Report No.: Page 2 of 65 17013446 001 Rating(s) ........................................... : For model EATON E Series DX 6000H, EATON E Series DX 6000HXL I/P : 220-240V~, 50/60Hz, 30.0A, 1Ф O/P: 220/230/240V~, 50/60Hz, 27A, 6kVA/4.2kW, 1Ф For model EATON E Series DX 10000H, EATON E Series DX 10000HXL: I/P : 220-240V~, 50/60Hz, 50.0A, 1Ф O/P: 220/230/240V~, 50/60Hz, 46A, 10kVA/7kW,1Ф TRF No.: IEC62040_1_1A TRF originator: SGS Fimko Report No.: Page 3 of 65 17013446 001 Copy of marking plate: Trade mark: Caution label on UPS: Caution label for the internal batteries: TRF No.: IEC62040_1_1A TRF originator: SGS Fimko Report No.: Page 4 of 65 17013446 001 Silkscreen for model EATON E Series DX 6000H: TRF No.: IEC62040_1_1A TRF originator: SGS Fimko Report No.: Page 5 of 65 17013446 001 Silkscreen for model EATON E Series DX 6000HXL: TRF No.: IEC62040_1_1A TRF originator: SGS Fimko Report No.: Page 6 of 65 17013446 001 Silkscreen for model EATON E Series DX 10000H: TRF No.: IEC62040_1_1A TRF originator: SGS Fimko Report No.: Page 7 of 65 17013446 001 Silkscreen for model EATON E Series DX 10000HXL: TRF No.: IEC62040_1_1A TRF originator: SGS Fimko Report No.: Page 8 of 65 17013446 001 Summary of testing: • Tests performed on the bench • Maximum ambient temperature: +40 °C • Tested for moderate conditions • EUT is designed for altitudes not exceeding 2000 m Additional evaluation according to EN 62040-1-1 for the output voltage was measured as a function of the input voltage for the certified supply voltage(s) including corresponding tolerances: as the output was varied from 220/230/240V, two different range were selected to demonstrate the output character. • • 198 V (-10%: 220 V, which is declared by manufacturer ) 254 V (+6%: 254 V, which is declared by manufacturer) Models: EATON E Series DX 6000H, EATON E Series DX 6000HXL, EATON E Series DX 10000H and EATON E Series DX 10000HXL: Input voltage [V] 198 220 230 240 254 (battery mode) 198 220 230 240 254 (battery mode) 198 220 230 240 254 (battery mode) Output voltage [V] (no load) output voltage set "220 V" 220.1 220.0 220.0 220.0 220.5 219.8 output voltage set "230 V" 230.3 230.4 230.4 230.4 230.4 230.2 Output voltage set "240 V" 240.4 240.6 240.7 240.5 240.5 240.5 Output voltage [V] (rated load) 220.1 220.1 220.0 220.1 220.1 220.1 230.3 230.4 230.4 230.1 230.3 230.4 240.2 240.2 240.1 240.1 240.5 240.3 Unless otherwise stated, all tests performed on model EATON E Series DX 6000HXL and model EATON E Series DX 10000HXL to represent the other similar models. TRF No.: IEC62040_1_1A TRF originator: SGS Fimko Report No.: Page 9 of 65 17013446 001 Particulars: test item vs. test requirements Equipment mobility ..................................... : Stationary (Castors must be locked under working condition) Operating condition ..................................... : Continuous Mains supply tolerance (%) ......................... : -10% ,+6% Tested for IT power systems ...................... : No IT testing, phase-phase voltage (V) ........... : N/A Class of equipment ..................................... : Class I Mass of equipment (kg)............................... : EATON E Series DX 6000H: 90kg EATON E Series DX 6000HXL:35kg EATON E Series DX 10000H: 103kg EATON E Series DX 10000HXL: 38kg Protection against ingress of water ............ : IP20 Test case verdicts Test case does not apply to the test object : N/A Test item does meet the requirement ........ : P(ass) Test item does not meet the requirement .. : F(ail) Testing Date of receipt of test item ......................... : Sep. 25. 2009 Date(s) of performance of test ................... : Oct. 2009 General remarks: ”This report is not valid as a CB Test Report unless appended by an approved CB Testing Laboratory and appended to a CB Test Certificate issued by an NCB in accordance with IECEE 02”. The test result presented in this report relate only to the object(s) tested. This report shall not be reproduced, except in full, without the written approval of the Issuing testing laboratory. ”(see Enclosure #)" refers to additional information appended to the report. "(see appended table)" refers to a table appended to the report. Throughout this report a point is used as the decimal separator. Standard IEC 62040-1-1:2002 is to be used in conjunction with IEC 60950-1:2001, which is referred to in this TRF by "RD". Comments: Summary of compliance with National Differences (for explanation of codes see below): AT, CH, DE, DK, FI, GB, HU, IT, KE, NL, NO, SE, SI, TR AT=Austria, CH=Switzerland, DE=Germany, DK=Denmark, FI=Finland, GB=United Kingdom, HU=Hungary, IT=Italy, KE=Kenya, NL=The Netherlands, NO=Norway, SE=Sweden, SI=Slovenia, TR=Turkey For National Differences see end of this test report. This report also includes 13 pages photo documents. Factory(ies): Santak Electronic (Shenzhen) Co.,Ltd. No. 8 Baoshi Rd., Block 72, Bao’an District, Shenzhen, Guangdong 518101, P.R. China TRF No.: IEC62040_1_1A TRF originator: SGS Fimko Report No.: Page 10 of 65 17013446 001 General product information: The EUT model is an on-line type uninterruptible power supply equipped with step-sinewave O/P for general supply of office equipment. See below block diagram for details The UPS is designed as "Primary" type: input and output circuits and battery circuits are considered as primary circuits and isolated from RS232 port by either double/reinforced insulation. Operator/laymen cannot replace the internal battery and external battery cabinet. Double/reinforced insulation provided between primary circuits or hazardous voltage to secondary circuits and SELV circuits by application of safety isolation transformers, use of photo coupler, bridging resistors, relays and sufficient clearances and creepage distances within the unit. Double/reinforced insulation provided between primary circuits or hazardous voltage to secondary circuits and SELV circuits by application of safety isolation transformers, use of photo coupler and sufficient clearances and creepage distances within the unit. Four castors fixed under the bottom of the UPS must be locked after installation when wired and ready for use. Before the UPS can be moved, all external wires must be completely disconnected. External battery cabinet rated 240VDC, 25A for model EATON E Series DX 6000HXL or 240VDC, 40A for model EATON E Series DX 10000HXL can be provided, it shall be evaluated in the final system. The enclosure consists of metal parts and thermoplastic front panel that is fixed to the metal chassis by metal screws. This report for UPS system covers 4 models of UPS (EATON E Series DX 6000H, EATON E Series DX 6000HXL, EATON E Series DX 10000H and EATON E Series DX 10000HXL). For UPS EATON E Series DX 6000H and EATON E Series DX 6000HXL are designed with same control logic, mains PCBs and output power except with or without internal battery and different charger board. For UPS EATON E Series DX 10000H and EATON E Series DX 10000HXL are designed with same control logic, mains PCBs and output power except with or without internal battery and different charger board. For UPS EATON E Series DX 6000H is same to EATON E Series DX 10000H except for rating for protection device and some power components See below table for detailed difference between four models (Other information see table 4.3 for details): EATON E Series DX 6000H EATON E Series DX 6000HXL EATON E Series DX 10000H EATON E Series DX 10000HXL Internal batteries 240VDC/24A (20 pieces with 7.2Ah battery used) None 240VDC/40A (20 pieces with 7.2Ah battery used) None Battery charger PCB (Primary+earth) 098-03731 (normal charger) mounted on PSDR board 098-01386 (quick charger) mounted in place of internal batteries 098-03731 (normal charger) mounted on PSDR board 098-01386 (quick charger) mounted in place of internal batteries Continued to next page. TRF No.: IEC62040_1_1A TRF originator: SGS Fimko Report No.: Page 11 of 65 PSDR board (Primary+earth) External battery cabinet 17013446 001 098-02191 None* Input breaker 240VDC/25A** 32A/250VAC 098-02309 None* 240VDC/40A** 50A/250VAC Remark: *External battery cabinet rating “240VDC, 25A” show on the rear panel of EATON E Series DX 6000H, “240VDC, 40A” show on the rear panel of EATON E Series DX 10000H due to the same design with other model. In fact, no external battery cabinet were provided for EATON E Series DX 6000H and EATON E Series DX 10000H. Double or reinforced insulation maintained between the internal bare live parts and external accessible area protectd by an additional cover provided to cover opening for the connector and fixed by screw. **It will not be provided currently. Main PCB used (others see above): 1. Input EMI PCB: 098-01093, for all models (Primary) 2. Output EMI board:098-01910 for all models (Primary) 3. CNTL PCB: 098-01094, for all models (Primary + SELV) 4. Parallel board. 098-01903 TRF No.: IEC62040_1_1A TRF originator: SGS Fimko Report No.: Page 12 of 65 17013446 001 IEC 62040-1-1 Clause Requirement – Test Result – Remark 4 GENERAL CONDITIONS FOR TESTS P 4.3 Components P 1.5.1/RD General See below. P Comply with IEC 60950-1 or relevant component Components which were found standard to affect safety aspects comply with the requirements of this standard or within the safety aspects of the relevant IEC component standards. (See appended table 4.3) 1.5.2/RD 1.5.4/RD 1.5.5/RD 1.5.6/RD Evaluation and testing of components Transformers Interconnecting cables Capacitors in primary circuits .......................... : Verdict P Components which were found to affect safety aspects comply with the requirements of this standard or within the safety aspects of the relevant IEC component standards. (See appended table 4.3) P Transformer used is suitable for their intended application and complies with the relevant requirements of the standard and particularly Annex C. P Interconnecting power cord set provided and fulfilled with the relevant national standard. See appended table 4.3 P Between lines: X2 type capacitors according to IEC 60384-14. Between lines and PE: Y2 type capacitors according to IEC 60384-14. P 1.5.7/RD Double insulation or reinforced insulation bridged by components N/A 1.5.7.1/RD General N/A 1.5.7.2/RD Bridging capacitors No bridging capacitors provided. N/A 1.5.7.3/RD Bridging resistors No such resistor N/A 1.5.7.4/RD Accessible parts N/A 1.5.8/RD Components in equipment for IT power systems Not applied for IT power systems. N/A 4.4 Power interface TRF No.: IEC62040_1_1A P TRF originator: SGS Fimko Report No.: Page 13 of 65 17013446 001 IEC 62040-1-1 Clause Requirement – Test Result – Remark 1.6.1/RD AC power distribution systems TN power system. P 1.6.2/RD Input current Highest normal load for this equipment is the charging of empty battery and operation with the maximum specified output load (see appended table 4.4) P 4.4 1.6.4/RD Neutral conductor The neutral conductor insulated from the body throughout the equipment. 4.5 Marking and instructions P 4.5.1 General P 4.5.2 Power rating See below P Input rated voltage/range (V)............................ : See page 3 for details P Input rated current/range (A) ............................ : See page 3 for details P Input symbol for nature of supply (d.c.) ........... : Not designed for "d.c. only". Therefore, no such marking required. Input rated frequency/range (Hz) ..................... : 50/60Hz P Output rated voltage/range (V) ........................ : See page 2 for details P Output rated current/range (A) ........................ : Refer to the marking plates P Number of output phases (1φ - 3φ) with/without neutral .............................................................. : UPS: 1φ No marking for provision of neutral required. P Output rated active power (W) ........................ : Refer to marking plate P Output rated apparent power (VA) .................. : Refer to marking plate P Output symbol for nature of supply (d.c.) ........ : No d.c. output. Therefore, no such marking required. Rated frequency or rated frequency range (Hz): 50/60Hz (all models) Max. ambient operating temperature range (°C) ................................................................... : Not shown. Manufacturer’s name or trademark or identification mark ........................................... : See page 3 for trademark. P Type/model or type reference .......................... : EATON E Series DX 6000H EATON E Series DX 6000HXL EATON E Series DX 10000H EATON E Series DX 10000HXL P Symbol for Class II equipment only ................. : Class I equipment TRF No.: IEC62040_1_1A Verdict P N/A N/A P N/A N/A TRF originator: SGS Fimko Report No.: Page 14 of 65 17013446 001 IEC 62040-1-1 Clause 4.5.3 Requirement – Test Result – Remark Verdict Other symbols ................................................. : Additional symbols or markings do not give rise to misunderstanding. P Certification marks .......................................... : See rating label for details P Instructions for units with automatic bypass/maintenance bypass, additional input a.c. supply, or external batteries, having text "See installation instructions before connecting to the supply" ................................................... : Text not required for this unit. Safety instructions See below. N/A P Guidance for installation for operator and service User's manual with directions person ............................................................. : regarding the maximum ambient temperature, electrical ratings, operation, description of interfaces, connection to the mains plus a note that the overall leakage current shall not exceed 3.5 mA. P Warning label with text "Isolate uninterruptible power supply (UPS) before working on this circuit" The warning information is specified in the user manual. P 4.5.4 Main voltage adjustment ................................. : No mains voltage adjustment device N/A 1.7.4/RD Supply voltage adjustment .............................. : No adjustment. N/A Methods and means of adjustment; reference to installation instructions .................................... : 4.5.5 1.7.5/RD Power outlets.................................................... : TRF No.: IEC62040_1_1A N/A No outlet. N/A TRF originator: SGS Fimko Report No.: Page 15 of 65 17013446 001 IEC 62040-1-1 Clause Requirement – Test Result – Remark 4.5.6 1.7.6/RD Fuse identification (marking, special fusing characteristics, cross-reference) ..................... : Fuse on PSDR board Verdict P F302: FU30A/250VDC (for model EATON E Series DX 6000H and EATON E Series DX 6000HXL) F301, F302:FU30A/250VDC (for model EATON E Series DX 10000H, EATON E Series DX 10000HXL) F303: FU30A/600VAC (for model EATON E Series DX 6000H and EATON E Series DX 6000HXL) F303, F304: FU30A/600VAC (for model EATON E Series DX 10000H and EATON E Series DX 10000HXL) Fuse on quick charger board (for model EATON E Series DX 6000HXL and EATON E Series DX 10000HXL) Fuse F1: F8A/600V Fuse on normal charger board (for model EATON E Series DX 6000H and EATON E Series DX 10000H) Fuse(F901-F906): F10A, 250VAC Breaker for EATON E Series DX 6000H, EATON E Series DX 6000HXL:32A, 400VAC Breaker for EATON E Series DX 10000H and EATON E Series DX 10000HXL: 50A, 400VAC 4.5.7 1.7.7/RD Wiring terminals See below. P 1.7.7.1/RD Protective earthing and bonding terminals ...... : Main earth connection for supply wiring is marked on main input screw terminal according IEC 60417 No. 5019. P 1.7.7.2/RD Terminal for a.c. mains supply conductors ..... : See page 4-7. Both input and output terminals are marked. P 1.7.7.3/RD Terminals for d.c. mains supply conductors .... : TRF No.: IEC62040_1_1A N/A TRF originator: SGS Fimko Report No.: Page 16 of 65 17013446 001 IEC 62040-1-1 Clause Requirement – Test Result – Remark 4.5.8 Battery terminals ............................................. : No marking required due to battery connectors designed in such a way to make wrong polarity connection impossible. 4.5.9 1.7.8/RD Controls and indicators See below. 1.7.8.1/RD Identification, location and marking ..................... LEDs provided, located on the front panel: Verdict N/A P • Green colour:(Normal) • Orange colour:(battery) • Red colour:(fault) P 1.7.8.2/RD Colours ........................................................... : See above. Colours are acceptable due to only used for information (no safety involved even if disregarded). P 1.7.8.3/RD Symbols according to IEC 60417 ..................... : Symbol for "standby" (No. 5009) provided on button on the front panel. P 1.7.8.4/RD Markings using figures ................................... : Not used. 4.5.10 1.7.9/RD Isolation of multiple power sources ................. : Marking attached near the breakers and connector for external battery cabinet. 4.5.11 IT power systems 1.7.10/RD IT power distribution systems 4.5.12 Protection in building installations Protection against electric shock does not rely on RCD. N/A 4.5.13 5.1/RD High leakage current (mA) .............................. : Leakage current of the equipment does not exceed 3.5 mA. N/A 4.5.14 1.7.11/RD Thermostats and other regulating devices Neither thermostats nor other regulating devices provided. N/A 4.5.15 1.7.12/RD Language(s) .................................................... : User's manual and markings are in both English. Other language will be provided when applying for national approval. TRF No.: IEC62040_1_1A N/A Not applied for IT power systems. P N/A N/A TRF originator: SGS Fimko Report No.: Page 17 of 65 17013446 001 IEC 62040-1-1 Clause Requirement – Test Result – Remark 4.5.16 1.7.13/RD Durability of markings The labels were subjected to the permanence of marking test. The labels were rubbed with cloth soaked with water for 15 s and then again for 15 s with the cloth soaked with petroleum spirit. Verdict P After this test there was no damage to the labels. The marking on the labels did not fade. There was neither curling nor lifting of the label edges. 4.5.17 1.7.14/RD Removable parts No required markings placed on removable parts. P 4.5.18 1.7.15/RD Replaceable batteries See information on page 3 for details P Language(s) .................................................... : 4.5.19 1.7.16/RD Operator access with a tool.............................. : N/A 4.5.20 Battery UPS with Integral batteries for models Eaton E Series DX 6000H and Eaton E Series DX 10000H P Clearly legible information ............................... : Warning label containing below described information placed on enclosure of UPS or user manual. P Battery type ..................................................... : Lead acid, type as "12Vdc/ 7Ah" P Nominal voltage of total battery (V) ................. : 240Vdc P Nominal capacity of total battery (optional) ..... : 7Ah P Warning label .................................................. : Warning label of UPS with information: P TRF No.: IEC62040_1_1A a) Chemical hazard b) Risk of electric shock and energy hazard c) Reference for maintenance and disposal to user's manual d) Lead acid battery inside UPS TRF originator: SGS Fimko Report No.: Page 18 of 65 17013446 001 IEC 62040-1-1 Clause Requirement – Test Result – Remark Instructions ...................................................... : Instructions of the UPS with information: Verdict P a) Maintenance and disposal instructions b) "Caution" statements regarding battery hazards c) Remark that servicing shall be performed by personnel knowledgeable of batteries 4.5.21 Installation instructions 5 FUNDAMENTAL DESIGN REQUIREMENTS P 5.1 Protection against electric shock and energy hazards P 2.1.1.2/RD Battery compartments ..................................... : No TNV circuits exist inside battery compartments N/A 2.1.1.4/RD Access to hazardous voltage circuit wiring No hazardous voltage circuit wiring can be accessed by operator. P 2.1.1.5/RD Energy hazards ............................................... : No energy hazard at operator accessible SELV interfaces (RS-232). P 2.1.1.6/RD Manual controls No conductive controls or handles or alike provided. 5.1.1 Operator access See below. P category a) Operator access to SELV circuits only. P category b) No operator access to any of the listed circuits and parts. P Access to ELV wiring No ELV wiring in operator accessible area. 5.1.2 2.1.1.3/RD Detailed information regarding external interfaces RS232 and connection of supply and loads provided in the user's manual. P N/A N/A Working voltage (Vpeak or Vrms); minimum distance (mm) through insulation 5.1.3 Discharge of capacitors in the primary circuit See appended table 5.1.3. P 2.1.1.7/RD Discharge of capacitors in equipment See appended table 5.1.3. P Time-constant (s); measured voltage (V)......... : 5.1.4 Backfeed protection TRF No.: IEC62040_1_1A Backfeed protection will be provided external to the UPS in the final installation. TRF originator: SGS Fimko Report No.: Page 19 of 65 17013446 001 IEC 62040-1-1 Clause Requirement – Test Result – Remark Description of the construction ........................ : 5.1.5 Emergency switching device 5.2 Insulation 2.2.3.1/RD Separation by double insulation or reinforced insulation (method 1) Verdict N/A RS-232 port can be considered as emergency switching device which can be controlled by software. Otherwise external breaker provided between terminal block and external wires. P P SELV circuits separated according to method 1. For details see appended tables 5.2. P 2.2.3.2/RD Separation by earthed screen (method 2) N/A 2.2.3.3/RD Protection by earthing of the SELV circuit (method 3) N/A 5.3 Limited current circuits 2.4.1/RD General requirements N/A 2.4.2/RD Limit values N/A No such circuits N/A Frequency (Hz)................................................. : Measured current (mA) .................................... : Measured voltage (V) ....................................... : Measured capacitance (µF) ............................. : 2.4.3/RD Connection of limited current circuits to other circuits 5.4 Provisions for protective earthing 2.6/RD Provisions for earthing and bonding See below. P 5.4.1 2.6.1/RD Protective earthing The chassis is reliably earthed by screw terminal with integrated star washer and screw. P 5.4.1 2.10/RD Clearances, creepage distances and distances through insulation 5.4.1 4.2.3/RD Steady force test, 30 N 5.4.1 5.3/RD Abnormal operating and fault conditions TRF No.: IEC62040_1_1A N/A P See appended tables 5.1.2, 5.8 and 9. P N/A See appended table 8.3. P TRF originator: SGS Fimko Report No.: Page 20 of 65 17013446 001 IEC 62040-1-1 Clause Requirement – Test Result – Remark 5.4.2 Bonding Metal enclosure and bonding conductors are provided. 5.5 AC and d.c. power isolation 2.6.2/RD Functional earthing No functional earthing necessary. P 2.6.3/RD Protective earthing and protective bonding conductors See below. P 2.6.3.1/RD General See 2.6.3.3/RD P 2.6.3.2/RD Size of protective earthing conductors Specified in the user manual P For model EATON E Series DX 6000H and model EATON E Series DX 6000HXL,: 2 Maximum 30A, Min. 2.5 mm EATON E Series DX 10000H, EATON E Series DX 10000HXL Maximum 50A, Min. 6mm2 P Protective Bonding by fixing earth terminal screw (M6) with star washer direct to chassis. P P P 2 Rated current (A), cross-sectional area (mm ), AWG................................................................. : 2.6.3.3/RD Verdict Size of protective bonding conductors 2 Rated current (A), cross-sectional area (mm ), AWG................................................................. : P 2.6.3.4/RD Resistance (Ω) of earthing conductors and their terminations, test current (A)............................ : 2.6.3.5/RD Colour of insulation........................................... : 2.6.4/RD Terminals P 2.6.4.1/RD General P 2.6.4.2/RD Protective earthing and bonding terminals See 2.6.3.3 P Rated current (A), type and nominal thread diameter (mm).................................................. : Max. 50A, M6 screw, steel with Zn platting. 2.6.4.3/RD Separation of the protective earthing conductor from protective bonding conductors Separated PE and protective bonding conductor used. 2.6.5/RD Integrity of protective earthing See below P 2.6.5.1/RD Interconnection of equipment This unit has it's own earthing connection. PE terminals of output reliably connected to bonding terminal of unit. P No switch or over-current protective device in protective earthing or bonding conductor. P 2.6.5.2/RD Components in protective earthing conductors and protective bonding conductors TRF No.: IEC62040_1_1A Green/Yellow P N/A TRF originator: SGS Fimko Report No.: Page 21 of 65 17013446 001 IEC 62040-1-1 Clause Requirement – Test Result – Remark 2.6.5.3/RD Disconnection of protective earth It is not necessary to disconnect earthing except for the removing of the earthed parts itself. Verdict P 2.6.5.4/RD Parts that can be removed by an operator No parts are intended to be removed for operator. 2.6.5.5/RD Parts removed during servicing No parts are intended to be removed for operator. 2.6.5.6/RD Corrosion resistance All safety earthing connections are compliance with Annex J P 2.6.5.7/RD Screws for protective bonding Protective Bonding by screw terminal with star washer direct to chassis. P 2.6.5.8/RD Reliance on telecommunication network or cable distribution system 5.5.1 Disconnect devices Building installation and specified external protection device which was stated in the user manual 5.5.2 Three-phase equipment EUT is single-phase equipment. N/A N/A N/A Interrupting neutral and phase conductors P N/A N/A 5.5.3 Switch as a disconnect device 1.7.8/RD Controls and indicators N/A 1.7.8.1/RD Identification, location and marking ................. : N/A 1.7.8.2/RD Colours ........................................................... : N/A 1.7.8.3/RD Symbols according to IEC 60417 ..................... : N/A 1.7.8.4/RD Markings using figures ................................... : N/A 5.5.4 Multiple power sources Only one supply connection provided. 5.5.5 Ungrounded conductors Ungrounded battery, the internal battery DC supply of the UPS can be disconnected by the quick connectors of the battery. 5.6 Overcurrent and earth fault protection P 2.7.3/RD Short-circuit backup protection P TRF No.: IEC62040_1_1A See sub clause 5.5.1. N/A N/A P TRF originator: SGS Fimko Report No.: Page 22 of 65 17013446 001 IEC 62040-1-1 Clause Requirement – Test Result – Remark 2.7.4/RD Number and location of protective devices ..... : Over current protection by breaker which disconnects phase and neutral conductor. Protection devices in the building installation considered to provide sufficient protection against earth faults. Verdict P 2.7.5/RD Protection by several devices One circuit breaker N/A 2.7.6/RD Warning to service personnel .......................... : See above N/A 5.6.1 Basic requirements Equipment relies on fuse or circuit breaker of the wall outlet protection of the building installation in regard to L to N short-circuit. P 5.6.2 Battery circuit protection Ungrounded batteries inside the UPS. Protection against overcurrent by 2 or 4 fuses in parallel in the plus pole of the battery supply circuit of the UPS. P 5.6.3 Location of protective device The fuse is directly located behind the supply wire of the batteries inside the UPS. P There are no hazardous conditions under any simulated fault conditions (see appended table 8.3). 5.6.4 Rating of protective device See below. P 5.3.1/RD Protection against overload and abnormal operation See appended table 8.3. P 5.7 Protection of personnel – Safety interlocks 5.7.1 Operator protection N/A 2.8/RD Safety interlocks N/A 2.8.1/RD General principles N/A 2.8.2/RD Protection requirements N/A 2.8.3/RD Inadvertent reactivation N/A 2.8.4/RD Fail-safe operation N/A 2.8.5/RD Moving parts N/A 2.8.6/RD Overriding N/A 2.8.7/RD Switches and relays N/A TRF No.: IEC62040_1_1A P TRF originator: SGS Fimko Report No.: Page 23 of 65 17013446 001 IEC 62040-1-1 Clause Requirement – Test Result – Remark 2.8.7.1/RD Contact gaps (mm) .......................................... : N/A 2.8.7.2/RD Overload test N/A 2.8.7.3/RD Endurance test N/A 2.8.7.4/RD Electric strength test 2.8.8/RD Mechanical actuators 5.7.2 Service person protection 5.7.2.1 Covers N/A 5.7.2.2 Location and guarding of parts N/A 5.7.2.3 Parts on doors N/A 5.7.2.4 Component access N/A 2.8.3/RD Inadvertent reactivation N/A 5.7.2.5 Moving parts N/A 5.7.2.6 Capacitor banks N/A 5.7.2.7 Internal batteries 5.8 2.10/RD Clearances, creepage distances and distances through insulation P 2.10.1/RD General See 2.10.3/RD, 2.10.4/RD and 2.10.5/RD. P 2.10.2/RD Determination of working voltage Unit was connected to a 240 V (maximum) TN power system P (see appended table 5.8) Verdict N/A N/A No adjustments or measurements inside the equipment are necessary while the unit is energized. Risk of short-circuiting minimized by design of used battery source and corresponding terminals and wiring methods used. P P See appended table 5.8. 2.10.3/RD Clearances See below, Annex G was not considered. P 2.10.3.1/RD General Annex F/RD and minimum clearances considered. P 2.10.3.2/RD Clearances in primary circuits See appended table 5.8 and 9. P 2.10.3.3/RD Clearances in secondary circuits Subclause 5.3.4/RD considered. N/A 2.10.3.4/RD Measurement of transient voltage levels Normal transient voltage considered (overvoltage category II for primary circuit). N/A TRF No.: IEC62040_1_1A TRF originator: SGS Fimko Report No.: Page 24 of 65 17013446 001 IEC 62040-1-1 Clause Requirement – Test Result – Remark 2.10.4/RD Creepage distances See appended table 5.8 and 9. P CTI tests........................................................... : CTI rating for all materials of min. 100. 2.10.5/RD Solid insulation See below. P 2.10.5.1/RD Minimum distance through insulation See appended table. P 2.10.5.2/RD Thin sheet material Insulation tape of transformer , See Annex C for transformer TX200 on CNTL board P Number of layers (pcs)..................................... : See appended table C.2/RD. Electric strength test See appended table 5.8, 6, 8.2 and 9. 2.10.5.3/RD Printed boards N/A Distance through insulation N/A Electric strength test for thin sheet insulating material Number of layers (pcs)..................................... : 2.10.5.4/RD Verdict Wound components N/A See only 2.10.5.2/RD P Number of layers (pcs)..................................... : N/A Two wires in contact inside wound component; angle between 45° and 90° ............................. : N/A 2.10.6/RD Coated printed boards N/A 2.10.6.1/RD General N/A 2.10.6.2/RD Sample preparation and preliminary inspection N/A 2.10.6.3/RD Thermal cycling N/A 2.10.6.4/RD Thermal ageing (°C)......................................... : N/A 2.10.6.5/RD Electric strength test 2.10.6.6/RD Abrasion resistance test N/A Electric strength test 2.10.7/RD 2.10.8/RD Enclosed and sealed parts ............................... : N/A Temperature T1=T2 + Tma – Tamb +10K (°C) ..... : N/A Spacings filled by insulating compound ........... : Certified sources of optical isolator are used. No other components applied for. P Electric strength test (See appended table 5.2) 2.10.9/RD Component external terminations See appended table 5.8 and 9. P 2.10.10/RD Insulation with varying dimensions Insulation kept homogenous TRF No.: IEC62040_1_1A N/A TRF originator: SGS Fimko Report No.: Page 25 of 65 17013446 001 IEC 62040-1-1 Clause Requirement – Test 5.9 External signalling circuits Result – Remark Verdict N/A No TNV circuits exist in the product, requirements not applicable to the evaluated product 2.3/RD TNV circuits N/A 2.3.1/RD Limits N/A Type of TNV circuits......................................... : 2.3.2/RD Separation from other circuits and from accessible parts Insulation employed ......................................... : 2.3.3/RD Separation from hazardous voltages Insulation employed ......................................... : 2.3.4/RD Connection of TNV circuits to other circuits N/A N/A N/A Insulation employed ......................................... : 2.3.5/RD Test for operating voltages generated externally N/A 5.10 2.5/RD Limited power sources N/A Requirements not applicable to the evaluated product. Inherently limited output N/A Impedance limited output N/A Overcurrent protective device limited output N/A Regulating network limited output under normal operating and single fault condition N/A Regulating network limited output under normal operating conditions and overcurrent protective device limited output under single fault condition N/A Output voltage (V), output current (A), apparent power (VA) ....................................................... : Current rating of overcurrent protective device (A) .................................................................... : 6 WIRING, CONNECTIONS AND SUPPLY P 6.1 3.1/RD General P TRF No.: IEC62040_1_1A TRF originator: SGS Fimko Report No.: Page 26 of 65 17013446 001 IEC 62040-1-1 Clause Requirement – Test Result – Remark 3.1.1/RD Current rating and overcurrent protection All internal wires are UL recognized, PVC insulated and rated: VW-1, 80°C/105°C, 300V/600V Verdict P The wiring has gauge suitable for the current intended to be carried. 3.1.2/RD 3.1.3/RD 3.1.4/RD Protection against mechanical damage Securing of internal wiring Insulation of conductors Wires do not touch sharp edges and heatsinks, which could damage the insulation and cause hazard. P Internal wires with only basic isolation are routed so that they are not close to any live bare components. The wires are secured by soldering and solder pins (or cable ties) so that a loosening of the terminal connection is unlikely. P The insulation of the individual conductors is suitable for the application and the working voltage. For the insulation materials see sub-clause 3.1.1. P 3.1.5/RD Beads and ceramic insulators See appended table 5.2 P 3.1.6/RD Screws for electrical contact pressure Protective bonding connections are provided by stud with at least two thread diameter. P 3.1.7/RD Insulating materials in electrical connections Contact pressure is not transmitted through insulating material. P 3.1.8/RD Self-tapping and spaced thread screws Not provided. 3.1.9/RD Termination of conductors All conductors are reliably secured by use of solder-pins or other mechanical means. P 10 N pull test Test performed and passed. P Sleeving on wiring Safety relevant sleeves are long enough to fit to wire length. P 3.1.10/RD TRF No.: IEC62040_1_1A N/A TRF originator: SGS Fimko Report No.: Page 27 of 65 17013446 001 IEC 62040-1-1 Clause Requirement – Test 6.2 Connection to power 3.2.2/RD Multiple supply connections 3.2.3/RD Result – Remark Verdict P Permanently connected equipment Clearly marked terminals for mains and separate connector for external battery supply. P Terminals for permanent connection to supply. P Number of conductors, diameter (mm) of cable and conduits ..................................................... : 3.2.4/RD Appliance inlets Not used. N/A 3.2.5/RD Power supply cords No power cord used N/A 3.2.5.1/RD AC power supply cords N/A Type .................................................................... : See above 2 Rated current (A), cross-sectional area (mm ), See above AWG....................................................................: 3.2.5.2/RD DC power supply cords N/A 3.2.6/RD Cord anchorages and strain relief N/A 3.2.7/RD Protection against mechanical damage N/A 3.2.8/RD Cord guards N/A 6.2.1 D (mm); test mass (g) ..................................... : Radius of curvature of cord (mm) .................... : Means of connection ....................................... : See subclause 3.2.4/RD. More than one supply connection ................... : Only one mains supply connection provided. P N/A 6.3 Wiring terminals for external power conductors 3.3.1/RD Wiring terminals 3.3.2/RD Connection of non-detachable power supply cords 3.3.3/RD Screw terminals ISO type M6 used. P 3.3.4/RD Conductor sizes to be connected Conductor size will be connected according to installation manual. P Rated current (A), cord/cable type, cross2 sectional area (mm ) ........................................ : TRF No.: IEC62040_1_1A N/A Input and output with separate terminals of same type P N/A 2 30A, 10AWG (4mm ) for Eaton E Series DX 6000H and Eaton E Series DX 6000H XL. 2 50A, 8AWG (6mm ) for Eaton E Series DX 10000H and Eaton E Series DX 10000HXL. TRF originator: SGS Fimko Report No.: Page 28 of 65 17013446 001 IEC 62040-1-1 Clause Requirement – Test Result – Remark 3.3.5/RD Wiring terminal sizes See below Rated current (A), type and nominal thread diameter (mm) ................................................. : ISO type M5 screw terminal used. Verdict N/A 3.3.6/RD Wiring terminals design P 3.3.7/RD Grouping of wiring terminals P 3.3.8/RD Stranded wire 7 PHYSICAL REQUIREMENTS 7.1 Enclosure Metal enclosure not used to carry current. Metal enclosure completely enclosing hazardous parts. P 7.2 Stability See below. P 4.1/RD Angle of 10° The unit does not overbalance P Barrier between terminals for each clamping unit provided. P P Tilted to an angle of 10° Test: force (N) .................................................. : N/A 7.3 Mechanical strength 4.2.1/RD General Tests performed and passed. Results see below. After tests, unit complied with the requirements of sub-clauses 2.1.1/RD, 2.6.1/RD and 2.10/RD. P 4.2.2/RD Steady force test, 10 N 10 N applied to all components other than enclosure. P 4.2.3/RD Steady force test, 30 N 4.2.4/RD Steady force test, 250 N 250 N applied to outer enclosure. P 4.2.5/RD Impact test See below. P Fall test No hazard as result from steel ball fall test. P Swing test No hazard as result from steel ball swing test. P 4.2.6/RD Drop test Not required for this equipment. N/A 4.2.7/RD Stress relief test Test performed at 70°C no distortion found on front panel. P 4.2.8/RD Cathode ray tubes No CRT in the unit. Picture tube separately certified ....................... : TRF No.: IEC62040_1_1A P N/A N/A N/A TRF originator: SGS Fimko Report No.: Page 29 of 65 17013446 001 IEC 62040-1-1 Clause Requirement – Test Result – Remark Verdict 4.2.9/RD High pressure lamps No high pressure lamp provided. 4.2.10/RD Wall or ceiling mounted equipment; force (N) . : 7.4 Construction details 4.3.1/RD Edges and corners Edges and corners of the enclosure are rounded. 4.3.2/RD Handles and manual controls; force (N) .......... : No handles or manual controls provided. No axial pull applied to push-buttons. N/A 4.3.3/RD Adjustable controls No such adjustable controls device N/A 4.3.4/RD Securing of parts Mechanical fixings in such a way designed that they will withstand mechanical stress occurring in normal use. P 4.3.5/RD Connection of plugs and sockets No mismating of connectors, plugs or sockets possible. P 4.3.6/RD Direct plug-in equipment Not direct plug-in type. N/A N/A P P N/A Dimensions (mm) of mains plug for direct plug-in ............................................................ : N/A Torque and pull test of mains plug for direct plug-in; torque (Nm); pull (N)............................ : N/A 4.3.7/RD Heating elements in earthed equipment No heating elements provided. N/A 4.3.8/RD Batteries (see also 4.5.20) Lead-acid battery protected against overcharging and overdischarging by regulating network. Performance evaluated during the abnormal operation test. Details see in table 8.3. P 4.3.9/RD Oil and grease Insulation in intended use not considered to be exposed to oil or grease. N/A 4.3.10/RD Dust, powders, liquids and gases The equipment in intended use not considered to be exposed to dust, powders, liquids and gases. For the ventilation of the lead-acid battery refer to table N.4. P 4.3.11/RD Containers for liquids or gases No container for liquids or gases provided. TRF No.: IEC62040_1_1A N/A TRF originator: SGS Fimko Report No.: Page 30 of 65 17013446 001 IEC 62040-1-1 Clause Requirement – Test Result – Remark 4.3.12/RD Flammable liquids ............................................ : No flammable liquids provided. Verdict N/A Quantity of liquid (l) .......................................... : N/A Flash point (°C) ................................................ : N/A 4.3.13/RD Radiation; type of radiation .............................. : No hazardous radiation. P 4.3.13.1/RD General See below. P 4.3.13.2/RD Ionizing radiation No ionizing radiation present. 4.3.13.3/RD N/A Measured radiation (pA/kg) ............................. : Measured high-voltage (kV) ............................ : Measured focus voltage (kV) .......................... : CRT markings ................................................. : Effect of ultraviolet (UV) radiation on materials No UV radiation present. N/A Part, property, retention after test, flammability classification .................................................... : N/A 4.3.13.4/RD Human exposure to ultraviolet (UV) radiation . : N/A 4.3.13.5/RD Laser (including LEDs) See below. P Laser class ...................................................... : Emission of indicator LEDs far below the limiting value of LED Class 1. 4.3.13.6/RD Other types ...................................................... : 7.4.1 Openings See appended table 7.4.1. P 7.4.2 Gas concentration For the ventilation of the leadacid battery refer to table N.4. P 7.4.3 Equipment movement No castors provided. 7.5 4.7/RD Resistance to fire 4.7.1/RD Reducing the risk of ignition and spread of flame See below. P Method 1, selection and application of components wiring and materials Use of materials with the required flammability classes. P N/A P Method 2, application of all of simulated fault condition tests 4.7.2/RD Conditions for a fire enclosure TRF No.: IEC62040_1_1A N/A N/A See below. P TRF originator: SGS Fimko Report No.: Page 31 of 65 17013446 001 IEC 62040-1-1 Clause Requirement – Test Result – Remark 4.7.2.1/RD Parts requiring a fire enclosure With having the following components: Verdict P 1. Components in primary circuits 2. Insulated wiring The fire enclosure is required. 4.7.2.2/RD Parts not requiring a fire enclosure N/A 4.7.3/RD Materials 4.7.3.1/RD General PCB rated accordingly. For details see table 4.3. P 4.7.3.2/RD Materials for fire enclosures Metal enclosure with thermoplastic front panel. For details see table 4.3. P 4.7.3.3/RD Materials for components and other parts outside fire enclosures See subclause 4.7.2/RD. 4.7.3.4/RD Materials for components and other parts inside Internal components except fire enclosures small parts are V-2, HF-2 or better. P N/A P Batteries have a flammability class of HB (or better). 4.7.3.5/RD Materials for air filter assemblies No air filters provided. N/A 4.7.3.6/RD Materials used in high-voltage components No high voltage components provided. N/A 7.6 Battery location 7.6.1 Accessibility and maintainability Maintenance free batteries used inside the UPS. The batteries are connected by quick connect terminals (no necessary tightening). 7.6.2 Vibration No requirements declared by the battery manufacturer. 7.6.3 Distance The temperature of the electrolyte and the gas emission are within the limits of this standard (see appropriate subclauses). 7.6.4 Insulation No Ni-Cd battery used inside. 7.6.5 Wiring The protection of connection wiring complies with subclause 3/RD. TRF No.: IEC62040_1_1A P P N/A P N/A P TRF originator: SGS Fimko Report No.: Page 32 of 65 17013446 001 IEC 62040-1-1 Clause Requirement – Test Result – Remark Verdict 7.6.6 Electrolyte spillage Sealed maintenance free batteries provided with an unlikely emission of electrolyte (VRLA type). P 7.6.7 Ventilation For the ventilation of the leadacid battery refer to table N.4. P 7.6.8 Charging voltages See appended table 8.3. P 7.7 Temperature rise P Maximum temperatures See appended table 7.7 P 4.5.2/RD Resistance to abnormal heat P 8 ELECTRICAL REQUIREMENTS AND SIMULATED ABNORMAL CONDITIONS P 8.1 5.1.1/RD General P 8.1.1 Earth leakage current See subclause 5.1.2/RD below. P 5.1.2/RD Equipment under test (EUT) EUT has only one mains connection. However, total touch current is depending on interconnected equipment. P 5.1.7/RD Equipment with touch current exceeding 3.5 mA ............................................................. : Touch current of the equipment does not exceed 3.5 mA. P However due to the connected load has influence on the overall touch current a corresponding statement was provided in the user’s manual. 8.1.2 Pluggable equipment type B UPS N/A 3.2.5/RD Power supply cords N/A 3.2.5.1/RD AC power supply cords N/A Type ................................................................. : 2 Rated current (A), cross-sectional area (mm ), AWG................................................................. : 3.2.5.2/RD DC power supply cords 8.2 Electric strength 5.2.1/RD General (see appended table 5.8) P 5.2.2/RD Test procedure (see appended table 5.8) P TRF No.: IEC62040_1_1A N/A P TRF originator: SGS Fimko Report No.: Page 33 of 65 17013446 001 IEC 62040-1-1 Clause Requirement – Test Result – Remark 8.3 Abnormal operating and fault conditions 5.3.1/RD Protection against overload and abnormal operation See appended table 8.3. 5.3.2/RD Motors Approved source of DC fan is used. 5.3.3/RD Transformers With the shorted circuit of the main transformer TX200 on CNTL board, no high temperatures of the transformers were recorded. Verdict P P N/A P See appended Annex C. 5.3.4/RD Functional insulation.......................................... : The functional insulation was short circuit. For the test results, refer to the appended table 8.3. P 5.3.5/RD Electromechanical components Refer to appended table 8.3. P 5.3.8/RD Compliance criteria for abnormal operating and fault conditions Refer to appended table 8.3. 8.3.1 Simulation of faults None of the listed components are provided. N/A 8.3.2 Conditions for tests No fire occurred. Electric strength tests applied between primary and secondary, and respectively chassis, passed. P P 9 CONNECTION TO TELECOMMUNICATION NETWORKS N/A 6.1/RD Protection of telecommunication network service persons, and users of other equipment connected to the network, from hazards in the equipment N/A 6.1.1/RD Protection from hazardous voltages N/A 6.1.2/RD Separation of the telecommunication network from earth N/A 6.1.2.1/RD Requirements N/A Test voltage (V) ............................................... : Current in the test circuit (mA) ...................... : 6.1.2.2/RD Exclusions ........................................................ : N/A 6.2/RD Protection of equipment users from overvoltages on telecommunication networks N/A 6.2.1/RD Separation requirements N/A 6.2.2/RD Electric strength test procedure N/A 6.2.2.1/RD Impulse test N/A 6.2.2.2/RD Steady-state test N/A TRF No.: IEC62040_1_1A TRF originator: SGS Fimko Report No.: Page 34 of 65 17013446 001 IEC 62040-1-1 Clause Requirement – Test Result – Remark Verdict 6.2.2.3/RD Compliance criteria N/A 6.3/RD Protection of the telecommunication wiring system from overheating N/A Max. output current (A) .................................... : Current limiting method .................................... : 1.4.8/RD Normal operating voltages .............................. : N/A 1.4.11/RD Power from a telecommunication network ...... : N/A 2.1.1/RD Protection in operator access areas N/A 2.1.1.1/RD Access to energized parts N/A Test by inspection ........................................... : N/A Test with test finger ......................................... : N/A Test with test pin ............................................. : N/A Test with test probe ......................................... : N/A 2.1.1.2/RD Battery compartments ..................................... : N/A 2.1.3/RD Protection in restricted access locations N/A 2.3/RD TNV circuits N/A 2.3.1/RD Limits N/A Type of TNV circuits......................................... : 2.3.2/RD Separation from other circuits and from accessible parts Insulation employed ......................................... : 2.3.3/RD Separation from hazardous voltages Insulation employed ......................................... : 2.3.4/RD Connection of TNV circuits to other circuits N/A N/A N/A Insulation employed ......................................... : 2.3.5/RD Test for operating voltages generated externally N/A 2.6.1/RD Protective earthing N/A 2.6.5.8/RD Reliance on telecommunication network or cable distribution system N/A 2.9.5/RD Grade of insulation N/A 2.10.3.3/RD Clearances in secondary circuits N/A 2.10.3.4/RD Measurement of transient voltage levels N/A 2.10.4/RD Creepage distances N/A 3.5/RD Interconnection of equipment N/A 3.5.1/RD General requirements N/A TRF No.: IEC62040_1_1A TRF originator: SGS Fimko Report No.: Page 35 of 65 17013446 001 IEC 62040-1-1 Clause Requirement – Test Result – Remark 3.5.2/RD Types of interconnection circuits....................... : N/A M/RD ANNEX M, CRITERIA FOR TELEPHONE RINGING SIGNALS (see 2.3.1/RD) N/A M.1/RD Introduction N/A M.2 /RD Method A N/A M.3/RD Method B N/A M.3.1/RD Ringing signal N/A M.3.1.1/RD Frequency (Hz) ................................................ : M.3.1.2/RD Voltage (V) ...................................................... : M.3.1.3/RD Cadence; time (s), voltage (V) ........................ : M.3.1.4/RD Single fault current (mA) .................................. : M.3.2/RD Tripping device and monitoring voltage ........... : N/A M.3.2.1/RD Conditions for use of a tripping device or a monitoring voltage N/A M.3.2.2/RD Tripping device N/A M.3.2.3/RD Monitoring voltage (V) ...................................... : N/A A/RD ANNEX A, TESTS FOR RESISTANCE TO HEAT AND FIRE P A.1/RD Flammability test for fire enclosures of movable equipment having a total mass exceeding 18 kg, and of stationary equipment (see 4.7.3.2/RD) P A.1.1/RD Samples ........................................................... : Wall thickness (mm) ........................................ : A.1.2/RD Conditioning of samples; temperature (°C)...... : N/A A.1.3/RD Mounting of samples ........................................ : N/A A.1.4/RD Test flame (see IEC 60695-11-3) N/A Flame A, B, C or D .......................................... : A.1.6/RD Verdict Compliance criteria N/A Sample 1 burning time (s) ................................ : Sample 2 burning time (s) ................................ : Sample 3 burning time (s) ................................ : A.2/RD Flammability test for fire enclosures of movable equipment having a total mass not exceeding 18 kg, and for material and components located inside fire enclosures (see 4.7.3.2/RD and 4.7.3.4/RD) A.2.1/RD Samples, material ............................................ : Wall thickness (mm) ........................................ : TRF No.: IEC62040_1_1A N/A TRF originator: SGS Fimko Report No.: Page 36 of 65 17013446 001 IEC 62040-1-1 Clause Requirement – Test Result – Remark Verdict A.2.2/RD Conditioning of samples N/A A.2.3/RD Mounting of samples N/A A.2.4/RD Test flame (see IEC 60695-11-4) N/A Flame A, B or C ............................................... : A.2.5/RD Test procedure N/A A.2.6/RD Compliance criteria N/A A.2.7/RD Sample 1 burning time (s) ................................ : Sample 2 burning time (s) ................................ : Sample 3 burning time (s) ................................ : Alternative test acc. to IEC 60695-2-2, cl. 4 and 8 N/A Sample 1 burning time (s) ................................ : Sample 2 burning time (s) ................................ : Sample 3 burning time (s) ................................ : A.3/RD Hot flaming oil test (see 4.6.2) N/A A.3.1/RD Mounting of samples N/A A.3.2/RD Test procedure N/A A.3.3/RD Compliance criterion N/A B/RD ANNEX B, MOTOR TESTS UNDER ABNORMAL CONDITIONS (see 4.7.2.2/RD and 5.3.2/RD) B.1/RD General requirements VDE or TUV approved source of primary DC fan provided. No further tests of this subclause necessary. P N/A Position ............................................................ : Manufacturer ................................................... : Type ................................................................ : Rated values .................................................. : B.2/RD Test conditions N/A B.3/RD Maximum temperatures N/A B.4/RD Running overload test N/A B.5/RD Locked-rotor overload test N/A Test duration (days) ........................................ : Electric strength test: test voltage (V) ............. : TRF No.: IEC62040_1_1A TRF originator: SGS Fimko Report No.: Page 37 of 65 17013446 001 IEC 62040-1-1 Clause Requirement – Test Result – Remark Verdict B.6/RD Running overload test for d.c. motors in secondary circuits N/A B.7/RD Locked-rotor overload test for d.c. motors in secondary circuits N/A B.7.1/RD Test procedure N/A B.7.2/RD Alternative test procedure; test time (h) ........... : N/A B.7.3/RD Electric strength test N/A B.8/RD Test for motors with capacitors N/A B.9/RD Test for three-phase motors N/A B.10/RD Test for series motors N/A Operating voltage (V) ...................................... : ANNEX C, TRANSFORMERS (see 1.5.4/RD and 5.3.3/RD) P Position ............................................................ : Transformer TX200 used on CNTL board Manufacturer ................................................... : See table 4.3 Type ................................................................ : See table 4.3 Rated values .................................................. : See table 4.3 Method of protection......................................... : Circuit design (inherently) C.1/RD Overload test See appended table 5.3. P C.2/RD Insulation See appended table C.2. P C/RD Protection from displacement of windings ....... : P D/RD ANNEX D, MEASURING INSTRUMENTS FOR TOUCH-CURRENT TESTS (see 5.1.4/RD) P D.1/RD Measuring instrument Measuring instrument according to figure D.1 was used. P D.2/RD Alternative measuring instrument Not used. E/RD ANNEX E, TEMPERATURE RISE OF A WINDING (see 1.4.13/RD) F/RD ANNEX F, MEASUREMENT OF CLEARANCES AND CREEPAGE DISTANCES (see 2.10/RD) TRF No.: IEC62040_1_1A N/A N/A P TRF originator: SGS Fimko Report No.: Page 38 of 65 17013446 001 IEC 62040-1-1 Clause Requirement – Test Result – Remark G/RD ANNEX G, ALTERNATIVE METHOD FOR DETERMINING MINIMUM CLEARANCES Verdict N/A Alternative method not used G.1/RD Summary of the procedure for determining minimum clearances N/A G.2/RD Determination of mains transient voltage (V) ... : N/A G.2.1/RD AC mains supply N/A G.2.2/RD DC mains supply N/A G.3/RD Determination of telecommunication network transient voltage (V) ......................................... : N/A G.4/RD Determination of required withstand voltage (V): N/A G.5/RD Measurement of transient levels (V) ................ : N/A G.6/RD Determination of minimum clearances............. : N/A H ANNEX H, GUIDANCE ON PROTECTION AGAINST INGRESS OF WATER AND FOREIGN OBJECTS (see IEC 60529) N/A J/RD ANNEX J, TABLE OF ELECTROCHEMICAL POTENTIALS (see 2.6.5.6/RD) P Metal used ....................................................... : Ring-type lug, Screw and star washer steel with Zn platting. Trace(Copper) contact with screw and spring washer steel was covered by stannum. Enclosure is made of mild steel. K/RD ANNEX K, THERMAL CONTROLS (see 1.5.3 and 5.3.7) N/A K.1/RD Making and breaking capacity N/A K.2 /RD Thermostat reliability; operating voltage (V)..... : N/A K.3/RD Thermostat endurance test; operating voltage (V) ................................................................... : N/A K.4/RD Temperature limiter endurance; operating voltage (V) ....................................................... : N/A K.5/RD Thermal cut-out reliability N/A K.6/RD Stability of operation N/A L ANNEX L, BACKFEED PROTECTION TEST N/A L.1 General N/A L.2 Test for pluggable equipment type A or pluggable equipment type B UPS TRF No.: IEC62040_1_1A N/A TRF originator: SGS Fimko Report No.: Page 39 of 65 17013446 001 IEC 62040-1-1 Clause Requirement – Test Result – Remark L.3 Test for permanently connected UPS N/A L.4 Single-fault conditions N/A M ANNEX M, EXAMPLES OF REFERENCE LOAD CONDITIONS P M.1 General P M.2 Reference resistive load N/A M.3 Reference inductive-resistive load N/A M.4 Reference capacitive-resistive loads M.5 Reference non-linear load N/A M.5.1 Test method N/A M.5.2 Connection of the non-linear reference load N/A N ANNEX N, VENTILATION OF BATTERY COMPARTMENTS P N.1 General Sufficient openings are provided in such a way that a local concentration of hydrogen and oxygen is not possible. No requirement regarding the separation of operational arcing parts from battery vents/valves. P N.2 Hydrogen concentration See N.1 above. P N.3 Blocked conditions No fans or other devices provided for ventilation purposes. N/A N.4 Overcharge test See appended table N.4. P U/RD ANNEX U, INSULATED WINDING WIRES FOR USE WITHOUT INTERLEAVED INSULATION (see 2.10.5.4/RD) See below. Worst-case power factors as specified by the manufacturer maintained during the relevant tests. See separate test report X ANNEX X, GUIDANCE FOR DISCONNECTION OF BATTERIES DURING SHIPMENT Verdict P N/A N/A Informative X.1 Applicable products N/A X.2 Battery disconnection N/A X.3 Package labelling/marking N/A TRF No.: IEC62040_1_1A TRF originator: SGS Fimko Report No.: Page 40 of 65 17013446 001 IEC 62040-1-1 Clause Requirement – Test X.4 Damage inspection N/A X.5 The importance of safe handling procedures N/A Y/RD ANNEX Y, ULTRAVIOLET LIGHT CONDITIONING TEST (see 4.3.13.3/RD) N/A Y.1/RD Test apparatus ................................................ : N/A Y.2/RD Mounting of test samples ................................ : N/A Y.3/RD Carbon-arc light-exposure apparatus .............. : N/A Y.4/RD Xenon-arc light exposure apparatus ............... : N/A TRF No.: IEC62040_1_1A Result – Remark Verdict TRF originator: SGS Fimko Report No.: Page 41 of 65 4.3 17013446 001 TABLE: list of critical components Object/part no. Manufacturer/ trademark Type/model P Technical data Standard Mark(s) of conformity 1. models for Eaton E Series DX 6000H/ 6000H XL/10000H/10000HXL DC FAN(1 pcs for 6000H/ 6000HXL, 2 pcs NMB for 10000H/ 10000HXL 4715KL 12VDC, 0.90A IEC/EN 60950-1 VDE 116206 Metal enclosure -- -- Min. 1.2mm -- Test in appliance Front panel C2950 2.5MM, 5VB, 75℃ UL94 UL E207780 (Alternative) SABIC INNOVATIVE PLASTICS JAPAN L L C CHIMEI PA-765A(+) 2.5MM, 5VB, 80℃ UL94 UL E56070 Air flow Sheet various various 0.15mm min., V-0 UL UL Battery wire For 10000H various various 105℃, 600V, 12AWG min., VW-1 UL UL I/P Wire & O/P Wire various various 105℃, 600V, 12AWG min., VW-1 UL UL Ground wire various various 105℃, 600V, 14AWG min., VW-1 UL UL Breaker for ABB 6000H/6000HXL S200 2 pole, 32A, IEC/EN 60947-2 CCA/DE1 33308 400VAC, type D Alternative Tian shui GSB2 2 pole, 32A, IEC/EN 60898-1 TUV R50107925 400VAC, type D Alternative Liang xin NDB2 Alternative Moeller FAZ-C32/2 Breaker for 10000H/10000 HXL ABB S200 Alternative Tian shui GSB2 Alternative Liang xin NDB2 Alternative Moeller FAZ-C50/2 TRF No.: IEC62040_1_1A 2 pole, 32A, IEC/EN 60898-1 TUV R50125739 400VAC, type D 2 pole, 32A, IEC/EN 60898-1 VDE 40000771 400VAC, type C 2 pole, 50A, IEC/EN 60947-2 CCA/DE1 33308 400VAC, type D 2 pole, 50A, IEC/EN 60898-1 TUV R50107925 400VAC, type D 2 pole, 50A, IEC/EN 60898-1 TUV R50125739 400VAC, type D 2 pole, 50A, VDE 40000771 400VAC, type C IEC/EN 60898-1 TRF originator: SGS Fimko Report No.: Page 42 of 65 17013446 001 Maintain Switch Tianshui For 6000H/6000HXL GSH1-40/29 40A, 690V IEC/EN 60947-3 TUV R50099240 For Tianshui 10000H/10000H XL GSH1-63/29 63A, 690V IEC/EN 60947-3 TUV R50099240 Terminal block HOPPY HP-RT60 60A, 600VAC Battery For 6000H/10000H Alternative Panasonic Corp UP-RW1236 12V, 36W IEC/EN 60947-1 TUV R50081852 IEC/EN 60947-71 UL 1989 UL MH13723 YUASA NPW36-12 12V, 36W UL 1989 UL MH28947 12V, 7.2AH 12V, 36W UL 1989 UL 1989 UL MH14533 UL MH29104 400VDC, 2200µF -- Test in appliance 400VDC, 2200µF -- Test in appliance Maintain Switch Alternative Alternative CSB GP1272 TOPLITE NPW36-12 (GUANGZHOU) TECHNOLOGY BATTERY CO LTD BUS Capacitors RIFA ALS32A1017L3 (2pcs) for C 6000H/6000HXL Alternative Nichicon PWRM 2G222 Bus Capacitors (2pcs) for 10000H/ 10000HXL Alternative Rubycon 450LSQ5600MR 450VDC, Y77*131 5600µF -- Test in appliance RIFA -- Alternative Nichicon ALS32A1024N5 450VDC, C 5600µF HCGF6A2W562 450VDC, 5600µF Test in appliance Test in appliance -- Battery connector for Eaton E Series DX 6000HXL Battery connector Phoenixtec Power Co., Ltd. PPC 25R-A 25A, 250VDC IEC/EN 619842001 Test in TUV-RH report 11007379 001 IEC/EN 619842001 Test in TUV-RH report 11006865 001/002 Battery connector for Eaton E Series DX 10000HXL Battery connector Phoenixtec PPC 25R-5A Power Co., Ltd. TRF No.: IEC62040_1_1A 30A, 250VDC TRF originator: SGS Fimko Report No.: Page 43 of 65 17013446 001 I/P EMI board for Eaton E Series DX 6000H/6000HXL/10000H/10000HXL TENTA Electronics Industrial Co. Ltd. MEX 2.2uF, 275V IEC/EN 60384UL E186475 14 VDE 119119 UL 414&UL1283 NANJING YUYUE ELECTRONIC S CO., LTD CT7 0.01uF, 250VAC IEC/EN 6038414 VDE 40008013 (Alternative) MURATA KH 0.01uF, 250VAC IEC/EN 6038414 VDE 40002796 (Alternative) Dongguan South Hongming Ceramic CO.,LTD F 0.01uF, 250VAC IEC/EN 6038414 VDE 118357 X-capacitor (C01,C04) Y-capacitor (C02,C03) MOV(MOV1,MO V2,MOV3,MOV4, JOYIN MOV5,MOV6) Thermal Fuse F01-F03 UCHIHASHI ESTEC CO LTD JVR20N511K 550Vac, 85℃ 122 2A, 250Vac, 115℃ UL1449 IEC/EN 61051-1 IEC/EN 61051-2 IEC/EN 610512-2 IEC/EN 60691 UL 60691 UL E154922 VDE 005937 VDE 40003729 UL E50082 O/P EMI for Eaton E Series DX 6000H/ 6000HXL/10000H/10000HXL X-capacitor (C01,C02) TENTA Electronics Industrial Co. Ltd. MEX 2.2uF, 275V IEC/EN 6038414 UL E186475 UL1414&UL128 VDE 119119 3 Y-capacitor (C03,C04) 070-11203-00 NANJING YUYUE ELECTRONIC S CO., LTD CT7 4.7nF, 250VAC IEC/EN 6038414 VDE 40008013 (Alternative) MURATA KH 4.7nF, 250VAC IEC/EN 6038414 VDE 40002796 (Alternative) Guangdong South Hongming Electronic F 4.7nF,250VAC IEC/EN 6038414 VDE 118357 Relay(RY02) 30A,250Vac SONG CHUAN 841-P-1A-B-C-H Coil:12Vdc Gap:1.5mm Relay(RY01) 30A,250Vac Only for 10000H/ SONG CHUAN 841-P-1A-B-C-H Coil:12Vdc 10000HXL Gap:1.5mm TRF No.: IEC62040_1_1A UL 508 IEC/EN 61810-1 IEC/EN 6025523 IEC/EN 61810-5 UL 508 IEC/EN 61810-1 IEC/EN 6025523 IEC/EN 61810-5 UL E88991 TUV R9653713 UL E88991 TUV R9653713 TRF originator: SGS Fimko Report No.: Page 44 of 65 17013446 001 Normal charger Board for Eaton E Series DX 6000H/10000H Transformer (TX901) CLICK 080-42115 130°C -- Test in appliance Transformer (TX902) CLICK/Song Yuan 080-30517 130°C -- Test in appliance PS2561L-1 Internal cr>4.0mm, external cr>7.0mm, dti>0.4mm IEC/EN 607475-2, VDE 40008862 IEC/EN 60950-1 215 series F10A, 250VAC UL 248 UL E10480 IEC/EN 60127-2 VDE 40013521 -- Min.6A, 900V -- Test in appliance Test in appliance Photocoupler (U907,U908, U909) NEC Fuse(F901,F902, Suzhou F903,F904,F905, Littelfuse OVS F906) Ltd. Mosfet (Q907,Q908) -- Quick Charger Board for Eaton E Series DX 6000HXL/10000HXL E- capacitor (C107, C310,C311) IGBT (Q105, Q301) SCR (Q04) Fuse(F1) Transformer (TX1) Transformer (TX2) Inductor (L101,L103, L301,L302) -- -- 220uF,450V, 105°C -- -- -- Min.28A, 900V -- -- -- Min. 35A, 1200V -- Littelfuse, Inc. KLKD8 F8A, 600Vdc UL 248 CLICK 080-30597 130°C -- CLICK 080-42003 130°C -- Shangyong/Ju 082-11037; Qun/Mao Hong 082-11143 130°C -- Photocoupler (U101,U106 U302,U501) NEC PS2561L-1 Photocoupler U103 TOSHIBA TLP250 TRF No.: IEC62040_1_1A Internal cr>4.0mm, external cr>7.0mm, dti>0.4mm Internal cr>4.0mm, external cr>7.0mm, dti>0.4mm Test in appliance Test in appliance UL E10480 Test in appliance Test in appliance Test in appliance IEC/EN 607475-2, VDE 40008862 IEC/EN 60950-1 IEC/EN 607475-2, VDE 40011913 IEC/EN 60950-1 TRF originator: SGS Fimko Report No.: Page 45 of 65 Photocoupler U107 Current Transformer (CT101,CT102) 17013446 001 NEC PS2561L-1 Internal cr>4.0mm, external cr>7.0mm, dti>0.4mm CLICK/SHENY UAN 080-20514 130°C -- Test in appliance VDE 094710 UL E183539 IEC/EN 607475-2, VDE 40008862 IEC/EN 60950-1 PSDR board for Eaton E Series DX 6000H/ 6000HXL X-capacitor (C307,C308) AID MEX 1.0uF, 275Vac IEC/EN 6038414 UL1414 UL1283 HCT Transformer (HCT1) Bes Teks Technology CTC0500 105°C -- Test in appliance Transformer (TX1) CLICK 080-56702 130°C -- Test in appliance 082-11114 200°C -- 082-11209 200°C -- CLICK/Song Yuan 080-20448 130°C -- Test in appliance CLICK/Song Yuan 080-20510 130°C -- Test in appliance Fuse (F302) Littelfuse, Inc. BLN F30A, 250Vac UL248 UL E10480 Fuse (F303) Littelfuse, Inc. KLKD F30A, 600Vdc UL248 UL E10480 PS2561L-1 Internal cr>4.0mm, external cr>7.0mm, dti>0.4mm IEC/EN 607475-2, VDE 40008862 IEC/EN 60950-1 Inductor (L201,L202) Inductor (L301,L302) Current Transformer (CT201) Current Transformer (CT301,CT302,C T303,CT304) Photocoupler (U108, U110) Relay (RY2) Shangyong/Ma o Hong Shangyong/Ma o Hong NEC SONG CHUAN TRF No.: IEC62040_1_1A 737-1Z-C-T Coil:12Vdc 30A, 300Vac Test in appliance Test in appliance UL 508 IEC/EN 61810-1 UL E88991; IEC/EN 60255- TUV R50044822 23 IEC/EN 61810-5 TRF originator: SGS Fimko Report No.: Page 46 of 65 17013446 001 PSDR board for Eaton E Series DX 10000H/10000HXL -- -- 350V, 100uF, 105°C -- Test in appliance SCR (Q207,Q208,Q301, -Q302,Q305) -- Min. 35A, 1200V -- Test in appliance -- -- Min. 40A, 1200V -- Test in appliance IGBT (Q306,Q307,Q310, -Q311) -- Min. 60A, 1000V -- Test in appliance Mosfet(Q104) -- Min. 3A, 900V -- Test in appliance VDE 094710 UL E183539 E-Capacitor (C100) IGBT (Q201-Q204) -- AID MEX 1.0uF, 275Vac IEC/EN 6038414 UL1414 UL1283 HCT Transformer (HCT1) LEM HY 50-P 105°C -- Test in appliance Transformer (TX1) CLICK 080-56702 130°C -- Test in appliance Inductor (L201,L202) Ju Qun/ Shangyong/ Mao Hong 082-11142 200°C -- Test in appliance Inductor (L301,L302) Shangyong/Mao 082-11208 Hong 200°C -- Test in appliance Current Transformer (CT201) CLICK/Song Yuan 080-20448 130°C -- Test in appliance CLICK/Song Yuan 080-20510 130°C -- Test in appliance Littelfuse, Inc. BLN F30A, 250Vac UL248 UL E10480 Littelfuse, Inc. KLKD F30A, 600Vdc UL248 UL E10480 X-capacitor (C307,C308) Current Transformer (CT301,CT302,CT 303,CT304) Fuse (F301, F302) Fuse (F303, F304) Photocoupler (U108,U110) Relay (RY1) NEC PS2561L-1 Song Chuan 735H-2C-F-C TRF No.: IEC62040_1_1A Internal cr>4.0mm, external cr>7.0mm, dti>0.4mm Coil:12Vdc, 30A,250VAC IEC/EN 60747-52, VDE 40008862 IEC/EN 60950-1 UL 508 UL E88991 TRF originator: SGS Fimko Report No.: Page 47 of 65 Relay (RY3, RY4) Song Chuan 832A-1C-F-C Coil: 12Vdc Contact:30A, 250Vac 17013446 001 UL 508 IEC/EN 61810-1 UL E88991 IEC/EN 60255VDE 006615 23 IEC/EN 61810-5 CNTL board for Eaton E Series DX 6000H/Eaton E Series DX 6000HXL Eaton E Series DX 10000H/Eaton E Series DX 10000HXL Transformer (TX200) CLICK Photocoupler (U203,U205,U206, NEC U106) Test in appliance 080-42109 130°C -- PS2561-1 Internal cr>4.0mm, external cr>7.0mm, dti>0.4mm IEC/EN 607475-2 IEC/EN 60950-1 VDE 40008862 Note(s): 1. An asterisk indicates a mark that assures the agreed level of surveillance. 2. Transformer sources are identical in design (which includes used materials). Only differences are manufacturer and type designation. 3. Thermal class of insulation system of all relay sources is classified as Class B according to IEC 60085 TRF No.: IEC62040_1_1A TRF originator: SGS Fimko Report No.: Page 48 of 65 4.4 fuse # 17013446 001 TABLE: electrical data (in normal conditions) Irated (A) U (V) P P (W) I (A) Ifuse (A) condition/status For model EATON E Series DX 6000H Circuit breaker 30 220V/50Hz 4.30 19.57 19.57 Normal operation with and with battery charging. 30 240V/50Hz 4.25 19.07 19.07 Same as above 30 220V/60Hz 4.34 19.52 19.52 Same as above 30 240V/60Hz 4.22 19.05 19.05 Same as above For model EATON E Series DX 6000HXL 30 220V/50Hz 4.54 22.59 22.59 Normal operation with and with battery charging. (charger current 4.2A) 30 240V/50Hz 4.56 20.08 20.08 Same as above 30 220V/60Hz 4.56 22.62 22.62 Same as above 30 240V/60Hz 4.62 20.85 20.85 Same as above Circuit breaker For model EATON E Series DX 10000H Circuit breaker 50 220V/50Hz 7.02 32.08 32.08 Normal operation with and with battery charging. 50 240V/50Hz 6.97 29.25 29.25 Same as above 50 220V/60Hz 7.12 32.12 32.12 Same as above 50 240V/60Hz 6.98 29.35 29.35 Same as above For model EATON E Series DX 10000HXL 50 220V/50Hz 7.42 34.53 34.53 Normal operation with and with battery charging. (charger current 4.2A) 50 240V/50Hz 7.36 31.75 31.75 Same as above 50 220V/60Hz 7.43 34.62 34.62 Same as above 50 240V/60Hz 7.42 31.85 12.75 Same as above Circuit breaker Note(s): TRF No.: IEC62040_1_1A TRF originator: SGS Fimko Report No.: Page 49 of 65 5.1.2 17013446 001 TABLE: distance through insulation measurements distance through insulation di at/of: P Up (V) test voltage (V) required di (mm) di (mm) Note(s): See component list in table 4.3. 5.1.3 TABLE: discharge of capacitors in the primary circuit Condition τ calculated τ measured (s) (ms) t u→ 0V (s) P Comments Line mode (L-N) -- 0.78 -- -- 0.81 -- Bypass mode (L-N) Note: Input voltage 254V/60Hz Overall capacity: C01+C04=4.4uF on input EMI board, C37+C38=2.0.0uF on PSDR board, C01+C02=4.4uF on output EMI board Discharge resistor: By regulating network 5.2 2.2.2/RD TABLE: insulation / hazardous voltage measurement Transformer Location P max. Voltage Voltage Limitation Note(s): No voltage on secondary side (CNTL board) exceeding SELV limits during normal/abnormal operation. No test necessary. 5.2 2.2.3/RD TABLE: insulation / SEL voltage measurement Location Voltage measured (V) -- -- P Comments -- Note(s): No voltage on secondary side (CNTL board) exceeding SELV limits during normal/abnormal operation. No test necessary. TRF No.: IEC62040_1_1A TRF originator: SGS Fimko Report No.: Page 50 of 65 5.3 2.4/RD 17013446 001 TABLE: limited current circuits Location Voltage (V) N/A Current (mA) Freq. (Hz) Limit (mA) Comments Note(s): TABLE: provisions for protective earthing 5.4 2.6.3.3/RD Location P Resistance measured (mΩ) Comments I/P earth O/P earth 16 I/P earth metal enclosure 16 I/P earth earth on PCB(PSDR board 16 I/P earth earth on PCB(Charger board) 16 Test current of 128A for 360s.* Note(s): *Per client’s request, voltage drop not more than 2.5V measured. 2.5V/128A=19.5mΩ 5.8 2.10.2/RD TABLE: working voltage measurement Location RMS voltage (V) P Peak voltage (V) Comments Note(s): Mains voltage considered 5.8 and 9 P TABLE: clearance and creepage distance measurements clearance cl and creepage distance dcr at/of: Up (V) U r.m.s. (V) required cl (mm) cl (mm) required dcr (mm) dcr (mm) Whole unit Internal live part of battery connector to accessible part (for model 6000HXL, 10000HXL) 420 250 4.0 5.6 5.0 5.6 BUS Capacitor to metal enclosure 420 250 2.0 * 2.5 * Battery to enclosure 420 250 4.0 6.0 5.0 6.0 4.0 See below 5.0 See below CNTL board Primary to secondary on the copper side TRF No.: IEC62040_1_1A 420 250 TRF originator: SGS Fimko Report No.: Page 51 of 65 17013446 001 -under transformer TX200 6.9 6.9 -under optocoupler U203 6.9 6.9 Quick charger board (for model 6000HXL, 10000HXL) Primary trace to earthed trace/screw 420 250 2.0 See below 2.5 See below -near U205 4.0 4.0 -under C311 6.3 6.3 Quick charger board (for model 6000H, 10000H) Primary trace to earthed trace/screw 420 250 2.0 See below 2.5 See below -near F906 5.0 5.0 -near P907 6.3 6.3 On input EMI board Primary trace to earthed trace 420 250 2.0 See below 2.5 See below -under C02 2.8 2.8 -under capacitor C05 2.8 2.8 Primary trace to earthed screw 420 250 2.0 -near capacitor R01 See below 2.5 See below 3.6 3.6 On PSDR board Primary trace to earthed screw** 420 250 2.0 See below 2.5 See below -near capacitor C127 2.9 3.2 -near CN205 3.0 3.0 -near CN103 4.1 4.1 -near CN302 2.7 2.7 -near R347 4.8 4.8 Primary trace to metal enclosure 420 250 2.0 2.7 2.5 8.0 Note(s): The Cl.& Cr. Measured considering 10N force performed on component in each item above. * Since each source of bus capacitor to metal enclosure has pass 1500Vac hi-pot test, the plastic cover of the case can be consider as basic insulation. ** since the distance between copper side of PSDR board and earthed metal enclosure is larger than 2.5mm, distance measured between the primary components to earthed trace/screw for reference. TRF No.: IEC62040_1_1A TRF originator: SGS Fimko Report No.: Page 52 of 65 5.8, 6, 8.2 and 9 17013446 001 TABLE: electric strength tests, impulse tests and voltage surge tests test voltage applied between: P test voltage (V) a.c. / d.c. breakdown Yes /?o Primary to Secondary interface (RS-232) 3000Vac No L/N to earthed metal enclosure 1500Vac No Output L/N to earthed metal enclosure 1500Vac No Primary to secondary of transformer TX200 used on the CNTL 3000Vac board No Primary to core of transformer TX200 used on the CNTL board 1500Vac No Secondary to core of transformer TX200 used on the CNTL board 1500Vac No Any combination of 2 layers insulation tape used on the transformer TX200 used on the CNTL board 3000Vac No Enclosure of bus capacitor(each source of the capacitor) 1500Vac No Note(s): 7.4.1 Table: enclosure openings 4.6.1/RD and 4.6.2/RD Location Size (mm) P Comments Top None No openings Bottom None No openings Side None No openings Front Ф3.0 Numerous for ventilation Back Ф116.0 1 round opening for ventilation of DC fan and covered by fan guard for Eaton E Series DX 6000H/6000HXL(2pcs for Eaton E Series DX 10000H/10000HXL) Note(s): 7.5 TABLE: resistance to fire part manufacturer of material P type of material thickness (mm) flammability class Note(s): see table 4.3 for details TRF No.: IEC62040_1_1A TRF originator: SGS Fimko Report No.: Page 53 of 65 7.5 and 8.3 No. 17013446 001 TABLE: fault condition tests P ambient temperature (°C) ...................................... : 25 model/type of power supply ................................... : -- manufacturer of power supply ............................... : -- rated markings of power supply ............................. : -- Component no. Fault Test voltage (V) Test time Fuse no. Fuse current (A) Result Normal charger board on model EATON E Series DX 10000H 1 U908 Pin 1-2 s-c 240Vac 30min F901, F902, F903 -- UPS operates as normal. 2 U908 Pin 3-4 s-c 240Vac 30min F901, F902, F903 -- UPS operates as normal. 3 Q907 D-S s-c 240Vac 1min F901, F902, F903 -- 4 R930 s-c 240Vac 3S F901, F902, F903 -- UPS output remains normal. Charger Fuse F901, F902, F903 opened. Charger output shut down. UPS operates as normal. 5 Two polarities of battery (after fuse) s-c Battery mode 3S F303 -- The fuse F303 opened, UPS stopped working immediately. After recovery, UPS works normally. Quick charger board for model EATON E Series DX 10000HXL 6 Charger Rectifier s-c diode D303 240Vac 5s F1 -- 5S later, EUT changes to bypass mode.R322 and Q301 damaged. 7 Q301 (C-E) s-c 240Vac 1s F1 -- The fuse F1 opened,CHGR board has no output, but the EUT output is normal. 8 Q105 (C-E) s-c 240Vac 10min F1 -- EUT output is normal,no hazard. 9 R320 s-c 240Vac 10min F1 -- EUT output is normal,no hazard. 10 Two polarities of battery (after fuse) s-c Battery mode 1s F303, F304 -- The fuse F303 and F304 opened, UPS stop working immediately. After recovery, UPS works normally. TRF No.: IEC62040_1_1A TRF originator: SGS Fimko Report No.: Page 54 of 65 17013446 001 PSDR board (for similar design on PSDR board, test with model EATON E Series DX 10000HXL to represent other models) 11 Transformer TX1 s-c Pin 11-12 12 Transformer TX1 s-c Pin 10-9 Battery mode 1.5h F301, F302 -- UPS changes to bypass mode, TX1 is 90.5°C,ambient is 28.1°C.After recovery, UPS works normally. Battery mode 1.0h F301, F302 -- UPS changes to bypass mode, TX1 is 68.1°C, ambient is 28.3°C. After recovery, UPS works normally. EUT changes to bypass mode. F301, F302 opened, Q306 damaged, no hazard. After 1s, UPS changes to bypass mode. F301, F302 opened, Q203,Q204,Q201 and Q202 damaged, no hazard. 13 Transistor Q306 (c-e) s-c 240Vac 1s F301, F302 -- 14 Transistor Q201 (c-e) s-c 240Vac 1s F301, F302 -- 15 Line Detecting Resistor R01 s-c Battery mode 3h F301, F302 -- UPS works normally,no hazard. 16 Battery Detecting s-c Resistor R380 240Vac 2h F301, F302 -- UPS changes to bypass mode, the battery LED warns. After recovery, UPS works normally. 17 Bus voltage Detecting Resistor R01 o-c 240Vac 3h F301, F302 -- UPS works normally,no hazard. 18 BUS capacitor s-c 240Vac 3s F301, F302 -- UPS changes to bypass mode, F301 and F302 opened. CNTL board 19 Transformer TX200 (Pin9Pin10) s-c 240Vac 3s Circuit -breaker UPS changes to bypass mode and warns. After recovery, UPS did’t work normally, TX200 damaged. 20 Optocoupler U203 (pin1-2) s-c 240Vac 10min Circuit -breaker UPS work normally,no hazards. 21 Optocoupler U203 (pin3-4) s-c 240Vac 10min Circuit -breaker UPS works normally,no hazards. -- UPS shut down after 3 seconds, recoverable after fault removed, no hazards Whole unit (model EATON E Series DX 10000H) 5min 22 Output s-c 240Vac TRF No.: IEC62040_1_1A -- TRF originator: SGS Fimko Report No.: Page 55 of 65 17013446 001 23 output o-l 240Vac 1h -- -- 24 Output s-c Battery mode 5min Battery Fuse -- 25 output o-l Battery mode 1h Battery Fuse -- 26 Fan locked 240Vac 1h -- -- 27 Ventilation opening Blocke d 240Vac 1h Battery Fuse -- UPS operates as normal. UPS transfer to bypass mode after 31mins, 28 Fan locked Battery mode 1h -- -- UPS operates as normal 29 Ventilation opening Blocke d Battery mode 1h Battery Fuse -- UPS transfer to bypass mode after 27mins. Whole unit (model EATON E Series DX 10000HXL) 1s 30 Output s-c 240Vac 31 output o-l 240Vac 30mins 32 Output s-c Battery mode 1s TRF No.: IEC62040_1_1A Input -breaker Input -breaker F303,F 304 -- 125% load, after 10min15min UPS transfer to bypass mode. 150% load, after 30sec60sec UPS transfer to bypass mode. UPS shut down after 3 seconds, recoverable after fault removed, no hazards 125% load, after 10min15min UPS transfer to bypass mode. 150% load, after 30sec60sec UPS transfer to bypass mode. EUT fault and no output immediately.No hazard. (measured on PSDR board, temperature of TX1 is 38.9°C. TX1 of charger board is 40.7°C.) EUT changes to bypass mode within 1s at condition of overload 130%. No hazard. (measured on PSDR board, temperature of TX1 is 35.5°C, TX1 of charger board is 41.6°C.) EUT fault and no output immediately. No hazard. (measured on PSDR board, temperature of TX1 is 40.1 °C. TX1 of charger board is 48.7°C.) TRF originator: SGS Fimko Report No.: Page 56 of 65 17013446 001 33 output o-l 240Vac 60mins -- -- 34 Fan locked 240Vac 20mins F303,F 304 -- 35 Ventilation opening Blocked 240Vac 36 Fan locked Battery mode 20mins F303,F 304 -- 37 Ventilation opening Blocked Battery mode 30mins F303,F 304 -- 1hr Input -breaker 110% load, after 15min UPS transfer to bypass mode. 120% load, after 10min UPS transfer to bypass mode. Max. Temperature of PSDR: TX1=35.1°C U108=41.6°C Charger: TX1=79.2°C TX2=71.3°C EUT fault and changes to bypass. No hazard. (measured on PSDR board, temperature of TX1 is 139.8°C,TX1 of charger board is 65.7°C.) EUT fault and changes to bypass. No hazard. (measured on PSDR board, temperature of TX1 is 139.9 °C ,TX1 of charger board is 59.5°C.) EUT fault and changes to bypass. No hazard. (measured on PSDR board, temperature of TX1 is 139.8 °C, TX1 on charger board is 65.7°C.) EUT fault and changes to bypass. No hazard. (measured on PSDR board, temperature of TX1 is 39.9 °C, TX1 on charger board is 68.7°C.) Note(s): 1: s-c means short-circuit. o-l means overload. o-c means open-circuit. 2: For the test which would cause the fuse F1, F301, F302, F303, F304 opened and where the fuse rating is over 10A, all the tests repeated at least 10 times to demonstrate the same result. TRF No.: IEC62040_1_1A TRF originator: SGS Fimko Report No.: Page 57 of 65 7.7 17013446 001 TABLE: maximum temperatures P test voltage (V) ................................ See notes as below t1 (°C) ................................-- t2 (°C) ................................-- Maximum temperature T of part/at: T (°C) allowed Tmax (°C) A B C D E Enclosure (plastic panel) 33.5 33.4 26.4 29.6 30.7 82.5 Enclosure (metal) 37.2 36.2 29.1 32.5 37.0 57.5 Input breaker 40.7 41.3 33.8 36.5 34.3 57.5 Primary lead wire 44.2 43.8 36.3 38.5 36.7 92.5 Output lead wire 67.6 70.5 62.6 64.7 62.7 92.5 DC fan 40.1 45.4 34.6 42.7 38.1 -- Battery wire 34.3 36.2 29.1 33.6 39.4 92.5 X Capacitor C04 on input EMI board 45.9 46.2 39.1 38.4 39.4 87.5 Inductor L01 on input EMI board 61.7 59.2 49.9 49.1 50.1 107.5 Y capacitor C03 on input EMI board 41.6 43.1 36.2 38.4 36.2 112.5 PCB for input EMI board 47.4 47.4 39.8 40.1 39.9 117.5 Transformer CT303 coil on PSDR board 53.0 55.1 45.8 47.3 63.9 107.5 Transformer CT201 coil on PSDR board 57.7 62.3 52.1 55.8 53.0 107.5 Inductor L301 on PSDR board 91.6 84.5 74.4 71.3 102.4 177.5 Inductor L302 on PSDR board 75.2 71.9 61.4 61.0 93.9 177.5 Inductor L201 on PSDR board 95.7 98.5 88.4 91.6 102.2 177.5 Inductor L202 on PSDR board 110.2 113.7 101.4 106.4 107.1 177.5 Relay RY1 on PSDR board 57.0 61.3 51.7 55.5 60.3 72.5 Capacitor C100 on PSDR board 36.9 38.0 30.1 33.7 40.0 92.5 PCB between D201 and Q201 on PSDR board 83.4 86.1 72.8 75.9 79.7 117.5 PCB between Q301 and Q305 on PSDR board 60.4 61.4 52.4 54.6 65.0 117.5 X-capacitor C307 on PSDR board 36.0 36.7 29.2 31.2 35.1 87.5 Charger transformer TX901 core 52.8 94.1 48.2 88.0 48.3 97.5 Charger transformer TX901 coil 47.5 80.4 42.9 74.7 43.3 97.5 For model EATON E Series DX 10000H TRF No.: IEC62040_1_1A TRF originator: SGS Fimko Report No.: Page 58 of 65 17013446 001 PCB under Q907 on Charger board 40.6 61.6 34.8 55.5 35.0 117.5 CNTL transformer TX200 coil on CNTL board 37.6 36.8 29.3 33.6 43.6 87.5 CNTL transformer TX200 core on CNTL board 40.0 38.3 31.1 34.8 43.7 87.5 Optocoupler U203 on CNTL board 40.5 37.3 29.6 33.3 42.7 112.5 PCB near transformer TX200 on CNTL board 40.6 37.6 29.8 33.7 44.5 117.5 X-capacitor C01 on output EMI board 39.0 41.4 36.7 38.0 38.3 87.5 Inductor L01 on output EMI board 60.9 61.8 52.6 58.5 54.3 107.5 PCB near L801 on output EMI board 64.5 66.1 60.5 61.8 60.7 117.5 Relay 01 on output EMI board 56.7 58.3 45.8 54.9 54.8 72.5 Relay 02 on output EMI board 36.5 38.8 31.9 35.9 40.6 72.5 Y-cap C04 on output EMI board 34.3 37.0 29.1 33.8 37.2 112.5 Bus-capacitor 49.3 52.6 44.6 46.5 52.0 72.5 Ambient 30.8 33.3 29.0 29.2 29.4 -- For model EATON E Series DX 10000HXL Enclosure (plastic panel) 27.8 28.2 31.1 30.5 31.9 82.5 Enclosure (metal) 30.2 29.7 31.8 32.5 33.6 57.5 Input breaker 30.7 30.3 31.5 32.6 29.4 57.5 Primary lead wire 45.7 40.4 41.0 40.7 30.0 92.5 Output lead wire 39.2 39.2 40.1 41.6 40.2 92.5 DC fan 39.7 58.8 39.7 44.6 45.8 -- Battery wire 30.5 30.5 31.7 32.9 42.4 92.5 X Capacitor C04 on input EMI board 32.9 31.9 35.0 32.7 31.0 87.5 Inductor L01 on input EMI board 43.1 40.2 39.8 38.8 30.7 107.5 Y capacitor C03 on EMI board 34.0 33.1 34.6 34.2 32.6 112.5 PCB for input EMI board 34.7 33.7 34.6 34.6 30.9 117.5 Transformer CT303 coil on PSDR board 47.9 44.7 45.6 44.9 67.8 107.5 Transformer CT201 coil on PSDR board 38.7 39.0 39.1 41.0 41.5 107.5 Inductor L301 on PSDR board 82.9 74.6 71.5 64.1 102.5 177.5 Inductor L302 on PSDR board 64.6 58.1 59.2 56.4 116.1 177.5 Inductor L201on PSDR board 81.2 80.4 80.9 81.4 98.7 177.5 Inductor L202 on PSDR board 73.3 72.7 73.2 74.1 96.0 177.5 TRF No.: IEC62040_1_1A TRF originator: SGS Fimko Report No.: Page 59 of 65 17013446 001 Relay RY1 on PSDR board 53.9 53.7 54.1 55.1 63.5 72.5 Capacitor C100 on PSDR board 31.3 31.9 33.7 33.8 42.4 92.5 PCB between D201 and Q201 on PSDR board 88.9 84.8 85.8 81.5 94.0 117.5 PCB between Q301 and Q305 on PSDR board 58.2 54.4 55.3 52.7 66.3 117.5 X-capacitor C307 on PSDR board 32.0 31.4 34.8 33.3 36.3 87.5 Changer transformer CT101 coil 37.8 36.3 35.7 37.6 34.8 107.5 Inductor L103 on charger board 47.4 45.8 42.2 45.5 36.1 107.5 Inductor L101 on charger board 46.9 46.9 42.7 46.3 36.7 107.5 X-capacitor C310 on charger board 36.5 35.6 35.7 40.2 35.2 87.5 PCB under Q105 on Charger board 44.0 43.2 40.3 41.9 36.9 117.5 Inductor L301 on Charger board 39.2 37.7 36.1 35.6 32.8 107.5 CNTL transformer TX200 coil on CNTL board 31.9 32.4 32.4 34.7 47.4 97.5 CNTL transformer TX200 core on CNTL board 32.5 33.0 32.9 35.2 47.1 97.5 Optocoupler U203 on CNTL board 29.8 30.5 30.2 32.5 45.1 112.5 PCB near transformer TX200 on CNTL board 30.7 31.2 31.1 33.4 46.7 117.5 X-capacitor C01 on output EMI board 36.1 34.9 35.5 36.8 36.2 87.5 Inductor L01 on output EMI board 54.4 53.9 54.1 54.1 54.1 107.5 PCB near L801 on output EMI board 40.3 40.7 41.4 42.8 43.4 117.5 Relay 01 on output EMI board 50.8 51.5 52.7 54.8 52.8 72.5 Relay 02 on output EMI board 54.3 54.1 55.3 57.0 56.0 72.5 Y-cap C04 on output EMI board 33.3 34.0 34.8 36.7 36.5 112.5 Bus-capacitor 38.1 37.2 37.0 37.3 46.1 72.5 Ambient 27.5 27.8 29.3 28.6 27.9 -- Temperature T of winding: R1 (Ω) R2 (Ω) T (°C) allowed Tmax (°C) insulation class Note(s): Note(s): 1. The temperatures were measured under worst case normal mode defined in 1.2.2.1 and as described in sub-clause 1.6.2 and at voltages as described below A: 198V/60Hz B: 220V/50Hz C: 220V/60Hz TRF No.: IEC62040_1_1A TRF originator: SGS Fimko Report No.: Page 60 of 65 17013446 001 D: 254V/50Hz E: Battery mode Having a specified maximum ambient temperature of +40 °C - Class B → Tmax = 120 °C-10 °C-(40°C-27.5 °C )= 97.5°C - 130°C → Tmax = 130 °C-10 °C-(40°C-27.5 °C) = 107.5°C - 200°C → Tmax = 200 °C-10 °C-(40°C-27.5 °C) = 177.5°C Other components: → Tmax=Tmax-(40-27.5) °C 2. Since model EATON DX 6000H and EATON DX 6000HXL are similar to model EATON DX 10000H and EATON DX 10000H except for some rating components, heating tests performed on model EATON DX 10000H and EATON DX 10000HXL to represent the other two models 7.7 TABLE B: ball pressure test of thermoplastic parts P allowed impression diameter (mm) .....................: ≤ 2mm part test temperature (°C) impression diameter (mm) 125 1.1 Terminal Block Note(s): Bobbin of transformer TX200 on CNTL board is Phenolic, no further tests required. 8.1.1 TABLE: earth leakage current P Limit (mA) 0.02 N → terminal A (mA) 0.03 Metal enclosure 3.0 3.0 3.5 Plastic enclosure 0.01 0.01 3.5 Condition L→ terminal A (mA) RS-232 terminal Comments 0.25 Note(s):Input voltage 254V/60Hz C.2/RD Safety isolation transformer P Construction details: Transformer part name: TX200 on CNTL board Manufacturer: See appended table 4.3 Type: See appended table 4.3 Recurring peak voltage 420Vpeak Required clearance for reinforced insulation (from table 2H and 2J) 4.0 TRF No.: IEC62040_1_1A TRF originator: SGS Fimko Report No.: Page 61 of 65 17013446 001 Effective voltage rms 250Vrms Required creepage distance for reinforced insulation (from table 2L) 2.5 Measured min. creepage distance Location inside (mm) outside (mm) Primary winding/pin to secondary winding/pin 5.0 10 Primary winding/pin to core 2.5 3.3 Secondary winding/pin to core 2.5 3.3 inside (mm) outside (mm) Primary winding/pin to secondary winding/pin 5.0 10 Primary winding/pin to core 2.5 3.3 Secondary winding/pin to core 2.5 3.3 Measured min. clearances Location Construction: Concentrically wound transformer design, core size EE-16. N1, N2 are primary winding which is wound around the internal side of the bobbin. 3 layers of mylar tapes are used to separate primary and secondary windings. N3, N4, N5 are secondary windings on outer side of bobbin. Margin tape with width of 2.5mm is used on both side of bobbin and each winding layer. Tubing is used on every winding exits to the bare pins on bobbin. Pin numbers Prim. 6-7, 8-9-10 Sec. 1-2, 3-4 Bobbin Material Phenolic, PM 9820, SUMITOMO BAKELITE Thickness 0.7mm Electric strength test With 3000 V a.c. after humidity treatment Result TRF No.: IEC62040_1_1A Pass TRF originator: SGS Fimko Report No.: Page 62 of 65 N.4 17013446 001 Ventilation of battery compartments (For model EATON E Series DX 6000H, EATON E Series DX 10000H) P The required dimension for the ventilation openings will be calculated with the following formula: A > K1 * Q with Q = (0.054 m³/Ah) * n * I * C where: K1 : constant factor of 28 h * cm²/m³ Q : airflow in m³/h n : number of battery cells I : constant factor (0,2A/100Ah for valve regulated lead acid batteries) C : nominal capacity of the battery With the specific data for the UPS the following dimension for the ventilation openings is required: n : 120 (6 cells per battery provided) C : 7.2Ah A > 28 h * cm²/m³ * (0.054 m³/Ah) * n * 0.2 A/100 Ah * C A > 2.6cm² Verdict The size of ventilation openings and holes in the UPS side enclosure exceed the required dimension for ventilation (For model EATON E Series DX 6000H, EATON E Series DX 10000H A=25.3 cm²) TRF No.: IEC62040_1_1A TRF originator: SGS Fimko Page 63 of 65 Report No.: 17013446 001 National Differences Clause Requirement − Test Result – Remark Verdict APPENDIX Group Differences, Special National Conditions and National Deviations of CENELEC according to CB Bulletin No. 112A, December 2006 (EN 62040-1-1, SN EN 62040-1-1, DIN EN 62040-1-1, NEK-EN 62040-1-1, SSEN 62040-1-1) P (IEC Publication 62040-1-1:2002) SPECIAL NATIONAL CONDITIONS AND NATIONAL DEVIATIONS S = Special National Condition, A = National Deviation (A-deviation), C = CENELEC Common Modification, F = other information NO=Norway, SE=Sweden P=Pass, F=Fail, N/A=Not applicable. Placed in the column to the right. 4.5.3 S (NO): When safety relies upon connection to Evaluated when applying for the safety earth (see 5.9), a pluggable equipment national approval type A UPS shall have a marking on the equipment, stating that the UPS must be connected to an earthed mains socket-outlet. The marking text shall be as follows: N/A “Apparatet skal tilkoples jordet stikkontakt” 4.5.3 S (SE): When safety relies upon connection to Evaluated when applying for the safety earth (see 5.9), a pluggable equipment national approval type A UPS shall have a marking on the equipment, stating that the UPS must be connected to an earthed mains socket-outlet. The marking text shall be as follows: N/A “Apparaten skall anslutas till jordat uttag” 9 S (NO, SE): Requirements of 6.1.2.1 and 6.1.2.2 in the Reference Document (RD) IEC 609501:2001 apply with the following additions: No TNV circuits N/A Add the following text between the first and second paragraph of subclause 6.1.2.1/RD: If this insulation is solid, including insulation forming part of a component, it shall at least consist of either - two layers of thin sheet material, each of which shall pass the electric strength test below, or - one layer having a distance through insulation of at least 0,4 mm, which shall pass the electric strength test below. If this insulation forms part of a semiconductor component e.g. an optocoupler, there is no distance through insulation requirement for the insulation consisting of an insulating compound completely filling the casing, so that clearances and creepage distances do not exist, if the component passes the electric strength test in Group Differences, Special National Conditions and National Deviations of CENELEC according to CB Bulletin No. 112A, December 2006 Page 64 of 65 Report No.: 17013446 001 National Differences Clause Requirement − Test Result – Remark Verdict accordance with the compliance clause below and in addition: - passes the tests and inspection criteria of 2.10.8 with an electric strength test of 1,5 kV multiplied by 1,6 (the electric strength test of 2.10.7 shall be performed using 1,5 kV); and - is subjected to routine testing for electric strength during manufacturing, using a test voltage of 1,5 kV. It is permitted to bridge this insulation with a capacitor complying with EN 132400:1994, subclass Y2. A capacitor classified Y3 according to IEC 6038414:1993, may bridge this insulation under the following conditions: - the additional testing shall be performed on all the test specimens as described in IEC 6038414, - the impulse test of 2,5 kV is to be performed before the endurance test in IEC 60384-14, in the sequence of tests as described in IEC 60384-14. Add the following text to subclause 6.1.2.2/RD: The exclusions are applicable for permanently connected equipment and pluggable equipment type B and equipment intended to be used in restricted access location where equipotential bonding has been applied, e.g. in a telecommunication centre, and which has provision for permanently connected protective earthing conductor and is provided with instructions for the installation of that conductor by a service person. Annex ZA C: This European standard incorporates by dated or undated reference, provisions from other publications. These normative references are cited at the appropriate places in the text and the publications are listed hereafter. For dated references, subsequent amendments to or revisions of any of these publications apply to this European Standard only when incorporated in it by amendment or revision. For undated references the latest edition of the publication referred to applies (including amendments). NOTE: When an international publication has been modified by common modifications, Group Differences, Special National Conditions and National Deviations of CENELEC according to CB Bulletin No. 112A, December 2006 P Page 65 of 65 Report No.: 17013446 001 National Differences Clause Requirement − Test Result – Remark indicated by (mod), the relevant EN/HD applies. EN 60417 Series IEC 60417 Series EN 60529:1991 + corr. May 1993 IEC 60529:1989 IEC/TR 60755:1983 + A1:1988 + A2:1992 EN 60950-1:2001 IEC 60950-1 (mod):2001 EN 61000-2-2:2002 IEC 61000-2-2:2002 IEC 61008-1:1996 1) IEC 61009-1:1996 2) EN 62040-1-2:2003 IEC 62040-1-2:2002 + corr. December 2002 IEC 62040-2:1999 EN 62040-3:2001 EN 62040-3 (mod):1999 Verdict 1) The European standard EN 61008-1:1994 (IEC 61008-1:1990 + A1:1992, mod) + corrigendum December 1997 + A2:1995 (IEC/A2:1995) + A11:1995 + A12:1996 + corrigendum April 1998 + A13:1998 + A14:1998 applies. 2) The European standard EN 61009-1:1994 (IEC 61009-1:1991, mod.) + corrigendum December 1997 + A1:1995 (IEC/A1:1995) + A11:1995 + A2:1996 + A13:1998 + corrigendum April 1998 + A14:1998 + A15:1998 + A17:1998 applies. Group Differences, Special National Conditions and National Deviations of CENELEC according to CB Bulletin No. 112A, December 2006 Page 1 of 13 Type Designation: Report Number: EATON E Series DX 6000H, EATON E Series DX 6000HXL, EATON E Series DX 10000H, EATON E Series DX 10000HXL 17013446 001 Figure 1 front view (for all models) Figure 2 back view (for model EATON E Series DX 6000H) Page 2 of 13 Type Designation: Report Number: EATON E Series DX 6000H, EATON E Series DX 6000HXL, EATON E Series DX 10000H, EATON E Series DX 10000HXL 17013446 001 Figure 3 back view (for model EATON E Series DX 6000HXL) Figure 4 back view (for model EATON E Series DX 10000H) Page 3 of 13 Type Designation: Report Number: EATON E Series DX 6000H, EATON E Series DX 6000HXL, EATON E Series DX 10000H, EATON E Series DX 10000HXL 17013446 001 Figure 5 back view (for model EATON E Series DX 10000HXL) Figure 6 side view of PSDR board for model EATON E Series DX 6000H and EATON E Series DX 10000H Page 4 of 13 Type Designation: Report Number: EATON E Series DX 6000H, EATON E Series DX 6000HXL, EATON E Series DX 10000H, EATON E Series DX 10000HXL 17013446 001 Figure 7 side view of model EATON E Series DX 6000H and EATON E Series DX 10000H Figure 8 view of internal battery for model EATON E Series DX 6000H and EATON E Series DX 10000H Page 5 of 13 Type Designation: Report Number: EATON E Series DX 6000H, EATON E Series DX 6000HXL, EATON E Series DX 10000H, EATON E Series DX 10000HXL 17013446 001 Figure 9 side view of model EATON E Series DX 6000H and EATON E Series DX 10000H Figure 10: side view of PSDR board for model EATON E Series DX 6000HXL and EATON E Series DX 10000HXL Page 6 of 13 Type Designation: Report Number: EATON E Series DX 6000H, EATON E Series DX 6000HXL, EATON E Series DX 10000H, EATON E Series DX 10000HXL 17013446 001 Figure 11 view of the quick charger board for model EATON E Series DX 6000HXL and EATON E Series DX 10000HXL Figure 12 component side of quick charger board for model EATON E Series DX 6000HXL and EATON E Series DX 10000HXL Page 7 of 13 Type Designation: Report Number: EATON E Series DX 6000H, EATON E Series DX 6000HXL, EATON E Series DX 10000H, EATON E Series DX 10000HXL 17013446 001 Figure 13 copper side of quick charger board for model EATON E Series DX 6000HXL and EATON E Series DX 10000HXL Figure 14: component side of CNTL board for all models Page 8 of 13 Type Designation: Report Number: EATON E Series DX 6000H, EATON E Series DX 6000HXL, EATON E Series DX 10000H, EATON E Series DX 10000HXL 17013446 001 Figure 15: copper side of CNTL board for all models Figure 16: component side of input EMI board for all models Page 9 of 13 Type Designation: Report Number: EATON E Series DX 6000H, EATON E Series DX 6000HXL, EATON E Series DX 10000H, EATON E Series DX 10000HXL 17013446 001 Figure 17: copper side of input EMI board for all models Figure 18: component side of output EMI board Page 10 of 13 Type Designation: Report Number: EATON E Series DX 6000H, EATON E Series DX 6000HXL, EATON E Series DX 10000H, EATON E Series DX 10000HXL 17013446 001 Figure 19: copper side of output EMI board Figure 20: component side of PSDR board for all model Page 11 of 13 Type Designation: Report Number: EATON E Series DX 6000H, EATON E Series DX 6000HXL, EATON E Series DX 10000H, EATON E Series DX 10000HXL 17013446 001 Figure 21: copper side of PSDR board for all model Figure 22: component side of normal charger board for model EATON E Series DX 6000H and EATON E Series DX 10000H Page 12 of 13 Type Designation: Report Number: EATON E Series DX 6000H, EATON E Series DX 6000HXL, EATON E Series DX 10000H, EATON E Series DX 10000HXL 17013446 001 Figure 23: copper side of normal charger board for model EATON E Series DX 6000H and EATON E Series X 10000H Figure 24: component side of parallel board for all models Page 13 of 13 Type Designation: Report Number: EATON E Series DX 6000H, EATON E Series DX 6000HXL, EATON E Series DX 10000H, EATON E Series DX 10000HXL 17013446 001 Figure 25: copper side of parallel board for all models Figure 26: Terminal block and separate PE terminal screw.