .450 16-2 Solid (1 pr) & add. green ground 16 green 190 .500 16-2 Solid (1 pair) & 12-2 Solid unshielded** 12 green 280 .585 14-2 Solid (1 pair) 14 green 170 .470 14-4 Solid (2 pair) 14 green 230 .565 14-2 Solid (blue, white) 14 green 175 .470 14-2 Solid (black, red) 14 green 175 .470 14-2 Solid (orange, yellow) 14 green 175 .470 14-2 Solid (gray, gray*) 14 green 175 .470 14-4 Solid (blue, blue*, white, white*) 14 green 230 .510 14-4 Solid (black, black*, red, red*) 14 green 230 .510 www.ptsupply.com marketing@ptsupply.com C 0V 12 on du ct ol or or s Stocking Sizes Color Codes C Solid TFN • UL 62, 83, 1424, 1479, 1569, • NEC® 300.22(C), 392, 330, Specialty Colors Solid THHN References and Ratings 1581 File Reference E80042 FPLP 105°C (dry) Trade Size 16 Copper Conductors Galvanized, interlocking steel strip (red striped) MC 90°C (dry) Grounding Cable Tape 2 black, white 4 black, white, red, blue 6 black, white, red, blue, yellow, orange 8 black, white, red, blue, yellow, orange, brown, purple Note: All designations and weights are subject to normal manufacturing tolerances. * with silver stripe ** 16-2 black/white, 16-2 black/red *** Tinned copper drain/grounding conductor 800-238-7514