HIGH PERFORMANCE AIR CONDITIONING TELECOMMUNICATIONS CONTROL SITES Cooling Capacity from 5 to 21 kW PRODUCT DOCUMENTATION English HIWALL TT-PD-272427 - 21.07.2005 HIWALL TT HIWALL TT is the newest packaged, direct expansion, air conditioner range, with built-in air-cooled condenser, for outdoor installation. Low outdoor noise makes it especially suitable for wireless networks. Optimal application: containerised BTS/Node B, and Remote Nodes for WLL and Fibre Optic Networks, and other technological environments. The galvanised steel cabinet is fully coated with RAL7035 polyester powder, and it is designed for improved rigidity and enhanced resistance against FRONT VIEW HIWALL TT-PD-272427 - 21.07.2005 vandalism (openings, grilles & screws). On models TT 05-06-08-10-13, the larger central maintenance panel is provided with handles for easier access. An Aluminium alloy cabinet is also available The direct expansion cooling circuit is based around a high efficiency hermetic scroll compressor, and built-in air cooled condenser, equipped with pressureactuated fan speed controller. All safety devices are included and pre-set. Furthermore, HIWALL TT units offer optional features such as fresh air BACK VIEW Freecooling and High humidity control, Electric Heating, 48VDC or 230V/1Ph/50Hz Emergency Cooling, Clogged Filter alarm, new Fast Plug connectors (power supply, alarms, remote display, etc.) and an Aluminium alloy cabinet. HIWALL TT is CE marked, pre-charged with refrigerant and fully tested before delivery. 1 Contents 1 Features and Benefits 2 Model Number Description 3 Mechanical Specifications 4 Microprocessor Controls 5 Options 6 Test and Reference Norms 7 Technical Data and Performances 8 Dimensional Data The Quality Management System of Liebert-HIROSS S.p.A. High Performance Air Conditioning has been approved by Lloyd’s Register Quality Assurance to the quality management system standard ISO 9001:2000. The product conforms to European Union directives 98/37/CE (89/392/CEE; 91/368/CEE; 93/68/CEE), 89/336/CEE; 73/23/CEE. Units are supplied complete with a test certificate and conformity declaration and control component list. HIWALL TT units are CE marked as they comply with the European directives concerning mechanical, electrical and electromagnetic safety. HIWALL TT-PD-272427 - 21.07.2005 0-0 1 Features and Benefits Features and Benefits Plug and Play Easier Handling Vandal-Proof Being a packaged outdoor air conditioner especially suitable for container installation, Hiwall TT does not take up any internal room: all components are built-in and protected by the robust, vandal-proof, heavy gauge, metal cabinet. The refrigeration circuit is pre-charged with refrigerant, tuned and fully tested before delivery. No piping or refrigeration work is required on site: just prepare cut-outs in the wall - according to the template available with the documentation – and make power available. As soon as the unit is fixed on the wall with its grilles and sealed, place the remote control display in a suitable position and feed the machine: Hiwall TT is now operational. Hiwall TT can be lifted easily thanks to eyebolts on its top side, even on site, using truck-cranes. The whole refrigeration circuit is housed in the heavy gauge galvanised steel cabinet, with special IP20 openings to protect sensitive components. No external piping is required. All external screws are anti-vandal type (special head). Faster Start-Up Installation can be further speeded up using the fast plug connector option (available on request, according to the unit configuration): no wiring is requested on site, and therefore the connection can be performed even by non-skilled personnel. In case of unit replacement i.e. when the requested cooling capacity increases over the single unit capacity the fast plugs allow replacement in a few minutes. Commissioning Hiwall TT is now completely automated: auto-test performs a complete cycle - testing functions such as cooling, heating, Freecooling & alarms – without changing any pre-set value. HIWALL TT-PD-272427 - 21.07.2005 Low Noise Hiwall TT is especially suitable for urban installation within telecommunication networks. The main components - such as compressor, fans, insulation - have been selected to reduce the sound emission. Furthermore, the rigidity of the cabinet has been enhanced, in order to avoid spurious vibrations. Cost Effective Cooling The refrigeration circuit features state-of-the-art components as far as design and efficiency are concerned. A scroll compressor and plug fans – with backward curved blades – reduce the energy absorbed, while larger heat exchangers optimise airflow and minimise pressure drops. The optional Freecooling significantly reduces running cost Invest-as-you-Grow Wall cut-outs among Hiwall TT models are compatible (fixing holes are compatible as an option): This allows the user to replace the air conditioner with a more powerful one only when the installed heat load increases significantly, as typically happens within telecommunication networks, where new standards – such as UMTS – and possibly other Carriers are co-located in the same site. Continuous Operation When equipped with the optional Emergency Cooling feature, the unit does not stop operation even in the case of a mains failure: Fed either by a 48VDC emergency supply from batteries, or by 230/1/50 from an inverter/generator, Hiwall TT auto-sets its parameters to ventilate and maximise Freecooling in order to keep the indoor temperature below the shut-down limit. 1-1 2 Model Number Description Model Nomenclature / Digit Numbers 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 TT10 Family TT = Telecommunication Cooling Capacity “ kW” Nominal Cooling Capacity Technology HIWALL TT Digits 1, 2, 3, 4 - Basic Unit Hiwall TT Basic Unit Main Features: D Upflow Air Discharge D Scroll Hermetic Compressor D Thermostatic Expansion Valve D Variex - Variable Condenser Fan Speed Control D Airflow Sensor D Anti-Vandalism Cabinet D Front Maintenance Digit 5 - Free 0 = Free Digit 9 - Fresh Air Freecooling and High Humidity Control (2) 0 = No Freecooling 1 = Freecooling with Modulating Damper 2 = Freecooling with Fast Return Damper A = Freecooling with Modulating Damper and Humitemp B = Freecooling with Fast Return Damper and Humitemp (2) Metallic pre-filter is included. Digit 10 - Microprocessor Control Digit 6 - Condenser Fan Control 1 = Microface E; no Display 2 = Microface E; with Remote Display Digit 7 - Emergency Cooling and Alarm Board With Hiromatic Evolution (inclusive of RS422 with RJ Connectors) 5 = Languages SET 1, temperature control 6 = Languages SET 2, temperature control 0 = Variex 0 = No Emergency Cooling 1 = Emergency Cooling, 48 VDC Supply (DC fan) (1) 2 = Emergency Cooling, 230 VAC Supply (AC fan) (1) A = No Emergency Cooling; with Alarm Board B = Emergency Cooling; 48 VDC Supply (DC fan); with Alarm Board (1) C = Emergency Cooling; 230 VAC Supply (AC fan); with Alarm Board (1) (1) Option possible only if digit 9 is other than “0”. Digit 8 - Main Power Supply and Electric Heating 0 = 230V/1Ph/50Hz; no Electric Heating (TT05-06) 400V/3Ph/+N+PE/50Hz; no Electric Heating (TT08÷21) 1 = 230V/1Ph/50Hz; with Electric Heating (TT05-06) 400V/3Ph/+N+PE/50Hz; with Electric Heating (TT08÷21) (5) Languages SET 1: GB, F, I, D, E, P, NL, S (6) Languages SET 2: GB, PL, CZ, H, RUS, TK Digit 11 - Air Filter 0 = G3 1 = G4 2 = G3; with Clogged Filter Alarm 3 = G4; with Clogged Filter Alarm Digit 16 - Refrigerant 1 = R407C - Scroll 2 = R22 - Scroll 3 = R407C - Rotary (TT05-06) 4 = R22 - Rotary (TT05-06) Digit 17 - Special Requirements 0 = None X = Special TT 05-06: 0 = Light RAL 7035 A = Light Aluminium B = Heavy RAL 7035 C = Heavy Aluminium TT 08÷21: 0 = Heavy RAL 7035 A = Heavy Aluminium D HIWALL TT-PD-272427 - 21.07.2005 0 = No Grilles, no TT Expandability 1 = With Grilles, no TT Expandability 2 = No Grilles, with TT Expandability 3 = With Grilles, with TT Expandability Digit 13 - Cabinet On Request: D Digit 15 - Wall Grilles and TT Expandability (same wall cut-outs for the whole TT range) P = PLP and Pallet C = Cardboard and Wooden Crate S = Seaworthy D D 0 = Standard Aluminium Fins 1 = Standard Evap. Fins and Epoxy Coated Cond. Fins 2 = Epoxy Coated Evap. Fins and Standard Cond. Fins 3 = Epoxy Coated Evap. and Cond. Fins Digit 12 - Packing Accessories: Bottom Support Bracket for HIWALL TT LAN Screened Cable; MM Connectors (3m, 5m, 10m available length) Installation Template (paper, 1:1 scale) Digit 14 - Heat Exchangers (Coils) Fast Plug Connectors with Pre-Wired Cables 2-1 3 Mechanical Specifications Mechanical Specifications Construction and Panels The unit is designed to be installed outdoor, coping with the worst weather conditions. The self-supporting cabinet is made of heavy gauge galvanised steel panels, painted on both sides with RAL7035 polyester powder, insulated with polyurethane foam, fire-proof class 1. The back panel (wall side) includes integral spigots, 50mm deep. Fixed panels are secured by water-tight, aluminium rivets. All external screws are anti-vandalism type, to be opened with a special tool supplied with the unit. Metal safety grids – rated IP20 - protect the machine and prevent contact with sensitive/dangerous components. Conditioned air is delivered into the room at high-level. Extract is at mid-level. Refrigeration Circuit Evaporator Fan Condenser Coil Evaporator fans are centrifugal type, with backward curved blades (plug-type), direct driven by integral electric motors. Fans are statically and dynamically balanced with self-lubricated bearings, equipped with an air flow sensor as standard to provide an alarm in case of low air flow. Full front access for maintenance. Evaporator Coil A single, inclined coil with copper tubes and aluminium fins, having a large heat exchange surface to reduce humidity removal and increase efficiency. A galvanised steel condensate drain tray (10/10 mm thick) is provided. Air Filter The refrigeration compressor is a hermetic scroll type, complete with internal protection against overheating. A crankcase heater maintains a minimum refrigerant temperature to allow reliable start-up and operation even in very cold climate. The circuit is pre-charged with refrigerant and includes: a thermostatic expansion valve, filter dryer and sight glass, low pressure and high pressure switches and two access valves. The compressor is housed in a compartment separated from the air flow and protected by an insulated panel closed with anti-vandalism screws, accessible from the front side for complete maintenance. HIWALL TT-PD-272427 - 21.07.2005 and casing are made from corrosion-proof materials. The pressure-actuated speed regulator maintains the minimum speed needed to reject heat load from the condenser, reducing compressor cycling and outdoor noise. The condenser coil is made of copper tubes and aluminium fins, sized to allow operation even in a harsh ambient, at least up to 45ºC. It is protected by metal safety grids, rated IP20. Electrical Board The electrical board is housed in a compartment isolated from the air stream and closed by a screwed on panel. It is built in accordance with EN 60204-1 recommendations. Each power circuit (both AC and DC) is protected by an automatic switch. Two plates - three openings each - are available on the back panel of the Hiwall TT (wall side), for power and control cabling to the container: The most suitable plate can be used, according to the configuration of the unit and the position of the cable tray. The air filter is located in the cabinet, before the evaporator coil, providing filtration both for indoor and fresh air (Freecooling option), it is easily removable from the front (outdoor) side of the unit. The air filter is 48 mm deep (TT05÷13) or 60 mm (TT15÷21), pleated type with a synthetic fibre surface and metal frame, giving G3 class efficiency (CEN-EN). Connectivity Condenser Fan Hiwall TT is packed as standard on a wooden pallet with shock-proof angle pieces and a top cover made of pressed cardboard/polystyrene sandwich, protected by flexible polythene film. LAN (Local Area Networking) among several units is allowed as standard; sharing setting parameters, rotating the units during their operation, keeping units in stand-by and re-activating them when required. WAN (Wide Area Networking) is provided as an option. PLP Packing The condenser fan is of the axial type, with integral IP54 motor and internal thermal protection, statically and dynamically balanced, including sealed-for-life bearings. Blades, impeller 3-1 Mechanical Specifications Operating Conditions Ambient (outdoor) temperature from –25oC to at least 45oC (reference: indoor air temperature = 24oC). Indoor temperature from 21oC (30%R.H. to 80%R.H.) up to 32oC, 40%R.H (compressor running). Please see individual performance chart. Fig. 3a - HIWALL TT 05 - 06 - 08 - 10 - 13 - 15 - 18 - 21 (drawing not to scale) INSIDE OUTSIDE INSIDE OUTSIDE Evaporator Fan Air Supply Duct Electric Heaters Fast Plugs (on request) Electrical Panel Control Display Evaporator Coil Air Filter Air Suction Duct FC Actuator Condenser Coil Condenser Fan Compressor COMPRESSOR COOLING 3-2 FREECOOLING HIWALL TT-PD-272427 - 21.07.2005 4 Microprocessor Controls Microprocessor Controls Microface Evolution D D D D HIWALL TT is controlled by the Microface Evolution: the Main Board is housed in the electrical panel and it is connected to the remote display, to be installed in the container/room (connection cable is included). The user interface is the 3-digit back-lit display showing parameter values and relevant symbols/codes in a tree menu. It features navigation push-buttons and status leds. Both high and low priority alarms activate a visual indicator and buzzer. Input for Remote On-Off and volt-free contacts for simple remote monitoring of low and high priority alarms: high/low room temperature, high/low refrigerant pressure, fan/control failure are available. LAN management: functions provided as standard include stand-by (in case of failure or overload of the unit in operation, the second one starts automatically), automatic rotation, and cascade (division of the load among several units, through split of the proportional band). D D D (*) The self-test function automatically activates/deactivates the main components (evaporator fan, compressor, freecooling damper, heaters, alarms) without changing the pre-set parameters, to easily start-up and commission the unit. No skilled personnel are requested (*). All settings are protected through a 3-Level password system (*). Automatic restart is provided after a power failure. The Remote display is required to activate the function. Technical Data Microface Evolution - E2prom: . . . . . . . . . . . . . . . . . . . . 64 Kbit Eprom/Flash memory: . . . . . . . . 2 or 4 Mbit RAM memory space: . . . . . . . . . 256 Kbit Analogue Input: . . . . . . . . . . . . . 3 x Analog 0-10V Digital Input: . . . . . . . . . . . . . . . . 8 x Flexible Analogue multi input Analogue Output: . . . . . . . . . . . . 2 x Analogue 0-10V Digital output: . . . . . . . . . . . . . . . 7 triacs output and 2+1 relay output Time and date function buffered by LI-battery Hirobus LAN connectors: . . . . . 3 RJ45 sockets (to Microf./Hirom. LAN and Slave-Board and Microf. Display) Hironet connectors: . . . . . . . . . . 1 RJ9 socket for RS485 (direct connection to proprietary supervision) HIWALL TT-PD-272427 - 21.07.2005 4-1 5 Options Microface Board, without Remote Display Options energy efficiency of the system and reduces the running time of the compressor. Combined operation (FC + DX) is available on request. Humitemp Sensor A combined temperature + humidity sensor can be fitted, in order to avoid high indoor humidity levels in Freecooling mode, by acting on the modulating damper. SPRING / Fast Return Damper Actuator Hiwall TT can be supplied without a remote display and relevant connection cable. A service display (Microface / Hiromatic) is therefore needed to start-up and maintain the unit; then operation is completely automated, allowing remote communication through volt-free contacts. To automatically close the Freecooling damper in case of an AC power failure (DC power failure on 48VDC Emergency Cooling version), to avoid uncontrolled fresh air. Fast run time (few sec). 48VDC Emergency Cooling HIWALL TT-PD-272427 - 21.07.2005 Aluminium Alloy Cabinet Al Mg alloy, unpainted, protected during transportation by a polyethylene film. It is especially recommended for the larger TT15÷21 models to optimise the weight (TT15: 235 kg / TT18: 238 kg / TT21: 239 kg). Epoxy Coated Coils The condenser coil and/or evaporator coils are available with aluminium fins coated by epoxy film, for aggressive environments. R22 Refrigerant Alarm Board The AC mains power supply is used for the compressor, condenser fan and heaters. 48VDC is used for for evaporator fans, damper actuator and controls. Therefore, a mains failure doesn’t stop the unit. Hiwall TT continues ventilating to avoid hot spots and activates the built-in Freecooling system when the automatically optimised, emergency temperature threshold is reached. 230VAC Emergency Cooling The 400V/3Ph+N+PE/50Hz mains power supply is used for the compressor, condenser fan and heaters. 230/1/50 is used for evaporator fans, damper actuator and controls. Operation as per 48VDC Emergency Cooling. Clogged Filter Alarm All external openings are rated IP20. This feature strongly enhances the Electric heating is single step, protected by a safety thermostat with manual reset and activated according to the relevant pre-set parameter (adjustable). Heavy-duty heaters are used. This version is also available, pre-charged with R22 before delivery. Fresh Air Freecooling An integrated modulating damper opens/closes to cool the room with external fresh air, with the compressor off. The warm exhaust air is automatically rejected outside through the unit, without any additional louver. Activation parameters are adjustable. A dedicated temperature sensor is fitted in the air supply section to avoid excessively low air supply temperatures (adjustable parameter). A Metallic washable, external air pre-filter is included. Electric Heating To generate an alarm when the main air filter is dirty: the switch is factory set and adjustable on site if a different setting is needed. Giving individual High/Low priority alarms on volt-free contacts (either normally closed or normally open). Outputs are provided for the following alarms: High or Low refrigerant pressure; High room Temperature; Low room Temperature; Fan Failure, Clogged Filter alarm. Wall Grilles and TT Expandability Air distribution grilles are made of extruded aluminium; double row of adjustable fins and protection net on the supply grille, single row of adjustable fins on the intake grille. TT Expandability means same wall cut-outs for the whole TT range, including holes for fixing screws. When this option is selected, TT05÷13 are provided with larger fixing brackets to match with TT15÷21 openings. Replacing the unit with a more powerful one does not require any further wall cut-out change. When both items are selected - Wall grilles and TT Expandability - TT05÷13 units are provided with larger fixing brackets and TT15÷21 grilles, compatible with the largest model available. Installation template for Hiwall TT15÷21 has to be used. Of course, no further TT Expandability is allowed on models TT15÷21. 5-1 Options Hiromatic Evolution, Graphic Display D D D D D D Featuring a 24h graphic record of controlled parameters as well as the last 200 events occurred. A back-up battery keeps the data stored in the memory (graphic data record, alarms). SMM, Wireless SMS Communication The unit is able to send short text messages (SMS) of the its status/alarms to the display of GSM900-1800MHz mobile phones, allowing real time, cost effective maintenance. Special Packing The following options are available: Wooden crate: cardboard box with additional wooden crate Seaworthy: a wooden case for sea transportation. Horizontal Support Bracket (accessory) D D D 32 Kbyte buffer RAM integrated RS-422/485 gate to Hirolink communication manager connection (Evolution) Hiromatic System Window: system operation status at a glance Self-explanatory Icons: they are used for the Menu-Layout of the Hiromatic Evolution Online Help: Every single parameter has its own multi-page explanation (Evolution) Status Report of the latest 200 event-messages of the unit/system Four different Graphic Data Records (Evolution) Timer Mode (electronic timer included in the Software) Semi or Full Manual Mode software management including all safety devices Installation Template (paper, 1:1 scale) (accessory) To permit quick and easy cutting out of wall apertures. Fast Plug Connectors (on request) The unit is provided with fast plug connectors on the back panel, according to the configuration: AC power supply, DC power supply, alarms, control display, ground. 10m long cables are also provided. No wiring is requested on site. D D D 4-Level Passwords system to protect all the settings Ergonomic design for use also as portable device (start-up and ”flying connections” by service personnel) Multi-language menu with on-the-fly language selection Technical Data Hiromatic Evolution - Eprom/Flash memory: 2 or 4 Mbit RAM memory space: 256 Kbit Time and date function buffered by LI-battery Hirobus Lan connectors: 2 RJ45 sockets (to Microface) Hironet connectors: 2 RJ9 socket for RS422/485 (Hirolink connection towards Supervision Systems) Low-Noise TT21 Model (on request) The 58 dB(A) (*) version is available on request, for continental climates up to 40oC ambient. (*) outdoor SPL @35oC outdoor, 2m front side, Free Field. Colours (on request) Other RAL colours are available on request. Made of galvanised steel, RAL7035 colour, supports the unit during installation. Hirobus, LAN Cable (accessory) 8-poles, shielded cable, either 3 or 5 or 10 metres long, for LAN (Local Area Network) connection. 5-2 HIWALL TT-PD-272427 - 21.07.2005 6 Test and Reference Test and Reference Norms Safety D D D D Hiwall TT units are designed, manufactured and tested according to the European Union directives: 98/37/CE (formerly 89/392/CEE, 91/368/CEE, 93/68/CEE) 89/336/CEE 73/23/CEE Mark Each unit is supplied complete with individual test certificate and a declaration of conformity to the European Union directives. The units are marked “CE”. Electrical Board Design and manufacturing is compliant with EN 60204-1. Electro-Magnetic Compatibility (EMC) Hiwall TT complies with the following EMC standards: EN 50081-1, Emission (“Generic emission standard, Part 1: Residential, commercial and light industry, Jan 1992”) EN 50082-2, Immunity (“Generic immunity standard, Part 2: Industrial environment, Mar 1995”). HIWALL TT-PD-272427 - 21.07.2005 Quality The Quality Management System of Liebert-HIROSS S.p.A. High Performance Air Conditioning has been approved by Lloyd’s Register Quality Assurance to the quality management system standard ISO 9001:2000. 6-1 7 Technical Data and Performances Technical Data and Performances Tab. 7a - HIWALL TT (48VDC EFC Version) Model TT Air supply Main power supply Emergency power supply Performance Total cooling capacity (1) Sensible cooling capacity (1) Compressor-AC power input (1) Compressor-AC max current (FLA) Compressor-AC starting current (LRA) Condenser fan-AC power input (1) Condenser fan-AC max. current (FLA) Evaporator fan-DC power input (1) Evaporator fan-DC max. current (FLA) (2) Evaporator fan-DC start-up current Evaporator air flow Condenser max. air flow Freecooling max. air flow Outdoor Sound Pressure Level (3) Indoor Sound Pressure Level (3) Max. ambient temperature (4) 05 kW kW kW A A kW A kW A A m3/h m3/h m3/h dB(A) dB(A) oC 06 08 10 230V±10%/1Ph/50Hz 5,7 5,4 2,20 14,8 61 0,20 1,2 0,11 2.6 0.1 1520 2400 1300 54 51 47 5,0 5,0 1,66 11,4 47 0,20 1,2 0,11 2.6 0.1 1520 2400 1300 52 51 50 13 8,1 8,1 1,87 6 32 0,24 1,3 0,31 9.6 0.1 2.900 4.000 2.600 52 56 48 10,4 10,0 2,83 7 46 0,24 1,3 0,31 9.6 0.1 2.900 4.000 2.600 53 56 46 12,7 12,3 3,75 10 50 0,24 1,3 0,39 9.6 0.1 3.100 4.000 2.800 54 57 45 Refrigeration Circuits Compressor, type / Quantity Refrigerant Expansion device Evaporator coil, tubes / Fins material Condenser coil, tubes / Fins material - Scroll / 1 R407 C Thermostatic valve Copper / Aluminium Copper / Aluminium Filtration Main air filter - quantity / Type Efficiency (CEN (CEN-EU) EU) Pre-filter - quantity / Type - 1 / Pleated G3 1 / Aluminium Evaporator Fan Quantity / Type / Poles Driven - Condenser Fan Quantity / Type / Poles Driven / Motor protection Control system - Electric Heating Type / Steps Heating capacity Heating - max. current kW A Cabinet Frame Painting Insulation type / Thickness -/mm Overall Dimensions Width / Height / Depth Weight mm kg 15 18 21 Upflow 400V ±10% / 3Ph+N+PE / 50Hz 48VDC ±17% 15,5 15,5 4,25 13 66 0,23 1,3 0,62 19,8 0.1 4.900 4.900 3.600 56 58 47 1 / plug / - 18,3 17,6 5,19 14 74 0,23 1,3 0,62 19,8 0.1 4.900 4.900 3.600 57 59 46 20,6 19,6 5,62 16 101 0,73 3,4 0,78 19,8 0.1 5.200 6.900 3.850 62 60 45 2 / plug / Direct 1 / axial / 6 Direct / IP44 1/axial/4 Direct / IP54 variable speed Tube / 1 3,0 13,0 Finned / 1 6,0 8,7 4,5 6,5 Galvanised steel Polyester - RAL7035 Polyurethane class A1 / 10 855 / 1800 / 490 168 168 242 936 / 2.125 / 630 245 247 1.010 / 2.250 / 760 328 331 332 Notes: (1) - Reference conditions are 27 oC; 47% R.H. indoor; 35 oC outdoor. Nominal power supply. (2) - It refers to maximum speed setting. Individual factory set may be lower (see power input figures for the fan), according to the model. (3) - Measured with outdoor temperature 35 oC; 2 metres from the unit; free field conditions. (4) - Maximum outdoor temperature referred to indoor air temperature = 24 oC. HIWALL TT-PD-272427 - 21.07.2005 7-1 Technical Data and Performances Tab. 7b - HIWALL TT (AC Version: either without 48VDC EFC or with 230V/1Ph/50Hz EFC) Model TT Air supply Main power supply Emergency power supply (optional) Performance Total cooling capacity (1) Sensible cooling capacity (1) Compressor-AC power input (1) Compressor-AC max current (FLA) Compressor-AC starting current (LRA) Condenser fan-AC power input (1) Condenser fan-AC max. current (FLA) Evaporator fan-AC power input (1) Evaporator fan-AC max. current (FLA) Evaporator air flow Condenser max. air flow Freecooling max. air flow Outdoor Sound Pressure Level (2) Indoor Sound Pressure Level (2) Max. ambient temperature (3) 05 kW kW kW A A kW A kW A m3/h m3/h m3/h dB(A) dB(A) oC 06 08 13 15 18 8,1 8,1 1,87 6 32 0,24 1,3 0,37 2,5 2.900 4.000 2.600 52 56 48 5,7 5,4 2,20 14,8 61 0,20 1,2 0,14 0,7 1520 2400 1300 54 52 47 10,4 10,0 2,83 7 46 0,24 1,3 0,37 2,5 2.900 4.000 2.600 53 56 46 12,7 12,3 3,75 10 50 0,24 1,3 0,48 2,5 3.100 4.000 2.800 54 57 45 18,3 17,6 5,19 14 74 0,23 1,3 0,72 5,0 4.900 4.900 3.600 57 59 46 15,5 15,5 4,25 13 66 0,23 1,3 0,72 5,0 4.900 4.900 3.600 56 58 47 Refrigeration Circuits Compressor, type / Quantity Refrigerant Expansion device Evaporator coil, tubes / Fins material Condenser coil, tubes / Fins material - Scroll / 1 R407 C Thermostatic valve Copper / Aluminium Copper / Aluminium Filtration Main air filter - quantity / Type Efficiency (CEN-EU) (CEN EU) Pre-filter - quantity / Type - 1 / Pleated G3 1 / Aluminium (on units with Freecooling option) Evaporator Fan Quantity / Type / Poles Driven / Motor protection - Condenser Fan Quantity / Type / Poles Driven / Motor protection Control system - Electric Heating Type / Steps Heating capacity Heating - max. current kW A Cabinet Frame Painting Insulation type / Thickness -/mm Overall Dimensions Width / Height / Depth Weight mm kg 21 Upflow 400V ±10% / 3Ph+N+PE / 50Hz 230V ±10% / 1Ph / 50Hz 230V±10%/1Ph/50Hz 5,0 5,0 1,66 11,4 47 0,20 1,2 0,14 0,7 1520 2400 1300 52 52 50 10 1 / plug / 4 2 / plug / 4 Direct / IP44 Direct / IP54 1 / axial / 6 Direct / IP44 1 / axial / 6 Direct / IP54 Variable speed Tube / 1 3,0 13,0 20,6 19,6 5,62 16 101 0,73 3,4 0,88 5,0 5.200 6.900 3.850 62 60 45 1/axial/4 Finned / 1 6,0 8,7 4,5 6,5 Galvanised steel Polyester - RAL7035 Polyurethane class A1 / 10 855 / 1800 / 490 168 168 242 936 / 2.125 / 630 245 247 1.010 / 2.250 / 760 328 331 332 Notes: (1) - Reference conditions are 27 oC; 47% R.H. indoor; 35 oC outdoor. Nominal power supply. (2) - Measured with outdoor temperature 35 oC; 2 metres from the unit; free field conditions. (3) - Maximum outdoor temperature referred to indoor air temperature = 24 oC. 7-2 HIWALL TT-PD-272427 - 21.07.2005 8 Dimensional Data Dimensional Data Fig. 8a - HIWALL TT 05 - 06 (Overall Dimensions) 480 192 524 192 450 486 36 A 104 700 15 877 104 86 850 410 650 1192 410 180 1799 410 739 607 410 180 B REAR VIEW 73 SIDE SECTION 50 FRONT VIEW 15 907 TOP VIEW 907 Key A ) Holes for M8 fixing screws (5 + 5 per unit) B) Lifting eye bolt (optional) HIWALL TT-PD-272427 - 21.07.2005 8-1 Dimensional Data Fig. 8b - HIWALL TT 08 - 10 - 13 (Overall Dimensions) 15 REAR VIEW 99 630 248 272 99 271 445 865 1465 445 270 2125 445 665 445 270 55 272 548 960 74 15 SIDE SECTION 112 FRONT VIEW 600 A 105 780 105 TOP VIEW 990 27 936 27 Key A ) Holes for M8 fixing screws (5 + 5 per unit) 8-2 HIWALL TT-PD-272427 - 21.07.2005 Dimensional Data Fig. 8c - HIWALL TT 15 - 18 - 21 (Overall Dimensions) 1034 15 760 REAR VIEW 136 272 248 272 136 375 1006 445 1600 445 2250 325 445 613 112 445 538 245 95 15 SIDE SECTION 61 FRONT VIEW 132 A 800 132 TOP VIEW 27 1064 1010 27 Key A ) Holes for M8 fixing screws (5 + 5 per unit) HIWALL TT-PD-272427 - 21.07.2005 8-3 Dimensional Data Fig. 8d - HIWALL TT 05 - 06 (Individual Installation Template) (No TT Expandability) B 700 700 88,5 410 37 37 250 min. 446 min. 1000 410 410 180 250 410 90 739 331,5 180 50 37 88,5 C A = 877 = 877 = Key A ) Holes for M8 fixing screws (5 + 5 per unit) B ) Wall cut-outs for wiring. Two symmetric plates per unit are available C ) Overall dimensions 8-4 HIWALL TT-PD-272427 - 21.07.2005 Dimensional Data Fig. 8e - HIWALL TT 08 - 10 - 13 (Individual Installation Template) To be used also on optional TT 05 - 06 meant to be later replaced by TT 08 - 10 - 13 models (TT Expandability) B 800 800 80 445 13 13 250 min. 630 min. 1217 445 445 300 250 445 90 212 619 300 74 48 80 C A = 960 = 960 = Key A ) Holes for M8 fixing screws (5 + 5 per unit) B ) Wall cut-outs for wiring. Two symmetric plates per unit are available C ) Overall dimensions HIWALL TT-PD-272427 - 21.07.2005 8-5 Dimensional Data Fig. 8f - HIWALL TT 15 - 18 - 21 (Individual Installation Template) 117 13 800 800 117 13 250 min. 600 min. 1218 445 445 350 250 445 90 519 445 350 95 38 B 162 To be used also on optional TT 08 - 10 - 13 meant to be later replaced by TT 15 - 18 - 21 models (TT Expandability) C A = 1034 = 1034 = Key A ) Holes for M8 fixing screws (5 + 5 per unit) B ) Wall cut-outs for wiring. Two symmetric plates per unit are available C ) Overall dimensions 8-6 HIWALL TT-PD-272427 - 21.07.2005 Der Hersteller erklärt hiermit, dass dieses Produkt den Anforderungen der Europäischen Richtlinien gerecht wird: Le Fabricant déclare que ce produit est conforme aux directives Européennes: El Fabricante declara que este producto es conforme a las directivas Europeas: O Fabricante declara que este produto está em conformidade com as directivas Europeias: Tillverkare försäkrar härmed att denna produkt överensstämmer med Europeiska Uniones direktiv: De Fabrikant verklaart dat ditofprodukt conform de Europese richtlijnen is: Since the Liebert HIROSS Company has a policy continuous product improvement,Vaimistaja it reservesvakuuttaa the right to change and täyättää seuraavien EU--- direktiivien vaatimukset: täten, ettädesign tämä tuote specifications without previous notice. Produsent erklærer herved at dette produktet er i samsvar med EU--- direktiver: Fabrikant erklærer herved, at dette produkt opfylder kravene i EU direktiverne: Ο ΚατασÀευαστÞj δηλþνει üτι το παÃüν πÃοΪüν εßναι ÀατασÀευασmÝνο αýmφωνα mε τιj οδηγßεj τηj Ε.Ε.: 98/37/CE; 89/336/CEE; 73/23/CEE Issued by T.D.Service The Manufacturer hereby declares that this product conforms to the European Union directives: Printed in Italy by Liebert HIROSS S.p A. Il Fabbricante dichiara che questo prodotto è conforme alle direttive Europee: Issued by T.D.Service --- Printed in Italy by Liebert HIROSS S.p.A. Emerson Network Power Liebert HIROSS Headquarters Via Leonardo da Vinci, 16/18 35028 --- Piove di Sacco (PD) --- Italy tel. +39 049 9719111 fax +39 0495841257 www.liebert---hiross.com --info@liebert---hiross.com Liebert HIROSS in Europe High Performance Air Conditioning Via Leonardo da Vinci, 16/18 35028 --- Piove di Sacco (PD) tel. +39 049 9719111 fax +39 0495841257 info.hpac@liebert---hiross.com Emerson Network Power NV --- Belgium Interleuvenlaan 50 B---3001 LEUVEN tel. +32 16 380222 fax. +31 16 380227 Uninterruptible Power Supply (UPS) Via Gioacchino Rossini, 6 20098 --- San Giuliano Milanese (MI) tel. +39 02 98250 1 fax +39 02 98250337 info.ups@liebert---hiross.com Liebert HIROSS Services Via Leonardo da Vinci, 16/18 35028 --- Piove di Sacco (PD) --- Italy tel. +39 049 9719111 fax +39 0499719045 service@liebert---hiross.com Emerson Network Power GesmbH --Austria Handelskai 102 ---112 --- 1200 Wien tel. +43 1 331890 fax +43 1 331892450 Liebert HIROSS --- Czech Republic Na Pricce 72/6 --- 14200 Praha 4 tel. +42 02 41727954 fax +42 02 41718717 Emerson Network Power S.A. --- France 124 Avenue Gallieni --- 93170 Bagnolet tel. +33 1 43600177 fax +33 1 43607007 Emerson Network Power GmbH --Germany Liebigstrasse 9 --- 85551 Kirchheim tel. +49 89 9050070 fax +49 89 90500710 The Quality Management System of the High Performance Air Conditiong Division of Liebert HIROSS SpA is certified by Lloyd’s Register Quality Assurance to ISO 9001:2000 Emerson Network Power Kft. --- Hungary 1146 Budapest Erzsébet királyné útja 1/c tel. + 36 1 273 3890 fax. +36 1 422 0621, +36 1 273 3897 Emerson Network Power and Liebert HIROSS --- RUSSIA, CIS Malaya Trubetskaya Str. 8 Korp. B, 11th floor --- 119881 Moscow tel. +7 095 2329473 fax +7 0952320358 Liebert HIROSS Italia S.r.L. --- Italy Via Gioacchino Rossini, 6 20098 --- San Giuliano Milanese --- Milano tel. +39 02 982501 fax +39 02 98250273 Emerson Network Power SA --- Spain Eduardo Torroja, 23 Poligono Ind. Leganes --- 28914 Leganes --Madrid tel. +34 91 4957700 fax + 34 9149578 49 Emerson Network Power B.V. --Netherlands Rooseindsestraat 29 5705 BP HELMOND tel. +31 492 508520 fax. +31 492 508525 Emerson Network Power Sp z.o.o. Poland Ul. Konstruktorska, 11A --- PL --- 02 ---673 Warszawa tel. +48 22 5485260 fax +48 22 5485261 Emerson Network Power AG Switzerland Raeffelstrasse 29 --- 8045 Zürich tel. +41 1 456 50 60 fax +41 1 456 50 70 Emerson Network Power Ltd United Kingdom Fourth Avenue, Globe Park --- Marlow Buckinghamshire --- SL71YG tel. +44 1628 403200 fax +44 1628 403203 www.liebert--- hiross.com