STRA-07 Room Controller. Installation and maintenance manual. Content STRA-07 for Fancoils Installation preparations................................2 Controller/Display handling.........................5 Technical data..................................................5 Installation.......................................................6 Configuration..................................................6 Operating modes............................................7 Activation operating modes.........................7 Control states..................................................8 Actuators.........................................................9 Fan control.......................................................9 Forced ventilation/Condensation detector/ Frost protection..............................................10 Parameter settings.........................................10 Fläkt Woods 8713 GB 2014.04 1 Specifications are subject of alteration without further notice. STRA-07 Room Controller. Installation and maintenance manual. STRA-07 for Fancoils Installation instruction Ensure that the installation complies with local safety regulations. Information about commissioning of the product can be found in the manual ”STRA Manual”, which is available for download from www.flaktwoods.com. 1. 2. alt. 3. 4. 5. Dimensions Dimensions in mm Fläkt Woods 8713 GB 2014.04 2 Specifications are subject of alteration without further notice. STRA-07 Room Controller. Installation and maintenance manual. STRA-07 for Fancoils Wiring STRA-07 has been constructed to be as compact as possible. Therefore, the controller’s communication input is not galvanically separated from the supply voltage. This means that it is important to keep G and G0 in order, as well as the communication input’s A and B. All units that share the same transformer and communication loop must use the same transformerpole for G (terminal 10) and G0 (terminal 11). On the communication loop the A-terminal (terminal 42) should only be connected to another A-terminal and the Bterminal (terminal 43) to another B-terminal. Otherwise, there is great danger of short-circuit with damaged components as a result. Inputs AI UI CI DI Outputs DO UO PT1000-sensor, 0...50°C, accuracy +/- 0.1°C AI: PT1000-sensor, 0...100°C, accuracy +/- 0.2°C or DI: see DI below Fläkt Woods’s condensation detector, STRZ-16 Closing potential-free contact connected to +C in one end 24 V AC, max 0,5 A DO:24 V AC, max 2.0 A or AO:0.5...10 V DC, max 5 mA +C, power output for DI only...24 V DC, max 10mA, short circuit protected Fläkt Woods 8713 GB 2014.04 3 Specifications are subject of alteration without further notice. STRA-07 Room Controller. Installation and maintenance manual. Terminal 10 11 12 Designation G G0 D01 13 DO2 14 D03 20 21 22 GDO G0 D04 23 UO1 24 UO2 30 AI1 31 UI1 32 DI1 33 DI2/CI 40 41 42 43 +C AGnd A B Fläkt Woods 8713 GB 2014.04 Operation Supply voltage 24 V AC Supply voltage 0 V For forced ventilation, low speed. 24 V AC output, max 0,5 A. 24 V AC actuator is connected between terminal 12 and terminal 20, GDO. For forced ventilation, average speed. 24 V AC output, max 0,5 A. 24 V AC actuator is connected between terminal 13 and terminal 20, GDO. For forced ventilation, high speed. 24 V AC output, max 0,5 A. 24 V AC actuator is connected between terminal 13 and terminal 20, GDO 24 V AC out common for DO. Internally connected to terminal 10, G. 0 V common for UO. Internally connected to terminal 11, G0. For forced ventilation, 24 V AC output, max 0,5 A. 24 V AC actuator is connected between terminal 22 and terminal 20, GDO Control of heating (FS) or cooling via change-over. For 0...10 V DC valve actuator, max 5 mA (FS). The valve actuator’s 0…10 V control signal terminal is connected to terminal 23 and its supply terminals to terminals 10 and 11. Make sure that the reference pole G0 is connected to the correct terminal on the actuator. alternative For 24 V AC thermal actuator, max 2,0 A. The thermal actuator is connected between terminals 23 and 20, GDO. On the display, go into the parameter menu and change parameter 20 to thermal actuator. Control output heating or cooling (FS). For 0...10 V DC valve actuator, max 5 mA (FS). The valve actuator’s 0…10 V control signal terminal is connected to terminal 24 and its supply terminals to terminals 10 and 11. Make sure that the reference pole G0 is connected to the correct terminal on the actuator. alternative For 24 V AC thermal actuator, max 2,0 A. The thermal actuator is connected between terminals 24 and 20, GDO. On the display, go into the parameter menu and change parameter 20 to thermal actuator. For external room sensor, PT1000. Measuring range 0...50°C. Sensor is connected between terminals 30 and 41, AGnd. For switching between heating and cooling on a two-pipe system (Change-over). PT1000-sensor is connected between terminals 31 and 41, AGnd. Measuring range: 0...100°C. alternatively For potential-free contact. A potentialfree contact is connected between terminals 31 and 40, +C. Occupancy detector. A potential-free contact is connected between terminals 32 and 40, +C. Closed contact corresponds to occupancy. See also section Occupancy detector in the section Operating modes. Fläkt Woods’s condensation detector, STRZ-16 (FS). The sensor is connected between terminals 33 and 41, AGnd. alternative Window contact (DI). A potential-free contact is connected between terminals 33 and 40, +C. Closed contact indicates closed window. 24 V DC out common for DI and UI (with digital function) Analogue ground, reference for AI and UI (with analogue function) RS-485-Communication RS-485-Communication 4 Specifications are subject of alteration without further notice. STRA-07 Room Controller. Installation and maintenance manual. STRA-07 for Fancoils Plug-in of relay-box STRZ-14 to fan coil unit Plug-in of condensation detector Plug-in of relay-box STRZ-14 to STRA-07 QFDK, mounted in ceiling Fläkt Woods 8713 GB 2014.04 5 Specifications are subject of alteration without further notice. STRA-07 Room Controller. Installation and maintenance manual. STRA-07 for Fancoils Display handling Set point The display has the following indications: In Occupied mode, the controller operates from a heating setpoint (FS = 22°C), or a cooling setpoint (FS = 24°C) that can be changed using the INCREASE and DECREASE buttons. Pressing on INCREASE increases the current setpoint by 0.5°C with each press up to the max. limit (FS = +3°C). Pressing on DECREASE decreases the current setpoint by 0.5°C with each press down to the min. limit (FS = -3°C). Switching between heating and cooling setpoints is done automatically in the controller depending on the heating and cooling requirement. Fan control It is possible to set different parameter values in a parameter menu in the display, using the buttons on the controller. You change parameter values with the INCREASE and DECREASE buttons and confirm changes with the Occupancy button. Fan control STRA-07 has a fan button. When you press the button, a symbol is shown in the display for 10 seconds. During this time, it is possible to change the fan speed using the INCREASE/DECREASE buttons. The controller has the following positions: Auto 0 I II III Automatic control of the fan speed to maintain desired room temperature. Fan Off. Manual position with low speed. Manual position with medium speed. Manual position with high speed. In operating modes Off and Unoccupied, the fan is stopped, regardless of the setting in the display. Fläkt Woods 8713 GB 2014.04 6 Specifications are subject of alteration without further notice. STRA-07 Room Controller. Installation and maintenance manual. Technical data Supply voltage Internal consumption Ambient temperature Storage temperature Ambient humidity Protection class Communication Modbus Communication speed Built-in temperature sensor Material, casing Weight 18...30 V AC, 50...60 Hz 2.5 VA 0...50°C -20...+70°C Max 90% RH IP20 RS485 (EXOline or Modbus) with automatic detection/change-over 8 bits, 1 or 2 stop bits. Odd, even (FS) or no parity. 9600 bps (not changeable) NTC type, measuring range 0...50°C, accuracy +/-0.5°C at 15...30°C Polycarbonate, PC 110 g This product conforms with the requirements of European EMC standards CENELEC EN 61000-6-1 and EN 61000-6-3, and the requirements of European LVD standard IEC 60 730-1. It carries the CE mark. Inputs External room sensor Occupancy detector Condensation detector alt. window contact CO2 sensor PT1000-sensor, 0…50°C. Suitable sensor is Fläkt Woods STRZ-05 Closing potential-free contact. Suitable occupancy detector is Fläkt Woods STRZ-09. Fläkt Woods condensation detector STRZ-16 alt. window contact STRZ-38 resp. potential-free contact STRZ-18, CO2 sensor with built-in relay. Active sensor is also possible to use. Outputs Fan control Forced ventilation Valve actuator alt. thermal actuator Valve actuator Thermal actuator Control Actuator exercise Terminal blocks Fläkt Woods 8713 GB 2014.04 3 outputs for speed I, II and III respectively, 24 V AC, max 0.5 A 24 V AC actuator, max 0.5 A 2 outputs 0…10 V DC, max 5 mA 24 V AC, max 2.0 A Heating or cooling FS = 23 hours interval So-called lift type for cable cross-section 2.1 mm2 7 Specifications are subject of alteration without further notice. STRA-07 Room Controller. Installation and maintenance manual. STRA-07 for Fancoils Configuration The controllers are configured via the display through setting the required parameters. See section Display handling/Parameter menu. Different applications require different parameters to be set. Display: the background lighting is lit (dimmed), and the occupancy indication is shown (see the chapter Display handling). The current room temperature (or setpoint depending on the configuration) is also shown in the display. Bypass Operating modes STRA-07 has five different operating modes. Through the occupancy button you are able to switch between three of them. Occupied is the preset mode. Off Operating mode Off means that the controller is not heating or cooling, and the fans are stopped. However, the temperature must not drop below the set minimum temperature (FS=8°C). If it does, the controller will start heating, and (if a fan is used) start the fan whether it has been manually stopped or not. Operating mode Bypass means that the controller controls the room temperature in the same way as in operating mode Occupied. The output for forced ventilation is also active. After a configurable time (FS=2 hours) in Bypass, the controller automatically returns to the preset operating mode. Bypass is normally activated when the Occupancy button is pressed, via an occupancy detector or a central command. The operating mode is useful for example in conference rooms, where many people are present at the same time for a certain period of time. Display: The background lighting is not lit, and only OFF is shown in the display. Unoccupied Operating mode Unoccupied means that the room where the controller is placed is not used for an extended period of time, for example during holidays or long weekends. Both heating and cooling are disconnected and the fans are stopped within a temperature interval with configurable min/max temperatures (FS min=15°C, max=30°C). Display: The background lighting is not lit, but the current room temperature (or setpoint depending on the configuration) is shown in the display. OFF is also shown in the display. Stand-by Operating mode Stand-by means that the room is in an energy save mode and is not used at the moment. This can be during nights, weekends, evenings etc. The controller is prepared to change operating mode to Occupied (comfort) if someone enters the room (presence). The room temperature is controlled around the applicable heating and cooling setpoints, with an extended temperature interval (FS=+/-3°C). For example, if the heating setpoint=22°C and the cooling setpoint=24°C, the controller will allow the temperature in the room to be between 19°C and 27°C. The setpoints can also be adjusted +/- 3°C via the display. Display: the background lighting is lit (dimmed). The occupancy indication and the symbol for forced ventilation are shown (see the chapter Display handling). The current room temperature (or setpoint depending on the configuration) is shown in the display. Activation of the different operating modes Preset operating mode Occupied is the preset operating mode. On models without display the preset mode can be changed to Standby using dipswitch SW3. OFF (FS): Occupied, ON: Standby. This is configured in the parameter menu in the display, parameter 45. The operating mode is changed at the following events: • When the Occupancy button is pressed (if the controller has an Occupancy button). • Activation/deactivation of an occupancy detector on the digital input. • CO2 value exceeded. • Via central control, for example central time control, central booking system etc. Occupancy button Display: the background lighting is lit (dimmed). STANDBY and the current room temperature (or setpoint depending on the configuration) are shown in the display. Occupied Operating mode Occupied means that the room is in use and is therefore in a comfort mode. The controller regulates the room temperature around a heating setpoint and a cooling setpoint (FS heating setpoint=22°C, cooling setpoint=24°C). The setpoints can also be adjusted +/- 3°C locally via the display, or via a central command. Fläkt Woods 8713 GB 2014.04 8 Specifications are subject of alteration without further notice. STRA-07 Room Controller. Installation and maintenance manual. STRA-07 for Fancoils Shutdown • Cooling/Cooling When the Occupancy button is held depressed for more than 5 seconds, the controller changes operating mode to ”Shutdown” (Off/Unoccupied), regardless of the current operating mode. Via the display , you can configure which operating mode, Off or Unoccupied, should be activated on ”Shutdown”. The factory setting is that Unoccupied is activated. For the control states, UO1 is used for the left control function and UO2 is used for the right control function. For control states where only one control function is active (Heating, Heating or cooling via the change-over function, and Cooling), only UO1 is used. If you press the Occupancy button for less than 5 seconds when the controller is in operating mode Shutdown or the preset operating mode, the controller changes to operating mode Bypass. If you press the button for less than 5 seconds when the controller is in Bypass, it changes operating mode to the Preset operating mode. In control state Heating, the unit is always a heating controller and controls according to the heating setpoint plus/minus the setpoint displacement. The setpoint can be adjusted in the display. After a configurable time in Bypass (FS=2 hours), the controller returns to the preset operating mode. Like control state Heating but with change-over function, i. e. when the change-over input is active, the controller becomes a cooling controller and regulates according to the basic cooling setpoint plus/minus the setpoint displacement. See more in the section Change-over. Heating For handling of the Occupancy button in combination with central control, see the section Central control below. Occupancy detector Heating or cooling via the change-over function Heating/Heating Split output signal For local control of the operating mode between the preset operating mode and Bypass, an occupancy detector is connected. In control state Heating/Heating, the controller is always a heating controller and controls according to the basic heating setpoint plus the setpoint displacement. When the controller output signal reaches 50%, it is divided between two actuators. 0…48% of the signal is sent to actuator 1 and 52…100% of the signal is sent to actuator 2. See the figure below. When occupancy is indicated, the controller changes operating mode to Bypass. If you want to be able to enter the room temporarily without activating Bypass, for example to pick something up, you can configure a powerup delay. This means that Bypass is not activated until the power-up delay has expired. The Bypass delay can be set to a value between 0 and 60 minutes (FS=0 min). In Bypass on presence, there is a switch-off timer, which means that if there is no occupancy indication during this time (FS=10 min), the controller will return to the preset operating mode. Control states Heating/Cooling In control state Heating/Cooling, the controller functions as a heating controller when the room temperature is lower than the basic heating setpoint plus half the neutral zone. The neutral zone is the difference in temperature between the heating setpoint and the cooling setpoint. When the room temperature exceeds this limit, the controller becomes a cooling controller. There is a hysteresis of 0.1°C when the controller changes from heating to cooling controller and vice versa. When the controller is heating, it regulates according to the basic heating setpoint plus the setpoint displacement, and when it is cooling according to the basic cooling setpoint plus the setpoint adjustment. The controllers can be configured for different control states/control sequences: • Heating • Heating or cooling via the change-over function • Heating/Heating • Heating/Cooling • Heating/Cooling with VAV-control and forced supply air function • Heating/Cooling with VAV-control • Cooling Fläkt Woods 8713 GB 2014.04 9 Specifications are subject of alteration without further notice. STRA-07 Room Controller. Installation and maintenance manual. STRA-07 for Fancoils Thermal actuators When thermal actuator control has been selected, this is controlled digitally with time proportional pulses via output UO…. By pulsing, the opening degree of the actuator (and its valve) is varied. The period time (in seconds) is the sum of the on and off output times on the output. The period time is FS=60s. The controller varies the on and off output times proportionally depending on the output signal demand to the actuator. Actuator exercise All actuators are exercised. The exercise takes place at set intervals in hours (FS=23 hours interval). An opening signal is sent to the actuator for as long time as the run time has been configured. Then a closing signal is sent for as long time and the exercise is finished. Cooling In control state Cooling, the unit is always a cooling controller and controls according to the basic cooling setpoint plus the setpoint displacement. Cooling/Cooling Split output signal In control mode Cooling/Cooling, the controller always functions as a cooling controller and controls according to the basic cooling setpoint plus the setpoint displacement. When the controller output signal reaches 50%, it is divided between two actuators. 0…48% of the signal is sent to actuator 1 and 52…100% of the signal is sent to actuator 2. See the figure below. Actuators STRA-07 can be used with two types of actuators: • Analogue 0…10 V actuators • Thermal actuators The actuator type is set via the parameter menu in the display. Analogue actuators The following output signals can be set for analogue actuators: • 0…10 V (FS) • 2…10 V • 10…2 V • 10…0 V Fläkt Woods 8713 GB 2014.04 10 Specifications are subject of alteration without further notice. STRA-07 Room Controller. Installation and maintenance manual. STRA-07 for Fancoils Manual setting of speed I-III means that the speed of the fan in operating modes Stand-by, Occupied and Bypass is always the set speed. In the other operating modes, the fan is demand controlled. Fan control In STRA-07 it is possible to control a fan at the following speeds: Off, Low speed, Medium speed, High speed, Auto. The fan speed in the Auto position depends on the controller output signal and the settings for each speed. Auto control Manual control The fan can be manually controlled to work at any speed. On models with display, you press the fan button once and a fan symbol is lit for 10 seconds in the display. As long as the symbol is lit, you can change the fan speed with the INCREASE/DECREASE buttons. Models without display have a fan switch. In auto mode, you can configure if the fan should be controlled by the heating output, the cooling output, or both the heating and cooling outputs. When the selected output exceeds the start value that has been set for each speed (FS speed 1=20%, speed 2=60%, speed 3=100%), the fan is activated. It stops when the controller output signal drops below the set value minus the set hysteresis (FS=5%). When the fan speed changes, there is always a minimum delay (2-3 s) between the inactivation of the output for the current speed and the activation of the output for the new speed. Only one fan speed output is defined at a time. Off/Unoccupied In operating modes Off and Unoccupied, the fan is stopped, regardless of the position of the fan switch or the setting in the display, on condition that the temperature is within the set temperature limits. If the temperature is not within the set temperature limits, the fan will be started in the corresponding Auto position, regardless of the settings. Figure 9. Fan button on models with display Figure 10. Alter fan speed The controller has the following positions: Auto 0 I II III Fläkt Woods Automatic control of the fan speed to maintain desired room temperature. Fan Off. Manual position with low speed. Manual position with medium speed. Manual position with high speed. 8713 GB 2014.04 11 Specifications are subject of alteration without further notice. STRA-07 Room Controller. Installation and maintenance manual. STRA-07 for Fancoils Functions description Parameter Settings Change-over Change-over is a function for installations with 2-pipe systems. It makes it possible to use the same pipe for both heating and cooling, depending on requirements during for example the summer (cooling output) and the winter (heating output). Control states To activate the change-over function, control mode Heating or cooling via the change-over function should be configured. STRA-07 has an input for change-over. The input can be either of the type analogue Pt1000-sensor or a closing contact connected to a digital input (FS=Pt1000-input). The Pt1000-sensor is mounted so that it senses the temperature on the feed wire to the battery. If the temperature drops below 18°C (FS), change-over is activated and the heating output, UO1 alt. DO2/DO3 (-Tmodels), is set to cooling. When the temperature exceeds 22°C (FS) the change-over function is deactivated and the heating output is set to heating. When using a digital signal input (potential-free contact), closing the contact switches the change-over function and sets the heating output, UO1 alt. DO2/DO3 (-T-models), to cooling. On open contact, the change-over function sets the heating output to heating. STRA-07 is delivered with a number of factory settings. To acquire the desired function, the controller must be adapted to it’s specific application. This is done through the parameter menu in the display. Applications may vary and incorrectly set parameters can effect the controller and application negatively. Be sure to set the necessary parameters relevant for your application. If you experience problems, contact Fläkt Woods TSS controls. Parameter menu It is possible to set different parameter values in a parameter menu. The parameter menu is accessed by simultaneously holding the INCREASE and DECREASE buttons depressed for about 5 seconds and then pressing the INCREASE button twice. The Service indication will be displayed. First the display will show the parameter-number 1. Scroll between parameters by using the INCREASE and DECREASE buttons. Press the Occupancy button to select the desired parameter. The parameter number will be replaced by the parameter value. The value can be changed using the INCREASE and DECREASE buttons. If a button is held depressed the value will start scrolling, first slowly and then with increasing speed in 3 – 4 steps with 2 – 3 seconds between steps. Acknowledge/Regret To acknowledge and store a set parameter value, press the Occupancy button again, the display then returns to showing the parameter number. To retrieve the original value, i.e. the value before change, press the INCREASE and DECREASE buttons at the same time. The original value is shown on the display. It is also possible to control change-over via a central command. See the variable list in Part IV of this manual. Condensation detector Special input CI There is a special input (CI) on STRA-07 controllers. This input is intended for Fläkt Woods’s condensation detector, STRZ-16, and functions internally as a digital input, i. e. condensation or no condensation. When the condensation detector is activated, the cooling control is blocked and the controller is set in neutral position. When condensation ceases, the controller will start controlling from the neutral position. Return After a certain time, about 1 minute, or when the INCREASE and DECREASE buttons are pressed at the same time while in the menu, the display returns to the normal view. Exit is shown on the display after the last parameter. The parameter menu is exited by pressing the Occupancy button while in Exit. Pressing on INCREASE goes to the first parameter and pressing on DECREASE goes to the last parameter.. Window Contact When the window contact has been configurated the regulator is set to normal operation when window is closed. If the window is open, the regulator is set in mode off, heating and cooling outputs are set to 0 V and the frost protection function is activated. Frost protection STRA has built-in frost protection, which is activated when the controller is not in use. The frost protection prevents the temperature from dropping below 8°C. Return to normal fan speed and control occurs automatically when the room temperature exceeds 8°C. Fläkt Woods 8713 GB 2014.04 12 Specifications are subject of alteration without further notice. STRA-07 Room Controller. Installation and maintenance manual. STRA-07 for Fancoils Quick guide to Fläkt Woods standard applications: 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. Desired basic heating setpoint: 01 Desired basic cooling setpoint: 02 Application control state: 11 Type of temperature sensor: 15 State of function UO1 (heating output): 20 State of function UO2 (cooling output): 21 State output signal range, heating actuator: 29 State output signal range, cooling actuator: 30 Preset operating mode: 45 State operating mode by depressing occupancy button for 46 5 sec: Configuration of fan control 50 Start signal (%) for fan speed 1 51 Start signal (%) for fan speed 2 52 Start signal (%) for fan speed 3 53 Parameters The following parameters can be changed in the parameter menu (FS = Factory setting): Parameter number Description Values 1 Occupied Heating Setpoint 2 Occupied Cooling Setpoint 3 Standby Neutral Zone 4 Unoccupied Heating Setpoint 5 Unoccupied Cooling Setpoint 6 Frost protection Setpoint 7 P-Band 8 I-Time 9 Cooling Changeover difference temperature (Room and media) 10 Heating Changeover difference temperature (Room and media) 11 Heating/Cooling Functions 0=Heat, 1=Heat/Heat, 2=Heat or Cool via changeover, 3=Heat/Cool, 4=Heat/Cool with VAV and forced v'entilation, 5=Heat/Cool with VAV, 6=Cool, 7=Cool/Cool, 8=Heat/Cool with UO3, 9=Heat/Cool with Change-Over 12 Boost Mode Timer 13 P.I.R Delay Off 14 P.I.R Delay On 15 Connected sensor on AI1 0=internal, 1=external, 2=Change over sensor 16 UI1 Signal 0 = Disabled, 1 = Change over sensor digital, 2 = Change over sensor analogue 17 Connected sensor DI1 Input 0=Disabled, 1=Window contact, 3=P.I.R, 4=Change over sensor 18 Connected sensor DI2 input 0=Disabled, 1=Window Contact, 2=Condensation Sensor, 4=Change over sensor 20 Function of UO1 Signal 0=None, 1=Thermal actuator heat, 2= None, 3=Heating actuator 0...10V, 4= None, 5=On/off actuator heat, 6= None 21 Function of UO2 Signal 0= None 1= None, 2=Thermal actuator Cool, 3= None, 4=Cooling actuator 0…10V, 5= None, 6=On/off actuator cool Fläkt Woods 8713 GB 2014.04 13 Unit °C °C °C °C °C °C °C sec °C FS STRA-07 22 24 3 15 30 8 10 300 3 °C 4 3 min min min 120 10 0 0 2 3 2 3 4 Specifications are subject of alteration without further notice. STRA-07 Room Controller. Installation and maintenance manual. Parameters The following parameters can be changed in the parameter menu (FS = Factory setting): Parameter number Description 22 Function of UO3 Signal 24 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 Fläkt Woods Values 0=None, 1=Forced Vent Digital, 2=Forced Vent 3 Step Analog, 3=None, 4=Ordinary Analog output, 5=None, 6=Control of EC-fan U03 output in manual mode Actuator type for UO3 0=0-10v, 1=2-10v, 2=10-2v, 3=10-0v Heating Modulating Actuator Control 0=0-10v, 1=2-10v, 2=10-2v, 3=10-0v Cooling Modulating Actuator Control 0=0-10v, 1=2-10v, 2=10-2v, 3=10-0v Heating Thermal Actuator Time Cooling Thermal Actuator Time Travelling Time for Increase/Decrease Heating Valve 0 (Not in use) Travelling Time for Increase/Decrease Cooling Valve 0 (Not in use) Increase/Decrease NZ (Not in use) 0 Heating Valve Periodic Exercise Interval 0=inactive Cooling Valve Periodic Exercise Interval 0=inactive Hysteresis for the heating thermostat function Hysteresis for the cooling thermostat function The minimum heat output in heating mode Fan runs on low speed (Not in use) 0 Display View 0=Actual Temp Value, 1=Heating Setpoint, 2=Cooling Setpoint, 3=Average of Heating/Cooling, 4=Only Setpoint Displacement, 5=CO2, 6=Heating Setpoint + Setpoint Displacement, 7=Cooling Setpoint + Setpoint Displacement, 8=Average of Heating/Cooling Setpoints + Setpoint Displacement, 9=Calculated Flow in L/S Highest Setpoint Offset Increase Lowest Setpoint Offset Decrease Normal Mode Function 0=Off, 1=Unoccupied, 2=Stand-by, 3=Occupied Energy Saving Mode Function 0=Off, 1=Unoccupied BMS Operating Mode 0=Off, 1=Unoccupied, 2=Standby, 3=Occupied, 4=Not Used, 5=No Remote control Minimum airflow on cooling UO2 in % of 0-10V. Parameter is in use when cooling/heating mode with VAV is selected. Maximum airflow on cooling UO2 in % of 0-10V. Parameter is in use when heating/cooling mode with VAV is selected. Fan Control 0=No control, 1=Heating, 2=Cooling, 3=Both Fan Speed 1 Limit 0 Fan Speed 2 Limit 0 8713 GB 2014.04 14 Unit FS STRA-07 0 0 0 0 0 sec sec sec 60 60 120 sec 120 % hours hours °C °C % 2 23 23 2 2 0 0 0 °C °C 3 3 3 1 5 20 0 3 % % 5 60 Specifications are subject of alteration without further notice. STRA-07 Room Controller. Installation and maintenance manual. Parameters The following parameters can be changed in the parameter menu (FS = Factory setting): Parameter number Description 53 Fan Speed 3 Limit 54 Fan Start/Stop Hyst 55 Fan Speeds 56 External Temperature Sensor Calibration Gain AI1 57 Sensor Calibration Gain UI1 58 Internal Temperature Sensor Calibration Gain 59 Filter factor for AI temperature 60 Normally open/Normally closed DI1 61 Normally open/Normally closed DI2 62 Normally open/Normally closed UI1 63 Heating Manual Override 64 Cooling Manual Override 65 Forced ventilation Manual Override 66 Changeover Manual Override 67 68 69 70 Manual Mode Heating Output Manual Mode Cooling Output Modbus Address Modbus Parity 71 72 73 Modbus Timeout Modbus Response Delay Heating output 74 HMI Displacement View 75 76 Free Cooling Forced Ventilation control mode 77 P.I.R Activated Operation Mode 78 79 80 81 The Controller PLA Address. Used in EXOline The Controller ELA Address. Used in EXOline Cool output AI2 Input 82 83 84 Flow at 0 volt on AI2 (Not in use) Flow at 10 volt at AI2 (Not in use) The minimum time the valve is open when the calculation of change over is made Alarm triggers when temperature falls below Alarm triggers when temperature raise above CO2 Level to Change to Boost Mode CO2 Level below "Boost Mode CO2 Start" value to start Boost Mode Timer countdown AI CO2 Filter CO2 Sensor PPM for 0v CO2 Sensor PPM for 10v 86 87 97 98 100 104 105 Fläkt Woods 8713 GB 2014.04 Values Unit % °C °C °C °C FS STRA-07 100 5 3 0 0 0 0.2 0 1 0 2 2 2 2 % % 0 0 2 millisecond Millisecond 3 5 0 0 0 N/A 0 0 4 0 0 l/s l/s sec 0 100 60 °C °C PPM PPM 40 15 0 0 PPM PPM 0 104 0 0 0 0 0 = For N/C-actuator, 1=For N/O-actuator 0=N/O, 1=N/C 0=N/O, 1=N/C 0=, 1=Manual, 2=Auto 0=, 1=Manual, 2=Auto 0=, 1=Manual, 2=Auto 0=Heating, 1=Cooling, 2=Auto 0=None, 1=Odd, 2=Even 0 = For N/C-actuator, 1=For N/O-actuator 0=The offset, 1=The active setpoint + offset, 2=The heating setpoint + offset, 3=The cooling setpoint + offset, 4=Occupied Heating Setpoint + Offset, 5=Occupied Cooling setpoint + Offset, 6=Occupied Average + Offset 0=ON, 1=OFF 0=No Action, 1=Forced on Heat/Cool output at 100%, 2=Forced on Cool output at 100% 3=Occupied, 4=Bypass 0 0 0=N/O, 1=N/C 0=Disable, 5=CO2, 7=0-100% , 8=Flow calculation, 9=0-10V 0 0 15 Specifications are subject of alteration without further notice. STRA-07 Room Controller. Installation and maintenance manual. Parameters The following parameters can be changed in the parameter menu (FS = Factory setting): Parameter number Description 112 VAV CO2 Minimum Limit 113 VAV CO2 Maximum Limit 114 Port Mode 115 116 117 118 119 120 121 122 125 126 127 128 129 Fläkt Woods BACnet address BACnet device ID low 4 figures BACnet device ID high 3 figures BACnet Max Master Com Speed Values 0=EXOline/Modbus, 1=BACnet Above 127 = Slave 0=9600, 1=19200, 2=38400, 3=76800 (BACnet) Reset com to factory default (Modbus 9K6, 8, N, 1) The lowest output the fan will need to start (Not in 0 use) The highest speed of the fan (Not in use) 0 The Model in Regin Range 1939 = STRA-07, 1943 = STRA-04, 1945 = STRA-14 Major Version Minor Version Branch Version Revision 8713 GB 2014.04 16 Unit PPM PPM FS STRA-07 0 0 0 127 0 V 0 10 V Read Only 100 1939 Specifications are subject of alteration without further notice.