KACO blueplanet 50.0 TL3
grid-tied inverter
KACO new energy
is a leader in power electronics specializing in PV inverters, performance
monitoring systems, and power supply systems for industrial rail applications. KACO new energy inverters
paired with smart modules optimized by Tigo Energy achieve increased performance and lower maintenance
costs over the life of the system. Smart modules optimized by Tigo can enable up to 30% longer strings
and achieve significant balance of system (BOS) savings.
Safer Solar
Lower BOS Costs
More Efficient O&M
Maximized Energy Harvest
Highest Power Density
Fully Integrated
Module-level disconnect remotely deactivates
modules providing additional safety and
qualifying for new rapid shutdown requirements.
Module-level monitoring to pinpoint problems.
Detailed real-time alerts and analytics.
Install more modules on any roof.
Uneven string lengths enables design flexibility.
30% lower max open circuit voltage & longer
strings. Fewer combiners, fuses & copper wiring
required.
Impedance matching
mismatch losses.
technology
eliminates
No additional hardware required for rack
mounting.
blueplanet
50.0 TL3
Model number
Energy Yield
97.5% CEC efficiency
Safety
Compliant with NEC 690 section III
for PV system AC & DC disconnection
DC Electrical Specifications
DC maximum input voltage (VDC)
DC maximum peak power operating range (MPP) (VDC)
DC operating range (VDC)
DC minimum start voltage (VDC)
DC maximum operating current (ADC)
DC maximum short circuit current per channel (ADC)
DC input overload protection
1000
480-850
200-850
250
108
165
Yes / Voltage / Current
AC Electrical Specifications
AC maximum continuous output power (W)
CEC weighted efficiency (%)
50,000
97.5
AC nominal voltage / operating range L to Neutral (VAC)
Reliability
AC and DC surge protection
NEMA 3R construction
Operations
Integrated AC & DC BOS components
Up to 75% lighter than other inverters
Integrated web server
Graphical user interface
Warranties are only as valuable as
the strength and longevity of the
manufacturer.
KACO new energy is one of the
few established inverter companies
older than the warranties they
offer.
480 / 243 to 304
AC continuous output current (A)
Frequency nominal / range (Hz)
Power factor
Total harmonic distortion (%)
Standby losses (W)
AC input terminals and conductor
Utility connection
60
60 / 60.5 to 59.3
> .99
<5
< 1.5
4 / 4-18 AWG AL Cu
Wye 4 wire (A, B, C, N)
PV System Disconnects - PSD (optional)
Integrated AC / DC disconnect
AC disconnection means
AC disconnection ratings
AC overcurrent protection devices (OCPD)
Yes
Rotary switch visible and accessible from outside of enclosure
100 A VAC Break L1-L2-L3
Current limiting inverter, OCPD provided by system integrator
AC LOTO provision
AC input terminals / conductor size
LOTO in OPEN
L1-L2-L3 N PE / 14 AWG - 1/0 Cu
DC disconnection means
DC disconnection ratings
DC LOTO provision
Rotary switch accessible from outside of enclosure
200 A breaking positive and negative
LOTO in OPEN
DC input terminals / conductor size, per channel
1 Pos and 1 Neg / 4 AWG - 300 kcmil Cu
Mechanical and Environmental Specifications
Mounting
Unit weight (lbs/kg)
Ground mount, roof mount
381 / 173
Unit dimensions HxWxD (in/mm)
53.5 x 33 x 14 / 1360 x 840 x 355
Operating temperature range (°F / °C)
(-13 to 140 / -25 to 601)
Storage temperature range (°F / °C)
Noise emissions
Humidity (%)
Enclosure rating (Inverter / PSD)
Cooling
Altitude (ft./m)
(-22 to 158 / -30 to 70)
< 58 db
0 to 95 non condensing
NEMA 3R
Forced convection with variable speed fan
8000 / 2400
Communications and user interface
Graphical user interface with 3 LED status indicators
Connectivity
Ethernet, Modbus (TCP IP), USB, RS485, S0 output
Agency approvals / Regulatory compliance
UL / IEEE / CSA / FCC
Fault signal relay
DC polarity safeguard
GFDI compliant with NEC 690.35 for use with
ungrounded PV system arrays
1
UL 1741 2nd Ed. 2010 / CSA C22.2 No. 107.1 /
IEEE 1547 / FCC Class A
Potential free normally open contact
Short circuit diode
IEC 62109-2 certified by Bureau Veritas for
residual ground fault current isolation monitor and interrupter
function.
Possible power output derate between 45-60° C
T: +1 ( 86 6 ) 5 2 2 6 7 6 5 • F: + 1 ( 5 3 0 ) 4 7 7 5 9 9 5
k a c oinf o@k a c o- n e w e n e r g y. co m • w w w . k a co - n e w e n e r g y. co m
Specifications are subject to change without notice. KACO blueplanet TL3 04/25/14