Untitled

advertisement
Report No.:
Page 2 of 65
17013446 001
Rating(s) ........................................... : For model EATON E Series DX 6000H, EATON E Series DX
6000HXL
I/P : 220-240V~, 50/60Hz, 30.0A, 1Ф
O/P: 220/230/240V~, 50/60Hz, 27A, 6kVA/4.2kW, 1Ф
For model EATON E Series DX 10000H, EATON E Series DX
10000HXL:
I/P : 220-240V~, 50/60Hz, 50.0A, 1Ф
O/P: 220/230/240V~, 50/60Hz, 46A, 10kVA/7kW,1Ф
TRF No.: IEC62040_1_1A
TRF originator: SGS Fimko
Report No.:
Page 3 of 65
17013446 001
Copy of marking plate:
Trade mark:
Caution label on UPS:
Caution label for the internal batteries:
TRF No.: IEC62040_1_1A
TRF originator: SGS Fimko
Report No.:
Page 4 of 65
17013446 001
Silkscreen for model EATON E Series DX 6000H:
TRF No.: IEC62040_1_1A
TRF originator: SGS Fimko
Report No.:
Page 5 of 65
17013446 001
Silkscreen for model EATON E Series DX 6000HXL:
TRF No.: IEC62040_1_1A
TRF originator: SGS Fimko
Report No.:
Page 6 of 65
17013446 001
Silkscreen for model EATON E Series DX 10000H:
TRF No.: IEC62040_1_1A
TRF originator: SGS Fimko
Report No.:
Page 7 of 65
17013446 001
Silkscreen for model EATON E Series DX 10000HXL:
TRF No.: IEC62040_1_1A
TRF originator: SGS Fimko
Report No.:
Page 8 of 65
17013446 001
Summary of testing:
•
Tests performed on the bench
•
Maximum ambient temperature: +40 °C
•
Tested for moderate conditions
•
EUT is designed for altitudes not exceeding 2000 m
Additional evaluation according to EN 62040-1-1 for the output voltage was measured as a function of the
input voltage for the certified supply voltage(s) including corresponding tolerances: as the output was
varied from 220/230/240V, two different range were selected to demonstrate the output character.
•
•
198 V (-10%: 220 V, which is declared by manufacturer )
254 V (+6%: 254 V, which is declared by manufacturer)
Models: EATON E Series DX 6000H, EATON E Series DX 6000HXL, EATON E Series DX 10000H and
EATON E Series DX 10000HXL:
Input voltage [V]
198
220
230
240
254
(battery mode)
198
220
230
240
254
(battery mode)
198
220
230
240
254
(battery mode)
Output voltage [V] (no load)
output voltage set "220 V"
220.1
220.0
220.0
220.0
220.5
219.8
output voltage set "230 V"
230.3
230.4
230.4
230.4
230.4
230.2
Output voltage set "240 V"
240.4
240.6
240.7
240.5
240.5
240.5
Output voltage [V] (rated load)
220.1
220.1
220.0
220.1
220.1
220.1
230.3
230.4
230.4
230.1
230.3
230.4
240.2
240.2
240.1
240.1
240.5
240.3
Unless otherwise stated, all tests performed on model EATON E Series DX 6000HXL and model EATON
E Series DX 10000HXL to represent the other similar models.
TRF No.: IEC62040_1_1A
TRF originator: SGS Fimko
Report No.:
Page 9 of 65
17013446 001
Particulars: test item vs. test requirements
Equipment mobility ..................................... :
Stationary (Castors must be locked under working condition)
Operating condition ..................................... :
Continuous
Mains supply tolerance (%) ......................... :
-10% ,+6%
Tested for IT power systems ...................... :
No
IT testing, phase-phase voltage (V) ........... :
N/A
Class of equipment ..................................... :
Class I
Mass of equipment (kg)............................... :
EATON E Series DX 6000H: 90kg
EATON E Series DX 6000HXL:35kg
EATON E Series DX 10000H: 103kg
EATON E Series DX 10000HXL: 38kg
Protection against ingress of water ............ :
IP20
Test case verdicts
Test case does not apply to the test object :
N/A
Test item does meet the requirement ........ :
P(ass)
Test item does not meet the requirement .. :
F(ail)
Testing
Date of receipt of test item ......................... :
Sep. 25. 2009
Date(s) of performance of test ................... :
Oct. 2009
General remarks:
”This report is not valid as a CB Test Report unless appended by an approved CB Testing
Laboratory and appended to a CB Test Certificate issued by an NCB in accordance with IECEE 02”.
The test result presented in this report relate only to the object(s) tested.
This report shall not be reproduced, except in full, without the written approval of the Issuing testing
laboratory.
”(see Enclosure #)" refers to additional information appended to the report.
"(see appended table)" refers to a table appended to the report.
Throughout this report a point is used as the decimal separator.
Standard IEC 62040-1-1:2002 is to be used in conjunction with IEC 60950-1:2001, which is referred to in
this TRF by "RD".
Comments:
Summary of compliance with National Differences (for explanation of codes see below):
AT, CH, DE, DK, FI, GB, HU, IT, KE, NL, NO, SE, SI, TR
AT=Austria, CH=Switzerland, DE=Germany, DK=Denmark, FI=Finland, GB=United Kingdom, HU=Hungary,
IT=Italy, KE=Kenya, NL=The Netherlands, NO=Norway, SE=Sweden, SI=Slovenia, TR=Turkey
For National Differences see end of this test report.
This report also includes 13 pages photo documents.
Factory(ies):
Santak Electronic (Shenzhen) Co.,Ltd.
No. 8 Baoshi Rd., Block 72, Bao’an District, Shenzhen, Guangdong 518101, P.R. China
TRF No.: IEC62040_1_1A
TRF originator: SGS Fimko
Report No.:
Page 10 of 65
17013446 001
General product information:
The EUT model is an on-line type uninterruptible power supply equipped with step-sinewave O/P for
general supply of office equipment.
See below block diagram for details
The UPS is designed as "Primary" type: input and output circuits and battery circuits are considered as
primary circuits and isolated from RS232 port by either double/reinforced insulation. Operator/laymen cannot
replace the internal battery and external battery cabinet.
Double/reinforced insulation provided between primary circuits or hazardous voltage to secondary circuits
and SELV circuits by application of safety isolation transformers, use of photo coupler, bridging resistors,
relays and sufficient clearances and creepage distances within the unit.
Double/reinforced insulation provided between primary circuits or hazardous voltage to secondary circuits and
SELV circuits by application of safety isolation transformers, use of photo coupler and sufficient clearances
and creepage distances within the unit.
Four castors fixed under the bottom of the UPS must be locked after installation when wired and ready for
use. Before the UPS can be moved, all external wires must be completely disconnected.
External battery cabinet rated 240VDC, 25A for model EATON E Series DX 6000HXL or 240VDC, 40A for
model EATON E Series DX 10000HXL can be provided, it shall be evaluated in the final system.
The enclosure consists of metal parts and thermoplastic front panel that is fixed to the metal chassis by metal
screws.
This report for UPS system covers 4 models of UPS (EATON E Series DX 6000H, EATON E Series DX
6000HXL, EATON E Series DX 10000H and EATON E Series DX 10000HXL).
For UPS EATON E Series DX 6000H and EATON E Series DX 6000HXL are designed with same control
logic, mains PCBs and output power except with or without internal battery and different charger board.
For UPS EATON E Series DX 10000H and EATON E Series DX 10000HXL are designed with same
control logic, mains PCBs and output power except with or without internal battery and different charger
board.
For UPS EATON E Series DX 6000H is same to EATON E Series DX 10000H except for rating for
protection device and some power components
See below table for detailed difference between four models (Other information see table 4.3 for details):
EATON E Series
DX 6000H
EATON E Series
DX 6000HXL
EATON E Series
DX 10000H
EATON E Series
DX 10000HXL
Internal batteries
240VDC/24A
(20 pieces with
7.2Ah battery
used)
None
240VDC/40A
(20 pieces with
7.2Ah battery
used)
None
Battery charger PCB
(Primary+earth)
098-03731
(normal charger)
mounted on
PSDR board
098-01386 (quick
charger)
mounted in place
of internal
batteries
098-03731
(normal charger)
mounted on
PSDR board
098-01386 (quick
charger)
mounted in place
of internal
batteries
Continued to next page.
TRF No.: IEC62040_1_1A
TRF originator: SGS Fimko
Report No.:
Page 11 of 65
PSDR board
(Primary+earth)
External battery cabinet
17013446 001
098-02191
None*
Input breaker
240VDC/25A**
32A/250VAC
098-02309
None*
240VDC/40A**
50A/250VAC
Remark:
*External battery cabinet rating “240VDC, 25A” show on the rear panel of EATON E Series DX 6000H,
“240VDC, 40A” show on the rear panel of EATON E Series DX 10000H due to the same design with other
model. In fact, no external battery cabinet were provided for EATON E Series DX 6000H and EATON E
Series DX 10000H. Double or reinforced insulation maintained between the internal bare live parts and
external accessible area protectd by an additional cover provided to cover opening for the connector and
fixed by screw.
**It will not be provided currently.
Main PCB used (others see above):
1. Input EMI PCB: 098-01093, for all models (Primary)
2. Output EMI board:098-01910 for all models (Primary)
3. CNTL PCB: 098-01094, for all models (Primary + SELV)
4. Parallel board. 098-01903
TRF No.: IEC62040_1_1A
TRF originator: SGS Fimko
Report No.:
Page 12 of 65
17013446 001
IEC 62040-1-1
Clause
Requirement – Test
Result – Remark
4
GENERAL CONDITIONS FOR TESTS
P
4.3
Components
P
1.5.1/RD
General
See below.
P
Comply with IEC 60950-1 or relevant component Components which were found
standard
to affect safety aspects comply
with the requirements of this
standard or within the safety
aspects of the relevant IEC
component standards. (See
appended table 4.3)
1.5.2/RD
1.5.4/RD
1.5.5/RD
1.5.6/RD
Evaluation and testing of components
Transformers
Interconnecting cables
Capacitors in primary circuits .......................... :
Verdict
P
Components which were found
to affect safety aspects comply
with the requirements of this
standard or within the safety
aspects of the relevant IEC
component standards. (See
appended table 4.3)
P
Transformer used is suitable for
their intended application and
complies with the relevant
requirements of the standard
and particularly Annex C.
P
Interconnecting power cord set
provided and fulfilled with the
relevant national standard. See
appended table 4.3
P
Between lines: X2 type
capacitors according to IEC
60384-14. Between lines and
PE: Y2 type capacitors
according to IEC 60384-14.
P
1.5.7/RD
Double insulation or reinforced insulation bridged
by components
N/A
1.5.7.1/RD
General
N/A
1.5.7.2/RD
Bridging capacitors
No bridging capacitors
provided.
N/A
1.5.7.3/RD
Bridging resistors
No such resistor
N/A
1.5.7.4/RD
Accessible parts
N/A
1.5.8/RD
Components in equipment for IT power systems Not applied for IT power
systems.
N/A
4.4
Power interface
TRF No.: IEC62040_1_1A
P
TRF originator: SGS Fimko
Report No.:
Page 13 of 65
17013446 001
IEC 62040-1-1
Clause
Requirement – Test
Result – Remark
1.6.1/RD
AC power distribution systems
TN power system.
P
1.6.2/RD
Input current
Highest normal load for this
equipment is the charging of
empty battery and operation
with the maximum specified
output load (see appended
table 4.4)
P
4.4
1.6.4/RD
Neutral conductor
The neutral conductor insulated
from the body throughout the
equipment.
4.5
Marking and instructions
P
4.5.1
General
P
4.5.2
Power rating
See below
P
Input rated voltage/range (V)............................ :
See page 3 for details
P
Input rated current/range (A) ............................ :
See page 3 for details
P
Input symbol for nature of supply (d.c.) ........... :
Not designed for "d.c. only".
Therefore, no such marking
required.
Input rated frequency/range (Hz) ..................... :
50/60Hz
P
Output rated voltage/range (V) ........................ :
See page 2 for details
P
Output rated current/range (A) ........................ :
Refer to the marking plates
P
Number of output phases (1φ - 3φ) with/without
neutral .............................................................. :
UPS: 1φ
No marking for provision of
neutral required.
P
Output rated active power (W) ........................ :
Refer to marking plate
P
Output rated apparent power (VA) .................. :
Refer to marking plate
P
Output symbol for nature of supply (d.c.) ........ :
No d.c. output. Therefore, no
such marking required.
Rated frequency or rated frequency range (Hz):
50/60Hz (all models)
Max. ambient operating temperature range
(°C) ................................................................... :
Not shown.
Manufacturer’s name or trademark or
identification mark ........................................... :
See page 3 for trademark.
P
Type/model or type reference .......................... :
EATON E Series DX 6000H
EATON E Series DX 6000HXL
EATON E Series DX 10000H
EATON E Series DX 10000HXL
P
Symbol for Class II equipment only ................. :
Class I equipment
TRF No.: IEC62040_1_1A
Verdict
P
N/A
N/A
P
N/A
N/A
TRF originator: SGS Fimko
Report No.:
Page 14 of 65
17013446 001
IEC 62040-1-1
Clause
4.5.3
Requirement – Test
Result – Remark
Verdict
Other symbols ................................................. :
Additional symbols or markings
do not give rise to
misunderstanding.
P
Certification marks .......................................... :
See rating label for details
P
Instructions for units with automatic
bypass/maintenance bypass, additional input
a.c. supply, or external batteries, having text
"See installation instructions before connecting
to the supply" ................................................... :
Text not required for this unit.
Safety instructions
See below.
N/A
P
Guidance for installation for operator and service User's manual with directions
person ............................................................. : regarding the maximum
ambient temperature, electrical
ratings, operation, description of
interfaces, connection to the
mains plus a note that the
overall leakage current shall not
exceed 3.5 mA.
P
Warning label with text "Isolate uninterruptible
power supply (UPS) before working on this
circuit"
The warning information is
specified in the user manual.
P
4.5.4
Main voltage adjustment ................................. :
No mains voltage adjustment
device
N/A
1.7.4/RD
Supply voltage adjustment .............................. :
No adjustment.
N/A
Methods and means of adjustment; reference to
installation instructions .................................... :
4.5.5
1.7.5/RD
Power outlets.................................................... :
TRF No.: IEC62040_1_1A
N/A
No outlet.
N/A
TRF originator: SGS Fimko
Report No.:
Page 15 of 65
17013446 001
IEC 62040-1-1
Clause
Requirement – Test
Result – Remark
4.5.6
1.7.6/RD
Fuse identification (marking, special fusing
characteristics, cross-reference) ..................... :
Fuse on PSDR board
Verdict
P
F302: FU30A/250VDC (for
model EATON E Series DX
6000H and EATON E Series
DX 6000HXL)
F301, F302:FU30A/250VDC
(for model EATON E Series DX
10000H, EATON E Series DX
10000HXL)
F303: FU30A/600VAC (for
model EATON E Series DX
6000H and EATON E Series
DX 6000HXL)
F303, F304: FU30A/600VAC
(for model EATON E Series DX
10000H and EATON E Series
DX 10000HXL)
Fuse on quick charger board
(for model EATON E Series DX
6000HXL and EATON E Series
DX 10000HXL)
Fuse F1: F8A/600V
Fuse on normal charger board
(for model EATON E Series DX
6000H and EATON E Series
DX 10000H)
Fuse(F901-F906): F10A,
250VAC
Breaker for EATON E Series
DX 6000H, EATON E Series
DX 6000HXL:32A, 400VAC
Breaker for EATON E Series
DX 10000H and EATON E
Series DX 10000HXL: 50A,
400VAC
4.5.7
1.7.7/RD
Wiring terminals
See below.
P
1.7.7.1/RD
Protective earthing and bonding terminals ...... :
Main earth connection for
supply wiring is marked on main
input screw terminal according
IEC 60417 No. 5019.
P
1.7.7.2/RD
Terminal for a.c. mains supply conductors ..... :
See page 4-7. Both input and
output terminals are marked.
P
1.7.7.3/RD
Terminals for d.c. mains supply conductors .... :
TRF No.: IEC62040_1_1A
N/A
TRF originator: SGS Fimko
Report No.:
Page 16 of 65
17013446 001
IEC 62040-1-1
Clause
Requirement – Test
Result – Remark
4.5.8
Battery terminals ............................................. :
No marking required due to
battery connectors designed in
such a way to make wrong
polarity connection impossible.
4.5.9
1.7.8/RD
Controls and indicators
See below.
1.7.8.1/RD
Identification, location and marking ..................... LEDs provided, located on the
front panel:
Verdict
N/A
P
•
Green colour:(Normal)
•
Orange colour:(battery)
•
Red colour:(fault)
P
1.7.8.2/RD
Colours ........................................................... :
See above. Colours are
acceptable due to only used for
information (no safety involved
even if disregarded).
P
1.7.8.3/RD
Symbols according to IEC 60417 ..................... :
Symbol for "standby" (No. 5009)
provided on button on the front
panel.
P
1.7.8.4/RD
Markings using figures ................................... :
Not used.
4.5.10
1.7.9/RD
Isolation of multiple power sources ................. :
Marking attached near the
breakers and connector for
external battery cabinet.
4.5.11
IT power systems
1.7.10/RD
IT power distribution systems
4.5.12
Protection in building installations
Protection against electric
shock does not rely on RCD.
N/A
4.5.13
5.1/RD
High leakage current (mA) .............................. :
Leakage current of the
equipment does not exceed
3.5 mA.
N/A
4.5.14
1.7.11/RD
Thermostats and other regulating devices
Neither thermostats nor other
regulating devices provided.
N/A
4.5.15
1.7.12/RD
Language(s) .................................................... :
User's manual and markings
are in both English. Other
language will be provided when
applying for national approval.
TRF No.: IEC62040_1_1A
N/A
Not applied for IT power
systems.
P
N/A
N/A

TRF originator: SGS Fimko
Report No.:
Page 17 of 65
17013446 001
IEC 62040-1-1
Clause
Requirement – Test
Result – Remark
4.5.16
1.7.13/RD
Durability of markings
The labels were subjected to
the permanence of marking
test. The labels were rubbed
with cloth soaked with water for
15 s and then again for 15 s
with the cloth soaked with
petroleum spirit.
Verdict
P
After this test there was no
damage to the labels. The
marking on the labels did not
fade. There was neither curling
nor lifting of the label edges.
4.5.17
1.7.14/RD
Removable parts
No required markings placed on
removable parts.
P
4.5.18
1.7.15/RD
Replaceable batteries
See information on page 3 for
details
P
Language(s) .................................................... :

4.5.19
1.7.16/RD
Operator access with a tool.............................. :
N/A
4.5.20
Battery
UPS with Integral batteries for
models Eaton E Series DX
6000H and Eaton E Series DX
10000H
P
Clearly legible information ............................... :
Warning label containing below
described information placed on
enclosure of UPS or user
manual.
P
Battery type ..................................................... :
Lead acid, type as "12Vdc/ 7Ah"
P
Nominal voltage of total battery (V) ................. :
240Vdc
P
Nominal capacity of total battery (optional) ..... :
7Ah
P
Warning label .................................................. :
Warning label of UPS with
information:
P
TRF No.: IEC62040_1_1A
a)
Chemical hazard
b)
Risk of electric shock
and energy hazard
c)
Reference for
maintenance and
disposal to user's
manual
d)
Lead acid battery inside
UPS
TRF originator: SGS Fimko
Report No.:
Page 18 of 65
17013446 001
IEC 62040-1-1
Clause
Requirement – Test
Result – Remark
Instructions ...................................................... :
Instructions of the UPS with
information:
Verdict
P
a) Maintenance and disposal
instructions
b) "Caution" statements
regarding battery hazards
c) Remark that servicing shall
be performed by personnel
knowledgeable of batteries
4.5.21
Installation instructions
5
FUNDAMENTAL DESIGN REQUIREMENTS
P
5.1
Protection against electric shock and energy hazards
P
2.1.1.2/RD
Battery compartments ..................................... :
No TNV circuits exist inside
battery compartments
N/A
2.1.1.4/RD
Access to hazardous voltage circuit wiring
No hazardous voltage circuit
wiring can be accessed by
operator.
P
2.1.1.5/RD
Energy hazards ............................................... :
No energy hazard at operator
accessible SELV interfaces
(RS-232).
P
2.1.1.6/RD
Manual controls
No conductive controls or
handles or alike provided.
5.1.1
Operator access
See below.
P
category a)
Operator access to SELV
circuits only.
P
category b)
No operator access to any of
the listed circuits and parts.
P
Access to ELV wiring
No ELV wiring in operator
accessible area.
5.1.2
2.1.1.3/RD
Detailed information regarding
external interfaces RS232 and
connection of supply and loads
provided in the user's manual.
P
N/A
N/A

Working voltage (Vpeak or Vrms); minimum
distance (mm) through insulation
5.1.3
Discharge of capacitors in the primary circuit
See appended table 5.1.3.
P
2.1.1.7/RD
Discharge of capacitors in equipment
See appended table 5.1.3.
P

Time-constant (s); measured voltage (V)......... :
5.1.4
Backfeed protection
TRF No.: IEC62040_1_1A
Backfeed protection will be
provided external to the UPS in
the final installation.

TRF originator: SGS Fimko
Report No.:
Page 19 of 65
17013446 001
IEC 62040-1-1
Clause
Requirement – Test
Result – Remark
Description of the construction ........................ :
5.1.5
Emergency switching device
5.2
Insulation
2.2.3.1/RD
Separation by double insulation or reinforced
insulation (method 1)
Verdict
N/A
RS-232 port can be considered
as emergency switching device
which can be controlled by
software. Otherwise external
breaker provided between
terminal block and external
wires.
P
P
SELV circuits separated
according to method 1.
For details see appended tables
5.2.
P
2.2.3.2/RD
Separation by earthed screen (method 2)
N/A
2.2.3.3/RD
Protection by earthing of the SELV circuit
(method 3)
N/A
5.3
Limited current circuits
2.4.1/RD
General requirements
N/A
2.4.2/RD
Limit values
N/A
No such circuits
N/A
Frequency (Hz)................................................. :

Measured current (mA) .................................... :

Measured voltage (V) ....................................... :

Measured capacitance (µF) ............................. :

2.4.3/RD
Connection of limited current circuits to other
circuits
5.4
Provisions for protective earthing
2.6/RD
Provisions for earthing and bonding
See below.
P
5.4.1
2.6.1/RD
Protective earthing
The chassis is reliably earthed
by screw terminal with
integrated star washer and
screw.
P
5.4.1
2.10/RD
Clearances, creepage distances and distances
through insulation
5.4.1
4.2.3/RD
Steady force test, 30 N
5.4.1
5.3/RD
Abnormal operating and fault conditions
TRF No.: IEC62040_1_1A
N/A
P
See appended tables 5.1.2, 5.8
and 9.
P
N/A
See appended table 8.3.
P
TRF originator: SGS Fimko
Report No.:
Page 20 of 65
17013446 001
IEC 62040-1-1
Clause
Requirement – Test
Result – Remark
5.4.2
Bonding
Metal enclosure and bonding
conductors are provided.
5.5
AC and d.c. power isolation
2.6.2/RD
Functional earthing
No functional earthing
necessary.
P
2.6.3/RD
Protective earthing and protective bonding
conductors
See below.
P
2.6.3.1/RD
General
See 2.6.3.3/RD
P
2.6.3.2/RD
Size of protective earthing conductors
Specified in the user manual
P
For model EATON E Series DX
6000H and model EATON E
Series DX 6000HXL,:
2
Maximum 30A, Min. 2.5 mm
EATON E Series DX 10000H,
EATON E Series DX 10000HXL
Maximum 50A, Min. 6mm2
P
Protective Bonding by fixing
earth terminal screw (M6) with
star washer direct to chassis.
P
P
P
2
Rated current (A), cross-sectional area (mm ),
AWG................................................................. :
2.6.3.3/RD
Verdict
Size of protective bonding conductors
2
Rated current (A), cross-sectional area (mm ),
AWG................................................................. :
P
2.6.3.4/RD
Resistance (Ω) of earthing conductors and their
terminations, test current (A)............................ :

2.6.3.5/RD
Colour of insulation........................................... :
2.6.4/RD
Terminals
P
2.6.4.1/RD
General
P
2.6.4.2/RD
Protective earthing and bonding terminals
See 2.6.3.3
P
Rated current (A), type and nominal thread
diameter (mm).................................................. :
Max. 50A, M6 screw, steel with
Zn platting.

2.6.4.3/RD
Separation of the protective earthing conductor
from protective bonding conductors
Separated PE and protective
bonding conductor used.
2.6.5/RD
Integrity of protective earthing
See below
P
2.6.5.1/RD
Interconnection of equipment
This unit has it's own earthing
connection. PE terminals of
output reliably connected to
bonding terminal of unit.
P
No switch or over-current
protective device in protective
earthing or bonding conductor.
P
2.6.5.2/RD
Components in protective earthing conductors
and protective bonding conductors
TRF No.: IEC62040_1_1A
Green/Yellow
P
N/A
TRF originator: SGS Fimko
Report No.:
Page 21 of 65
17013446 001
IEC 62040-1-1
Clause
Requirement – Test
Result – Remark
2.6.5.3/RD
Disconnection of protective earth
It is not necessary to disconnect
earthing except for the removing
of the earthed parts itself.
Verdict
P
2.6.5.4/RD
Parts that can be removed by an operator
No parts are intended to be
removed for operator.
2.6.5.5/RD
Parts removed during servicing
No parts are intended to be
removed for operator.
2.6.5.6/RD
Corrosion resistance
All safety earthing connections
are compliance with Annex J
P
2.6.5.7/RD
Screws for protective bonding
Protective Bonding by screw
terminal with star washer direct
to chassis.
P
2.6.5.8/RD
Reliance on telecommunication network or
cable distribution system
5.5.1
Disconnect devices
Building installation and
specified external protection
device which was stated in the
user manual
5.5.2
Three-phase equipment
EUT is single-phase equipment.
N/A
N/A
N/A
Interrupting neutral and phase conductors
P
N/A
N/A
5.5.3
Switch as a disconnect device
1.7.8/RD
Controls and indicators
N/A
1.7.8.1/RD
Identification, location and marking ................. :
N/A
1.7.8.2/RD
Colours ........................................................... :
N/A
1.7.8.3/RD
Symbols according to IEC 60417 ..................... :
N/A
1.7.8.4/RD
Markings using figures ................................... :
N/A
5.5.4
Multiple power sources
Only one supply connection
provided.
5.5.5
Ungrounded conductors
Ungrounded battery, the
internal battery DC supply of the
UPS can be disconnected by
the quick connectors of the
battery.
5.6
Overcurrent and earth fault protection
P
2.7.3/RD
Short-circuit backup protection
P
TRF No.: IEC62040_1_1A
See sub clause 5.5.1.
N/A
N/A
P
TRF originator: SGS Fimko
Report No.:
Page 22 of 65
17013446 001
IEC 62040-1-1
Clause
Requirement – Test
Result – Remark
2.7.4/RD
Number and location of protective devices ..... :
Over current protection by
breaker which disconnects
phase and neutral conductor.
Protection devices in the
building installation considered
to provide sufficient protection
against earth faults.
Verdict
P
2.7.5/RD
Protection by several devices
One circuit breaker
N/A
2.7.6/RD
Warning to service personnel .......................... :
See above
N/A
5.6.1
Basic requirements
Equipment relies on fuse or
circuit breaker of the wall outlet
protection of the building
installation in regard to L to N
short-circuit.
P
5.6.2
Battery circuit protection
Ungrounded batteries inside the
UPS. Protection against
overcurrent by 2 or 4 fuses in
parallel in the plus pole of the
battery supply circuit of the
UPS.
P
5.6.3
Location of protective device
The fuse is directly located
behind the supply wire of the
batteries inside the UPS.
P
There are no hazardous
conditions under any simulated
fault conditions (see appended
table 8.3).
5.6.4
Rating of protective device
See below.
P
5.3.1/RD
Protection against overload and abnormal
operation
See appended table 8.3.
P
5.7
Protection of personnel – Safety interlocks
5.7.1
Operator protection
N/A
2.8/RD
Safety interlocks
N/A
2.8.1/RD
General principles
N/A
2.8.2/RD
Protection requirements
N/A
2.8.3/RD
Inadvertent reactivation
N/A
2.8.4/RD
Fail-safe operation
N/A
2.8.5/RD
Moving parts
N/A
2.8.6/RD
Overriding
N/A
2.8.7/RD
Switches and relays
N/A
TRF No.: IEC62040_1_1A
P
TRF originator: SGS Fimko
Report No.:
Page 23 of 65
17013446 001
IEC 62040-1-1
Clause
Requirement – Test
Result – Remark
2.8.7.1/RD
Contact gaps (mm) .......................................... :
N/A
2.8.7.2/RD
Overload test
N/A
2.8.7.3/RD
Endurance test
N/A
2.8.7.4/RD
Electric strength test
2.8.8/RD
Mechanical actuators
5.7.2
Service person protection
5.7.2.1
Covers
N/A
5.7.2.2
Location and guarding of parts
N/A
5.7.2.3
Parts on doors
N/A
5.7.2.4
Component access
N/A
2.8.3/RD
Inadvertent reactivation
N/A
5.7.2.5
Moving parts
N/A
5.7.2.6
Capacitor banks
N/A
5.7.2.7
Internal batteries
5.8
2.10/RD
Clearances, creepage distances and distances through insulation
P
2.10.1/RD
General
See 2.10.3/RD, 2.10.4/RD and
2.10.5/RD.
P
2.10.2/RD
Determination of working voltage
Unit was connected to a 240 V
(maximum) TN power system
P
(see appended table 5.8)
Verdict
N/A
N/A
No adjustments or
measurements inside the
equipment are necessary while
the unit is energized.
Risk of short-circuiting
minimized by design of used
battery source and
corresponding terminals and
wiring methods used.
P
P
See appended table 5.8.
2.10.3/RD
Clearances
See below, Annex G was not
considered.
P
2.10.3.1/RD
General
Annex F/RD and minimum
clearances considered.
P
2.10.3.2/RD
Clearances in primary circuits
See appended table 5.8 and 9.
P
2.10.3.3/RD
Clearances in secondary circuits
Subclause 5.3.4/RD
considered.
N/A
2.10.3.4/RD
Measurement of transient voltage levels
Normal transient voltage
considered (overvoltage
category II for primary circuit).
N/A
TRF No.: IEC62040_1_1A
TRF originator: SGS Fimko
Report No.:
Page 24 of 65
17013446 001
IEC 62040-1-1
Clause
Requirement – Test
Result – Remark
2.10.4/RD
Creepage distances
See appended table 5.8 and 9.
P
CTI tests........................................................... :
CTI rating for all materials of
min. 100.

2.10.5/RD
Solid insulation
See below.
P
2.10.5.1/RD
Minimum distance through insulation
See appended table.
P
2.10.5.2/RD
Thin sheet material
Insulation tape of transformer ,
See Annex C for transformer
TX200 on CNTL board
P
Number of layers (pcs)..................................... :
See appended table C.2/RD.

Electric strength test
See appended table 5.8, 6, 8.2
and 9.

2.10.5.3/RD
Printed boards
N/A
Distance through insulation
N/A

Electric strength test for thin sheet insulating
material
Number of layers (pcs)..................................... :
2.10.5.4/RD
Verdict
Wound components
N/A
See only 2.10.5.2/RD
P
Number of layers (pcs)..................................... :
N/A
Two wires in contact inside wound component;
angle between 45° and 90° ............................. :
N/A
2.10.6/RD
Coated printed boards
N/A
2.10.6.1/RD
General
N/A
2.10.6.2/RD
Sample preparation and preliminary inspection
N/A
2.10.6.3/RD
Thermal cycling
N/A
2.10.6.4/RD
Thermal ageing (°C)......................................... :
N/A
2.10.6.5/RD
Electric strength test
2.10.6.6/RD
Abrasion resistance test

N/A

Electric strength test
2.10.7/RD
2.10.8/RD
Enclosed and sealed parts ............................... :
N/A
Temperature T1=T2 + Tma – Tamb +10K (°C) ..... :
N/A
Spacings filled by insulating compound ........... :
Certified sources of optical
isolator are used. No other
components applied for.
P
Electric strength test
(See appended table 5.2)

2.10.9/RD
Component external terminations
See appended table 5.8 and 9.
P
2.10.10/RD
Insulation with varying dimensions
Insulation kept homogenous
TRF No.: IEC62040_1_1A
N/A
TRF originator: SGS Fimko
Report No.:
Page 25 of 65
17013446 001
IEC 62040-1-1
Clause
Requirement – Test
5.9
External signalling circuits
Result – Remark
Verdict
N/A
No TNV circuits exist in the product, requirements not applicable to the evaluated
product
2.3/RD
TNV circuits
N/A
2.3.1/RD
Limits
N/A
Type of TNV circuits......................................... :
2.3.2/RD
Separation from other circuits and from
accessible parts
Insulation employed ......................................... :
2.3.3/RD
Separation from hazardous voltages
Insulation employed ......................................... :
2.3.4/RD
Connection of TNV circuits to other circuits

N/A

N/A

N/A
Insulation employed ......................................... :

2.3.5/RD
Test for operating voltages generated externally
N/A
5.10
2.5/RD
Limited power sources
N/A
Requirements not applicable to the evaluated product.
Inherently limited output
N/A
Impedance limited output
N/A
Overcurrent protective device limited output
N/A
Regulating network limited output under normal
operating and single fault condition
N/A
Regulating network limited output under normal
operating conditions and overcurrent protective
device limited output under single fault condition
N/A
Output voltage (V), output current (A), apparent
power (VA) ....................................................... :

Current rating of overcurrent protective device
(A) .................................................................... :

6
WIRING, CONNECTIONS AND SUPPLY
P
6.1
3.1/RD
General
P
TRF No.: IEC62040_1_1A
TRF originator: SGS Fimko
Report No.:
Page 26 of 65
17013446 001
IEC 62040-1-1
Clause
Requirement – Test
Result – Remark
3.1.1/RD
Current rating and overcurrent protection
All internal wires are UL
recognized, PVC insulated and
rated:
VW-1, 80°C/105°C,
300V/600V
Verdict
P
The wiring has gauge suitable
for the current intended to be
carried.
3.1.2/RD
3.1.3/RD
3.1.4/RD
Protection against mechanical damage
Securing of internal wiring
Insulation of conductors
Wires do not touch sharp edges
and heatsinks, which could
damage the insulation and
cause hazard.
P
Internal wires with only basic
isolation are routed so that they
are not close to any live bare
components. The wires are
secured by soldering and solder
pins (or cable ties) so that a
loosening of the terminal
connection is unlikely.
P
The insulation of the individual
conductors is suitable for the
application and the working
voltage. For the insulation
materials see sub-clause 3.1.1.
P
3.1.5/RD
Beads and ceramic insulators
See appended table 5.2
P
3.1.6/RD
Screws for electrical contact pressure
Protective bonding connections
are provided by stud with at
least two thread diameter.
P
3.1.7/RD
Insulating materials in electrical connections
Contact pressure is not
transmitted through insulating
material.
P
3.1.8/RD
Self-tapping and spaced thread screws
Not provided.
3.1.9/RD
Termination of conductors
All conductors are reliably
secured by use of solder-pins
or other mechanical means.
P
10 N pull test
Test performed and passed.
P
Sleeving on wiring
Safety relevant sleeves are long
enough to fit to wire length.
P
3.1.10/RD
TRF No.: IEC62040_1_1A
N/A
TRF originator: SGS Fimko
Report No.:
Page 27 of 65
17013446 001
IEC 62040-1-1
Clause
Requirement – Test
6.2
Connection to power
3.2.2/RD
Multiple supply connections
3.2.3/RD
Result – Remark
Verdict
P
Permanently connected equipment
Clearly marked terminals for
mains and separate connector
for external battery supply.
P
Terminals for permanent
connection to supply.
P

Number of conductors, diameter (mm) of cable
and conduits ..................................................... :
3.2.4/RD
Appliance inlets
Not used.
N/A
3.2.5/RD
Power supply cords
No power cord used
N/A
3.2.5.1/RD
AC power supply cords
N/A

Type .................................................................... : See above
2
Rated current (A), cross-sectional area (mm ),
See above
AWG....................................................................:

3.2.5.2/RD
DC power supply cords
N/A
3.2.6/RD
Cord anchorages and strain relief
N/A
3.2.7/RD
Protection against mechanical damage
N/A
3.2.8/RD
Cord guards
N/A
6.2.1
D (mm); test mass (g) ..................................... :

Radius of curvature of cord (mm) .................... :

Means of connection ....................................... :
See subclause 3.2.4/RD.
More than one supply connection ................... :
Only one mains supply
connection provided.
P
N/A
6.3
Wiring terminals for external power conductors
3.3.1/RD
Wiring terminals
3.3.2/RD
Connection of non-detachable power supply
cords
3.3.3/RD
Screw terminals
ISO type M6 used.
P
3.3.4/RD
Conductor sizes to be connected
Conductor size will be
connected according to
installation manual.
P
Rated current (A), cord/cable type, cross2
sectional area (mm ) ........................................ :
TRF No.: IEC62040_1_1A
N/A
Input and output with separate
terminals of same type
P
N/A
2
30A, 10AWG (4mm ) for Eaton
E Series DX 6000H and Eaton
E Series DX 6000H XL.
2
50A, 8AWG (6mm ) for Eaton
E Series DX 10000H and Eaton
E Series DX 10000HXL.

TRF originator: SGS Fimko
Report No.:
Page 28 of 65
17013446 001
IEC 62040-1-1
Clause
Requirement – Test
Result – Remark
3.3.5/RD
Wiring terminal sizes
See below
Rated current (A), type and nominal thread
diameter (mm) ................................................. :
ISO type M5 screw terminal
used.
Verdict
N/A

3.3.6/RD
Wiring terminals design
P
3.3.7/RD
Grouping of wiring terminals
P
3.3.8/RD
Stranded wire
7
PHYSICAL REQUIREMENTS
7.1
Enclosure
Metal enclosure not used to
carry current. Metal enclosure
completely enclosing hazardous
parts.
P
7.2
Stability
See below.
P
4.1/RD
Angle of 10°
The unit does not overbalance
P
Barrier between terminals for
each clamping unit provided.
P
P
Tilted to an angle of 10°
Test: force (N) .................................................. :
N/A
7.3
Mechanical strength
4.2.1/RD
General
Tests performed and passed.
Results see below. After tests,
unit complied with the
requirements of sub-clauses
2.1.1/RD, 2.6.1/RD and
2.10/RD.
P
4.2.2/RD
Steady force test, 10 N
10 N applied to all components
other than enclosure.
P
4.2.3/RD
Steady force test, 30 N
4.2.4/RD
Steady force test, 250 N
250 N applied to outer
enclosure.
P
4.2.5/RD
Impact test
See below.
P
Fall test
No hazard as result from steel
ball fall test.
P
Swing test
No hazard as result from steel
ball swing test.
P
4.2.6/RD
Drop test
Not required for this equipment.
N/A
4.2.7/RD
Stress relief test
Test performed at 70°C no
distortion found on front panel.
P
4.2.8/RD
Cathode ray tubes
No CRT in the unit.
Picture tube separately certified ....................... :
TRF No.: IEC62040_1_1A
P
N/A
N/A
N/A
TRF originator: SGS Fimko
Report No.:
Page 29 of 65
17013446 001
IEC 62040-1-1
Clause
Requirement – Test
Result – Remark
Verdict
4.2.9/RD
High pressure lamps
No high pressure lamp
provided.
4.2.10/RD
Wall or ceiling mounted equipment; force (N) . :
7.4
Construction details
4.3.1/RD
Edges and corners
Edges and corners of the
enclosure are rounded.
4.3.2/RD
Handles and manual controls; force (N) .......... :
No handles or manual controls
provided. No axial pull applied
to push-buttons.
N/A
4.3.3/RD
Adjustable controls
No such adjustable controls
device
N/A
4.3.4/RD
Securing of parts
Mechanical fixings in such a
way designed that they will
withstand mechanical stress
occurring in normal use.
P
4.3.5/RD
Connection of plugs and sockets
No mismating of connectors,
plugs or sockets possible.
P
4.3.6/RD
Direct plug-in equipment
Not direct plug-in type.
N/A
N/A
P
P
N/A
Dimensions (mm) of mains plug for direct
plug-in ............................................................ :
N/A
Torque and pull test of mains plug for direct
plug-in; torque (Nm); pull (N)............................ :
N/A
4.3.7/RD
Heating elements in earthed equipment
No heating elements provided.
N/A
4.3.8/RD
Batteries (see also 4.5.20)
Lead-acid battery protected
against overcharging and overdischarging by regulating
network. Performance
evaluated during the abnormal
operation test. Details see in
table 8.3.
P
4.3.9/RD
Oil and grease
Insulation in intended use not
considered to be exposed to oil
or grease.
N/A
4.3.10/RD
Dust, powders, liquids and gases
The equipment in intended use
not considered to be exposed
to dust, powders, liquids and
gases. For the ventilation of the
lead-acid battery refer to table
N.4.
P
4.3.11/RD
Containers for liquids or gases
No container for liquids or
gases provided.
TRF No.: IEC62040_1_1A
N/A
TRF originator: SGS Fimko
Report No.:
Page 30 of 65
17013446 001
IEC 62040-1-1
Clause
Requirement – Test
Result – Remark
4.3.12/RD
Flammable liquids ............................................ :
No flammable liquids provided.
Verdict
N/A
Quantity of liquid (l) .......................................... :
N/A
Flash point (°C) ................................................ :
N/A
4.3.13/RD
Radiation; type of radiation .............................. :
No hazardous radiation.
P
4.3.13.1/RD
General
See below.
P
4.3.13.2/RD
Ionizing radiation
No ionizing radiation present.
4.3.13.3/RD
N/A
Measured radiation (pA/kg) ............................. :

Measured high-voltage (kV) ............................ :

Measured focus voltage (kV) .......................... :

CRT markings ................................................. :

Effect of ultraviolet (UV) radiation on materials
No UV radiation present.
N/A
Part, property, retention after test, flammability
classification .................................................... :
N/A
4.3.13.4/RD
Human exposure to ultraviolet (UV) radiation . :
N/A
4.3.13.5/RD
Laser (including LEDs)
See below.
P
Laser class ...................................................... :
Emission of indicator LEDs far
below the limiting value of LED
Class 1.

4.3.13.6/RD
Other types ...................................................... :
7.4.1
Openings
See appended table 7.4.1.
P
7.4.2
Gas concentration
For the ventilation of the leadacid battery refer to table N.4.
P
7.4.3
Equipment movement
No castors provided.
7.5
4.7/RD
Resistance to fire
4.7.1/RD
Reducing the risk of ignition and spread of
flame
See below.
P
Method 1, selection and application of
components wiring and materials
Use of materials with the
required flammability classes.
P
N/A
P
Method 2, application of all of simulated fault
condition tests
4.7.2/RD
Conditions for a fire enclosure
TRF No.: IEC62040_1_1A
N/A
N/A
See below.
P
TRF originator: SGS Fimko
Report No.:
Page 31 of 65
17013446 001
IEC 62040-1-1
Clause
Requirement – Test
Result – Remark
4.7.2.1/RD
Parts requiring a fire enclosure
With having the following
components:
Verdict
P
1. Components in primary
circuits
2. Insulated wiring
The fire enclosure is required.
4.7.2.2/RD
Parts not requiring a fire enclosure
N/A
4.7.3/RD
Materials
4.7.3.1/RD
General
PCB rated accordingly. For
details see table 4.3.
P
4.7.3.2/RD
Materials for fire enclosures
Metal enclosure with
thermoplastic front panel. For
details see table 4.3.
P
4.7.3.3/RD
Materials for components and other parts
outside fire enclosures
See subclause 4.7.2/RD.
4.7.3.4/RD
Materials for components and other parts inside Internal components except
fire enclosures
small parts are V-2, HF-2 or
better.
P
N/A
P
Batteries have a flammability
class of HB (or better).
4.7.3.5/RD
Materials for air filter assemblies
No air filters provided.
N/A
4.7.3.6/RD
Materials used in high-voltage components
No high voltage components
provided.
N/A
7.6
Battery location
7.6.1
Accessibility and maintainability
Maintenance free batteries
used inside the UPS. The
batteries are connected by
quick connect terminals (no
necessary tightening).
7.6.2
Vibration
No requirements declared by
the battery manufacturer.
7.6.3
Distance
The temperature of the
electrolyte and the gas
emission are within the limits of
this standard (see appropriate
subclauses).
7.6.4
Insulation
No Ni-Cd battery used inside.
7.6.5
Wiring
The protection of connection
wiring complies with subclause
3/RD.
TRF No.: IEC62040_1_1A
P
P
N/A
P
N/A
P
TRF originator: SGS Fimko
Report No.:
Page 32 of 65
17013446 001
IEC 62040-1-1
Clause
Requirement – Test
Result – Remark
Verdict
7.6.6
Electrolyte spillage
Sealed maintenance free
batteries provided with an
unlikely emission of electrolyte
(VRLA type).
P
7.6.7
Ventilation
For the ventilation of the leadacid battery refer to table N.4.
P
7.6.8
Charging voltages
See appended table 8.3.
P
7.7
Temperature rise
P
Maximum temperatures
See appended table 7.7
P
4.5.2/RD
Resistance to abnormal heat
P
8
ELECTRICAL REQUIREMENTS AND SIMULATED ABNORMAL CONDITIONS
P
8.1
5.1.1/RD
General
P
8.1.1
Earth leakage current
See subclause 5.1.2/RD below.
P
5.1.2/RD
Equipment under test (EUT)
EUT has only one mains
connection. However, total
touch current is depending on
interconnected equipment.
P
5.1.7/RD
Equipment with touch current exceeding
3.5 mA ............................................................. :
Touch current of the equipment
does not exceed 3.5 mA.
P
However due to the connected
load has influence on the
overall touch current a
corresponding statement was
provided in the user’s manual.
8.1.2
Pluggable equipment type B UPS
N/A
3.2.5/RD
Power supply cords
N/A
3.2.5.1/RD
AC power supply cords
N/A

Type ................................................................. :
2

Rated current (A), cross-sectional area (mm ),
AWG................................................................. :
3.2.5.2/RD
DC power supply cords
8.2
Electric strength
5.2.1/RD
General
(see appended table 5.8)
P
5.2.2/RD
Test procedure
(see appended table 5.8)
P
TRF No.: IEC62040_1_1A
N/A
P
TRF originator: SGS Fimko
Report No.:
Page 33 of 65
17013446 001
IEC 62040-1-1
Clause
Requirement – Test
Result – Remark
8.3
Abnormal operating and fault conditions
5.3.1/RD
Protection against overload and abnormal
operation
See appended table 8.3.
5.3.2/RD
Motors
Approved source of DC fan is
used.
5.3.3/RD
Transformers
With the shorted circuit of the
main transformer TX200 on
CNTL board, no high
temperatures of the
transformers were recorded.
Verdict
P
P
N/A
P
See appended Annex C.
5.3.4/RD
Functional insulation.......................................... : The functional insulation was
short circuit. For the test results,
refer to the appended table 8.3.
P
5.3.5/RD
Electromechanical components
Refer to appended table 8.3.
P
5.3.8/RD
Compliance criteria for abnormal operating and
fault conditions
Refer to appended table 8.3.
8.3.1
Simulation of faults
None of the listed components
are provided.
N/A
8.3.2
Conditions for tests
No fire occurred. Electric
strength tests applied between
primary and secondary, and
respectively chassis, passed.
P
P
9
CONNECTION TO TELECOMMUNICATION NETWORKS
N/A
6.1/RD
Protection of telecommunication network service persons, and users of other
equipment connected to the network, from hazards in the equipment
N/A
6.1.1/RD
Protection from hazardous voltages
N/A
6.1.2/RD
Separation of the telecommunication network from earth
N/A
6.1.2.1/RD
Requirements
N/A
Test voltage (V) ............................................... :

Current in the test circuit (mA) ...................... :

6.1.2.2/RD
Exclusions ........................................................ :
N/A
6.2/RD
Protection of equipment users from overvoltages on telecommunication networks
N/A
6.2.1/RD
Separation requirements
N/A
6.2.2/RD
Electric strength test procedure
N/A
6.2.2.1/RD
Impulse test
N/A
6.2.2.2/RD
Steady-state test
N/A
TRF No.: IEC62040_1_1A
TRF originator: SGS Fimko
Report No.:
Page 34 of 65
17013446 001
IEC 62040-1-1
Clause
Requirement – Test
Result – Remark
Verdict
6.2.2.3/RD
Compliance criteria
N/A
6.3/RD
Protection of the telecommunication wiring system from overheating
N/A
Max. output current (A) .................................... :

Current limiting method .................................... :

1.4.8/RD
Normal operating voltages .............................. :
N/A
1.4.11/RD
Power from a telecommunication network ...... :
N/A
2.1.1/RD
Protection in operator access areas
N/A
2.1.1.1/RD
Access to energized parts
N/A
Test by inspection ........................................... :
N/A
Test with test finger ......................................... :
N/A
Test with test pin ............................................. :
N/A
Test with test probe ......................................... :
N/A
2.1.1.2/RD
Battery compartments ..................................... :
N/A
2.1.3/RD
Protection in restricted access locations
N/A
2.3/RD
TNV circuits
N/A
2.3.1/RD
Limits
N/A
Type of TNV circuits......................................... :
2.3.2/RD
Separation from other circuits and from
accessible parts
Insulation employed ......................................... :
2.3.3/RD
Separation from hazardous voltages
Insulation employed ......................................... :
2.3.4/RD
Connection of TNV circuits to other circuits

N/A

N/A

N/A
Insulation employed ......................................... :

2.3.5/RD
Test for operating voltages generated externally
N/A
2.6.1/RD
Protective earthing
N/A
2.6.5.8/RD
Reliance on telecommunication network or
cable distribution system
N/A
2.9.5/RD
Grade of insulation
N/A
2.10.3.3/RD
Clearances in secondary circuits
N/A
2.10.3.4/RD
Measurement of transient voltage levels
N/A
2.10.4/RD
Creepage distances
N/A
3.5/RD
Interconnection of equipment
N/A
3.5.1/RD
General requirements
N/A
TRF No.: IEC62040_1_1A
TRF originator: SGS Fimko
Report No.:
Page 35 of 65
17013446 001
IEC 62040-1-1
Clause
Requirement – Test
Result – Remark
3.5.2/RD
Types of interconnection circuits....................... :
N/A
M/RD
ANNEX M, CRITERIA FOR TELEPHONE RINGING SIGNALS (see 2.3.1/RD)
N/A
M.1/RD
Introduction
N/A
M.2 /RD
Method A
N/A
M.3/RD
Method B
N/A
M.3.1/RD
Ringing signal
N/A
M.3.1.1/RD
Frequency (Hz) ................................................ :

M.3.1.2/RD
Voltage (V) ...................................................... :

M.3.1.3/RD
Cadence; time (s), voltage (V) ........................ :

M.3.1.4/RD
Single fault current (mA) .................................. :

M.3.2/RD
Tripping device and monitoring voltage ........... :
N/A
M.3.2.1/RD
Conditions for use of a tripping device or a
monitoring voltage
N/A
M.3.2.2/RD
Tripping device
N/A
M.3.2.3/RD
Monitoring voltage (V) ...................................... :
N/A
A/RD
ANNEX A, TESTS FOR RESISTANCE TO HEAT AND FIRE
P
A.1/RD
Flammability test for fire enclosures of movable equipment having a total mass
exceeding 18 kg, and of stationary equipment (see 4.7.3.2/RD)
P
A.1.1/RD
Samples ........................................................... :

Wall thickness (mm) ........................................ :

A.1.2/RD
Conditioning of samples; temperature (°C)...... :
N/A
A.1.3/RD
Mounting of samples ........................................ :
N/A
A.1.4/RD
Test flame (see IEC 60695-11-3)
N/A

Flame A, B, C or D .......................................... :
A.1.6/RD
Verdict
Compliance criteria
N/A
Sample 1 burning time (s) ................................ :

Sample 2 burning time (s) ................................ :

Sample 3 burning time (s) ................................ :

A.2/RD
Flammability test for fire enclosures of movable equipment having a total mass
not exceeding 18 kg, and for material and components located inside fire
enclosures (see 4.7.3.2/RD and 4.7.3.4/RD)
A.2.1/RD
Samples, material ............................................ :

Wall thickness (mm) ........................................ :

TRF No.: IEC62040_1_1A
N/A
TRF originator: SGS Fimko
Report No.:
Page 36 of 65
17013446 001
IEC 62040-1-1
Clause
Requirement – Test
Result – Remark
Verdict
A.2.2/RD
Conditioning of samples
N/A
A.2.3/RD
Mounting of samples
N/A
A.2.4/RD
Test flame (see IEC 60695-11-4)
N/A

Flame A, B or C ............................................... :
A.2.5/RD
Test procedure
N/A
A.2.6/RD
Compliance criteria
N/A
A.2.7/RD
Sample 1 burning time (s) ................................ :

Sample 2 burning time (s) ................................ :

Sample 3 burning time (s) ................................ :

Alternative test acc. to IEC 60695-2-2, cl. 4 and
8
N/A
Sample 1 burning time (s) ................................ :

Sample 2 burning time (s) ................................ :

Sample 3 burning time (s) ................................ :

A.3/RD
Hot flaming oil test (see 4.6.2)
N/A
A.3.1/RD
Mounting of samples
N/A
A.3.2/RD
Test procedure
N/A
A.3.3/RD
Compliance criterion
N/A
B/RD
ANNEX B, MOTOR TESTS UNDER ABNORMAL CONDITIONS (see 4.7.2.2/RD
and 5.3.2/RD)
B.1/RD
General requirements
VDE or TUV approved source
of primary DC fan provided. No
further tests of this subclause
necessary.
P
N/A
Position ............................................................ :

Manufacturer ................................................... :

Type ................................................................ :

Rated values .................................................. :

B.2/RD
Test conditions
N/A
B.3/RD
Maximum temperatures
N/A
B.4/RD
Running overload test
N/A
B.5/RD
Locked-rotor overload test
N/A
Test duration (days) ........................................ :

Electric strength test: test voltage (V) ............. :

TRF No.: IEC62040_1_1A
TRF originator: SGS Fimko
Report No.:
Page 37 of 65
17013446 001
IEC 62040-1-1
Clause
Requirement – Test
Result – Remark
Verdict
B.6/RD
Running overload test for d.c. motors in
secondary circuits
N/A
B.7/RD
Locked-rotor overload test for d.c. motors in secondary circuits
N/A
B.7.1/RD
Test procedure
N/A
B.7.2/RD
Alternative test procedure; test time (h) ........... :
N/A
B.7.3/RD
Electric strength test
N/A
B.8/RD
Test for motors with capacitors
N/A
B.9/RD
Test for three-phase motors
N/A
B.10/RD
Test for series motors
N/A
Operating voltage (V) ...................................... :

ANNEX C, TRANSFORMERS (see 1.5.4/RD and 5.3.3/RD)
P
Position ............................................................ :
Transformer TX200 used on
CNTL board

Manufacturer ................................................... :
See table 4.3

Type ................................................................ :
See table 4.3

Rated values .................................................. :
See table 4.3

Method of protection......................................... :
Circuit design (inherently)

C.1/RD
Overload test
See appended table 5.3.
P
C.2/RD
Insulation
See appended table C.2.
P
C/RD
Protection from displacement of windings ....... :
P
D/RD
ANNEX D, MEASURING INSTRUMENTS FOR TOUCH-CURRENT TESTS
(see 5.1.4/RD)
P
D.1/RD
Measuring instrument
Measuring instrument
according to figure D.1 was
used.
P
D.2/RD
Alternative measuring instrument
Not used.
E/RD
ANNEX E, TEMPERATURE RISE OF A WINDING (see 1.4.13/RD)
F/RD
ANNEX F, MEASUREMENT OF CLEARANCES AND CREEPAGE DISTANCES
(see 2.10/RD)
TRF No.: IEC62040_1_1A
N/A
N/A
P
TRF originator: SGS Fimko
Report No.:
Page 38 of 65
17013446 001
IEC 62040-1-1
Clause
Requirement – Test
Result – Remark
G/RD
ANNEX G, ALTERNATIVE METHOD FOR DETERMINING MINIMUM
CLEARANCES
Verdict
N/A
Alternative method not used
G.1/RD
Summary of the procedure for determining
minimum clearances
N/A
G.2/RD
Determination of mains transient voltage (V) ... :
N/A
G.2.1/RD
AC mains supply
N/A
G.2.2/RD
DC mains supply
N/A
G.3/RD
Determination of telecommunication network
transient voltage (V) ......................................... :
N/A
G.4/RD
Determination of required withstand voltage (V):
N/A
G.5/RD
Measurement of transient levels (V) ................ :
N/A
G.6/RD
Determination of minimum clearances............. :
N/A
H
ANNEX H, GUIDANCE ON PROTECTION AGAINST INGRESS OF WATER
AND FOREIGN OBJECTS (see IEC 60529)
N/A
J/RD
ANNEX J, TABLE OF ELECTROCHEMICAL POTENTIALS (see 2.6.5.6/RD)
P
Metal used ....................................................... :

Ring-type lug, Screw and star
washer steel with Zn platting.
Trace(Copper) contact with
screw and spring washer steel
was covered by stannum.
Enclosure is made of mild steel.
K/RD
ANNEX K, THERMAL CONTROLS (see 1.5.3 and 5.3.7)
N/A
K.1/RD
Making and breaking capacity
N/A
K.2 /RD
Thermostat reliability; operating voltage (V)..... :
N/A
K.3/RD
Thermostat endurance test; operating voltage
(V) ................................................................... :
N/A
K.4/RD
Temperature limiter endurance; operating
voltage (V) ....................................................... :
N/A
K.5/RD
Thermal cut-out reliability
N/A
K.6/RD
Stability of operation
N/A
L
ANNEX L, BACKFEED PROTECTION TEST
N/A
L.1
General
N/A
L.2
Test for pluggable equipment type A or
pluggable equipment type B UPS
TRF No.: IEC62040_1_1A
N/A
TRF originator: SGS Fimko
Report No.:
Page 39 of 65
17013446 001
IEC 62040-1-1
Clause
Requirement – Test
Result – Remark
L.3
Test for permanently connected UPS
N/A
L.4
Single-fault conditions
N/A
M
ANNEX M, EXAMPLES OF REFERENCE LOAD CONDITIONS
P
M.1
General
P
M.2
Reference resistive load
N/A
M.3
Reference inductive-resistive load
N/A
M.4
Reference capacitive-resistive loads
M.5
Reference non-linear load
N/A
M.5.1
Test method
N/A
M.5.2
Connection of the non-linear reference load
N/A
N
ANNEX N, VENTILATION OF BATTERY COMPARTMENTS
P
N.1
General
Sufficient openings are
provided in such a way that a
local concentration of hydrogen
and oxygen is not possible. No
requirement regarding the
separation of operational arcing
parts from battery vents/valves.
P
N.2
Hydrogen concentration
See N.1 above.
P
N.3
Blocked conditions
No fans or other devices
provided for ventilation
purposes.
N/A
N.4
Overcharge test
See appended table N.4.
P
U/RD
ANNEX U, INSULATED WINDING WIRES FOR USE WITHOUT INTERLEAVED
INSULATION (see 2.10.5.4/RD)
See below.
Worst-case power factors as
specified by the manufacturer
maintained during the relevant
tests.
See separate test report
X
ANNEX X, GUIDANCE FOR DISCONNECTION OF BATTERIES DURING
SHIPMENT
Verdict
P
N/A

N/A
Informative
X.1
Applicable products
N/A
X.2
Battery disconnection
N/A
X.3
Package labelling/marking
N/A
TRF No.: IEC62040_1_1A
TRF originator: SGS Fimko
Report No.:
Page 40 of 65
17013446 001
IEC 62040-1-1
Clause
Requirement – Test
X.4
Damage inspection
N/A
X.5
The importance of safe handling procedures
N/A
Y/RD
ANNEX Y, ULTRAVIOLET LIGHT CONDITIONING TEST (see 4.3.13.3/RD)
N/A
Y.1/RD
Test apparatus ................................................ :
N/A
Y.2/RD
Mounting of test samples ................................ :
N/A
Y.3/RD
Carbon-arc light-exposure apparatus .............. :
N/A
Y.4/RD
Xenon-arc light exposure apparatus ............... :
N/A
TRF No.: IEC62040_1_1A
Result – Remark
Verdict
TRF originator: SGS Fimko
Report No.:
Page 41 of 65
4.3
17013446 001
TABLE: list of critical components
Object/part no.
Manufacturer/
trademark
Type/model
P
Technical data
Standard
Mark(s) of
conformity 1.
models for Eaton E Series DX 6000H/ 6000H XL/10000H/10000HXL
DC FAN(1 pcs
for 6000H/
6000HXL, 2 pcs NMB
for 10000H/
10000HXL
4715KL
12VDC, 0.90A
IEC/EN 60950-1 VDE 116206
Metal enclosure --
--
Min. 1.2mm
--
Test in
appliance
Front panel
C2950
2.5MM, 5VB,
75℃
UL94
UL E207780
(Alternative)
SABIC
INNOVATIVE
PLASTICS
JAPAN L L C
CHIMEI
PA-765A(+)
2.5MM, 5VB,
80℃
UL94
UL E56070
Air flow Sheet
various
various
0.15mm
min., V-0
UL
UL
Battery wire
For 10000H
various
various
105℃, 600V,
12AWG min.,
VW-1
UL
UL
I/P Wire
& O/P Wire
various
various
105℃, 600V,
12AWG min.,
VW-1
UL
UL
Ground wire
various
various
105℃, 600V,
14AWG min.,
VW-1
UL
UL
Breaker for
ABB
6000H/6000HXL
S200
2 pole, 32A,
IEC/EN 60947-2 CCA/DE1 33308
400VAC, type D
Alternative
Tian shui
GSB2
2 pole, 32A,
IEC/EN 60898-1 TUV R50107925
400VAC, type D
Alternative
Liang xin
NDB2
Alternative
Moeller
FAZ-C32/2
Breaker for
10000H/10000
HXL
ABB
S200
Alternative
Tian shui
GSB2
Alternative
Liang xin
NDB2
Alternative
Moeller
FAZ-C50/2
TRF No.: IEC62040_1_1A
2 pole, 32A,
IEC/EN 60898-1 TUV R50125739
400VAC, type D
2 pole, 32A,
IEC/EN 60898-1 VDE 40000771
400VAC, type C
2 pole, 50A,
IEC/EN 60947-2 CCA/DE1 33308
400VAC, type D
2 pole, 50A,
IEC/EN 60898-1 TUV R50107925
400VAC, type D
2 pole, 50A,
IEC/EN 60898-1 TUV R50125739
400VAC, type D
2 pole, 50A,
VDE 40000771
400VAC, type C IEC/EN 60898-1
TRF originator: SGS Fimko
Report No.:
Page 42 of 65
17013446 001
Maintain Switch
Tianshui
For
6000H/6000HXL
GSH1-40/29
40A, 690V
IEC/EN 60947-3 TUV R50099240
For
Tianshui
10000H/10000H
XL
GSH1-63/29
63A, 690V
IEC/EN 60947-3 TUV R50099240
Terminal block
HOPPY
HP-RT60
60A, 600VAC
Battery
For
6000H/10000H
Alternative
Panasonic Corp
UP-RW1236
12V, 36W
IEC/EN 60947-1 TUV R50081852
IEC/EN 60947-71
UL 1989
UL MH13723
YUASA
NPW36-12
12V, 36W
UL 1989
UL MH28947
12V, 7.2AH
12V, 36W
UL 1989
UL 1989
UL MH14533
UL MH29104
400VDC,
2200µF
--
Test in
appliance
400VDC,
2200µF
--
Test in
appliance
Maintain Switch
Alternative
Alternative
CSB
GP1272
TOPLITE
NPW36-12
(GUANGZHOU)
TECHNOLOGY
BATTERY CO
LTD
BUS Capacitors RIFA
ALS32A1017L3
(2pcs) for
C
6000H/6000HXL
Alternative
Nichicon
PWRM 2G222
Bus Capacitors
(2pcs) for
10000H/
10000HXL
Alternative
Rubycon
450LSQ5600MR 450VDC,
Y77*131
5600µF
--
Test in
appliance
RIFA
--
Alternative
Nichicon
ALS32A1024N5 450VDC,
C
5600µF
HCGF6A2W562 450VDC,
5600µF
Test in
appliance
Test in
appliance
--
Battery connector for Eaton E Series DX 6000HXL
Battery
connector
Phoenixtec
Power Co., Ltd.
PPC 25R-A
25A, 250VDC
IEC/EN 619842001
Test in TUV-RH
report 11007379
001
IEC/EN 619842001
Test in TUV-RH
report 11006865
001/002
Battery connector for Eaton E Series DX 10000HXL
Battery connector Phoenixtec
PPC 25R-5A
Power Co., Ltd.
TRF No.: IEC62040_1_1A
30A, 250VDC
TRF originator: SGS Fimko
Report No.:
Page 43 of 65
17013446 001
I/P EMI board for Eaton E Series DX 6000H/6000HXL/10000H/10000HXL
TENTA
Electronics
Industrial Co.
Ltd.
MEX
2.2uF, 275V
IEC/EN 60384UL E186475
14
VDE 119119
UL 414&UL1283
NANJING
YUYUE
ELECTRONIC
S CO., LTD
CT7
0.01uF, 250VAC
IEC/EN 6038414
VDE 40008013
(Alternative)
MURATA
KH
0.01uF, 250VAC
IEC/EN 6038414
VDE 40002796
(Alternative)
Dongguan
South
Hongming
Ceramic
CO.,LTD
F
0.01uF, 250VAC
IEC/EN 6038414
VDE 118357
X-capacitor
(C01,C04)
Y-capacitor
(C02,C03)
MOV(MOV1,MO
V2,MOV3,MOV4,
JOYIN
MOV5,MOV6)
Thermal Fuse
F01-F03
UCHIHASHI
ESTEC CO
LTD
JVR20N511K
550Vac, 85℃
122
2A, 250Vac,
115℃
UL1449
IEC/EN 61051-1
IEC/EN 61051-2
IEC/EN 610512-2
IEC/EN 60691
UL 60691
UL E154922
VDE 005937
VDE 40003729
UL E50082
O/P EMI for Eaton E Series DX 6000H/ 6000HXL/10000H/10000HXL
X-capacitor
(C01,C02)
TENTA
Electronics
Industrial Co.
Ltd.
MEX
2.2uF, 275V
IEC/EN 6038414
UL E186475
UL1414&UL128 VDE 119119
3
Y-capacitor
(C03,C04)
070-11203-00
NANJING
YUYUE
ELECTRONIC
S CO., LTD
CT7
4.7nF, 250VAC
IEC/EN 6038414
VDE 40008013
(Alternative)
MURATA
KH
4.7nF, 250VAC
IEC/EN 6038414
VDE 40002796
(Alternative)
Guangdong
South
Hongming
Electronic
F
4.7nF,250VAC
IEC/EN 6038414
VDE 118357
Relay(RY02)
30A,250Vac
SONG CHUAN 841-P-1A-B-C-H Coil:12Vdc
Gap:1.5mm
Relay(RY01)
30A,250Vac
Only for 10000H/ SONG CHUAN 841-P-1A-B-C-H Coil:12Vdc
10000HXL
Gap:1.5mm
TRF No.: IEC62040_1_1A
UL 508
IEC/EN 61810-1
IEC/EN 6025523
IEC/EN 61810-5
UL 508
IEC/EN 61810-1
IEC/EN 6025523
IEC/EN 61810-5
UL E88991
TUV R9653713
UL E88991
TUV R9653713
TRF originator: SGS Fimko
Report No.:
Page 44 of 65
17013446 001
Normal charger Board for Eaton E Series DX 6000H/10000H
Transformer
(TX901)
CLICK
080-42115
130°C
--
Test in
appliance
Transformer
(TX902)
CLICK/Song
Yuan
080-30517
130°C
--
Test in
appliance
PS2561L-1
Internal
cr>4.0mm,
external
cr>7.0mm,
dti>0.4mm
IEC/EN 607475-2,
VDE 40008862
IEC/EN 60950-1
215 series
F10A, 250VAC
UL 248
UL E10480
IEC/EN 60127-2 VDE 40013521
--
Min.6A, 900V
--
Test in
appliance
Test in
appliance
Photocoupler
(U907,U908,
U909)
NEC
Fuse(F901,F902, Suzhou
F903,F904,F905, Littelfuse OVS
F906)
Ltd.
Mosfet
(Q907,Q908)
--
Quick Charger Board for Eaton E Series DX 6000HXL/10000HXL
E- capacitor
(C107,
C310,C311)
IGBT (Q105,
Q301)
SCR (Q04)
Fuse(F1)
Transformer
(TX1)
Transformer
(TX2)
Inductor
(L101,L103,
L301,L302)
--
--
220uF,450V,
105°C
--
--
--
Min.28A, 900V
--
--
--
Min. 35A, 1200V --
Littelfuse, Inc.
KLKD8
F8A, 600Vdc
UL 248
CLICK
080-30597
130°C
--
CLICK
080-42003
130°C
--
Shangyong/Ju 082-11037;
Qun/Mao Hong 082-11143
130°C
--
Photocoupler
(U101,U106
U302,U501)
NEC
PS2561L-1
Photocoupler
U103
TOSHIBA
TLP250
TRF No.: IEC62040_1_1A
Internal
cr>4.0mm,
external
cr>7.0mm,
dti>0.4mm
Internal
cr>4.0mm,
external
cr>7.0mm,
dti>0.4mm
Test in
appliance
Test in
appliance
UL E10480
Test in
appliance
Test in
appliance
Test in
appliance
IEC/EN 607475-2,
VDE 40008862
IEC/EN 60950-1
IEC/EN 607475-2,
VDE 40011913
IEC/EN 60950-1
TRF originator: SGS Fimko
Report No.:
Page 45 of 65
Photocoupler
U107
Current
Transformer
(CT101,CT102)
17013446 001
NEC
PS2561L-1
Internal
cr>4.0mm,
external
cr>7.0mm,
dti>0.4mm
CLICK/SHENY
UAN
080-20514
130°C
--
Test in
appliance
VDE 094710
UL E183539
IEC/EN 607475-2,
VDE 40008862
IEC/EN 60950-1
PSDR board for Eaton E Series DX 6000H/ 6000HXL
X-capacitor
(C307,C308)
AID
MEX
1.0uF, 275Vac
IEC/EN 6038414
UL1414
UL1283
HCT
Transformer
(HCT1)
Bes Teks
Technology
CTC0500
105°C
--
Test in
appliance
Transformer
(TX1)
CLICK
080-56702
130°C
--
Test in
appliance
082-11114
200°C
--
082-11209
200°C
--
CLICK/Song
Yuan
080-20448
130°C
--
Test in
appliance
CLICK/Song
Yuan
080-20510
130°C
--
Test in
appliance
Fuse
(F302)
Littelfuse, Inc.
BLN
F30A, 250Vac
UL248
UL E10480
Fuse
(F303)
Littelfuse, Inc.
KLKD
F30A, 600Vdc
UL248
UL E10480
PS2561L-1
Internal
cr>4.0mm,
external
cr>7.0mm,
dti>0.4mm
IEC/EN 607475-2,
VDE 40008862
IEC/EN 60950-1
Inductor
(L201,L202)
Inductor
(L301,L302)
Current
Transformer
(CT201)
Current
Transformer
(CT301,CT302,C
T303,CT304)
Photocoupler
(U108, U110)
Relay
(RY2)
Shangyong/Ma
o Hong
Shangyong/Ma
o Hong
NEC
SONG
CHUAN
TRF No.: IEC62040_1_1A
737-1Z-C-T
Coil:12Vdc
30A, 300Vac
Test in
appliance
Test in
appliance
UL 508
IEC/EN 61810-1 UL E88991;
IEC/EN 60255- TUV R50044822
23
IEC/EN 61810-5
TRF originator: SGS Fimko
Report No.:
Page 46 of 65
17013446 001
PSDR board for Eaton E Series DX 10000H/10000HXL
--
--
350V, 100uF,
105°C
--
Test in
appliance
SCR
(Q207,Q208,Q301, -Q302,Q305)
--
Min. 35A, 1200V --
Test in
appliance
--
--
Min. 40A, 1200V --
Test in
appliance
IGBT
(Q306,Q307,Q310, -Q311)
--
Min. 60A, 1000V --
Test in
appliance
Mosfet(Q104)
--
Min. 3A, 900V
--
Test in
appliance
VDE 094710
UL E183539
E-Capacitor
(C100)
IGBT (Q201-Q204)
--
AID
MEX
1.0uF, 275Vac
IEC/EN 6038414
UL1414
UL1283
HCT
Transformer
(HCT1)
LEM
HY 50-P
105°C
--
Test in
appliance
Transformer
(TX1)
CLICK
080-56702
130°C
--
Test in
appliance
Inductor
(L201,L202)
Ju Qun/
Shangyong/
Mao Hong
082-11142
200°C
--
Test in
appliance
Inductor
(L301,L302)
Shangyong/Mao
082-11208
Hong
200°C
--
Test in
appliance
Current
Transformer
(CT201)
CLICK/Song
Yuan
080-20448
130°C
--
Test in
appliance
CLICK/Song
Yuan
080-20510
130°C
--
Test in
appliance
Littelfuse, Inc.
BLN
F30A, 250Vac
UL248
UL E10480
Littelfuse, Inc.
KLKD
F30A, 600Vdc
UL248
UL E10480
X-capacitor
(C307,C308)
Current
Transformer
(CT301,CT302,CT
303,CT304)
Fuse
(F301, F302)
Fuse
(F303, F304)
Photocoupler
(U108,U110)
Relay (RY1)
NEC
PS2561L-1
Song Chuan
735H-2C-F-C
TRF No.: IEC62040_1_1A
Internal
cr>4.0mm,
external
cr>7.0mm,
dti>0.4mm
Coil:12Vdc,
30A,250VAC
IEC/EN 60747-52,
VDE 40008862
IEC/EN 60950-1
UL 508
UL E88991
TRF originator: SGS Fimko
Report No.:
Page 47 of 65
Relay (RY3, RY4)
Song Chuan
832A-1C-F-C
Coil: 12Vdc
Contact:30A,
250Vac
17013446 001
UL 508
IEC/EN 61810-1
UL E88991
IEC/EN 60255VDE 006615
23
IEC/EN 61810-5
CNTL board for Eaton E Series DX 6000H/Eaton E Series DX 6000HXL
Eaton E Series DX 10000H/Eaton E Series DX 10000HXL
Transformer
(TX200)
CLICK
Photocoupler
(U203,U205,U206, NEC
U106)
Test in
appliance
080-42109
130°C
--
PS2561-1
Internal
cr>4.0mm,
external
cr>7.0mm,
dti>0.4mm
IEC/EN 607475-2
IEC/EN 60950-1 VDE 40008862
Note(s):
1. An asterisk indicates a mark that assures the agreed level of surveillance.
2. Transformer sources are identical in design (which includes used materials). Only differences are
manufacturer and type designation.
3. Thermal class of insulation system of all relay sources is classified as Class B according to IEC 60085
TRF No.: IEC62040_1_1A
TRF originator: SGS Fimko
Report No.:
Page 48 of 65
4.4
fuse #
17013446 001
TABLE: electrical data (in normal conditions)
Irated (A)
U (V)
P
P (W)
I (A)
Ifuse (A)
condition/status
For model EATON E Series DX 6000H
Circuit
breaker
30
220V/50Hz
4.30
19.57
19.57
Normal operation with and
with battery charging.
30
240V/50Hz
4.25
19.07
19.07
Same as above
30
220V/60Hz
4.34
19.52
19.52
Same as above
30
240V/60Hz
4.22
19.05
19.05
Same as above
For model EATON E Series DX 6000HXL
30
220V/50Hz
4.54
22.59
22.59
Normal operation with and
with battery charging.
(charger current 4.2A)
30
240V/50Hz
4.56
20.08
20.08
Same as above
30
220V/60Hz
4.56
22.62
22.62
Same as above
30
240V/60Hz
4.62
20.85
20.85
Same as above
Circuit
breaker
For model EATON E Series DX 10000H
Circuit
breaker
50
220V/50Hz
7.02
32.08
32.08
Normal operation with and
with battery charging.
50
240V/50Hz
6.97
29.25
29.25
Same as above
50
220V/60Hz
7.12
32.12
32.12
Same as above
50
240V/60Hz
6.98
29.35
29.35
Same as above
For model EATON E Series DX 10000HXL
50
220V/50Hz
7.42
34.53
34.53
Normal operation with and
with battery charging.
(charger current 4.2A)
50
240V/50Hz
7.36
31.75
31.75
Same as above
50
220V/60Hz
7.43
34.62
34.62
Same as above
50
240V/60Hz
7.42
31.85
12.75
Same as above
Circuit
breaker
Note(s):
TRF No.: IEC62040_1_1A
TRF originator: SGS Fimko
Report No.:
Page 49 of 65
5.1.2
17013446 001
TABLE: distance through insulation measurements
distance through insulation di at/of:
P
Up
(V)
test voltage
(V)
required di
(mm)
di
(mm)
Note(s): See component list in table 4.3.
5.1.3
TABLE: discharge of capacitors in the primary circuit
Condition
τ calculated
τ measured
(s)
(ms)
t u→ 0V
(s)
P
Comments
Line mode
(L-N)
--
0.78
--
--
0.81
--
Bypass mode
(L-N)
Note: Input voltage 254V/60Hz
Overall capacity: C01+C04=4.4uF on input EMI board, C37+C38=2.0.0uF on PSDR board,
C01+C02=4.4uF on output EMI board
Discharge resistor: By regulating network
5.2
2.2.2/RD
TABLE: insulation / hazardous voltage measurement
Transformer
Location
P
max. Voltage
Voltage Limitation
Note(s): No voltage on secondary side (CNTL board) exceeding SELV limits during normal/abnormal
operation. No test necessary.
5.2
2.2.3/RD
TABLE: insulation / SEL voltage measurement
Location
Voltage measured (V)
--
--
P
Comments
--
Note(s): No voltage on secondary side (CNTL board) exceeding SELV limits during normal/abnormal
operation. No test necessary.
TRF No.: IEC62040_1_1A
TRF originator: SGS Fimko
Report No.:
Page 50 of 65
5.3
2.4/RD
17013446 001
TABLE: limited current circuits
Location
Voltage
(V)
N/A
Current
(mA)
Freq.
(Hz)
Limit
(mA)
Comments
Note(s):
TABLE: provisions for protective earthing
5.4
2.6.3.3/RD
Location
P
Resistance measured (mΩ) Comments
I/P earth O/P earth
16
I/P earth metal enclosure
16
I/P earth earth on PCB(PSDR
board
16
I/P earth earth on PCB(Charger
board)
16
Test current of 128A for 360s.*
Note(s): *Per client’s request, voltage drop not more than 2.5V measured. 2.5V/128A=19.5mΩ
5.8
2.10.2/RD
TABLE: working voltage measurement
Location
RMS voltage (V)
P
Peak voltage (V) Comments
Note(s): Mains voltage considered
5.8 and 9
P
TABLE: clearance and creepage distance measurements
clearance cl and creepage
distance dcr at/of:
Up
(V)
U r.m.s.
(V)
required cl
(mm)
cl
(mm)
required
dcr (mm)
dcr
(mm)
Whole unit
Internal live part of battery
connector to accessible part
(for model 6000HXL,
10000HXL)
420
250
4.0
5.6
5.0
5.6
BUS Capacitor to metal
enclosure
420
250
2.0
*
2.5
*
Battery to enclosure
420
250
4.0
6.0
5.0
6.0
4.0
See below
5.0
See below
CNTL board
Primary to secondary on the
copper side
TRF No.: IEC62040_1_1A
420
250
TRF originator: SGS Fimko
Report No.:
Page 51 of 65
17013446 001
-under transformer TX200
6.9
6.9
-under optocoupler U203
6.9
6.9
Quick charger board (for model 6000HXL, 10000HXL)
Primary trace to earthed
trace/screw
420
250
2.0
See below
2.5
See below
-near U205
4.0
4.0
-under C311
6.3
6.3
Quick charger board (for model 6000H, 10000H)
Primary trace to earthed
trace/screw
420
250
2.0
See below
2.5
See below
-near F906
5.0
5.0
-near P907
6.3
6.3
On input EMI board
Primary trace to earthed trace
420
250
2.0
See below
2.5
See below
-under C02
2.8
2.8
-under capacitor C05
2.8
2.8
Primary trace to earthed screw
420
250
2.0
-near capacitor R01
See below
2.5
See below
3.6
3.6
On PSDR board
Primary trace to earthed
screw**
420
250
2.0
See below
2.5
See below
-near capacitor C127
2.9
3.2
-near CN205
3.0
3.0
-near CN103
4.1
4.1
-near CN302
2.7
2.7
-near R347
4.8
4.8
Primary trace to metal
enclosure
420
250
2.0
2.7
2.5
8.0
Note(s): The Cl.& Cr. Measured considering 10N force performed on component in each item above.
* Since each source of bus capacitor to metal enclosure has pass 1500Vac hi-pot test, the plastic cover of
the case can be consider as basic insulation.
** since the distance between copper side of PSDR board and earthed metal enclosure is larger than
2.5mm, distance measured between the primary components to earthed trace/screw for reference.
TRF No.: IEC62040_1_1A
TRF originator: SGS Fimko
Report No.:
Page 52 of 65
5.8, 6, 8.2
and 9
17013446 001
TABLE: electric strength tests, impulse tests and voltage surge tests
test voltage applied between:
P
test voltage (V)
a.c. / d.c.
breakdown
Yes /?o
Primary to Secondary interface (RS-232)
3000Vac
No
L/N to earthed metal enclosure
1500Vac
No
Output L/N to earthed metal enclosure
1500Vac
No
Primary to secondary of transformer TX200 used on the CNTL 3000Vac
board
No
Primary to core of transformer TX200 used on the CNTL
board
1500Vac
No
Secondary to core of transformer TX200 used on the CNTL
board
1500Vac
No
Any combination of 2 layers insulation tape used on the
transformer TX200 used on the CNTL board
3000Vac
No
Enclosure of bus capacitor(each source of the capacitor)
1500Vac
No
Note(s):
7.4.1
Table: enclosure openings
4.6.1/RD and 4.6.2/RD
Location
Size (mm)
P
Comments
Top
None
No openings
Bottom
None
No openings
Side
None
No openings
Front
Ф3.0
Numerous for ventilation
Back
Ф116.0
1 round opening for ventilation of DC fan and
covered by fan guard for Eaton E Series DX
6000H/6000HXL(2pcs for Eaton E Series DX
10000H/10000HXL)
Note(s):
7.5
TABLE: resistance to fire
part
manufacturer of material
P
type of material
thickness
(mm)
flammability
class
Note(s): see table 4.3 for details
TRF No.: IEC62040_1_1A
TRF originator: SGS Fimko
Report No.:
Page 53 of 65
7.5 and
8.3
No.
17013446 001
TABLE: fault condition tests
P
ambient temperature (°C) ...................................... :
25

model/type of power supply ................................... :
--

manufacturer of power supply ............................... :
--

rated markings of power supply ............................. :
--

Component no.
Fault
Test
voltage (V)
Test
time
Fuse
no.
Fuse
current
(A)
Result
Normal charger board on model EATON E Series DX 10000H
1
U908 Pin 1-2
s-c
240Vac
30min
F901,
F902,
F903
--
UPS operates as normal.
2
U908 Pin 3-4
s-c
240Vac
30min
F901,
F902,
F903
--
UPS operates as normal.
3
Q907 D-S
s-c
240Vac
1min
F901,
F902,
F903
--
4
R930
s-c
240Vac
3S
F901,
F902,
F903
--
UPS output remains
normal. Charger Fuse F901,
F902, F903 opened.
Charger output
shut down.
UPS operates as normal.
5
Two polarities of
battery (after
fuse)
s-c
Battery
mode
3S
F303
--
The fuse F303 opened, UPS
stopped working immediately.
After recovery, UPS works
normally.
Quick charger board for model EATON E Series DX 10000HXL
6
Charger Rectifier s-c
diode D303
240Vac
5s
F1
--
5S later, EUT changes to
bypass mode.R322 and
Q301 damaged.
7
Q301 (C-E)
s-c
240Vac
1s
F1
--
The fuse F1 opened,CHGR
board has no output, but the
EUT output is normal.
8
Q105 (C-E)
s-c
240Vac
10min
F1
--
EUT output is normal,no
hazard.
9
R320
s-c
240Vac
10min
F1
--
EUT output is normal,no
hazard.
10
Two polarities of
battery (after
fuse)
s-c
Battery
mode
1s
F303,
F304
--
The fuse F303 and F304
opened, UPS stop working
immediately. After recovery,
UPS works normally.
TRF No.: IEC62040_1_1A
TRF originator: SGS Fimko
Report No.:
Page 54 of 65
17013446 001
PSDR board (for similar design on PSDR board, test with model EATON E Series DX 10000HXL to
represent other models)
11
Transformer TX1 s-c
Pin 11-12
12
Transformer TX1 s-c
Pin 10-9
Battery
mode
1.5h
F301,
F302
--
UPS changes to bypass
mode, TX1 is 90.5°C,ambient
is 28.1°C.After recovery, UPS
works normally.
Battery
mode
1.0h
F301,
F302
--
UPS changes to bypass
mode, TX1 is 68.1°C,
ambient is 28.3°C. After
recovery, UPS works
normally.
EUT changes to bypass
mode. F301, F302 opened,
Q306 damaged, no hazard.
After 1s, UPS changes to
bypass mode. F301, F302
opened, Q203,Q204,Q201
and Q202 damaged, no
hazard.
13
Transistor Q306
(c-e)
s-c
240Vac
1s
F301,
F302
--
14
Transistor Q201
(c-e)
s-c
240Vac
1s
F301,
F302
--
15
Line Detecting
Resistor R01
s-c
Battery
mode
3h
F301,
F302
--
UPS works normally,no
hazard.
16
Battery Detecting s-c
Resistor R380
240Vac
2h
F301,
F302
--
UPS changes to bypass
mode, the battery LED
warns. After recovery, UPS
works normally.
17
Bus voltage
Detecting
Resistor R01
o-c
240Vac
3h
F301,
F302
--
UPS works normally,no
hazard.
18
BUS capacitor
s-c
240Vac
3s
F301,
F302
--
UPS changes to bypass
mode, F301 and F302
opened.
CNTL board
19
Transformer
TX200 (Pin9Pin10)
s-c
240Vac
3s
Circuit -breaker
UPS changes to bypass
mode and warns. After
recovery, UPS did’t work
normally, TX200 damaged.
20
Optocoupler
U203 (pin1-2)
s-c
240Vac
10min
Circuit -breaker
UPS work normally,no
hazards.
21
Optocoupler
U203 (pin3-4)
s-c
240Vac
10min
Circuit -breaker
UPS works normally,no
hazards.
--
UPS shut down after 3
seconds, recoverable after
fault removed, no hazards
Whole unit (model EATON E Series DX 10000H)
5min
22 Output
s-c
240Vac
TRF No.: IEC62040_1_1A
--
TRF originator: SGS Fimko
Report No.:
Page 55 of 65
17013446 001
23
output
o-l
240Vac
1h
--
--
24
Output
s-c
Battery
mode
5min
Battery
Fuse
--
25
output
o-l
Battery
mode
1h
Battery
Fuse
--
26
Fan
locked
240Vac
1h
--
--
27
Ventilation
opening
Blocke
d
240Vac
1h
Battery
Fuse
--
UPS operates as normal.
UPS transfer to bypass
mode after 31mins,
28
Fan
locked
Battery
mode
1h
--
--
UPS operates as normal
29
Ventilation
opening
Blocke
d
Battery
mode
1h
Battery
Fuse
--
UPS transfer to bypass
mode after 27mins.
Whole unit (model EATON E Series DX 10000HXL)
1s
30 Output
s-c
240Vac
31
output
o-l
240Vac
30mins
32
Output
s-c
Battery
mode
1s
TRF No.: IEC62040_1_1A
Input
-breaker
Input
-breaker
F303,F
304
--
125% load, after 10min15min UPS transfer to
bypass mode.
150% load, after 30sec60sec UPS transfer to
bypass mode.
UPS shut down after 3
seconds, recoverable after
fault removed, no hazards
125% load, after 10min15min UPS transfer to
bypass mode.
150% load, after 30sec60sec UPS transfer to
bypass mode.
EUT fault and no output
immediately.No hazard.
(measured on PSDR board,
temperature of TX1 is
38.9°C. TX1 of charger
board is 40.7°C.)
EUT changes to bypass
mode within 1s at condition
of overload 130%. No
hazard.
(measured on PSDR board,
temperature of TX1 is
35.5°C, TX1 of charger
board is 41.6°C.)
EUT fault and no output
immediately. No hazard.
(measured on PSDR board,
temperature of TX1 is
40.1 °C.
TX1 of charger board is
48.7°C.)
TRF originator: SGS Fimko
Report No.:
Page 56 of 65
17013446 001
33
output
o-l
240Vac
60mins
--
--
34
Fan
locked
240Vac
20mins
F303,F
304
--
35
Ventilation
opening
Blocked 240Vac
36
Fan
locked
Battery
mode
20mins
F303,F
304
--
37
Ventilation
opening
Blocked Battery
mode
30mins
F303,F
304
--
1hr
Input
-breaker
110% load, after
15min UPS transfer to
bypass mode.
120% load, after 10min UPS
transfer to bypass mode.
Max. Temperature of
PSDR:
TX1=35.1°C
U108=41.6°C
Charger: TX1=79.2°C
TX2=71.3°C
EUT fault and changes to
bypass. No hazard.
(measured on PSDR board,
temperature of TX1 is
139.8°C,TX1 of charger
board is 65.7°C.)
EUT fault and changes to
bypass. No hazard.
(measured on PSDR board,
temperature of TX1 is
139.9 °C ,TX1 of charger
board is 59.5°C.)
EUT fault and changes to
bypass. No hazard.
(measured on PSDR board,
temperature of TX1 is
139.8 °C, TX1 on charger
board is 65.7°C.)
EUT fault and changes to
bypass. No hazard.
(measured on PSDR board,
temperature of TX1 is
39.9 °C, TX1 on charger
board is 68.7°C.)
Note(s):
1: s-c means short-circuit. o-l means overload. o-c means open-circuit.
2: For the test which would cause the fuse F1, F301, F302, F303, F304 opened and where the fuse rating is
over 10A, all the tests repeated at least 10 times to demonstrate the same result.
TRF No.: IEC62040_1_1A
TRF originator: SGS Fimko
Report No.:
Page 57 of 65
7.7
17013446 001
TABLE: maximum temperatures
P
test voltage (V) ................................
See notes as below

t1 (°C) ................................--

t2 (°C) ................................--

Maximum temperature T of part/at:
T (°C)
allowed
Tmax (°C)
A
B
C
D
E
Enclosure (plastic panel)
33.5
33.4
26.4
29.6
30.7
82.5
Enclosure (metal)
37.2
36.2
29.1
32.5
37.0
57.5
Input breaker
40.7
41.3
33.8
36.5
34.3
57.5
Primary lead wire
44.2
43.8
36.3
38.5
36.7
92.5
Output lead wire
67.6
70.5
62.6
64.7
62.7
92.5
DC fan
40.1
45.4
34.6
42.7
38.1
--
Battery wire
34.3
36.2
29.1
33.6
39.4
92.5
X Capacitor C04 on input EMI board
45.9
46.2
39.1
38.4
39.4
87.5
Inductor L01 on input EMI board
61.7
59.2
49.9
49.1
50.1
107.5
Y capacitor C03 on input EMI board
41.6
43.1
36.2
38.4
36.2
112.5
PCB for input EMI board
47.4
47.4
39.8
40.1
39.9
117.5
Transformer CT303 coil on PSDR
board
53.0
55.1
45.8
47.3
63.9
107.5
Transformer CT201 coil on PSDR
board
57.7
62.3
52.1
55.8
53.0
107.5
Inductor L301 on PSDR board
91.6
84.5
74.4
71.3
102.4
177.5
Inductor L302 on PSDR board
75.2
71.9
61.4
61.0
93.9
177.5
Inductor L201 on PSDR board
95.7
98.5
88.4
91.6
102.2
177.5
Inductor L202 on PSDR board
110.2
113.7
101.4
106.4
107.1
177.5
Relay RY1 on PSDR board
57.0
61.3
51.7
55.5
60.3
72.5
Capacitor C100 on PSDR board
36.9
38.0
30.1
33.7
40.0
92.5
PCB between D201 and Q201 on
PSDR board
83.4
86.1
72.8
75.9
79.7
117.5
PCB between Q301 and Q305 on
PSDR board
60.4
61.4
52.4
54.6
65.0
117.5
X-capacitor C307 on PSDR board
36.0
36.7
29.2
31.2
35.1
87.5
Charger transformer TX901 core
52.8
94.1
48.2
88.0
48.3
97.5
Charger transformer TX901 coil
47.5
80.4
42.9
74.7
43.3
97.5
For model EATON E Series DX 10000H
TRF No.: IEC62040_1_1A
TRF originator: SGS Fimko
Report No.:
Page 58 of 65
17013446 001
PCB under Q907 on Charger board
40.6
61.6
34.8
55.5
35.0
117.5
CNTL transformer TX200 coil on
CNTL board
37.6
36.8
29.3
33.6
43.6
87.5
CNTL transformer TX200 core on
CNTL board
40.0
38.3
31.1
34.8
43.7
87.5
Optocoupler U203 on CNTL board
40.5
37.3
29.6
33.3
42.7
112.5
PCB near transformer TX200 on
CNTL board
40.6
37.6
29.8
33.7
44.5
117.5
X-capacitor C01 on output EMI board
39.0
41.4
36.7
38.0
38.3
87.5
Inductor L01 on output EMI board
60.9
61.8
52.6
58.5
54.3
107.5
PCB near L801 on output EMI board
64.5
66.1
60.5
61.8
60.7
117.5
Relay 01 on output EMI board
56.7
58.3
45.8
54.9
54.8
72.5
Relay 02 on output EMI board
36.5
38.8
31.9
35.9
40.6
72.5
Y-cap C04 on output EMI board
34.3
37.0
29.1
33.8
37.2
112.5
Bus-capacitor
49.3
52.6
44.6
46.5
52.0
72.5
Ambient
30.8
33.3
29.0
29.2
29.4
--
For model EATON E Series DX 10000HXL
Enclosure (plastic panel)
27.8
28.2
31.1
30.5
31.9
82.5
Enclosure (metal)
30.2
29.7
31.8
32.5
33.6
57.5
Input breaker
30.7
30.3
31.5
32.6
29.4
57.5
Primary lead wire
45.7
40.4
41.0
40.7
30.0
92.5
Output lead wire
39.2
39.2
40.1
41.6
40.2
92.5
DC fan
39.7
58.8
39.7
44.6
45.8
--
Battery wire
30.5
30.5
31.7
32.9
42.4
92.5
X Capacitor C04 on input EMI board
32.9
31.9
35.0
32.7
31.0
87.5
Inductor L01 on input EMI board
43.1
40.2
39.8
38.8
30.7
107.5
Y capacitor C03 on EMI board
34.0
33.1
34.6
34.2
32.6
112.5
PCB for input EMI board
34.7
33.7
34.6
34.6
30.9
117.5
Transformer CT303 coil on PSDR
board
47.9
44.7
45.6
44.9
67.8
107.5
Transformer CT201 coil on PSDR
board
38.7
39.0
39.1
41.0
41.5
107.5
Inductor L301 on PSDR board
82.9
74.6
71.5
64.1
102.5
177.5
Inductor L302 on PSDR board
64.6
58.1
59.2
56.4
116.1
177.5
Inductor L201on PSDR board
81.2
80.4
80.9
81.4
98.7
177.5
Inductor L202 on PSDR board
73.3
72.7
73.2
74.1
96.0
177.5
TRF No.: IEC62040_1_1A
TRF originator: SGS Fimko
Report No.:
Page 59 of 65
17013446 001
Relay RY1 on PSDR board
53.9
53.7
54.1
55.1
63.5
72.5
Capacitor C100 on PSDR board
31.3
31.9
33.7
33.8
42.4
92.5
PCB between D201 and Q201 on
PSDR board
88.9
84.8
85.8
81.5
94.0
117.5
PCB between Q301 and Q305 on
PSDR board
58.2
54.4
55.3
52.7
66.3
117.5
X-capacitor C307 on PSDR board
32.0
31.4
34.8
33.3
36.3
87.5
Changer transformer CT101 coil
37.8
36.3
35.7
37.6
34.8
107.5
Inductor L103 on charger board
47.4
45.8
42.2
45.5
36.1
107.5
Inductor L101 on charger board
46.9
46.9
42.7
46.3
36.7
107.5
X-capacitor C310 on charger board
36.5
35.6
35.7
40.2
35.2
87.5
PCB under Q105 on Charger board
44.0
43.2
40.3
41.9
36.9
117.5
Inductor L301 on Charger board
39.2
37.7
36.1
35.6
32.8
107.5
CNTL transformer TX200 coil on
CNTL board
31.9
32.4
32.4
34.7
47.4
97.5
CNTL transformer TX200 core on
CNTL board
32.5
33.0
32.9
35.2
47.1
97.5
Optocoupler U203 on CNTL board
29.8
30.5
30.2
32.5
45.1
112.5
PCB near transformer TX200 on
CNTL board
30.7
31.2
31.1
33.4
46.7
117.5
X-capacitor C01 on output EMI board
36.1
34.9
35.5
36.8
36.2
87.5
Inductor L01 on output EMI board
54.4
53.9
54.1
54.1
54.1
107.5
PCB near L801 on output EMI board
40.3
40.7
41.4
42.8
43.4
117.5
Relay 01 on output EMI board
50.8
51.5
52.7
54.8
52.8
72.5
Relay 02 on output EMI board
54.3
54.1
55.3
57.0
56.0
72.5
Y-cap C04 on output EMI board
33.3
34.0
34.8
36.7
36.5
112.5
Bus-capacitor
38.1
37.2
37.0
37.3
46.1
72.5
Ambient
27.5
27.8
29.3
28.6
27.9
--
Temperature T of winding:
R1
(Ω)
R2
(Ω)
T
(°C)
allowed
Tmax (°C)
insulation
class
Note(s): Note(s):
1. The temperatures were measured under worst case normal mode defined in 1.2.2.1 and as described in
sub-clause 1.6.2 and at voltages as described below
A: 198V/60Hz
B: 220V/50Hz
C: 220V/60Hz
TRF No.: IEC62040_1_1A
TRF originator: SGS Fimko
Report No.:
Page 60 of 65
17013446 001
D: 254V/50Hz
E: Battery mode
Having a specified maximum ambient temperature of +40 °C
- Class B → Tmax = 120 °C-10 °C-(40°C-27.5 °C )= 97.5°C
- 130°C → Tmax = 130 °C-10 °C-(40°C-27.5 °C) = 107.5°C
- 200°C → Tmax = 200 °C-10 °C-(40°C-27.5 °C) = 177.5°C
Other components:
→ Tmax=Tmax-(40-27.5) °C
2. Since model EATON DX 6000H and EATON DX 6000HXL are similar to model EATON DX 10000H and
EATON DX 10000H except for some rating components, heating tests performed on model EATON DX
10000H and EATON DX 10000HXL to represent the other two models
7.7
TABLE B: ball pressure test of thermoplastic parts
P
allowed impression diameter (mm) .....................: ≤ 2mm

part
test temperature
(°C)
impression diameter
(mm)
125
1.1
Terminal Block
Note(s): Bobbin of transformer TX200 on CNTL board is Phenolic, no further tests required.
8.1.1
TABLE: earth leakage current
P
Limit
(mA)
0.02
N → terminal A
(mA)
0.03
Metal enclosure
3.0
3.0
3.5
Plastic
enclosure
0.01
0.01
3.5
Condition
L→ terminal A
(mA)
RS-232
terminal
Comments
0.25
Note(s):Input voltage 254V/60Hz
C.2/RD
Safety isolation transformer
P
Construction details:
Transformer part name: TX200 on CNTL board
Manufacturer: See appended table 4.3
Type:
See appended table 4.3
Recurring peak voltage
420Vpeak
Required clearance for reinforced insulation
(from table 2H and 2J)
4.0
TRF No.: IEC62040_1_1A
TRF originator: SGS Fimko
Report No.:
Page 61 of 65
17013446 001
Effective voltage rms
250Vrms
Required creepage distance for reinforced insulation
(from table 2L)
2.5
Measured min. creepage distance
Location
inside (mm)
outside (mm)
Primary winding/pin to secondary winding/pin
5.0
10
Primary winding/pin to core
2.5
3.3
Secondary winding/pin to core
2.5
3.3
inside (mm)
outside (mm)
Primary winding/pin to secondary winding/pin
5.0
10
Primary winding/pin to core
2.5
3.3
Secondary winding/pin to core
2.5
3.3
Measured min. clearances
Location
Construction:
Concentrically wound transformer design, core size EE-16. N1, N2 are primary winding which is wound around
the internal side of the bobbin. 3 layers of mylar tapes are used to separate primary and secondary windings.
N3, N4, N5 are secondary windings on outer side of bobbin. Margin tape with width of 2.5mm is used on both
side of bobbin and each winding layer. Tubing is used on every winding exits to the bare pins on bobbin.
Pin numbers
Prim.
6-7, 8-9-10
Sec.
1-2, 3-4
Bobbin
Material
Phenolic, PM 9820, SUMITOMO BAKELITE
Thickness
0.7mm
Electric strength test
With 3000 V a.c. after humidity treatment
Result
TRF No.: IEC62040_1_1A
Pass
TRF originator: SGS Fimko
Report No.:
Page 62 of 65
N.4
17013446 001
Ventilation of battery compartments (For model EATON E Series DX 6000H,
EATON E Series DX 10000H)
P
The required dimension for the ventilation openings will be calculated with the
following formula:
A > K1 * Q
with Q = (0.054 m³/Ah) * n * I * C
where:
K1 : constant factor of 28 h * cm²/m³
Q : airflow in m³/h
n : number of battery cells
I : constant factor (0,2A/100Ah for valve regulated lead acid batteries)
C : nominal capacity of the battery
With the specific data for the UPS the following dimension for the ventilation
openings is required:
n : 120 (6 cells per battery provided)
C : 7.2Ah
A > 28 h * cm²/m³ * (0.054 m³/Ah) * n * 0.2 A/100 Ah * C
A > 2.6cm²
Verdict
The size of ventilation openings and holes in the UPS side enclosure exceed the
required dimension for ventilation (For model EATON E Series DX 6000H, EATON
E Series DX 10000H A=25.3 cm²)
TRF No.: IEC62040_1_1A
TRF originator: SGS Fimko
Page 63 of 65
Report No.: 17013446 001
National Differences
Clause
Requirement − Test
Result – Remark
Verdict
APPENDIX Group Differences, Special National Conditions and National Deviations of
CENELEC according to CB Bulletin No. 112A, December 2006
(EN 62040-1-1, SN EN 62040-1-1, DIN EN 62040-1-1, NEK-EN 62040-1-1, SSEN 62040-1-1)
P
(IEC Publication 62040-1-1:2002)
SPECIAL NATIONAL CONDITIONS AND NATIONAL DEVIATIONS
S = Special National Condition, A = National Deviation (A-deviation), C = CENELEC Common Modification, F = other information
NO=Norway, SE=Sweden
P=Pass, F=Fail, N/A=Not applicable. Placed in the column to the right.
4.5.3
S (NO): When safety relies upon connection to
Evaluated when applying for
the safety earth (see 5.9), a pluggable equipment national approval
type A UPS shall have a marking on the
equipment, stating that the UPS must be
connected to an earthed mains socket-outlet. The
marking text shall be as follows:
N/A
“Apparatet skal tilkoples jordet stikkontakt”
4.5.3
S (SE): When safety relies upon connection to
Evaluated when applying for
the safety earth (see 5.9), a pluggable equipment national approval
type A UPS shall have a marking on the
equipment, stating that the UPS must be
connected to an earthed mains socket-outlet. The
marking text shall be as follows:
N/A
“Apparaten skall anslutas till jordat uttag”
9
S (NO, SE): Requirements of 6.1.2.1 and 6.1.2.2
in the Reference Document (RD) IEC 609501:2001 apply with the following additions:
No TNV circuits
N/A
Add the following text between the first and
second paragraph of subclause 6.1.2.1/RD:
If this insulation is solid, including insulation
forming part of a component, it shall at least
consist of either
- two layers of thin sheet material, each of which
shall pass the electric strength test below, or
- one layer having a distance through insulation of
at least 0,4 mm, which shall pass the electric
strength test below.
If this insulation forms part of a semiconductor
component e.g. an optocoupler, there is no
distance through insulation requirement for the
insulation consisting of an insulating compound
completely filling the casing, so that clearances
and creepage distances do not exist, if the
component passes the electric strength test in
Group Differences, Special National Conditions and National Deviations of CENELEC according to CB
Bulletin No. 112A, December 2006
Page 64 of 65
Report No.: 17013446 001
National Differences
Clause
Requirement − Test
Result – Remark
Verdict
accordance with the compliance clause below
and in addition:
- passes the tests and inspection criteria of 2.10.8
with an electric strength test of 1,5 kV multiplied
by 1,6 (the electric strength test of 2.10.7 shall be
performed using 1,5 kV); and
- is subjected to routine testing for electric
strength during manufacturing, using a test
voltage of 1,5 kV.
It is permitted to bridge this insulation with a
capacitor complying with EN 132400:1994,
subclass Y2.
A capacitor classified Y3 according to IEC 6038414:1993, may bridge this insulation under the
following conditions:
- the additional testing shall be performed on all
the test specimens as described in IEC 6038414,
- the impulse test of 2,5 kV is to be performed
before the endurance test in IEC 60384-14, in the
sequence of tests as described in IEC 60384-14.
Add the following text to subclause 6.1.2.2/RD:
The exclusions are applicable for permanently
connected equipment and pluggable equipment
type B and equipment intended to be used in
restricted access location where equipotential
bonding has been applied, e.g. in a
telecommunication centre, and which has
provision for permanently connected protective
earthing conductor and is provided with
instructions for the installation of that conductor
by a service person.
Annex ZA
C: This European standard incorporates by dated
or undated reference, provisions from other
publications. These normative references are
cited at the appropriate places in the text and the
publications are listed hereafter. For dated
references, subsequent amendments to or
revisions of any of these publications apply to this
European Standard only when incorporated in it
by amendment or revision. For undated
references the latest edition of the publication
referred to applies (including amendments).
NOTE: When an international publication has
been modified by common modifications,
Group Differences, Special National Conditions and National Deviations of CENELEC according to CB
Bulletin No. 112A, December 2006
P
Page 65 of 65
Report No.: 17013446 001
National Differences
Clause
Requirement − Test
Result – Remark
indicated by (mod), the relevant EN/HD applies.
EN 60417 Series
IEC 60417 Series
EN 60529:1991 + corr. May 1993
IEC 60529:1989

IEC/TR 60755:1983 + A1:1988
+ A2:1992
EN 60950-1:2001
IEC 60950-1 (mod):2001
EN 61000-2-2:2002
IEC 61000-2-2:2002

IEC 61008-1:1996
1)

IEC 61009-1:1996
2)
EN 62040-1-2:2003
IEC 62040-1-2:2002 + corr.
December 2002

IEC 62040-2:1999
EN 62040-3:2001
EN 62040-3 (mod):1999
Verdict

1)
The European standard EN 61008-1:1994 (IEC
61008-1:1990 + A1:1992, mod) + corrigendum
December 1997 + A2:1995 (IEC/A2:1995) +
A11:1995 + A12:1996 + corrigendum April
1998 + A13:1998 + A14:1998 applies.
2)
The European standard EN 61009-1:1994 (IEC
61009-1:1991, mod.) + corrigendum December
1997 + A1:1995 (IEC/A1:1995) + A11:1995 +
A2:1996 + A13:1998 + corrigendum April 1998
+ A14:1998 + A15:1998 + A17:1998 applies.
Group Differences, Special National Conditions and National Deviations of CENELEC according to CB
Bulletin No. 112A, December 2006
Page 1 of 13
Type Designation:
Report Number:
EATON E Series DX 6000H,
EATON E Series DX 6000HXL,
EATON E Series DX 10000H,
EATON E Series DX 10000HXL
17013446 001
Figure 1 front view (for all models)
Figure 2 back view (for model EATON E Series DX 6000H)
Page 2 of 13
Type Designation:
Report Number:
EATON E Series DX 6000H,
EATON E Series DX 6000HXL,
EATON E Series DX 10000H,
EATON E Series DX 10000HXL
17013446 001
Figure 3 back view (for model EATON E Series DX 6000HXL)
Figure 4 back view (for model EATON E Series DX 10000H)
Page 3 of 13
Type Designation:
Report Number:
EATON E Series DX 6000H,
EATON E Series DX 6000HXL,
EATON E Series DX 10000H,
EATON E Series DX 10000HXL
17013446 001
Figure 5 back view (for model EATON E Series DX 10000HXL)
Figure 6 side view of PSDR board for model EATON E Series DX 6000H and EATON
E Series DX 10000H
Page 4 of 13
Type Designation:
Report Number:
EATON E Series DX 6000H,
EATON E Series DX 6000HXL,
EATON E Series DX 10000H,
EATON E Series DX 10000HXL
17013446 001
Figure 7 side view of model EATON E Series DX 6000H and EATON E Series DX
10000H
Figure 8 view of internal battery for model EATON E Series DX 6000H and EATON E
Series DX 10000H
Page 5 of 13
Type Designation:
Report Number:
EATON E Series DX 6000H,
EATON E Series DX 6000HXL,
EATON E Series DX 10000H,
EATON E Series DX 10000HXL
17013446 001
Figure 9 side view of model EATON E Series DX 6000H and EATON E Series DX
10000H
Figure 10: side view of PSDR board for model EATON E Series DX 6000HXL and
EATON E Series DX 10000HXL
Page 6 of 13
Type Designation:
Report Number:
EATON E Series DX 6000H,
EATON E Series DX 6000HXL,
EATON E Series DX 10000H,
EATON E Series DX 10000HXL
17013446 001
Figure 11 view of the quick charger board for model EATON E Series DX 6000HXL and
EATON E Series DX 10000HXL
Figure 12 component side of quick charger board for model EATON E Series DX
6000HXL and EATON E Series DX 10000HXL
Page 7 of 13
Type Designation:
Report Number:
EATON E Series DX 6000H,
EATON E Series DX 6000HXL,
EATON E Series DX 10000H,
EATON E Series DX 10000HXL
17013446 001
Figure 13 copper side of quick charger board for model EATON E Series DX 6000HXL
and EATON E Series DX 10000HXL
Figure 14: component side of CNTL board for all models
Page 8 of 13
Type Designation:
Report Number:
EATON E Series DX 6000H,
EATON E Series DX 6000HXL,
EATON E Series DX 10000H,
EATON E Series DX 10000HXL
17013446 001
Figure 15: copper side of CNTL board for all models
Figure 16: component side of input EMI board for all models
Page 9 of 13
Type Designation:
Report Number:
EATON E Series DX 6000H,
EATON E Series DX 6000HXL,
EATON E Series DX 10000H,
EATON E Series DX 10000HXL
17013446 001
Figure 17: copper side of input EMI board for all models
Figure 18: component side of output EMI board
Page 10 of 13
Type Designation:
Report Number:
EATON E Series DX 6000H,
EATON E Series DX 6000HXL,
EATON E Series DX 10000H,
EATON E Series DX 10000HXL
17013446 001
Figure 19: copper side of output EMI board
Figure 20: component side of PSDR board for all model
Page 11 of 13
Type Designation:
Report Number:
EATON E Series DX 6000H,
EATON E Series DX 6000HXL,
EATON E Series DX 10000H,
EATON E Series DX 10000HXL
17013446 001
Figure 21: copper side of PSDR board for all model
Figure 22: component side of normal charger board for model EATON E Series DX
6000H and EATON E Series DX 10000H
Page 12 of 13
Type Designation:
Report Number:
EATON E Series DX 6000H,
EATON E Series DX 6000HXL,
EATON E Series DX 10000H,
EATON E Series DX 10000HXL
17013446 001
Figure 23: copper side of normal charger board for model EATON E Series DX 6000H
and EATON E Series X 10000H
Figure 24: component side of parallel board for all models
Page 13 of 13
Type Designation:
Report Number:
EATON E Series DX 6000H,
EATON E Series DX 6000HXL,
EATON E Series DX 10000H,
EATON E Series DX 10000HXL
17013446 001
Figure 25: copper side of parallel board for all models
Figure 26: Terminal block and separate PE terminal screw.
Download