F16 Fire Detection and Alarm System

advertisement
F16
PREVENTATIVE MAINTENANCE
TECHNICAL DATA SCHEDULES
Fire Detection and Alarm System
FIRE
Activity
Type Of Service
Last Amendment Date:17/07/15
A
B
C
D
E
1
Check external alarm
Y
Y
Y
Y
2
Check following panels as applicable: Fire indicator panel, sub-indicator panel,
repeater panel, fire brigade panel, mimic panel, fire fan control panel for:
Visibility, accessibility, dust and contaminants.
Y
Y
Y
Y
3
Check battery enclosure for vented batteries.
Y
Y
Y
Y
4
Simulate an alarm condition:
Confirm that all required common or general visual and audible indicators
operate and the external alarm is activated.
Confirm the Occupant warning system is initiated.
Y
Y
Y
Y
5
Initiate an isolate/disable condition at the fire indicator panel and confirm that all
required common or general visual and audible indications operate.
Y
Y
Y
Y
6
Test the operation of each filament type visual indicators.
Y
Y
Y
Y
7
Check local control station for visibility, accessibility, door labelling and
cleanliness.
Y
Y
Y
8
Check visual warning devices for condition and damage that is likely to
adversely affect their function.
Y
Y
Y
9
Test the operation of each inhibit or auto/manual switch.
Y
Y
Y
10
Test the operation of the manual initiative switch and confirm normal system
discharge sequence.
Y
Y
Y
11
Confirm the system inoperative visual warning device operates for:
(a)Operation of service switch
(b)Fault in the discharge actuator circuit.
(c)Operation of lock-off valve.
(d)Operation of manual inhibit switch (where fitted).
(e)Isolation or fault in any part of the fire detection or control system that
prevents the automatic or electrical manual discharge of the suppression
system.
Y
Y
Y
12
Test the system logic.
Y
Y
Y
13
Test each supervised actuator circuit to ensure a fault is registered at the FIP.
Y
Y
Y
14
Test the function of each actuator and ensure that each actuator operates
correctly.
Y
Y
Y
15
Check all manual call points.
Y
Y
16
Inspect any other warning device used for alarm indicating to ensure they are in
place.
Y
Y
01/09/2016
1
12:55:25 PM
F16
PREVENTATIVE MAINTENANCE
TECHNICAL DATA SCHEDULES
Fire Detection and Alarm System
FIRE
Activity
Type Of Service
Last Amendment Date:17/07/15
A
B
C
D
E
17
Test the operation of each control.
Y
Y
18
Test the operation of each visual indicator.
Y
Y
19
Check batteries
Y
Y
20
Test detectors as specified in Appendix G of AS 1851-2012 and confirm correct
alarm zone indication.
For special hazards test all detectors.
Y
Y
21
Test the occupant warning system and check the signals are distinctly audible in
all areas of the building.
Y
Y
22
Test 20% of alarm acknowledgement facilities that have not been tested in the
last 5 years.
Y
Y
23
Undertake battery discharge test.
Y
Y
24
Test each input and output supervised circuit.
Y
25
Simulate a circuit fault condition at the FIP and confirm that all required common
or general visual and audible indications operate.
Y
26
Apply short circuits as required to verify that no more than 40 devices are
disabled by a single short circuit.
Y
27
Check power supply supervision.
Y
28
Check each collective fire detection circuit by confirming fault signal is registered
when last detector on the circuit is removed.
Y
29
Conduct a functional test with each system interface.
Y
30
Check the occupant warning system speaker circuits.
Y
31
For each monitored link check that a link loss is indicated at the monitored site.
Y
32
Test one detector of each type per circuit with alarm verification facility enabled.
Y
33
SMOKE HAZARD MANAGEMENT SYSTEMS - ADDITIONAL ACTIVITIES
CAUTION: TAKE PRECAUTIONS TO PREVENT UNACCEPTABLE
VENTILATION SYSTEM CHANGES
Y
34
Check that after initiation by a signal from the FIP, he FFCP remains operating in
the fire mode until reset by the reset switch on the FFCP.
Y
35
Check that manual override ON-AUTO-OFF control operates.
Y
36
Check the operation of the airflow fault indicator.
Y
37
Check the operation of the air handling equipment interconnecting cable open
and closed circuit faults indicators.
Y
01/09/2016
2
12:55:25 PM
F16
PREVENTATIVE MAINTENANCE
TECHNICAL DATA SCHEDULES
Fire Detection and Alarm System
FIRE
Activity
Type Of Service
Last Amendment Date:17/07/15
A
B
C
D
38
Check the operation of the electricity phase fail fault indicator
Y
39
Check the operation of the fan running, fan stopped and fan fault indicators.
Y
40
SPECIAL HAZARD SYSTEMS - ADDITIONAL ACTIVITIES
CAUTION: TAKE PRECAUTIONS TO PREVENT THE DISCHARGE OF THE
SYSTEM DURING THESE TESTS.
Y
41
Test each suppression system status monitored function.
Y
42
Simulate the system operation.
Y
43
Test and record the the system discharge sequence.
Y
44
Test the agent release detection device and confirm the operation of the agent
release is indicated at the FIP.
Y
45
SMOKE AND HEAT ALARMS
Y
Y
46
Check condition of alarms for dust and paint.
Y
Y
47
Check all alarms battery missing indicator has not operated.
Y
Y
48
Check main power ON indicator.
Y
Y
49
Check alarm test.
Y
Y
50
Check other warning devices.
Y
Y
51
Check interconnecting alarms.
Y
52
Test all alarms.
Y
53
Test operation of any other warning devices.
Y
54
Clean each alarm.
Y
55
Check battery and replace if required.
Y
56
Check alarms and replace if service life reached.
Y
57
Record results in log book.
Y
Y
Y
E
Y
Special Comments and Technical Data