Feeder MC - Service Wire

advertisement
Armored Cable
Manufacturing quality. Delivering service.
Feeder MC
XHHW-2
600 Volt Copper
Description:
3 or 4 conductors, stranded, insulated with heat & moisture
resistant cross-linked polyethylene (type XHHW-2), phase identified, cabled together with suitable fillers** & green or bare ground
conductor. Cable core covered with binder tape, aluminum or
galvanized steel interlocked armor. Jacket available upon request.
Applications
Service Wire’s Feeder Size MC cable is designed to be a cost effective replacement for conduit & wire. Suitable for service, branch
& feeder circuits. Ideal for use in commercial, industrial & utility
applications. This flexible cable assembly offers: labor/time savings,
an increased resistance to mechanical damage, system design flexibility & the reliability of a factory assembled & tested cable system.
FOUR CONDUCTOR
Part Number
Size AWG
or MCM
Strand
(no.)
Standards:
• UL 1569, ICEA S-95-658/NEMA WC-70
• NEC Article 330 • Cable Tray Rated • RoHS Compliant
• 600 Volt, 90°C rated
Color coding: K1 solid colors (#8-#1). Black and Numbered (1/0 and
larger). Green ground on #1 and smaller. Bare ground on 1/0 and larger.
Features
Suitable for use in NEC hazardous locations:
• Class I, Div. 2 • Class II, Div. 2
Two-hour Firewall rated, (2/0 AWG and smaller)
For use in Theatres (Article 520), Motion Picture & TV Studios
(Article 530) & Places of Assembly with more than 100 people
Can be messenger supported (Article 330)
Insulation
Thickness
(mils)
Insulated/Bare
Copper
Grounding
Conductor(s)
(AWG)
Diameter
over Armor
(inch)
Approx. Net Wt.
per 1000 ft. (lbs.)
Alum.
Armor
Galv.
Armor
Ampacity*
(30°C
Ambient
Wet/Dry)
90°C
MC8/4
8
7
45
10
.89
416
517
44
MC6/4
6
7
45
8
1.03
591
730
60
MC4/4
4
7
45
8
1.11
823
968
76
MC3/4
3
7
45
6
1.23
1,010
1,172
88
MC2/4
2
7
45
6
1.33
1,237
1,491
104
MC1/4
1
19
55
6
1.43
1,507
1,783
120
MC1/04
1/0
19
55
6
1.43
1,789
2,047
136
MC2/04
2/0
19
55
6
1.55
2,174
2,450
156
MC3/04
3/0
19
55
4
1.65
2,700
3,011
180
MC4/04
4/0
19
55
4
1.79
3,295
3,639
208
MC250/4
250
37
65
4
1.99
4,027
4,397
232
MC300/4
300
37
65
3
2.13
4,717
5,160
256
MC350/4
350
37
65
3
2.25
5,465
5,884
280
MC400/4
400
37
65
3
2.37
6,104
6,594
304
MC500/4
500
37
65
2
2.57
7,585
8,063
344
MC600/4
600
61
80
2
2.85
9,040
9,619
380
MC750/4
750
61
80
1
3.09
11,212
11,774
428
*Per NEC Table 310-16. **Fillers used when required.
NOTE: The data shown is approximate and subject to standard industry tolerances.
NOTE: 4-Conductor ampacity assumes all four conductors are hot. If three are hot and one is a neutral, use the three conductor ampacity.